The document is a routine test certificate from Havells India Limited for a 3C X 185 SQ.MM A2XFY 6.35/11 KV cable supplied to M/s K POWER CONTROL. The test results show that the cable from drum HT C21 withstood the high voltage test at 21 kV AC for 5 minutes and had conductor resistances within specified limits, with less than 5% partial discharge.
The document is a routine test certificate from Havells India Limited for a 3C X 185 SQ.MM A2XFY 6.35/11 KV cable supplied to M/s K POWER CONTROL. The test results show that the cable from drum HT C21 withstood the high voltage test at 21 kV AC for 5 minutes and had conductor resistances within specified limits, with less than 5% partial discharge.
The document is a routine test certificate from Havells India Limited for a 3C X 185 SQ.MM A2XFY 6.35/11 KV cable supplied to M/s K POWER CONTROL. The test results show that the cable from drum HT C21 withstood the high voltage test at 21 kV AC for 5 minutes and had conductor resistances within specified limits, with less than 5% partial discharge.