APPLICATION NOTE

Metasys Integrator® Vilter® Application

lntroduction Page 3
● Application Details *3
● Component Requirements 4
● Vendor Contact Information 6
● Design Considerations 6

Cable Connections 7
● Cable Pinouts 7
● Connecting the Cable 7

Metasys Integrator Setup 9

Point Mapping Tables 11


● Reciprocating Compressor 11
● Twin Screw Compressor 13
● Single Screw Compressor 15
● Evaporative Condenser 17

Metasys Network Setup 19


● Mapping to a CS Object 19

* Indicates those sections where changes have occurred since the last printing.

© 1994 Johnson Controls, Inc. 1


Code No. LIT-6295520
2 Metasys Integrator—Metasys Integrator Vilter Application
lntroduction
This document explains Metasys Integrator Vilter Manufacturing Corporation
applications. Use this document with the Metasys Integrator Technical Bulletin, which
provides information on installing and commissioning Metasys Integrator. For
information on Vilter equipment, see Vilter documentation (obtainable from Vilter
representative).

Application Metasys Integrator allows Vilter equipment to become an integral part of the Metasys
and Metasys Companion Networks. Once Vilter refrigeration controllers are connected
Details to a Metasys or Companion Network via the Metasys Integrator, their data is available to
the full complement of Metasys Facility Management System (FMS) features, including
Change-of-State (COS) monitoring, alarm notification, scheduling, trend, and totalization.
Metasys Integrator transmits both status information and commands between the Vilter
devices and the Metasys or Companion Network.
Metasys Integrator supports four Vilter controllers:
● Reciprocating Compressor
● Twin Screw Compressor
● Single Screw Compressor
● Evaporative Condenser
One controller (of any type) is designated as a master controller, and acts as the interface
between Vilter equipment and non-Vilter devices (such as Metasys Integrator). The
master controller connects to Metasys Integrator through the RS-232 Bus, and to the other
controllers through the RS-485 8044 BITBUS.
Each Metasys Integrator vendor port can connect to one master controller. Each master
controller can connect up to 250 Vilter controllers.
Figure 1 shows Vilter and Metasys integration, and Figure 2 shows Vilter and Metasys
Companion integration.
N1LAN

Standard NCU
RS-232 Reciprocating
BUS Compressor
(Master Node)
RS-485 8044
Metasys BITBUS
Integrator
Twin Screw Single Screw Evaporative
Compressor Compressor Condenser
UNT

N2 Bus
vilter1

Figure 1: Vilter and Metasys Integration

Metasys Integrator—Metasys Integrator Vilter Application 3


PC-Version Panel Version/LTD

or

Converter

Reciprocating
RS-232 Compressor
(Master Node)
Metasys RS-485 8044
Integrator BITBUS

Twin Screw Single Screw Evaporative


UNT
Compressor Compressor Condenser

N2 Bus

voltcomp

Figure 2: Vilter and Metasys Companion Integration

Component To integrate Vilter equipment, you’ll need the following components:


● properly installed Vilter devices
Requirements ● RS-232 cable (for connecting the master controller to Metasys Integrator)
● Metasys Integrator
● N2 Bus (for connecting Metasys Integrator to the Metasys or Companion Network)
● portable PC for downloading vendor communication tables (.VCT files) and
network setup information into Metasys Integrator, and for running diagnostics
● cable for connecting portable PC to Metasys Integrator
● the correct vendor communication table (.VCT file) to download into Metasys
Integrator (supplied on Metasys Integrator diskette)
This document describes the RS-232 cable and the vendor communication tables. Vilter
documentation describes their equipment. The remaining components are described in
the Metasys Integrator Technical Bulletin.

Metasys Release To integrate Vilter equipment into the Metasys Network, you’ll need:
Requirements ● Metasys OWS software Release 4.0 or higher
● Metasys Integrator software/firmware Release 2.0 or higher

Metasys To integrate Vilter equipment into the Metasys Companion Network, you’ll need:
Companion ● Metasys Companion Release 4.0 or higher
Release ● Metasys Integrator software/firmware Release 2.0 or higher
Requirements
Vendor Integration between Metasys Integrator and Vilter has been tested with the equipment
Component listed in Table 1. Changes to this equipment or integration of Vilter products not
Requirements discussed in this document will require additional software development and testing by

4 Metasys Integrator—Metasys Integrator Vilter Application


Systems Products. For information on integrating other products, call the Installation and
Retrofit Systems Team in Milwaukee (extension 4662).

