Professional Documents
Culture Documents
PREFACE
ACKNOWLEDGEMENTS
1 TRANSFORMER OPERATION
Brief Early History of the Transformer
Principle of Operation
The e.m.f. Equation
The Transformer on No Load
Primary phasor diagram
Secondary phasor diagram
Combined phasor diagram
Voltage and turns relationship
The Transformer on Load
On-load phasor diagram
On-load voltage diagram
Referred Values of Resistance, Reactance and Impedance
Transformer Efficiency
Efficiency
4 D.C. MACHINES
Testing of D.C. Machines
Output
Efficiency
Losses
Testing methods
D.C. Generators in Parallel
Parallel operation
Load sharing
Commutation and Armature Reaction
Commutation
Armature reaction
Special D.C. Machines
The rotary transformer
The rotary converter
The rotating amplifier
5 D.C. RECTIFICATION
Electromagnetic Induction
Inductance
The Direct Current LR Circuit
Growth of current
Decay of current
The field switch and discharge resistor
The Direct Current CR Circuit
Growth of current
Discharge conditions
The Alternating Currents LR and CR Circuit
Current asymmetry
Rectification
Terms
Rectifier arrangements
Battery charging by rectifier
eCopyright
PREFACE
This book is companion to Volume 6 (Basic Electrotechnology for
Engineers) and covers aspects of theory lying outside the scope of
Volume 6. The syllabus covers fully the Department of Trade and
Maritime and Coastguard Agency syllabuses’ requirements in
Electrotechnology for Marine Engineers, and beyond, and provides
practical applications and illustrations to Coastguard, Merchant and
Naval students, whether studying for engineering qualifications and
certificates, or not.
You can never cross the ocean until you have the courage to
lose sight of the shore.
Christopher Columbus
ACKNOWLEDGEMENTS
I would like to thank my wife Anne and family for their ongoing
support while completing this Volume, which has taken over 2 years
to complete, sometimes subject to the phenomenon of the ‘moving
goalpost’. I would also like to express my profound gratitude for
those who have mentored and encouraged me in my work over the
past 30 years, especially Professor Roy Sambles FRS, who as my
Ph.D. supervisor and more recently as president-elect of the Institute
of Physics (president from 2015), has profoundly influenced my
interest in practical physics and engineering applications generally.
Having worked with many physics models it is a rare event to find
one that works well, but it is a rarer event indeed to find those we
might ourselves wish to model or imitate in part, demonstrating that it
is possible to be both a Christian and a scientist in the 21st century
without sacrificing academic credibility. Thanks for the example Roy.
Examples:
The need for the transformer arose out of the problems that were
being encountered at this time in terms of transmission of power. D.C.
power was mainly used in the 1880s and it was difficult to achieve
over any great distance because of either practical safety issues
using high voltages on thin wires or low voltages on very thick ones.
However, with A.C. systems you can use a high voltage to transmit
the electrical current down very long wires and then use a device (the
transformer) to drop or step the voltage down to more manageable
voltage levels. In reality, power can be stepped down several times
on power distribution systems. Stanley first demonstrated a full A.C.
power distribution system using both step-up and step-down
transformers in 1886 in Great Barrington, MA, followed by
development of the first three-phase transformer in Germany by
Russian-born engineer Mikhail Dolivo-Dobrovolsky in 1889, two
essential factors of electrical distribution systems used to this day, in
land, sea and air applications.
Principle of Operation
We begin our discussion with the ‘traditional’ view of the transformer,
introducing the ‘phasor’ approach before finishing our discussion with
modern versions of the device once the basic principle of operation is
understood.
Consider next a second coil, isolated from the first but wound on the
same iron core. The first or primary coil of insulated wire, when
carrying an A.C. current, produces the accompanying flux which now
links with the secondary or second coil of insulated wire. Since the
flux varies, not only the flux-linkages associated with the primary, but
also those associated with the secondary vary and again an e.m.f. is
induced through mutual induction. As for the primary, the e.m.f.
magnitude and direction can be deduced from first principles as
shown in Volume 6. The transformer can be considered to be an
arrangement of two or more coils, electrically separated but linked by
the common thread of a magnetic circuit. If an A.C. voltage is applied
to the primary causing an A.C. current to flow, by mutual induction an
A.C. voltage is generated across the secondary. If the secondary
circuit is completed, a current will flow and energy will transfer from
the primary to the secondary.
▲ Figure 1.1
▲ Figure 1.2
▲ Figure 1.3
From Faraday’s law, the average e.m.f. induced value per turn = the
rate of change of flux-linkages = volts.
Again since the induced e.m.f. is equal and opposite to the supply
voltage then:
Em1 = 2π fN1Φm
To avoid saturation of the iron, the Φm value must not exceed 0.03584
Wb or 35.85 mWb.
▲ Figure 1.4
The transformer phasor diagram has been introduced and the test
instruments’ readings are used to explain the diagram. The no-load
current will be the ammeter reading I0 and the wattmeter reading
indicates the power input P0 = V1I0 cosφ0. From such readings it is
deduced that the no-load current I0 is resolved into a power
component I0 cosφ0 (the working component), i.e. responsible for the
unwanted heat, and regarded as a loss.
The primary phasor diagram also shows the other component of the
no-load current I0. This component will be I0 sinφ0, i.e. a reactive or
wattless component, which, being at right angles to the voltage, and
in phase with the flux Φ, can be regarded as producing the latter.
Thus I0 sinφ0 is denoted by Im and termed the magnetising
component. The following can be deduced:
.
▲ Figure 1.5
We also have V1I0 cosφ0 = V1Iw = heat loss due to the iron loss in the
core + a small copper loss in the primary.
The illustrations of figure 1.5 show two phasor diagrams. The first is
for the primary winding, that is for E1 drawn dotted (because it is
usual to omit this). The second diagram of figure 1.5 is for the
secondary winding and the induced e.m.f. E2 drawn at right angles to
the common core flux Φ. Unlike the primary since no supply voltage is
applied, no anti-phase voltage phasor is drawn, i.e. there is no phasor
corresponding to V1. When the secondary circuit is completed, the
induced e.m.f. becomes an active voltage responsible for the current
through the connected load and may be expressed as V2 (the
secondary terminal voltage). Thus on no-load V2 = E2.
▲ Figure 1.6
Since the induced e.m.f.s in the primary and secondary windings are
in accordance with the e.m.f. equation then:
The tapping should be 3000 – 2727 or 273 turns from the end which
is remote from that made common for 440 and 400 V. Figure 1.7
shows the arrangement.
▲ Figure 1.7
The turns required for 240 V will be 1500 + 136 = 1636, for a fully
tapped secondary.
The secondary consists of 1636 turns with tappings at 136 and 272
turns from the end which is remote from that made common for 240,
220 and 200 V.
This secondary flux links with the primary and by Lenz’s law produces
a demagnetising effect which results in the core flux Φ reducing. Flux
reduction through the primary results in a small reduction of the
primary induced e.m.f. E1. The effect of the supply voltage V1 then
produces a larger primary current, most of which counters the
secondary current’s demagnetising effect. The increase in I1 due to I2
flowing, caused by the greater difference between V1 and E1, is made
up of an extra primary-current component I1 which will add to the no-
load current I0 which continues to flow to produce the components Im
and Iw. The new primary current I1 consists of and I0, and a phasor
summation is shown.
▲ Figure 1.8
V1 = 4.44 Φm fN1
Phasor diagram shows ΦL2 drawn in phase with I2 and ΦL1 in phase
with I1. Both ΦL2 and ΦL1 are small in comparison to Φ because,
although they are produced by currents of load magnitudes compared
to the very small value of Im, the magnetic circuits are through air,
while Φ is through iron. Leakage fluxes can be drawn in phase with
the energising currents but in the case of the primary, and I1 are
assumed identical, I0 being neglected, no error is introduced if ΦL2, is
assumed to be caused by I1 and drawn in phase with it.
Example 1.5. If the transformer iron core of example 1.1 is used for
50 kVA operation, estimate the wire area used for primary and
secondary windings. The wire should not work at a current density
above 2.33 A mm2, to ensure a safe working temperature in mm2 (2
decimal places).
▲ Figure 1.10
▲ Figure 1.11
Passage of a load current causes voltage drops I1R1 and I2R2 which,
being due to resistance, are in phase with the current. These voltage
drops, if considered with the primary and secondary terminal
voltages, are like the armature voltage drops in a motor-generator
introduced to understand transformer working. Thus for a generator
or secondary of a transformer, as terminal voltage is less than the
generated voltage by an internal voltage drop, it follows that the latter
must be subtracted from the generated voltage. For the transformer a
construction is involved, the generated or induced e.m.f.
is V2 and the voltage-drop phasor I2R2 drawn in phase with the
current. Note the slight phase displacement of terminal-voltage
phasor V2 from the original no-load position V2.
Similarly for the primary, as for a motor, the supply voltage V1 must
overcome the induced e.m.f. V1 and armature internal resistance or,
in this case, the primary winding. Here and an allowance
is made for phasor construction, I1R1 is drawn in phase with I1.
The on-load diagrams (figures 1.12 and 1.13) take into account both
resistance and reactance voltage drops. Points to note are:
▲ Figure 1.12
▲ Figure 1.13
current and resistance is given by: I2R2 Thus the total resistance
voltage drop of the primary referred to the secondary is:
Z1 = 38 ×1.905 - 72.4 V
Transformer Efficiency
Only a basic treatment is made here regarding losses and efficiency.
Since a transformer is a static device, the only losses which occur
are: (1) iron losses and (2) copper losses.
to the secondary
Efficiency
For maximum efficiency, copper loss equals the iron loss so:
then ‘loading’ for maximum efficiency = 7.43 kW.
Practice Examples
1.1 A single-phase transformer is designed to operate at 2 V per turn
and a turns ratio of 3:1. If the secondary winding is to supply a load
of 8 kVA at 80 V, determine: (a) the primary supply voltage, (b) the
number of turns on each winding and (c) the current in each
winding (all 3 significant figures).
1.2 A 25 kVA, 440/110 V, 50 Hz, single-phase, marine-type, step-
down, ‘engine room’ transformer is designed to work with 1.5 V per
turn with a flux density not exceeding 1.35 T. Calculate: (a) the
required number of turns on the primary and secondary windings
respectively, (b) the cross-sectional area of the iron core (4
significant figures) and (c) the secondary current (2 decimal
places).
1.3 A single-phase, marine-type, step-down transformer has the
following particulars: Turns ratio 4:1; no-load current 5.0 A at 0.3 at
0.3 P.F. (lagging); secondary voltage 110 V; secondary load 10 kVA
at 0.8 P.F. (lagging). Calculate: (a) the primary voltage, neglecting
the internal voltage drop (3 significant figures), (b) the secondary
current on load (3 significant figures), (c) the primary current (1
decimal place) and (d) the primary P.F. (3 decimal places).
1.4 A 6.6 kV, 50 Hz, single-phase transformer with a transformation
ratio of 1:0.06 takes a no-load current of 0.7 A and a full-load
current of 7.827 A when the secondary is loaded to 120 A at 0.8
P.F. (lagging). What is the no-load P.F. (2 decimal places)?
1.5 A 1 kVA, single-phase transformer has an iron loss = 15 W and a
full-load copper loss of 30 W. Calculate its efficiency on full-load
output at 0.8 P.F. (lagging) (2 decimal places).
1.6 A single-phase power transformer supplies a load of 20 kVA at a
power-factor of 0.81 (lagging). The iron loss of the transformer is
200 W and the copper loss at this load is 180 W. Calculate: (a) the
efficiency (1 decimal place), (b) if the load is now changed to 30
kVA at a power-factor of 0.91 (lagging) and (c) calculate the new
efficiency (1 decimal place).
1.7 A 20 kVA, 2000/220 V, single-phase transformer has a primary
resistance of 2.5 Ω and a secondary resistance of 0.028 Ω.
Corresponding leakage reactances are 2.8 Ω and 0.028 Ω. If the
secondary terminals were accidentally short-circuited, estimate the
current which would flow in the primary circuit (3 significant
figures).
1.8 The resistances of the primary and secondary windings of a 27.5
kVA, 450/112 V, single-phase, marine-type transformer are 0.055
and 0.00325 Ω respectively. At the rated supply voltage iron loss is
170 W. Calculate for this transformer: (a) the full-load efficiency at
0.8 P.F. (lagging), (b) the kVA output at which efficiency is a
maximum at 0.8 P.F. (lagging) and (c) the value of maximum
efficiency at 0.8 P.F. (lagging) (all 2 decimal places).
1.9 A three-phase, marine, dry-type transformer is used to step down
the voltage of a three-phase, star-connected alternator to provide
the supply for 120 V lighting. The transformer has a 4:1 phase
turns ratio and is delta connected on the primary side and star
connected on the secondary side. If the lighting is supplied at the
line voltage of the transformer, what must be the phase voltage of
the star-connected alternator (3 significant figures)?
1.10 A 200 kVA, 6600/415 V, three-phase transformer connected in
delta/star supplies a 120 kW, 415 V, 50 Hz three-phase motor
whose P.F. and efficiency are 0.8 (lagging) and 83% respectively.
Neglecting transformer losses, calculate the current in each
transformer winding (Primary 2 decimal places, Secondary 1
decimal place).
Machine Efficiency – getting the most output for the least
input.
Chris Lavers
The operating principle of the transformer, with and without load, was
introduced in Chapter 1 and developed until the causes of internal
voltage drop were considered. Phasor diagrams were added to help
visualise the vector quantities and attention given to the fact that
secondary effects can be seen to be reflected in the primary side,
provided they are equated, using the turns ratio. Thus a step-down
transformer with a 2:1 turns ratio (Primary:Secondary) and a 3 V drop
in the secondary is equivalent to a voltage drop of 6 V in the primary.
It is possible to equate the secondary phasor diagram with
corresponding primary conditions provided the turns ratio relationship
is used now that the phasor method is understood. This technique is
here explored further for a better marine engineer’s understanding of
how transformer efficiency, percentage resistance, reactance and
impedance are obtained. It is unlikely that most of those reading this
volume will have to make all these measurements and perform the
consequent calculations to find the values, but it is a part of the
STCW Code that as a marine engineer criteria exists for evaluating
your competence in the isolation, dismantling and re-assembly of
plant and equipment in accordance with accepted practice.
Figures 2.2a and 2.2b now take the form shown. It is seen that the
The next step is to draw the combined diagram with the in-phase
voltage components added, to give the total resistance and reactance
voltage drops.
reactance referred to the primary side, i.e. the total reactance of the
windings is now considered to be in the primary only.
Also
Similarly
And
Since the turns ratio is taken into account when referring the voltages
and resistance and reactance values from one winding to the other,
the transformer can be omitted from the third equivalent circuit
illustration. The fourth and final illustration shows how the equivalent
circuit is modified to allow for the load, resulting from the iron loss and
magnetising magneto-motive force.
▲ Figure 2.4
Figure 2.3 shows the transformer phasor diagram associated with the
simplified equivalent circuit. Although treatment up to now has shown
all resistance and reactance referred to the primary side, it can be
referred to the secondary side. The simplified equivalent circuit and
phasor diagram are shown in figure 2.6 with = V1, as all voltage
drops are accounted for on the secondary side so that:
Voltage Regulation
This expression refers to the ‘sitting down’ of terminal voltage on
load, and is expressed as a percentage (%) or per-unit value. It is the
ratio of change in secondary terminal voltage between no-load and
full-load to the no-load terminal voltage, for a constant primary input
voltage.
▲ Figure 2.6
Thus:
also
Substituting we have:
Thus V22 + 9.9V2 – 48 400 + 27.92 = 0
The formula uses a plus or minus sign and with the latter, a negative
regulation results. With a capacitive load, secondary voltage rises
with increased load, resulting in a –ve regulation value or regulation
‘UP’. Sitting down of terminal voltage means a +ve regulation value or
regulation ‘DOWN’. Loading conditions, influenced by the P.F., are
shown in figure 2.7.
This is the same value as that obtained by applying the formula to the
secondary side.
Internal Voltage-Drop Formula
(For Approximation)
The reasoning for this expression is based on the phasor diagram of
figure 2.3. It is assumed that the transformer internal voltage-drop
are parallel.
Figures 2.8a and 2.8b show this triangle and the phasors referred to,
drawn parallel and designated OA and OB (added constructions are
shown by the dotted lines). Since the numerical difference between
the no-load and the on-load terminal voltages is equal to the internal
voltage drop, then on the phasor diagram, it is the difference in
lengths of V1 and (the lines OA and OB) a difference given by
For a capacitive load( figures 2.8c and 2.8d), the voltage drop is =
= FC – AE = BCcosφ1 – ACsinφ1
Transformer Testing
As for all electrical machines, transformer testing is central to
checking overall performance. As direct loading involves wasted
energy, methods enabling the design specification to be checked by
assessment are used if possible. Such methods determine the size of
losses, overall efficiency, regulation and, for a transformer, involve 2
complementary tests. These are (1) the Open-Circuit Test (O.C.) and
(2) the Short-Circuit Test (S.C.). The technique measures iron and
copper losses separately and the results are applied to appropriate
formulae. Similar tests are used for other A.C. machines such as the
alternator and induction motor. Variations of the basic O.C. and S.C.
tests help to obtain further information where appropriate.
The open-circuit test
▲ Figure 2.9
(b)
At 25 Hz we can write
– 900 = – Hf
Thus the hysteresis loss = 900 W at 50 Hz
and so the eddy-current loss = 2500 – 900
=1600 W at 50 Hz.
The short-circuit test
The procedure for using the O.C. and S.C. test results for calculation
purposes is illustrated in the next example, with reference to phasor
diagram (figure 2.11).
Consider figure 2.11, since the secondary terminal voltage is zero (on
S.C.), the applied voltage is used to drive current through the
transformer’s equivalent impedance referred to the primary. Thus
point B of figure 2.8 coincides with point O and:
▲ Figure 2.10
▲ Figure 2.11
O.C. Test Primary voltage 3300 V, second voltage 400 V, input power
430 W.
Calculate:
(a) The efficiency at full load and 1/2 full load both at 0.707 P.F.
(lagging).
(b) The regulation at full load for 0.707 P.F. (lagging and leading).
(c) Full-load terminal voltage under the condition of 0.707 P.F.
(lagging).
Also
Also
Therefore:
and
Note that on 1/2 full load, current is halved and copper loss α I2 is
quartered.
The disadvantages of the O.C. and the S.C. tests lie in the fact that
iron and copper losses do not occur at the same time and so the
temperature rise of a transformer cannot be checked by tests alone. If
more than one unit is available, to avoid waste of power by direct
loading, a back-to-back test may be used. Sumpner’s test is
performed with 2 transformers which should be identical (but may be
similarly rated units provided the turns ratios are the same). If the
copper loss of one unit where PCu is the reading of one wattmeter
Similarly,
and,
Efficiency
The efficiency curve is shown, in figure 2.12a, with the effect of the
power factor. The earlier statement that maximum efficiency occurs
when copper loss = iron losses can now be proved (figure 2.12b).
▲ Figure 2.12
Now
If therefore by simplification
copper loss = the iron losses. Thus for a given kW output at constant
terminal voltage, since then
Practice Examples
2.1 On open-circuit, a single-phase, marine, dry-type transformer
gives 115 V at its secondary terminals when the primary winding is
supplied with 460 V. The resistance and leakage reactance of the
primary windings are 0.36 and 0.83 Ω respectively while those of
the secondary windings are 0.02 and 0.06 Ω respectively. If the
secondary terminals are accidently short-circuited while the
transformer is connected to the supply, what would be the value of
current flowing in the primary winding (3 significant figures)?
Assume that the supply voltage is maintained at 460 V and the
magnetising current value can be neglected.
2.2 For a 25 kVA, 450/121 V, single-phase transformer, the iron and
full-load copper losses are respectively 165 and 280 W. Calculate
(a) the efficiency at full load, unity P.F. and at half-full load 0.8 P.F.
lagging (2 decimal places); (b) and the load at which efficiency is
maximum in kVA (1 decimal place).
2.3 A marine, dry-type, 17.5 kVA, 450/121 V, 50/60 Hz, single-phase
transformer gave the following data on test:
O.C. Test 450 V, 1.5 A, 115 W at 50 Hz
S.C. Test 15.75 V, 38.9 A, 312 W at 50 Hz
Estimate (a) efficiency of the transformer and (b) the voltage of the
secondary terminals (both 1 decimal place) and when supplying
full-load current, at 0.8 P.F. (lagging), from the secondary side.
Assume the input voltage is maintained at 450 V, 50 Hz.
2.4 A single unit of the 3 units making up a three-phase, marine, dry-
type transformer, was subjected to a short-circuited test and the
following results were obtained:
Voltage applied to the H.V. side: 14.3 V at 60 Hz
Current supplied: 55.6 A
Power taken: 316 W
The unit is rated at 25 kVA, 450/121 V, 60 Hz.
Determine the approximate value of the secondary terminal voltage
(3 decimal places) when the transformer is operating at full-load,
0.8 P.F. (lagging) and 0.8 P.F. (leading).
2.5 The resistances of the primary and secondary windings of a 27.5
kVA, 450/121 V, single-phase, marine, dry-type transformer are
0.055 and 0.00325 Ω respectively. The iron loss is 170 W. (a) At
0.8 P.F. (lagging), calculate the full-load efficiency (1 decimal
place). (b) At 0.8 P.F. (lagging), calculate the kVA output (2 decimal
places) at which efficiency is a maximum and find the maximum
efficiency value (2 decimal places).
2.6 A 50 kVA, 440/110 V, single-phase transformer has an iron loss =
250 W. With the secondary windings short-circuited, full-load
currents flow in the windings when 25 V is applied to the primary,
power input being 500 W. For this transformer determine (a) the
percentage voltage regulation at full-load, 0.8 P.F. (lagging) (2
decimal places) and (b) the fraction of full load at which the
efficiency is a maximum (3 decimal places).
2.7 A 10 kVA, 440/110 V, single-phase, marine, dry-type transformer
was tested and gave the following results:
O.C. Test – Primary applied voltage 440 V, power input 75 W.
S.C. Test – Primary applied voltage 30 V for full-load current, power
input 135 W.
Draw the equivalent primary circuit indicating the values of the
circuit constants, but neglecting no-load conditions, and then
calculate (a) the secondary terminal voltage when the transformer
is operating at full load, 0.8 P.F. (lagging) with the rated voltage
applied to the primary, (b) transformer efficiency for (a) above (both
1 decimal place).
2.8 A 50 kVA, 440/230 V, marine, lighting-transformer has primary
resistance and reactance of 0.09 and 0.19 Ω respectively and
secondary resistance and reactance of 0.015 and 0.042 Ω
respectively. Calculate the secondary terminal voltage (3 significant
figures) when the transformer is supplying full-load current at 0.8
P.F. (lagging). If the secondary terminals were accidently short-
circuited, what would be the current taken by the primary winding,
assuming the primary supply voltage remained constant at 440 V
(4 significant figures)?
2.9 A 17.5 kVA, 460/115 V, 60 Hz, single-phase transformer has
primary and secondary resistances of 0.125 and 0.008 Ω
respectively and primary and secondary leakage reactances 0.39
and 0.025 Ω respectively. The iron loss, when normal voltage is
applied to the primary winding, is 300 W. Draw the equivalent
circuit and calculate (a) for the full-load, 0.8 P.F. (lagging) condition,
the voltage at the secondary terminals (3 significant figures) and (b)
the efficiency of the transformer (1 decimal place). Neglect the no-
load current.
2.10 A marine, dry-type, 50 kVA, 440/110 V, single-phase transformer
gave the following data on test:
O.C. Test – Primary applied voltage 440 V, secondary voltage 110
V, power input to primary 250 W.
S.C. Test – Primary applied voltage 25 V, primary current 113.6 A,
power input at primary 500 W.
Calculate (a) the efficiency at half full-load, 0.7 P.F. lagging (1
decimal place) and (b) the voltage regulation at full-load, 0.8 P.F.
lagging (2 decimal places).
