Professional Documents
Culture Documents
Abstract—The fast and accurate detection of the single-phase- to compensate the capacitive fault current, the detection of
to-ground fault is of great significance for the reliability and a single-phase-to-ground fault is more difficult than that in
safety of the power supply. In this paper, novel algorithms for solid grounded systems. And then, the zero-sequence over the
distribution network protection were proposed with distributed
parameters analysis in non-direct grounded systems. At first, current protection algorithm and zero-sequence captive current
novel generating mechanisms of zero-sequence voltage and resid- direction based protection algorithm are no longer applicable
ual current were proposed. Then the compositions of residue in compensated networks [4]–[6]. But the grounding fault
parameters, including residual current and residual admittances, protection algorithm based on the active component direction
were decomposed in detail. After that, an improved algorithm of the zero-sequence current cannot be influenced by the com-
for a fault resistance calculation of a single phase-to-earth fault
was also proposed, and the algorithm is much more convenient pensation of the Petersen coil [7]. However, compared with the
as it only needs to measure the variation of the zero-sequence residual current in the feeder, the active component is lower,
voltage and does not need the prerequisites of the faulty feeder let alone the low-current faults are produced by high fault
selection. Furthermore, the fault feeder can also be selected by resistance. So, the sensitivity of the conventional detection
an improved calculation algorithm of zero-sequence admittance algorithm was low [7]. In addition, the active component of
of the faulty feeder, which cannot be affected by the asymmetry
of the network. Theoretical analysis and the MATALB/Simulink the zero-sequence current can also be greatly influenced by
simulation results demonstrate the effectiveness of the proposed the asymmetry of the networks, especially in high resistance
algorithms. ground faults.
Index Terms—Fault resistance calculation, fault feeder selec- The most important steady-state data-based algorithms for
tion, non-direct grounded system, residual parameters, residual single-phase-to-ground fault detection are DESIR (Detection
current, zero-sequence voltage. Sélective par des Intensités Residuéls/“Elective Detection us-
ing Residual Currents”) and DDA (Differential Detection
using phase-to-ground Admittances) [2], [6]–[8]. These al-
I. I NTRODUCTION gorithms are generally based on calculating and monitoring
the resistances of each phase and feeder, partial residual
I˙res = I˙bd = (U̇0 − U̇bd )(jωCΣ + GΣ ) where I˙bdΣ is the sum of the natural unbalance current of each
n
feeder, I˙bdΣ = I˙bdi (i = 1, 2, . . . , n), I˙bdi is the natural
P
= U̇∆res (jωCΣ + GΣ ) (7) i=1
unbalance current of the feeder i, k̇Σ is the sum of the natural
n
where U̇∆res is named as the residual voltage, which indicates P
unbalanced parameters of all feeders, k̇Σ = k̇i , k̇i is the
the deviation of the zero-sequence voltage U̇0 from the natural i=1
unbalanced voltage U̇bd . natural unbalanced parameters of the feeder i (i = 1, 2, . . . , n).
Analogously, the residual current I˙res of the non-direct The natural unbalanced voltage of the feeder i can be written
grounded system is equal to the neutral-to-earth current, as: as:
I˙bdi ĖA k̇i
U̇bdi = − =− (11)
I˙res + I˙Y0 = 0. (8) ẎΣi jωC Σi + GΣi
As can be seen from (7) and (9), despite the grounding I˙resi = (U̇0 − U̇bdi )(jωCΣi + GΣi ) (12)
modes being different, the calculation form of the residual I˙resΣ = (U̇0 − U̇bd )(jωCΣ + GΣ ). (13)
currents are the same. Through the above derivation we can
form a novel generating mechanism of the residual current in
İres1 Sound Feeder 1
the power network and its physical meaning are expounded:
asymmetrical power network produces the residual current İres
adaptively, and the current produced by the residual voltage
C1C C1B C1A
U̇∆res on the zero-sequence impedance of the feeder is residual ĖA G1C G1B G1A
ĖB
current. So, the residual current is controlled by the zero-
sequence impedance and the residual voltage, jointly. ĖC
Residual voltage can be changed by injecting the funda- İresi Fault Feeder i
. .
