Professional Documents
Culture Documents
Oil-immersed
Distribution Transformers
Elvim range
(c) Autotransformers
They are used for voltage transformation within relatively small limits, for connection of electric energy systems
of various voltages, for starting of AC (alternative current) motors, etc.
The construction of the magnetic circuit of the three-phase transformers can be done, alternatively, as follows:
(a) With three legs (vertical limbs) (b) With five legs (vertical limbs)
The magnetic flux of one leg must close through the Free return of the flux through the external legs.
other two legs and the flux also flows through the
windings of the other phases, namely the transformer
has non free return of the flux.
There are two different technologies for stacking the sheets of the magnetic material of the core:
At the industrial site of Schneider Electric Greece, Elvim distribution transformers are manufactured, with voltages
up to 36 kV, having oil as cooling medium and the following technical characteristics:
Single-phase transformers from 5 up to 500 kVA.
Three-phase transformers from 25 up to 2500 kVA.
A potential transformer user has a lot of reasons to choose Elvim distribution transformers that are manufactured
by the industrial site of Schneider Electric Greece. Some of the most important reasons are the following:
More than 35 years of experience in transformer The high automation of the industrial process has
manufacturing (the manufacturing site is active since dramatically decreased the delivery time.
1969). As a result, the best techniques and methods For example, special transformers can be delivered
are used during transformer design and within 3 weeks.
manufacturing.
All the transformer offers are treated very carefully in
The application of the ISO 9001 quality assurance order to finally give an offer, which fully satisfies
system in combination with the very careful the needs of the transformer user.
monitoring of the whole industrial process lead in the The offer is technically complete and represents the
manufacturing of high quality transformers. optimum technical and economical solution for the
specific transformer application.
The application of the ISO 14001 environmental
management system assures the protection of the The wound core technology that is followed has the
environment and the reasonable use of natural following advantages, in comparison with the stack
resources during the transformer production. core technology:
The application of the OHSAS 18001 Health & Lower magnetization current.
Safety system assures that each employee enjoys As a result, the transformer has lower current
the maximum level of health and safety in the harmonics (better quality), lower consumption
working environment. of reactive power and lower magnetization
current.
The use of the best materials for the transformer Less noise.
construction. The reliability of the suppliers of the
transformer materials is systematically monitored
and checked.
A.3.2 Windings
For the construction of transformer metallic parts, the following basic mechanical equipment is used:
CNC machines for cutting, punching and bending Equipment for oil leak detection of the transformer
of steel sheets. tanks.
Different types of welding machines (i.e. MIG-MAG, Modern painting shop for the painting of the metallic
TIG, and electrode) for the welding of the metallic parts. The usual painting procedure includes the
parts. following steps: sandblasting, decreasing-
phosphatizing Fe, painting with 4 coats (two primer
Machines for construction and welding of
coats and two final color coats) with total thickness
corrugated panels and tanks. Certified technicians
of 160 μm. This painting procedure results in a
and welders are the operators of these machines.
durable corrosion protection and therefore lengthy
Stud welding equipment for stud welding on the life expectancy.
transformer cover so that secure insulator
placement is achieved.
A.3.4 Assembly
various cranes from 1 to 35 tons, two vacuum chambers, in which the transformers
are filled with oil,
one drying chamber to dry the active parts in order to
remove the moisture, which is absorbed by the
machines for the processing of transformer oil, so
transformer insulating materials during the
that the oil obtains the appropriate characteristics,
production procedure,
according to the international standards.
Transformer oil according to IEC 60296 specifications Oil can also be filled later on without vacuum under the
is used as cooling medium. prerequisite that the oil level covers the active part and
The initial filling of transformer with oil is done under the oil has been filtered. In agreement with the
high vacuum in order to assure the high penetration of customer, the oil can be supplied from Schneider
oil everywhere and to remove air bubbles or moisture Electric or another company provided that the oil is
that could cause dielectric failure of coil. according to the given standard.
A.4.1 Tank
The transformer tank consists of the bottom plate, The corrugated panels do not allow the creation
frame, and the tank sides. of significant increase of pressure internally,
which is caused by the increase of oil temperature
The tank sides are made of corrugated panels in order during transformer’s operation.
to increase the total cooling area.
The transformer tank has two earthing points.
The tank of sealed type transformers (without oil The rolling system or the base skid is welded to the tank
conservator) is filled with oil and is sealed. bottom plate.
A.4.2 Cover
There are two lifting lugs on the tank cover, which Moreover, a neutral earthing link is also placed
are used for lifting and carrying the transformer. on the cover. A pressure relief device is usually placed
On request, the thermometer pocket and the on the cover of the sealed type transformers.
thermometer with two electrical contacts are placed on
the cover.
The lifting lugs are used for lifting and carrying the transformer.
A.4.4 Rollers
The transformers up to 160 kVA are usually manufactured as pole-mounted. The transformers above 160 kVA
are equipped with bi-directional rollers.
In the lower part of the tank side there is a draining and sampling oil valve, which allows the oil sampling in order
to test the oil dielectric strength.
This link ensures the neutral earthing of the three-phase winding with the transformer tank.
For medium voltage of 6, 10, 20, 30 kV, porcelain bushings according to DIN 42531 are used. Alternatively,
on request, plug-in bushings can be used.