Speculations? I have none. I am resting on certainties.
Michael Faraday
Instrument Transformers
This section covers current and voltage transformers: the latter are
sometimes called potential transformers. When current in a circuit is
too high to directly apply measuring instruments a Current
Transformer (C.T.) produces a reduced current, accurately
proportional to the current in the circuit, and also isolates the
measuring instrument from any high voltage in the circuit. Digital
clamp meters use a C.T. for measuring A.C. current. Instrument
transformers may also be used with indicating or recording
instruments, protective equipment, alarms and control gear, and have
several advantages.
▲ Figure 3.1
Im is decided by the factors shown and for a C.T. working flux density
is typically 1–1.5 × 10–4 T compared with a usual power transformer
figure of 14 × 10–4 T. The iron circuit length is made as short as
possible using high-permeability iron. N may be large, but this is not
possible if a single-turn or ‘bar-primary’ is used. Other construction
features result from the following requirements. Since the iron circuit
must have low reluctance, for the best C.T.s, laminations have the
least number of joints, or are ideally complete rings. Windings are
placed by hand and leakage reactance is reduced by superimposing
or sandwiching windings. The primary circuit is largely unaffected by
insertion of a C.T. The rated secondary current is commonly
standardised to 1 or 5 A. For example, a 2000 5 C.T. provides an
output current of 5 A when the primary passes 2000 A.
C.T. burdens are typically given as 1.5, 3, 5, 10, 20, 30, 45 and 60
VA. Burden ratings are typically in the form B-0.1, B-0.2, B-0.3, B-0.4,
etc. This means a C.T. with a burden rating of B-0.1 can tolerate up to
0.1 Ω impedance in the metering circuit before its output current is no
longer on a fixed ratio to the primary current (essential for accurate
proportionality). Consequently the knee-point voltage of a C.T. is the
magnitude of the secondary voltage after which output current ceases
to follow linearly the input current. The knee-point is defined as the
voltage at which a 10% increase in applied voltage increases the
magnetising current by 50%, above this point the magnetising current
increases in a rapid non-linear manner even for small voltage
increases across the secondary terminals.
The wattmeter and P.F.I. burdens are 5 × 0.3 × 5 = 7.5 VA. The total
burden is then 3.75 + 7.5 + 7.5 = 18.75 VA and a C.T. rating equal or
greater than this is needed. Thus a 30 VA unit is suitable. Instrument
burdens add arithmetically, as they are due mainly to a resistance
load, and any error introduced by this assumption is small.
If a suitably rated unit is not available one should use 2 C.T.s. and 2
independent instrument circuits. Thus an ammeter may be energised
from the first C.T. together with another instrument like an over
current relay, and the second C.T. used for the wattmeter and P.F.
indicator. However, most instrument and protective-gear circuits are
separated rather than mixed. Shapes and sizes vary significantly
depending on the end user, switchgear and manufacturer. C.T.
accuracy is directly related to several other factors besides burden
and class which are rating factor, load, external E.M. fields,
temperature and the physical arrangement. The rating factor, the
factor by which the nominal full load current of a C.T. can be
multiplied to determine its maximum measurable primary current,
depends largely on ambient temperature with most C.T.s rated for
35°C and 55°C working.
The theory of the voltage transformer (V.T.) follows that of the power
transformer (P.T.), the main difference being that the secondary
current, referred to the primary, may be of the same order of
magnitude as the no-load current. From phasor theory is to as
the turns ratio, and the desired approximation of V2 to V1 is achieved
if the voltage drops, as mentioned, are reduced.
The following precautions are usually taken in the use and building of
transformers:
Unlike the C.T., the primaries are connected across the ‘mains’ and
an S.C. on the secondary will be a short referred to the primary. S.C.
protection is needed and high-rupturing-capacity fuses are fitted in
primary circuits. As this is a high-voltage supply, fuses are insulated
and a specialist tool provided for replacement without switching the
‘mains’ off. A secondary circuit’s mid-point can be earthed so the
maximum voltage to earth on the system is 55 V. As instruments are
in parallel as for the C.T., disconnection or reconnection of a suspect
meter is not difficult. There is no danger of a high induced voltage, as
for the C.T., but short-circuiting of terminals must not be undertaken.
PHASE ANGLE. Like the C.T., a V.T. can introduce metering errors in
both voltage magnitude and phase. Ratio and phase-angle errors
depend on the impedance voltage drops’ relative sizes, and it was
explained how these can be minimised. Phase-angle error is only
important when power measurement is required.
The Auto-Transformer
▲ Figure 3.4
ratio =
or Φm = . Since Φm = BmA
The winding must be tapped 625 turns from the end, common to
primary and secondary.
▲ Figure 3.5
Here So ratio =
Three-phase transformation
▲ Figure 3.8
Methods of connection
1. Star/Star. Figure 3.9a shows the arrangement and connection
event of a winding failure the unit need not be shut down since, by
disconnecting the faulty winding, supply can be maintained at a
reduced output (graceful degradation). This working method, known
as open-delta, is favoured by Continental and American marine
practice. As no neutral point is available, a 3-wire supply is used. Any
3rd harmonic currents, set up by 3rd harmonic e.m.f.s in the phases,
circulates around the closed mesh and won’t flow out into the lines.
The connection avoids distortion of secondary e.m.f. waveform by
internally generated harmonics.
phase-turns ratio.
phase currents.
▲ Figure 3.10
▲ Figure 3.11
▲ Figure 3.12
The transductor
This device was similar in construction to a power transformer. It was
a type of magnetic amplifier used in power systems for compensating
reactive power, consisting of an iron-cored inductor with 2 windings –
a main winding through which an A.C. current flowed from the power
system, and a secondary control winding carrying a small D.C.
current. By varying the small secondary D.C. current, a transductor’s
iron core can be controllably saturated at different levels thus varying
the reactive power absorbed. Transductors were widespread before
the advent of modern solid-state electronics and have largely been
replaced.
▲ Figure 3.13
For the –ve supply voltage half-cycle, the operation is repeated. Core
1 comes out of saturation but its winding is short-circuited by core 2
which has gone into saturation. Control is obtained over a full cycle
by the D.C. control winding with its current maintained continuously in
one direction. Control current reversal only changes the order in
which saturation of the cores occurs, and the controlling effect is as it
was before. Figure 3.14 shows the waveforms associated with a
simple mag amp. Output is alternating and pulsed, and may be
converted for D.C. operation with a suitable rectifier.
winding and Ic the control current. N = the number of turns of the main
winding and I the load current. The relationship shows the current
gain is proportional to the turns ratio of load and control windings.
▲ Figure 3.14
Since , load current depends on the turns ratio and the control
current, independent of the supply voltages or load resistance, and
the amplifier is regarded as a constant current source. Before leaving
the current waveform (figure 3.14), it is noted that, since the control
current is fed from a D.C. source its value might be assumed
constant (from the control circuit resistance). However, if flux is
constant, IcNc = IN and if I varies, Ic will vary. Thus a reflection of the
load-current peaks is seen in the control current.
With the input signal in one direction a current through the feedback
winding aids the control winding and increases gain. With a reversed
signal, current through the feedback winding remains in the same
direction and opposes the control current, reducing gain. The new
characteristic is shown in figure 3.17. Current gains of up to 300 and
power gains of 104 are possible with this arrangement. Thus a bias
winding can be added to move the no-signal operating point and if
two amplifiers are used a reversible output with no standing current is
achieved. Amplifiers can also be used in cascade for increased gain.
and x2 + y2 = 1802
or
Resistance of coil =
Reactance of coil =
Inductance of coil =
(b)
Load current =
Lighting transformer.
Supply transformer.
Assuming no losses
Solid-State Transformers
Although hopefully obvious to the reader, the historic context of the
transformer has been in terms of high-power handling transmission
with the power grid delivering A.C. power (for reasons discussed),
with every appliance, from electrical equipment such as vacuum
cleaners and hair dryers, to washing machines, P.C.s, notebooks,
electric motors, batteries, etc. running on D.C. power. It is only
recently that transformer interest has shifted in weighting towards the
lower power ‘personal computing power requirements’ end of the
spectrum, generating developments in computer based Solid-State
Transformer (S.S.T.) applications, an area rather unsuited to the high-
power requirements of the majority of marine and terrestrial electrical
power distribution systems. The term S.S.T. is a little inaccurate
because it is not a transformer in the traditional sense, but an array of
high-power semiconductor silicon solid-state components, control
circuitry and digital software employed to flexibly convert the voltage
and provide control to the power distribution networks, an
arrangement referred to as a smart transformer.
In this way the ‘Victorian’ power grids of the world can be reorganised
into something more like the Internet for the 21st Century – a network
channelling energy not from just a few centralised power stations but
from any number of sources to a selected destination by the most
efficient routes (as in communications packet switching) balancing
both supply and demand, minimising power plant production waste in
terms of waste power and pollution.
Practice Examples
3.1 A direct-reading wattmeter with a 5 A current-coil and a 110 V
voltage-coil is used to measure the power in a single-phase, 6.6 kV
circuit, carrying a maximum current = 100 A. State the appropriate
ratios for the instrument transformers (2 decimal places), and
calculate the constant by which the wattmeter reading must be
multiplied to measure the power consumed (2 significant figures).
3.2 A 75 kW, 415 V, three-phase induction motor has 80% full-load
efficiency. The input line current is measured by a C.T. operated
ammeter. Suggest an appropriate ratio for the C.T. if ammeter full-
scale deflection is 5 A (2 decimal places). State the expected
ammeter reading (1 significant figure). The motor P.F. on full load =
0.87 (lagging).
3.3 A single-phase wattmeter with 5 A and 250 V ranges is used in
conjunction with a 25/5 C.T. to measure the power of one phase of
a balanced, three-phase, star-connected load. If the load absorbs
12 kW from a three-phase, 415 V, 50 Hz, supply and 0.8 P.F.
(lagging), calculate (a) the wattmeter reading (2 decimal places),
(b) the load’s impedance per phase (2 decimal places) and (c) if a
phase impedance consists of a resistor and reactance in series,
calculate their equivalent phase values (3 decimal places).
3.4 The output power of a 415 V, three-phase alternator supplying a
balanced load is measured by one wattmeter. If the current
transformer has a 25/5 ratio and the wattmeter reading is 7 kW,
what is the total power (3 significant figures)?
3.5 For recording the input to a three-phase, 7.5 kW induction motor,
which is rated to take a line current of 14 A at 415 V, the following
instruments are to be used:
Ammeter 0 to 5 A, of resistance 0.08 Ω.
Voltmeter 0 to 120 V, of resistance 3636 Ω.
Three-phase wattmeter (two element type): current coils 0 to 5 A,
of resistance 0.1 Ω; voltage coils 0 to 120 V, resistance 4 kΩ.
Estimate the ratio and burden rafting of suitable current and voltage
transformers (1 decimal place).
3.6 The primary and secondary voltages of an auto-transformer are
500 V and 400 V respectively. Find the windings’ current
distribution if the secondary current is 100 A (2 decimal places),
and calculate the possible copper saving percentage (2 significant
figures).
3.7 A double-wound, 6 kVA, 250/150 V, single-phase transformer, is
used as an auto-transformer on 400 V mains, to supply a load of 12
kVA at 250 V. Check the windings’ current load and with a practical
connection method determine the arrangement’s suitability.
3.8 Find the values of the currents flowing in the branches of a three-
phase, star-connected A.T. loaded with 400 kW and 0.8 P.F.
(lagging) with a ratio of 440/550 V (3 significant figures). Neglect
voltage drops, magnetising current and all transformer losses.
3.9 A 440 V, three-phase induction motor started with a delta-
connected A.T. provided with a 70% tapping on each phase
winding. Find the voltage applied across the motor terminals at the
starting stage when the transformer tappings are in the circuit (4
significant figures).
3.10 A three-phase, 440 V, 40 kW induction motor has 82% efficiency
and operates with 0.85 P.F. (lagging). When direct-on started, the
motor takes a current of 6 × full-load current and produces a torque
of 1.5 × full-load torque. Calculate the current taken from the supply
and the ratio of starting to full-load torque if a motor is started
through a star-connected A.T. with a 75% tapping (2 decimal
places).
For an engineer it is not how full or empty the glass is, but
what design size you require.
Chris Lavers
Output
Efficiency
Bearing friction is minimised using the correct bearing type for the duty
undertaken by a machine. Small and medium size high-speed
machines are often provided with ball or roller bearings. Low-speed
machines of such sizes use well-lubricated sleeve bearings. In marine
work this bearing is chosen because of its superior vibration
performance. For large machines, special bearing arrangements involve
forced high-pressure lubrication. Rotor weight and speed, drive type,
position and machine mounting are factors which decide the bearing
type. Bearing friction loss is roughly proportional to speed. Brush friction
depends on the friction coefficient, the total pressure and peripheral
commutator speed. It must be appreciated that a specific machine
brush grade should be chosen in accordance with the design
requirements and must not be altered. In summary: Mechanical losses
are proportional to speed and attention will be drawn to this relationship
as required.
Example 4.1. A 220 V shunt motor takes 10.25 A on full load. Armature
resistance is 0.8 Ω and the field resistance is 880 Ω. Losses due to
friction, windage and iron = 150 W. Find the output power and motor
efficiency on full load (3 significant figures).
Field copper loss = 220 × 0.25 = 55 W Friction, windage and iron loss =
150 W
Dividing by VIa
obtained.
Constant loss.
Note: the field copper loss is included in Pc. The same condition for
maximum efficiency can be devised for a motor.
Testing methods
(1) The Friction Brake. This can be a rope, band or drum type (taking
the form shown in figures 4.1a and 4.1b).
▲ Figure 4.1
For type (a) the force recorded by spring balances and acting on the
drum equals (W – w) newtons. If the radius of the drum is R metres,
torque T is given by (W – w) R newton metres.
▲ Figure 4.2
▲ Figure 4.3
▲ Figure 4.4
(1) The Swinburne Method. This is suitable for large machines where
loading either as a generator or as a motor might present difficulty. For
a D.C. shunt motor change of speed from no load to full load is small.
Mechanical loss is assumed to stay constant from no load to full load. If
field current is held constant during loading, core loss is assumed to
remain constant. To make a test, a machine is run ‘light’ as a motor
irrespective of its final function. Armature and field resistances are
measured before the no-load test and ambient temperature are noted.
During the test, the supply voltage and input current are recorded after
the speed is adjusted to the value at which the machine is required to
operate on load. Efficiency is then assessed (figure 4.5).
▲ Figure 4.5
When a machine is run light no output is taken from the shaft (net
mechanical output power is zero), only sufficient input power is needed
to supply the machine no-load losses (the copper and rotational losses).
or Whence:
Once rotational loss is determined for a particular speed and excitation
condition, one can assess the efficiency at any load (speed and
excitation is assumed constant). Thus for a generator we use the
expression:
No load.
Pc = 5029.3 W or 50.3 kW
Full load.
(2) Summation of Losses Method (by Auxiliary Motor). Figure 4.6 shows
the arrangement with 2 machines coupled together by a belt. In practice
to avoid belt-slip or losses due to belt friction, machines are fixed in line
and directly coupled. The smaller machine is the auxiliary motor and
tests are made in stages.
▲ Figure 4.6
Let P0 be the input power to the auxiliary motor when running light and
at the speed required to drive the large machine at its operational speed
of N rev/min.
Let P1 be the input power to the auxiliary motor when coupled to the
large main machine and driving its armature in an un-excited field at an
operational speed = N rev/min. So: P1 – P0 = PM the mechanical losses
(windage and friction) of the large machine.
Let P2 be the input power to the auxiliary motor, coupled to the main
machine and driving its armature in an excited field at a speed of N
rev/min.
Then P2 – P1 = Iron losses (PFe) of the main machine under the correct
test conditions of speed and flux. Since PM and PFe = PR rotational loss
(PR) is determined from P2 – P0.
(1) The Hopkinson Method. The test is performed and used for
machines which are similarly rated. Machines are mechanically and
electrically connected (figure 4.7).
▲ Figure 4.7
The machine operating as a motor is started by cutting out the starting
resistance and speed adjusted by variation of the field regulator,
controlling IfM. The generator self-excites and its voltage is controlled by
the regulator varying the current IfG. A change-over switch is operated
from position 1 to position 2 and the generated voltage EG adjusted and
compared with the mains voltage V. When EG = V the parallel switch is
closed since no current can circulate between G and M for this
condition. If EG is increased by raising IfG, a generator can be loaded,
i.e. it supplies current. The motor consequently loads and requires an
increased current from the generator. By manipulating the field
regulators of both machines a condition is achieved when either the
motor or generator is fully loaded. Power taken from the supply will be a
minimum and then supplies both machine losses. Under this condition:
From this expression PRM + PRG is found and if they are assumed to be
similar the rotational loss of each machine can be found. Resistance Ra
and Rf are measured ‘hot’ after the test and efficiency calculated for any
load under normal working conditions either as a generator or motor
(example 4.6). Note: approximate efficiency is found on the test-bed for
checking from the following.
Let P be the power transmitted through the coupling between motor and
generator.
Then and
Since IM = 100 A Then IaM = 100 – 2.5 = 97.5 A and IaG = (100–15) + 3
= 88 A
(2) Field’s Method. Due to the tendency for series motors to race on no-
load and difficulties of operating a series generator in parallel with a
constant voltage supply, regenerative test method is not possible
without taking precautions and giving the test-rig continual attention. In
its essential form Field’s test is not strictly a regenerative method. Two
similar series motors are mechanically coupled, one machine acting as
a motor and the other as a separately excited generator. Both series
fields are connected in series with the motor armature and the
generator output absorbed in a resistance load with no switches in the
circuit to eliminate any possibility of a detached load. The method of
calculating efficiency is given in example 4.7.
Example 4.7. The following results were obtained from a Field’s test on
2 series motors: Motor current 20 A; Generator output current 17.5 A;
Generator voltage 160 V; Supply voltage 220 V; Resistance of each
armature 0.6 Ω; Resistance of each series field 0.4 Ω. Estimate full-load
efficiency of a machine as a motor (2 decimal places).
Motor and generator field copper losses = 202 (2 × 0.4) = 400 × 0.8 =
320 W
(1) Shunt Generators. Such machines are easily paralleled and operate
with stability for the following reasons. If the prime-mover of No. 1 (see
figure 4.8) slowed down momentarily, the generated e.m.f. would fall
and the output current, I1, given by the expression would fall.
▲ Figure 4.8
(2) Series Generator. A series generator will not self-excite until the load
circuit is completed and its resistance made less than the critical value.
Such a machine cannot be paralleled onto ‘live busbars’. To investigate
parallel operation, assume 2 similar series generators in parallel,
started together from rest with the load circuit completed. If the latter is
adjusted until self-excitation results, operational stability can be
examined (figure 4.9).
▲ Figure 4.9
Load sharing
Example 4.8. Two shunt generators A and B, each with straight line
load characteristics operating in parallel. The characteristics are:
Machin
Open-circuit voltage Terminal voltage at 50 A
e
A 460 V 420 V
B 440 V 410 V
Determine how both machines share a 100 A load and find the common
busbar voltage (1 decimal place).
and, EB = V + IBRaB
(b)
440 = V + 0.6 IB
Subtracting 80 = l.4IA or
Graphical Solution. Two methods are possible and both are applied to
this problem.
Method 1. The two characteristics are plotted (figure 4.11a) with voltage
ordinates spaced 100 A apart. The common terminal or busbar voltage
is given by the intersection of the lines. The required answers can be
read off the graph. The method is suited for problems where load
sharing for one current value is needed. If a problem requires solution
for more than one load current method 2 is more suitable.
▲ Figure 4.11
Commutation
For both lap and wave windings as a brush passes from one segment
to the next, a coil element of a single coil or a series of coils is short-
circuited briefly during the commutation process. Brushes are placed at
points on the commutator where currents converge from and diverge to
parallel paths of the armature. At these points brushes contact adjacent
segments connected to coil elements in the interpolar gaps, optimally
placed for short-circuit. In summary: the currents in the armature coil
elements on either side of the brushes are in opposite directions and as
the commutator turns and a complete S.C. element passes under a
brush from one side to the other, current in the element must reverse. In
the arrangement of figure 4.12 adjacent segments pass under a brush,
and current in connected coil element X must be stopped and restarted
in the opposite direction. A width of brush equal to that of a commutator
segment is assumed.
▲ Figure 4.12
▲ Figure 4.13
Figure 4.13 shows the current/time curve for coil element X being
commutated. The time marked ‘t’ is the period when current direction
reverses, i.e. the time taken for a brush to pass completely from one
segment to the next, is perhaps 1/1000th second or less. The ±ve signs
of the current ordinate are arbitrary and indicate current reversal.
The commutation condition here is for the ‘ideal case’ and is not
achieved in practice. For the coil element being commutated, because
of self and mutual inductance effects, due to the rapid collapse of flux
associated with a changing current, an induced e.m.f. is set up called
the reactance voltage. According to Lenz’s law, this e.m.f. opposes and
tends to slow the rate of current change. Thus current in the S.C. coil
element changes more slowly and the condition is shown by a new
current/time graph (figure 4.15).
▲ Figure 4.15
It is seen from the actual working conditions graph that although the coil
current has reversed, it has not reached its full –ve value when
commutation finishes. The effect of ‘under-commutation’, where for the
instant considered, i.e. when , the last section of a brush carries
Since for the coil element X inductance and resulting reactance voltage
are the main causes of poor commutation, it is clear these must be
minimised. If an e.m.f. can be generated in coil element X to produce a
current in the same direction as occurs when the element enters the
armature-current path after it has been commutated, the effect of under-
commutation can be cancelled. This is the main means of improving
commutation but commutation can benefit by increasing brush
resistance. ‘Resistance commutation’ is used in small machines and is
one of the methods used for improving commutation.
▲ Figure 4.17
So reactance voltage =
METHODS OF IMPROVING COMMUTATION. These are considered
under 3 distinct headings but a combination of 2 methods is often used.
Armature reaction
We will now look further at the armature reaction effect. The armature
conductors produce flux when a machine is supplying or taking current.
This armature reaction effect provides the characteristics of various
D.C. generator and motor types. Armature reaction may be defined as:
‘the effect on the main-field flux caused by armature flux, which due to
the armature current, distorts and weakens the main-field flux’.
Armature flux is at right angles to the main flux and termed a cross-
magnetising flux crossing each air-gap twice, i.e. if the N pole-piece is
considered, armature flux is opposite to the main flux at the leading pole
tip and in the same direction at the trailing pole tip. The terms leading
and trailing are used in this regard with the armature rotation taken as
the reference for this distinction. The net effect of a cross-magnetising
flux is seen in figures 4.21a and 4.21b where the total flux twists and
the M.N.A. moves through an angle of lead.
▲ Figure 4.21
▲ Figure 4.22
▲ Figure 4.23
▲ Figure 4.24
Armature flux combines with the main flux to give the resultant flux,
represented by a new m.m.f. vector diagram. The resultant F is found
by resolving Fa into quadrature components Fc and Fb. Fb is a
demagnetising component which weakens Fm to give a new reduced
value Fm1. Fc is the cross-magnetising component which acts with Fm1
to give the new resultant F. To ensure satisfactory commutation, the
new armature reaction condition results in the 2 effects mentioned
previously, namely: (1) the main field weakens and (2) the main-field
flux density in the air-gap distorts. The forward movement of brushes or
angle of lead is only required for generators. For a machine operating
as a motor, the armature current direction is reversed for the same
rotation direction and main field polarity. As a result armature flux
reverses and brushes are given an angle of lag for correct operation.
The main flux is distorted and weakened as before, and if brushes
move when a motor runs, speed can vary. This is not a recommended
method of speed variation as optimum commutation conditions are
desired, but the cause of speed variation is due to flux-density variation.
Example 4.10. A 150 kW, 250 V, 6-pole D.C. generator has a lap-wound
armature with 432 conductors. If the brushes are given a 5° angle of
lead from the G.N.A., estimate the added ampere-turns per pole
needed to neutralise an armature’s demagnetising effect when a
machine is on full load. Neglect the shunt field current. A solution is
considered with 2 pole-pitches.
