You are on page 1of 8

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO.

5, OCTOBER 2014 2215

A Novel Method of Ground Fault Phase


Selection in Weak-Infeed Side
Shaofeng Huang, Lan Luo, and Kai Cao

Abstract—The sequence current-based fault phase selector I. INTRODUCTION


and traditional low-voltage fault phase selector have diffi-
culties in being applied to the weak-infeed side. This study
proposes a new method of ground fault phase selection for
high-voltage/extra-high-voltage transmission-line protection
under weak-infeed conditions. The method utilizes the relative
I N PROTECTION for the transmission line, faults should be
cleared as fast as possible in order to enhance the transient
stability of the power system, minimizing voltage disturbances
phase-angle relationship between negative- and zero-sequence and damage to the equipment [1]. As a primary procedure of
voltages and a relative phase relationship between superimposed the relay, fault phase selection is required to be fast and accurate
positive-sequence voltage and superimposed negative-sequence
voltage to identify the fault phase under weak-infeed conditions. in transmission-line protection. The measured impedance of the
Theory analysis and simulation have proven that the proposed distance relay indicates the distance from the relay to fault point
method has high immunity against fault resistance as well as correctly only if the fault phase selector identifies the fault phase
impedance phase-angle inequality and overload. accurately.
Index Terms—Distance protection, fault phase selector, fault The methods of fault phase selection can be divided into three
resistance, ground fault, impedance inequality, overload, relative categories: 1) methods based on frequency components; 2)
phase angle, sequence voltage difference, superimposed compo- methods based on superimposed components; and 3) methods
nents, weak-infeed condition.
based on transient signals [2]–[6]. Currently, these three
categories are all applied in high-voltage/extra-high-voltage
NOMENCLATURE (HV/EHV) transmission-line protection. In [2], a new method
of fault phase selection is proposed for phase selection on
Prefault voltage at the fault point. six-phase transmission lines by using six-sequence compo-
nents. In [3], a phase selection algorithm for weak-infeed
Superimposed sequence voltage at the fault
conditions and cross-country faults based on sequence com-
point , 2, 0.
ponents and adaptive techniques is presented. In [4], a phase
Superimposed sequence voltage at the relay selector using superimposed sequence currents in conjunc-
point , 2, 0. tion with the correlation analysis is proposed to improve the
Sequence voltage at the fault point , 2, 0. operation performance of fast phase selection, which com-
bines the advantage of the phase-comparison scheme with
Sequence voltage at the relay point , 2, 0. a magnitude comparison scheme to guarantee the reliability
Sequence current at the fault point , 2, 0. of phase selection. In [5], a phase selection scheme based
on fault-generated high-frequency noise and artificial neural
Integrated impedance in sequence network networks (ANNs) is presented. In [6], the fault phase selector
, 2, 0. based on the combination of current component and adaptive
Impedance from relay to fault point , 2, 0. cumulative sum method (ACUSUM) is proposed, which can
System equivalent impedance behind relay detect even low magnitude faults with high resistances and has
point , 2, 0. good performance in speed and accuracy. In [7], a method of
fault phase selection based on the initial current traveling wave
Phase angle of . and wavelet-transform technology is proposed.
Rated voltage of the transmission line. In China, the sequence current-based fault phase selector [8]
is widely used. Reference [9] proposes an improved fault phase
selector aimed at solving the problem of probable malopera-
tion of the sequence current-based fault phase selector during
Manuscript received August 01, 2013; revised December 03, 2013 and March
15, 2014; accepted April 27, 2014. Date of publication May 20, 2014; date of power swings. In [10], a fault phase selection scheme devel-
current version September 19, 2014. This work was supported by the National oped from [8] for faults with high-fault resistance during normal
Basic Research Program of China (973 Program) under 2012CB215206. Paper
operating situations and power swings is presented. Although
no. TPWRD-00858-2013.
The authors are with the Electrical Engineering Department, North China the sequence current-based fault phase selector has many ad-
Electric Power University, Beijing 102206, China (e-mail: huangsf@sf-auto. vantages, it has difficulties applying in weak-infeed side. Be-
com; luo57093652@163.com; caokai_hd@163.com).
sides, the sequence current-based fault phase selector utilizes
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. measured values of phase to ground impedance and phase to
Digital Object Identifier 10.1109/TPWRD.2014.2322073 phase impedance to identify the single phase to ground faults

