You are on page 1of 6

Design and Analysis of Different Passive Damping

for Grid-Connected LCL filters to Achieve


Desirable System Performance
Shenyiyang Bian, Jinming Xu, Qiang Qian, Shaojun Xie
College of Automation Engineering
Nanjing University of Aeronautics and Astronautics
Nanjing, Jiangsu, China
Email: 296347797@qq.com

Abstract—The LCL filter has excellent high-frequency LCL filter and multituned traps filter with shunt RC damper,
harmonics attenuation capability, However, due to the inherent and the parameters designed in this paper ensure the minimal
resonance of LCL filter, it is necessary to add damping strategy. peak in the filter admittance. This paper also designs and
Although there are many passive damping schemes, such as compares the parameters of several LCL filter and multituned
series R, series RL, shunt RC and shunt RLC, there are few traps filter with shunt RC damper. In [7], various passive
studies on the performance comparisons of these passive damping schemes were evaluated at different switching
damping schemes. Besides, it is hard to know which one is cost- frequencies, including the following aspects: the value of the
effective, given that higher-order damping methods complicate inductor and capacitor, the passive component storage energy
the power circuit and require more components. Therefore, this
and the damping loss. The shortcoming of that paper is that
paper aims to study the performances, merits and applicable
occasions of various types of passive damping schemes. At first,
the parameters of the passive damping and LCL filters in this
based on the traditional LCL filter parameter design method, article were not optimized, and the detailed design method of
combined with the design criteria derived from the view of the LCL filter parameters with passive damping is not given,
improving the system dynamic, the unified design flowchart of neither.
the LCL filter with various passive damping is proposed. Then, In summary, there are many documents discussing filter
for a 5kW single-phase grid-connected inverter, the parameters parameter design methods. But the performance comparison
of LCL filter with above four passive damping schemes are of various passive damping schemes has not been studied.
selected. Their performances are evaluated from the aspects of
Hence, this paper compares the performance of different
damping loss, volume and weight. Finally, comparative results
have shown the applicable occasions of different passive
passively damped LCL filters with optimal design from the
damping schemes. perspective of damping loss and total energy storage under the
premise of achieving desirable system performance, and gives
Keywords—grid-connected inverter; digital control; LCL guidance on selecting damping schemes. The damping
filter; passive damping schemes discussed in this paper include series R, series RL,
shunt RC, and shunt RLC, as shown in Fig. 1.
I. INTRODUCTION
II. MATHEMATICAL MODEL AND ANALYSIS OF SINGLE-
Nowadays, the LCL filter has been widely used in
PHASE GRID-CONNECTED LCL INVERTER
photovoltaic grid-connected inverters because of its excellent
high-frequency attenuation capability. However, the LCL Fig. 2 shows the structure and control block diagram of a
filter also has the disadvantage of having resonance peaks at single-phase grid-connected LCL inverter under digital
the resonance frequency. Passive damping can suppress the control which adopts single grid current control. Among them,
resonance peak. This method is easy to implement, but the Udc is the DC voltage, uinv is the inverter side voltage, i1 is the
additional damping resistor will cause the filter to have inverter side current, ig is the grid current, ug is the grid
damping loss. So it is necessary to optimize the filter and voltage, iref is the current reference, Gc is the current regulator,
passive damping parameters. [1]-[2] proposed a LCL filter Gd is the delay time.
parameter design method that does not require damping and Thus, the open-loop transfer function of the single phase
can guarantee the excellent performance of the inverter grid-connected LCL inverter can be written as:
system. This method considers both the filter filtering
performance and the parameter design method of the stability i
GOL ( s ) = K PWM Gc ( s )Gd ( s )Guginv ( s ) (1)
and dynamic performance of the inverter system, and gives the
flow chart of the LCL filter parameter design of the single loop The LCL filter and its derived filter structure (e.g., LCL
control. However, because the stability is achieved by placing filter with passive damping) can be represented by the
the LCL resonance frequency in a certain range, the size of structure shown in Fig. 3. Then the transfer function of uinv to
selected LCL parameters may not be minimal. Based on the ig is:
traditional LCL filter design steps, the paper [3] gives an
optimization scheme which makes the inductance minimum, i Z3
i.e., to minimize the filter cost, and [4] proposes an optimal Guginv ( s) = (2)
Z1Z 2 + Z1Z3 + Z 2 Z 3
design considering the limitation of total harmonics. In [5], a
parameter design method of LCL filter with shunt RC When digital control is used, the inherent delay caused by
damping is proposed. This method uses a split-capacitance digital control will influence system performance to some
ratio as a variable to make a trade-off between effective extent. The digital control delay is mainly divided into two
damping and power loss in a shunt damping circuit, but does parts, one is the delay of sampling and calculation, and the
not consider the stability and robustness of the inverter other is the delay caused by the digitally controlled PWM
system. An optimization procedure was proposed in [6] for the process, which has the characteristics of the zero-order holder.