Effective conductors in two pole-pitches = Effective armature
turns = 72
The flux-density distribution under the main poles and in the interpolar
gap, caused by the main-field ampere-turns and the armature ampere-
turns respectively, is shown separately and combined. The armature-
current m.m.f. acts with the main-field m.m.f. to produce a resultant
m.m.f. and flux-density distribution pattern which is uneven over the
pole arc. The e.m.f.s generated in the armature-coil elements are non-
uniform as they pass across the pole face and voltages between
commutator segments may, in some positions, be much higher than the
mean value. If field distortion is pronounced there is a danger of a
‘flash-over’ across the commutator. The effect of the armature m.m.f.
can be mitigated against partly by fitting a compensating winding, which
is an expensive solution only used in large machines subject to heavy
and sudden current peaks, and is not discussed here as use is limited.
Examples of such applications include motors for steel-rolling mills and
special generators such as those used in electric locomotives.
This device was a cross-field generator (C.F.G.) given the brand name
Amplidyne, a special-purpose D.C. generator which still supplies large
precisely controlled D.C. currents to large D.C. motors used to drive
heavy physical loads, such as gun turrets or missile launchers. It is
really a motor and generator which for most maritime purposes has
been replaced in low-power applications by the MOSFET and Insulated-
Gate Bipolar Transistor (IGBT).
Practice Examples
4.1 A D.C. shunt motor has an armature resistance of 0.9 Ω and takes
an armature current of 18 A from 230 V mains. Calculate the motor’s
power output and overall efficiency (3 significant figures). Rotational
losses are measured to be 112 W and shunt-field resistance is 300 Ω.
4.2 Calculate the light-load current taken by a 100 kW, 460 V shunt
motor assuming the armature and field resistances to remain
constant and to equal 0.03 Ω and 46 Ω respectively. Efficiency at full
load is 88% (2 significant figures).
4.3 A 200 V, 15 kW motor when tested by the Swinburne method gave
the following results: Running light, the armature current was 6.5 A
and the field current 2.2 A. With the armature locked the current was
70 A, when a potential difference of 3 V was applied to the brushes.
Calculate the efficiency on full load (1 decimal place).
4.4 A Hopkinson ‘back-to-back’ test made on two shunt generators
rated at 150 kW, 220 V, required 140 A to be taken from the mains.
The field currents of the two machines were 5 A and 7 A and the
armature resistance measured to be 0.02 Ω. Estimate the efficiency
of each machine when loaded to 150 kW (1 decimal place).
4.5 The results of a test made to determine the open-circuit
characteristic of a ship’s shunt-connected generator are set out
below. The test was made with the machine being separately excited
and driven at 700 rev/min.
Electromagnetic Induction
In Volume 6, both Faraday’s and Lenz’s laws were introduced. These
laws stated the magnitude and direction of the e.m.f. which is self-
induced in an inductor when its associated flux-linkages are
changing. A basic formula was given for the
Eav gives the value of the induced e.m.f., when N is the number of
turns of the coil, Φ is the flux value (in weber) associated with the coil,
and t is the time taken for the flux to change. This formula is useful, if
a steady rate of change occurs but if the change occurs in a short
interval or varies from instant to instant the condition is best
expressed as .
Note: it is the flux that is changing and not the number of turns. Now
the calculus method was introduced and is suitable here for finding
the rate of change of flux as instantaneous values are involved. Here
e gives the instantaneous magnitude of induced e.m.f. resulting from
a rate of change of flux, which differs from instant to instant.
Inductance
Or
Thus
Chapter 9.
Note: l is used for the length of the magnetic circuit to avoid confusion
with L, the inductance.
ampere
inductance.
▲ Figure 5.1
▲ Figure 5.2
Growth of current
From earlier work on induction and inductance, it was seen that, the
effects of induction are always present, even under a circuit’s steady
running conditions. For our study we are concerned with transient
conditions, i.e. effects which occur when an inductive circuit is
switched ‘on’ or ‘off’. Our main interest here is in D.C. circuit
conditions but mention will be made of corresponding A.C. conditions.
per second. This current will not reach a steady value since there is
no resistance and continues to grow (figure 5.3a).
▲ Figure 5.3
Here e is not the symbol for induced e.m.f. but is the base of
Naperian Logarithms, where e = 2.718 and log10e = 0.4343.
Differential equations of this type are derived at appropriate points
and the solution method will be of interest to students. This method is
set out as follows for the above equation.
Since
or
Thus .
This is often known as the Helmholtz equation and shows that the
growth curve is of exponential form. Further investigation of the
mathematics leads to the term time-constant and its meaning.
Similarly substituting in
or 0.4343 t = 0.301
Thus seconds.
Thus
the current to attain 63.2% of the full value. The following deduction
will be of interest.
Thus
So log2 =
and and
seconds.
seconds.
Here and
Then giving:
Also
Decay of current
Assume for simplicity that the inductor, after connection to the supply,
is short-circuited at the same instant as the supply is switched off. As
the field collapses the energy put into the magnetic field must be
released through a current with heat generated in the circuit’s
resistance with the arrangement shown in figure 5.4. The current
decays in a circuit with the same constants as before.
▲ Figure 5.4
When t = 0 i = I ∴K = logeI
giving
or
which can be written as
▲ Figure 5.5
The field dies slowly but the induced voltage will be kept at a safe
value.
(c) Let RT be the total resistance of the circuit. Then 5RT = 750
So RD = 150 – 100 = 50 Ω
(d) Here
The Direct Current CR Circuit
Because the LR circuit behaviour was considered in some detail, it is
appropriate to give attention to that of a circuit of resistor R and a
capacitor of capacitance C connected to a D.C. supply. In Chapter 8
of Volume 6 the capacitor was introduced and its ability to store
electricity discussed. Charging action was described, in that, a
current will pass on closing a switch to the supply, and the current
falls to zero as the potential difference across the capacitor plates
rises to eventually equal the applied e.m.f. supply. Discharging
conditions were also described and attention given to a thorough
investigation of charging and discharging, noting that the quantity of
electricity which can be stored is proportional to charging voltage.
Growth of current
Charging is considered and as stated above, Q ∝ V, so we rewrite Q
= CV where C is a constant, termed the capacitance. Since Q = It it
follows that . The current, at any instant, depends on
▲ Figure 5.6
▲ Figure 5.7
So loge whence
or giving
and or
THE TIME CONSTANT. If the initial rate of current build up, i.e. ,
Discharge conditions
The circuit switch of figure 5.7 is operated so the capacitor is
disconnected from the supply and discharges through a short-circuit.
As no resistance is present, the discharge current will be very large
and may damage the capacitor. It is usual to include resistance in a
circuit for this reason which may be achieved by moving R to the
hinged side of the switch. The circuit time constant will be the same
as for the charging condition, but may be altered by adding a further
discharge resistance RD into the short-circuiting link.
▲ Figure 5.8
voltage across the resistance after a time t seconds is v volts and the
current at that instant . The current is caused by the voltage
change or
of voltage dv
Thus
giving i = 5.488 μA. For this charging current, the voltage drop across
the resistor will be 5.488 × 10–6 × 50 × 106 = 274.4 V.
Current asymmetry
▲ Figure 5.9
Let the actual current after closing the switch at any instant be i = i1 +
i2. The simplest condition to understand is shown, which assumes the
supply voltage is going through its normal value when the switch
closes. Since the current for the normal closed circuit condition has a
definite value and phase angle (but is actually zero when the switch is
closed), it follows that a component of D.C. current is induced which
decays exponentially to zero. This is shown in the diagram and i2 is
assumed to be the instantaneous value of the transient current which
may or may not be present, according to the circuit conditions at the
instant of switching.
The expression for the transient current is obtained from the following
deduction where i1 is the permanent current.
(a)
Under steady conditions i2 = 0 and (b)
Rectification
Several terms should be first understood before the half-wave and
full-wave rectification methods are considered in detail.
Terms
(1) Peak Inverse (or Reverse) Voltage (P.I.V.). This is the maximum
value of reversed voltage which a rectifier unit must withstand
during non-conducting periods.
(2) Peak Current Rating. When a rectifier is used with a ‘reservoir’
capacitor smoothing system, it can pass pulses of current which
are greater than the load current. The greatest current value, which
can be safely passed, is the device Peak Current Rating.
(3) Ripple. This is the output voltage variation which produces a
current in the load consisting of a steady value and superimposed
sinusoidal fundamental and harmonic values. The ripple is
expressed as the ratio of r.m.s. ripple current to the mean current,
or r.m.s. ripple voltage to the mean voltage.
Rectifier arrangements
▲ Figure 5.10
The applied and rectified voltages have the waveforms shown (figure
5.10a). The latter is half sinusoidal as is the current if load is resistive.
If the load is inductive or capacitive the current waveform shape is
altered. By suitable choice of L and C values, smoothing is
introduced. To estimate the effect of current obtained from half-wave
rectification one must consider the process for which current is used.
For electrolysis or battery-charging, current is unidirectional and used
in half-wave pulses, as shown. The effect of current is equivalent to
that of a smaller D.C. flowing at a constant value over the time of a
complete cycle. The average value of a sine wave is or 0.6365
times the maximum value but since one half of the wave is
suppressed, the average output currents ID must be taken over a
complete cycle and is thus: or 0.318 times Im (the peak value).
values to maximum or peak value for a sinusoidal half wave has not
been deduced from first principles, but forms a useful exercise and
should be attempted by a student for either a mathematical or
graphical solution.
centre-tap transformer, and is used for older valve diodes where the 2
anodes and a single cathode are accommodated in one glass
envelope. A transformer is essential, although its use is uneconomic,
since each half of the secondary is used only half the time, while
insulation for twice the voltage of a half-winding is needed. The D.C.
side can however be completely isolated from the A.C. mains with
such a transformer.
▲ Figure 5.11
the value of the required series resistor. There are two rectifier units
in series when conduction occurs during a half cycle. Thus the
average value of D.C. current required by an instrument for full-scale
deflection, i.e. to read 110 V A.C., is 10 × 10–3 A.
So
▲ Figure 5.14
For a resistive load the output current and voltage waveforms are
similar and represented by rectangular blocks. The circuit was used
widely for plating equipment as the arrangement has a higher
efficiency and a lower voltage regulation than a three-phase bridge
rectifier. It can be shown mathematically that there is a definite
relation between the D.C. output and A.C. applied voltages. This
relation is written as where N is the number of diodes
voltage.
The P.I.V. is the full peak line voltage applied across a rectifier unit
when it is not conducting. Here the ratio is:
If the conditions for the Y–B and B–R lines are considered the
appropriate diodes will be conducting and the illustrations of figure
5.15 can be studied. If all 3 voltage conditions between the lines are
considered, it is seen that a level of output voltage is reached so that,
as the voltage across any conducting diode circuit falls below this
value, the conduction ceases but D.C. continuity is maintained
through the pair of diodes in a parallel circuit across which voltage
rises. The concept of a commutating switch is useful here with each
diode circuit conducting for a sixth of a cycle, with the switch having 6
positions. In the general formula, the number of rectifying diode
circuits is 6 – 2 for each voltage cycle, one for forward and one for
reverse. Thus N = 6 and if Vm is the maximum value of applied line
voltage then:
▲ Figure 5.15
So step-up ratio
When the rectifier output voltage exceeds the battery, output current
flows into the battery to charge it. During the complementary half-
cycles, a rectifier offers no conduction and a reverse current does not
flow. Thus charging is possible and an actual effective current value
can be determined by making a graphical solution in accordance with
figure 5.16. The rectified voltage wave is plotted, the battery e.m.f. set
off and the resultant voltage waveform drawn. Instantaneous values
of current are deduced from where Rb is the battery internal
Practice Examples
5.1 A D.C. supply of 100 V is applied to a coil of resistance 10 Ω and
inductance 10 H. Find the current 0.1 s after switching on, and the
time for the current to reach 5 A (both 3 decimal places).
5.2 A resistor is connected across the terminals of a 20 μF capacitor
previously charged from a D.C. supply to 500 V. If the p.d. falls to
300 V in 0.5 min, determine the resistor value (3 significant
figures).
5.3 The field winding of a separately excited D.C. generator has an
inductance of 10 H and a resistance of 50 Ω. There is a discharge
resistance of 50 Ω in parallel with the coil. The coil is energised by
a D.C. supply at 200 V which is suddenly switched off. Find the
field current 0.04 s after the instant the supply is switched off (3
decimal places).
5.4 A resistor of 100 kΩ is connected in series with a 50 μF capacitor
to a D.C. supply of 200 V. Calculate the voltage across the
capacitor and the current at a time 0.2 s after switching on (both 2
decimal places).
5.5 The time constant of a coil is 2.0 and the inductance is 15 H.
Determine the current 0.2 s after connecting the coil to a 300 V,
D.C. mains. Find the time taken for the current to reach half its
maximum steady value (3 decimal places).
5.6 A 1 μF capacitor is charged from a D.C. supply to 50 V, then
discharged through a 5 MΩ resistor. After 5 s another 5 MΩ resistor
is connected in parallel with the first. Determine the voltage after a
further 5 s have elapsed (2 decimal places), and find the capacitor
current (1 significant figure).
5.7 A relay coil has a 1 kΩ non-inductive resistor connected across it
and the parallel arrangement is connected to a 50 V D.C. supply.
The relay data is: Resistance 2 kΩ, Inductance 100 H, Operating
current 10 mA, Release current 1 m A. Find the time taken by the
relay to (a) operate when the supply is applied (3 significant
figures) and (b) release when the supply is removed. Assume
instantaneous operation when the current reaches both the operate
and release values (4 significant figures).
5.8 A circuit has a 2 μF capacitor in series with a 100 kΩ resistor
used to control another device so that if the p.d. across the
capacitor reaches 63.2 V its instant discharge is effected and the
voltage, applied to the circuit, recharges the capacitor as before. If
the applied voltage is 100 V, find: (a) the initial current (1 significant
figure) and (b) the charging current at the instant before the
capacitor is discharged (3 significant figures). Sketch a current/time
curve for the current in the resistor throughout the charging and
discharging sequence and (c) determine the frequency of the
sequence.
5.9 A metal rectifier, a moving-coil ammeter and a thermo-junction
ammeter are connected in series across a 2 V supply. The rectifier
has a forward resistance of 20 Ω, an infinite reverse resistance and
the resistances of the ammeters are neglected. When a D.C.
supply is applied, the ammeters give identical readings. With an
A.C. supply at 50 Hz and 2 V (r.m.s.) the readings are different.
Calculate the actual meter readings (1 significant figure).
5.10 Given that a three-phase, 50 Hz supply is at 450 V between
lines and feeds a delta-star transformer with primary to secondary
turns ratio 1:5, determine the D.C. output voltage on no-load from a
suitably connected full-wave rectifier, and the ripple voltage size (1
decimal place) and frequency (1 significant figure).
It was found that the dynamos in a power house six miles
away were repeatedly burned out, due to the powerful high
frequency currents set up in them, and which caused heavy
sparks to jump through the windings and destroy the
insulation!
Credited to Nikola Tesla regarding the Colorado tests of
1898–1900
A.C. generators or alternators (as they are also called) operate on the
same fundamental principle of electromagnetic induction as do D.C.
generators. In Chapter 7, Volume 6, we introduced the basic laws of
electromagnetic induction, and considered the principles of e.m.f.
generation by dynamic induction. Generation of an alternating or A.C.
voltage is accomplished by a relatively simple arrangement but, if the
A.C. generator is to function as a machine, distinct from the D.C.
generator, it is clear that further work is needed. The advantages of
A.C. over D.C., from a power generation and applications view point,
have been discussed but if both generators are compared, the A.C.
generator wins out because it does not need a commutator (as there
is no need to invert the opposite negative half-wave cycle) and
remembering our discussion of the transformer (Chapters 1 – 3) it
can easily step up or step down voltage so that a low-voltage A.C.
current can be made into a high-voltage A.C. current and vice versa.
If it is just a relative movement of conductors with respect to the
magnetic field it is irrelevant whether the field moves and the
conductors are stationary or vice versa. Thus we have 2 operational
modes available to the machine designer but the arrangement of
moving field with fixed armature is usually preferred due to reasons to
be discussed. A rotating magnetic field which continuously changes
direction is also a key principle to A.C. motor operation. The basics of
machine construction are here considered before the main A.C.
generator theory is given.
Rotating-armature type
Rotating-field type
The stationary portion is called the stator and carries the armature
conductors while the field system moves and is called the rotor. The
magnetic field is produced by energising the pole windings with D.C.
through slip-rings from a D.C. generator (the exciter), usually driven
off the main shaft with D.C. voltage below 110 V, although 220 V or
440 V may be used. A stator arrangement has an advantage in that it
can be uniformly slotted and wound for high voltage working. As no
centrifugal forces are involved, a greater insulation thickness can be
used and there is more room for windings and end-connections than
if these were on a moving rotor. Bracing end-connections against
electro-magnetic forces, evident under S.C. conditions, is easier and
more effective. A rotor can be made compact, with a construction
allowing a low-voltage, high-current winding to withstand the large
centrifugal forces encountered. The stator core is built from
laminations insulated from each other, like the armature of a D.C.
machine, but for small A.C. generators each lamination may be a
complete ring. The rotating-field machine is built in 2 main forms
under the general category of the Salient-Pole Rotor or the Cylindrical
Rotor.
The number of poles varies from 4 to 40, usually made from steel
laminations or cast-iron with laminated pole-shoes. The pole-shoe
width is of a pole-pitch and its shape chosen to provide a sinusoidal
where of a pole pitch is slotted, leaving for the pole centre. Field
windings are made up from coils of copper strips, wound as for the
salient-pole rotor.
▲ Figure 6.2
Excitation Arrangements
Modern methods of energising the A.C. generator field are placed
under 2 headings: (1) Rotary excitation and (2) Static excitation
systems. At first the field current was obtained from a separate D.C.
generator but with development of the semiconductor rectifier, other
excitation methods were added to give desired characteristics. One
such characteristic for a marine alternator is a fast response speed to
the Automatic Voltage Regulator (A.V.R.). It is usual practice to
‘direct-on’ start large induction motors which may have start currents
comparable with the full-load current of the supply alternator. A.V.R.
controls the field current to keep output voltage constant. If output
voltage from stationary armature coils drops due to an increase in
demand, more current is fed into the rotating field coils through the
voltage regulator. This increases the magnetic field around the field
coils which induces a larger voltage in the armature coils, so the
output voltage is brought back up to its original voltage. Both
analogue and digital A.V.R. systems exist, where in the former the
terminal voltage of an A.C. generator is fed back by a feedback circuit
and the difference between the terminal voltage and a reference
voltage circuit’s output. In the latter, the output voltage of an A.C.
generator is produced through a full-wave rectifier and converted to a
digital signal by an Analogue to Digital (A/D) converter by thyristor
with field current control. The thyristor remains non-conductive until a
firing pulse is applied through the gate to cathode junction (so
controlling the firing pulses). If the anode is +ve with respect to
cathode when the pulse is applied a silicon-controlled rectifier will
conduct and stay conducting until the anode voltage goes –ve. Thus
current goes to zero. A.V.R. regulates the voltage applied to the
generator as a generator can draw a large amount of power from the
source, especially for diesel generators and avoids the changing load
causing voltage fluctuations that could damage a generator. Transient
voltage performance is important and as the voltage dip is a function
of alternator reactance, this must be accounted for, even at the
expense of machine size and cost. In relation to excitation, due to the
high inductance of the field systems of the exciter and main
alternator, large time constants may be involved. Many excitation
designs use field-forcing techniques, with the 2 main excitation
methods now considered.
The time taken to move through 2 pole-pitches = time for one cycle
giving or Hz with N the synchronous speed for a
frequency of ƒ HERTZ.
E.M.F. equation
▲ Figure 6.6
For A.C. work, r.m.s. values are required and if sine-wave working is
assumed, the relation: Form factor = may be used.
So the r.m.s. value of e.m.f./conductor = volts and as
volts.
▲ Figure 6.7
OA and OB are shown in figure 6.8. with KD always less than 1. If the
same number of conductors for each type of winding is considered,
for a Distributed Winding, the e.m.f. per phase = KD × e.m.f. for a
concentrated winding, or Eph = 2.22 × KD × Zph × Φ × ƒ volts.
Terminal voltage = .
The resultant e.m.f. = AE and angle AOE = nα, if there are n slots per
pole per phase.
Now
and
or
Example 6.3. From example 6.2, find the no-load terminal voltage of
a three-phase, 4-pole alternator having 2 slots per pole per phase
with 2 conductors per slot. The flux per pole is 0.14 Wb, the machine
speed 1500 rev/min and the connection of the phases is in star (3
significant figures).
As before
Terminal voltage =
The two sides of the coil are not 180° apart, the span being less than
a pole-pitch. From phasor diagram (figure 6.10c), the resultant e.m.f.
is AC or = 2AB and the Pitch Factor, Ks defined as the ratio of
Thus
The effect of the Pitch Factor is observed if the span is 140° or less,
i.e. θ = 40° or more. For θ = 40° Ks = 0.94. The term ‘chorded’ is
used in connection with coils pitched less or greater than the pole-
pitch. Occasionally the term Winding Factor is used to include the
Distribution and Coil-span Factors.
Since the voltages of the coils are out of phase by 30° (figure 6.10)
the resultant is given by:
internal angle.
Note
Here
Terminal voltage = .
▲ Figure 6.11
▲ Figure 6.16
The same result is obtained by fixing poles axially and skewing the
armature conductors. Method (2) is less favoured than (1) because it
does not permit easy modification once a machine is built.
Stator Windings
Mention was made of the types of slots into which stator or armature
conductors are placed. From a construction view, ‘open’ slots are
preferred (figure 6.17), one can preform and insulate the coil side,
made of one or more conductors, inserted into the slots. The main
‘open’ slot disadvantage results in teeth which encourage flux to
‘stray’ as it crosses the machine air-gap. Local magnetic leakage
from the slot is high and leakage reactance is low. Flux ‘jumps’ tooth
to tooth so a ‘ripple’ frequency is generated (figure 6.17). The ‘closed’
slot overcomes this effect but makes winding hard and gives the
machine a high leakage reactance.
▲ Figure 6.17
Types of windings
▲ Figure 6.18
▲ Figure 6.20
From
so 18 teeth
Thus
Also
then
Here and
or
▲ Figure 6.21
(refer to
figure 6.21).
Since regulation is influenced by P.F. and load current, these are
specified when stating percentage regulation. Due to magnetic circuit
iron hysteresis, a rise of p.d. when load is thrown off will be below the
fall in p.d. when a load is applied. One method of standardised
regulation is defined by the rise in p.d. when load is thrown off,
sometimes termed regulation ‘up’ or ‘down’.
(1) Armature Resistance. The voltage drop IR, caused by this factor,
is always small and usually neglected. It is proportional to the
current causing it and is in phase with the current. For the basic
phasor diagram, current is taken as the reference since the build
up of the diagram follows the procedure for a simple series circuit.
(2) Armature Reactance. The voltage drop due to this factor is
caused by individual inductive effects associated with the stator
winding. Any A.C. winding has self-inductance when carrying
current, but the consequent reactance is often attributed to the joint
reactance of individual parts, so mention is made of slot-reactance,
end-connection reactance, etc. Overall reactance is proportional to
current and is in quadrature with it. This reactance is one
constituent part of the Xs shown on the phasor (figure 6.22).
▲ Figure 6.22
or Generated voltage
▲ Figure 7.1
Needle rotation shows that a rotating magnetic field results from the
combined effect of the 3 separate single-phase alternating coils’
magnetic fields. In practice the 3 single-phase windings are laid out
along the stator circumference as described for the alternator. By
choosing a suitable coil pitch, a machine can be wound for any
number of poles, provided the number is even. The magnetic field
rotation speed depends on the number of poles and the supply
frequency. Explanations of the rotating magnetic field effect are here
given by 3 different methods. One alone is likely to be sufficient, but
comprehension of all 3 will allow a better understanding of armature
reaction effects when these are introduced.