0885-8977 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
2216 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 5, OCTOBER 2014

Denote the phase A to ground fault as an A-G fault and a


phase B to phase C to ground fault as a BC-G fault. It is the
same way for the B-G fault, CA-G fault, C-G fault, and AB-G
fault.
According to [14], when the A-G fault occurs, the positive-
Fig. 1. Weak-infeed system. and negative-sequence voltages at the fault point are opposite
in phase; when the BC-G fault occurs, the phase angle of the
positive- and negative-sequence voltage at the fault point are
and phase-to-phase to ground faults; it may cause maloperation equal. However, considering the load effect, the phase angle of
under serious overload condition. positive-sequence voltage at the relay point is not equal to the
A system may be considered weak when the source phase angle of the positive-sequence voltage at the fault point.
impedance is high. The weak-infeed system often has relatively In order to eliminate the load effect, the superimposed sequence
low values of fault current availability [11]. Weak-infeed con- voltages are utilized for fault phase selection in this study.
ditions occur only under fault conditions. They can be divided When the A-G bolted fault occurs, the superimposed posi-
into two types, conditional and unconditional. Conditional weak tive- and negative-sequence voltages at the fault point can be
infeed occurs in complex system configuration and is dependent expressed as follows:
on fault location; unconditional weak infeed occurs mainly
with independent power producers [12]. Under weak-infeed (1)
condition, no matter conditionally or unconditionally, because
the source impedance is very high, the relay current related
element cannot receive reliable fault currents from source for (2)
fault detecting [13]. The sequence current-based fault phase se-
lector may have difficulties in being applied to the weak-infeed According to (1) and (2) and the assumption that impedances
side. The traditional low-voltage (LV) fault phase selector may throughout the system have the same phase angles, the super-
have some problems in being applied to the weak-infeed side; imposed positive- and negative-sequence voltages at the fault
the fault resistance will make it difficult to choose the voltage point thus have the same phase angle, as shown
threshold.
This paper proposes a method of fault phase selection that can (3)
be applied to the weak-infeed condition, regardless of whether
it is conditional or unconditional. The relay only needs the local
When the BC-G bolted fault occurs, the superimposed pos-
voltage information for the fault phase selection by using this
itive- and negative-sequence voltages at the fault point can be
method. The method starts by using the relative phase-angle
expressed as follows:
relationship between negative- and zero-sequence voltages to
define a distinctive phase region which indicates the probable
fault phases. Then, the relative phase-angle relationship be- (4)
tween superimposed positive- and negative-sequence voltages
is used to differentiate between single-phase-to-ground faults (5)
and phase-to-phase-to-ground faults. The method provides a
simple way for fault phase selection in the weak-infeed side where “//” means the parallel connection.
and it has high immunity against fault resistance, impedance According to (4) and (5), the relative phase-angle difference
phase-angle inequality, and overload. between the superimposed positive- and negative-sequence
voltages is obtained, which is equal to 180 , as shown
II. ANALYSIS OF FAULT CHARACTERISTICS
(6)
The difficult part of fault phase selection is distinguishing be-
tween the single-phase-to-ground fault and phase-to-phase-to-
ground fault, because the phase-to-phase fault does not gen- According to the analysis from before, it can be concluded
erate zero-sequence components. It is easy to distinguish the that the superimposed positive- and negative-sequence voltages
phase-to-phase fault from other asymmetry faults by setting the at the fault point have the same phase angles when a single-
zero-sequence threshold. phase-to-ground bolted fault occurs; and the superimposed pos-
Taking a phase A to ground fault and phase B to phase C to itive- and negative-sequence voltages at the fault point are op-
ground fault, for instance, the characteristics of these two types posite in phase when a phase-to-phase-to-ground bolted fault
of ground faults are analyzed in this section. occurs, as shown in Fig. 2. The method of ground fault phase
Fig. 1 shows an equivalent two-end system. The relay at point selection in this study is based on this conclusion.
M is under a weak-infeed condition. The equivalent impedance Under normal conditions, the relay can use the relative phase-
behind point M is very high or there is no source behind point angle relationship between negative- and zero-sequence cur-
M. k is the fault point. It is assumed that all the impedances rents for fault phase selection. But the negative-sequence cur-
throughout the system have the same phase angle. rent is at a very low level in the weak-infeed side. Therefore, the
HUANG et al.: NOVEL METHOD OF GROUND FAULT PHASE SELECTION IN WEAK-INFEED SIDE 2217

Fig. 4. Influence of impedance phase-angle inequality on the relative phase-


angle relationship between negative- and zero-sequence voltages. (a) A-G fault.
Fig. 2. Phase relationship of fault components of sequence voltages. (b) BC-G fault.

