You are on page 1of 1

M

PT. MITRAIDA NUSANTARA ELEKTRIK


Design, Manufacture and Installation of Electrical Switchboard
Lingkungan Harum Manis (Jl. K.H. Nawawi) No.163 Cirimekar, Cibinong
Bogor 16917 Telp: (021) 8759518, 8762730 Fax: (021) 87916702
E-mail: mitraida@yahoo.com
Certificate No : 2014/0701

TEST REPORT OF OCR TERASAKI


PROJECT : PT. SRI INDONESIA DATE : 27 Okt 2021
NAME OF PANEL : LVMDB-201
UNIT NAME : INCOMING
BASE CURRENT : 3200 A
OCR TYPE : AGR-11BL-AL (18108-89)
CT : 3200 A

TEST RESULT
1. PROTECTIVE PICK UP CURRENT
SET DATA CURRENT INJECTION PICK UP
STANDARD RESULT
Current Seting Time Magnification % I (A) CURR.(A)
R 112 3584 105 ~ 120% 3584 OK
In = 1.0 ( 3200 A ) - S 113 3616 105 ~ 120% 3616 OK
T 114 3648 105 ~ 120% 3648 OK

2.PROTECTIVE LTD
SET DATA CURRENT INJECTION STANDARD TRIP TIME
RESULT
Current Seting Time Magnification % I (A) ( Sec ) Sec
R 600 19200 ±15% 10,2 OK
Ir = 1.0 ( 3200 A ) T1 = 10 Sec S 600 19200 ±15% 10,3 OK
T 600 19200 ±15% 10,5 OK

3. PROTECTIVE STD
SET DATA CURRENT INJECTION STANDARD TRIP TIME
RESULT
Current Seting Time Magnification % I (A) ( Sec ) Sec
R 120 23040 +70mS / -25mS 0,43 OK
Isd = 6 ( 19200 A ) T2 = 0,4 sec S 120 23040 +70mS / -25mS 0,42 OK
T 120 23040 +70mS / -25mS 0,43 OK

4. INSTANT
SET DATA CURRENT INJECTION STANDARD
TRIP TIME RESULT
Current Seting Time Magnification % I (A) TRIP ( Sec )
R 102 52224 ±20% - OK
Ii = 16 ( 51200 A ) - S 103 52736 ±20% - OK
T 104 53248 ±20% - OK

5. PROTECTIVE GF
SET DATA CURRENT INJECTION STANDARD
TRIP TIME RESULT
Current Seting Time Magnification % I (A) TRIP ( Sec )
R 120 ±20%
S 120 ±20%
Ig = ( A) T1 = Sec
T 120 ±20%
N 120 ±20%

Witness By
TESTED BY
1.
2.
3.
4.
5.

FM-QC-12 Rev : 0