▲ Figure 7.2
▲ Figure 7.3
current in the Yellow phase falls to zero, while the Blue phase rises to
maximum value and is negative.
The resultant magnetic field is shown in figure 7.4b and its axis will
have rotated through 30°. For Instant 3, the Blue phase current will be
at negative maximum. The Red and Yellow phases current will be +ve
but half of maximum value. The resultant magnetic field is as shown
(figure 7.4c) and its axis will rotate through a further 30°.
▲ Figure 7.4
On examining steps (a), (b) and (c) we observe that the three-phase
currents flowing through coils, suitably displaced from each other by
120° (electrical), produce a resultant magnetic field which rotates in
time and in phase with the currents, i.e. rotating at a speed decided
by the frequency, giving rise to the synchronous speed, as seen if
alternative methods are considered.
Thus,
ΦH = ΦR – ΦY cos 60 – ΦB cos 60
= Φm sin ωt – Φm sin(ωt – 120) cos 60
– Φm sin(ωt – 240) cos 60
= Φm[sin ωt – cos 60{sin(ωt – 120) cos 60}
+ sin(ωt – 240)]
= Φm[sin ωt – cos 60 sin(ωt – 180)*
by any one phase winding. If θ is the angle the resultant field makes
with the horizontal, then:
θ = ωt = 2πft
Method 3. By Deduction of Magnetomotive Force or Ampere-Turn
Field-Producing Patterns.
▲ Figure 7.6
(c) Instant when the currents in Rph and Yph are +ve and half the
maximum value.
▲ Figure 7.7
▲ Figure 7.8
Thus for figure 7.9a if, e.g. current in the red phase is maximum, the
m.m.f. and flux wave is symmetrically distributed across that phase
winding and maximum flux-linkages occur. Similarly for figure 7.9b
when current is zero the m.m.f. or flux distribution is such as to have
its zero value at the centre of the winding – zero flux-linkages occur,
i.e. peak value is displaced by 90°. Reference is made to this fact
when armature reaction effects are considered.
▲ Figure 7.9
Armature reaction
▲ Figure 7.11
the main poles. The armature m.m.f. is entirely magnetising but the
flux increase is not as big as the decrease in Case 2, due to iron
circuit saturation effects. The resulting flux increase increases the
generated voltage.
▲ Figure 7.12
▲ Figure 7.13
▲ Figure 7.14
Thus
▲ Figure 7.15
Since the ‘on-load’ or resultant flux is the original flux altered by the
armature-reaction flux, the e.m.f. E0 as originally generated is
considered to be weakened and retarded by an internally generated
e.m.f. Eb as shown. The final generated e.m.f. is E1. Since Eb is
proportional to armature flux which is proportional to current I, the
effect is similar to a reactance voltage drop, in quadrature with
current. The machine is credited with Xs – a larger reactance than the
leakage reactance XL, the extra amount Xa taking care of the
armature reaction e.m.f. The term ‘synchronous reactance’, Xs is now
treated in depth and must be appreciated by the reader, and is shown
on the phasor diagram.
The phasor diagram is drawn for one phase only, although the
armature-reaction effect is due to the combined action of all the
phases in a polyphase machine. From figure 7.7 it was shown that
the armature m.m.f., due to all 3 phases, produces its maximum
value, relative to any one phase, when the current in that phase is a
maximum. It is represented by a phasor in phase with the current in
that phase. Generated e.m.f. is produced by a change in flux linked
with the associated coils, and the e.m.f. phasors are shown lagging
fluxes by 90°.
▲ Figure 7.16
The voltage generated, when making the S.C. test, drives current
through the armature impedance. For the full-load current value IL the
field current is IfL as shown. From the O.C.C., for IfL a voltage of VL
generated. A current of IfL in the field gives a voltage of VL generated
and an armature current of IL results.
▲ Figure 7.17
Then
Synchronising torque
▲ Figure 7.18
busbars
The XS/ph of the busbar system being negligible.
Here
Synchronising power
Synchronising power = or =
newton meters.
Original condition.
Additional load.
Final condition.
By deduction:
Practice Examples
7.1 A 4-pole alternator, on open circuit, generates 200 V at 50 Hz
when its field current is 4 A. Determine the generated e.m.f. at a
speed of 1200 rev/min and a field current of 3 A, neglecting
saturation of the iron (3 significant figures).
7.2 A single-phase alternator has an effective resistance of 0.2 Ω and
a synchronous reactance of 2.2 Ω. Find the generated e.m.f. when
the load current is 50 A at a terminal voltage of 500 V. The load
operates at 0.8 P.F. (lagging) (3 significant figures).
7.3 Find the synchronous impedance and reactance of an alternator
in which a given field current produces an armature current of 250
A on S.C. and a generated e.m.f. = 1500 V on O.C. Armature
resistance is 2 Ω. Calculate terminal voltage in kV when a load of
250 A at 6.6 kV and 0.8 P.F. (lagging) is switched off (2 decimal
places).
7.4 A 250 kVA, 3000 V, three-phase, star-connected alternator has a
synchronous reactance of 20 Ω per phase. The armature
resistance measured between two terminals is 2.8 Ω. Determine
the value to which the terminal voltage will rise when full load at (a)
0.8 P.F. (lagging) and (b) 0.9 P.F. (leading) is switched off (both 4
significant figures).
7.5 A marine type 9 kVA, 230 V, single-phase alternator has an
armature resistance of 0.25 Ω. The results of the O.C. and S.C.
tests are as follows:
Principle of Operation
In its basic form the machine is known as a squirrel-cage or simply a
cage motor. The theory of the rotating magnetic field was introduced
in Chapter 7 and it is now appreciated how, if a polyphase motor’s
stator is suitably wound with an appropriate number of conductors
and energised from a polyphase supply, a rotating magnetic field is
produced. It is the effect of this field on the motor’s rotor which is
considered next to understand the operational theory. It can be
shown the rotating magnetic field will drag around a rotatable solid
iron cylinder when placed concentrically in the field. For efficiency,
copper conductors are embedded in the face of the cylinder to yield 2
forms of rotor known as (1) the cage and (2) the wound-rotor types.
The cage type is more simply constructed, consisting of copper bars
inserted without insulation into slots spaced evenly around the
circumference of a rotor built from iron laminations. Bars are
connected to copper rings at each end of the rotor and winding and
looks like a cage – hence the name. The winding consists of single
turns connected in parallel. The wound-rotor construction employs
insulated conductors placed in coil form, in a similar way to that of the
stator. There are thus 3 insulated phase windings, correctly
positioned and spaced relative to each other. Phase windings are
usually star-connected and the 3 free ends are brought out to slip-
rings insulated from the shaft. Contact is made to the rings with
brushes mounted on a brush-arm and the external circuit completed
through 3 star-connected variable resistors. Control gear, built into
the starter, allows resistors to be cut out and the slip-rings ‘shorted’.
Thus the winding, when the motor runs, is short-circuited and
resembles the cage winding except there are more turns per phase
coil. The theory set out as follows assumes conditions for a wound-
rotor machine.
If the field is considered to move, the relative cutting between flux and
rotor conductors induces e.m.f.s in the rotor, producing currents in the
direction shown as when the ‘right-hand generator rule’ is applied,
conductors move in the direction opposite to that as shown for the
flux and the latter considered to be stationary. Currents circulate in
paths provided by the end-rings and the conductors under the
opposite stator poles. Applying first principles for the action between
the flux and rotor currents, a force results in the direction shown, i.e.
the rotor conductors follow the rotating field because of the torque
produced. The rotor starts to revolve and accelerates up to speed N2
approaching the synchronous speed – the speed of the rotating field
N1. There is always a difference in speed between N1 and N2;
otherwise there is no relative cutting, no rotor e.m.f.s induced and
hence no rotor currents or torque.
▲ Figure 8.1
As a fraction we have
Fractional slip
Or percentage slip
When a motor ‘runs light’, i.e. unloaded, the torque is only that
required to overcome friction and windage so the speed is nearly
synchronous and the stator draws little current from the supply. As
load torque is increased, i.e. the motor is loaded, speed falls slightly
causing an increase in the relative cutting of the rotor conductors by
the field, so rotor e.m.f. and current are increased. This effect gives
the increased torque required and speed is determined by this
condition when power developed equals the power required. The fall
in speed from no-load to full-load is about 4–5% for small motors and
1.5–2% for large motors (with greater inertia). The speed-load
characteristic is similar to the D.C. shunt motor.
and
and .
(2) E.M.F. The rotating magnetic field cuts the stator and generates
an e.m.f. given by the formula E1 = 2.22 KD1 KS1 Zph1 Φf1 volts.
Neglecting voltage drops due to resistance and reactance E1 can be
considered as a back e.m.f. approximately equal to the supply
voltage V.
For a stationary rotor the rotating field cuts the rotor at the same
speed as the stator and an e.m.f. E2 is induced where = 2.22 KD2
KS2 Zph2 Φf2 volts. Here f2 = ƒ the supply frequency. With the rotor
revolving the induced e.m.f. varies depending on the rotor frequency
since
Rotor reactance per phase on full load sXph2 = 0.04 × 1.5 = 0.06
Ω
Rotor current
Relation between rotor loss, rotor input power
and rotor output
The power taken from the supply creates a rotating magnetic field or
flux (as in the transformer analogy). Copper and iron losses occur in
the stator winding, so the power put into the air-gap flux or the stator
output = stator input – stator losses. As no losses occur in the air-gap
we assume the stator output power is the rotor input power thus:
newton metres.
(a)
∴ Rotor copper loss = s × Rotor input
Since
(b)
Thus
= 492 × 3 watts
Torque conditions
▲ Figure 8.3
We thus have
Since then:
where C is a constant.
starting, torque varies inversely with slip at low speeds. Thus when
slip is high, torque is small and the relation explains the unstable
right-hand side of the torque/speed curve shown in figure 8.1. At high
speeds, i.e. small slip, rotor frequency is low and the reactance is
small compared with the resistance. Again with reference to the
to slip and this explains the stable left-hand side of the characteristic
(figure 8.3).
or R2 = sX2.
The above shows that maximum torque occurs when the slip .
▲ Figure 8.4
For figure 8.4, the following points are considered for load torque. For
line (b) and curve R21, starting torque produced by the motor is
greater than the load torque, so the motor starts and accelerates the
load. The machine runs up to speed, operating at about 4% slip. For
line (a) and curve R21, the load requires a greater starting torque than
that produced by the motor which cannot thus start and accelerate
unless load torque is reduced. However, if resistance is introduced
into the rotor circuit to operate on curve, R21, starting is possible and
the motor will run up to speed and operate at about 6%.
Impedance
= 0.268 or 26.8%.
Synchronous speed
∴ Motor speed = 1500 – 0.268 × 1500 = 1500 – 402
= 1098 rev/min.
Since the motor functions like a transformer, with the stator as the
primary and the rotor as the secondary, the phasor diagram will be
similar to that of the transformer and the associated reasoning can be
applied, provided the following points are noted.
Figure 8.5a shows the motor circuit with the rotor open-circuited, the
condition resembles a transformer on ‘no-load’. Figure 8.5b is drawn
for rotor standstill conditions, i.e. rotor locked and circuit complete, a
condition similar to a transformer ‘on-load’ and phasor relations, as
discussed earlier for the transformer, apply. Thus for the ‘locked rotor’
condition, the main flux generates stator and rotor e.m.f.s of E1 and
E2 respectively. I0 is the no-load current consisting of components Im
and Iw. Im is the current component which produces the ampere-turns
resulting in the main flux Φ, and Iw is the energy component supplying
the iron loss. The stator resistance voltage drop is I1R1 and the
reactance voltage drop is I1X1 and these when added by phasors with
the back e.m.f. E1 equal the supply voltage V. The rotor e.m.f. E2
produces a rotor current I2 which is limited by the resistance R2 and
reactance X2 of this circuit. The rotor secondary resistance and
reactance voltage drops, I2R2 and I2X2 respectively, by phasor
addition equal the induced e.m.f. E2 or E2 = I2Z2.
▲ Figure 8.5
When the rotor rotates, we get the conditions shown by the phasor
(figure 8.5c). Here the secondary e.m.f. is now reduced to or sE2
and the secondary reactance falls to or sX2. Since rotor resistance
is unaffected by slip, R2 is unchanged and the P.F. rises as the sX2
value falls. As mentioned under point (2), the P.F. is low if the motor
runs light since component I0 is large in relation to . When a motor
is loaded I2 and hence increases I0 being constant, the result is that
I1 rises and the P.F. condition improves.
Then
▲ Figure 8.6
we have:
Comparing this with the expression AB = K sin φ2 it is seen the locus
of I2 is on a circle with a diameter of constant value at right angles to
E2 as shown by figures 8.7a and 8.7b. is the reflection of I2 in the
primary or stator circuit. Thus lies on a circle of appropriate
diameter. Again, since the primary current is the phasor sum of I0 and
, the relevant parts of the primary diagram can be adapted to give
the Circle Diagram. It is unnecessary to know the diameter since the
circle can be built up from current values obtained from simple motor
tests. The diagram, once deduced, may be used for performance
assessment and is illustrated by example.
▲ Figure 8.7
Testing procedure
A P.F. quadrant is useful for ‘laying off’ and measuring P.F.s and the
procedure given here. An engineering drawing can be a highly
stylised representation of an engineering idea, where ‘laying off’
refers to measuring off a set distance. Along the vertical axis (figure
8.9), starting from point 0, a scale of 10 units is drawn, which is of
convenient length to give accuracy and a quadrant drawn. Scale the
vertical 0 to 1. For example, if a line drawn horizontally through the
0.2 mark to cut the quadrant and this point of intersection is joined to
the origin, the line obtained must subtend with OV an angle whose
cosine is 0.2.
No-load Test. This test gives I0 and φ0. Thus no-load P.F. cos
where P0 = the no-load three-phase power. To start the
This diagram (figure 8.9) aids P.F. estimation for any load current and
the optimum P.F. condition. It can be extended to estimate power
output, losses, slip, etc. Consider any load-current value OA. AL will
be the power component of OA and the input power to the motor is
× AL. This input power supplies the output power developed at
the motor shaft, and the machine losses: the iron (hysteresis and
eddy current) losses, the rotational (friction and windage) losses and
the copper (stator and rotor) losses.
For the locked-rotor test all input power is converted into losses, i.e.
copper and iron losses. Here there is no rotational loss but since the
rotor frequency is now at full ‘mains’ value, it is assumed that
constant loss component EH, under this condition, is made up of the
iron losses, i.e. rotational loss is nil but the rotor iron loss increases to
replace it. Component AsE is a measure of the rotor and stator
copper losses under the locked-rotor condition. Next consider any
stator current value such as OA. Since the stator current is
proportional to the rotor current then
Thus a line joining B to As cuts off the copper losses (to scale) for the
current considered KG, to scale, is a measure of total copper losses.
Thus on no-load
Standstill test
Note. The solution is drawn with a 10 mm = 10 A scale. This is not
apparent in printed form due to photographic reduction. Students
should draw this solution for themselves.
Join BAs. Bisect this line and produce bisector to give point M on BD.
Draw the circle. Produce MS to cut the circle at T. Drop TU – this is
the output component, with TU = 73 mm = 73 A and output power
.
Join OT. The estimated line current given by OT is 128 mm, i.e. 128 A
at 0.73 P.F. (lagging).
Torque Line. Further work on the circle diagram (figure 8.10) allows
the determination of other values for any machine. To draw the
Torque line, stator and rotor copper losses are separated. For the
locked-rotor test, since voltage is reduced, iron losses are negligible
and the test is assumed to give the copper losses – deduced for the
full voltage condition. Furthermore, if Rs is the stator resistance per
phase then the stator copper loss during the test is and, Rotor
copper loss = .
▲ Figure 8.10
data can be obtained from the circle diagram such as estimated slip,
overall efficiency, optimum P.F., etc. The following example shows
how these can be deduced and the student should again undertake
the practical solution themselves.
No-load Test.
Applied voltage 440 V. Line current 18.25 A. Input power 3.19 kW.
Locked-rotor Test.
Applied voltage 110 V. Line current 55.2 A. Input power 3.17 kW.
Construct the circle diagram and find (a) the line current, (b) P.F., (c)
full-load percentage slip and (d) the efficiency. At standstill rotor and
stator losses are equal.
▲ Figure 8.11
Using the P.F. quadrant, draw in the line for an angle whose cosine is
0.23. Next on this line measure off OB = 18.25 mm.
Using the P.F. quadrant draw in the OAs line by adjusting the locked-
rotor current to full voltage value, i.e.
Join As to B giving the output line, bisect this so the bisector cuts BD
at M. M is the centre of the circle, draw this in. For a 56 kW output the
power component .
From the output line erect two verticals X and Y = 73.5 mm and draw
the parallel to cut the circle at point A. Then OA = 114 mm or line
current = 114 A.
Practice Examples
8.1 The input to a three-phase induction motor is 50 kW. The stator
losses amount to 0.8 kW. Calculate the rotor copper loss per phase
(3 significant figures) and the total mechanical power developed in
kW, if the slip is 3% (1 decimal place).
8.2 A 500 V, 6-pole, 50 Hz, three-phase induction motor develops 20
kW inclusive of mechanical losses, when moving at 990 rev/min,
and 0.85 P.F. (lagging). Calculate (a) the percentage slip, (b) the
frequency of the rotor e.m.f. (1 decimal place), (c) the rotor copper
loss (3 significant figures), (d) the input to the motor in kW if the
stator loss is 2.5 kW (1 decimal place) and (e) the line currents (2
decimal places).
8.3 A 4-pole, three-phase, 60 Hz induction motor is rated at 15 kW.
Its full-load slip is 4%. The stator loss is measured as 950 W and
the mechanical rotor losses = 830 W. Find the rotor copper loss in
kW (2 decimal places) and machine efficiency (2 significant
figures).
8.4 A 6-pole, 50 Hz, three-phase, wound-rotor induction motor
running on full load develops a useful torque of 162.7 Nm. A
moving-coil ammeter in the rotor circuit fluctuates at 90 complete
‘beats’ per minute. The mechanical torque lost in friction is 13.56
Nm and the stator losses are 750 W. Calculate (a) speed of motor
(3 significant figures), (b) brake power input (3 decimal places), (c)
rotor copper loss (watts) (1 decimal place), (d) motor input in kW (2
decimal places) and (e) motor efficiency (2 significant figures).
8.5 A 75 kW, 440 V, three-phase, wound-rotor induction motor has a
rotor resistance and standstill reactance of 0.02 and 0.27 Ω/ph
respectively. The stator to rotor phase turns ratio is 3:1 and the
stator windings are connected in delta.
If the motor is started by means of a resistance starter with a
resistance of 0.25 Ω/ph, calculate the current taken by the motor
from the supply (a) at start (3 significant figures) and (b) under full-
load running conditions (1 decimal place) if full-load slip is 4%.
What would be the current taken from the supply if the motor was
accidently started with the starting resistance in the ‘run’ position (3
significant figures)? Neglect the no-load current, and stator winding
resistance and reactance. Assume the rotor to be star-connected.
8.6 Full-load torque is obtained with a 440 V, 12-pole, 60 Hz, three-
phase, delta-connected induction motor, when driving a main
circulating water pump at a speed of 576 rev/min. The slip-ring
rotor has a resistance of 0.02 Ω/ph and standstill reactance of 0.27
Ω/ph. Calculate (a) the ratio of maximum to full-load torque and (b)
the speed at maximum torque (revs/min) (1 decimal place).
8.7 A 440 V, three-phase, 10-pole, 50 Hz, boiler induced-draught fan
motor has a delta-connected stator winding and a wound rotor. The
resistance per phase of the rotor winding is 0.018 Ω and the ratio of
the stator conductors per phase to rotor conductor per phase is 4:1.
If the motor develops maximum torque when running at a speed of
540 rev/min, calculate the rotor current (3 significant figures) and
P.F. (3 decimal places) for the machine when running at full load,
with a slip of 4% and slip-rings short-circuited. Calculate the
developed full-load output power in kW (3 decimal places),
assuming mechanical losses are negligible. What starter resistance
per phase must be connected into the rotor circuit to give maximum
torque at start (3 decimal places)? Neglect stator winding
resistance and reactance.
8.8 A 37 kW, 12-pole, three-phase, 50 Hz squirrel-cage induction
motor as used aboard a tankship for driving a main circulating
water pump, gave the following test results:
No-load Test.
Applied voltage 440 V. Line current 19 A. Input power 2.17 kW.
Locked-rotor Test.
Applied voltage 100 V. Line current 70 A. Input power 3.88 kW.
The ratio stator/rotor copper loss is 4:5. Construct a circle diagram
and find for full-load conditions: (a) Input line-current (3 significant
figures) and P.F. (2 decimal places), (b) percentage slip (2 decimal
places) and (c) percentage efficiency (1 decimal place).
8.9 During tests on a three-phase, 440 V at 60 Hz, 8-pole, 22 kW
induction motor, the following figures were obtained:
No-load Test.
Applied voltage 440 V at 60 Hz. Input line current 10.5 A. Input
power 1.82 kW.
Locked-rotor Test.
Applied voltage 113 V at 60 Hz. Input line current 50 A. Input power
3.92 kW.
Estimate for full-load conditions: (a) Input line current (3 significant
figures) and P.F. (1 decimal place), (b) percentage slip (2 decimal
places), (c) percentage efficiency (1 decimal place) and (d)
developed torque of the motor in Nm (2 decimal places). For this
motor the rotor copper loss under standstill conditions was found to
be the same as the stator copper loss.
8.10 Draw the circle diagram for a three-phase, 415 V, 37 kW
induction motor from the following test results:
No-load Test.
Applied voltage 415 V. Input current 40 A. Input power 3.6 kW.
Locked-rotor Test.
Applied voltage 83 V. Input current 80 A. Input power 3.45 kW.
Under standstill conditions rotor copper loss and stator copper loss
are equal. From the circle diagram deduce (a) the full-load current
(1 significant figure) and P.F. (1 decimal place), (b) the full-load
efficiency (2 significant figures), (c) maximum output in kW (1
decimal place) and (d) the ratio of full-load torque to maximum
torque.
‘O tell me, when along the line
From my full heart the message flows,
What currents are induced in thine?
One click from thee will end my woes’.
Through many an Ohm the Weber flew,
And clicked the answer back to me,
‘I am thy Farad, staunch and true,
Charged to a Volt with love for thee’.
Credited to James Clerk Maxwell regarding telegraphy
A.C. Generators
A.C. generators can be connected in parallel because they control
each other electrically by a circulating current which keeps them in
phase. Series connection of A.C. generators is not practicable unless
the machines are coupled together mechanically. Without such
coupling, since no provision for a circulating current exists, it is not
possible for machines to control each other. As series running is not a
feasible arrangement it will not be considered here.
(1) The voltage of the incoming machine must equal that of the
busbars.
(2) The frequency of the incoming machine must be the same as that
of the busbars.
(3) The e.m.f. of the incoming machine must be in phase with the
busbar voltage.
(4) The phase sequence of an incoming machine must be similar to
the busbars, and the switching arrangements made so that like
phases of the machine and busbars are connected when the
paralleling procedure is completed.
▲ Figure 9.1
If conditions for the busbars and incoming machine are represented
by the figure 9.1 phasors, synchronising requirements are seen, i.e.
(1) the respective voltage phasors must be equal, (2) phasors must
rotate at the same speed and frequency, (3) they must be in phase
with each other, i.e. corresponding line to line voltages must reach
their positive maximum values at the same instant and (4) phasors
must rotate in the same direction–same phase sequence. On land
switchboard installations are provided with a synchronising panel of
voltmeters, frequency meters and a synchroscope. In marine work it
is common to add ‘synchronising lamps’ as well.