mental frequency current at the neutral-to-earth point [1], [7], U0 Y0
[22], or by adjusting the neutral-to-earth impedance, such as
the Petersen coil [23], [24]. GF CiC C C
GiC iB GiB iA GiA
the network, the small-random residual current of a feeder is B. Component Analysis of Residual Admittance
determined not only by the natural unbalance of itself, but also In the static version of DESIR [1], [6], [7], [25], the residual
by the natural unbalance of the whole system. current of the healthy feeders was considered as perpendicular
The sum of residual current of all feeders in (13) can be to the zero-sequence voltage. By analyzing the residual admit-
rewritten as: n tance, a fresh judgement of the phase relationship between the
X
I˙resΣ = I˙resi = τ̇Σ I˙bdΣ (15) residual current and zero-sequence voltage is essential.
i=1 1) In the Normal State
where τ̇Σ = Ẏ0 /ẎYΣ , and I˙resΣ = −U̇0 Ẏ0 . The residual admittance of the feeder in this paper is
2) In the Single-phase-to-ground Fault State defined as the quotient of the residual current divided by the
If the single-phase-to-ground fault is represented by a tran- zero-sequence voltage. In the normal state of the network,
sition conductance GF in feeder i, the zero-sequence voltage the residual admittances ẎresS of the sound feeder can be
U̇0F can be calculated as: calculated by using (10)–(12), as:
where τ̇Fi = (ẎΣi + GF )/(ẎYΣ + GF ). Likewise, the residual I˙resFi I˙bdi + I˙bdF I˙bdΣ − I˙bdi
ẎresFi = = ẎΣi − ẎYΣ + GF .
current of the sound feeder 1 in (19) can be rewritten as: U̇0F I˙bdΣ + I˙bdF I˙bdΣ + I˙bdF
(25)
I˙resS1 = −τ̇S1 I˙bdΣ − τ̇S1 I˙bdF + I˙bd1 (21) From (25), the residual admittance of the fault feeder is
where τ̇S1 = ẎΣi /(ẎYΣ + GF ). From (20) and (21), the the sum of three independent parts. Likewise, the residual
residual current in the fault network is the sum of three admittances ẎresS1 of the sound feeder 1 can be calculated
independent parts. One part is the natural unbalance current of as:
the feeder, the second part is proportional to the total natural I˙resS1 I˙bd1 I˙bd1
unbalance current of the system I˙bdΣ , and the third part is ẎresS1 = = ẎΣ1 − ẎYΣ − GF .
U̇0F I˙bdΣ + I˙bdF I˙bdΣ + I˙bdF
proportional to the unbalance current caused by the transition (26)
conductance I˙bdF . From (26), the residual admittance of the sound feeder is
If the single-phase-to-ground fault is metallic, GF → ∞, the also the sum of three independent parts. And the residual
unbalance introduced by the earth fault is considerably greater admittance of the sound feeder can also be affected by the
than the natural unbalances of the feeder. (20) and (21) can transition conductance GF . According to the component anal-
be rewritten as: ysis of the residual admittance, the phase relationship between
I˙resFi = −I˙bdΣ + I˙bdi (22) the residual current and the zero-sequence voltage is complex.
If the single-phase-to-ground fault is metallic,GF → ∞, the
I˙resS1 = I˙bd1 . (23) unbalance introduced by the earth fault is considerably greater
From (22) and (23), it can be seen that in the metallic than the natural unbalance of the feeder. (25) and (26) can be
single-phase-to-ground fault, the residual current of the sound rewritten as:
feeder is equal to its natural unbalance current, and the residual I˙resFi
current of the faulty feeder is equal to the negative sum of ẎresFi = = ẎΣi + k̇i − (ẎYΣ + k̇Σ ) ≈ ẎΣi − ẎYΣ
U̇0F
all sound feeders’ natural unbalance current. Then, the fault (27)
feeder can be selected. But, with low accuracy introduced by
˙
IresS1
the asymmetry of the network, this method cannot be used in ẎresS1 = = ẎΣ1 − k̇1 ≈ ẎΣ1 . (28)
the condition of the high- resistance-ground fault. U̇0F
LIU et al.: SINGLE-PHASE-TO-GROUND FAULT DETECTION WITH DISTRIBUTED PARAMETERS ANALYSIS IN NON-DIRECT GROUNDED SYSTEMS 143
As the unbalanced parameters (i.e., k̇i in equations (27) According to Kirchhoff’s current law (KCL), the sum of the
and (28) and k̇Σ ) are much smaller than the zero-sequence residual current variation of all feeders is equal to the variation
admittance (i.e., ẎΣi and ẎYΣ ), the residual admittance of current of the neutral-to-ground current. The residual current
the sound feeder is equal to its zero-sequence admittances, variation of the sound feeder 1 caused by the single-phase-to-
and the faulty feeder’s residual admittance is equal to the ground fault can be calculated as:
neutral grounding admittance plus the negative sum of all
the sound feeders’ zero-sequence admittances. In the metallic I˙∆resS1 = U̇∆0F ẎΣ1 . (33)
