You are on page 1of 1

PROSELECT : LV protection verification

Customer : PT.Apexindo Type of device : MASTERPACT MP16 H1


Site : Jakarta Serial number : 119110198306
Substation : - Control unit : ST208D
Switchboard : LV CT rated current : In = 1600 A
Function : ACBMP16H1 Breaking capacity (415 V) : 65 kA
Technician : Rendy

Date : 1/3/2013

Settings:

Long Time
Ir = 800 A
Tr(1,5 Ir) = 200 s

Short Time
Im = 10 x Ir
= 8000 A

Injection measurements
Measure Current (A) Guaranteed Time Guaranteed Result
ment no-tripping measured (s) tripping time
time (s) (s)
1 2400 14.1 18.7 35.4 valid
2 3200 9.02 11.6 20.04 valid
3 12000 0.0 0.01 0.03 valid
4 16000 0.0 0.01 0.03 valid

ACBMP16H1 1