The synchroscope
Parallel operation
With the motor load, reactive power is reduced by: –200 – (–173.2) =
–26.8 kVAr
Thus the motor reactive power rating = 26.8 kVAr (leading), i.e. +26.8
kVAr
Machine No. 2
Active power =
▲ Figure 9.2
Original apparent power = 125 kVA cos φ = 0.8 and sin φ = 0.6
Apparent power
Active power = 50 kW
Apparent power =
With the lagging kVAr of one machine made larger than the total
lagging kVAr, the kVAr of the other machine must be in anti-phase to
produce the final result. Thus as No. 1 alternator operates at a
lagging P.F., No. 2 alternator must operate with a leading P.F.
An increased No. 2 input makes it take more load so its speed settles
to that decided by the governor-actuated throttle-valve opening.
Meanwhile machine No. 1, now relieved of load, accelerates to a new
speed (frequency) determined in the last stage by the overall system
load. IS is a short-duration circulating current, created by transient
conditions arising from controls adjustment. Once the overall
paralleled system settles down, operating conditions are similar to
those found originally, except that I1, I2, cos φ1 and cos φ2 have new
values.
Load sharing
▲ Figure 9.6
▲ Figure 9.8
Let the increased load share taken by machine No. 1 be X kW, so No.
2 takes (Q–X) kW.
Hence
Example 9.4 Two large identical alternators each rated 1.25 MVA with
0.8 P.F. (lagging) supply a load in parallel. The governor setting on
the prime-mover of machine No. 1 drops from 50 Hz on no-load to 48
Hz on full load. The second machine (No. 2) drops from 50 to 47 Hz.
How will they share a load of 1.5 MW?
Machine No. 1 drops 2 Hz for 1000 kW (1250 kVA at 0.8 P.F.), i.e.
0.002 Hz per kW.
Machine No. 2 drops 3 Hz for 1000 kW (1250 kVA at 0.8 P.F.), i.e.
0.003 Hz per kW.
Here the load increase, i.e. from no-load to full load Q = 1500 kW
900 = 600 kW
▲ Figure 9.9
Total active load = 1000 kW cos φ = 0.8 (lagging) and sin φ = 0.6
Apparent power
∴ Reactive power
Machine No. 2
Active power = 1000 – 600 = 400 kW
∴ Apparent power
Apparent power
(lagging).
Operating action
If the motor is loaded, the rotor drop back further to angle φ2. The
resultant voltage is then ER2 and the current increases to I2, lagging
as before, on V by angle φ2. Power input is now VI2 cos φ2 and α2
adjusts itself until sufficient power is drawn from the supply to
manage the load. The phasor diagram is drawn from the busbar point
of view and shown in figure 9.12.
To the basic voltage phasors are added the voltage drops in the
motor due to resistance and synchronous reactance. Here angle α is
the ‘angle of retard’. The total mechanical power developed by the
motor is E2 I2 cos(φ1 – α2) which to a first approximation is expressed
as V2 I2 cos φ2. Power available at the shaft is less than this due to
the iron, friction and windage losses. An increased load torque
causes angle α to increase, meaning a larger current. At the same
time φ increases and the P.F. cos φ diminishes. For small φ values I
increases at a greater rate than cos φ decreases, so the power
developed increases. A value of φ is reached at which I increases at
a lower rate than cos φ decreases, so a maximum power condition is
obtained. Thus, once the current increase is countered by a P.F.
decrease, power starts to fall and, if the load torque required is
increased further, the motor will pull out of step and stall. Under
normal operating conditions if P is the total mechanical power
developed in watts W, V the supply voltage, I the motor current, cos φ
the motor P.F. and Ra the effective motor resistance then P = VI cos
φ – I2 Ra.
▲ Figure 9.12
Example 9.6. A 500 V, synchronous motor develops 7.5 kW, with 0.9
P.F. (lagging). The effective armature resistance is 0.8 Ω. Iron and
friction losses are 500 W and the excitation loss 800 W. Find (a) the
motor current, (b) the input power and (c) the overall efficiency (all 1
decimal place).
= 8.5 kW
Overall efficiency
Phase voltage
or E2 = 5570 V
Input power
= 762 kW.
Starting
▲ Figure 9.13
If the rotor is run at synchronous speed, the opposite stator and rotor
poles ‘lock-in’ and the motor continues to run as considered earlier
under the heading of Operating Action. Thus, to operate, the motor
must be brought up to speed, by some external means and
synchronised onto the supply as was the alternator. There are various
practical methods of running a motor up to speed and the following
are among the most usual.
(1) An A.C. or D.C. pony motor (a small motor that gets a larger
motor started) is coupled to the main machine of sufficient power to
drive the latter up to slightly above synchronous speed, running up a
synchronous motor. In one arrangement the D.C. exciter is used as
the pony motor to drive the main machine above synchronous speed.
It is then switched off and reconnected as a D.C. generator, to supply
the main motor’s field. As the latter slows down and passes through
synchronism, paralleling is affected and the load to be driven is then
taken up.
Consider a 3 kV system.
Induction Motors
Induction motors are included under the heading of ‘operation’, as
little has been said about their starting and control, and consideration
is now given to their operating requirements. As the three-phase
induction motor is the A.C. machine invariably used in marine
applications, attention is given to usual marine operational practice.
Starting
Cage-type motors are the most common and are considered first.
Since the torque produced is proportional to applied voltage squared,
direct application of line voltage has some advantages. Unlike D.C.
motors, which, under standstill conditions, offers low resistance to the
line voltage, A.C. motors have enough inherent impedance to limit
current to say 4–7 times the full-load current value. Thus a rheostatic
starter (which during starting cuts out successively one or more
resistors in the rotor circuit), as used for D.C. motors, is unnecessary
and A.C. motor-starting methods, for cage machines, takes 3 forms.
British practice rarely uses the star-delta starting method for marine
work due to the interval between change-over; the motor is
disconnected from the supply and any induced e.m.f. falls in value
and frequency. When supply reconnection is made, transient currents
flow which may have peaks larger than those resulting from direct-on
switching. High current conditions can occur and yet torque is of
Full-load input
Figure 9.14 shows the typical main circuit scheme for such a marine
auto-transformer starter type. An electrically controlled switch is used
for switching the power circuit, which is similar to a relay, except that
it is used with higher current ratings. With operation of the ‘on’ push-
button–auxiliary circuits not shown, contactors A and B close first.
The motor receives a reduced voltage depending on the transformer
tapping used. Time-lagged switches in the auxiliary contactor closing-
coil circuits are fitted and after a short period, contactor B opens. The
motor now receives an increased voltage with a section of the
transformer winding used as a series reactor. After a further time
interval, contactor C closes and contactor A opens. Thus the motor is
connected to the supply direct and the transformer disconnected.
Circuit protection for over-current and under-voltage is built into
contactor C since it is the main circuit or ‘running’ contactor.
▲ Figure 9.14
▲ Figure 9.16
▲ Figure 9.18
On starting, the rotating magnetic field links mainly with the outer
cage conductors as the rotor frequency is the supply frequency and
the large reactance of the inner, more highly inductive cage limits
current. The outer cage high resistance is thus more operative and
the corresponding torque higher.
Practice Examples
9.1 A synchronous motor with a power consumption of 50 kW is
connected in parallel with a load of 200 kW having 0.8 P.F.
(lagging). If the combined load has 0.9 P.F. (lagging), what is the
leading reactive kVA supplied by the motor (1 decimal place) and at
what P.F. is it working (3 decimal places)?
9.2 Two 3.3 kV, star-connected alternators when operating in parallel
supply the following loads: (a) 800 kW at unity P.F., (b) 600 kW at
0.707 P.F. (lagging). The current of one machine is 150 A at 0.85
P.F. (lagging). Find the current output (3 significant figures) and the
other machine’s P.F. (2 decimal places).
9.3 A ship’s electrical system is supplied by 2 identical three-phase,
star-connected alternators operating in parallel. The machines
share a total load of 1000 kW at 440 V, 0.8 P.F. (lagging). If the kW
loadings of the machines are equal and one machine supplies a
1000 A lagging current, find (a) the current supplied by the second
machine (3 significant figures), (b) each machine’s P.F.s (3 decimal
places) and (c) the reactive current circulating between two
machines (3 significant figures).
9.4 Two alternators A and B operate in parallel. When tested
individually, the frequency of machine A falls from 50 to 48.5 Hz
when the load is 150 kW, while machine B falls from 50 to 48.5 Hz
when the load is 220 kW. If the total load is 200 kW, find the
frequency of the paralleled system (2 decimal places), and the load
on each machine (2 and 3 significant figures respectively).
9.5 A 15 kW 440 V, three-phase star-connected synchronous motor
has an armature of 0.4 Ω effective resistance per phase. It gives
full-load output at 0.9 P.F. (leading). If the iron and friction losses
are 500 W, find the armature current (1 decimal place).
9.6 A 220 V, single-phase, synchronous motor has a synchronous
impedance of 5 Ω and an effective armature resistance of 0.5. Ω.
Calculate (a) the minimum armature current (2 decimal places), (b)
the generated e.m.f. (3 significant figures) and (c) angle of retard
for a total load of 5 kW (in ° and '), which includes the motor’s iron
and friction losses.
9.7 A three-phase, 440 V, 37 kW induction motor has 82% efficiency
operating at 0.85 P.F. (lagging). When ‘direct-on’ started the motor
takes a current 6 times full-load current and produces a torque =
1.5 times full-load torque. Calculate the current taken from the
supply (2 decimal places), and the ratio of starting to full-load
torque if the motor is started with an auto-transformer with a 75%
tapping.
9.8 Find the ratio of starting to full-load current for a 15 kW, 415 V,
three-phase, induction motor with a star-delta starter, given full-load
efficiency is 85%, the full-load P.F. is 0.8 (lagging), the short-circuit
current is 60 A at 220 V and the magnetising current negligible.
9.9 A 440 V three-phase wound-rotor induction motor has a rotor
resistance and standstill reactance of 0.02 and 0.27 Ω per phase
respectively. The stator to rotor phase turns ratio is 3:1 with the
stator windings connected in delta. If the motor is started with a
resistance starter of resistance 0.25 Ω per phase, calculate the
current taken by the motor from the supply (a) at starting and (b)
under full-load running conditions if the full-load slip is 4%. What
would be the current taken from the supply if the motor was
accidently started with the starting resistance in the ‘run’ position?
Neglect the no-load current, resistance and reactance of the stator
windings (3 significant figures).
9.10 A 6-pole, three-phase induction motor on full load develops a
useful torque of 162.4 Nm and the rotor e.m.f. makes 90 complete
cycles per minute. Calculate the power in kW (2 significant figures).
If the frictional mechanical torque lost is 13.6 Nm, find the rotor
copper loss, the input to the motor in kW (2 decimal places) and
the efficiency (1 decimal place). Assume the stator loss is 750 W.
Give us the tools to finish the job.
Sir Winston Churchill
Electron Emission
Electrons associated with the atoms of a metal are normally confined
to shells, as described in Volume 6. At a metal surface, ‘free’
electrons in the outer shells may leave the surface due to their
increased velocity. However, they are attracted back by the
unbalanced electric field created which sets up a potential barrier. If
these free electrons can break through the potential barrier, a process
termed electron emission results. Electron emission arises from
various sources and is described by one of the following processes:
(1) thermionic emission, (2) photoelectric emission, (3) secondary
emission or (4) cold or field emission. Of these thermionic emission is
considered first in some detail due to its relevance to various
common electron-related devices operation and laying the principles
for solid-state devices. Photoelectric and secondary emission will be
discussed with respect to modern image intensifiers for ‘night vision’
while cold emission will not be discussed as significant here.
Thermionic Emission
When a metal is heated, energy is transferred to it and electrons
acquire increased random velocities which may permit some to
escape the metal surface’s potential barrier, in a similar manner to a
rocket needing a certain minimum velocity to escape earth’s
gravitational attraction. Such electrons can also be likened to vapour
globules given off from a boiling water surface, where unless some
means of collecting electrons as they are emitted is found, they will
lose their velocities, forming a space charge. Such space charges or
electron clouds give rise to a –ve charge which repels further
electrons. We can picture electrons leaving a metal surface, repelled
by the space charge which has built up, subsequently returning to the
metal. To enable electrons to leave a heated metal surface, an
additional electrode is placed adjacent to, but insulated from, the
metal within a vacuum enclosure. A vacuum is needed as
atmospheric pressure prevents electrons moving between –ve
cathode and +ve anode. This electrode, the anode, is made +ve with
respect to the heated surface, the cathode. This arrangement was
first introduced in Volume 6 and is essential for the operation of radio
valves, CRTs, mercury-arc rectifiers and discharge lamps.
▲ Figure 10.1
Figure 10.3 shows the test circuit used to determine diode valve
characteristics. Conduction is only possible when the anode is +ve
with respect to the cathode and the more +ve the anode, the greater
the number of electrons reaching it, i.e. the larger the anode current.
However, the anode current cannot increase indefinitely, as there are
only a limited number of electrons leaving the cathode every second
and will reach a saturation value shown on the characteristic at a
point where, when anode voltage is increased beyond a certain
value, no increase of anode current is obtained and the curve bends
over to the horizontal. To obtain more anode current, cathode
temperature must be increased to increase electron emission.
▲ Figure 10.3
Static characteristics
Departure from Ohm’s Law in terms of diode behaviour shows that its
internal resistance varies with voltage. If a part of the static
characteristic, obtained from a test, is examined, it is seen (figure
10.4) that, for any anode current there is a fixed ratio of voltage to
current, the anode DC resistance.
▲ Figure 10.4
from the reciprocal of the slope of the line through the origin, i.e. .
Point P is the ‘operating point’ and the D.C. resistance value relative
to this point.
▲ Figure 10.5
▲ Figure 10.6
So ra = the ratio
A.C. resistance is less than the D.C. resistance over the working
range and example 10.1 shows comparative values.
▲ Figure 10.7
Or
Method 1 involves plotting the static characteristic and the load line.
Example 10.2. Using the test values of example 10.1, deduce the
dynamic characteristic for a 4 kΩ load-resistor. Find the circuit current
for a H.T. voltage of 110 V and the resistor’s voltage drop.
For a H.T. voltage of 110 V, the circuit current is 9.1 mA and the
voltage drop across the resistor = 110 – 74 V = 36 V.
▲ Figure 10.10
▲ Figure 10.11
The force magnitude is directly proportional to the potential gradient.
If the gradient is +ve, the force is towards the anode and if –ve, the
force is towards the cathode. For Curve 1 most of the emitted
electrons from the cathode pass the zero potential gradient value and
accelerate towards the anode to give a large anode current. For
Curve 3, only a few electrons have sufficient velocity to pass the point
of zero potential, most return to the cathode. The few electrons which
pass the point of zero potential gradient proceed to the anode to give
a small anode current. By altering grid potential the anode current is
controlled and may be optimised. As the grid is invariably kept at a
potential –ve to the cathode, electrons do not reach it and no current
is drawn from the grid voltage supply source.
Static characteristics
The circuit in figure 10.12 shows how a triode can be tested and
anode current controlled by (1) variation of grid voltage and (2)
variation of anode voltage. Curves when plotted from the test results
divide into 2 static characteristic groups: (1) the Mutual
Characteristics, which show the change in anode current Ia for a
change in grid voltage Vg, the anode voltage Va kept constant, and
(2) the Anode Characteristics which show the variation of anode
current Ia with a change in anode voltage Va, the grid voltage Vg kept
constant.
▲ Figure 10.12
▲ Figure 10.13
Valve parameters
These are derived from the slopes or change conditions of the graphs
and obtained by constructing small triangles as shown. As a straight
position of a graph is needed, the sides of a triangle are kept as small
as possible and referred to as ‘a small change of’ with the sign δ
used as previously.
Thus or , Va being
constant.
mA/V is common.
Parameter relationships
Here
Ionisation
In Volume 6 when ionisation was mentioned, it was stated that if an
electron is ‘lost’ from an atom, the latter acquires a +ve charge to
become a +ve ion. Ionisation of gas atoms is often accompanied by
monochromatic light emission, i.e. a single colour whose wavelength
depends on the gas ionised. It is unlike light given off by a tungsten-
filament lamp which covers a broad spectrum of visible white light.
Gas ionisation is mainly the result of the collision of fast, freely
moving electrons with gas atoms. We saw how electrons are emitted
from metal surfaces by thermionic emission, and how such electrons
travel at high velocity towards an electrode. If the latter is made +ve
with respect to the emitter, the higher the p.d. between anode and
cathode, the greater the electron velocity. If these collide with gas
atoms with velocity sufficient to remove further electrons from the
parent gas atoms, ionisation may cause light emission. The extra
electrons, subject to the electric field between the electrodes,
accelerate towards the anode, colliding with further atoms to maintain
ionisation. An electron ‘stream’ makes its way to the anode, with
current flowing from anode to cathode. The electronic device,
whether a gas-filled valve or discharge tube, depends on ionisation
for conduction. When electrons reach the anode, they displace further
electrons in the conducting metal of the circuit, which is why a current
is drawn from the mains to maintain operation. The +ve gas ions,
being heavier than electrons, move slowly to the cathode, combining
with electrons around the circuit. The ionised gas current consists of
electrons moving from cathode to anode and +ve ions moving from
anode to cathode. The +ve ions, moving to the cathode, will
neutralise any space charge and, if the voltage across the electrodes
is too high, may strike the cathode with velocity sufficient to damage
it. Proton mass is some 1850 times bigger than an electron and the
heat generated at the cathode by ion bombardment, under normal
operation, ensures that the temperature is high enough for electron
emission to continue.
▲ Figure 10.15
At start-up, current passes through both electrodes, heating them,
making them suitable for electron emission and reducing the start-up
voltage. The current sets up a small potential between the ends of
each filament, ionising gas and vapour near the electrodes, assisting
the main discharge ‘strike’. When electrodes are hot, the heating
current is broken by a starter-switch and a momentary surge voltage
(700–1000 V) is set up by a capacitor sufficient to start the main
discharge, and then maintained by the normal mains voltage. The coil
has two purposes, initially it gives a high-voltage impulse to strike the
tube, but then acts as a voltage dropper to maintain the correct p.d.
across the tube. ‘Instant-start’ fluorescent lamps are used ashore, but
marine systems often have circuits with a starter-switch. Its function is
to preheat the lamp electrodes, and apply a striking voltage. When a
control-switch is closed, the supply is applied to the circuit and as the
starter-switch closes, current flows through the filaments giving
sufficient electron emission to start ionisation. At a predetermined
time, the starter-switch opens automatically to interrupt the main
circuit. A collapsing field around the coil induces a high voltage
across the tube, causing it to strike. Once the main discharge current
flows, the voltage drop across the coil results in the correct p.d.
applied across the tube, and a stable running condition results. Lamp
efficiency is measured by comparing the lumens out for every watt in.
Fluorescent lamp efficiency is typically 40–50 lumens/watt which
compared with a tungsten filament lamp is some 14–16 lumens/watt.
This lamp type is relatively compact and mostly used for outdoor
installations on docks, wharfs and for some deck illumination. The
commonest hot-cathode discharge lamps are sodium and mercury-
vapour, with a sodium lamp illustrated in figure 10.16. When the
supply is switched on a 450 V voltage is applied from the secondary
winding of a high-reactance transformer connected across the lamp
electrodes causing a low discharge through the discharge tube so the
neon glows red. Heat produced gradually vaporises the metallic
sodium and the sodium vapour ionises to give a bright golden-yellow
discharge. A vacuum jacket thermally insulates the discharge tube to
improve sodium vaporisation. As the emitted light is monochromatic,
a fluorescent coating is not needed. High-pressure mercury-vapour
lamps are more often used than sodium lamps to illuminate deck
working-spaces and are briefly described in figure 10.16 in
conjunction with figure 10.17.
▲ Figure 10.16
▲ Figure 10.17
Once the main discharge strikes, electrodes are kept at their working
temperature by bombardment of +ve mercury ions. Having started the
lamp, the auxiliary electrode has no further purpose, and current flow
through it is minimised by a high ohmic value series resistor. A main
circuit stabilising coil also prevents excess build-up of current after
the discharge starts. Emitted light is mostly U.V., hence the
fluorescent coating. The main electrodes, without a preheating
current, are a spiral wire with barium or strontium oxide, which helps
increase electron emission when electrodes are heated. The lamp
takes several minutes to warm-up, as mercury vaporises and the
pressure rises to atmospheric pressure (1 bar). One disadvantage of
high working pressures is that a lamp will not restrike immediately
after switching off, and must cool down, allowing the pressure to fall,
before both discharge can recommence.
Image intensifiers
Photoelectric Effect
Electron emission is explained if light is considered to consist of
energy packets or photons . In 1905, Albert Einstein (1879–1955)
showed that light could be thought of as discrete quanta, or photons,
rather than waves. Based on Max Planck’s theory of black-body
radiation, Einstein proposed that photon energy was equal to its
frequency multiplied by a constant, later called the Planck’s constant.
Einstein states that a photon above a minimum threshold frequency
has sufficient energy to eject an electron. This discovery led to the
quantum revolution in physics and rightly earned Einstein the Nobel
Prize in Physics in 1921. In the Photoelectric Effect electrons are
emitted from a metal surface when a metal absorbs energy from
electromagnetic radiation of high-frequency radiation, acquiring more
energy than the work function (the electron binding energy) of the
material, and is ejected. However, if photon energy is too low,
electrons cannot escape. The photoelectric effect requires photons
with energies above a few electron volts in elements of high atomic
number. Electrons emitted in this way are called photoelectrons and
they were first observed by Heinrich Hertz (1857–1894) in 1887.
Understanding the photoelectric effect led to the conceptual
development of the quantum nature of light and electrons, influencing
ideas such as wave-particle duality.
E = hf = φ + (½ mv2)max
where ‘m’ is the mass of the electron and ‘v’ is its speed.
E0 = hf0 = φ
Secondary Emission
Some materials when bombarded by ‘primary’ electrons successfully
emit several ‘secondary’ electrons. An MCP usually has several
million small channels parallel to each other between the plate
surfaces (figure 10.19). Each channel has a diameter of only a few
microns and releases several electrons for every electron strike upon
it. In this way each channel acts as a separate electron multiplier.
When the alternating power supply is reversed the emitted electrons
are accelerated and provide further secondary emission through
subsequent ‘strikes’. Thus 1 electron rapidly becomes first 3, and
then 9, 27, and so on. A typical MCP may be composed of over 5
million individual narrow collimated channels which helps to reduce
image blurring due to bright light sources.
Practice Examples
10.1 A diode valve’s anode power dissipation is 336 mW. The anode
to cathode voltage is 160 V. Find the anode current (2 significant
figures).
10.2 When a 58 V anode voltage is applied to a 2-electrode valve the
anode current is 6 mA. Calculate the dissipated anode power (2
significant figures).
10.3 When the linear part of the Ia/Va characteristic of a diode valve is
examined, the slope is 1.64 mA/8.13 V. Find the valve’s A.C.
resistance (2 significant figures).
10.4 The Ia/Va characteristic of a diode valve shows an increase of
anode voltage from 75 to 129 V and current from 12 to 22 mA. Find
the valve A.C. resistance and the D.C. resistance for each voltage
condition (2 significant figures).
10.5 The Ia/Va curve of a diode valve is given by:
Plot the curve and find the A.C. resistance over the straight line
region (2 significant figures).
10.6 A vacuum diode has the following forward characteristics:
The diode is placed in series with a 300 Ω resistor load and the
combination fed from a 60 V D.C. supply, connected to make the
diode conduct. Determine the current flowing and the power
dissipated in the load resistor (2 significant figures both).
10.7 The following readings were obtained from the linear portions of
a triode valve’s static characteristics.
Semiconductors
This chapter introduces the semiconductor diode, a device
comparable in function to the thermionic diode in the electronic
circuits as discussed in Chapter 10. Semiconductor materials have
properties allowing their use for many device applications in response
to temperature, pressure, stress, light, magnetic and electric fields.
