Air Handling Units

Direct Expansion
BY Series
(Matching with CY series Condensing units)
BY07 thru BY25
6 TR thru 30 TR
20 kW thru 105 kW
Company Business
Zamil Air Conditioners was founded in 1974 as one of the first air conditioning companies to be established in Saudi Arabia
and today is a leading international manufacturer of air conditioning systems and is Number One in the Middle East.

Zamil Air conditioners manufactures both consumer and central air conditioners and has sales operations in over 55
countries in the Middle East, Europe, Africa and Asia.

The company’s operations are structured into four Strategic Business Units (SBUs) supporting five in-house product and
service brands as well as a number of international brands under the OEM sales.

The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima.

The four SBUs are:


1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers.
2. Unitary & Applied Business Unit supporting Zamil, Cooline, GE and OEM brands for commercial and industrial customers.
3. Zamil CoolCare Business Unit providing industrial, electro mechanical contracting services, HVAC maintenance,
retrofit & operation services and parts.
4. Geoclima srl is an independent business supporting other SBUs for their requirements of chillers & double skin AHU’s.

The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare direct their business operations
from the corporate headquarters in Dammam, Saudi Arabia.

Geoclima has its engineering & production operations located at Monfalcone, Italy and has a design center in Austria.

All the four SBUs, while operating independently, supplement each other’s activities in a way that makes synergy work at
its best and achieve the corporate goals of maximizing customer satisfaction.

Factories and Productions


Zamil Air Conditioners has two manufacturing plants in Dammam, Saudi Arabia and has one specialty production facility
in Italy operated by Geoclima.

The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central Air
Conditioning systems per year.

Quality & Product Certificates


The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2008 certification.

Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabia’s Standard Organization)
Certificate for Room Air Conditioners. ZAC’s products are also certified with:
1. CE (Council of European Community)
2. UL (Underwriters Laboratory)
3. Eurovent (Certified Performance)
4. ETL (Test Facilities)
5. SASO (Saudi Arabian Standards Organization)
6. ISO 9001:2008 (International Organization for Standardization)
7. ASME (American Quality of Mechanical Engineers)

Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammed
bin Fahd Al Saud Award for Factory Safety.

Our Products
In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Condition-
ers manufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from the
Concealed Units up to 5 TR, the Ducted Splits up to 30 TR, the Packaged Units up to 95 TR, the Single and Double Skin
Air Handling Units up to 138,316 CFM and the Water Chillers up to 500 TR cooling capacity.
INDEX
Contents Page

Outstanding features ................................................................................................................................ 2

Model decoding ........................................................................................................................................ 3

Blower drive options ................................................................................................................................. 4

Standard specifications ......................................................................................................................... 4-5

Options and accessories ....................................................................................................................... 5-6

Physical data ............................................................................................................................................ 7

Cooling capacities ............................................................................................................................... 8-14

Fan performance data ....................................................................................................................... 15-16

Electrical data .................................................................................................................................... 17-19

Dimensions, indoor units ................................................................................................................... 20-23

Dimensions, heater box .......................................................................................................................... 24

Dimensions, outdoor units ................................................................................................................. 25-27

Typical schematic wiring diagram ...................................................................................................... 28-31

Controls and sequence of operation ....................................................................................................... 32

Installation instructions ........................................................................................................................... 33

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

1
OUTSTANDING FEATURES
* HIGH EER (ENERGY EFFICIENCY RATIO)
* INDEPENDENT HORIZONTAL OR VERTICAL AIR DISCHARGE UNITS
* LOW CEILING HEIGHT REQUIREMENTS
* MICROPROCESSOR BASED CONTROLS
* ONE SIDE TOTAL SERVICE ACCESSIBILITY
* SINGLE POINT POWER ENTRY
* UV FLOW™ LIGHT EMITTERS FOR ENHANCED IAQ (INDOOR AIR QUALITY)
* NUMBERED CODED WIRES
* INSULATED DRAIN PAN
* FACTORY INSTALLED OPTIONS UPON REQUEST
* SMALL FOOTPRINT
* LIGHT WEIGHT
* PRE-PAINTED CABINETS WITH FIBERGLASS INSULATION
* LARGE CHOICE OF HEATERS; FACTORY OR FIELD INSTALLATION
* STANDARD OR OPTIONAL MOTORS; FACTORY OR FIELD INSTALLATION
* ALUMINUM OR SYNTHETIC FILTERS
* UL LISTED MAJOR COMPONENTS

2
MODEL DECODING
MODELS: BY07 - BY25
1& 2 3&4 5 6 7 8 9 10 11 12 13 14 15
BASIC FACE AREA ARRANGEMENT ELECTRICAL REFRIGERATION MODE BLOWER DRIVE HEATER EVAPORATOR FILTER OTHER OPTIONS THERMOSTAT
(SQ. FT.) SUPPLY CIRCUIT MOTOR OPTIONS COIL OPTION
OPTIONS
(V-Ph-Hz) (kW/STAGE)

BY 07 H : HORIZONTAL H : 208/230-3-60 FOR BY07 - BY14 C : COOL ONLY FOR BY07 FOR BY07 -BY14 A : ALUMINUM FOR BY07 N : NO OPTION S : UNIT WITH
J : ALT. I
AIR FIN N : NO FILTER THERMOSTAT
S : SINGLE D : 2 HP ODP N : NO HEATER
V : VERTICAL M : 380-3-60 K : ALT. II E : 1/2" ALUMINUM V : VOLT FREE
HANDLING E : 3 HP ODP A : 5/1 F : 1/2" SYNTHETIC CONTACTS* D : UNIT WITHOUT
UNIT (4 WIRE) D : DUAL B : 6/1 B : COATED
A : 1" ALUMINUM THERMOSTAT
C : 7.5 /1 ALUMINUM
10 FOR BY10 C : 1" SYNTHETIC
F : 460-3-60 D : 10 /2 FIN
D : 2 HP ODP
E : 12/2 FOR BY10, 14 & 18
E : 3 HP ODP C : COPPER FIN
F : 15 /2 N : NO FILTER
G : 20 /2
FOR BY14/18 A : 1" ALUMINUM
14 H : 25/2
B : 2" ALUMINUM
G : 5 HP ODP J : 30/2
C : 1" SYNTHETIC
J : 7.5 HP ODP FOR BY18 -BY25
FOR BY18 - BY25 D : 2"SYNTHETIC
18 N : NO HEATER
D : DUAL
E : 12/2
FOR BY25 F : 15 /2 FOR BY25
25 G : 20 /2
J : 7.5 HP ODP N : NO FILTER
H : 25/2
L : 10 HP ODP J : 30/2 B : 2" ALUMINUM
K : 35/2 D : 2"SYNTHETIC
L : 40/2

3
NOTE: * Blower motor RUN/TRIP indication.
BLOWER DRIVE OPTIONS
MOTOR BLOWER APPROX. SPEED
MODEL PULLEY PULLEY CHANGE PER
OPTION SPEED RANGE (RPM) PULLEY
NUMBER PITCH DIA. PITCH DIA.
HP RPM TURN (RPM)
(INCH) MINIMUM MAXIMUM (INCH)
ALT. I 2 1750 2.7 - 3.7 893 1156 5.6 62
BY07
ALT. II 3 1750 2.7 - 3.7 964 1321 4.9 71
BY10 ALT. I 2 1750 3.1 - 4.1 733 970 7.4 40
ALT. II 3 1750 3.1 - 4.1 875 1157 6.2 47
ALT. I 5 1750 3.7 - 4.7 809 1028 8.0 37
BY14
ALT. II 7.5 1750 4.3 - 5.5 940 1203 8.0 44
ALT. I 5 1750 3.7 - 4.7 809 1028 8.0 37
BY18
ALT. II 7.5 1750 4.3 - 5.5 875 1120 8.6 40
ALT. I 7.5 1750 4.3 - 5.5 685 880 11 38
BY25
ALT. II 10 1750 4.3 - 5.5 800 1023 9.4 44

STANDARD SPECIFICATIONS
A. General
These Zamil Air Handling Units are factory fabricated and assembled, consisting of forward-curved fan section with
blower motor, DX coil, electric heaters (optional), filters & electrical control box and are suitable for indoor applications.
The unit is ready to operate when piped to a suitable condensing unit, connected to power/controls and air ducts or
plenums.
They should be ordered separately as horizontal air discharge or vertical air discharge units as per application require-
ments.

B. Unit Enclosure
Casing Panels are of heavy gauge (G-90) galvanized steel. Removable access panels are provided for inspection and
access to all internal parts. These panels are insulated with 1/2" thick fiberglass insulation to prevent condensation from
forming on the unit casing. Insulation meets the requirements of NFPA 90A and is protected against deterioration and
errosion from air currents. Steel sheet is zinc-coated, galvanized by the hot dip process of lock forming quality conform-
ing to ASTM A 653 commercial weight G-90, followed by baked-on electrostatic polyester dry powder coat.

C. Coils
Coils are of the enhanced louvered fin-and-tube type, constructed of copper tubes, mechanically bonded to aluminum
fins. As an option, corrugated copper or enhanced coated aluminum fins may be provided. End plates and tube support
sheets are 18 gauge galvanized steel, formed to provide structural strength. Each coil is pressure tested in the factory at
not less than 300 psi (2070 kPa) air pressure. Coils conform to ARI 410.

D. Drain Pans
Drain pans provided under cooling coil section are made of G-90 galvanized steel with mastic coated liner for additional
corrosion protection. Drain outlets of 3/4" NPT is provided for field connection.

E. Evaporator Fan
Evaporator fan is of a centrifugal forward-curved blade design and sized to meet system airflow/pressure. Fan motor is
mounted on an adjustable base and secured by a locking device. Fan drive is through adjustable motor pitch pulley and
belt-driven. Fan shafts are designed to operate at less than 2/3rds of the first critical speed when the unit comes up to
rated revolutions per minute (RPM). Units have sealed, permanently lubricated ball or sleeve fan bearing and are stati-
cally / dynamically balanced in the fan housing during final assembly. Fan motors are of the open drip-proof type (totally
enclosed types are optional) and conform to NEMA MG-1 & MG-2. Motor starters are magnetic contactor, across-the-
line type.

4
F. Microprocessor Control
These air handling units are provided with a microprocessor control board incorporating the following features:
- BALANCE LOADING OF COMPRESSORS: The unit’s electronic control automatically operates lead/lag sequence
of compressors. This is to load the compressors evenly over long periods of operation. If required however, compres-
sor-1 can also be set to always lead. In this case, compressor-1 always starts first and stops last. (Selectable through
dip switch setting on control board).
- PUMP DOWN FUNCTION: In units equipped with pump down system, the controller provides the time delay between
solenoid’s opening and compressor starting to equalize the pressure in the system necessary for compressor to start-
up. (Selectable through dip switch setting on control board).
- COMPRESSOR ANTI-RECYCLING PROTECTION: The controller has a built-in 3 minutes minimum off timer for
compressor. This is for compressor protection in case of accidental manual re-set or immediate re-cycling of thermo-
stat due to load demand.
- COMPRESSOR LOCK-OUT FUNCTION: If any of the unit’s safety control trips due to abnormal conditions, the
electronic controls locks out the compressor after a pre-determined timing preventing a re-start unless attended by a
qualified service technician. The unit can be re-started through thermostat re-set after ensuring safe system condi-
tions.
- FAULT DIAGNOSTICS: In case of system fault, LED’s on the board emits a flashing signal indicating where the fault
is. This is to guide the service technician in identifying the fault.
- DIGITAL I/O’s: The unit’s control board is compatible to operate with a DDC controller or any standard 24V a.c.
thermostat commercially available.
- SEQUENTIAL CONTROL: With input signals from the thermostat, the motors in the equipment is started in sequen-
tial order: supply fan – condenser fan – compressor; at a pre-determined timings.

