You are on page 1of 1

P a g e | 39

TEST CERTIFICATE OF ISOLATOR AKSHAR ELECINFRA PVT. LTD.


Client ADANI GREEN ENERGY (MP) LTD., DAYAPAR Tested On 22/07/2023
Plant 725MW WIND POWER PLANT, DAYAPAR, GUJARAT Tested By ABHISEK B
Location TRAFO-5 BAY ( Isolator 89 B) Comp. Code P-437
1.0 EQUIPMENT DETATILS :
GR POWER
1.1 Make
SWITCHGEAR LTD
1.2 Isolator Sr. No. 2888/16675
1.3 Model (Isolator) -
1.4 Type of Isolator HDB
1.5 Voltage(Ur) 220 KV
1.6 STC (kA/Sec) (Ik/Tk) 40KA/3 Sec
1.7 Current (Ir) 2000 A
1.8 Type of Drive MOTOR
1.9 Motor Voltage (AC) 415VAC
2.0 Control Voltage (DC) 110 VDC

2.0 GENERAL CHECK-UP :


2.1 Check for physical damage if any OK
2.2 Check enclosure for cleanliness and vermin proofing OK

3.0 CONTROL CIRCUITS AND OPERATIONAL CHECKS :


3.1 Check electrical closing-opening OK
3.2 Remote closing / interlocks circuits checked OK
3.3 Check for signal lamps / annunciation circuits feature OK
3.4 Check panel space-heater circuit OK
4.0 Isolator IR Test
PHASE R-E Y-E B-E
VALUES in GΩ 510 GΩ 484 GΩ 397 GΩ

5.0 CONTACT RESISTANCE TEST :


PHASE R-R’ Y-Y’ B-B’
VALUES in µΩ 54.6 59.9 54.7
7. 0 REMARKS : TESTED OK.

Tested by Akshar Witness by Adani Witness by Adani


Name SOUMYA KANTI BHOWMICK
Sign
Date 04/06/2019
AKSHAR ELECINFRA PVT. LTD.

You might also like