978-1-5386-6054-6/18/$31.00 ©2018 IEEE

Authorized licensed use limited to: ULAKBIM UASL - MIDDLE EAST TECHNICAL UNIVERSITY. Downloaded on March 03,2022 at 12:05:04 UTC from IEEE Xplore. Restrictions apply.
i1 ig
Li Lg Li Lg
Cf Cf Q1 Q3

Rd Rd Ld Udc ug
Uinv Filter
(a) (b) Q2 Q4

Li Lg Li Lg
Cd Cd
Cs Cs
Rd Rd Ld
PWM iref
Gd Gc
modulator
(c) (d)
Fig. 2.Single-phase grid-connected LCL filter block diagram
Fig. 1. Four Common Passive Damping Schemes for LCL Filters (a)
series R. (b) series RL. (c) shunt RC. (d) shunt RLC.
i1 ig
Z1 Z2
Since the sampling switch can be equivalent to the expression Uinv Ug
1/Ts, the transfer function of the delay time is: Z3

1 −0.5 sTs
Gd ( s ) = e Gzoh ( s ) = e− sTs (3) Fig. 3 . Structure of LCL filter and its derived filter
Ts
By performing Fourier decomposition on the inverter side
In this paper, the proportional integral (PI) regulator is
voltage of the unipolar SPWM modulation, the ratio of the
used, and its transfer function is:
voltage of each harmonic of the inverter side voltage to the
1 fundamental voltage can be obtained:
Gc ( s ) = K p (1 + ) (4)
Ti s 2 J n ( mM π )
k ( m, n ) = (8)
III. PROPOSED DESIGN CRITERIA OF LCL-FILTER AND mM π
PASSIVE DAMPING Among them, M is the modulation ratio, m is the number of
A. Constraints of traditional LCL filter design harmonics relative to the switching frequency fsw, and n is the
number of times relative to the fundamental frequency f0. Jn(x)
The traditional LCL filter design often includes the
is the first type of Bessel function. The expressions of M and
following 5 points: inverter side current ripple limit, filter
Jn(x) are:
reactive power limit, filter total inductance voltage drop limit,
grid side current harmonic content limit and resonant 2U g
frequency limit [2]. M = (9)
U dc
First, the design process determines the inverter side
inductance parameter according to the maximum ripple of the
∞ ª ( −1)k § x ·2 k + n º
inverter side current, and the inverter side current ripple Jn ( x) = ¦ « ¨ ¸ » (10)
generally accounts for 15-35% of the rated current. Here, the k = 0 « k !( k + n ) ! © 2 ¹ »
maximum current ripple on the inverter side is set to 30% of ¬ ¼
the rated current, then the expression of Li is: Schematic diagram of the ratio of voltage harmonics on
the inverter side to the fundamental wave is shown in Fig. 4.
U dcU g
Li = (5) It can be seen that the maximum harmonic appears in (N-1)
30% ⋅ 4 f sw Po times. According to the IEEE Standard 519-2014 standard,
and in order to reduce the cost and bulk weight of the filter, let
In order to reduce the influence of the reactive power the grid-side current (N-1) times harmonics equal 0.3% of the
introduced by the LCL filter capacitor on the system nominal value:
performance, it is necessary to limit the reactive power
generated by the capacitor to not exceed 5% of the rated ­ig _( N −1) = Guig ( j 2π f 0 ( N − 1) ) ⋅ uinv _( N −1)
power. ° inv

® P (11)
Po ° ig _( N −1) = 0.3% I rated = 0.3% o
C f ≤ 5% (6) ¯ Ug
2π f0U g 2
Then, one can get many available LCL-filter parameters
Limiting the total inductor voltage drop by less than 10% that fulfilling the above five basic guidelines. The remaining
of the grid voltage is to prevent over-modulation of the question is how to choose one from so many available choices.
inverter: Hence, an optimization method is needed.
10%U g In this paper, the minimization of total storage energy in
Li + Lg < (7) LCL filter is used to minimize the volume and weight of the
2π f0 I rated