G. Control Panel
A complete factory-wired control panel is provided to ensure safe and proper operation.

OPTIONS AND ACCESSORIES


A. Electric Heaters
Electric heaters are of the resistance open coil type and conform to the requirements of UL 573 or equivalent. Electrical
characteristics, kW capacities and number of stages are as indicated. Thermal cut-outs, fusible links and airflow switches
are provided to shut-off power to heaters in case of airflow failure.

B. Filters
Filters are easily accessible through the filter access panel. Filters may be synthetic or permanent washable aluminum
type (refer to model decoding for details). As an accessory, bag filter section can be provided for belt driven units.

C. Discharge Air Plenum & Return Air Grille


As an accessory, discharge air plenum with return air grilles can be provided on vertical units.

D. UV Flow™ Light Emitters


The damp & dark environment inside the AHU is ideal for the growth and development of hazardous bacteria & fungi. The
UV flow concept uses emitters of Ultra Violet light to simulate the effect of healthy sun radiation. This will inhibit the growth
of these microorganisms reducing in this manner mold related allergies and diseases. Breath safely with UV flow™.
To order the UV flow™ use the kit numbers in the table below.

MODEL NUMBER BY07 BY10 BY14 BY18 BY25

KIT PART NUMBER 700-391-18 700-391-19 700-391-20 700-391-21 700-391-22

5
E. Electronic Thermostat
General information: Electronic thermostat shall control one or two stage heating and cooling applications. The thermo-
stat normally displays room temperature and mode of operation.
The temperature can be set by up/down buttons for both cooling and heating cycles. The thermostat also allows you to
select continuous fan operation, or have the fan on intermittent operation with the equipment.
The thermostat is best located about 1500 mm (5 Ft.) above floor level, on a partition wall (not an outside wall), and
should not be exposed to direct light from lamps, sun etc. It should be in return air stream, away from supply air registers/
diffusers.
• Single/dual stage - Cooling & heating.
• Low voltage control - 24 VAC (nominal).
• Room temperature display - in C or F.
0 0

• Mode of operation - FAN/COOL/HEAT/AUTO.


• Fan mode - ON: Continuous fan operation; AUTO: Fan operates ON/OFF with compressor.
• Heating & cooling setpoint is permissible.
• Temperature set button - Up for increasing & down for decreasing temperature.
• Built-in compressor fault & clogged filter indication led lights.
• Remote sensing function as an option. Duct sensor is provided with the thermostat.
TYPICAL THERMOSTAT
Heating Cooling Selector Switch Positions
Part No.
Stages Stages Mode Switch Fan Switch

800-652-61 1&2 1&2 OFF-HEAT/COOL ON - AUTO

6
PHYSICAL DATA
MODEL NUMBER BY07 BY10 BY14 BY18 BY25

EVAPORATOR BLOWER Type Centrifugal

Nominal airflow CFM (L/S) 2800 (1321) 4600 (2171) 5500 (2596) 7000 (3303) 9000 (4247)

Motor HP (Std/Alt) 2/3 3/2 5/7.5 5/7.5 7.5/10

Drive type Belt Belt Belt Belt Belt

Blower size 12x12 15x15 15x15 15x12 18x18

Quantity 1 1 1 2 2

EVAPORATOR COIL Type Corrugated Fin & Tube

Tube dia. - Rows - FPI 3/8 - 3 - 14 3/8 - 4 - 14 3/8 - 4 - 14 3/8 - 4 - 14 3/8 - 4 - 14

Face area, Sq. ft. (Sq. m.) 7 (0.65) 10 (0.93) 14 (1.3) 17.4 (1.62) 25 (2.32)

REFRIGERANT LINES Suction line size O.D. (inch) 1-1/8 1-3/8 1-3/8 - -
SINGLE COMPRESSOR
Liquid line size O.D. (inch) 5/8 5/8 5/8 - -

REFRIGERANT LINES Suction line size O.D. (inch) 7/8 7/8 1-1/8 1-3/8 1-3/8
DUAL COMPRESSOR
Liquid line size O.D. (inch) 1/2 1/2 5/8 5/8 7/8

RETURN AIR FILTER Size (inch) 20 x 20 x 1/2 18 x 24 x 1 20 x 24 x 1 20 x 24 x 1 20 x 24 x 2

Quantity 3 3 3 3 3

SHIPPING WEIGHT kg. (approx.) 165 225 300 340 420

7
COOLING CAPACITIES
(Single compressor units)
BY07 INDOOR UNIT WITH CY075 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 1900/0.102 2400/0.126 2900/0.148
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 68.38 74.46 80.91 71.74 78.24 85.14 74.17 80.84 88.13
85 SC 61.94 51.99 41.85 70.48 58.38 46.06 72.69 64.18 49.84
kW 6.55 6.74 6.88 6.83 7 7.14 7.33 7.49 7.64
TC 65.49 71.41 77.72 68.6 74.91 81.72 70.89 77.45 84.5
95 SC 60.59 50.71 40.64 67.23 57.03 44.83 69.47 62.89 48.58
kW 7.21 7.41 7.57 7.49 7.66 7.83 7.98 8.15 8.32
TC 62.34 68.12 74.28 65.25 71.38 78 67.22 73.67 80.63
105 SC 59.15 49.34 39.35 63.95 55.63 43.5 65.88 61.42 47.24
kW 7.94 8.14 8.32 8.21 8.4 8.59 8.7 8.89 9.09
TC 59.03 64.66 70.68 61.7 67.73 74.17 63.56 69.9 76.63
115 SC 57.63 47.91 38.01 60.47 54.21 42.14 62.29 60.01 45.87
kW 8.66 8.88 9.09 8.93 9.13 9.35 9.42 9.62 9.87
TC 55.63 61.12 67.07 58.14 63.99 70.24 59.9 65.88 72.63
125 SC 54.52 46.47 36.71 56.98 52.76 40.77 58.7 58.44 44.54
kW 9.38 9.61 9.85 9.63 9.86 10.14 10.12 10.36 10.66

BY07 INDOOR UNIT WITH CY090 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 2250/0.118 2800/0.144 3350/0.168
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 74.41 81.45 89.03 77.72 85.21 93.05 80.14 87.86 96.17
85 SC 69.27 57.95 46.47 76.16 64.68 50.79 78.53 70.74 54.78
kW 7.79 8.02 8.23 8.33 8.53 8.74 8.82 9.02 9.24
TC 70.98 77.94 85.25 74.06 81.33 89.07 76.34 83.8 91.98
95 SC 67.71 56.54 45.07 72.58 63.13 49.38 74.82 69.16 53.35
kW 8.67 8.89 9.1 9.18 9.39 9.61 9.67 9.87 10.11
TC 67.35 74.13 81.27 70.27 77.32 84.97 72.25 79.73 87.65
105 SC 66.08 54.99 43.62 68.87 61.57 47.96 70.81 67.67 51.88
kW 9.58 9.79 10 10.08 10.28 10.52 10.55 10.76 11.01
TC 63.63 70.23 77.3 66.25 73.2 80.62 68.17 75.37 83.17
115 SC 62.35 53.42 42.2 64.92 59.98 46.45 66.8 66.01 50.38
kW 10.47 10.68 10.91 10.95 11.16 11.42 11.42 11.64 11.92
TC 59.8 66.23 73.03 62.22 68.95 76.16 63.93 71.02 78.55
125 SC 58.61 51.85 40.67 60.98 58.36 44.91 62.66 64.43 48.84
kW 11.34 11.55 11.81 11.82 12.03 12.33 12.29 12.51 12.84

BY10 INDOOR UNIT WITH CY100 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 2800/0.05 3400/0.066 4000/0.076
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 93.7 101.72 110.43 97.19 105.68 114.75 99.69 108.38 118.1
85 SC 84.45 69.89 55.2 91.35 77.72 60.21 93.71 85.01 65.01
kW 8.88 9.09 9.34 9.11 9.32 9.62 9.49 9.72 10.05
TC 90.53 98.45 106.93 93.78 102.15 111.09 96.21 104.74 114.14
95 SC 83.14 68.66 54.01 88.15 76.41 59.02 90.44 83.72 63.74
kW 9.72 9.92 10.16 9.94 10.14 10.43 10.3 10.53 10.86
TC 86.75 94.68 103.07 89.93 98.17 106.98 92.2 100.75 110
105 SC 81.54 67.26 52.71 84.53 74.97 57.68 86.67 82.36 62.44
kW 10.64 10.85 11.14 10.85 11.08 11.42 11.22 11.46 11.85
TC 82.96 90.68 99.09 85.78 94.04 102.88 88.02 96.42 105.69
115 SC 77.99 65.75 51.38 80.63 73.49 56.36 82.74 80.8 61.08
kW 11.57 11.81 12.14 11.78 12.04 12.44 12.15 12.43 12.89
TC 78.57 86.31 94.62 81.33 89.47 98.19 83.31 91.73 100.86
125 SC 73.86 64.17 49.9 76.45 71.88 54.86 78.31 79.2 59.56
kW 12.61 12.87 13.27 12.81 13.11 13.59 13.18 13.51 14.06
TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

8
COOLING CAPACITIES
(Single compressor units)
BY10 INDOOR UNIT WITH CY120 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 3200/0.059 4000/0.076 4800/0.092
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 112.8 122.36 132.41 117.12 127.11 137.76 120.05 130.47 141.72
85 SC 106.89 88.89 70.55 114.78 99.61 77.42 117.65 109.78 83.96
kW 11.14 11.44 11.76 11.62 11.92 12.29 12.25 12.57 12.98
TC 104.71 113.62 123.17 108.58 118.09 128.1 111.48 121.11 131.79
95 SC 101.14 83.56 65.79 106.41 94.18 72.55 109.25 104.12 79
kW 11.88 12.18 12.52 12.34 12.65 13.06 12.98 13.3 13.77
TC 96.63 105.02 113.93 100.04 108.9 118.45 102.69 111.75 121.66
105 SC 91.8 76.15 59.36 95.04 86.1 65.79 97.56 95.63 71.82
kW 12.58 12.87 13.24 13.03 13.35 13.8 13.66 14 14.5
TC 91.61 99.75 108.41 94.81 103.35 112.59 97.05 105.92 115.66
115 SC 87.03 74.19 57.52 90.07 84.12 63.91 92.19 93.56 69.98
kW 13.25 13.56 13.96 13.7 14.03 14.51 14.33 14.68 15.23
TC 85.33 93.09 101.38 88.37 96.42 105.17 90.35 98.84 108
125 SC 81.07 71.74 55.21 83.95 81.68 61.56 85.84 91.19 67.62
kW 14.04 14.35 14.8 14.48 14.83 15.36 15.11 15.48 16.09

BY10 INDOOR UNIT WITH CY150 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 4000/0.076 4600/0.088 5000/0.095
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 130.72 141.5 152.59 133.69 144.78 156.04 135.29 146.53 157.97
85 SC 121.42 100.28 78.76 129.68 107.7 83.43 131.24 112.45 86.44
kW 13.6 13.95 14.33 14.07 14.42 14.82 14.43 14.78 15.2
TC 125.32 135.95 146.9 128.08 139 150.29 129.63 140.68 152.16
95 SC 119.09 98.14 76.77 124.24 105.5 81.48 125.74 110.26 84.5
kW 14.91 15.27 15.68 15.37 15.73 16.17 15.73 16.09 16.55
TC 119.22 129.71 140.69 121.86 132.62 143.95 123.31 134.18 145.69
105 SC 115.64 95.74 74.65 118.21 103.13 79.37 119.61 107.86 82.36
kW 16.35 16.73 17.17 16.8 17.18 17.67 17.15 17.54 18.05
TC 113.64 123.99 135 116.05 126.83 138.2 117.43 128.32 139.87
115 SC 110.23 93.55 72.7 112.57 101 77.45 113.91 105.74 80.45
kW 17.63 18.03 18.52 18.08 18.48 19.02 18.43 18.84 19.41
TC 107.89 118.27 129.48 110.24 121.05 132.45 111.55 122.47 134.27
125 SC 104.65 91.39 70.85 106.93 98.89 75.55 108.2 103.63 78.67
kW 18.9 19.32 19.87 19.34 19.77 20.38 19.69 20.13 20.77