Low voltage bushings of 1 kV series, according to DIN 42530, are used in the low voltage.
The applying medium voltage to the primary winding of Then we turn the handle right or left so that the pin is
transformer is not stable and depends upon the placed to the desirable tap position. If it is desirable to
transformer position in the distribution network. switch from one position (e.g. position 1) to another
Therefore, taken the primary voltage as granted, the tap (e.g. position 5), then the handling is implemented
changer is used in order to keep the secondary voltage step by step, through all intermediate positions
of the transformer as stable as possible. (e.g. positions 2, 3, 4).
The tap changer is placed into the transformer tank. The taps positions are inscribed on the rating plate of
The control interface of the tap changer is placed on the the transformer.
cover. The handling of the tap changer must be done For example, when the transformer is designed to
when the transformer is out of voltage, as follows: operate in two voltage levels, e.g. 20 kV and 15 kV, then
initially, the handle of the tap changer is pulled upwards using a 5-position tap changer, the regulation of the
so that the pin is released and entered into the fixed primary voltage can be ±2x2.5 % for medium voltage
annulus. 20 kV (i.e. voltages 19.0, 19.5, 20.0, 20.5, and 21.0 kV)
and ±2x3.3 % for medium voltage 15 kV (i.e. voltages
14.0, 14.5, 15.0, 15.5, and 16.0 kV).
The voltage selector (changeover switch) is used for The handling of the voltage selector is the same with the
the change of the transformer operating voltage from handling of the tap changer, the only difference is that
one voltage level to another (e.g. from 15 kV to 20 kV the annulus has two positions (e.g. 15 kV or 20 kV).
and vice-versa) in proportion with the voltage of the For example, if we want a 20-15/.4 kV transformer to
network that the transformer is connected. operate with primary voltage 19.5 kV, we set the voltage
selector at the 20 kV position and the tap changer at the
-2.5% position.
The thermocouple of the thermometer is set at the connected to the protection circuit for alarm and
higher oil layer, in order to measure the maximum oil tripping of the circuit, when the corresponding
temperature. The electrical contacts of the thermometer temperature limits are exceeded.
are regulated to the desirable temperatures and are
During the transformer oil temperature variation, and indicator with two marks: the first mark shows the oil
consequently the oil volume variation, the oil level at -20ºC and the second the oil level at +20ºC.
conservator undergoes this oil volume fluctuation. Transformers with oil conservator are usually equipped
The oil conservator is equipped with an oil level with an air dehumidifier and a Buchholz relay.
The protection of the oil-immersed transformers from If the gases are sufficient (i.e. the internal fault is
internal faults, which cause the development of gases significant), then the second float is moved downwards
or strong oil leakage, is implemented with Buchholz and the trip contact is activated. The trip contact is also
relay, which is installed between the transformer tank activated in case of strong oil flux to the oil conservator
and the oil conservator. In case of gases creation (as a after short-circuit or internal fault. Moreover, the
result of internal fault) or lack of oil, the first float is Buchholz relay provides protection from oil leakage.
moved downwards and the alarm contact is activated.
The air dehumidifier is placed on the oil conservator. The silica gel absorbs the moisture until its color is
Because of contraction and expansion of oil volume, yellow. When it is full of moisture and it changes its color
the air passes through the dehumidifier towards and and becomes soft blue-white, it must be dried
from the oil conservator. The air dehumidifier contains or it must be replaced. Drying is achieved by heating it
SiO2 crystals (silica gel), which absorb the air moisture. at temperatures between 120ºC and 150ºC until its
color becomes yellow again.
The silica gel should have the following colors:
Yellow (silica gel is fully dry).
Soft blue-white (silica gel is full of moisture).
The transformers are equipped with a filling valve, in order to have the ability to fill the transformers with mineral oil.
For the sealed type transformers (without oil with oil conservator, an oil level indicator of tube type
conservator), the oil level indicator is placed on the tank (glass transparent tube) or magnetic type is placed on
side or on the transformer cover. For the transformers the oil conservator.
According to the international standards, all the temperature rise, oil temperature rise, rated voltage of
transformer data are mentioned on the rating plate: the primary winding, rated voltage of the secondary
type of transformer, power in kVA, phases, frequency, winding, rated current of the primary winding, rated
short-circuit impedance, vector group, type of cooling, current of the secondary winding, no-load losses, load
windings material, serial number, year of losses, positions of tap changer and positions of
manufacturing, core and windings weight, oil weight, voltage selector (if one exists).
total weight, maximum ambient temperature, winding
Two tank earthing points are placed near the bottom of the tank (one earthing point in diametric opposite direction
with the other earthing point), in order to have the ability for tank earthing.
The sealed type transformers are usually equipped with a pressure relief valve and thermometer or DGPT2 relay.
The DGPT2 relay has an overpressure switch, thermometer with alarm and trip contacts and oil indicator with
contact for the trip of the circuit.
Buchholz relay
Tap changer
High voltage
bushings
Oil conservator Low voltage
bushings
Oil level
indicator Lifting lug
Rating plate
Tank
Rollers
The transformer tests are classified, in accordance with the specification IEC 60076, as follows:
Type tests.
Routine tests.
Special tests.