III. CRITERIA OF GROUND FAULT PHASE SELECTION IN THE


WEAK-INFEED SIDE

A. Influencing Factors
In order to establish the criteria for ground fault phase se-
lection in the weak-infeed side, the influencing factors, such
as fault resistance, impedance phase-angle inequality, and over-
load are studied during this section.
1) Influence on the Relative Phase-Angle Relationship Be-
Fig. 3. Relative phase-angle relationship between negative- and zero-sequence
voltages.
tween Negative- and Zero-Sequence Voltages: When an A-G
fault with fault resistance occurs, the negative- and zero-se-
quence voltages at the relay point can be expressed as follows:
relative phase-angle relationship between negative- and zero-
sequence voltages is used for the fault phase selection instead. (11)
When the A-G bolted fault occurs, the following can be
obtained: (12)

The phase-angle difference between negative- and zero-se-


quence voltages is obtained
(7)
When the BC-G bolted fault occurs, the following can be ob-
tained: (13)

(8) According to (13), the phase-angle difference between neg-


ative- and zero-sequence voltages is not affected by fault re-
sistance. Consider that the phase angle of the transmission-line
The relative phase-angle relationships between negative- and impedance varies from 75 to 85 and the phase angles of the
zero-sequence voltages under different types of ground fault are transformer impedance and power source are 90 approximately
shown in Fig. 3. in the HV/EHV system. The error of phase angle caused by
When the relay is under a weak-infeed condition, the equiv- impedance phase-angle inequality is considered to not be more
alent positive- and negative-sequence impedances behind it are than 15 . It is still considered . The phase-angle dif-
considered very large. The superimposed positive- and nega- ference between and can be neglected. Therefore, the
tive-sequence voltages at the relay point can be expressed as phase-angle difference has a region of 30 to 30 , as shown
follows: in Fig. 4(a).
As for the BC-G fault with fault resistance, the grounding
(9) resistance (denoted as ) can be much larger than interphase
resistance, so the influence of interphase resistance is neglected.
(10) According to the sequence network, the zero-sequence voltage
at the fault point can be expressed as follows:
Based on the analysis above, the relative phase-angle rela-
tionship between negative- and zero-sequence voltages can be (14)
used to indicate the probable fault phases. Then, the relative
phase-angle relationship between superimposed positive- and The phase-angle difference between negative- and zero-se-
negative-sequence voltages can be used to distinguish between quence voltages is obtained, as shown in (15). According to
the two types of ground faults. (15), the possible variation range of phase angle is from 90
2218 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 5, OCTOBER 2014

to 15 considering the influences of fault resistance and phase-


angle inequality, as shown in Fig. 4(b). The phase-angle differ-
ence is higher than 90 when the BG-G fault occurs because
when the fault resistance is very large, the zero-sequence
voltage is at a very low level and the fault phase selector will
identify it as a phase-to-phase fault

(15)
Fig. 5. Relative phase-angle relationship of superimposed sequence voltages
2) Influence on the Relative Phase-Angle Relationship when the BC-G fault occurs .
Between Superimposed Positive- and Negative-Sequence Volt-
ages: When an A-G fault with fault resistance occurs, the
superimposed positive-sequence voltage can be expressed as
follows:

(16)

According to (10), (11), and (16), the following equation is


obtained:

(17)