BY14 INDOOR UNIT WITH CY150 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 4000/0.050 4800/0.062 5800/0.076
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 141.18 152.95 164.83 145.99 157.94 170.28 149.86 162.43 175.25
85 SC 132.88 110.4 87.29 143.07 121.29 94.24 146.87 134.31 102.5
kW 13.72 14.07 14.51 14.23 14.6 15.1 15.12 15.52 16.09
TC 135.25 146.88 158.79 139.71 151.7 164.07 143.55 155.9 168.75
95 SC 130.17 107.9 85.06 136.92 118.83 92.04 140.68 131.77 100.23
kW 15.04 15.41 15.89 15.54 15.93 16.48 16.42 16.85 17.48
TC 128.63 140.12 152.07 132.81 144.62 157.24 136.47 148.6 161.75
105 SC 127.21 105.14 82.6 130.15 116.02 89.65 133.74 128.95 97.85
kW 16.49 16.89 17.41 16.99 17.41 18.03 17.86 18.32 19.03
TC 122.53 133.87 146.03 126.33 138.38 151.03 129.9 142.32 155.5
115 SC 120.08 102.58 80.42 123.8 113.62 87.47 127.3 126.67 95.74
kW 17.79 18.21 18.79 18.28 18.73 19.42 19.15 19.65 20.44
TC 116.43 127.8 140 120.05 131.93 145.03 123.33 135.78 149.5
125 SC 114.1 100.19 78.24 117.65 111.07 85.42 120.86 124.17 93.79
kW 19.07 19.52 20.18 19.57 20.05 20.82 20.43 20.98 21.85

TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

9
COOLING CAPACITIES
(Dual compressor units)
BY07 INDOOR UNIT WITH CY075 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 1900/0.102 2400/0.126 2900/0.148
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 67.64 74.3 81.32 71.22 78.24 85.76 73.67 80.97 88.88
85 SC 63.67 53.69 43.44 69.79 60.37 47.87 72.2 66.41 51.82
kW 6.6 6.96 7.3 6.96 7.31 7.65 7.51 7.87 8.21
TC 64 70.51 77.39 67.24 74.18 81.52 69.63 76.82 84.5
95 SC 61.92 52.03 41.9 65.9 58.68 46.28 68.23 64.79 50.26
kW 6.89 7.3 7.69 7.27 7.67 8.06 7.82 8.23 8.63
TC 60.68 67.05 73.79 63.69 70.44 77.69 65.83 72.92 80.38
105 SC 60.38 50.56 40.5 62.41 57.14 44.88 64.52 63.25 48.77
kW 7.15 7.6 8.05 7.53 7.99 8.43 8.11 8.56 9.01
TC 56.79 63.01 69.61 59.5 66.17 73.14 61.54 68.39 75.75
115 SC 55.66 48.85 38.91 58.31 55.43 43.2 60.31 61.46 47.15
kW 7.47 7.98 8.48 7.87 8.38 8.88 8.45 8.96 9.47
TC 53.23 59.31 65.76 55.74 62.22 69.1 57.49 64.24 71.38
125 SC 52.17 47.3 37.47 54.62 53.84 41.76 56.34 59.82 45.6
kW 7.78 8.34 8.9 8.19 8.75 9.31 8.78 9.34 9.92

BY07 INDOOR UNIT WITH CY090 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 2250/0.118 2800/0.144 3350/0.168
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 77.25 84.77 93.01 80.64 88.73 97.52 83.2 91.64 100.93
85 SC 74.76 62.82 50.77 79.03 69.94 55.47 81.54 76.43 59.75
kW 8.29 8.75 9.22 8.91 9.36 9.85 9.46 9.93 10.43
TC 73.43 80.86 88.93 76.62 84.49 93.17 78.97 87.28 96.31
95 SC 72.88 61.12 49.17 75.09 68.14 53.84 77.39 74.67 58.06
kW 8.61 9.11 9.63 9.24 9.74 10.28 9.8 10.31 10.87
TC 69.51 76.77 84.57 72.47 80.12 88.59 74.59 82.64 91.55
105 SC 68.12 59.35 47.45 71.02 66.32 52.12 73.1 72.76 56.34
kW 8.96 9.5 10.08 9.59 10.14 10.73 10.16 10.72 11.33
TC 65.39 72.47 80.11 68.2 75.62 83.76 70.21 77.99 86.49
115 SC 64.08 57.5 45.73 66.84 64.49 50.32 68.81 70.94 54.5
kW 9.33 9.92 10.54 9.97 10.56 11.21 10.54 11.15 11.82
TC 60.69 67.5 74.87 63.08 70.28 78.21 64.81 72.47 80.57
125 SC 59.47 55.42 43.75 61.81 62.31 48.31 63.51 68.78 52.39
kW 9.77 10.41 11.1 10.41 11.07 11.78 10.99 11.66 12.39

BY10 INDOOR UNIT WITH CY100 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 2800/0.05 3400/0.066 4000/0.076
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 96.14 105.61 115.62 100.3 110.11 120.61 103.18 113.41 124.31
85 SC 87.31 72.9 58.2 96.28 80.99 63.47 99.05 88.66 68.41
kW 9.3 9.78 10.26 9.63 10.11 10.61 10.08 10.56 11.08
TC 91.26 100.51 110.19 95.11 104.8 114.9 97.78 107.86 118.45
95 SC 85.2 70.92 56.28 91.31 79.05 61.54 93.87 86.69 66.5
kW 9.83 10.37 10.92 10.17 10.71 11.3 10.62 11.18 11.79
TC 86.5 95.41 104.88 89.93 99.35 109.18 92.37 102.14 112.41
105 SC 83.04 68.96 54.46 86.33 77.02 59.64 88.68 84.6 64.55
kW 10.35 10.95 11.59 10.7 11.32 11.99 11.17 11.8 12.49
TC 81.5 90.19 99.21 84.59 93.75 103.17 86.8 96.24 106.21
115 SC 78.24 66.99 52.5 81.21 74.96 57.64 83.33 82.47 62.56
kW 10.89 11.57 12.29 11.26 11.95 12.71 11.73 12.44 13.22
TC 76.37 84.73 93.41 79.11 88 97.16 81.22 90.35 99.83
125 SC 73.32 64.94 50.54 75.95 72.89 55.72 77.97 80.45 60.54
kW 11.46 12.22 13.03 11.84 12.61 13.45 12.31 13.11 13.98
TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC= 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

10
COOLING CAPACITIES
(Dual compressor units)
BY10 INDOOR UNIT WITH CY120 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 3200/0.059 4000/0.076 4800/0.092
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 114.47 125.97 138.9 119.74 132.31 146.38 123.61 136.72 151.86
85 SC 105.56 88.62 71.58 117.34 99.74 78.98 121.14 109.99 85.79
kW 11.43 12 12.59 12.01 12.6 13.21 12.73 13.32 13.95
TC 108.48 119.86 132.55 113.46 125.72 139.66 116.92 130.06 144.83
95 SC 102.83 86.12 69.21 111.19 97.12 76.6 114.58 107.51 83.38
kW 11.98 12.66 13.37 12.59 13.29 14.04 13.33 14.04 14.83
TC 102.34 113.48 125.93 106.84 118.96 132.59 110.01 122.98 137.38
105 SC 100.13 83.53 66.79 104.7 94.51 74.13 107.81 104.87 80.86
kW 12.52 13.3 14.14 13.16 13.96 14.86 13.91 14.74 15.67
TC 96.63 107.51 119.86 100.74 112.72 126.03 103.95 116.32 130.34
115 SC 96.63 81.11 64.61 98.73 92.12 71.87 101.87 102.33 78.47
kW 13.04 13.92 14.88 13.7 14.61 15.64 14.47 15.41 16.48
TC 90.07 100.72 112.69 93.77 105.43 118.28 96.63 108.83 122.28
125 SC 88.27 78.45 62.06 91.89 89.37 69.21 94.69 99.64 75.8
kW 13.67 14.67 15.79 14.35 15.4 16.59 15.12 16.22 17.45

BY10 INDOOR UNIT WITH CY150 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 4000/0.076 4600/0.088 5000/0.095
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 131.07 143.06 155.86 134.29 146.58 160.01 136.17 148.7 162.28
85 SC 121.55 100.91 79.91 130.26 108.33 84.78 132.08 113.24 87.87
kW 14.08 14.41 14.73 14.54 14.86 15.2 14.9 15.22 15.56
TC 124.62 136.3 148.97 127.68 139.79 152.87 129.41 141.76 154.96
95 SC 118.74 98.25 77.51 123.85 105.81 82.37 125.53 110.7 85.42
kW 15.52 15.88 16.26 15.98 16.33 16.74 16.33 16.68 17.1
TC 118.17 129.54 141.72 120.86 132.62 145.34 122.44 134.39 147.41
105 SC 114.62 95.68 74.99 117.24 103.1 79.81 118.77 107.93 82.93
kW 16.95 17.35 17.79 17.4 17.8 18.28 17.75 18.15 18.65
TC 111.37 122.43 134.48 113.85 125.44 137.8 115.25 127.02 139.66
115 SC 108.03 92.97 72.55 110.43 100.5 77.32 111.79 105.28 80.39
kW 18.38 18.81 19.34 18.83 19.27 19.85 19.18 19.63 20.23
TC 105.1 116.01 127.76 107.43 118.66 130.86 108.71 120.3 132.54
125 SC 101.95 90.58 70.28 104.21 97.97 75.05 105.45 102.89 78.08
kW 19.64 20.12 20.74 20.09 20.59 21.26 20.44 20.95 21.65

BY14 INDOOR UNIT WITH CY150 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 4000/0.05 4800/0.062 5800/0.076
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 136.47 149.13 162.76 141.39 154.82 169.24 145.82 159.92 175.25
85 SC 125.59 104.51 83.1 137.14 115.31 90.16 141.45 128.04 98.44
kW 14.32 14.64 15 14.82 15.14 15.54 15.7 16.03 16.48
TC 129.67 142.02 155.34 134.27 147.33 161.59 138.49 152.12 167
95 SC 122.62 101.7 80.47 130.25 112.45 87.58 134.34 125.19 95.7
kW 15.8 16.15 16.59 16.29 16.66 17.15 17.16 17.55 18.1
TC 122.7 134.74 147.76 126.95 139.63 153.52 130.66 144.08 158.75
105 SC 119.02 98.86 77.82 123.15 109.55 84.84 126.74 122.24 93.04
kW 17.26 17.67 18.18 17.75 18.18 18.77 18.63 19.09 19.75
TC 115.56 127.28 140 119.42 131.93 145.24 122.82 136.03 150
115 SC 112.09 96.01 75.15 115.84 106.76 82.07 119.14 119.43 90.17
kW 18.73 19.19 19.8 19.22 19.71 20.43 20.09 20.63 21.43
TC 109.11 120.52 132.93 112.52 124.65 137.79 115.75 128.49 142.25
125 SC 105.83 93.47 72.76 109.15 104.03 79.63 112.27 116.7 87.72
kW 20.02 20.54 21.27 20.52 21.08 21.92 21.4 22.02 22.97
TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