single-phase-to-ground fault, the residual current of the healthy Then the residual current variation of the fault feeder i
feeders is almost perpendicular to the zero-sequence voltage. caused by the single-phase-to-ground fault can be calculated
Then, the faulty feeder can be selected. But with low accuracy as:
introduced by the asymmetry of the network, this method also
cannot be used in the condition of the high-resistance-earth I˙∆resFi = U̇0F (ẎΣi + GF ) − U̇0 ẎΣi
fault. = −U̇∆0F (ẎYΣ − ẎΣi ). (34)
From (32) and (34), the faulted current can be recalculated
IV. A LGORITHMS FOR E ARTH FAULTS P ROTECTION
as:
A. Protection Algorithm of Fault Resistance Measurements I˙F = −U̇∆0F ẎYΣ . (35)
The algorithm of DDA can calculate the faulted current and
If the single-phase ground fault occurred on phase A, the
the fault resistance [6], [7], [25]. But this algorithm needs
fault resistance can be calculated as:
some preconditions, such as the fault feeder should be selected
correctly and the fault feeder’s zero-sequence admittances U̇0F + ĖA
RF = . (36)
should be measured accurately. What’s more, this algorithm −U̇∆0F ẎYΣ
not only needs to measure the variations of the zero-sequence
In (36), it is not necessary to measure the residual current
voltage, but also needs to measure the variation of the residual
variation of the fault feeder. So it is not necessary to select
current. Thus, it is complicated. And the DDA algorithm has
the fault feeder. Since the fault current I˙F has the same phase-
ignored the leakage conductance in its theoretical model.
angle with the fault phase-voltage U̇0FA = U̇0F + ĖA , the fault
From (10)–(12), in the normal state of the network, the
phase can be selected by comparing the phase-angle.
natural unbalanced current of the feeder i can be rewritten as:
In distribution systems, the normal switching events (such
I˙bdi = I˙resi − U̇0 ẎΣi . (29) as switching on/off a feeder) are essential. In order to mea-
sure the fault resistance adaptively, the total zero-sequence
From (16)–(18), if a single-phase-to-ground fault is repre- admittance of the network (i.e., ẎYΣ ) should be recalculated
sented by a transition conductance GF in feeder i, the residual after the switching events. At present, many algorithms for the
current of the fault feeder i can be rewritten as: total zero-sequence admittance measurements in a non-direct
I˙resFi = U̇0F ẎΣi + I˙F + I˙bdi (30) grounded system have been proposed [19], [26].
where I˙F = (U̇0F + ĖA )GF , I˙F is the faulted current. From B. Protection Algorithm of Fault Feeder Selection
(29) and (30), the faulted current I˙F can be calculated as: In order to select the fault feeder, [27] has proposed a
ground fault protection method based on the zero-sequence
I˙F = I˙resFi − I˙resi − (U̇0F − U̇0 )ẎΣi
calculated admittance. In [27], the asymmetry of the network
= I˙∆resFi − U̇∆0F ẎΣi (31) was not taken into account. The zero-sequence calculated
admittance of the sound feeder Ẏ0S1 and the fault feeder Ẏ0Fi
where I˙∆resFi is the variation of the residual current caused
were calculated respectively, as:
by the single-phase-to-ground fault; U̇∆0F is the zero-sequence
voltage variation caused by the single-phase-to-ground fault. I˙resS1
Ẏ0S1 = = ẎΣ1 (37)
If the single-phase-to-ground fault occurred on phase A, the U̇0F
fault resistance can be calculated as: I˙resFi
Ẏ0Fi = = ẎΣi − ẎYΣ (38)
U̇0F + ĖA U̇0F
RF = . (32)
I˙∆resFi − U̇∆0F ẎΣi It shows in (37) and (38) that the zero-sequence calculated
Equation (32) is derived based on the relationship of the admittance is equivalent to the residual admittance. However,
residual current and zero-sequence voltage, which is the same almost all networks are asymmetrical, so this method suffers
as with algorithm DDA [6], [7], [25]. As the theoretical model from the disadvantage of low accuracy in the condition of the
takes the leakage conductance of the feeder into account, (32) high-resistance-earth fault. And comparing (27) with (37), and
has the advantage of higher accuracy than the DDA algorithm. (28) with (38), this method can only be used in the case of a
As the DDA algorithm needs to measure the residual current metallic single-phase earth fault. An improved measurement of
variation I˙∆resFi of the fault feeder, the fault feeder selection zero-sequence calculated admittance is proposed below which
is a prerequisite for the fault resistance calculation. So it is of can eliminate the deviation introduced by the asymmetry of
some complexity. A simplified algorithm is proposed below. the network.