According to (17), the phase-angle difference between su-


Fig. 6. Distinctive phase region.
perimposed positive- and negative-sequence voltages is not af-
fected by fault resistance. Considering , the phase-
angle difference is almost 0 . on the equivalent impedances and fault resistance. Therefore,
As for the BC-G fault with fault resistance, the superimposed the influence of overload can be regarded as an influence of the
positive- and negative-sequence voltages are expressed as fol- equivalent impedances which has been discussed above.
lows:
B. Criteria of Fault Phase Selection
(18) The criteria of ground fault phase selection in the weak-infeed
side are proposed during this chapter. The criteria include two
(19) steps.
1) Distinctive Phase Region: Based on the analysis from
before, a distinctive phase region is proposed. Three separated
According to (18) and (19), the phase-angle difference be-
phase regions are divided, as shown in Fig. 6. The zero-sequence
tween superimposed positive- and negative-sequence voltages
voltage is regarded as the reference vector. The region where the
is obtained, as shown in (20). Through mathematical analysis,
negative-sequence voltage is indicates the probable fault phases.
the following inequalities are obtained, as shown:
Compared to the sequence current-based fault phase selector,
the negative-sequence voltage is easier for the relay to pick up
(20) in the weak-infeed side.
2) Fault-Type Identification: Considering the influ-
encing factors, the principle for distinguishing between
(21) the single-phase-to-ground fault and phase-to-phase-to-ground
fault in the weak-infeed side is proposed, as shown in (22),
According to (20) and (21), the phase-angle difference be- (23), and Fig. 7.
tween superimposed positive- and negative-sequence voltages Single-phase-to-ground fault
has a region of 165 to 270 when a BC-G fault occurs. The
relative phase-angle relationship is shown in Fig. 5. (22)
In the equivalent sequence networks, the influence of the
overloading condition is reflected in two aspects: 1) changing Phase-to-phase to ground fault
the equivalent electromotive force and 2) changing the equiva-
lent impedances (such as and ). According to (13), (15), (23)
(17), and (20), the relative phase-angle differences only depend
HUANG et al.: NOVEL METHOD OF GROUND FAULT PHASE SELECTION IN WEAK-INFEED SIDE 2219

Fig. 7. Fault-type identification.

Fig. 9. Simulation model. (a) IEEE 39-bus system and the (b) transmission line
between Buses 16 and 21.

the simulation is carried out in the IEEE 39-bus system [15]


(shown in Fig. 9) by using the PSCAD/EMTDC package.
The fault types include a single-phase-to-ground fault and
phase-to-phase-to-ground fault. The relay utilizes full-cycle
Fig. 8. Scheme of fault phase selection.
Fourier correlation analysis to extract the fundamental fre-
quency components. It takes a transient fault period of a cycle
where is the fault region obtained from the distinctive (0.0167 ms) to extract the 60-Hz fundamental frequency com-
phase region (e.g., for A-G or BC-G faults, is A). ponents. The sample rate of the relay is 1440 Hz.
Compared to the sequence current-based fault phase selector, Define
this principle can be used in the weak-infeed side. The se-
quence current-based fault phase selector utilizes the measured
impedance to distinguish between the single-phase-to-ground
fault and phase-to-phase-to-ground fault, which may be af-
fected by overload. The method using the relative phase-angle
where is the fault region number obtained from Fig. 6.
relationship between the superimposed positive- and nega-
In the IEEE 39-bus system, when the transmission line con-
tive-sequence voltages can solve this problem.
necting Bus 21 to Bus 22 is out of operation, the relay at Bus 21
3) Scheme of the Fault Phase Selection: Finally, combining
is under the weak-infeed condition. The fault point k1 is at the
the two steps above, the scheme for the ground fault phase selec-
beginning of the line between Bus 16 and Bus 21, k2 is at the
tion is obtained, as shown in Fig. 8. First, the scheme uses the
middle of the line, and k3 is at the end of the line. Faults occur
relative phase-angle relationship between negative- and zero-
at 0.05 s.
sequence voltages to indicate the probable fault phase. Then,
Under the weak-infeed condition, the voltage waveforms and
the scheme uses the relative phase-angle relationship between
sequence current magnitudes measured by the relay at Bus 21
the superimposed positive- and negative-sequence voltages to
are shown in Fig. 10 when an A-G fault with 50 occurs
identify the fault type.
at k3. The negative- and zero-sequence voltages are nearly equal
in phase. Meanwhile, the phase-angle difference between the su-
IV. SIMULATION VERIFICATION perimposed positive- and negative-sequence voltages is nearly
In order to verify and evaluate the proposed method of fault 0 . According to the proposed scheme, the result of the fault
phase selection, a series of faults under different conditions phase selection is phase A. Besides, the sequence current-based
along the transmission line is simulated in this chapter, and fault phase selector cannot be used in such a situation because
2220 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 5, OCTOBER 2014