11
COOLING CAPACITIES
(Dual compressor units)
BY14 INDOOR UNIT WITH CY180 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 4400/0.056 5500/0.073 6600/0.088
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 167.37 182.36 198.38 174.95 190.75 207.91 180.31 196.86 214.78
85 SC 148.38 124.49 100.23 168.42 139.28 109.92 178.51 153.29 118.92
kW 15.98 16.38 16.77 16.88 17.26 17.69 18.16 18.53 19.01
TC 160.47 175.3 190.98 167.52 183.36 200.09 172.55 189.13 206.53
95 SC 145.18 121.57 97.46 165.1 136.42 107.15 170.82 150.41 116.08
kW 17.54 17.94 18.35 18.42 18.8 19.27 19.68 20.07 20.59
TC 152.99 167.48 183.02 159.61 175.01 191.55 164.5 180.55 197.72
105 SC 141.81 118.35 94.53 158.01 133.12 104.14 162.85 147.16 113.09
kW 19.27 19.66 20.12 20.12 20.52 21.04 21.37 21.78 22.38
TC 145.32 159.66 174.86 151.46 166.67 183.02 155.87 171.68 188.9
115 SC 138.4 115.22 91.56 149.95 129.91 101.2 154.31 143.77 110.17
kW 20.96 21.37 21.88 21.81 22.22 22.83 23.04 23.49 24.18
TC 137.46 151.46 166.71 143.31 158.09 174.25 147.24 162.81 179.79
125 SC 134.94 111.91 88.66 141.88 126.61 98.19 145.77 140.48 107.15
kW 22.64 23.07 23.65 23.46 23.92 24.63 24.69 25.19 26

BY18 INDOOR UNIT WITH CY180 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 5050/0.052 6300/0.067 7550/0.082
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 176.47 192.66 209.84 183.92 201.29 219.69 189.49 207.19 226.5
85 SC 163.61 136.38 108.63 182.08 153.4 119.75 187.6 169.31 129.96
kW 16.72 17.13 17.59 17.44 17.85 18.39 18.38 18.81 19.42
TC 168.99 185 202 176.24 193.1 211.27 181.27 198.68 217.71
95 SC 160.21 133.27 105.79 174.47 150.21 116.83 179.45 166.1 127.02
kW 18.34 18.75 19.26 19.04 19.47 20.06 19.96 20.43 21.1
TC 161.07 176.68 193.29 167.73 184.36 202.03 172.38 189.51 208.28
105 SC 156.79 129.94 102.63 166.05 146.89 113.62 170.66 162.68 123.87
kW 20.14 20.57 21.14 20.81 21.28 21.97 21.73 22.24 23.03
TC 152.71 168.14 184.59 158.94 175.34 192.8 163.5 180.35 198.84
115 SC 151.18 126.55 99.54 157.35 143.44 110.47 161.87 159.36 120.79
kW 21.92 22.37 23.03 22.58 23.09 23.9 23.49 24.06 24.98
TC 144.35 159.6 175.88 150.16 166.33 183.57 154.29 170.86 189.08
125 SC 142.91 123.25 96.51 148.66 140.1 107.38 152.75 155.86 117.58
kW 23.68 24.17 24.95 24.33 24.9 25.85 25.23 25.88 26.98

BY18 INDOOR UNIT WITH CY220 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 5050/0.054 6300/0.069 7550/0.085
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 201.12 217.84 235.74 210 227.78 246.84 216.47 235.01 254.49
85 SC 176.71 148.27 119.48 199.83 165.44 130.66 212.14 181.79 140.9
kW 20.12 20.64 21.14 20.89 21.39 21.94 21.82 22.32 22.94
TC 193.86 210.39 227.69 202.31 219.59 238.15 208.24 226.17 245.7
95 SC 173.3 145.15 116.4 196.46 162.12 127.49 204.08 178.24 137.87
kW 22.01 22.55 23.08 22.76 23.27 23.88 23.69 24.2 24.88
TC 186.38 202.51 219.63 194.35 211.4 229.46 200.02 217.66 236.59
105 SC 169.81 141.82 113.38 192.94 158.9 124.38 196.02 175.04 134.72
kW 23.89 24.43 25.01 24.61 25.15 25.81 25.53 26.07 26.82
TC 178.68 194.63 211.36 186.12 202.93 220.77 191.46 208.83 227.48
115 SC 166.24 138.58 110.3 182.4 155.56 121.34 187.63 171.68 131.65
kW 25.76 26.3 26.93 26.46 27.01 27.75 27.35 27.94 28.78
TC 170.09 185.43 201.78 177.06 193.37 210.72 181.92 198.68 216.74
125 SC 162.39 134.77 106.76 173.52 151.86 117.82 178.29 167.8 127.96
kW 27.8 28.37 29.06 28.49 29.07 29.92 29.37 30.01 30.97
TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

12
COOLING CAPACITIES
(Dual compressor units)
BY18 INDOOR UNIT WITH CY240 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 5600/0.061 7000/0.078 8400/0.094
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 221.8 240.1 259.48 231.81 250.97 271.25 238.64 258.55 279.88
85 SC 188.82 158.41 127.52 213.75 176.76 139.28 231.48 193.93 150.34
kW 21.87 22.51 23.08 22.83 23.42 24.02 24.01 24.48 25.24
TC 214.24 232.09 251.03 223.57 242.47 262.5 230.22 249.45 270.47
95 SC 185.37 155.11 124.39 210.14 173.46 136.25 223.32 190.44 147.14
kW 23.87 24.49 25.06 24.8 25.37 25.99 25.75 26.37 27.2
TC 206.19 223.84 242.34 215.03 233.37 253.15 221.07 240.35 260.69
105 SC 181.79 151.81 121.22 206.56 169.9 132.99 214.44 187.14 143.85
kW 26.1 26.69 27.26 26.98 27.53 28.18 27.85 28.46 29.39
TC 197.89 215.1 233.41 206.19 224.26 243.79 211.92 230.88 250.91
115 SC 178.1 148.26 117.99 200 166.42 129.79 205.56 183.65 140.62
kW 28.29 28.86 29.43 29.13 29.67 30.35 29.9 30.58 31.56
TC 188.37 205.39 223.28 196.12 213.95 232.93 201.67 219.95 240.05
125 SC 173.88 144.41 114.37 190.24 162.52 126.07 195.62 179.56 137.11
kW 30.69 31.22 31.83 31.48 32.01 32.75 32.25 32.85 33.99

BY25 INDOOR UNIT WITH CY240 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 6000/0.041 7500/0.054 9000/0.067
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 228.24 247.37 267.41 239.54 259.47 281.25 247.06 268.05 290.56
85 SC 195.68 163.58 130.77 223.35 183.85 144.21 234.71 203.1 156.42
kW 22.42 23 23.62 23.09 23.66 24.39 23.95 24.54 25.38
TC 220.39 238.79 258.62 230.72 250.69 271.88 238.04 258.68 280.86
95 SC 192.32 160.12 127.63 219.18 180.62 141.03 226.14 199.73 153.27
kW 24.38 24.95 25.58 25.01 25.59 26.35 25.85 26.45 27.36
TC 211.76 229.94 249.57 221.57 240.93 261.85 228.24 248.54 270.78
105 SC 188.54 156.65 124.45 210.49 176.85 137.61 216.82 195.94 150.02
kW 26.56 27.11 27.77 27.15 27.72 28.54 27.95 28.57 29.55
TC 203.14 221.1 240.26 212.42 231.5 252.16 218.82 238.79 260.3
115 SC 184.87 153.26 121.2 201.8 173.41 134.43 207.88 192.55 146.63
kW 28.7 29.25 29.94 29.25 29.83 30.73 30.05 30.68 31.77
TC 193.2 210.95 229.66 201.96 220.77 240.84 207.84 227.47 248.66
125 SC 180.61 149.37 117.53 191.86 169.51 130.69 197.45 188.51 142.95
kW 31.05 31.59 32.36 31.57 32.16 33.18 32.34 33.01 34.24

BY25 INDOOR UNIT WITH CY300 OUTDOOR UNIT


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 7200/0.052 9000/0.067 10800/0.082
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 275.76 298.09 321.21 287.45 310.97 334.78 295.53 319.32 344.02
85 SC 246.81 206.13 164.71 279.95 230.66 180.24 289.62 253.39 194.65
kW 26.05 26.75 27.47 27.03 27.71 28.55 28.38 29.09 30.03
TC 264.78 286.86 309.72 275.69 298.87 323.15 283.76 307.14 332.38
95 SC 241.71 201.43 160.37 274.69 225.75 176.12 278.09 248.71 190.73
kW 28.39 29.1 29.87 29.35 30.05 30.95 30.68 31.42 32.44
TC 252.24 274.06 297 262.75 285.61 309.57 269.65 293.57 318.41
105 SC 235.98 196.17 155.69 262.75 220.63 171.3 264.25 243.7 185.92
kW 31.2 31.94 32.78 32.12 32.87 33.88 33.45 34.24 35.38
TC 240.63 262.2 285.21 250.59 273.12 297.54 257.41 280.92 306.31
115 SC 230.7 191.29 151.34 250.59 215.66 167.1 252.26 238.89 181.87
kW 33.71 34.47 35.39 34.61 35.4 36.51 35.91 36.76 38.04
TC 229.02 250.65 273.72 238.04 261.03 285.52 244.71 268.28 294.21
125 SC 225.57 186.71 147.21 233.28 211.06 162.92 239.81 234.12 177.83
` kW 36.19 36.99 38.02 37.07 37.91 39.16 38.36 39.29 40.72
TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

13
COOLING CAPACITIES
(Dual compressor units)
BY25 INDOOR UNIT WITH CY360 OUTDOOR UNIT
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER 9000/0.065 10500/0.079 12000/0.092
ENTERING AIR EVAPORATOR ENTERING AIR, WBE (0F)
TEMP. (0F)
62 67 72 62 67 72 62 67 72
TC 334.9 364.81 396.08 344.97 375.54 407.78 352.94 383.93 417.41
85 SC 304.4 255.21 204.79 331.8 275.15 217.53 345.88 294.2 229.85
kW 35.79 36.73 37.61 36.92 37.83 38.74 38.21 39.09 40.05
TC 321.57 350.77 381.72 330.78 360.98 393.3 338.3 369.36 402.41
95 SC 298.38 249.32 199.36 325.48 269.25 212.3 331.53 288.61 224.57
kW 38.58 39.51 40.42 39.7 40.58 41.54 40.96 41.84 42.87
TC 305.49 334.38 365.43 314.31 344.59 376.55 321.57 352.2 385.34
105 SC 290.83 242.41 193.28 308.03 262.75 206.27 315.14 281.85 218.6
kW 41.69 42.59 43.56 42.76 43.65 44.7 44 44.9 46.04
TC 289.8 318.38 348.75 297.84 327.75 359.35 304.31 335.03 367.76
115 SC 283.9 235.95 187.09 291.89 256.06 200.09 298.23 275.23 212.44
kW 44.74 45.64 46.7 45.78 46.69 47.87 47 47.94 49.23
TC 273.33 301.99 332.46 280.92 310.9 342.61 287.06 317.86 350.69
125 SC 267.87 229.35 181.21 275.3 249.51 194.25 281.32 268.75 206.66
kW 47.74 48.66 49.85 48.76 49.71 51.05 49.97 50.96 52.44

TC – Total Capacity (1000 Btuh) Gross kW – Total unit power input DBE – Dry Bulb Temp. (0F) of Air Entering Coil DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (0F) of Air Entering Coil WBL – Wet Bulb Temp. (0F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