144 CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, VOL. 5, NO. 1, MARCH 2019
TABLE I
1) Zero-sequence Calculated Admittance of the Sound Feeder Z ERO S EQUENCE PARAMETERS OF THE S IMULATION S YSTEM
As it shows in (12) and (19) the improved zero-sequence
calculated admittance of the sound feeder 1 can be calculated Name Feeder 1 Feeder 2 Feeder 3 Whole
Network
as: CA (µF) 4.064 6.107 3.343 13.514
I˙∆resS1 Capacitance CB (µF) 4.071 5.819 3.027 12.917
ẎΣ1 = (39) CC (µF) 4.243 6.285 3.161 13.689
U̇∆0F RA (kΩ) 43.085 28.694 56.37 13.193
Resistance RB (kΩ) 42.974 28.694 56.306 13.179
where I˙∆resS1 = I˙resS1 − I˙res1 , I˙∆resS1 is the residual current RC (kΩ) 42.717 28.530 56.054 13.106
variation of the sound feeder 1 caused by the earth fault. Capacitive current iC (A) 22.451 33.031 17.287 72.770
Resistance current iR (A) 0.404 0.605 0.308 1.316
2) Zero-sequence Calculated Admittance of the Fault Feeder Damping (%) 1.797 1.831 1.781 1.809
Mismatch (%) 1.420 2.238 2.885 1.750
From (12) and (18), we can see that the residual current
variation of the fault feeder i can be calculated as:
According to the simulation system parameters listed in
I˙∆resFi = I˙resFi − I˙resi = U̇∆0F ẎΣi + I˙F . (40) Table I, theoretical values of the natural unbalanced voltage
U̇bd and the natural unbalance currents I˙bd were calculated
From (35) and (40), it shows that the improved zero- respectively by using (1) and (4). Simulation values of the
sequence calculated admittance of the fault feeder i can be natural unbalanced voltage U̇bd and the natural unbalance cur-
calculated as: rent I˙bd were measured respectively in the simulation system.
I˙∆resFi Theoretical and simulation results are shown in Table II.
ẎΣi − ẎYΣ = . (41)
U̇∆0F TABLE II
T HEORETICAL AND S IMULATION R ESULTS OF THE NATURAL
Based on the above analysis, the fault feeder can be selected U NBALANCED VOLTAGE AND THE NATURAL U NBALANCE C URRENTS
by comparing the zero-sequence calculated admittance. In
Name Feeder 1 Feeder 2 Feeder 3 Whole
particular, the zero-sequence calculated admittance of the Network
sound feeder is equal to its zero-sequence admittance, but TheoreticalAmplitu- 81.963 290 129.229 401 166.554 650 101.049 452
the zero-sequence calculated admittance of the fault feeder is value of de (V)
Ubd Phase −57.170 171−96.782 516−153.974 722−106.546 771
equal to the value that its zero-sequence admittance minus the angle (◦ )
total zero-sequence admittance of the network. In addition, Simulation Amplitu- 81.963 289 129.229 401 166.554 649 101.049 450
as the improved fault feeder selection algorithm only needs value of de (V)
to measure the variation of each feeder’s residual current, the Ubd Phase −57.170 179−96.782 526−153.974 733−106.546 780
angle (◦ )
switching events have nothing to do with the algorithm as well TheoreticalAmplitu- 0.318779 0.7394 653 0.498 786 1.273 842
as the fault resistance and the asymmetry of the network. value of de (A)
Ibd Phase 31.800 177 −7.831 441 −64.995 289 −17.583 013
angle (◦ )
V. S IMULATION A NALYSIS Simulation Amplitu- 0.318 784 0.739 478 0.498 794 1.273 864
value of de (A)
Ibd Phase 31.800 173 −7.831 446 −64.995 295 −17.583 019
In order to validate the low-current fault detection algo- angle (◦ )
rithms proposed, extensive simulation tests have been run by
using the Matlab/Simulink shown in Fig. 3. The simulation
system is a 10 kV distribution network whose angular fre- A. Component Analysis of the Residual Current
quency is 50 Hz. The simulation system has three feeders. According to the parameters of the simulation system in
Different neutral grounded modes were considered. The in- Table I, the quotient τ̇i in (14) can be calculated. And
fluences of the unbalanced distribution parameters were also according to the natural unbalance currents in Table II, the
investigated. Performance of the protection against earth faults theoretical results of the residual currents can be calculated by
was assessed. The zero sequence parameters of the simulation using (14). Theoretical and simulation results of the residual
system are listed in Table I. currents of each feeder in the resistance grounded system are
shown in Table III. The ground resistance is 800 Ω.