Fig. 11. BC-G fault at k3 50 . (a) Waveforms of negative- and


Fig. 10. A-G fault at k3 . (a) Waveforms of negative- and zero- zero-sequence voltages. (b) Waveforms of superimposed positive- and nega-
sequence voltages. (b) Waveforms of the superimposed positive- and negative- tive-sequence voltages. (c) Magnitudes of sequence currents.
sequence voltages. (c) Magnitudes of sequence currents.

The original transmission line connecting Buses 16 to 21 is


the negative-sequence current is at a very low level (less than 60 km in the IEEE 39-bus system. If the transmission line is very
300 A). long, the errors of phase-angle differences caused by impedance
Similarly, the voltage waveforms and current magnitudes are phase-angle inequality will be affected by the fault distance ob-
obtained and shown in Fig. 11 when a BC-G fault with viously. In the following simulation, the length of the transmis-
50 occurs at k3. The leading phase angle of the negative- sion line between Buses 16 and 21 is extended to 300 km. A-G
sequence voltage with respect to the zero-sequence voltage is faults with 20- fault resistance with different fault distances
equal to . The superimposed positive- and negative-se- are simulated and the phase-angle differences and
quence voltages are nearly opposite in phase. According to the are shown in Fig. 12. Similarly, the phase-angle differences
proposed scheme, the result of the fault phase selection is phase and when BC-G faults occur with 20- fault resistance
BC. Because of the low level of negative-sequence current, the with different fault distances are simulated, as shown in Fig. 13.
current-based fault phase selector cannot be used in such a sit- It can be concluded from Figs. 12 and 13 that the proposed cri-
uation as well. teria have enough margins to tolerate the errors and the relay
The other ground faults with different fault resistance along will select the fault phase accurately.
the transmission line are also simulated. The results are shown For faults with very high fault resistance at the end of a long
in Table I. It can be seen that the proposed scheme can identify transmission line near the strong source end, the sequence volt-
the fault phase reliably. The worst situation in Table I is a C-G ages in the weak-infeed side may have low magnitudes and the
fault with 300- fault resistance at k3: the negative-sequence fault selection may fail. In such cases, protection of the trans-
voltage is low but still larger than 17.5 kV (5% ) and the fault mission line has to rely on the relay in the source side for fault
phase detected by the relay is phase C. detection and send signals to the weak-infeed side.
HUANG et al.: NOVEL METHOD OF GROUND FAULT PHASE SELECTION IN WEAK-INFEED SIDE 2221

TABLE I
GROUND FAULTS WITH DIFFERENT FAULT RESISTANCES ALONG THE TRANSMISSION LINE

Fig. 13. BC-G faults with against different fault location.


(a) Phase-angle difference between negative- and zero-sequence voltages.
Fig. 12. A-G faults with 20 against a different fault location. (b) Phase-angle difference between superimposed positive- and negative-se-
(a) Phase-angle difference between negative- and zero-sequence voltages. quence voltages.
(b) Phase-angle difference between superimposed positive- and negative-se-
quence voltages.

In order to study the influence of load conditions on this


TABLE II method, faults at k2 under different load conditions are sim-
GROUND FAULTS UNDER DIFFERENT LOAD CONDITIONS ulated and the results are shown in Table II. The transient re-
sistance is equal to 20 . In Table II, the first column lists the
prefault power flows on the transmission line between Buses
16 and 21 while the load on Bus 21 is different. It can be con-
cluded from Table II that the proposed scheme can identify the
fault phase under different load conditions.