14
FAN PERFORMANCE DATA
BELT DRIVEN MOTORS
MODEL No.: BY07
External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1.0 1.2 1.4
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1800 (849)
2000 (944)
820*
824*
0.62*
0.7*
900
905
I 0.71
0.79
965
970
0.82
0.91
1020
1026
0.88
1.0
1102
1107
1.03
1.12
1145
1152
1.14
1.25
1220
1225
1.26
1.35
2200 (1038) 853 0.81 927 0.91 986 1.02 1041 1.13 1111 1.25 1160 1.36 1237 1.48
2400 (1133) 950 0.94 1004 1.05 1059 1.21 1132 1.27 1155 1.38 1244 1.5 1297 1.65
2600 (1227) 968 1.1 1032 1.22 1086 1.33 1150 1.45 1194 1.57 1250 1.69 1305 1.82
2800 (1321) 1054 1.4 1106 1.5 1160 1.61 1216 1.76 1261 1.88 1323 2.02 1380* 2.2*
3000 (1416) 1066 1.55 1133 1.7 1180 1.82 1234 1.94 1276 2.09 1334* 2.23* 1400* 2.3*
3200 (1510) 1091 1.75 1157 1.91 1202 2.02 1255 2.2 1307 2.33 1359* 2.47*
3400 (1605) 1116 1.96 1171 2.1 1228 2.3 1276 2.45 1329 2.6 1368* 2.73* II
NOTES : 1. Values include losses for filters, unit casing and wet coils.
2. 2 HP motor and alternative drive I to be used for the unshaded portion.
3. 3 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

MODEL No.: BY10


External Static Pressure (inch wg.)
Airflow, 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
610 0.62 710 0.75 745 0.87 760 0.95 850 1.2 905 1.32 965 1.5 1000 1.6 1054 1.8 1100 2.0
2800 (1321)
3000 (1416) 625 0.69 720 0.80 760 I 0.95 810 1.12 865 1.25 915 1.4 970 1.6 1013 1.75 1065 2.0 1115 2.15
3200 (1510) 636 0.77 734 0.92 780 1.06 820 1.26 870 1.38 925 1.51 978 1.73 1023 1.86 1073 2.1 1122 2.28
3400 (1605) 660 0.88 746 1.01 805 1.18 833 1.34 881 1.5 939 1.67 983 1.84 1033 2.02 1083 2.25 1128 2.44
3600 (1699) 675 1.0 760 1.16 820 1.32 848 1.48 900 1.66 950 1.82 995 1.98 1043 2.21 1090 2.41 1131 2.6
3800 (1793) 700 1.13 778 1.3 840 1.43 868 1.63 913 1.8 966 2.0 1006 2.18 1056 2.39 1100 2.58 1143 2.78
4000 (1888) 727 1.28 790 1.45 865 1.62 882 1.8 926 1.96 980 2.18 1023 2.4 1066 2.6 1108 2.77
4200 (1982) 772 1.41 843 1.62 880 1.78 921 1.96 968 2.16 1011 2.36 1054 2.56 1096 2.76
4400 (2076) 791 1.58 864 1.79 887 1.94 934 2.14 979 2.34 1024 2.54 1067 2.77 II
4600 (2170) 840 1.79 890 1.96 931 2.2 975 2.38 1017 2.59 1058 2.77
4800 (2265) 857 1.95 906 2.17 947 2.4 988 2.57 1035 2.76
5000 (2360) 876 2.15 920 2.38 961 2.6 1005 2.76
NOTES : 1. Values include losses for filters, unit casing and wet coils.
2. 2 HP motor and alternative drive I to be used for the unshaded portion.
3. 3 HP motor and alternative drive II to be used for the shaded portion.

MODEL No.: BY14


External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
797 1.52 845 1.66 890 1.83 937 2.03 975 2.25 992 2.4 1075 2.64 1102 2.85
4000 (1888)
4200 (1982)
4400 (2076)
694*
705*
719*
1.21*
1.33*
1.43*
743*
761*
774
1.3*
1.45*
1.6
811
823
I 1.67
1.8
857
869
1.81
1.97
903
918
2.0
2.17
951
963
2.19
2.33
992
1006
2.43
2.58
1002
1010
2.6
2.78
1080
1093
2.82
2.97
II1110
1133
3.05
3.2
4600 (2170) 735* 1.57* 787 1.75 835 1.95 885 2.17 929 2.34 971 2.55 1013 2.75 1053 2.93 1100 3.17 1138 3.41
4800 (2265) 748* 1.72* 800 1.92 846 2.09 897 2.35 935 2.52 979 2.72 1023 2.91 1065 3.14 1107 3.4 1144 3.62
5000 (2360) 761* 1.87* 812 2.09 862 2.30 904 2.52 948 2.70 989 2.91 1032 3.11 1068 3.37 1113 3.6 1150 3.86
5200 (2454) 778 2.06 823 2.27 873 2.48 917 2.70 959 2.91 1001 3.11 1038 3.34 1070 3.59 1119 3.85 1159 4.08
5400 (2548) 800 2.31 846 2.5 894 2.72 934 2.94 979 3.15 1019 3.38 1056 3.64 1098 3.88 1133 4.10 1171 4.36
5600 (2643) 808 2.46 858 2.7 903 2.90 945 3.12 987 3.38 1028 3.65 1063 3.83 1106 4.14 1139 4.35 1176 4.57
5800 (2737) 826 2.68 869 2.9 917 3.12 955 3.4 1000 3.65 1041 3.9 1078 4.13 1114 4.37 1150 4.6 1186 4.78
6000 (2832) 837 2.90 885 3.12 927 3.37 965 3.64 1009 3.9 1047 4.13 1088 4.35 1123 4.59 1157 4.85 1194 5.05
6200 (2926) 850 3.12 900 3.41 940 3.65 980 3.92 1021 4.17 1061 4.38 1100 4.66 1133 4.85 1167 5.1 1205 5.4
6400 (3020) 879 3.41 920 3.70 962 3.96 1000 4.2 1040 4.45 1078 4.69 1114 4.92 1150 5.2 1183 5.45 1218 5.76
6600 (3115) 894 3.76 933 4.0 973 4.24 1013 4.44 1050 4.68 1091 4.92 1125 5.2 1161 5.51 1194 5.8 1229 6.08
NOTES : 1. Values include losses for filters, unit casing and wet coils.
2. Standard 5 HP motor and alternative drive I to be used for the unshaded portion.
3. Alt. 7.5 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

15
FAN PERFORMANCE DATA
BELT DRIVEN MOTORS
MODEL No.: BY18
External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
850 2.07 902 2.4 955 2.66 1005 2.96 1057 3.3 1104 3.6
5000 (2360)
5200 (2454)
715*
718*
1.33*
1.42*
731*
737*
1.56*
1.68*
787*
793* I 1.82*
1.96* 856 2.26 905 2.53 961 2.83 1010 3.15 1060 3.46 II 1107 3.76
1153*
1155*
3.88*
4.04*
5400 (2548) 721* 1.53* 750* 1.81* 802* 2.07* 860 2.35 911 2.66 966 2.96 1012 3.23 1062 3.57 1109 3.88 1157* 4.27*
5600 (2643) 725* 1.68* 756* 1.92* 807 2.21 866 2.5 916 2.79 968 3.07 1015 3.38 1065 3.73 1110 4.07 1158* 4.4*
5800 (2737) 729* 1.81* 762* 2.03* 816 2.35 872 2.64 921 2.9 970 3.23 1020 3.53 1066 3.84 1113 4.18 1159* 4.59*
6000 (2832) 733* 1.9* 775* 2.14* 833 2.42 877 2.78 930 3.02 980 3.4 1025 3.69 1070 4.0 1118 4.4 1162* 4.72*
6200 (2926) 738* 2.03* 788* 2.35* 839 2.57 888 2.92 935 3.24 985 3.56 1030 3.84 1080 4.27 1120 4.63 1163* 4.95*
6400 (3020) 745* 2.15* 795* 2.5* 850 2.71 900 3.08 940 3.41 990 3.72 1036 4.04 1082 4.45 1126 4.82 1165* 5.09*
6600 (3115) 753* 2.38* 800* 2.64* 855 2.92 905 3.25 950 3.58 1000 3.88 1045 4.23 1083 4.6 1127 5 1170* 5.3*
6800 (3209) 761* 2.5* 810 2.78 863 3.08 910 3.41 960 3.75 1004 4.14 1050 4.47 1090 4.83 1134 5.16 1175* 5.51*
7000 (3303) 772* 2.69* 820 2.92 875 3.33 918 3.58 967 3.95 1012 4.28 1054 4.66 1095 5.04 1135 5.39 1179* 5.72*
7200 (3398) 777* 2.84* 830 3.08 880 3.41 927 3.75 976 4.14 1017 4.47 1059 4.85 1100 5.19 1141* 5.58* 1183* 5.95*
7400 (3492) 794* 2.96* 845 3.3 890 3.62 936 3.95 985 4.4 1021 4.68 1065 5.09 1108 5.47 1150* 5.8* 1185* 6.12*
7600 (3587) 805 3.18 850 3.5 900 3.83 941 4.2 990 4.57 1026 4.85 1069 5.23 1112 5.66 1154* 6* 1193* 6.42*
7800 (3681) 820 3.36 870 3.69 909 4.1 954 4.5 1002 4.9 1041 5.14 1083 5.47 1125 5.9 1158* 6.36* 1200* 6.78*
8000 (3775) 830 3.59 880 3.86 922 4.25 963 4.65 1008 5.05 1046 5.33 1087 5.75 1128 6.12 1164* 6.6*
8200 (3870) 867 3.77 890 4.1 936 4.5 972 4.9 1016 5.25 1054 5.56 1100 6 1132 6.36 1172* 6.84*
8400 (3964) 890 4.05 904 4.42 945 4.75 986 5.1 1025 5.45 1066 5.85 1107 6.24 1140 6.72
NOTES : 1. Values include losses for filters, unit casing and wet coils.
2. Standard 5 HP motor and alternative drive I to be used for the unshaded portion.
3. Alt. 7.5 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

MODEL No.: BY25


External Static Pressure (inch wg.)
Airflow, 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
700 2.6 762 3.12 812 3.6 847 4.0 870 4.5 940 5.0 980 5.46 1010 6.0 1059* 6.6*
6000 (2832)
6400 (3020) 706 2.8 764 3.3 I 813 3.78 848 4.22 871 4.73 942 5.23 981 5.71 1011II 6.3 1060* 6.92*
6800 (3209) 716 3.05 766 3.5 814 4.0 849 4.42 872 4.96 944 5.45 982 5.97 1013 6.6 1062* 7.22*
7200 (3398) 722 3.24 768 3.7 815 4.19 850 4.64 873 5.2 945 5.68 983 6.23 1014 6.95 1063* 7.51*
7600 (3587) 732 3.4 770 3.82 816 4.35 851 4.88 874 5.45 947 5.9 985 6.5 1016 7.25 1064* 7.78*
8000 (3775) 740 3.6 772 4.0 818 4.56 852 5.18 875 5.65 948 6.12 986 6.8 1018 7.5 1065* 8.05*
8400 (3964) 751 3.9 778 4.35 821 4.85 853 5.5 876 5.97 949 6.48 988 7.2 1019 7.8 1066* 8.35*
8800 (4152) 759 4.2 784 4.65 824 5.16 857 5.81 878 6.3 951 6.8 990 7.6 1020 8.1 1067* 8.65*
9200 (4341) 770 4.5 790 5.0 828 5.5 862 6.14 880 6.75 953 7.15 992 8.0 1021 8.45 1068* 9.0*
9600 (4530) 779 4.9 796 5.35 832 5.84 870 6.45 900 7.1 955 7.6 994 8.35 1022 8.75 1069* 9.45*
10000 (4719) 790 5.2 806 5.67 838 6.15 878 6.7 915 7.4 957 8.06 996 8.71 1023 9.25 1070* 9.8*
10400 (4907) 801 5.55 813 6.1 849 6.6 890 7.1 920 7.85 965 8.4 1003 9.1 1034* 9.7*
10800 (5096) 809 5.9 825 6.5 870 7.0 898 7.5 928 8.3 973 8.8 1009 9.5
11200 (5286) 821 6.4 856 6.9 876 7.4 906 7.95 936 8.7 981 9.25 1014 9.9
11600 (5474) 852 6.8 872 7.3 885 7.9 914 8.45 944 9.15 989 9.6
12000 (5663) 870 7.2 885 7.8 892 8.5 925 9.0 952 9.6 996 10.1
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.
NOTES: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 7.5 HP motor to be used for the unshaded portion.
3. Alt. 10 HP motor to be used for the shaded portion.