İresS1
G T Feeder 1 TABLE III
C OMPONENT A NALYSIS OF THE R ESIDUAL C URRENT IN THE R ESISTANCE
G ROUNDED S YSTEM
İresF2
Feeder 2
Name Feeder 1 Feeder 2 Feeder 3
TZ GF Amplitude 0.306474 0.450 900 0.235 983
Quotient τi Phase angle (deg)
İresS3 5.658 430 5.639 157 5.667 515
. Feeder 3 Theoretical Amplitude (A) 0.272 320 0.171 586 0.398 767
Y0 value of Ires Phase angle (deg) −65.934 245 6.058 497 77.943 170
Simulation Amplitude (A) 0.272 325 0.171 589 0.398 773
value of Ires Phase angle (deg) −65.934 327 6.058 732 77.943 140
Amplitude relative error (%) −0.001 705 −0.001 620 −0.001 432
Fig. 3. The radial operated distribution simulation system with a faulty
Phase angle relative error (%) −0.000 123 −0.003 880 0.000 040
feeder.
LIU et al.: SINGLE-PHASE-TO-GROUND FAULT DETECTION WITH DISTRIBUTED PARAMETERS ANALYSIS IN NON-DIRECT GROUNDED SYSTEMS 145
TABLE V
Table VI shows that (14) can calculate the residual current FAULT- CURRENT M EASUREMENT IN D IFFERENT N EUTRAL P OINT
accurately which illustrates that the component analysis of the G ROUNDED C ONDITIONS
residual current is correct.
Neutral Point Grounded Conditions
Name Ungrounded Resistance Petersen Coil Petersen Coil
B. Component Analysis of Residual Admittance (R = 800 Ω) (v a =–15%) in Parallel with
Resistance
As the natural unbalance currents are presented in Table II, (v = 0%,
I˙bdi /I˙bdΣ can be calculated. And according to the simulation R = 400 Ω)
Amplit- 303.133 519 300.103 013 1938.399 717 1221.587 413
system parameters in Table I, the theoretical results of the ude (V)
U∆0F
feeder residual admittances can be calculated by using (24). Phase −86.905 962 −81.324 723 70.420 747 −1.302 286
Theoretical and simulation results of the residual admittances Angle
(deg)
of each feeder in the resistance grounded system are shown Amplit- 3.821 341 3.808 436 3.691 307 3.332 466
in Table IV. The neutral ground resistance is also 800 Ω. Theoretical ude (A)
value of IF Phase 2.057 797 1.987 197 –12.703 419 –1.302 286
Angle
TABLE IV
(deg)
C OMPONENT A NALYSIS OF R ESIDUAL A DMITTANCE IN R ESISTANCE
Amplit- 3.821 378 3.797 087 3.690 930 3.332 437
G ROUNDED S YSTEM Simulation ude (A)
value of IF Phase 2.057 785 1.883 774 –12.702 814 –1.298 787
Name Feeder 1 Feeder 2 Feeder 3 Angle
Amplitude 0.250250 0.580 500 0.391 560 (deg)
Ibdi /IbdΣ Phase angle (deg) 49.383 190 9.751 572 −47.412 276 Amplitude relative –0.000 956 0.297 988 0.010 104 0.000 880
Theoretical Amplitude 2.712 939 1.709 395 3.972 643 error (%)
value of Yres (×10−3 S) Phase angle 0.000 594 5.204 423 0.004 761 0.268 711
Phase angle (deg) 34.960 686 −73.046 571 178.838 100 relative error (%)
Simulation Amplitude 2.712 981 1.709 420 3.972 694 a v is the resonance deviation of the compensation network.