V. CONCLUSION
This paper proposes a new method of ground fault phase
selection for weak-infeed conditions. The proposed method
reliably defines a distinctive phase region according to the
phase-angle difference between negative- and zero-sequence
voltages. The relative phase-angle relationship between su-
perimposed positive- and negative-sequence voltages is used
2222 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 5, OCTOBER 2014

to differentiate between single-phase-to-ground faults and [11] IEEE Guide for Protective Relay Applications to Transmission Lines,
phase-to-phase-to-ground faults. IEEE Standard C37.113TM, 1999.
[12] M. Wang and Y. Chen, “Weak infeed study and protection solution,”
The method has high immunity against fault resistance as presented at the 8th Annu. Western Protect. Relay Conf., Spokane, WA,
well as impedance phase-angle inequality and overload. Simula- USA, Oct. 2011.
tions have been carried out in the IEEE 39-bus system to test the [13] A. Bartylak, “Evaluation of weak infeed tripping technique on the
ESKOM transmission network,” in Proc. CIGRE Canada, AB, Sep.
method with respect to various single-phase-to-ground faults 2005.
and phase-to-phase-to-ground faults with different fault resis- [14] J. D. Glover, M. S. Sarma, and T. J. Overbye, Power System Analysis
tances, fault locations, and load conditions. The results have & Design, 5th ed. Stamford, CT, USA: Cengage Learning, 2011.
[15] M. A. Pai, Energy Function Analysis for Power System Stability.
proven the reliability of the proposed method. Norwell, MA, USA: Kluwer, 1989.
However, if the potential transformer (PT) is broken, the relay
must quit the operation of fault phase selection based on this Shaofeng Huang was born in Fujian Province,
China, in 1958.
method and use the original methods. He is a Professor in the Electrical Engineering
Department, North China Electric Power University,
REFERENCES Beijing, China. His research interest is in the area of
power system protection.
[1] J. L. Blackburn and T. J. Domin, Protective Relaying: Principles and
Applications, 3rd ed. Boca Raton, FL, USA: CRC, 2006.
[2] W. Yan, Z. Dan, and Y. J. Jiao, “Fault location and phase selection
for UHV six-phase transmission lines,” presented at the Power Energy
Eng. Conf. (APPEEC), Asia-Pacific, Wuhan, China, 2011.
[3] B. Kasztenny, B. Campbell, and J. Mazereuw, “Phase selection for
single-pole tripping under weak infeed conditions and cross-country
faults,” presented at the 27th Annu. Western Protect. Relay Conf.,
Spokane, WA, USA, 2000. Lan Luo was born in Fujian Province, China, in
[4] X. N. Lin, M. H. Zhao, and K. Alymann, “Novel design of a fast phase 1989. He received the M.S. degree in power system
selector using correlation analysis,” IEEE Trans. Power Del., vol. 20, and automation from North China Electric Power
no. 2, pt. 2, pp. 1283–1290, Apr. 2005. University, Beijing, China.
[5] Z. Q. Bo, R. K. Aggarwal, A. T. Johns, H. Y. Li, and Y. H. Song, “A Currently, he is with North China Electric Power
new approach to phase selection using fault generated high frequency University. His research interest is in the area of
noise and neural networks,” IEEE Trans. Power Del., vol. 12, no. 3, power system protection.
pp. 106–115, Jul. 1997.
[6] M. R. Noori and S. M. Shahrtash, “Combined fault detector and faulted
phase selector for transmission lines based on adaptive cumulative sum
method,” IEEE Trans. Power Del., vol. 28, no. 3, pp. 1779–1787, Jul.
2013.
[7] X. Z. Dong, W. Kong, and T. Cui, “Fault classification and
faulted-phase selection based on the initial current traveling wave,”
IEEE Trans. Power Del., vol. 24, no. 2, pp. 552–559, Apr. 2009. Kai Cao was born in Shandong Province, China, in
[8] Z. Y. Xu, Q. X. Yang, and W. S. Liu, “A sequence fault phase selector 1988. He received the M.S. degree in power system
for transmission line protective relay,” in Proc. Chinese Soc. Elect. and automation from North China Electric Power
Eng., 1997, vol. 17, pp. 214–216. University, Beijing, China.
[9] W. Li, T. S. Bi, and Q. X. Yang, “Study on sequence component based Currently, he is with North China Electric Power
fault phase selector during power swings,” in Proc. 5th Int. Critical University. His research interest is in the area of
Infrastruct. Conf., 2010, pp. 1–5. power system protection.
[10] Z. Y. Xu, Q. X. Yang, and L. Ran, “Fault phase selection scheme of
EHV/UHV transmission line protection for high-resistance faults,” IET
Gen., Transm. Distrib., vol. 6, pp. 1180–1187, Apr. 2012.

You might also like