Metasys Integrator—Metasys Integrator Vilter Application 5


Table 1: Vilter Part and Software Version Numbers
Vilter Product Style Number Software/Firmware
Version Number*
VMC Reciprocating VMC VMC3.XX
Compressor
VRS Twin Screw Compressor VRS VRS2.XX
VSS Single Screw Compressor VSS VSS4.XX
Evaporative Compressor ALL VCF2.XX
* XX following the revision number indicates any revision of that level is valid.

Vendor Contact Vilter Manufacturing Corporation


2217 South First Street
Information Milwaukee, WI 53207
Technical Support
Phone: (414) 744-0111
FAX: (414) 744-2084

Design When integrating Vilter equipment, keep the following considerations in mind:
● Make sure all Vilter equipment is set up, started, and running properly before
Considerations attempting to integrate with the Metasys or Companion Network. (The Vilter
representative is responsible for operation of refrigeration controllers.)
● Make sure one of the controllers is designated as the master controller. (The Vilter
representative is responsible for defining the master controller.)
● Make sure the controller baud rate is set to 1200. (The Vilter representative is
responsible for setting the controller’s baud rate.)
● RS-232 cable distance between Metasys Integrator and the master controller can be
a maximum of 50 feet.
● Cable distance between the master controller and the last controller can be a
maximum of 4000 feet. Up to 28 controllers can be supported without the use of a
repeater (each repeater counts as one device).

6 Metasys Integrator—Metasys Integrator Vilter Application


Cable Connections

Cable Pinouts Use the following cable pinouts for the RS-232 connection between Metasys Integrator
and the Vilter master controller.

Vendor Port A or B RS-232C Terminal


on Integrator Block on the Master Controller

DB-9 Female

Signal Pin Pin Signal


RS-232
RD 2 6 TXD
TD 3 5 RXD
GND 5 1 GND
2 +5V
9 DSR
VILTER2
(50 ft. maximum)

Figure 3: Cable Pinouts

Connecting the Connect the female end of the RS-232 cable to either Vendor Port A or Vendor Port B on
Metasys Integrator. Connect the other end of the cable to the RS-232 terminal block on
Cable the master controller.

Vilter
Metasys Master
Integrator Controller

RS-232 Cable 6 RS-232


Vendor Port 5
A or B 1
Terminal
2 Block
9

VILTER3

Figure 4: Port to Port Connection

Metasys Integrator—Metasys Integrator Vilter Application 7


8 Metasys Integrator—Metasys Integrator Vilter Application
Metasys Integrator Setup
To set up Metasys Integrator, you’ll use a portable PC connected to Metasys Integrator’s
Terminal Port. Metasys Integrator setup involves:
● downloading the correct vendor communication table (.VCT file)
● setting up the ports
● assigning network addresses to the controllers
The following table provides information specific to Vilter applications. For detailed
procedures, see the Metasys Integrator Technical Bulletin.
Table 2: Metasys Integrator Setup for Vilter Applications
Vendor Communication Table (.VCT File)
Reciprocating Compressor VM_RECIP.VCT
Twin Screw Compressor VM_TSCRW.VCT
Single Screw Compressor VM_SSCRW.VCT
Evaporative Condenser VM_EVPCD.VCT
Port Setup
Baud Rate 1200
Word Length 8
Stop Bits 1
Parity None
Interface RS-232
Network Setup
Vendor Address Master Controller 0 only
Reciprocating Compressor 5-49
Twin Screw Compressor 50-99
Single Screw Compressor 100-149
Evaporative Condenser 150-174
Timeout Value 5000 ms
Poll Delay 55 ms
Performance Guide
Approximate Scan Time
(For a single N2 address)
Reciprocating Compressor 3 seconds
Twin Screw Compressor 3 seconds
Single Screw Compressor 3 seconds
Evaporative Condenser 3 seconds

Metasys Integrator—Metasys Integrator Vilter Application 9


10 Metasys Integrator—Metasys Integrator Vilter Application
Point Mapping Tables
The following tables (one for each application) show the points available for mapping in
the Vilter controllers.