value of Yres (×10−3 S)
Phase angle (deg) 34.960 692 −73.046 249 178.838 155 TABLE VI
Amplitude relative error (%) −0.001 562 −0.001 477 −0.001 290 T HE FAULT P HASE S ELECTION AND FAULT R ESISTANCE M EASUREMENT
Phase angle relative error (%) −0.000017 0.000 442 −0.000 031 IN D IFFERENT N EUTRAL P OINT G ROUNDED C ONDITIONS
TABLE VII
T RADITIONAL FAULT F EEDER S ELECTION IN D IFFERENT N EUTRAL VI. C ONCLUSION
P OINT G ROUNDED C ONDITIONS WITH 10 Ω FAULT R ESISTANCE
In this paper, several algorithms for single-phase-to-ground
Neutral Point Grounded Conditions fault detection with distributed parameters analysis in a non-
Name Ungrounded Resistance Petersen Coil Petersen Coil direct grounded system were proposed. The novel generating
(R = 800 Ω) (v = −15%) in Parallel mechanisms of zero-sequence voltage and residual current
with Resista-
nce (v = 0%, enrich the phase-sequence-analysis theory. The residual cur-
R = 400Ω) rent and the residual admittance in the fault network can
Amplitude 3.92546 6.847368 2.921928 3.92546 be decomposed into three separate parts. According to the
Feeder1 (×10−3 S)
Relative 0.929 961 –0.5323 963 –2.430 890 0.929 961
component analysis of the residual admittance, the phase
error(%) relationship between the residual current and zero-sequence
Amplitude 3.925845 6.998331
Feeder2 (×10−3 S)
2.920965 3.925845 voltage can also be recognized more accurately. The fault
current and fault resistance can be calculated accurately only
relative 0.939 844 1.660 560 –2.463 067 0.939 844
error(%) by measuring the zero-sequence voltage variation caused by
Amplitude 3.918 618 7.199 137
Feeder3 (×10−3 S)
2.916 139 3.918 618 the single-phase earth fault. It no longer needs the prerequisites
of the faulty feeder selection and the fault feeder’s zero-
relative 0.754 028 4.577 537 -2.624 210 0.754 028
error(%) sequence admittances measurement. And the fault phase can
also be selected. The fault feeder can be selected by comparing
TABLE VIII the zero-sequence calculated admittance, which only needs to
T RADITIONAL FAULT F EEDER S ELECTION IN D IFFERENT N EUTRAL measure each feeder’s residual current variation. The improved
P OINT G ROUNDED C ONDITIONS WITH 1500 Ω FAULT R ESISTANCE fault feeder selection method will not be affected by the fault
resistance and the asymmetry of the network.
Neutral Point Grounded Conditions
Name Ungrounded Resistance Petersen Coil Petersen Coil
(R = 800 Ω) (v = −15%) in Parallel
with Resista-
R EFERENCES
nce (v = 0%, [1] K. J. Sagastabeitia, I. Zamora, A. J. Mazón, Z. Aginako, and G. Buigues,
R = 400 Ω) “Low-current fault detection in high impedance grounded distribution
Amplitude 5.332 988 9.035 886 4.233 062 5.332 988 networks, using residual variations of asymmetries,” IET Generation,
Feeder1 (×10−3 S)
Transmission & Distribution, vol. 6, no. 12, pp. 1252–1261, Dec. 2012.
Relative 37.119 773 31.258 902 41.350 520 37.119 773 [2] D. Griffel, V. Leitloff, Y. Harmand, and J. Bergeal, “A new deal for
error(%) safety and quality on MV networks,” IEEE Transactions on Power
Amplitude 5.383 176 9.300 375 4.088 535 5.38 3176 Delivery, vol. 12, no. 4, pp. 1428–1433, Oct. 1997.
Feeder2 (×10−3 S)
[3] X. J. Zeng, K. Yu, Y. Y. Wang, and Y. Xu, “A novel single phase
Relative 38.410 195 35.100 975 36.524 451 38.410 195 grounding fault protection scheme without threshold setting for neutral
error(%) ineffectively earthed power systems,” CSEE Journal of Power and
Amplitude 3.697 387 8.426 913 2.730 330 3.697 387 Energy Systems, vol. 2, no. 3, pp. 73–81, Sep. 2016.
Feeder3 (×10−3 S) [4] M. Givelberg, E. Lysenko, and R. Zelichonok, “Zero sequence direc-
Relative −4.934 171 22.412 705 −8.828 755 −4.934 171 tional earth-fault protection with improved characteristics for compen-
error(%) sated distribution networks,” Electric Power Systems Research, vol. 52,
no. 3, pp. 217–222, Dec. 1999.
[5] X. J. Zeng, K. K. Li, W. L. Chan, S. Su, and Y. Y. Wang, “Ground-fault
TABLE IX feeder detection with fault-current and fault-resistance measurement in
I MPROVED FAULT F EEDER S ELECTION IN D IFFERENT N EUTRAL P OINT mine power systems,” IEEE Transactions on Industry Applications, vol.