As such they are used frequently as sensors and transducers. The
term ‘semiconductor’ includes all solids whose electrical conductivity
lies between that of metals and insulators. Germanium and silicon,
and gallium arsenide are perhaps the most important semiconductor
materials of current working device choice, but graphene, a
substance made from pure carbon, with atoms arranged in a regular
hexagonal pattern similar to graphite but only one atom thick, may
provide novel new commercial devices in the near future. However,
before investigating the electrical properties of current materials such
as germanium and silicon, it is worth recalling the history of
semiconductor development in electrical work. The electrical
properties of semiconductor materials will then be examined, without
which diode and transistor operation will not be understood.
Basic theory
Conduction control
▲ Figure 11.3
I = IF – IR = 0.
In summary for the arrangement shown, few charges can cross the
barrier unless they have an energy level high enough to overcome
the junction barrier’s potential. The +ve charge of the N-type will
however attract the minority carrier electrons from the P-type side
and the –ve charge will attract the minority carrier +ve holes from the
P-type side. The resulting current I = IF – IR will be zero and since
there is no external voltage applied the junction will be in equilibrium
with charges and potentials as shown. Semiconductor diode
behaviour will be investigated for the condition of an external
electromotive force or applied electric potential.
▲ Figure 11.7
Recti er operation
fi
Since the junction diode requires no heater supply, it is easily
introduced directly into circuit arrangements to allow both half-wave
and full-wave recti cation. The characteristic shows the device is
fi
suitable for a recti er and if an alternating voltage of about 1 V (peak
fi
to peak) is applied to a P-N junction, the potential barrier will
alternatively increase and decrease over time to allow recti cation.
fi
The reverse current is considered negligible. Silicon is used in
preference to germanium for most large power rectifiers as it can
carry large currents and operate at higher temperatures and its
reverse current is also lower than that for germanium with similar
forward current values.
Plot the anode characteristics for the diode and determine from it (a)
the ‘forward’ D.C. resistance when the current is 3 mA and (b) the
forward anode voltage when the D.C. resistance is 200 Ω.
(a) From the graph of figure 11.9 the forward D.C. resistance
▲ Figure 11.9
The characteristic is plotted and the load line drawn for 100 Ω thus:
With no current flow the full 2 V is applied across the diode and point
A obtained. With a diode D.C. resistance of zero, the maximum
current which could possibly flow will be . Thus point B is
▲ Figure 11.10
Rectifier Circuits
Most electronic circuits operated from a D.C. supply will likely obtain
their voltage supply from batteries while at sea. However, as batteries
discharge, continuity of voltage supply cannot be assured and
reliability of the equipment falls. Rectifier circuits, using the
unidirectional conduction properties of junction diodes, are often
incorporated in electronic units which are to be connected to A.C.
supplies. The rectified output can thus be either half or full-wave
arrangements, which are now considered in turn.
Half-wave
▲ Figure 11.11
Full-wave
▲ Figure 11.12
▲ Figure 11.13
▲ Figure 11.14
▲ Figure 11.15
The output voltage has a definite ripple, the ripple voltage, but the
ripple is reduced with the use of increasingly higher capacitance
values. A capacitor used in this way is sometimes referred to as a
storage or reservoir capacitor. The time taken to fully charge a
capacitor is still very small and decreases as the capacitor value
increases. Thus for practical purposes, it is assumed to charge up
instantaneously. In a half-wave rectifier circuit the capacitor may be
assumed to discharge in the time taken for a complete cycle .
▲ Figure 11.16
Example 11.3. A full-wave rectifier with capacitor smoothing,
operating from a 50 Hz A.C. supply, produces a D.C. output of
maximum value 60 V. The capacitor has a value of 2000 μF.
Find the peak to peak value of the ripple voltage when delivering 250
mA to a resistive load (2 decimal places).
t = Discharge time =
In many cases this ripple does not actually affect the load operation
but in some electronic circuits its presence is undesirable and should
be eliminated. Connecting a capacitor across the load will affect the
P.I.V. developed across the diode, because when the diode is in a
non-conducting mode, the voltage developed across it is the peak
value of the supply PLUS the peak value of the capacitor voltage.
i.e.
Filter Circuit
The storage or reservoir capacitor may not completely eliminate
ripple and, if complete ripple suppression is needed, another
capacitor and an iron cored inductor should be connected as shown
in figure 11.17.
▲ Figure 11.17
▲ Figure 11.18
The rectifier circuit D.C. output, even though it may be smoothed with
a capacitor, may vary due to peak value variations of input voltage
Vm, which are often encountered as the A.C. mains voltage changes
due to supply variations or fluctuations. Similarly as the D.C. load is
increased the increased current causes the output voltage to fall due
to voltage drops in the circuit. These effects are undesirable in
electronic control and monitoring devices and can be effectively
reduced by a stabilising circuit which incorporates a zener diode as a
voltage reference to provide a steady output voltage.
It has already been shown that a P-N junction diode will break down
at a definite voltage when reverse biased. This breakdown, or zener
effect, occurs at a definite voltage determined by the manufacturer. A
junction diode continuously operated with reverse bias is called a
zener diode.
Series Stabilisation
To produce a stabilised voltage the zener diode may be connected
across the load as shown in figure 11.21. The zener diode voltage
rating is then determined by the D.C. voltage across the load.
▲ Figure 11.21
VO = VZ + IZ × RZ
VO = 9.1 + 15 × IZ
VI = I × RS + VO
30 = 15 + 500 × IZ + 9.1 + 15 × IZ
(1) If the load is varied so that IO rises then II will tend to rise with a
consequent larger RS voltage drop, VZ will fall but a small decrease of
VZ causes a large decrease in IZ and compensates for the increased
IO. II will remain constant as will the RS voltage drop and the output
voltage VO.
If the load current falls, II will tend to fall reducing the voltage drop
across RS. A small increase of VZ will cause a large increase of IZ
which counters the effect of a reduced IO. The RS voltage drop is
fairly constant and so VO remains fairly constant. When no load
current is taken, maximum load current plus IZ(min) flows through the
zener diode, while on full load the zener conducts IZ(min).
(2) If the supply voltage varies, VI rises and VO will rise. VZ will rise
causing a large increase of IZ. The RS voltage drop will get larger and
compensates for the rise of supply voltage to keep VO largely
constant. Conversely if the supply voltage VI falls, VO and VZ will fall,
causing a large decrease of IZ resulting in a smaller RS voltage drop
offsetting the fall of VI, so VO will tend towards minimising change. VZ
will remain constant provided IZ(min) flows continuously.
amperes. The current rise is diverted through the zener, with the IZ
rise equalling the increase of II and the voltage rise
.
Stability is defined by ‘the output voltage when the input voltage rises
by 1 volt’. This stability value is obtained from the ratio .
Practice Examples
11.1 The following data represent the forward characteristics of a P-N
junction diode.
Estimate (a) the forward D.C. resistance when the current is 1.5
mA and (b) the voltage and current for a forward D.C. resistance of
1.75 kΩ.
11.2 On test, a full-wave, silicon semiconductor rectifier is found to
give a constant forward voltage drop of 0.7 V, independent of
current. Calculate the power dissipated in the rectifier diode for a
D.C. current of 5 A. If the rectifier dissipates heat, at the rate of 0.1
J/s/°C rise in temperature, find the maximum D.C. output current
rating if the temperature rise is to be limited to 70°C.
11.3 The following values refer to a germanium diode.
Plot the anode characteristics for the diode and determine from it
(a) the ‘forward’ D.C. resistance when the current is 3.45 mA (2
decimal places).
11.4 A half-wave rectifier with capacitor smoothing is fed from a 230
V, 50 Hz supply via a 12:1 step-down transformer. The volt drop
across the diode when conducting is 0.75 V. Calculate the peak
value of the D.C. output voltage and the P.I.V. rating of the diode.
11.5 An electronic circuit requires 350 mA D.C. from a half-wave
rectifier circuit which incorporates a 1800 μF capacitor for
smoothing. If the supply voltage is 50 V, 60 Hz, calculate (a) the
peak value of the D.C. output voltage and (b) the peak to peak
value of the output ripple voltage.
11.6 A D.C. load is to be supplied from a 250/40 V, 50 Hz transformer
and bridge rectifier circuit with a 2000 μF capacitor for smoothing.
Determine (a) the P.I.V. Rating of each diode and (b) the peak to
peak value of the ripple voltage when supplying 250 mA.
11.7 An A.C. supply of 50 V is connected to a voltage doubler circuit
as illustrated in figure 11.18. Calculate the peak voltage across the
load resistor assuming the diodes to have negligible forward
voltage drop.
11.8 The output from a rectifier circuit with capacitor smoothing is 25
V ± 20%. A zener diode series stabilising circuit is connected to this
supply to provide a stabilised output from which currents up to 50
mA will be drawn. The zener diode has a breakdown value of 9.7 V
and for stability it must carry a minimum current of 1 mA. The diode
resistance above 9.7 V is 12 Ω. Determine (a) a suitable value of
series resistance and (b) the stabilised voltage.
11.9 A zener diode has a breakdown value of 8.2 V and, beyond this
voltage, will have a resistance of 12 Ω. It is connected in a
stabilising circuit, with a series resistor of 400 Ω to an unstabilised
D.C. supply voltage of 40 V. When the load current is 40 mA
calculate the zener diode current, the load voltage and the power
dissipated in the diode (all 3 significant figures).
11.10 Figure 11.23 illustrates a rectifier circuit incorporating capacitor
smoothing and zener stabilisation. The zener diode has a
breakdown value of 24 V and requires a minimum current of 1 mA
for stable operation. For values of voltage above 24 V the slope
resistance is 14 Ω. For a stabilised D.C. load current of 60 mA
calculate (a) the peak to peak ripple voltage measured across the
capacitor, (b) the required P.I.V. rating of the diodes, (c) the
minimum value of RS for stable operation and (d) the power rating
of the zener diode.
▲ Figure 11.23
The transistor is the information engine of the digital age.
Chris Lavers
The Transistor
This chapter continues our discussion of solid-state electronics by
introducing the transistor. The transistor is a semiconductor device
used to amplify and switch electronics signals and electrical power
and has quite simply revolutionised electronics. It is composed of a
semiconductor material with at least 3 terminals, for connection to an
external circuit. A current or voltage applied to a pair of the
transistor’s terminals changes the current flowing through another
pair of terminals acting as a controllable electronic switch. Because
the controlled output power can be significantly higher than the
controlling input power, a transistor can be viewed as an electronic
amplifier of a signal. Today, transistors are available as separate
devices, or more commonly as one of millions of similar components
within integrated circuits.
The next key step forward was the development of the junction-alloy
transistor which made the point-contact transistor obsolete by 1956.
Physical electronic theory had by then progressed to the stage where
a range of different semiconductor junction possibilities could be
fabricated. Shockley proposed a 4-layer P-N-P-N device and a
different class of uniplanar devices based on the ‘field-effect’
principle. In fact a wide range of solid-state devices are now
available, covering various ‘families’ of such devices, but the chief
among these is still the junction transistor, the subject of this chapter.
This family is split into 2 sub-groups covering P-N-P and N-P-N types.
Another family covers the field-effect devices which can also be
divided into 2 groups – the Junction Field-Effect Transistor (JFET or
FET) and Insulated-Gate Field-Effect Transistor (IGFET) more
commonly known as a Metal Oxide Semiconductor FET (MOSFET)
and refers to its construction from metal layers (the gate), the oxide
(the insulator) and a semiconductor. Further families cover 3-junction
devices like the thyristor, diac and triac, while developments in
diffusion techniques, metal oxide processing and nano-scale
photolithographic etching have created the integrated circuit with
transistors, resistors and capacitors formed better during
manufacture. Study of these now numerous devices includes in no
particular order: Schottky, Avalanche, Darlington transistors, carbon
nanotube FET, organic FET and FETS used to sense the
environment, and the Single Electron Transistor (SET) which would
require in-depth discussion, and so we return to our discussion of the
junction transistor.
▲ Figure 12.1
▲ Figure 12.2
OPERATION. Figure 12.3 shows a basic P-N diode and a basic P-N-
P transistor arrangement, the latter consists of a region of N-type
material sandwiched by P-type material regions. The N-type material,
the base, is rich in electrons but is very thin (0.005–0.05 mm). The
outer regions – the sandwich ‘slices’ – the emitter and collector, are
both rich in +ve charge carriers or holes. An N-P-N transistor will
have the materials reversed. Amplifying action is obtained because
the current between the emitter and base influences the current at a
higher power level between the collector and base. Before describing
this action in detail, we will revise the explanation of junction diode
operation by remembering that on one side there are only holes
(figure 12.3a), while on the other side there are only electrons.
Application of a voltage across the junction, so the P-end is +ve and
the N-end is –ve, results in current flow since holes move left to right
and electrons move from right to left. Reversal of applied potential
results in no current flow since there are no holes free to move right
to left or electrons free to move left to right. The junction provides an
‘easy’ path in one direction only and is virtually open circuit in the
other direction. With a +ve potential applied to the P-side and a –ve
potential on the N-side, the diode is forward biased and current
readily passes provided the voltage is above the barrier potential,
typically 0.6 V for silicon, and 0.2 V (smaller) for germanium.
▲ Figure 12.3
▲ Figure 12.4
Substituting in
. Thus
With the ‘forward current transfer ratio’ , similarly β is given
These current ratios are defined by the static value of the short-circuit
forward current ratio with the symbol hF. Another subscript is added
to indicate the configuration, hence the above hFB and hFE.
δIe is deduced from the fact that emitter current = collector current +
base current.
Transistor characteristics
Transistor performance can be investigated by making suitable tests
and from the results and the characteristics of each configuration
drawn. These are the (1) Input Characteristic, (2) Output
Characteristic and (3) Transfer Characteristic. The last can be
deduced from the first two but a test is useful in that an average value
for the forward current transfer ratio is obtained directly. In figure 12.5
the emitter arrow indicates the conventional current direction, i.e. the
direction in which +ve holes are injected into the base. For N-P-N
transistors, the current carriers (collector current) consist of electrons
flowing from the N-type emitter into the P-type base. Conventional
current (hole) flow is in the opposite direction, hence the arrow
reversal on the emitter which points away from the base. Device
polarities are reversed with the collector +ve with respect to the base
and the emitter –ve biased. N-P-N transistor use has increased, as
diode manufacturing techniques have improved unit cost reduction.
▲ Figure 12.5
▲ Figure 12.6
So Input impedance .
▲ Figure 12.8
The reason for the shapes of the curves is that the collector will
always collect holes if it has a –ve bias. Current Ic is almost
independent of applied voltage, because it is a reverse current, and
depends only on the minority carriers (+ve holes) which are available,
themselves depending on Ie. The ‘transfer characteristic’ is found by a
direct test, holding the base-collector voltage at a fixed value and
varying Ie. The effect on Ic is noted, as shown in figure 12.8b, and its
slope is a measure of α or hFB – the forward current transfer ratio
(current gain), whose value is deduced directly from the output
characteristic. For this mode for a fixed value of Vc, the
change in Ic noted for a change in Ie, and current gain deduced. For
example (figure 12.8a) for a constant Vc value of –4 V, when the
emitter current is raised from 2 to 4 mA (difference 2 mA), the
collector current rises from 1.9 to 3.8 mA (1.8 mA difference). Thus
(approx.). Difficulties arise in achieving the required
accuracy for α, when using this method, and a more reliable result is
achieved by plotting the transfer characteristic.
▲ Figure 12.9
Figure 12.10 shows the phase relationship between the input and
output voltages; they are in phase which is the opposite of that
observed for a valve where the input and output voltages are 180° out
of phase. In the common-base mode, the transistor’s full abilities are
not exploited, in that control by the base current of the collector
current is not used. The configuration gives a current gain of less
than 1 and amplification is only achieved by the different impedance
levels in the emitter and collector circuits. It is convenient to deal in
terms of voltage gain, but true amplification is considered in terms of
a power gain and this aspect is important for transistor work. Thus for
the circuit of figure 12.9, the forward-biased transistor emitter-base
diode is of low impedance, e.g. 15 Ω. If a 0.5 mA current change
takes place, the power change = 0.52 × 10–6 × 15 = 3.75 μW. In the
collector circuit, a corresponding change of 0.49 mA takes place with
an impedance of say 1000 Ω. Thus power change is 0.492 × 10–6 ×
103 = 0.492 × 10–3 = 0.24 × 10–3 or 240 μW, giving a power gain of
(approx.).
▲ Figure 12.10
To achieve this gain, it is vital to match the signal source to the input
impedance and the load to the transistor output impedance. In the
common-base mode current amplification cannot be obtained as ‘a’ is
less than unity. Voltage amplification is possible because the emitter-
base junction has a low resistance and if a large load resistance
value is used in the collector circuit, a high-voltage gain results.
Power gain can be large, as shown, and is mostly used for R.F.
circuits.
∴ Voltage gain .
▲ Figure 12.11
▲ Figure 12.14
A ‘transfer characteristic’ is obtained by plotting Ic against Ib, with Vc
constant. This can be deduced from the output characteristic and is
shown in figure 12.14b.
Thus
Input resistance depends on the working D.C. bias value because the
gradient of the curve changes with Vb, with output resistance
obtained from figure 12.14a given by the slope of the appropriate
curve. Output A.C. resistance will be high and nearly constant for a
given Ib value if the working conditions are beyond the curve’s turn-
over point. When Vc is small, i.e. below this value, output resistance
is much reduced. The reader’s attention is drawn to the deduction
made earlier: β or or .
mA
also . Thus .
▲ Figure 12.15
base current is now the input current. As Ib is very small, the ratio is
large with a value of about 50. Figure 12.15 shows how supply
voltage is applied between emitter and collector and circuit current is
controlled by base current. As stated earlier α' or β is used for
common-emitter ‘current-gain’ but hFE is recommended, i.e. the
‘forward current transfer ratio’, with values between 20 and 100. The
transfer characteristic slope (figure 12.14b) gives this value. It is easy
to explain the high gain for this mode. Two separate current paths are
seen in figure 12.15. For one, a current flows into the emitter and out
through the base. For the other, current flows out of the collector and
returns via the supply to the emitter. The collector current is less than
the emitter current by the very small base current. Alternatively, the
base current is the difference between the emitter and collector
currents: Ib = Ie – Ic. Any change occurring in Ie or Ic leads to a
change in Ib equal to this difference. Thus for a transistor with a
common-base gain factor α = 0.98, when Ie is increased by 1 mA, Ic
changes by 0.98 mA and the resulting change in Ib is 0.02 mA. Here
a certain base current change is associated with a change in the
collector current which is 49 times bigger, and there is a current gain
between the circuits.
▲ Figure 12.16
or current gain
= 57.5.
▲ Figure 12.17
Load lines
▲ Figure 12.18
when Vc = 0, then
(3) The gain is determined for working about the operating point O
We have β or .
Leakage current
▲ Figure 12.19
One efficient and common method of stabilising the base bias uses a
potential divider made up from R1 and R2. As the current I1 in the
series resistors is more than the base current, the base potential is
held fairly constant in spite of base current variation when A.C. input
signals are applied. Use of resistor R3, inserted between the emitter
and the battery +ve terminal, was explained in relation to example
12.2 for resistor RE. Its value is much larger than the transistor
internal emitter resistance and the current is largely unaffected when
transistor temperature changes, so thermal runaway is avoided. Use
of silicon, instead of germanium for semiconductor devices, is mainly
to raise operating temperature and stabilising circuit techniques are
still used for silicon transistors.
The thyristor
▲ Figure 12.21
▲ Figure 12.22
▲ Figure 12.23
If a thyristor’s current/voltage characteristic is considered (figure
12.23), further explanation of the holding current can be made. With
no gate connection, if an increasing voltage is applied between the
anode and cathode, a small but constant current flows through the
device between the terminals. At a certain voltage value, the
Breakover Voltage (VBO), current suddenly increases in value,
limited only by load conditions. The device has switched itself into a
state of low impedance by internal electron-hole rearrangement and
stays in this state until current is reduced below the holding value.
The thyristor then reverts to its ‘blocking state’. With the gate
connected and an electrical bias of the correct relation to the anode
applied, it is found that the VBO value can be controlled but, as
stated, once the thyristor has ‘fired’ the gate has no further effect.
(2) Burst-fire Control. Figure 12.25 shows the method. The thyristor is
switched on for several consecutive positive half-cycles. Conduction
is thus for one or more half-waves of load current with periods of non-
conduction interposed. The method is suitable for large loads where
thermal or mechanical inertia ensures that the effect can be
smoothed out to equate to that of a smaller constant (averaged)
current. A gate pulse is applied by a timing circuit at the instant just
before the start of a +ve half-cycle of the main circuit voltage and as
the latter rises from zero, load current rises in a sinusoidal manner
and falls similarly. This occurs for each conducting half-cycle and
radio interference will be minimised. The number of conduction cycles
can be varied by the duration of pulsing the gate but the heating at
the gate electrode must be taken into account by the circuit designer.
Since the gate supplies current during the pulsing period, this source
of added temperature rise can be reduced using a H.F. supply for the
trigger circuit.
▲ Figure 12.25
Practice Examples
12.1 A transistor connected in a common-emitter circuit shows
changes in emitter and collector currents of 1.0 and 0.98 mA,
respectively. What mA change in base current produces these
changes (2 decimal places), and what is the current gain of the
transistor (2 significant figures)?
12.2 In a certain transistor, a change in emitter current of 1 mA
produced a change in base current of 0.1 mA. Calculate the
common-emitter and common-base short-circuit current gains (both
1 decimal place).
12.3 A certain transistor has a common-emitter short-circuit current
gain α' or β = 50 or β = 50. Calculate the common-base short-
circuit current gain (2 decimal places).
12.4 For a common-emitter transistor, the transfer characteristic is
given by the values:
12.7 From the data given for example 12.6, plot the collector
current/emitter-current or transfer characteristic for Vc = –30 V and
hence calculate the current gain α (2 decimal places). From this
value deduce the current gain (β) for the common-emitter mode (2
significant figures).
12.8 The data given in the table refers to a P-N-P transistor in the
common-emitter configuration.
Plot the collector current/collector voltage characteristic for base
currents of –20, –40, –60 and –80 μA and using these determine
(a) the output resistance of the transistor for the Ib = –60 μA
condition, in kΩ (1 significant figure) and (b) the current gain when
the collector voltage is –6 V (2 significant figures).
12.9 From figure 12.26, calculate the value of the bias resistor to give
a standing base current of 40 μA in kΩ (3 significant figures). The
supply voltage is 9 V and for the transistor VBE = –0.2 V and VCE =
–5 V.
▲ Figure 12.26
Radar receivers are usually but not always located in the same place
as the transmitter and are termed monostotic radar. Radar with a
separately located receiver are known as bistatic radars, and where
multiple receivers are used the term multistatic radar is used. For the
case of marine radar we will only discuss monostatic radar and so
bistatic and multistatic systems will not be discussed further. The
reflected radar signal detected by even a relatively large ship’s
search radar is usually very weak, but can be amplified significantly
using sophisticated electronic amplifiers and digital signal processing
methods and with modern display systems now provide a
surprisingly high degree of accuracy. However, it must be pointed out
that there are many things which do not show up on radar displays
and the information provided by the radar on its own provides at best
an incomplete tactical picture and situational awareness of the
navigational and possible war-fighting scene.
Radio and the visible part of the spectrum provide two ‘windows’ of
good atmospheric transmission where the weak absorption of radio
waves by the atmosphere enables radar to detect targets at
relatively long ranges, ranges at which other electromagnetic
wavelengths, such as visible light and NIR, are much too strongly
attenuated. Weather phenomena such as fog, clouds, rain, snow,
sleet and volcanic ash that block visible light are often transparent to
radio waves. From an aircraft perspective volcanic ash is a deadly
hazard as it does not show up well at usual radar frequencies.
Certain radio frequencies that are absorbed or scattered by water
vapour, rain drops or atmospheric gases such as oxygen are
generally avoided when designing radars, except when their
detection is intended, i.e. for weather radar.