Authorized licensed use limited to: ULAKBIM UASL - MIDDLE EAST TECHNICAL UNIVERSITY. Downloaded on March 03,2022 at 12:05:04 UTC from IEEE Xplore. Restrictions apply.
where, Li is the inverter-side inductor, Lg is the grid-side
inductor, fsw is the switching frequency, Kpwm is the equivalent
1 gain of the inverter bridge.
Ratio of harmonics to the

In addition, considering that the gain margin (GM) and


fundamental wave

0.8
phase margin (PM) influence the robustness and the dynamic
0.6 performance of the system, it is desirable that GM  3dB and
0.4 PM  45° [10]. Besides, in order to ensure the stability of the
system, the amplitude-frequency gain at the LCL resonance
0.2 frequency is suppressed to below 0 dB, that is:
0
1 N 2N 3N 20 lg GOL ( j 2π f res ) < 0 (16)
Number of harmonics(mN±n)
It is worth noting that some passive damping schemes
Fig. 4. Schematic diagram of the ratio of voltage harmonics on the affect the switching frequency harmonic suppression.
inverter side to the fundamental wave
Therefore, it is often necessary to redesign the parameters of
the LCL filter with passive damping, and all of the above
filter. The expression of the total energy storage of the LCL limitations and requirements need to be considered in the
filter is as shown in the (12). redesign process.
I rated 2 ( Li + Lg ) U g 2 C f C. Similarities and differences in the design of LCL filter
Wenergy = + (12) parameters with different damping schemes
2 2
For these four LCL filters with different passive damping
It can be seen that the total energy storage is a binary one- schemes, the impedance of Z3 in Fig. 3 is much smaller than
time function for Lg and Cf. that of Z1 and Z2 near the switching frequency. That is, Li is
B. Requirements for the stability of the inverter system the main part of the equivalent impedance of the filter near
the switching frequency, which is the same as the LCL filter.
Note that the above LCL parameter design only considers Therefore, the parameters of Li can all be determined by (5)
the performance of the filter itself and does not consider the like LCL filter.
stability of the inverter system. As a result, damping strategies
are usually required. In order to design the parameters of For the shunt RC and shunt RLC schemes, as with the
damping circuit, this study tries to use more criteria which are other two schemes, the reactive power of the capacitor limits
obtained from the view of improving the system dynamic. the range of Cf, which is the sum of Cs and Cd. In order to
reduce the number of variables and the complexity of
In order to ensure that the inverter system has good parameter design of the two schemes, the split capacitor ratio
dynamic response, it is hoped that the system has a higher is set to 1, that is, Cs=Cd=0.5Cf.
bandwidth, which is generally taken as one-tenth of the
control frequency [8]. For the series RL and shunt RLC scheme, the inductance
can reduce the low frequency loss. In order not to affect the
Near the cutoff frequency, the LCL filter can be regarded damping performance near the resonant frequency, the value
as a single L filter with a total inductance of Li and Lg, and the of the damping inductance Ld should satisfy:
PI regulator transfer function can be approximated as Kp [9].
So the open-loop transfer function of the inverter system can ω0 Ld ≤ Rd ≤ ωres Ld (17)
be simplified as:
In this paper, the damping inductance Ld is set to five times
K K the lower limit value, namely:
GOL ( s ) = PWM P Gd (s) (13)
s( Li + Lg ) Rd
Ld = 5 (18)
The open loop gain at the cutoff frequency is equal to one, ωres
and the delay time has no effect on the amplitude gain, so that
the expression of the open loop cutoff frequency fc can be After determining the Rd and the resonance frequency, Ld
obtained: can be determined. For the series RL and shunt RLC schemes,
since the current flowing through the inductor Ld at the
K p K PWM fundamental frequency is very small, so the energy storage of
fc = (14) Ld can be ignored relative to the total energy storage of the
2π ( Li + Lg )
LCL filter. Therefore, the total energy storage of these two
It can be derived that the bandwidth of the inverter system schemes can also be expressed by (12). In addition, since the
is related to the PI regulator parameters. To satisfy the performance of the low and high frequency bands is similar
requirement for bandwidth, the parameters of Kp and Ti should to the series R damping scheme after series RL damping, it
follow: can be considered that the design of the series R scheme
which aims at minimizing total energy storage is not affected.
­ ( Li + Lg ) f sw Therefore, the parameter design process of the two schemes
° Kp = can be considered to be the same. Similarly, the design
° 2 K PWM process of the shunt RLC scheme parameters is also the same
® 2
(15)
as shunt RC.
°T = 1 ai , a = 3
° i K i
¯ PWM f sw