G ROUNDED C ONDITIONS WITH 1500 Ω FAULT R ESISTANCE 44, no. 2, pp. 424–429, Mar./Apr. 2008.
[6] T. Welfonder, V. Leitloff, R. Fenillet, and S. Vitet, “Location strategies
Neutral Point Grounded Conditions and evaluation of detection algorithms for earth faults in compensated
Name ungrounded Resistance Petersen Coil Petersen Coil MV distribution systems,” IEEE Transactions on Power Delivery, vol.
(R = 800 Ω) (v = −15%) in Parallel 15, no. 4, pp. 1121–1128, Oct. 2000.
with Resista- [7] V. Leitloff, R. Feuille, and D. Griffel, “Detection of resistive single-phase
nce (v = 0%, earth faults in a compensated power-distribution system,” European
R = 400 Ω) Transactions on Electrical Power, vol. 7, no. 1, pp. 65–73, Jan./Feb.
Amplitude 3.889 329 3.980 542 3.889 532 3.889 306 1997.
Feeder1 (×10−3 S) [8] I. Zamora, A. J. Mazon, K. J. Sagastabeitia, and J. J. Zamora, “New
Relative −0.017 110 −2.362 721 −0.022 341 −0.016 519 method for detecting low current faults in electrical distribution sys-
error(%) tems,” IEEE Transactions on Power Delivery, vol. 22, no. 4, pp. 2072–
Amplitude 6.884 084 6.918 631 7.212 921 6.793 648 2079, Oct. 2007.
Feeder2 (×10−3 S) [9] F. Ruz, A. Quijano, and E. Gómez, “DSTRP: a new algorithm for high
relative –0.000 955 –0.502 798 –4.777 775 1.312 759 impedance fault detection in compensated neutral grounded M.V. power
error(%) systems,” European Transactions on Electrical Power, vol. 13, no. 1,
Amplitude 2.994 755 2.994 755 2.994 912 2.994 738 pp. 23–28, Jan./Feb. 2003.
Feeder3 (×10−3 S) [10] K. J. Sagastabeitia, I. Zamora, A. J. MazÓn, Z. Aginako, and G. Buigues,
relative –0.000 941 –0.000 941 –0.006 191 –0.000 369 “Phase asymmetry: a new parameter for detecting single-phase earth
error(%) faults in compensated MV networks,” IEEE Transactions on Power
Delivery, vol. 26, no. 4, pp. 2251–2258, Oct. 2011.
[11] S. Hänninen, M. Lehtonen, and U. Pulkkinen, “A probabilistic method
the zero-sequence calculated admittance accurately, and the for detection and location of very high resistive earth faults,” Electric
improved fault feeder selection method will not be affected Power Systems Research, vol. 54, no. 3, pp. 199–206, Jun. 2000.
[12] Y. Sheng and S. M. Rovnyak, “Decision tree-based methodology for
by the fault resistance, neutral point grounded conditions, and high impedance fault detection,” IEEE Transactions on Power Delivery,
the asymmetry of the network. vol. 19, no. 2, pp. 533–536, Apr. 2004.
LIU et al.: SINGLE-PHASE-TO-GROUND FAULT DETECTION WITH DISTRIBUTED PARAMETERS ANALYSIS IN NON-DIRECT GROUNDED SYSTEMS 147
[13] A. H. Etemadi and M. Sanaye-Pasand, “High-impedance fault detection Hongzhong Ma received his B.S. (1989), M.S.
using multi-resolution signal decomposition and adaptive neural fuzzy (1994) and Ph.D (2002) degrees from Southeast
inference system,” IET Generation, Transmission & Distribution, vol. 2, University of China. Currently, he is a Professor
no. 1, pp. 110–118, Jan. 2008. at Hohai University. He is also the Director of
[14] C. J. Kim, S. J. Lee, and S. H. Kang, “Evaluation of feeder monitoring the Department of Electrical Engineering, Hohai
parameters for incipient fault detection using Laplace trend statistic,” University, China. His primary research interests are
IEEE Transactions on Industry Applications, vol. 40, no. 6, pp. 1718– condition monitoring and fault diagnosis of electri-
1724, Nov./Dec. 2004. cal equipment, electrical machines and drives, and
[15] X. Z. Dong, J. Wang, S. X. Shi, B. Wang, B. Dominik, and M. Redefern, power system research.