The type tests, which are performed on one transformer from every transformer type, are the following:
The special tests are not included in the category of type or routine tests and are executed after agreement between
customer and manufacturer. The special tests are the following:
The rated power, Pn, of the three-phase transformer is calculated by the following formula:
Pn= Un In √3 where Un is the rated voltage and In is the rated current of the transformer.
The temperature rise is the maximum rise when the Transformer typical characteristics:
transformer operates at the primary rated voltage,
The average temperature rise of the winding
secondary rated current and rated frequency.
is 65 K.
The top oil temperature rise is 60 K.
The rated power of the transformer is typically On request, transformers operating under different
calculated for the following conditions: ambient temperature conditions can be produced.
Maximum ambient temperature of 40ºC.
Average daily ambient temperature of 30ºC.
Average annual ambient temperature of 20ºC.
The rated power of the transformer is valid for installation altitude up to 1000 m. If the transformer is going to be
installed in an altitude higher than 1000 m, this should be mentioned in the transformer specification.
The short-circuit impedance is the percentage of the the short-circuit impedance, the higher the voltage
primary rated voltage that has to be applied at the drop. The lower the short-circuit impedance, the higher
transformer primary winding, when the secondary the short-circuit current, in case of short-circuit. Based
winding is short-circuited, in order to have the rated on the short-circuit impedance, the following are
current at the primary winding. determined: the voltage drop due to the transformer
The short-circuit impedance is very important, because loading, the distribution of loads in case of transformers
it represents the transformer’s impedance. The higher parallel operation, and the short-circuit current.
The vector group determines the phase displacement These connections are the following:
between the primary and the secondary winding. D (d): delta connection for high voltage
The three primary or secondary windings can be (low voltage) winding
connected with different ways in order to have a three- Y (y): star connection for high voltage (low voltage)
phase transformer. winding
Z (z): zigzag connection for high voltage
(low voltage) winding
N (n): the neutral exists in high voltage
(low voltage) winding for connection outside the
transformer.
Table 1: No load losses P0 (W) and sound power level (Lw(A)) for Um 24kV
The rated primary voltage (input voltage) is the voltage to withstand the overvoltages that can appear in the
at which the transformer is designed to operate. The network. The calculation of the winding insulation is
rated primary voltage determines the basic insulation based on the basic insulation level.
level (BIL) of the transformer, according to international The rated secondary voltage (output voltage) is the
standards (IEC 60076). The BIL is a basic transformer voltage at the terminals of the secondary winding at no-
characteristic, since it indicates the transformer ability load, under rated primary voltage and rated frequency.
The frequency at which the transformer is designed to operate is 50 Hz or 60 Hz in accordance with the network
frequency.
A.6.11 Noise
The transformer noise is due to the magnetostriction of the sheets of the magnetic circuit.
In general, a transformer operating at low magnetic induction has low noise level.
A.6.12 Efficiency
The distribution transformers are very efficient where S is the transformer load in VA, losses are the
machines since their efficiency is greater than 95%. losses in W and cos φ is the power factor.
The power efficiency of any electrical machine is The transformer efficiency is increased with the
defined as the ratio of the useful power output to the decrease of transformer losses.
total power input. The efficiency can be defined by The transformer losses are divided into no-load losses
simultaneously measuring the output and the input and load losses. The no-load losses are constant, while
power. However, this measurement is expensive and the load losses are proportional to the transformer
difficult, especially for large machines. Moreover, in load. Consequently, the efficiency of the transformer is
case of high efficiency machines (e.g. transformer), calculated by the following formula:
higher precision can be achieved, if the efficiency is
expressed through the losses. Consequently, the S cos φ
transformer efficiency is calculated by the following n=
formula: S cos φ + NLL + LL(S/SB )2
S cos φ
n= where NLL are the no-load losses, LL are the load
S cos φ + losses losses and SB is the rated power of the transformer
in VA.
The short-circuit current is composed of the The asymmetrical short-circuit current stresses
asymmetrical and the symmetrical short-circuit current. mechanically the transformer, while the symmetrical
The amplitude of the first peak of the asymmetrical short-circuit current stresses thermally the transformer.
short-circuit current is equal to κ√2 times the value of Elvim transformers are designed and tested to with-
the symmetrical short-circuit current. stand short-circuit currents according to IEC 60076-5.
The factor κ√2 depends on the ratio of Ux /Ur, where
Ux is the voltage drop in the reactive components of the
transformer and Ur is the voltage drop in the resistance Ux / Urκ√2
components of the transformer. 1 1.51
1.5 1.63
Table 3 presents the values of the factor κ√2 versus the
2 1.75
ratio Ux/Ur.
3 1.95
The symmetrical short-circuit current, IK , is expressed 4 2.09
5 2.19
as a function of the rated current In. If the secondary
6 2.28
winding is short-circuited and the nominal current is
8 2.38
applied at the primary winding, the following equation
10 2.46
holds:
15 2.56
IK 100 25 2.66
= 50 2.77
In UK
where UK is the short-circuit impedance. Table 3: Values of the factor κ√2 versus the ratio Ux /Ur
The no-load current represents the current that the transformer absorbs, when rated voltage is applied to the
primary winding and the secondary winding is open-circuited. The no-load current is expressed as a percentage
of the value of the rated current.