Reciprocating Table 3: Reciprocating Compressor


Compressor NPT1 NPA2 Unit Description
To get the hardware AI 1 DegF Suction Temperature
reference for AI 2 DegF Discharge Temperature 1
mapping points to AI 3 DegF Discharge Temperature 2
CS object attributes AI 4 DegF Oil Temperature
(via the software AI 5 PSI Suction Pressure
model), combine the
AI 6 PSI Discharge Pressure 1
NPT (Network Point
Type) and NPA AI 7 PSI Discharge Pressure 2
(Network Point AI 8 PSI Filter Outlet Pressure
Address). For AI 9 PSI Filter Inlet Pressure
example, the AI 10 PSI Calculated Oil Pressure
hardware reference AI 11 PSI Calculated Filter Differential Pressure
for the Discharge
AI 12 Amps Motor Current
Temperature 2 is
AI3. AI 13 % Percent Capacity
AI 14 Hour Compressor Runtime
BI 1 Compressor On 0-no, 1-yes
BI 2 Alarm Active 0-ok, 1-alarm
BI 3 Trip Active 0-ok, 1-trip
BI 4 Mode 0-local, 1-central
BI 5 Comp Wait - Suction Pressure 0-ok, 1-wait
BI 6 Comp Wait - Max Time @ Min Cap 0-ok, 1-wait
BI 7 Comp Wait - Hot Starts/Hour 0-ok, 1-wait
BI 8 Comp Wait - Anti recycle Timer 0-ok, 1-wait
BI 9 Comp Wait - Remote Command 0-ok, 1-wait
BI 10 Hi Suction Pulldown Control 0-off, 1-active
1 Network Point Type
2 Network Point Address
Continued on next page . . .

Metasys Integrator—Metasys Integrator Vilter Application 11


NPT1 NPA2 Unit Description
(Cont.)
BO 1 Mode Off/Auto 0-off, 1-auto
BO 2 Alarm Acknowledge 0-n/a, 1-ack
BD 1 Suction Temp Alarm 0-ok, 1-alarm
BD 2 Discharge Temp 1 Alarm 0-ok, 1-alarm
BD 3 Discharge Temp 2 Alarm 0-ok, 1-alarm
BD 4 Oil Temp Alarm 0-ok, 1-alarm
BD 5 Suction Pressure Alarm 0-ok, 1-alarm
BD 6 Discharge Pressure 1 Alarm 0-ok, 1-alarm
BD 7 Discharge Pressure 2 Alarm 0-ok, 1-alarm
BD 8 Filter Outlet Pressure Alarm 0-ok, 1-alarm
BD 9 Filter Pressure Alarm 0-ok, 1-alarm
BD 10 Oil Pressure Alarm 0-ok, 1-alarm
BD 11 Suction Temp Trip 0-ok, 1-trip
BD 12 Discharge Temp 1 Trip 0-ok, 1-trip
BD 13 Discharge Temp 2 Trip 0-ok, 1-trip
BD 14 Oil Temp Trip 0-ok, 1-trip
BD 15 Suction Pressure Trip 0-ok, 1-trip
BD 16 Discharge Pressure 1 Trip 0-ok, 1-trip
BD 17 Discharge Pressure 2 Trip 0-ok, 1-trip
BD 18 Filter Outlet Pressure Trip 0-ok, 1-trip
BD 19 Filter Pressure Trip 0-ok, 1-trip
BD 20 Oil Pressure Trip 0-ok, 1-trip
BD 21 Motor Aux Safety Trip 0-ok, 1-trip
BD 22 Aux #1 Safety Relay Trip 0-ok, 1-trip
1 Network Point Type
2 Network Point Address

12 Metasys Integrator—Metasys Integrator Vilter Application


Twin Screw Table 4: Twin Screw Compressor
NPT1 NPA2 Unit Description
Compressor
AI 1 DegF Suction Temperature
AI 2 DegF Discharge Temperature
AI 3 DegF Spare Temperature
AI 4 DegF Oil Injection Temperature
AI 5 PSI Suction Pressure
AI 6 PSI Discharge Pressure
AI 7 PSI Manifold/Filter Outlet Pressure
AI 8 PSI Filter Inlet Pressure
AI 9 PSI Calculated Oil Pressure
AI 10 PSI Calculated Filter Differential Pressure
AI 11 Amps Motor Current
AI 12 % Percent Capacity
AI 13 Hour Compressor Runtime
BI 1 Compressor On 0-no, 1-yes
BI 2 Alarm Active 0-ok, 1-alarm
BI 3 Trip Active 0-ok, 1-trip
BI 4 Mode 0-local, 1-central
BI 5 Comp Wait - Suction Pressure 0-ok, 1-wait
BI 6 Comp Wait - Remote Command 0-ok, 1-wait
BI 7 Comp Wait - Hot Starts/Anti recycle 0-ok, 1-wait
BI 8 Comp Wait - Prelube Timer 0-ok, 1-wait
BI 9 Comp Wait - Percent Capacity 0-ok, 1-wait
BI 10 Comp Wait - Oil Pressure 0-ok, 1-wait
1 Network Point Type
2 Network Point Address
Continued on next page . . .