16
ELECTRICAL DATA
MODEL No.: BY07 MODEL No.: BY10
POWER VOLTAGE BLOWER POWER VOLTAGE BLOWER
ELECTRIC HEATER RANGE MOTOR ELECTRIC HEATER
SUPPLY RANGE MOTOR SUPPLY
MCA MOCP MCA MOCP
(V-Ph-Hz) (V-Ph-Hz)
MIN. MAX. HP FLA kW FLA MIN. MAX. HP FLA kW FLA

– – 8.3 15 – – 8.3 15
5 12.6 24 25 5 12.6 24 25
2 6.6 6/7.5 15.1/18.8 27.1/31.8 30/35 2 6.6 6/7.5 15.1/18.8 27.1/31.8 30/35
(STD.) 10*/12* 25.1/30.1 39.6/45.9 40/50 (ALT.) 10*/12* 25.1/30.1 39.6/45.9 40/50
15*/20* 37.7/50.2 55.4/71 60/80 15*/20* 37.7/50.2 55.4/71 60/80
25*/30* 62.8/75.3 86.8/102.4 90/110
25*/30* 62.8/75.3 86.8/102.4 90/110
208/230-3-60 187 253 – – 11 20
5 12.6 26.8 30 208/230-3-60 187 253
– – 11 20
3 8.8 6/7.5 15.1/18.8 29.9/34.5 35/35
(ALT.) 10*/12* 25.1/30.1 42.4/48.6 45/50 5 12.6 26.8 30
15*/20* 37.7/50.2 58.1/73.8 60/80 3 8.8 6/7.5 15.1/18.8 29.9/34.5 35/35
(STD.)
25*/30* 62.8/75.3 89.5/105.1 90/110 10*/12* 25.1/30.1 42.4/48.6 45/50
– – 5 15 15*/20* 37.7/50.2 58.1/73.8 60/80
5 7.6 14.5 15 25*/30* 62.8/75.3 89.5/105.1 90/110
2 4 6/7.5 9.1/11.4 16.4/19.3 20/20
(STD.) 10*/12* 15.2/18.2 24/27.8 25/30
– – 5 15
15*/20* 22.8/30.4 33.5/43 35/45
5 7.6 14.5 15
25*/30* 38/45.6 52.5/62 60/70
380-3-60 342 418 2 4 6/7.5 9.1/11.4 16.4/19.3 20/20
– – 6.4 15
(4 WIRE) (ALT.) 10*/12* 15.2/18.2 24/27.8 25/30
5 7.6 15.9 20
3 5.14 6/7.5 9.1/11.4 17.8/20.7 20/25 15*/20* 22.8/30.4 33.5/43 35/45
(ALT.) 10*/12* 15.2/18.2 25.4/29.2 30/30 25*/30* 38/45.6 52.5/62 60/70
15*/20* 22.8/30.4 34.9/44.4 40/45
380-3-60 342 418
25*/30* 38/45.6 53.9/63.4 60/70 (4 WIRE) – – 6.4 15
– – 4.4 15 5 7.6 15.9 20
5 6.3 12.3 15
3 5.14 6/7.5 9.1/11.4 17.8/20.7 20/25
2 3.5 6/7.5 7.5/9.4 13.8/16.1 15/20 (STD.)
(STD.) 10*/12* 15.2/18.2 25.4/29.2 30/30
10*/12* 12.6/15.1 20.1/23.3 25/25
15*/20* 22.8/30.4 34.9/44.4 40/45
15*/20* 18.8/25.1 27.9/35.8 30/40
25*/30* 38/45.6 53.9/63.4 60/70
25*/30* 31.4/37.7 43.6/51.5 45/60
460-3-60 414 506 – – 5.1 15
5 6.3 13 15 – – 4.4 15
3 4.1 6/7.5 7.5/9.4 14.5/16.9 15/20 5 6.3 12.3 15
(ALT.) 10*/12* 12.6/15.1 20.9/24 25/25 2 3.5 6/7.5 7.5/9.4 13.8/16.1 15/20
15*/20* 18.8/25.1 28.6/36.5 30/40 (ALT.) 10*/12* 12.6/15.1 20.1/23.3 25/25
25*/30* 31.4/37.7 44.4/52.3 45/60 15*/20* 18.8/25.1 27.9/35.8 30/40
25*/30* 31.4/37.7 43.6/51.5 45/60
LEGEND
460-3-60 414 506
FLA – Full Load Amps – – 5.1 15
5 6.3 13 15
HP – Horse Power
3 4.1 6/7.5 7.5/9.4 14.5/16.9 15/20
(STD.)
MCA – Minimum Circuit Amps 10*/12* 12.6/15.1 20.9/24 25/25
15*/20* 18.8/25.1 28.6/36.5 30/40
MOCP – Maximum Over Current Protection
25*/30* 31.4/37.7 44.4/52.3 45/60

* Combination of 2 heater modules

17
ELECTRICAL DATA
MODEL No.: BY14 MODEL No.: BY18
POWER VOLTAGE BLOWER POWER VOLTAGE BLOWER
RANGE MOTOR ELECTRIC HEATER RANGE MOTOR ELECTRIC HEATER
SUPPLY SUPPLY
MCA MOCP MCA MOCP
(V-Ph-Hz) (V-Ph-Hz)
MIN. MAX. HP FLA kW FLA MIN. MAX. HP FLA kW FLA
– – 17.3 30 – – 17.3 30
5 12.6 33 40 5 12.6 33 40
5 13.8 6/7.5 15.1/18.8 36.1/40.8 45/45 5 13.8 6/7.5 15.1/18.8 36.1/40.8 45/45
(STD.)
(STD.) 10*/12* 25.1/30.1 48.6/54.9 50/60 10*/12* 25.1/30.1 48.6/54.9 50/60
15*/20* 37.7/50.2 64.4/80 70/90 15*/20* 37.7/50.2 64.4/80 70/90
25*/30* 62.8/75.3 95.8/111.4 100/125 25*/30* 62.8/75.3 95.8/111.4 100/125
35*/40* 87.9/100.4 127.1/142.8 150/150
208/230-3-60 187 253 208/230-3-60 187 253
– – 24.4 40 – – 24.4 40

5 12.6 40.1 50 5 12.6 40.1 50

7.5 19.5 6/7.5 15.1/18.8 43.3/47.9 50/60 7.5 19.5 6/7.5 15.1/18.8 43.3/47.9 50/60
(ALT.)
(ALT.) 10*/12* 25.1/30.1 55.8/62 60/70 10*/12* 25.1/30.1 55.8/62 60/70
15*/20* 37.7/50.2 71.5/87.1 80/90
15*/20* 37.7/50.2 71.5/87.1 80/90
25*/30* 62.8/75.3 102.9/118.5 110/125
25*/30* 62.8/75.3 102.9/118.5 110/125
35*/40* 87.9/100.4 134.3/149.9 150/175
– – 11.3 20
– – 11.3 20
5 7.6 20.8 25
5 7.6 20.8 25
5 9 6/7.5 9.1/11.4 22.6/25.5 25/30
5 9 6/7.5 9.1/11.4 22.6/25.5 25/30 (STD.)
(STD.) 10*/12* 15.2/18.2 30.3/34 35/35
10*/12* 15.2/18.2 30.3/34 35/35
15*/20* 22.8/30.4 39.8/49.3 45/50
15*/20* 22.8/30.4 39.8/49.3 45/50
25*/30* 38/45.6 58.8/68.3 60/70
25*/30* 38/45.6 58.8/68.3 60/70
35*/40* 53.2/60.8 77.8/87.3 80/90
380-3-60 342 418
380-3-60 342 418 (4 WIRE) – – 15.6 25
(4 WIRE) – – 15.6 25
5 7.6 25.1 35
5 7.6 25.1 35
7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35
7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35 (ALT.)
10*/12* 15.2/18.2 34.6/38.4 40/45
(ALT.) 10*/12* 15.2/18.2 34.6/38.4 40/45 15*/20* 22.8/30.4 44.1/53.6 50/60
15*/20* 22.8/30.4 44.1/53.6 50/60 25*/30* 38/45.6 63.1/72.6 70/80
25*/30* 38/45.6 63.1/72.6 70/80 35*/40* 53.2/60.8 82.1/91.6 90/100
– – 8.6 15
– – 8.6 15 5 6.3 16.5 20
5 6.3 16.5 20 5 6.9 6/7.5 7.5/9.4 18/20.4 20/25
(STD.)
5 6.9 6/7.5 7.5/9.4 18/20.4 20/25 10*/12* 12.6/15.1 24.4/27.5 30/30
(STD.)
10*/12* 12.6/15.1 24.4/27.5 30/30 15*/20* 18.8/25.1 32.1/40 35/45
15*/20* 18.8/25.1 32.1/40 35/45 25*/30* 31.4/37.7 47.9/55.8 50/60
25*/30* 31.4/37.7 47.9/55.8 50/60 35*/40* 43.9/50.2 63.5/71.4 70/80
460-3-60 414 506
– – 12.2 20
460-3-60 414 506
– – 12.2 20 5 6.3 20.1 25
5 6.3 20.1 25 7.5 9.75 6/7.5 7.5/9.4 21.6/23.9 25/30
(ALT.)
7.5 9.75 6/7.5 7.5/9.4 21.6/23.9 25/30 10*/12* 12.6/15.1 27.9/31.1 30/35
(ALT.)
10*/12* 12.6/15.1 27.9/31.1 30/35 15*/20* 18.8/25.1 35.7/43.6 40/45
15*/20* 18.8/25.1 35.7/43.6 40/45 25*/30* 31.4/37.7 51.4/59.3 60/70
25*/30* 31.4/37.7 51.4/59.3 60/70 35*/40* 43.9/50.2 67.1/74.9 70/80