The transformer manufacturing is based on the international standards as well as on specific customer needs.
From time to time, some of the standards may be modified and in that case they are republished.
A list of transformer standards, according to IEC, is shown in Table 4.
The above standards are related with the electrical characteristics and the accessories of transformers.
The IEC 60076 standard describes the electrical characteristics and the transformer tests that are related with the
dynamic, thermal and electrical withstand of transformers. The DIN standard defines the transformer accessories
and the EN 50464-1 standard defines the lists of transformer losses and short-circuit impedance.
A.8 Tolerances
Constructional reasons result in deviations between the measured parameters and the values that are defined by
the specification of the transformer user (i.e. the guaranteed values).
Table 5 presents the tolerances that are applied to certain items, according to IEC 60076-1.
Ιtem Tolerance
Voltage ratio The lower of the following values:
a) ±0.5% of guaranteed voltage ratio
b) ±1/10 of the measured short-circuit impedance on
the principal tapping
Short-circuit impedance ±10% of the guaranteed short-circuit impedance
No-load losses +15% of the guaranteed no-load losses
Load losses +15% of the guaranteed load losses
Total losses (load and no-load) +10% of the guaranteed total losses
(load and no-load)
No-load current +30% of the guaranteed no-load current
A.9.1 Overloading
The rated overloading of transformer depends on the For example, if the transformer is loaded with 50% of its
transformer’s previous load or the corresponding oil rated power continuously, then the transformer can be
temperature at the beginning of the overloading. overloaded to150% of its rated power for 15 minutes or
Examples of the permissible duration and the to 120% of its rated power for 90 minutes.
respective levels of the acceptable overloadings are
shown in Table 6.
Moreover, it should be noted that the oil temperature is overloading must be done very carefully, since there is a
not a safe measure for the winding temperature, since danger for the winding temperature to exceed the
the time constant of the oil is 2 to 4 hours, while the time critical temperature of 105ºC, without this being visible
constant of the winding is 2 to 6 minutes. Therefore, the by the oil temperature.
determination of the permissible duration of the
The parallel operation of two or more transformers is Their vector groups should be the same and the
feasible, when the following requirements are met: connection should be implemented with the
corresponding terminals U-u, V-v, W-w. In other
The ratio of their rated power should be less words, the transformers must have the same
than 3:1. inherent phase angle difference between primary
Their voltage ratio should be the same and secondary terminals, the same polarity and the
(the permitted tolerance is according to same phase sequence. It should be noted that, in
IEC 60076-1, Table 5, § A.8). case that the vector groups are not the same, the
Their short-circuit impedance should be the same parallel operation of transformers of groups 5 and 11
(the permitted tolerance is according to is permitted, if the connection is implemented
IEC 60076-1, Table 5, § A.8). according to Table 7.
If the parallel operated transformers have the same where Pi is the load that is distributed to the i
voltage ratio but different short-circuit impedance, then transformer, Pni is the rated power of the i transformer
the load is distributed among them in such a way that
each transformer accepts a specific level of load for UKi is the rated short-circuit impedance of the i
which the short-circuit impedance becomes the same transformer and UK min is the minimum rated short-
for all the parallel operated transformers. circuit impedance of the n parallel operated
transformers.
When none of the parallel operated transformers is
permitted to be overloaded, the transformer with the Finally, the total power of the n parallel operated
minimum short-circuit impedance must operate transformers is:
maximum under its rated power.
UK min
Pi = Pni , An arithmetic example of the load distribution of
UKi
transformers in parallel operation is given in § A.13.3.
Customer
Sales engineer
Transformer type three-phase single-phase
Rated power (kVA)
Rated primary/secondary voltage (kV)
Frequency (Hz) 50 60
Quantity (items)
Unit price (€)
Payment method
Order date
Delivery date
Comments
The selection of the most appropriate transformer starts with the definition of the proper and detailed specification.
The special needs of each project specify the special characteristics or accessories that are needed. The evaluation
of the alternative transformer offers depends on the transformer user. The economic evaluation method of the
transformers by the electrical utilities and industrial users is presented below.
The electrical utilities evaluate the transformers based Among alternative transformer offers, the economical
on the criterion of the total owning cost, TOC (€), which optimum is the one with the minimum total owning cost.
is calculated from the following equation: The values of the parameters BP, NLL, and LL are
determined by the transformer manufacturer.
TOC = BP + A* NLL + B* LL, The values of the parameters A and B are determined by
the electrical utilities.
where BP (€) is the transformer sales price,
A (€/W) is the no-load losses factor, NLL (W) are the no-
load losses, B (€/W) is the load losses factor, and LL
(W) are the load losses.
The procurement of transformers by the industrial users is based mainly on the transformer sales price and
secondary on the transformer losses. An arithmetic example for the determination of the most economical
transformer for an industrial user is presented in § A.13.4.
General Description
Single-phase distribution transformers, 50 Hz.
IEC 60076 standard is followed.
The cooling is implemented with natural circulation (ONAN) of mineral oil according to IEC 60296.
Sealed type transformers.
Outdoor installation.
Pole-mounted.
Rated primary voltage 20 kV, rated secondary voltage 231 V at no-load.
The top oil temperature rise is 60 K and the average temperature rise of the winding is 65 K.