Radar waves scatter in many different ways depending on the
relationship between the size of the radio wave and a target’s size
and shape. If the wavelength is much smaller than the target’s size,
waves will reflect in a similar way to light reflected from a mirror. If
however the wavelength is much bigger than the target size it may
not be visible at all due to poor reflection. Low-frequency radar also
depends strongly on resonances for detection, and cannot provide
direct target identification.
▲ Figure 13.1
If the elapsed time t from transmission of the short radar pulse to the
time the echo is received is measured electronically knowledge of
the wave speed allows the contact range to be calculated accurately.
Since electromagnetic waves travel close to the speed of light in
vacuum, and only a little less in our planet’s thin atmosphere, with a
value of c = 3 × 108 ms–1, the distance they travel may be given as
follows: distance = ct. Hence contact range R, which is half the total
distance, is given by: R = ct/2. If the elapsed recorded time from
pulse transmission to reception is 1 ms the radar range from the
transmitted to the reflecting target will be given by: R = 3 × 108 × 1 ×
10–6 / 2 = m.
Here P is the average transmitted power, G the antenna gain, i.e. the
ship’s RCS (a measure of the contact size seen by the radar beam),
tot is the time the radar contact is illuminated by the rotating radar
beam, Aeff is the effective size of the receive antenna and Smin is the
minimum signal energy required for detection by the receiver.
Changes to any of these parameters will alter the MDR. Generally
wave loss increases with increasing frequency and so the MDR falls.
Clearly a ship’s search radar has control of all but the elusive RCS of
the vessels around it and the environmental conditions.
PEAK POWER. For radar peak power is the maximum pulse power,
but the average power is much lower as the radar power is zero
during the receive period (which should be much greater than the
time the radar transmits). Increasing peak power increases average
power up to practical limits where a radar may overheat or sparking
could occur.
Antennas
Clutter
Radar returns are produced from nearly all types of surfaces when
illuminated by radar. Therefore in competition with the ship’s radar
returns there are many sources of unwanted echoes from our radar
transmissions. Clutter may include sea returns, returns from cliffs
and weather itself. The definition of clutter depends on the radar
function, e.g. weather is not clutter in a weather detecting radar. The
two main types of clutter observed on a Plan Position Indicator (PPI)
display are Surface Clutter and Volume Clutter.
Environmental effects
Lasers
Lasers for marine applications
Stimulated emission
Laser safety
Laser products are usually labelled with a safety class number which
identifies how dangerous a laser is.
Raster Navigational charts are raster charts that also conform to IHO
specifications and are produced by converting paper charts to digital
images by scanner. Images are similar to digital camera pictures
which may be ‘zoomed in’ for more detailed information as can ENC.
War-fighting ECDIS
LORAN-C
LORAN (LOng RAnge Navigation) is a terrestrial navigation system
using Low-Frequency (LF) radio transmitters. Before satellite-based
GPS systems, it was the primary location method used in marine
applications. The United States, Canada and Japan still uses
LORAN. Russia uses a similar system called CHAYKA. The current
version, LORAN-C, is an ocean navigation aid, requiring a special
receiver. A Master transmitter and Slave transmitter emit pulses at
the same frequency, and is an example of 2 source interference.
▲ Figure 13.5 Two source interference
Measuring the difference between the arrival times of the two pulses
determines on which hyperbolic Line of Crossed LOPs from the 2
master-slave pairs, and provides the observer at point P with a
hyperbolic fix (figure 13.5). The LOP is the locus of all points in
space where the observed time differences between arrival of
signals from the 2 paired stations are constant, forming a hyperbola.
LORAN-C is thus described as a hyperbolic radio navigation system.
A LORAN-C chain consists of a Master transmitter with 2, 3 or 4
Slaves designated W, X, Y and Z. LF transmitters operate at 100
kHz and emit groups of typically microsecond duration pulses at a
specified interval, the Group Repetition Interval (GRI), unique to
each chain and selected to avoid interference with other chains.
Slave station transmission is delayed with respect to the Master, the
secondary coding delay, ensuring pulse groups are always received
in sequence (M, W, X, Y, Z). The master transmits 9 pulses while
slaves transmit 8, with the master’s 9th pulse used for identification.
LORAN was an American development of the British GEE radio
navigation system, used in World War II, with a range of about 400
miles. In LORAN, one station is kept constant in each application,
the Master, paired separately with 2 other Slave stations. Given 2
secondary stations, the Time Difference (TD) between the Master
and first secondary identifies one curve, and the TD between the
Master and second secondary identifies another curve. The
intersection of lines determines a geographic point in relation to the
position of the 3 stations. These curves are referred to as Time
Delay or TD lines. Essentially we measure the distance we have
travelled by counting the number of constructive to destructive half
wavelengths moved. Modern LORAN receivers display Latitude and
Longitude instead of signal TDs, with high accuracy.
Limitations of LORAN
LORAN suffers from the effects of weather and also from ionospheric
effects near sunset and sunrise. The most accurate signal is the
Ground wave that follows earth’s surface along a water path (best
surface conductivity). At night indirect Skywaves, taking paths
refracted back to the earth’s surface by the ionosphere, are a
problem as multiple signals arrive from different paths. The
ionosphere’s response to sunset and sunrise accounts for significant
disturbances and errors during these periods. Magnetic storms can
also seriously effects LORAN-C performance (in the range 90 to 100
kHz), as it is an RF-based system. Due to such interference, the very
phenomenon LORAN is based upon, and further propagation loss
suffered by LF signals from land features and man-made structures,
LORAN signal accuracy degrades significantly in land.
These systems all work by using accurate timed radio signals using
a standard based on the Caesium atomic clock, to pinpoint their
range from a number of satellites at known orbital positions. Using
various satellite ranges, projected geometric spheres can be
intersected to determine a user’s position, in a similar manner to
radar Direction Finding.
To be able to measure the time taken for the signal to reach us, the
satellite and the receiver codes must first be synchronised. Each
satellite transmits a unique digital code, which is synchronised with
the code on the GPS receiver. The code contains information about
the position of the satellite and the time the code was transmitted
(figure 13.6).
It is then possible to work out when the signal left the satellite, as the
same code is used by the receiver and the satellite. It is then
necessary to look at the incoming code from the satellite and see
how long ago the receiver generated the same code, and then to
work out the exact time the coded signal left the satellite.
The U.S. GPS NAVSTAR project was the first developed in 1973 to
overcome the limitations of previous navigation systems. GPS
consists of 3 major segments: a space segment, a control segment
and a user segment (figure 13.8). GPS users are only really
concerned with the visual representation of the latter component,
and of course, its accuracy.
▲ Figure 13.8 Segments of the GPS system
NAVSTAR
The first operational GPS was the U.S. Navigation Satellite Timing
and Ranging GP system or NAVSTAR GPS. The NAVSTAR GPS is
currently managed by the U.S. Department of Defence (DoD) who
launched the first generation of test satellites (Block I) in 1978. The
first operational satellites (Block II and Block IIA) were launched from
1989 onwards and now the next generation of satellites (Block IIR) is
being launched.
GLONASS
GALILEO
The European Union (EU) GALILEO project was formed from the
need to have a separate system independent from the United States,
to allow the European Union to stand alone on its own if ever
needed. It also stemmed from the need for a more accurate
horizontal and vertical positioning for civilian engineering and
aviation requirements not readily available from the other existing
networks. The system will be interoperable with NAVSTAR GPS and
GLONASS, thereby increasing constellation visibility and positional
accuracy with the use of a greater number of satellites. GALILEO will
achieve better coverage at high latitudes (Northern Europe) and also
make up part of the Global Maritime Distress and Safety Service
(GMDSS) and exceptionally high accuracy is achieved using signals
from additional strategically located ground stations (differential
GPS). One company TOPCON now provides receivers which can
detect GPS NAVSTAR, GLONASS and GALILEO to provide
unprecedented accuracy from over 80 separate satellites.
The system was developed from 2001 to 2005 with the deployment
of the satellites due to take place from 2007 which was realised with
several satellite launches in 2013. The European Union and its
partners of the European Space Agency have signed agreements
with non-European countries, most notably China, although China
has its own plans to extend its own current Beidou capability (limited
to Asia and the West Pacific) to create COMPASS, the People’s
Republic of China Global System, planned to be operational by
2020. India intends its own regional navigational system, to be
operational starting from 2014 covering India and the Northern
Indian Ocean, the IRNSS system.
AIS units can transmit and receive 26 different message types. Data
are sent every 2 to 10 seconds depending on the vessel’s size and
speed while underway, or every 3 minutes if the vessel is at anchor.
AIS will state the vessel’s Maritime Mobile Service Identity (MMSI),
navigation status, rate of turn, speed over the ground, position,
course over ground, true heading and time stamp. Additional
information such as ship type, cargo, ship dimensions, draught and
destination ETA is broadcast less frequently on up to 6 minute
intervals.
Emergency Beacons
Distress radio beacons, also known variously as emergency
beacons, Personal Locator Beacons or PLBs, Emergency Locator
Transmitters (ELTs), or Emergency Position Indicating Radio
Beacons (EPIRBs), are tracking transmitters which can aid in the
detection and location of sinking vessels, aircraft and people in
distress. They are radio beacons that interface with worldwide
services of Cospas-Sarsat, the recognised international satellite
system for Search And Rescue (SAR). When manually activated, or
automatically activated upon immersion, such beacons send out a
distress signal. The distress signal is monitored worldwide and the
location of the distress is then detected by various non-geostationary
satellites, and then located by a combination of GPS and Doppler
triangulation.
Most PLBs are brightly coloured and waterproof. PLBs vary in size
from cigarette-packet to paperback book size and weigh between 0.2
and 1 kg. EPIRBs and ELTs are generally larger, but will need to fit
into a cube of some 30 cm a side, weighing between 2 and 5 kg.
They can be purchased from marine suppliers, and hiking supply
stores. The units have a life of 10 years, and operate across the
range of –40 to 40°C, and will transmit for 24 to 48 hours.
Activation
The most modern 406 MHz beacons with GPS track to a precision of
100 m in 70% of the world nearest to the equator, and send a serial
number so the responsible authority can look up phone numbers to
notify the registrator (e.g. next-of-kin) in about 4 minutes. The GPS
system permits stationary, wide-view geosynchronous
communications satellites to enhance the Doppler position received
by Low Earth Orbit (LEO) satellites. EPIRB beacons with built-in
GPS are usually called GPS Position-Indicating Radio Beacons
(GPIRBs). Rescue will not begin until a Doppler track is available.
COSPAS-SARSAT specifications state that a beacon location is not
‘resolved’ unless at least 2 Doppler tracks match or a Doppler track
confirms an encoded (GPS) track.
Satellites
Practice Examples
13.1 A radar contact is detected using pulse delay ranging. If the
elapsed recorded time from pulse transmission to reception is 0.2
ms, and given that c = 3 × 108 ms–1, find the radar range of the
target (1 decimal place).
13.2 Considering the formula for Maximum Detection Range
Production of displays
To measure time a reference is provided on a CRT which causes the
spot to travel across the screen at a constant speed. The signal that
causes this is called a time base.
▲ Figure 14.2 A typical time base waveform for TV and marine radar ‘A type’
displays
Oscilloscope CRTs
CRT advantages
CRTs have high contrast ratios (over 15 000:1), and excellent colour
and have no input lag. There is no ghosting and ‘smearing’ artefacts
during fast motion due to sub-millisecond response time. CRTs have
near zero colour, saturation, contrast or brightness distortion and
provide a wide viewing angle range. They can be used or stored in
extremely hot and cold temperature conditions without harm to the
system.
CRT disadvantages
CRTs are still popular in specific market niches and provide better
colour fidelity, contrast and better off-axis viewing (wider viewing
angle) than many flat screen LCDs. CRTs emit a small amount of X-
ray radiation from the electron beam’s bombardment of the shadow
mask/aperture and phosphors but the amount of radiation leaving the
monitor is considered harmless. Older colour and monochrome CRTs
contain toxic substances, such as cadmium, in the phosphors. Many
countries treat CRTs as toxic waste and prohibit disposal in landfills or
by incineration. In Europe, disposal of CRT televisions and monitors
is covered by a relevant EU Directive. As electronic waste, CRTs are
considered one of the hardest types to recycle having high
concentration of lead and phosphors, both of which are needed for
the CRT display. Under some circumstances, signals radiated from
the electron guns can be captured remotely to show what was on the
CRT. Special maritime TEMPEST shielding can mitigate against this.
Such potentially exploitable signals, however, occurs with other
display technologies and electronics in general. CRTs are affected by
earth’s magnetic field and are factory preset biased for operation in
north or south hemispheres, or equatorial regions, but may require
‘trimming’ if crossing between hemispheres on the world’s oceans, as
‘crossing the bar’ is not an uncommon event. Adjustment requires
considerable technical skill, besides the required safety precautions
associated with opening the CRT display housing. CRTs are sensitive
to magnetic interference, which causes images to shimmer (e.g. if a
transformer or other electro-magnetic source is close to the screen)
or colours change (if unshielded speakers are also too near).
▲ Figure 14.4
Schadt and Helfrich described what is now known as the T.N. effect,
where an electric field applied perpendicular to the plates of an L.C.
cell realigns in the bulk to a uniform nematic with the long molecular
axes lying perpendicular to the plates (homeotropic). In the T.N. state
if cell thickness is much greater than the incident wavelength the
twisted structure guides light through the cell. But under application of
a D.C. voltage the uniform homeotropic nematic no longer guides
light through the sample as waveguide conditions change too fast,
giving high contrast ratios between light and dark states (figure 14.5).
The simplest practical cell is the T.N. cell. Light of one polarisation
passes through the first polaroid (polariser) and then a second
polaroid (analyser). If the second polaroid is twisted by 90º the half
twist structure will transmit polarised light.
NEMATICS. Friedel coined the word ‘nematic’ from the Greek nema,
meaning a thread, and refers to certain thread-like defects (or
disclination lines) which are commonly observed. A schematic
representation of the order in a nematic phase is shown in figure 14.4
and a real optical texture of a typical nematic L.C. phase is shown in
figure 14.6.
Switching speeds
But why all the interest in Ferroelectric Liquid Crystal (F.L.C.) displays
anyway? Two reasons initially, speed and memory (or bistability). For
the various effects which LCDs employ the ‘switch on’ ton and ‘switch
off’ toff times are often quoted at 90% and 10% saturated response
respectively. High-speed devices rely on electron movement, while
thermal and molecular processes are unfortunately slower, but how
slow?
Such analytical F.L.C. phase expressions are few and mostly due to
the patient and enduring work of Dr Frank Leslie, Strathclyde
University, Scotland. Optical data and multilayer modelling for F.L.C.
cells was developed by Elston and Sambles in Exeter, UK, in the
1990s. This enabled horizontal tilt or so-called in-plane tilt, of the
molecular axis to be determined as well as the vertical (out of plane
tilt) with theoretical expressions similar in some respects to those
used in nematic theory and then trying to fit real experimental data to
various theory models. In this way models were found that began to
explain what was going on under an applied voltage.
The Vertical tilt took the form (2/Π)C arctan (A sin 2 (z(Π – B)/d + B)),
where (2/Π)C controls the maximum tilt value, d is the half-cell
thickness and A is a function of applied r.m.s. voltage. Horizontal tilt is
found in a similar way. In our own work, good comparisons of theory
with data were found with and without voltages applied (figure 14.10)
which allowed values for the constants: A, B and C in the above
expression to be found under certain conditions. In 1982, Dr Water
and my external Ph.D. supervisor, Dr Peter Raynes FRS, Head of
Liquid Crystal Research at DERA Malvern, developed the STN.
Liquid crystal molecules aligning in a cell between surfaces with a
natural twist between 240 and 270° give better switching, making
them suitable for notebooks, and more recently mobile phones.
▲ Figure 14.10 Reflectivity for incident and reflected TM polarised radiation from a
3.5 micron thick F.L.C. cell 40 nm I.T.O. coated, with 40 nm Polyimide alignment
layer. (No voltage applied. Data crosses, theory continuous line.)
In the future, LCD advances will have profound implications for
Maritime bridge training. Bridge simulation already plays an important
part in Naval and Merchant Shipping fleets, but development of
individual fully interactive virtual reality experience will revolutionise
things further. One suggestion for both military and civilian displays
applications is to provide heads-up visors for see-through glasses
display where a variety of different types of information can be
displayed more comfortably to the human operator. This information
could be e-mail, data, a high-quality video-link, images or electronic
charts (ECDIS).
History
In 1936, a Hungarian engineer, Kálmán Tihanyi, described the
principle of ‘plasma television’, conceiving the first flat-panel display
system. The monochrome plasma video display was co-invented in
1964 by Bitzer, Slottow and Willson for the PLATO Computer System.
Neon orange monochrome ‘Digivue’ display panels built by glass
producer Owens-Illinois were popular in the early 1970s because
they were rugged and needed neither memory nor circuitry to refresh
images.
They can provide superior contrast ratios and wider viewing angles
than LCDs, and images do not suffer from degradation at high angles
unlike LCDs. Less visible motion blur occurs, due to the high refresh
rates and a fast response time, contributing to superior performance
when displaying content with large amounts of rapid motion.
Plasma is often cited as having better (i.e. darker) black levels (and
higher contrast ratios). Each cell on a plasma display has to be
precharged before it is due to be illuminated (otherwise the cell will
not respond quickly enough) and this precharging means cells cannot
achieve a true black, whereas an LED backlit LCD panel can actually
turn off parts of the screen. Some manufacturers have reduced the
precharge and associated background glow, so that the black levels
on modern plasmas rival CRT. With LCD technology, black pixels are
generated by light polarisation method, but many panels cannot
completely block the underlying backlight.
Screen burn-out
Image burn-out occurs on CRTs and plasma panels when the same
picture is displayed for long periods as can take place with marine
radar showing short-range sea clutter. This causes phosphors to
overheat, losing some of their luminosity to produce a ‘shadow’ image
that is visible with the power off. Burn-out is especially a problem on
plasma panels because they run hotter than CRTs. Plasma displays
also exhibit another image retention issue which is sometimes
confused with screen burn-out. In this mode, when a group of pixels
is run at high brightness (e.g. when displaying white) for an extended
period, a charge build-up in the pixel structure occurs and a ‘ghost
image’ is seen. However, unlike burn-out, charge build-up is transient
and disappears after the image condition that caused the effect has
been removed and a long enough period has been passed.
Until the early 2000s, plasma displays were the most popular choice
for H.D. TV flat panel display as they had many benefits over LCDs.
Beyond plasma’s deeper blacks, increased contrast, faster response
time, greater colour spectrum and wider viewing angle, they also had
much bigger screens than LCDs, and it was believed LCD technology
was suited only to small-sized TVs. However, improvements in LCD
fabrication methods have reduced the technological gap. The
increased size, lower weight, falling prices and often lower electrical
power consumption of LCDs now makes them competitive with
plasma TV sets with screen sizes having increased since the
introduction of plasma displays. In 2010, the shipments of plasma
TVs were estimated at 18.2 million units globally.
ElectroLuminescent Displays
ElectroLuminescent Displays (E.L.D.s) are a type of flat panel display
created by sandwiching a layer of ElectroLuminescent (E.L.) material
such as GaAs between 2 conductors. When current flows, the layer
of material emits visible light. E.L. is an optical and electrical
phenomenon where a material emits light in response to an electric
current passed through it, or to a strong electric field. E.L. works by
exciting atoms by passing an electric current through them, causing
them to emit photons. By varying the material being excited, the
colour of the light emitted can change. An E.L.D. is constructed using
flat, opaque electrode strips running parallel to each other, covered
by a layer of electroluminescent material, followed by another layer of
electrodes, perpendicular to the bottom layer. This top layer must be
transparent to let light escape. At each intersection, the material
emits light, creating a pixel.
History
E.L. from polymer films was first observed by Roger Partridge at the
National Physical Laboratory, UK, with a device made of a 2.2 μm
thick poly(n-vinylcarbazole) film between 2 charge injecting
electrodes. The first diode device was reported at Eastman Kodak by
Tang and Van Slyke in 1987 with a 2-layer structure with separate
hole and electron transporting layers so the recombination and light
emission occur in the middle of the organic layer, resulting in a
reduction in operating voltage and efficiency improvement. In 1990
Burroughes et al. at the Cavendish Laboratory in Cambridge reported
a high-efficiency green light-emitting polymer-based device with 100
nm thick films of poly(p-phenylene vinylene).
▲ Figure 14.12 Theoretical device output response for the OLED shown in figure
14.11. The top curve shows the largest absorption is in the PEOPT layer (A = 1 – R
with T = 0).
Phosphorescent materials
Fabrication
OLED advantages
OLED disadvantages
Outdoor performance
Power consumption
Holographic Displays
We introduce holography as a candidate for future maritime display
devices. One key aim of display technology is the desire to show
dynamic 3D images that appears to ‘float freely in space’, much as
Leia Organa did when projected from R2-D2 to Luke Skywalker in
George Lucas movie Star Wars (incidentally the man who played
Darth Vader in the original Star Wars films worked for my grandfather
in Bristol for some time, but that was not the reason he turned to the
Dark side!). The history of 3D displays, however, began in 1838 when
Charles Wheatstone at Kings’ College London proposed the
stereoscope, based on stereo vision principles. Because human eyes
are separated between 5 and 7 cm, we observe different
perspectives of an object, so the illusion of depth can be created
using two 2D images whose features are slightly offset from each
other. The brain merges these 2 images into a single 3D perspective.
The desire for dynamic 3D images spurred rapid development of
early 3D-movie technology. Stereoscopy using polarised glasses
found wide use in 3D cinemas from 1952. Ideally a 3D display should
render objects as they naturally appear, so 2 orthogonal states, e.g.
left and right circular polarisation, are used to distinguish the left and
right perspectives. These 2 views are then projected onto a highly
reflective screen through orthogonal polarisation filters, and
observer’s polarised glasses then separate the left and right views.
Practice Examples
14.1 An incident photon has a wavelength of 600 nm, what will be the
equivalent energy in electron Volts (eV) (4 decimal places)?
14.2 If an incident photon of wavelength 550 nm strikes a
photocathode having a barium oxide layer with work function = 1.6
eV, what will be the energy of an electron released from the
electrode surface in eV (2 significant figures)?
14.3 If the photon of Question 14.2 were decreased by 5 nm show
using differentiation the expected change in the energy of the
incident photon (2 decimal places).
14.4 If the voltage between the Cathode and Anode of a CRT is 10
000 V, what is the Electric Field generated across the device if the
separation between the electrodes is 10 cm (2 significant figures)?
14.5 With the time-base of a CRT switched off, an unknown voltage is
applied across the CRT’s Y plates. The vertical deflection of the
spot is measured and found to be 5.5 mm. If the voltage sensitivity
of the CRT is 4 V mm–1 what is the potential difference of the
unknown voltage (1 decimal place)?
14.6 Use the Index formula C = (H – L)/(H + L), where H is the
highest reflectivity and L the lowest reflectivity, to estimate the
Index for an unswitched room temperature F.L.C. cell between the
incident angles of the first mode (dip) below the critical angle and
the critical angle itself. Use figure 14.10 for this estimation (2
decimal places).
14.7 Describe the operation of a typical CRT used to deflect an
electron beam across a display screen.
14.8 Describe how a typical Twisted Nematic LCD and ordinary
Nematic LCD device operates. If the Vertical tilt for a Smectic C*
device takes the form (2/Π)C arctan (A sin 2 (z(Π – B)/d + B)),
where (2/Π)C controls the maximum tilt value, d is the half-cell
thickness and A a function of applied r.m.s. voltage, what will be
the vertical tilt in degrees for 2 volts applied if A = 10, B = 3 and C =
2 when z/d=0.5 (2 decimal places)?
14.9 Explain with the aid of a diagram how an OLED operates, and
the important device interfaces.
14.10 Compare the properties of the different display devices
discussed in this chapter.