LEGEND
FLA – Full Load Amps

HP – Horse Power

MCA – Minimum Circuit Amps

MOCP – Maximum Over Current Protection

* Combination of 2 heater modules

18
ELECTRICAL DATA
MODEL No.: BY25
POWER VOLTAGE BLOWER
RANGE MOTOR ELECTRIC HEATER
SUPPLY
MCA MOCP
(V-Ph-Hz)
MIN. MAX. HP FLA kW FLA
– – 25.5 45
5 12.6 41.2 50
7.5 20.4 6/7.5 15.1/18.8 44.3/49 60/60
(STD.)
10*/12* 25.1/30.1 56.9/63.2 70/70
15*/20* 37.7/50.2 72.6/88.3 80/90
25*/30* 62.8/75.3 103.9/119.6 110/125
35*/40* 87.9/100.4 135.3/151 150/175
208/230-3-60 187 253
– – 32.6 50
5 12.6 48.3 70
10 26.1 6/7.5 15.1/18.8 51.5/56.2 70/70
(ALT.)
10*/12* 25.1/30.1 64/70.3 80/80
15*/20* 37.7/50.2 79.7/95.4 90/100
25*/30* 62.8/75.3 111.1/126.8 125/150
35*/40* 87.9/100.4 142.4/158.1 150/175
– – 15.6 25
5 7.6 25.1 35
7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35
(STD.)
10*/12* 15.2/18.2 34.6/38.4 40/45
15*/20* 22.8/30.4 44.1/53.6 50/60
25*/30* 38/45.6 63.1/72.6 70/80
35*/40* 53.2/60.8 82.1/91.6 90/100
380-3-60 342 418
(4 WIRE) – – 20 35
5 7.6 29.5 40
10 16 6/7.5 9.1/11.4 31.4/34.2 45/45
(ALT.)
10*/12* 15.2/18.2 39/42.8 50/50
15*/20* 22.8/30.4 48.5/58 50/60
25*/30* 38/45.6 67.5/77 70/80
35*/40* 53.2/60.8 86.5/96 90/100
– – 12.8 20
5 6.3 20.6 25
7.5 10.2 6/7.5 7.5/9.4 22.2/24.5 30/30
(STD.)
10*/12* 12.6/15.1 28.4/31.6 35/35
15*/20* 18.8/25.1 36.3/44.1 40/45
25*/30* 31.4/37.7 52/59.8 60/60
35*/40* 43.9/50.2 67.7/75.5 70/80
460-3-60 414 506
– – 16.3 25
5 6.3 24.1 35
10 13 6/7.5 7.5/9.4 25.7/28 35/35
(ALT.)
10*/12* 12.6/15.1 31.9/35.1 40/40
15*/20* 18.8/25.1 39.8/47.6 45/50
25*/30* 31.4/37.7 55.5/63.3 60/70
35*/40* 43.9/50.2 71.2/79 80/80

LEGEND
FLA – Full Load Amps

HP – Horse Power

MCA – Minimum Circuit Amps

MOCP – Maximum Over Current Protection

* Combination of 2 heater modules

19
DIMENSIONS
BY07 - BY14 (HORIZONTAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL
A B C D E F G H J K L M
BY07 1360(53.5) 1100(43.31) 600(23.62) 813(32) 182(7.16) 406(15.98) 66(2.6) 995(39.17) 550(21.65) 378(14.88) 721(28.38) 123(4.84)
BY10 1490(58.7) 1400(55.12) 675(26.57) 813(32) 332(13.1) 406(15.98) 42(1.65) 1295(51) 625(24.61) 378(14.88) 721(28.38) 198(7.8)
BY14 1625(64) 1600(63) 705(27.75) 1321(52) 187(7.36) 406(15.98) 55(2.16) 1495(58.86) 655(25.8) 471(18.54) 791(31.14) 153(6.02)

20
DIMENSIONS
BY07 - BY14 (VERTICAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL
A B C D E F G H J K L M
BY07 1360(53.5) 1100(43.31) 600(23.62) 813(32) 213(8.4) 406(15.98) 85(3.34) 991(39) 504(19.83) 302(11.87) 697(27.53) 110(4.33)
BY10 1490(58.7) 1400(55.12) 675(26.57) 813(32) 365(14.38) 406(15.98) 35(1.38) 1299(51.15) 607(23.91) 338(13.29) 732(28.81) 123(4.84)
BY14 1625(64) 1600(63) 705(27.75) 1321(52) 224(8.82) 406(15.98) 49(1.92) 1497(58.95) 607(23.91) 370(14.59) 929(36.56) 110(4.33)

21
DIMENSIONS
BY18 - BY25 (HORIZONTAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL
A B C D E F G H J K L M
BY18 1625(64) 2070(81.5) 705(27.75) 1575(62) 382(15.04) 483(19.02) 35(1.38) 1965(77.36) 655(25.79) 471(18.54) 791(31.14) 153(6.02)
BY25 1825(71.85) 2362(93) 840(33.1) 1575(62) 590(23.23) 483(19.02) 50(1.97) 2257(88.86) 790(31.1) 503(19.8) 913(35.94) 288(11.34)

22
DIMENSIONS
BY18 - BY25 (VERTICAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL
A B C D E F G H J K L M
BY18 1625(64) 2070(81.5) 705(27.75) 1575(62) 422(16.61) 483(19.02) 46(1.81) 1969(77.52) 596(23.46) 354(13.94) 878(34.57) 110(4.33)
BY25 1825(71.85) 2362(93) 840(33.1) 1575(62) 625(24.61) 483(19.02) 74(2.91) 2217(87.28) 596(23.46) 704(27.72) 878(34.57) 110(4.33)

23
DIMENSIONS - HEATER BOX
BY07 - BY14

.2")
(1 6
412

P
) TY
.4 (1"
25
205 (8.1")

DIMENSIONS
MODEL HEATER ACCESS COVER
A
BY07 818 (32.2) HEATER CONTROLS MTG
BY10 818 (32.2) COVER
HEATER CONTROLS MTG
BY14 1326(52.2) PLATE

BY18 - BY25

")
(1 9.4
492

P
") TY
4 (1
25.
205 (8.1")

1581 (6
2.3")

HEATER ACCESS COVER


(BOTH SIDES) HEATER CONTROLS MTG
COVER
HEATER CONTROLS MTG
PLATE

NOTES: 1. All dimensions are in mm (dimensions in brackets are in inches).


2. Heater box is an optional feature.

24
DIMENSIONS
MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CY075 - CY120
1061 [41.771"]

1016 [40"]

571 [22.480"]
966 [38.031"]
1123 [44.212"]
1161 [45.708"]

115 [4.527"]
190 [7.480"]

82 [3.228"]

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Dual system units will have 2 set of service valves.
3. Allow 32" (812 mm) clearance to service end of the unit, 24" (610 mm) on remaining sides and 48" (1219 mm) between units for
proper airflow.

25
DIMENSIONS
MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CY150 - CY300

MODEL NUMBER A B C D E F G

CY150 - CY220 1900 (74.8) 1120 (44.09) 1145 (45.07) 1071 (42.16) 150 (5.9) 800 (31.5) 800 (31.5)

CY240 - CY300 2200 (86.61) 1225 (48.23) 1300 (51.18) 1179 (46.41) 300 (11.81) 800 (31.5) 800 (31.5)

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Single system units will have 1 set of service valves.
3. Allow 32" (812 mm) clearance to service end of the unit, 48" (1219 mm) on remaining sides for proper airflow.

26
DIMENSIONS
MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CY360
195 [7.677"]

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Allow 32" (812 mm) clearance to service end of the unit, 48" (1219 mm) on remaining sides for proper airflow.

27
TYPICAL SCHEMATIC WIRING DIAGRAM
(Matching with single compressor units)
HVTB OR BMC
L1
REFER TO UNIT
L2
NAMEPLATE FOR
POWER SUPPLY L3

LUG

BMC

68
69
70
BM

TO CONDENSING UNIT ATB

HC2
AFS
NC
28 C
HC1
NO

230V BMC

TO CONDENSING UNIT ATB

LOCK2(RED) LOCK1(RED) ECB


SYSTEM2(ORG) SYSTEM1(YEL)
30

29
PRI

FUSE

P3_##
TRANS

ON DIP
SEC

DIP SWITCH
POWER(GRN) W2 W1 Y1 G C R TO CONDENSING UNIT ATB

J_PROG

THERMOSTAT / DDC CONTROLLER


(by others)
LVTB
R
R
24Vac C
C
BM CONTROL G
G
STG1 COOLING Y1
Y1
STG1 HEATING W1
W1
STG2 HEATING W2
W2

CONNECTION APPLICABLE FOR 1PH BM APPLICABLE FOR BM WITH


EXTERNAL OLR (OPTION)
TO HVTB
L1
L2
L3

BMC

OLR
68
69
70

BM

LVTB BMC ATB


18 OLR 19
G 2
BM

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.

28
TYPICAL SCHEMATIC WIRING DIAGRAM
(Matching with single compressor units)

ECB DIP SWITCH SETTINGS & LED INDICATORS LEGEND


DIP SWITCH FUCTIONS FACTORY SETTINGS OF DIP SWITCHES LED INDICATORS
AI ANTI ICE THERMOSTAT
Green power on/off indicator
S1 OFF=TEST MODE DISABLE ON= TEST MODE ENABLE
DIP SWITCH # S1 S2 S3 S4 Red system lock-out due to system fault AFS AIRFLOW SWITCH
system 1 fault diagnostic
S2
LOAD BALANCE
OFF= (Comp1&2 Auto Lead Lag) ON= COMPRESSOR 1 LEAD ON ATB AUXILIARY TERMINAL BLOCK
OFF Yellow blinking slow - LPS1/ HPS1/ SSPS1/
OLR1/CB1 ckt fault AR AUXILIARY RELAY
S3 OFF= WITHOUT PUMP DOWN ON= WITH PUMP DOWN OPTION note:
Set dip switch # 3 according to unit's option system 2 fault diagnostic BM BLOWER MOTOR
S4 on-board programming function (always set to on) (pump down or no pump down) Orange blinking slow - LPS2/ HPS2/ SSPS2/
OLR2/ CB2 ckt fault BMC BLOWER MOTOR CONTACTOR
CAP CAPACITOR
TO HVTB TO HVTB TO HVTB TO HVTB
ECB ELECTRONIC CONTROL BOARD
L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3
FL FUSE LINK
HC HEATER CONTACTOR
HVTB HIGH VOLTAGE TERMINAL BLOCK
HTR HEATER
F11
F12
F13