Tolerances of losses and short-circuit impedance according to IEC 60076.
The transformer painting type is RAL 7033.
Basic Equipment
3-position tap changer with ± 5 % tappings at 20 kV.
LV and HV bushings.
Valves for filling, filtering and oil sampling.
Pole-mounting elements.
Rating plate.
Electrical Characteristics
Rated Power (kVA) 5 10 15 20 25 30 50
No-load losses (W) (*) 55 55 70 85 105 120 180
Load losses at 20 kV (W)(*) 150 320 485 650 725 800 1350
Voltage drop cosφ =1 3.04 3.23 3.26 3.28 2.94 2.71 2.74
at full load (%) cosφ = 0.8 3.99 4.00 4.00 4.00 3.97 3.93 3.93
Rated short-circuit impedance (%)(*) 4 4 4 4 4 4 4
Load cosφ =1 96.06 96.39 96.43 96.46 96.79 97.02 97.03
Efficiency (%) 100% cosφ =0.8 95.12 95.52 95.58 95.61 96.02 96.31 96.32
Load cosφ =1 96.42 96.96 97.04 97.08 97.34 97.53 97.56
75% cosφ = 0.8 95.56 96.23 96.33 96.38 96.69 96.93 96.96
Order Details
Rated power Load losses
Short-circuit impedance Altitude of installation (if the altitude exceeds 1000 m)
Rated voltages Primary tappings
No-load losses Special accessories
Rated frequency Ambient temperature
(*) Transformers with different losses and short-circuit impedance can be manufactured, on request.
Dimensions (mm)
Rated power (kVA) 5 10 15 20 25 30 50
A (mm) 620 620 690 690 730 730 805
B (mm) 540 540 630 630 640 640 770
C (mm) 930 1050 1020 1020 1020 1020 1035
Total weight (Kg) 115 140 155 165 210 225 295
Due to evolution of standards and materials, the present manual will bind us only after confirmation from our
transformer design department.
General Description
Three-phase disrtibution transformers, 50 Hz.
IEC 60076 standard is followed.
Transformers with oil conservator.
The cooling is implemented with natural circulation of mineral oil according to IEC 60296.
Indoor or outdoor installation.
Ground-mounted.
Rated primary voltage 20 kV, rated secondary voltage 400 V at no-load.
Vector group Dyn11.
The top oil temperature rise is 60 K and the average temperature rise of the winding is 65 K.
Tolerances of losses and short-circuit impedance according to IEC 60076.
The transformer painting type is RAL 7033.
Basic Equipment
5-position tap changer with ± 2 x 2.5 % tappings at 20 kV.
LV and HV bushings.
Oil conservator with oil level indicator.
Thermometer with oil level indicator and electrical contacts.
Buchholz relay.
Air dehumidifier.
Valves for filling, filtering and oil sampling.
Bi-directional rollers.
Rating plate.
Electrical Characteristics
Rated power (kVA) 250 400 500 630 800 1000 1250 1600
No-load losses (W)(*) 610 850 1000 1200 1450 1750 2100 2550
No-Load losses at 20 kV (W)(*) 4450 6450 7800 9300 11000 13500 16400 19800
Voltage drop cosφ=1 1.94 1.78 1.73 1.65 1.55 1.52 1.48 1.41
at full load (%) cosφ=0.8 4.92 4.82 4.79 4.74 4.68 4.66 4.64 4.59
Rated short-circuit impedance (%)(*) 6 6 6 6 6 6 6 6
Load cosφ=1 98.02 98.21 98.27 98.36 98.47 98.50 98.54 98.62
Efficiency (%)) 100% cosφ=0.8 97.53 97.77 97.85 97.96 98.09 98.13 98.18 98.28
Load cosφ=1 98.37 98.53 98.58 98.66 98.74 98.77 98.81 98.87
75% cosφ=0.8 97.97 98.17 98.24 98.33 98.43 98.47 98.51 98.59
Order Details
Rated power Vector group
Short-circuit impedance Altitude of installation (if the altitude exceeds 1000 m)
Rated voltages Primary tappings
No-load losses Special accessories
Rated frequency Ambient temperature
Load losses Details of cable boxes (on request)
(*) Transformers with different losses and short-circuit impedance can be manufactured, on request.
D D
1. Transformer tank
2. Tank cover
3. Lifting lugs
4. Roller DIN 42561
5. Draining and sampling valve DIN 42551
B
Dimensions (mm)
Rated power (kVA) 250 400 500 630 800 1000 1250 1600
A (mm) 1475 1700 1735 1710 1855 1960 1940 2155
B (mm) 905 1005 1005 1050 1195 1290 1270 1450
C (mm) 1530 1490 1720 1815 1890 1895 2085 2095
D (mm) 520 670 670 670 670 820 820 820
Total weight (Kg) 1100 1380 1700 1940 2380 2650 3200 3760
Due to the evolution of standards and materials, the present manual will bind us only after confirmation from our
transformer design department.
General Description
Three-phase distribution transformers, 50 Hz.
Combination of losses Dk-A0, EN 50464-1:2007.
IEC 60076 standard is followed.
The cooling is implemented with natural circulation of mineral oil according to IEC 60296.
Transformers with oil conservator.
Indoor or outdoor installation.
Ground-mounded.