“Traveling wave based single-phase-to-ground protection method for
power distribution system,” CSEE Journal of Power and Energy Systems,
vol. 1, no. 2, pp. 75–82, Jun. 2015.
[16] M. F. Abdel-Fattah and M. Lehtonen, “Transient algorithm based on
earth capacitance estimation for earth-fault detection in medium-voltage
networks,” IET Generation, Transmission & Distribution, vol. 6, no. 2,
pp. 161–166, Feb. 2012. Honghua Xu received his B.S. (2004), M.S. (2007)
[17] M. Michalik, W. Rebizant, M. Lukowicz, S. J. Lee, and S. H. Kang, and Ph.D. (2011) degrees from the Institute of
“High-impedance fault detection in distribution networks with use of Microelectronics, Peking University, Beijing, China.
wavelet-based algorithm,” IEEE Transactions on Power Delivery, vol. Since 2011, he has been with the Nanjing Power
21, no. 4, pp. 1793–1802, Oct. 2006. Supply Company, Jiangsu Electric Power Company,
[18] J. P. Lu, J. Li, W. Y. Li, Y. Li, and Y. Xue, “A new approach to Nanjing, Jiangsu, China. His research interests focus
identifying faulty lines in distribution systems based on traveling wave on condition monitoring and fault diagnosis of power
refraction and coupling,” Electric Power Systems Research, vol. 78, no. systems, smart grids and the integration of renewable
3, pp. 353–360, Mar. 2008. energy sources in the grid.
[19] X. J. Zeng, Y. Xu, and Y. Y. Wang, “Some novel techniques for insu-
lation parameters measurement and Petersen-coil control in distribution
systems,” IEEE Transactions on Industrial Electronics, vol. 57, no. 4,
pp. 1445–1451, Apr. 2010.
[20] H. N. Yao, M. Y. Cao, The Resonance Grounding of the Electronic
System. Beijing, China: China Electron. Power Press, 2001, pp. 34–36.
(in Chinese) Ping Ju received B.Sc. and M.Sc. degrees from
[21] Q. C. Zhang, Y. Zhang, W. N. Song, and D. Z. Fang, “Transmission Southeast University, Nanjing, China in 1982 and
line fault location for single-phase-to-earth fault on non-direct-ground 1985, respectively, and a Ph.D. degree from Zhe-
neutral system,” IEEE Transactions on Power Delivery, vol. 13, no. 4, jiang University, Hangzhou, China, all in Electri-
pp. 1086–1092, Oct. 1998. cal Engineering. From 1994 to 1995, he was an
[22] X. J. Zeng, K. K. Li, W. L. Chan, and X. G. Yin, “On-site safety Alexander-von-Humboldt Fellow at the University
evaluation for earth fault in mining power systems,” IEEE Transactions of Dortmund, Germany. He is currently a Professor
on Industry Applications, vol. 39, no. 6, pp. 1563–1569, Nov./Dec. 2003. of Electrical Engineering with Hohai University,
[23] K. Y. Lien, S. L. Chen, C. J. Liao, T. Y. Guo, T. M. Lin, and J. S. Nanjing, China. His research interests include high
Shen, “Energy variance criterion and threshold tuning scheme for high voltage insulation technology, modeling and control
impedance fault detection,” IEEE Transactions on Power Delivery, vol. of power systems.
14, no. 3, pp. 810–817, Jul. 1999.
[24] I. Zamora, A. J. Mazón, K. J. Sagastabeitia, O. Picó, and J. R. Saenz,
“Verifying resonant grounding in distribution systems,” IEEE Computer
Applications in Power, vol. 15, no. 4, pp. 45–50, Oct. 2002.
[25] V. Leitloff, “Etude, conception et réalisation d’un automate de gestion
de réseaux MT compensés,” Ph.D. dissertation, Institut National Poly-
technique de Grenoble (INPG)/Rhone Alpes, France, 1994.
[26] B. W. Liu, H. Z. Ma, P. F. Shen, and B. B. Chen, “New flexible control
system of full compensation single-phase ground fault fundamental
current,” Proceedings of the CSEE, vol. 36, no. 9, pp. 2322–2330, Mar.
2016. (in Chinese)
[27] X. J. Zeng, X. G. Yin, Z. Zhang, D. S. Chen, and M. H. Wen, “Study on
feeder grounding fault protection based on zero sequence admittance,”
Proceedings of the CSEE, vol. 21, no. 4, pp. 5–10, Apr. 2001. (in
Chinese)