References
[1] Elston, S., and Sambles, J. R., ‘Determination of the Optic Tensor
Profile in a FLC layer by the Propagation of Optic Modes’,
Ferroelectrics, 1991, Vol. 113, pp. 325–337.
[2] Lavers, C. R., and Sambles, J. R., ‘An Examination of the Optical
Dielectric Tensor of a Liquid Crystal Waveguide’, Ferroelectrics,
1991, Vol. 113, pp. 351–359.
[3] The Matlab procedure used here was adapted by G. F. Burkhard,
E. T. Hoke, M. D. McGehee, Advanced Materials, Vol. 22 (2010), p.
3293 from Leif Pettersson et al.’s work (Journal of Applied Physics,
Vol. 86, No. 1 (1999), p. 487 and Journal of Applied Physics, Vol.
93, No. 7 (2003), p. 3693) to generate a Matlab Transfer Matrix
solution for reflected and absorbed light in the various layers.
Chapter 1
(c) Since the kVA rating figure is the same for primary and secondary
1.2. (a) With the required voltage/turns of 1.5 V for a 440 V supply
Then
(c)
1.3. (a) This solution is made with the aid of the phasor diagram shown by
figure 1.9.
(b)
(d)
1.4. Again, using the phasor diagram of figure 1.9 we have, since this is a
step-down transformer in terms of voltage, the primary current reduced by
the same ratio.
Thus
Using the modified cosine rule, we can write
giving α = 27°38'
and since cos φ2 = 0.8 i.e. φ2 = 36°52'
and φ0 = α + φ2 = 27°38' + 36°52' = 64°30'
so cos φ0 = 0.43
1.5. The substitution of values in the efficiency expression has been made in
kW and kVA
or
1.6.
1.7. For this solution, in accordance with theory, all secondary values are
referred to the primary.
or Efficiency = 97.59%.
(b) For maximum efficiency, Copper loss = Iron loss
Total Losses under this condition = 2 × 0.17 = 0.34 kW
At Full load. Output = 27.5 kVA when copper loss is 0.374 kW
1.9. Although this and the next problem are not entirely concerned with
transformer theory, they have been included to remind the students of
three-phase, line to phase voltage and kW to kVA relationships.
The diagram for the problem is shown.
Secondary phase voltage of transformer
1.10.
Chapter 2
2.1. Using the desired expression
or Efficiency = 97.75%.
Again (b). Transformer efficiency is maximum when the iron losses and
the copper losses are equal.
If the copper loss is 0.28 kW at 25 kVA, it will be
or at
So Maximum efficiency occurs at 19.2 kVA.
For efficiency.
From O.C. test. Iron loss = 115 W
From S.C. test. Copper loss = 312 W
or Efficiency = 96.8%.
For voltage regulation
From S.C. test. Equivalent impedance referred to the primary
2.9. For the equivalent circuit refer to the text and diagrams of Chapter 2,
figure 2.6.
For this problem equivalent resistance referred to the secondary side is
Full-load secondary terminal voltage = 115 – 6.43 = 108.57 V
Chapter 3
3.1. For the voltage transformer, the appropriate ratio would be
. The voltage will not vary appreciably and this ratio
suitable. Normal reading would then occur at about two-thirds full scale.
By using a C.T. ratio, the wattmeter, being used on the 5 A and 110 V
ranges, must have its reading multiplied by the factors of 30 for the
current and 60 for the voltage.
The required constant is 30 × 60 = 1800.
Note: The result could be arrived at, in a more direct fashion, since the
power per phase = = 4 kW or 4000 W. The C.T. ratio = i.e.
reading= = 800 W
It is pointed out that, since the load is balanced and star-connected, the
voltage-coil of the wattmeter is connected between a line and the star-
3.4. Since the power is being measured by one wattmeter, it is evident that a
neutral or star-point is available or has been artificially created and the
total power will be three times the power measured – which is phase
power.
Although phase voltage is applied to the instrument, reduced current in
the ratio of is being applied, i.e. the wattmeter constant for the
∴ V.T. burden = 3.96 + 3.6 = 7.56 say 10 VA. Here again, a transformer
rating greater than the burden is usual.
Thus the single section of winding carries 80 A and the common section
of winding carries (100 – 80) = 20 A
3.7. Normal current rating of L.T. winding
With the L.T. winding connected in series with the H.T. winding so that the
latter forms the common section, the output current would be 40 + 24 = 64
A. Thus the maximum load kVA rating . A load of 12
kVA could therefore be supplied, since the current rating of the windings
would be in direct proportion to the kVA values.
The phasor diagram shows the output voltage between lines as given by
the solution
full load value = 0.5625 × 1.5 × full-load value = 0.844 × full-load value.
Chapter 4
4.1. Back e.m.f. = 230 – (18 × 0 9) = 230 – 16.2 = 213.8 V
Power developed by armature = 213.8 × 18 W
= 3848.4 W = 3.848 kW
Power developed by shaft = 3.848 – 0.112 = 3.736 kW
Alternative solution.
Solving for
Thus .
Thus Ia = 82.56 A where the motor armature current is 82.56 A and the
field current 2.2 A.
∴ Total input current = 84.76 A
The motor input power is 200 × 84.76 W
or Efficiency = 88.5%.
4.4. A machine is rated at 150 kW, 220 V. Therefore the current would be
During testing, it can be assumed that, overloading is not desirable and
therefore the machine which should be fully loaded would be the motor
The motoring machine takes 681.8 A. Its field would be weaker than that
of the generator, since the back e.m.f. would be below 220 V. Therefore
motor field current IfM = 5 A and IaM = 681.8 – 5 = 676.8 A.
The generating machine supplies 681.8 – 140 = 541.8 A
The field current IfG = 7 A so IaG = 541.8 + 7 = 548.8 A
Input from the line = 140 × 220 W
= 2PR + Armature Cu loss of 2 machines + Field Cu loss of 2 machines
So 30 800 = 2PR + 0.02(676.82 + 548.82) + 220(5 + 7)
= 2PR + 0.02(457 550 + 302 000) + (220 × 12)
= 2PR + (0.02 × 759 550) + 2640
= 2PR + 15 191 + 2640 = 2PR + 17 831
4.5 Since E α Φ and N, then new voltage values can be deduced for each
field-current value by multiplying by the speed ratio
If values (amperes)
0 0.1 0.24 0.5 0.77 1.2 1.92 3.43
E at 700 rev/min (volts)
10 20 40 80 120 160 200 240
E at 850 rev/min (volts) = 10 × 1.21 = 12.1 and so for all values it is
12.1 24.2 48.4 96.8 145.2 193.6 242 290.4
(a) The results, when plotted, are shown by the curves in the above figure.
Read 210 V on the 850 rev/min characteristic. Join this point to zero.
This is the field resistance voltage-drop line for self-excitation to 210 V.
The corresponding If = 1.4 A
Similarly read 250 V on the 850 rev/min characteristic. Join this point to
zero. This is the field resistance voltage-drop line for self-excitation to
250 V. Corresponding If = 2.1 A.
Also Torque T α Φ I so T α I2
Thus T2 = 0.25T1
4.7 For a fan T α N12 and for the two speed conditions
Again if Eb1 is the original back e.m.f. and Eb2 the final back e.m.f.
then Eb1 = 110 – (28 × 0.5) = 96 V
Again, generated voltage Eb α Φ N and since Φ α I then Eb α I N
4.9. With R = 0 and a motor resistance of 0.3 Ω, the voltage-drop when the
current is 20 A is 20 × 03 = 6 V
Then back e.m.f. Eb1 = 220 – 6 = 214 V
With R = 3 Ω, a motor resistance of 0.3 Ω and a current of 15 A the back
e.m.f. Eb2 = 220 – 15 × 3.3 = 220 – 49.5 = 170.5 V
Since the generated e.m.f. is proportional to speed and flux then
For the first speed condition N1 = 1200 rev/min, Eb1 = 214 V and the flux
is Φ1. For the second speed condition Eb2 = 170.5 V and Φ2 = 0.8 Φ1
Using the above deduction
or N2 = 1195 rev/min
Torque is proportional to armature current and flux, whereas power output
is proportional to torque and speed. The relationship can therefore be
expressed as
Thus the power output at the original speed is 1.67 times the power output
at the second speed condition.
Chapter 5
5.1. (a)
or
∴ i = 10 – 10e–0.1
Let x = 10e–0.1 Then log x = log 10 – 0.1 log e
or log x = 1 – (0.1 × 0.4343) = 1 – 0.04343
= 0.95657 giving x = 9.048
Thus i = 10 – 9.048 = 0.952 A
(b) 5 = 10(1 – e–t), i.e. 1 – e–t = 0.5
or e–t = 0.5 giving et = 2
So t log e = log 2 and t × 0.4343 = 0.3010
i.e. t = 0.693 s.
5.3. It must be pointed out that, although the discharge resistor is in parallel
with the field when the circuit is connected normally, it is actually in series
with the field coil when the supply is switched off.
Since i = Ie–Rt/L and R = 50 + 50 = 100 Ω
or i = 2 × 10–3 × 0.9607
= 1.9214 mA
The voltage across the capacitor is given by
v = V(1 – e–t/CR) = V – Ve–t/CR
= 200 – 200x or v = 200 – (200 × 0.9607)
So v = 200 – 192.14 = 7.86 V
The voltage across the capacitor can also be obtained thus:
Voltage drop across the resistor = 1.9214 × 10–3 × 100 × 103 = 192.14
So voltage across capacitor = 200 – 192.14 = 7.86 V.
–6 × 2.5 × 106
v = 18.4e–5/1×10 = 18.4e–2
= 1 × 10–6 A or 1 μA (approx.).
5.7. (a) The ‘operate time’ of the relay is when i reaches a value of 10 × 10–3
A.
Substituting in i = I(1 – e–Rt/L)
(b) When the supply is removed, a back e.m.f. is generated by the fall of
linked flux in the relay coil. This causes a current to pass through the
coil and the resistor. The current is given by
i = Ie–Rt/L
The release time of the relay is when i reaches a value of 1 × 10–3 A
applied voltage.
(b) Let i be the charging current when v = 63.2 V. Then 100 – 63.2 = i
100 000
5.9. With D.C. and the rectifier conducting, the circuit current would be
or 100 mA
The moving-coil ammeter would read this and the thermocouple ammeter,
whose reading depends on the temperature difference between two
junctions, which in turn is directly proportional to the heating effect of a
current, will indicate a value dependent on the average heating power, i.e.
on its r.m.s. value. In this case it will read .
Thus as explained, the meter readings are identical. With A.C. only half-
wave conduction occurs and the moving-coil instrument reads the
average over a whole cycle even though current passes for a cycle
only.
peak to peak =
Chapter 6
6.1. A synchronous motor rotates at the speed at which the magnetic field
rotates. The speed of this magnetic field, as for the synchronous speed of
an alternator is decided by the frequency ƒ of the supply and the number
of poles P of the machine.
= 15 × 50
= 750 rev/min
For 60 Hz working, since speed is proportional to frequency then new
speed
Where n = no of slots/pole/phase.
Also, for the generation of e.m.f., E is proportional to flux per pole and
speed.
The flux per pole is in turn proportional to the field current ∴ E α NIf where
It is the field current or E = KNIf
7.4. Full-load line current of the alternator =
Open-circuit phase voltage Eph when a full-load, lagging current at 0.8 P.F.
is switched off, is given by:
Open-circuit line voltage when load is switched off =
For the 0.9 P.F. (leading) condition:
7.6. If the resistance voltage drop is to be taken into account then the
voltage resistive component
= V + IR cosφ
= 230 + 39 × 0.25 × 0.8
= 230 + 7.8 = 237.8 V
From the graph of the previous question it is seen that, the field current
required to produce this voltage on open circuit = 4.05 A. This is F in the
m.m.f. diagram.
The field current required to produce the full-load current of 39 A on short
circuit = 3.45 A. This is (Fa + Fx) of the m.m.f. diagram.
= 16.4 + 12.25 + (8.1 × 3.5 × 0.6)
= 16.4 + 12.25 + 17.01 = 45.66
Thus
Using the graph the generated voltage for 6.75 A would be 293 V.
7.7. The voltage per phase from the given line values are
or E = 279.3 V
From the O.C.C., the field current required to produce this voltage (on
O.C.) = 123 A. If the graphical method of solution is applied, this field
current is shown as OA. The field current required to produce full-load
current on short circuit = 52 A, shown by OB.
The field current required to produce full-load current, at normal voltage, is
the vector sum of these values displaced by (90 + φ) degrees, i.e. O.C.
From the graph, OC = 160 A and this current produces an O.C. phase
voltage of 302 V. Thus when load is switched off, the terminal voltage will
rise to .
A reasonable value of voltage would be the average given by
.
7.8 The voltage per phase from the given line values are
(V) 90 166 229 254 274 306 328 342
Full-load current
Using the Graphical Method of solution, it is seen from the diagram that,
the field current required to produce a voltage of 299.7 V is OA = 9.6 A.
The field current required to produce full-load current on short-circuit =
6.95 A. This is OB.
By constructing a P.F. quadrant and marking off, at point A, a length equal
to OB, point C is obtained.
From the graph OC = 15.8 A and this field current produces a phase
voltage of 350 V.
Here:
= 1000 rev/min
Actual speed N2 = 990 rev/min
∴ Slip speed = 1000 – 990 = 10 rev/min.
8.3.
= 1000 rev/min
Rotor frequency
Thus
8.8.
= 0.32 (lagging)
Current scale. 10 mm = 20 A. (This was for the original diagram before
photographic reduction.)
Note. The copper losses have been divided in the ratio 4:5 by the simple
geometrical construction shown, i.e. DW is divided into 9 parts and the
appropriate parallel drawn to give point C.
Standstill test.
If full voltage is applied, current =
By drawing the line XY parallel to the output line and spaced 295 mm, we
get point A and the output current, OA = 374 A.
P.F. = 0.91 (lagging), as read off the quadrant.
Overall efficiency =
or 86.4%.
= 3.39%
Developed torque is represented by AJ
Here AJ = 30.5 mm or 30.5 A
∴ Developed torque = synchronous watts
Here rev/min .
8.10. No-load.
Current = 40 A
Locked rotor.
Current scale 10 mm = 30 A (on original diagram).
Length of no-load current phasor =
The circle diagram is drawn in the accepted manner and the input line
current is determined by drawing in the line XY parallel to the output line.
The power component of the output current
i.e. the spacing of XY above the output
line.
Line current OA = 25 mm = 75 A
P.F. from quadrant = 0.78 (lagging)
Draw the perpendicular bisector of the output line to cut the circle. Drop
the vertical TU = 46 mm = 138 A – the power component for maximum
power.
Chapter 9
9.1. For the 200 kW load, cos φ1 = 0.8 and sin φ1 = 0.6
For the 50 kW load, cos φ2 is not known
Thus φ2 is unknown, as is also sin φ2.
For the combined load, cos φ = 0.9, φ = 25°50'
sin φ = 0.4357
Apparent power rating of 200 kW load =
9.2. The reactive power of the motor is leading in order to provide P.F.
improvement and is obviously the difference between that of the 200 kW
load and the total load. Thus:
Reactive power of motor = (150 – 121.1)
= 28.9 kVAr (leading)
P.F. of motor
Apparent power of machine No. 1 =
machine
But machine No. 2 supplies a reactive current of 1000 × 0.753 = 753 A
∴ 753 – 492 = 261 A must be passed to No. 1
This goes to make up the 492 A for the load, i.e. 231 + 261
Circulating current = 261 A.
9.4. Machine A drops 1.5 Hz for 150 kW, i.e. 0.01 Hz per kW
Machine B drops 1.5 Hz for 220 kW, i.e. 0.0068 Hz per kW
Let the load on machine A be x kilowatts. Then the load on
Machine B is (200 – x) kilowatts
When the machines are in parallel and of common frequency then:
50 – 0.01 x = 50 – 0.0068 (200 – x)
or 0.01 x = (0.0068 × 200) – 0.0068 x
then 0.0168x = 1.36 or
9.5. Electrical output of motor = (20 × 746) + 500 = 14 920 + 500 = 15 420
W
Also since output
we have
9.6. Armature current is a minimum when the motor P.F. is unity.
Thus here cosφ = 1 and P = VI – I2R
Hence 5000 = 220I – 0.512
or I2 – 440I + 10 000 = 0
Solving I2 – 440I + 2202 = –10 000 + 2202
The angle of retard (α) can be obtained from the Sine Rule, but note that
since the P.F. is unity, IR is in phase with V and the angle between OV and
Er can be obtained from the impedance triangle.
Thus cosine of this angle =
9.9 Stator phase voltage = 440 V. Due to transformer action, the rotor phase
voltage
Output power
or
Point B is thus obtained and AB gives the load line for a load-resistance
value of 300 Ω.
The point of intersection with the characteristic is P and the standing
current is 100 mA.
The power dissipated in the load resistor
= (100 × 10–3)2 × 300 W = 3 W
Alternatively (from the load), for point P, Va = 30 V
∴ Voltage dropped across load resistor
= V – Va = 60 – 30 = 30 V
Power dissipated = Voltage across resistor × Anode current
= 30 × 100 × 10–3 = 3 W
Chapter 11
11.1. Plot the graph from the given data.
(b) Construct D.C. resistance line through origin whose slope is 1.75
kΩ.
Thus when D.C. resistance = 1.75 kΩ
Anode voltage = 3.83V
Anode current = 2.2 mA
11.2. P = VI, where V is the forward voltage of the diode for a current of 5 A.
∴ P = 0.7 × 5 = 3.5 W
The rate of heat dissipation per °C rise is 0.1 J/s or 0.1 W
Thus the rate of heat dissipation for a 70°C rise is = 0.1 × 70 = 7 W
If the voltage drop is constant at 0.7 V then the diode current is given by
.
11.3. (a) Following after example 11.1 the forward D.C. resistance
11.5. (a)
(b) Since the rectified supply is half wave time for discharge
Q = CVr = It
Ripple voltage Vr = 3.24 V
11.7.
Since output voltage is doubled: Output voltage is 141.42 V
11.10. I = IL + Iz = 60 + 1 = 61 mA
V i = 25 volts (r.m.s.)
Rs = 186 Ω minimum
(d) Power rating is based upon maximum zener current.
Vi = Vz + Iz (Rz + Rs) (IL = 0)
35.36 = 24 + Iz (14 + 186)
Chapter 12
12.1. Using the values given, the change in base current can be deduced
from Ib = Ie – Ic
Here δIe = 1 mA and δIc = 0.98 mA
∴ δI = 1 – 0.98 = 0.02 mA
The current gain
12.5. For a constant Vc of –4.5 V, the following values can be read from the
figure.
When the above results are plotted the following can be deduced from the
transfer characteristic.
Thus β = 41.
The current gain value can also be obtained from the transfer
characteristic which can be deduced as shown below. The 3, 5 and 7 V
graphs are drawn and the 6 V line deduced – shown dotted.
Then .
12.9. Here the voltage across RB is the base to collector voltage VBC which
is the collector to emitter voltage less the base-emitter voltage.
∴ VBC = VCE – VBE = 5 – 0.2 = 4.8 V
= 120 kΩ
12.10. Voltage across 1.2 kΩ resistor = 1.2 × 103 × 0.5 × 10–3 = 0.6 V
Voltage across base and + ve line = VB–E + 0.6 = 0.1 + 0.6 = 0.1 + 0.6 =
0.7 V
∴ Voltage across 4.7 kΩ resistor of potential divider = 0.7 V
Current through resistor = = 0.149 × 10–3 A = 0.149 mA
Since no data are given for the base current, this is assumed to be
negligible.
Voltage drop across 47 kΩ resistor
= 0.149 × 10–3 × 47 × 103 = 7.7 V
The supply voltage will need to be 7.7 V.
Chapter 13
13.1.
13.3. For the MDR to remain unchanged the factor inside the 4th root must
be unchanged so that: PNEW × GNEW × AEFF NEW = POLD × GOLD × AEFF
OLD
Therefore: 1.6POLD × 1.3GOLD × AEFF NEW = POLD × GOLD × AEFF OLD
So 1.6 × 1.3 AEFF NEW = 1 × AEFF OLD
So AEFF NEW = 0.48 AEFF OLD or a 52% decrease in Antenna Area would
give this result.
13.4.
Chapter 14
incident photon.
14.2. for the incident photon.
But the photon needs to overcome the work function which is 1.6 eV.
Hence the emitted electron has kinetic energy = 2.25 – 1.6 = 0.65 eV.
14.4.
17. Show that 3 sine-wave A.C. currents, displaced from one another
by 30°, can be represented (a) graphically by drawing their
waveforms and (b) by phasors. If the currents each have a
maximum value of 100 A, calculate the resultant maximum value.
What is its r.m.s. value?
18. Find the current flowing in each branch of the following circuit. A
200 V D.C. supply charges, through a 10 Ω resistor, two batteries
A and В in parallel.
A has an e.m.f. of 108 V and internal resistance 0.24 Ω
B has an e.m.f. of 105 V and internal resistance 0.26 Ω.
20. Ten 2 V batteries are connected (a) in series and (b) in parallel to
an external resistance which remains the same for both
conditions. If the power dissipated in the external resistance is 15
W for the parallel connection and 500 W for the series connection,
find the internal resistance of each cell and the circuit current in
each case.
28. Explain what is meant by, and the significance of the following
terms: (a) voltage stabilisation, (b) impedance, (c) rectification, and
(d) grid bias voltage.
= 314.28 Ω
Thus
Also or L = Flux-linkages/ampere
8. Let R = the resistance per phase and V the voltage between lines.
For the Star connection:
Total power =
Thus I2 = 8.55 A
Secondary current =
Under this condition the armature voltage drop would be 421 × 0.5
= 210.5 V, i.e. back e.m.f. will be 9.5 V. This would be explained by
a reduced flux, the main flux being weakened by the armature
reaction effect. Since T α Φ Ia then Φ will be reduced in proportion
to the armature current increase so that here T3 = T2 = T1. So this
value of armature current can be discounted as an answer.
12. Initial condition.
Lighting load 100 kW cos φ = 1 sin φ = 0
i.e. Apparent power =
= 0.98 (leading).
13. Current from +ve to –ve line through fault to earth
The voltage drop between the +ve line and earth = voltage across
one lamp
This voltage drop = 7.33 × 10 = 73.33 V
The voltage drop between the –ve line and earth = voltage across
the other lamp
This voltage drop = 7.33 × 5 = 36.65 V
Additional load on generator = 7.33 × 110 = 806.3 W
= 0.81 kW
14. This is a series circuit and since the current and voltage are in
phase then the condition is one of resonance. The respective
voltage phasors for the values of voltage across the inductor and
capacitor are equal in magnitude, but in phase opposition.
At resonance the current
= 348.4 m
i.e. fault is 348.4 m from the supply point.
16. Initially at balance (a)
Solving
920 = 102.4IA + 100IB
and 95 × 10.24 = (10 × 10.24IA) + (10.26 × 10.24IB)
giving 920 = 1024IA + 100IB (c)
19. For series resonance the voltage drop due to the reactance of the
inductor equals that across the capacitor of IXL = IXC whence XL =
Xc
We are also given for the series condition and for the
parallel condition
23.
= 0.2812 kW
Similarly secondary current
I2 = 397.7 A
∴ Secondary copper loss =
= 0.237 kW
Total copper loss PCu = 0.2812 + 0.237 = 0.5182 kW
Then by plotting loge Ia to a base of loge Va the slope and the value
of k is obtained thus:
From the graph n is the slope =
Copyright © Christopher Ralph Lavers and Adlard Coles Nautical 1970, 1977,
2014
The right of the author to be identified as the author of this work has been asserted
by him in accordance with the Copyright, Designs and Patents Act, 1988.
A CIP catalogue record for this book is available from the British Library.
Note: while all reasonable care has been taken in the publication of this book, the
publisher takes no responsibility for the use of the methods or products described
in the book.
To find out more about our authors and books visit www.bloomsbury.com. Here
you will find extracts, author interviews, details of forthcoming events and the
option to sign up for our newsletters.