Rated primary voltage 20 kV, rated secondary voltage 400 V at no-load.
Vector group Dyn11.
The top oil temperature rise is 60 K and the average temperature rise of the winding is 65 K.
Tolerances of losses and short-circuit impedance according to IEC 60076.
The transformer painting type is RAL 7033.
Basic Equipment
5-position tap changer with ± 2 x 2.5 % tappings at 20 kV.
LV and HV bushings.
Oil conservator with oil level indicator.
Thermometer with oil level indicator and contacts.
Buchholz relay.
Air dehumidifier.
Valves for filling, filtering and oil sampling.
Bi-directional rollers.
Rating plate.
Electrical Characteristics
Rated Power (kVA) 250 400 500 630 800 1000 1250 1600
No-load losses (W)(*) 425 610 750 860 940 1100 1350 1700
Load losses at 20 kV (W)(*) 3250 4600 5500 6500 8700 10500 13300 17000
Voltage drop cosφ=1 1.37 1.22 1.17 1.11 1.26 1.22 1.24 1.24
at full load (%) cosφ=0.8 3.33 3.25 3.22 3.17 4.49 4.47 4.48 4.48
Rated short-circuit impedance (%)(*) 4 4 4 4 6 6 6 6
Load cosφ=1 98.55 98.71 98.77 98.85 98.81 98.85 98.84 98.84
Efficiency (%) 100% cosφ=0.8 98.20 98.40 98.46 98.56 98.52 98.57 98.56 98.56
Load cosφ=1 98.81 98.95 98.99 99.05 99.04 99.07 99.07 99.07
75% cosφ=0.8 98.52 98.69 98.73 98.82 98.80 98.85 98.84 98.84
Order Details
Rated power Vector group
Short-circuit impedance Altitude of installation (if the altitude exceeds 1000 m)
Rated voltages Primary tappings
No-load losses Special accessories
Rated frequency Ambient temperature
Load losses Details of cable boxes (on request)
(*) Transformers with different losses and short-circuit impedance can be manufactured, on request.
D D
1. Transformer tank
2. Tank cover
3. Lifting lugs
4. Roller DIN 42561
5. Draining and sampling valve DIN 42551
B
Dimensions (mm)
Rated power (kVA) 250 400 500 630 800 1000 1250 1600
A (mm) 1580 1710 1705 1790 1950 2030 2120 2300
B (mm) 880 900 1020 1000 1140 1260 1350 1300
C (mm) 1480 1560 1580 1670 1740 1780 1880 1950
D (mm) 520 670 670 670 670 820 820 820
Total weight (Kg) 1150 1500 1750 2100 2400 2800 3200 4050
Due to the evolution of standards and materials, the present manual will bind us only after confirmation from our
transformer design department.
General Description
Three-phase distribution transformers, 50 Hz.
IEC 60076 standard is followed.
The cooling is implemented with natural circulation of mineral oil according to IEC 60296.
Transformers with oil conservator.
Indoor or outdoor installation.
Ground-mounted.
Rated primary voltage 20 and 15 kV, rated secondary 400 V at no-load.
Vector group Dyn11.
The top oil temperature rise is 60 K and the average temperature rise of the winding is 65 K.
Tolerances of losses and short-circuit impedance according to IEC 60076.
The transformer painting type is RAL 7033.
Basic Equipment
Voltage selector.
5-position tap changer with ± 2 x 2.5 % tappings at 20 kV and ± 2 x 3.33 % tappings at 15 kV.
LV and HV bushings.
Oil conservator with oil level indicator.
Thermometer with level indicator and contacts.
Buchholz relay.
Air dehumidifier.
Valves for filling, filtering and oil sampling.
Bi-directional rollers.
Rating plate.
Electrical Characteristics
Rated power (kVA) 250 400 500 630 800 1000 1250 1600
No-load losses (W)(*) 575 810 930 1000 1180 1360 1720 1950
Load losses as 20 kV (W)(*) 4000 6350 7500 9300 10800 12800 13500 17400
Voltage drop cosφ=1 1.77 1.75 1.67 1.65 1.52 1.45 1.25 1.26
at full load (%) cosφ=0.8 4.82 4.81 4.76 4.74 4.66 4.62 4.49 4.49
Rated short-circuit impedance (%)(*) 6 6 6 6 6 6 6 6
Load cosφ=1 98.20 98.24 98.34 98.39 98.52 98.60 98.80 98.81
Efficiency (%) 100% cosφ=0.8 97.76 97.81 97.94 98.00 98.16 98.26 98.50 98.51
Load cosφ=1 98.52 98.56 98.65 98.70 98.81 98.87 99.02 99.03
75% cosφ=0.8 98.15 98.21 98.31 98.38 98.51 98.59 98.77 98.79
Order Details
Rated power Vector group
Short-circuit impedance Altitude of installation (if the altitude exceeds 1000 m)
Rated voltages Primary tappings
No-load losses Special accessories
Rated frequency Ambient temperature
Load losses Details of cable boxes (on request)
(*) Transformers with different losses and short-circuit impedance can be manufactured, on request.