Metasys Integrator—Metasys Integrator Vilter Application 13


NPT1 NPA2 Unit Description
(Cont.)
BO 1 Mode Off/Auto 0-off, 1-auto
BO 2 Alarm Acknowledge 0-n/a, 1-ack
BD 1 Suction Temp Alarm 0-ok, 1-alarm
BD 2 Discharge Temp Alarm 0-ok, 1-alarm
BD 3 Lo Oil Injection Temp Alarm 0-ok, 1-alarm
BD 4 Hi Oil Injection Temp Alarm 0-ok, 1-alarm
BD 5 Suction Pressure Alarm 0-ok, 1-alarm
BD 6 Discharge Pressure Alarm 0-ok, 1-alarm
BD 7 Manifold Pressure Alarm 0-ok, 1-alarm
BD 8 Percent Capacity Alarm 0-ok, 1-alarm
BD 9 Run Oil Pressure Alarm 0-ok, 1-alarm
BD 10 Filter Pressure Start Alarm 0-ok, 1-alarm
BD 11 Filter Pressure Run Alarm 0-ok, 1-Alarm
BD 12 Suction Temp Trip 0-ok, 1-trip
BD 13 Discharge Temp Trip 0-ok, 1-trip
BD 14 Lo Oil Injection Temp Trip 0-ok, 1-trip
BD 15 Hi Oil Injection Temp Trip 0-ok, 1-trip
BD 16 Suction Pressure Trip 0-ok, 1-trip
BD 17 Discharge Pressure Trip 0-ok, 1-trip
BD 18 Manifold Pressure Trip 0-ok, 1-trip
BD 19 Percent Capacity Trip 0-ok, 1-trip
BD 20 Run Oil Pressure Trip 0-ok, 1-trip
BD 21 Filter Pressure Start Trip 0-ok, 1-trip
BD 22 Filter Pressure Run Trip 0-ok, 1-trip
BD 23 Motor Aux Safety Trip 0-no, 1-trip
BD 24 Aux #1 Safety Relay Trip 0-no, 1-trip
1 Network Point Type
2 Network Point Address

14 Metasys Integrator—Metasys Integrator Vilter Application


Single Screw Table 5: Single Screw Compressor
NPT1 NPA2 Unit Description
Compressor
AI 1 DegF Suction Temperature
AI 2 DegF Discharge Temperature
AI 3 DegF Oil Separator Temperature
AI 4 DegF Oil Injection Temperature
AI 5 PSI Suction Pressure
AI 6 PSI Discharge Pressure
AI 7 PSI Manifold/Filter Outlet Pressure
AI 8 PSI Filter Inlet Pressure
AI 9 PSI Calculated Differential Pressure
AI 10 PSI Calculated Run Cycle Monitor Pressure
AI 11 PSI Calculated Allow Start Pressure
AI 12 PSI Calculated Filter Differential Pressure
AI 13 Amps Motor Current
AI 14 % Percent Capacity
AI 15 % Percent Volume
AI 16 Hour Compressor Runtime
BI 1 Compressor On 0-no, 1-yes
BI 2 Alarm Active 0-ok, 1-alarm
BI 3 Trip Active 0-ok, 1-trip
BI 4 Mode 0-local, 1-central
BI 5 Comp Wait - Suction Pressure 0-ok, 1-wait
BI 6 Comp Wait - Remote Command 0-ok, 1-wait
BI 7 Comp Wait - Hot Starts/Anti recycle 0-ok, 1-wait
BI 8 Comp Wait - Percent Capacity 0-ok, 1-wait
BI 9 Comp Wait - Percent Volume 0-ok, 1-wait
BI 10 Comp Wait - Oil Pressure 0-ok, 1-Wait
1 Network Point Type
2 Network Point Address
Continued on next page . . .