Authorized licensed use limited to: ULAKBIM UASL - MIDDLE EAST TECHNICAL UNIVERSITY. Downloaded on March 03,2022 at 12:05:04 UTC from IEEE Xplore. Restrictions apply.
Determine Li based on inverter-
6
side current limit X:3.35
5

Z:Rd ()
4 Y:7.5
Z:4
3
Determine the range of Cf values
based on the reactive power limit 2
1
10
8
Determine the total inductance 6

Y:Lg*10-1
4
range according to the total

(mH)
2
inductance limit 6 8 10 12 14 16
2 4
X:Cf (uF)
According to the grid current Fig. 6. The set of values of Cf, Lg, and Rd
standard, determine Lg,Cf,Rd
value collection 6
5 X:2.9

Z:Rd ()
4 Y:7.8
Determine Lg,Cf,Rd on the
3 Z:3.76
intersection of the contour
surface of Lg,Cf,Rd and the 2 W=0.54
contour surface of total energy 1 W=0.53
10 W=0.52
Rd parameters
Adjust Lg,Cf,

storage W and complete the LCL W=0.51


8
parameter design initially
6

Y:Lg*10-1
4
energy storage W

(mH)
Reduce the total

2 10 12 14 16
2 4 6 8
GM>3dB? X:Cf (uF)
No
PM>45°?
20lg|GOL(j2fres)|<0? Fig. 7. The final parameters of Cf, Lg, and Rd

Yes The series R scheme is taken as an example to describe the


filter and passive damping parameters design process in detail.
Is it possible to reduce the Yes The design specifications of the prototype selected in this
total energy storage W? paper are as follows: DC voltage 380V, grid voltage 220V,
grid frequency 50Hz, rated power 5kW. According to the
No prototype index, the modulation ratio M can be calculated as
Determine PI regulator 0.82, and the frequency modulation ratio N is 300.
parameters based on cutoff
The design first determines the inverter side inductance
Redesign

frequency limits
parameters based on the inverter-side current limit.
Kp

Then, according to the reactive power limit and the grid-


Check the open-loop No side current standard, the set of Cf, Lg, and Rd values can be
cutoff frequency fc determined, as shown in Fig. 6.
Yes By intersecting the contours of the total energy storage
with the surfaces of the Cf, Lg, and Rd values, we can obtain a
No Check resonant cluster of total energy storage contours on the value set.
frequency
The total energy storage is increased until it finds the
Yes parameters that satisfy the minimum total energy storage of
Plot open-loop Bode plots and GM  3dB, PM  45°, and the amplitude gain below 0dB at
test system performance again
the resonant frequency. The final parameters are shown in Fig.
7.
Complete the design
Finally, the open-loop cutoff frequency and resonant
Fig. 5. Parameter design flowchart of LCL filter with passive damping frequency of the system should be verified. The open-loop
cutoff frequency is 1.34 kHz, which is about one tenth of the
switching frequency. The resonant frequency is 4.46 kHz,
IV. UNIFIED DESIGN STEPS OF LCL FILTER PARAMETERS which satisfies the resonance frequency limit.
WITH PASSIVE DAMPING
V. PARAMETER DESIGN AND LOSS ANALYSIS
After the above analysis and simplification in Section III
the unknown variables of these four LCL filters with passive The parameters of a 5kW single-phase grid-connected
damping schemes are only Cf, Lg, Rd and Ld, and Ld does not LCL filter grid-connected inverter are designed. The DC
affect the design of parameters of filter and passive damping. voltage is 380V, and the AC grid is 220V/ 50Hz. The unipolar
The unified flowchart of parameter optimization design of modulation is selected for the PWM, and the switching
passively damped LCL filter can be performed, as shown in frequency is 15 kHz. The inverter side current ripple is set to
Fig. 5. 15% of the rated value, the grid side current shall meet the
IEEE Standard 519-2014 and the amplitude margin GM 
3dB, phase margin PM  45e, the filter and passive damping