D
D
1. Transformer tank
2. Tank cover
3. Lifting lugs
4. Roller DIN 42561
5. Draining and sampling valve DIN 42551
B
Dimensions (mm)
Rated power (kVA) 250 400 500 630 800 1000 1250 1600
A (mm) 1530 1650 1873 1758 2025 1990 2135 2240
B (mm) 925 1035 960 1005 1225 1230 1280 1470
C (mm) 1520 1530 1718 1820 1890 1890 1910 2080
D (mm) 520 670 670 670 670 820 820 820
Total weight (Kg) 1100 1560 1800 2100 2550 2800 3200 3760
Due to the evolution of standards and materials, the present manual will bind us only after confirmation from our
transformer design department.
General Description
Three-phase distribution transformers, 50 Hz.
IEC 60076 standard is followed.
The cooling is implemented with natural circulation of mineral oil according to IEC 60296.
Sealed type transformers (without oil conservator).
Indoor or outdoor installation.
Ground-mounted.
Rated primary voltage 20 kV, rated secondary 400 V at no-load.
Vector group Yzn5 (up to 160 kVA) and Dyn5 (from 250 kVA to 1600 kVA).
The top oil temperature rise is 60 K and the average temperature rise of the winding is 65 K.
Tolerances of losses and short-circuit impedance according to IEC 60076.
The transformer painting type is RAL 7033.
Basic Equipmemt
5-position tap changer with ± 2 x 2.5 % tappings at 20 kV.
LV and HV bushings.
Valves for filling, filtering and oil sampling.
Oil level indicator.
Bi-directional rollers.
Rating plate.
Pressure relief device.
Thermometer with two electrical contacts.
Electrical Characteristics
Rated power (kVA) 25 40 50 63 100 125 160 250 400 630 800 1000 1600
No-load losses (W)(*) 110 170 180 230 320 380 460 650 930 1270 1350 1700 2300
Load losses at 20 kV (W)(*) 700 985 1100 1350 1750 2100 2350 3250 4600 6500 8600 10500 13600
Voltage drop cosφ=1 2.84 2.51 2.26 2.20 1.81 1.75 1.54 1.47 1.32 1.21 1.25 1.22 1.03
at full load (%) cosφ=0.8 3.96 3.87 3.77 3.75 3.57 3.54 3.43 4.63 4.53 4.46 4.48 4.47 4.33
Rated short-circuit impedance (%)(*) 4 4 4 4 4 4 4 6 6 6 6 6 6
Load cosφ=1 96.86 97.19 97.50 97.55 97.97 98.05 98.27 98.46 98.64 98.78 98.77 98.79 99.02
Efficiency (%) 100% cosφ=0.8 96.11 96.52 96.90 96.96 97.48 97.58 97.85 98.09 98.30 98.48 98.47 98.50 98.77
Load cosφ=1 97.38 97.64 97.91 97.95 98.29 98.36 98.54 98.70 98.84 98.97 98.98 99.00 99.18
75% cosφ=0.8 96.75 97.07 97.41 97.45 97.87 97.96 98.18 98.37 98.56 98.71 98.73 98.75 98.97
Order Details
Rated power Vector group
Short-circuit impedance Altitude of installation (if the altitude exceeds 1000 m)
Rated voltages Primary tappings
No-load losses Special accessories
Rated frequency Ambient temperature
Load losses Details of cable boxes (on request)
(*) Transformers with different losses and short-circuit impedance can be manufactured, on request.
Alternative position
of rating plate
D D
B
1. Corrugated panels
2. Tank earthing point
3. Filling valve DIN 42553
4. Draining and sampling valve
5. Lifting lugs
6. High voltage bushings
7. Low voltage bushings DIN 42530
8. Rating plate
9. Thermometer with two electrical contacts
10. Tap changer
11. Pressure relief device
12. Rollers
13. Neutral earthing link
A 14. Oil level indicator
Dimensions (mm)
Rated power (kVA) 25 40 50 63 100 125 160 250 400 630 800 1000 1600
A (mm) 850 870 900 930 950 1000 1130 1370 1530 1820 1870 1900 2260
B (mm) 680 680 680 680 680 680 770 855 895 1160 1240 1220 1415
C (mm) 1140 1140 1140 1200 1260 1275 1275 1270 1350 1350 1460 1570 1600
D (mm) 520 520 520 520 520 520 520 520 670 670 670 820 820
Total weight (Kg) 365 435 450 500 640 705 825 1050 1450 1950 2220 2600 2740
Due to the evolution of standards and materials, the present document will bind us only after confirmation from our
transformer design department.
er = LL = 9300 = 0.014762 = 1.4762% and ex = U2k - e2r = 0.062 - 0.0147622 = 0.05816 = 5.816 %
SB 630000
Among the three transformers, the third transformer The maximum total load of the three transformers is:
has the minimum short-circuit impedance,
Ptot = Pn,1 + Pn,2 + Pn,3 = 728 + 417 + 315 = 1460 kVA.
i.e Uk, min = 4.0 %.
The load of transformer 1 is:
The three transformers have total installed power:
Uk, min
Pn,1 = P1 U = 800 4 = 728 kVA. P = P1 + P2 + P3 = 800 + 500 + 315 = 1615 kVA.
k,1 4.4
The comparison of the two offers will be based on the annual total owning cost, which is the sum of the annual
buying cost and the annual usage cost. An approximation of the annual buying cost can be found by dividing the
sales price with the years of depreciation. An approximation of the annual usage cost can be calculated based on
the annual charge due to the transformer operation (annual charge for load losses and no-load losses).