Metasys Integrator—Metasys Integrator Vilter Application 15


NPT1 NPA2 Unit Description
(Cont.)
BO 1 Mode Off/Auto 0-off, 1-auto
BO 2 Alarm Acknowledge 0-n/a, 1-ack
BD 1 Suction Temp Alarm 0-ok, 1-alarm
BD 2 Discharge Temp Alarm 0-ok, 1-alarm
BD 3 Lo Oil Separator Temp 1 Alarm 0-ok, 1-alarm
BD 4 Lo Oil Separator Temp 2 Alarm 0-ok, 1-alarm
BD 5 Lo Oil Injection Temp Alarm 0-ok, 1-alarm
BD 6 Hi Oil Injection Temp Alarm 0-ok, 1-alarm
BD 7 Suction Pressure Alarm 0-ok, 1-alarm
BD 8 Discharge Pressure Alarm 0-ok, 1-alarm
BD 9 Manifold Pressure Alarm 0-ok, 1-alarm
BD 10 Percent Capacity Alarm 0-ok, 1-alarm
BD 11 Percent Volume Alarm 0-ok, 1-alarm
BD 12 Run Cycle Oil Press Alarm 0-ok, 1-alarm
BD 13 Filter Pressure Start Alarm 0-ok, 1-alarm
BD 14 Filter Pressure Run Alarm 0-ok, 1-Alarm
BD 15 Suction Temp Trip 0-ok, 1-trip
BD 16 Discharge Temp Trip 0-ok, 1-trip
BD 17 Lo Oil Separator Temp 1 Trip 0-ok, 1-trip
BD 18 Lo Oil Separator Temp 2 Trip 0-ok, 1-trip
BD 19 Lo Oil Injection Temp Trip 0-ok, 1-trip
BD 20 Hi Oil Injection Temp Trip 0-ok, 1-trip
BD 21 Suction Pressure Trip 0-ok, 1-trip
BD 22 Discharge Pressure Trip 0-ok, 1-trip
BD 23 Manifold Pressure Trip 0-ok, 1-trip
BD 24 Percent Capacity Trip 0-ok, 1-trip
BD 25 Percent Volume Trip 0-ok, 1-trip
BD 26 Start Cycle Oil Pressure Temp 0-ok, 1-trip
BD 27 Run Cycle Oil Press Trip 0-ok, 1-trip
BD 28 Filter Pressure Start Trip 0-ok, 1-trip
BD 29 Filter Pressure Run Trip 0-ok, 1-trip
BD 30 Motor Aux Safety Trip 0-no, 1-trip
BD 31 Aux #1 Safety Relay Trip 0-no, 1-trip
1 Network Point Type
2 Network Point Address

16 Metasys Integrator—Metasys Integrator Vilter Application


Evaporative Table 6: Evaporative Condenser
NPT1 NPA2 Unit Description
Condenser
AI 1 DegF Ambient Temperature
AI 2 DegF Spare Temperature #1
AI 3 DegF Spare Temperature #2
AI 4 DegF Spare Temperature #3
AI 5 PSI Condenser Pressure
AI 6 Amps Motor Current
AI 7 % Percent Capacity
AI 8 # Total Fans On
AI 9 # Total Pumps On
AI 10 Hour Condenser Runtime
BI 1 Condenser Control On 0-no 1-yes
BI 2 Alarm Active 0-ok, 1-alarm
BI 3 Trip Active 0-ok, 1-trip
BI 4 Mode 0-local, 1-central
BI 5 Comp Wait - Condenser Pressure 0-ok, 1-wait
BI 6 Ambient Temperature Alarm 0-ok, 1-alarm
BI 7 Condenser Pressure Alarm 0-ok, 1-alarm
BI 8 Ambient Temperature Temp 0-ok, 1-trip
BI 9 Condensing Pressure Trip 0-ok, 1-trip
BO 1 Mode Off/Auto 0-off, 1-auto
BO 2 Alarm Acknowledge 0-n/a, 1-ack
1 Network Point Type
2 Network Point Address

Metasys Integrator—Metasys Integrator Vilter Application 17


18 Metasys Integrator—Metasys Integrator Vilter Application
Metasys Network Setup
Metasys Network Setup is described in the Metasys Integrator Technical Bulletin. This
section contains details specific to Vilter applications.

Mapping to a Table 7: Software Model and CS Object Definition


CS Object Application Software Model Display Attribute NT Command
(on Models diskette) (recommended) Attribute
(recommended)
Reciprocating VM_RECIP.DDL
Compressor
Twin Screw VM_TSCRW.DDL AI5 BI1
Compressor Suction Pressure Compressor On
Single Screw VM_SSCRW.DDL
Compressor
Evaporative VM_EVPCD.DDL AI1 BI1
Condenser Ambient Condenser Control
Temperature On

Metasys Integrator—Metasys Integrator Vilter Application 19


Notes

Controls Group FAN 629.5


507 E. Michigan Street Metasys Connectivity Technical Manual
P.O. Box 423 Metasys Integrator Release 5.0
Milwaukee, WI 53201 Printed in U.S.A.