Authorized licensed use limited to: ULAKBIM UASL - MIDDLE EAST TECHNICAL UNIVERSITY. Downloaded on March 03,2022 at 12:05:04 UTC from IEEE Xplore. Restrictions apply.
parameters of the undamped, series R, series RL, shunt RC VI. SIMULATION VERIFICATIONS
and shunt RLC are shown in Table I. In order to verify the correctness of parameter design and
Under unipolar SPWM modulation, the voltage harmonics loss calculation, this paper uses saber simulation software to
of the inverter side of a single-phase full-bridge converter are build a single-phase grid-connected LCL inverter model,
mainly distributed around the fundamental wave frequency, observe the current into the grid and the current flowing
switching frequency, and frequency multiplication. The through the damping resistor under different damping
(N±1)th harmonic content is the largest, and it can be seen that schemes. The (N-1)th harmonic content of the grid current and
only harmonic currents of these frequencies flow through the damping loss of the inverter with different damping schemes
damping resistors. Since the damping loss after twice the are shown in Table III.
switching frequency is small, the loss of passive damping can It can be seen that the current into the grid meets the IEEE
be written as: Standard 519-2014 standard, the damping loss is not much
Pd _ total = Pd _ f0 + Pd _ f sw = Pd _ f0 + Pd _( f sw ± f0 ) + Pd _( f sw ± 3 f0 ) different from the result calculated in Section V, which proves
the correctness of the theoretical calculation.
(19)
The damping loss of the filters for the four passive
damping schemes are calculated, as shown in Table II.

TABLE I. FILTER PARAMETERS WITH DIFFERENT PASSIVE DAMPING

Inverter side Grid side Damping Damping Total energy


Damping scheme Filter capacitor/uF
inductor/mH inductor/mH resistor/ inductor/mH storage/W

Undamped 1 4.1 0.38 - - 0.456

Series R 1 2.9 0.78 3.76 - 0.53

Series RL 1 2.9 0.78 3.76 0.67 0.53

Shunt RC 1 3.3 0.92 25.9 - 0.577

Shunt RLC 1 3.3 0.92 25.9 5.1 0.577

TABLE II. CALCULATED DAMPING LOSS OF FILTERS WITH FOUR PASSIVE DAMPING SCHEMES

Damping scheme Pd_f0/W Pd_fsw/W Pd_total/W Total loss percentage/%

Series R 0.1511 8.323 8.4741 0.169

Series RL 4.723*10^-4 8.1977 8.1982 0.164

Shunt RC 0.3368 3.1275 3.4643 0.069

Shunt RLC 0.0013 3.2711 3.2724 0.065

TABLE III. THE MAXIMUM HARMONIC CONTENT OF THE GRID SIDE CURRENT AND DAMPING LOSS IN EACH SCHEME IN SIMULATIONS

Maximum harmonic content


Damping scheme Pd_total/W
of the grid side current/%

Series R 0.288 8.1317

Series RL 0.279 7.8571

Shunt RC 0.262 3.0384

Shunt RLC 0.264 2.8449

TABLE IV. COMPARISON RESULTS AND RECOMMENDED USE OCCASIONS OF THE FOUR DAMPING SCHEMES

Damping scheme Total inductance Damping loss Total energy storage Recommended use occasion