Manufacturer A Manufacturer B
The annual buying cost (€) is: The annual buying cost (€) is:
5870 € 7045 €
OC1 = = 1174 € OC2 = = 1409 €
5 5
The annual charge (€) for the no-load losses is: The annual charge (€) for the no-load losses is:
€ €
NLLC1 = 8,760 h * 1.2 kW * 0.075 = 788.4 € NLLC2 = 8,760 h * 0.94 kW * 0.075 = 617.58 €
kWh kWh
The annual charge (€) for the load losses is: The annual charge (€) for the load losses is:
€ €
LLC1 = (200 * 8 h) * 0,62 * 8.7 kW * 0.075 = 375.84 € LLC2 = (200 * 8 h) * 0,62 * 6.75 kW * 0.075 = 291.6 €
kWh kWh
The annual total owning cost (€) is: The annual total owning cost (€) is:
TOC1 = OC1 + NLLC1 + LLC1 = 2338.24 € TOC2 = OC2 + NLLC2 + LLC2 = 2318.18 €
As a result, although the transformer sales price of the second manufacturer is 20% more expensive (i.e.
1175 € more expensive), the transformer of the second manufacturer is finally more economical, since its
annual total owning cost is 0.9% less (i.e. 20.06 € less). From the above, it is concluded that the cheapest
transformer is not always the most economical. In particular, the difference at the annual total owning cost
could be more than 0.9%. This will happen, if we consider more years for the depreciation (instead of the
current assumption of 5 years), or if we use the transformer more (instead of the current assumption of 60%
average loading, 8 hours per day, 200 working days per year).
When the transformer is going to be installed inside an electrical room (indoor installation), particular attention
should be paid to the calculation of the dimensions of the installation area as well as to the ventilation of the
installation room. The ventilation of the electrical room influences the cooling, and consequently, the transformer’s
life. The distance between the walls of the room and the transformer end points must be from 50 to 60 cm.
F1 = 4.25 . V . 104W ,
100 H . t3
where V is the total transformer losses (kW), W is the air
resistance, H is the height (m) of the opening for the
output of air from the horizontal symmetry axis of
transformer (Figure 3), and t is the temperature rise (°C)
of the transformer room.
The cross-section area of the opening for the output of
air, F2 (m2), should be 10% to 15% larger than the
cross-section area of the opening for the input of air
(F1).
Gravel
The transformer is delivered at the industrial site of regulations of the local authorities (e.g. construction
Schneider Electric at Inofyta, Greece. authority, electrical utility).
The responsibility for the safe transportation, unloading, The unloading and transportation of the transformer
and connection to the network belongs to the should be done in such a way that the transformer does
transformer user. The substation must be constructed not deviate by more than 15° from its horizontal
after study and design from a certified engineer and the position. When the transformer is installed at its
relevant authorities (e.g. electrical utility, etc) must position, no deviation is allowed from its horizontal
approve the substation design. position. If the transformer is equipped with a Buchholz
Under the transformer, there should be an oil collection relay, the Buchholz connection instructions must be
tank, which has on its upper part a metallic mesh and followed.
gravel. The oil collection tank must have the appropriate Before the connection of the transformer to the network,
volume, so that in case of leakage all the quantity of the the transformer must be optically checked,
transformer oil can be collected within the oil collection in order to ensure that it has no damage during its
tank. The whole substation has an isodynamic mesh. transportation or it has no oil leakage. In case of
The resistance of the earthing must be less than 1Ω and scratches in its painting, the transformer must be
generally the substation must be constructed in repainted immediately in order to avoid future rust.
accordance with the existing instructions and
If the transformer has a Buchholz relay, the following connection instructions are suggested:
Initially, the protective cylindrical cover of the testing button of the Buchholz relay must be unscrewed, and then
the cylindrical piece of wood (which blocks the floats during transportation) must be removed.
Next, it is necessary to check (from the inspection door) if the Buchholz relay is full with oil. In case that it is not
full, the hexagonal cover must be removed and the ventilation valve must be opened so that the Buchholz relay
to be filled with oil. The filling and the free movement of the floats with the contacts are checked through the
inspection door. As soon as the Buchholz relay is filled with oil, the ventilation valve must be closed again.
A general arrangement of the Buchholz relay (and the transformer) is shown in Figure 4.
A typical wiring of thermometer and Buchholz relay connected to an alarm panel is shown in Figure 5.
Electrical contacts
The electrical contacts consist of two pairs of normally open contacts.
The one pair of contacts is used for alarm and the other pair of contacts for tripping off the circuit breaker.
The required voltage is 24-230V alternative or direct current.
In case of transformer
transportation, the dehumidifier
must be removed, its tap must
be sealed and a cap must 1. Top cover Type Oil H D F silica gel Tank
be put to the tube of the oil 2. Stainless tank weight weight volume
conservator. 3. Transparent silica
gel tank VE.1 1500 kg 250 mm 100 mm 1/2” GF 0,35 kg 0,465 dm3
Schneider 318-05AD/04.09
Inofyta Plant
55th km Athens-Lamia N.R., GR-32011 Inofyta, Greece