requirement for the smallest volume,


Series R small largest (0.16%) small
weight or cost of the filter

the occasion that low frequency loss is


Series RL small large small
large

Shunt RC high small high requirement for smaller damping loss

requirement for the smallest damping


Shunt RLC high smallest high
loss

Authorized licensed use limited to: ULAKBIM UASL - MIDDLE EAST TECHNICAL UNIVERSITY. Downloaded on March 03,2022 at 12:05:04 UTC from IEEE Xplore. Restrictions apply.
VII. DISCUSSIONS calculation is verified by simulation. Finally, according to the
In Section V, the LCL filter and the passive damping above calculations, the characteristics of each passive
parameters are designed to minimize the total energy storage. damping scheme and its suitable occasions are summarized.
Since the system bandwidth and amplitude margin are The series R scheme has a simple structure, small cost and
basically the same, the performance of the inverter system can volume, and the shunt RC scheme has the advantage of small
be regarded as the same. damping loss. Compared with the series R and shunt RC
schemes, there are no obvious improvements in the two
Under this premise, by observing Tables I and Table II, the schemes of series RL and parallel RLC when the low
characteristics of each scheme and its recommended frequency loss is small.
occasions can be seen:
ACKNOWLEDGMENT
1) The series R damping scheme has the largest damping
loss (0.16%), but its structure is the simplest, and the volume, This work was supported by the National Natural Science
weight and cost of the filter are also the smallest. It is Foundation of China (No. 54177077, No. 51807089).
recommended to use in situations where minimum volume, REFERENCES
weight and cost are required.
[1] M. Sanatkar-Chayjani and M. Monfared, “Design of LCL and LLCL
2) For the series RL scheme, the shunt inductance across filters for single-phase grid connected converters,” IET Power
the damper inductor can greatly reduce the fundamental Electron., vol. 9, no. 9, pp. 1971-1978, Jul. 2016.
[2] J. Xu, S. Xie, L. Huang, and L. Ji, “Design of LCL-filter considering
frequency damping loss, but the fundamental frequency loss
the control impact for grid-connected inverter with one current
is much smaller than the switching frequency loss, so the total feedback only,” IET Power Electron., vol. 10, no. 11, pp. 1324-1332,
loss cannot effectively reduced. Therefore, this scheme is Sept. 2017.
recommended for occasions with large low frequency loss. [3] J. Verveckken, J. F. Silva, and J. Driesen, “Optimal analytic LCL filter
When the low frequency loss is small, the added inductor Ld design for grid-connected voltage-source converter,” IEEE EuroCon,
is not useful. pp. 823-830Jul. 2013.
[4] X. Zheng, L. Xiao, Y. Lei, and Z. Wang, “Optimisation of LCL filter
3) The damping loss of the shunt RC scheme is based on closed-loop total harmonic distortion calculation model of the
significantly less than the series R and series RL schemes, but grid-connected inverter,” IET Power Electron., vol. 8, no. 6, pp. 860-
the volume, weight and total inductance are also large. Shunt 868, Jun. 2015.
RC schemes are recommended for use where it is desirable to [5] P. Channegowda and V. John, “Filter optimization for grid interactive
voltage source inverters,” IEEE Trans. Ind. Electron., vol. 57, no. 12,
suppress damping loss effectively.
pp. 4106-4114, Dec. 2010.
4) The shunt RLC scheme achieves minimal damping loss, [6] R. N. Beres, X. Wang, F. Blaabjerg, M. Liserre, and C. L. Bak,
“Optimal design of high-order passive-damped filters for grid-
but it also costs the most. It is suitable for occasions where connected applications,” IEEE Trans. Power Electron., vol. 31, no. 3,
minimal damping loss are required. Like the series RL pp. 2083-2098, Mar. 2016.
scheme, this scheme is not suitable for occasions with small [7] R. N. Beres, X. Wang, F. Blaabjerg, M. Liserre, and C. L. Bak, “A
low frequency loss. review of passive power filters for three-phase grid-connected voltage-
source converters,” IEEE J. Emerg. Sel. Topics Power Electron., vol.
The comparison results and recommended use occasions 4, no. 1, pp. 54-69, Mar. 2016.
of four damping schemes are shown in Table IV. [8] J. Xu and S. Xie, “LCL-resonance damping strategies for grid-
connected inverters with LCL filters: a comprehensive review,”
VIII. CONCLUSIONS Journal of Modern Power Systems and Clean Energy, vol. 6, no. 2, pp.
292-305, Mar. 2018.
This paper combines the traditional filter parameter design [9] J. Xu, S. Xie, B. Zhang, and Q. Qian, “Robust grid current control with
method with the performance requirements of the inverter impedance-phase shaping for LCL-filtered inverters in weak and
system, including gain margin, phase margin, and amplitude distorted grid,” IEEE Trans. Power Electron., Early Access, DOI:
gain at resonant frequency. Then, the parameter design 10.1109/TPEL.2018.2808604.
[10] D. Yang, X. Ruan, and H. Wu, “A Real-Time Computation Method
method of LCL filter with passive damping is summarized, With Dual Sampling Mode to Improve the Current Control
which aims at minimizing total energy storage. According to Performance of the LCL-Type Grid-Connected Inverter,” IEEE Trans.
the method, four kinds of filter parameters with passive Ind. Electron., vol. 62, no. 7, pp. 4563-4572, Jul. 2015.
damping are designed, and the damping loss of each scheme
is calculated. The correctness of the parameter and loss

Authorized licensed use limited to: ULAKBIM UASL - MIDDLE EAST TECHNICAL UNIVERSITY. Downloaded on March 03,2022 at 12:05:04 UTC from IEEE Xplore. Restrictions apply.

You might also like