F14
F15
F16

F17
F18
F19

F20
F21
F22

71A F11
72A F12
73A F13

F11
F12
F13

F17
F18
F19
F17
F18
F19
L1 LINE 1
74A
75A
76A

74A
75A
76A
71A
72A
73A

71B
72B
73B

74B
75B
76B

74A
75A
76A
71A
72A
73A
L2 LINE 2
HC1 HC1 HC1 HC2
HC2 HC3 HC4 HC3
L3 LINE 3
T1H
T2H
T3H
T1F
T2F
T3F
T1G
T2G
T3G

T1H
T2H
T3H

LVTB LOW VOLTAGE TERMINAL BLOCK


T1F
T2F
T3F

T1I
T2I
T3I

HEATER1 HEATER2 HEATER3 HEATER4 HEATER1 HEATER3 LUG LUG GROUND

T1G
T2G
T3G

T1H
T2H
T3H
T1F
T2F
T3F

T1I
T2I
T3I
29 HC1 28 30 HC3 28 HEATER1 HEATER2 HEATER3 HEATER4 MOHT MANUAL RESET OHT
29 HC1 28 30 HC3 28
HC4
NTB NEUTRAL TERMINAL BLOCK
HC2 29 HC1 28 30 HC2 28
OHT OVERHEAT THERMOSTAT
HEATER OPTION-1 (SEE TABLE) HEATER OPTION-2 (SEE TABLE) HEATER OPTION-3 (SEE TABLE) OLR OVER LOAD RELAY
SM SYSTEMIZER
HEATER TYPES VFC VOLT FREE CONTACT
HEATER DATA TABLE OPTIONS ___ FIELD WIRING
OHT OHT
HEATER DATA TABLE
FL FL 1) ANTI ICE OPTION + DISCONNECT TAB - 1/4"
H1 HTR OPT# STG I STG II STG
FL OR MOHT
5 K.W 2 1 5 K.W
COMP
6 K.W 2 1 6 K.W
OHT OHT 21A AI-1 23A NOTES
7.5 K.W 2 1 7.5 K.W
H2 LPS 1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
10 K.W 2 2 5 K.W 5 K.W
THERMOSTAT CONTROL VOLTAGE - 24VAC.
12 K.W 2 2 6 K.W 6 K.W
CONNECTION APPLICABLE FOR ANTI ICE
OHT 15 K.W 2 2 7.5 K.W 7.5 K.W 2. ANY WIRE REPLACEMENT SHOULD BE OF THE
(#1) FL 2) VFC OPTION FOR BM RUN &TRIP INDICATION
20 K.W 2 2 10 K.W 10 K.W 900C OR ITS EQUIVALENT.
H3 FL USE COPPER CONDUCTOR WIRES ONLY.
25 K.W 2 2 12.5 K.W 12.5 K.W 48 BMCA-1A 49
48A
OHT FL 30 K.W 2 2 15 K.W 15 K.W 3. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORT
(#2)
CYCLE PROTECTION FOR COMPRESSOR IS AVAIL-
35 K.W 2 7.5+10 K.W 7.5+10 K.W
OHT * BM ON ABLE IN ZAMIL ELECTRONIC THERMOSTAT.
40 K.W 2 2*10 K.W 2*10 K.W
H4 FL FL
* BMCA-2A 52 4. IF HEATERS ARE FACTORY INSTALLED, PLEASE
NOTES: HTR-35 & 40KW IS APPLICABLE FOR 51 51A
FL BY 18 MODEL ONLY. READ BROKEN LINES AS CONTINUOUS LINES.
USE OPTION 1 FOR 230V-3PH UNIT MODEL
OHT * USE OPTION 3 FOR 380V/460V-3PH UNIT MODEL 5. FUSED DISCONNECT SWITCH OR CIRCUIT
* BM TRIP
BREAKER TO BE PROVIDED BY CONSUMER WITH
BM TRIP CONNECTION FOR BM WITH OLR RATING AS RECOMMENDED BY ZAMIL.

51 OLR-2 52 6. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLT-


AGE ACROSS TERMINAL X1, X2 & 2 IS 230 VAC.

BM TRIP 7. NTB IS APPLICABLE FOR UNITS WITH 1 PHASE


BLOWER MOTOR ONLY. ALSO APPLICABLE FOR
UNITS WITH 380 VOLT.

29
TYPICAL SCHEMATIC WIRING DIAGRAM
(Matching with dual compressor units)

APPLICABLE FOR 1PH BM APPLICABLE FOR BM WITH EXTERNAL OLR

HVTB BMC TO HVTB


L1 68
REFER TO UNIT
NAMEPLATE FOR
L2 69
BM

L1
L2
L3
POWER SUPPLY

L3 70 BMC

OLR
LUG

68
69
70
BM

LVTB OLR 19 BMC ATB


18
G 2

TO CU ATB

HC2
NC
28 C
HC1
NO

BMC

TO CONDENSING UNIT ATB


230V
TO CU ATB
41B

41A

4B

4A

3B

3A
30

29

14
OUTFAN2

OUTFAN1

HEATER2

HEATER1
NEUTRAL

COMP1
COMP2
INFAN
LIVE

X2

X1

P2

P1

LOCK2(RED) LOCK1(RED) ECB


SYSTEM2(ORG) SYSTEM1(YEL)
30

29
PRI

FUSE

HP1
TRANS

240v (HP1)
12v-0-12v
HP2
(HP2)

LP1 26A 13
SEC

DIP SWITCH
(LP1) 23A
POWER(GRN) 14 TO CONDENSING UNIT ATB
J_PROG LP2 22B 15
(LP2) 23B
16

THERMOSTAT / DDC CONTROLLER

LVTB

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.

30
TYPICAL SCHEMATIC WIRING DIAGRAM
(Matching with dual compressor units)

LEGEND
ECB DIP SWITCH SETTINGS & LED INDICATORS
DIP SWITCH FUCTIONS FACTORY SETTINGS OF DIP SWITCHES LED INDICATORS AI ANTI ICE THERMOSTAT
S1 OFF=TEST MODE DISABLE ON= TEST MODE ENABLE
Green power on/off indicator
AFS AIRFLOW SWITCH
DIP SWITCH # S1 S2 S3 S4 Red system lock-out due to system fault
LOAD BALANCE system 1 fault diagnostic
ATB AUXILIARY TERMINAL BLOCK
S2 OFF= ON= COMPRESSOR 1 LEAD ON
(Comp1&2 Auto Lead Lag) OFF Yellow blinking slow - LPS1/ HPS1/ SSPS1/ AR AUXILIARY RELAY
S3 OFF= WITHOUT PUMP DOWN ON= WITH PUMP DOWN OPTION note:
OLR1/CB1 ckt fault
BM BLOWER MOTOR
system 2 fault diagnostic
Set dip switch # 3 according to unit's option
(pump down or no pump down) Orange blinking slow - LPS2/ HPS2/ SSPS2/
BMC BLOWER MOTOR CONTACTOR
S4 on-board programming function (always set to on)
OLR2/ CB2 ckt fault ECB ELECTRONIC CONTROL BOARD
FL FUSE LINK
TO HVTB TO HVTB TO HVTB TO HVTB
HC HEATER CONTACTOR
L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 HVTB HIGH VOLTAGE TERMINAL BLOCK
HTR HEATER
L1 LINE 1
L2 LINE 2
F11
F12
F13

F14
F15
F16

F17
F18
F19

F20
F21
F22

71A F11
72A F12
73A F13

F11
F12
F13

F17
F18
F19
F17
F18
F19
L3 LINE 3
74A
75A
76A

74A
75A
76A
71A
72A
73A

71B
72B
73B

74B
75B
76B

74A
75A
76A
71A
72A
73A
LVTB LOW VOLTAGE TERMINAL BLOCK
HC1
HC1 HC2 HC3 HC4 HC1 HC3 HC2
LUG LUG GROUND
LLS LEAD LAG SWITCH
T1H
T2H
T3H
T1F
T2F
T3F
T1G
T2G
T3G

T1H
T2H
T3H
T1F
T2F
T3F

T1I
T2I
T3I

HEATER1 HEATER2 HEATER3 HEATER4 HEATER1 HEATER3 MOHT MANUAL RESET OHT

T1G
T2G
T3G

T1H
T2H
T3H
T1F
T2F
T3F

T1I
T2I
T3I
29 HC1 28 30 HC3 28 HEATER1 HEATER2 HEATER3 HEATER4 NTB NEUTRAL TERMINAL BLOCK
HC1 28 HC3 28
29 30 OHT OVERHEAT THERMOSTAT
HC2 HC4 HC1 28 30 HC2 28
29
OLR OVER LOAD RELAY
HEATER OPTION-1 (SEE TABLE) HEATER OPTION-2 (SEE TABLE) HEATER OPTION-3 (SEE TABLE) SM SYSTEMIZER
VFC VOLT FREE CONTACT
HEATER TYPES
HEATER DATA TABLE ___ FIELD WIRING
OHT OHT
FL
HEATER DATA TABLE
OPTIONS + DISCONNECT TAB - 1/4"
FL
H1 HTR OPT# STG I STG II STG
1) ANTI ICE OPTION FL OR MOHT
5 K.W 2 1 5 K.W

OHT OHT
6 K.W 2 1 6 K.W COMP1 NOTES
7.5 K.W 2 1 7.5 K.W 21A AI-1 23A
H2 1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
10 K.W 2 2 5 K.W 5 K.W LPS1
THERMOSTAT CONTROL VOLTAGE - 24VAC.
12 K.W 2 2 6 K.W 6 K.W

OHT 15 K.W 2 2 7.5 K.W 7.5 K.W COMP2 2. ANY WIRE REPLACEMENT SHOULD BE OF THE
(#1) FL AI-2 23B
20 K.W 2 2 10 K.W 10 K.W 21B 900C OR ITS EQUIVALENT.
H3 FL LPS2 USE COPPER CONDUCTOR WIRES ONLY.
25 K.W 2 2 12.5 K.W 12.5 K.W
OHT
(#2)
FL 30 K.W 2 2 15 K.W 15 K.W 3. IF HEATERS ARE FACTORY INSTALLED, PLEASE
OHT
35 K.W
* 2 7.5+10 K.W 7.5+10 K.W 2) VFC OPTION FOR BM RUN &TRIP INDICATION READ BROKEN LINES AS CONTINUOUS LINES.
40 K.W 2 2*10 K.W 2*10 K.W
H4 FL FL
* 4. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORT
NOTES: HTR-35 & 40KW IS APPLICABLE FOR 48 49
FL BY 18 & 25 MODELS ONLY. 48A CYCLE PROTECTION FOR COMPRESSOR IS AVAIL-
USE OPTION 1 FOR 230V-3PH UNIT MODEL ABLE IN ZAMIL ELECTRONIC THERMOSTAT.
OHT * USE OPTION 3 FOR 380V/460V-3PH UNIT MODEL
* BM ON 5. FUSED DISCONNECT SWITCH OR CIRCUIT
52 BREAKER TO BE PROVIDED BY CONSUMER WITH
51 51A
RATING AS RECOMMENDED BY ZAMIL.

6. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLT-


BM TRIP AGE ACROSS TERMINAL X1, X2 & 2 IS 230 VAC.
BM TRIP CONNECTION FOR BM WITH OLR 7. NTB IS APPLICABLE FOR UNITS WITH 1 PHASE
BLOWER MOTOR ONLY. ALSO APPLICABLE FOR
51 OLR-2 52 UNITS WITH 380 VOLT.

BM TRIP

31
CONTROLS & SEQUENCE OF OPERATION
Scroll compressors are designed to operate in single direction only. Hence, care has to be taken to ensure correct
rotation when the system is operated. Verification of correct rotation is by observing that the suction pressure drops and
discharge pressure rises when compressor run. Reverse rotation results in abnormal sound, as well as, substantially low
current draw and by interchanging power supply wire L1 & L3 will correct this problem.
The operation of the air conditioning unit is controlled by a 24VAC electronic control board.
GENERAL
The thermostat normally displays room temperature and mode of operation. The five buttons on the front of the unit
allow complete control of the thermostat. The thermostat also allows to select continuous fan operation (useful when
using an air cleaner) or have the fan come on with the compressor.
SWITCH FUNCTION
- On/Off Key : Switch the system On or Off.
- Up Key : To increases the set temperature.
- Down Key : To decreases the set temperature.
- Mode Key : Changes the mode to Fan, Cool, Heat or Auto.
- Fan Key : Changes the Fan Operation to Auto or Continuous.
- °C/°F selection : By pressing Mode & UP key together, toggles between °C to °F or vice versa.
USER CONTROLS
Mode:
Select the desired mode of operation by pressing of the mode button:

F
A
N

H
E
A
T
C
O
O
L

A
U
T
O
Fan: In this mode of operation, the compressor will be in inactive state. Display shows room temperature. Fan will be running.

Cool: In this mode of operation, the compressor will be ON after a delay depending on the differential of room
temperature & Set temperature.
Heat: In this mode of operation, Fan is ON.
Auto: In auto mode, thermostat provide automatic changeover from heating to cooling mode & vice versa. Ther-
mostat automatically switches to maintain the desired temperature.
DIP SWITCH OPTIONS AND FUNCTIONS
There are 4 small DIP (Dual in line package) switches on the back of the circuit board which must be configured by
the installer.
HOOK-UP WIRING DIAGRAM
DIP SWITCH SELECTION ( THERMOSTAT CONTROLLER TO AIR HANDLING UNIT )
SWITCH ON OFF
1 N. A. - THERMOSTAT
(ZAC P/N 80065261)

2 N. A. -
3 N. A. - NOTE: OPTIONAL CONNECTION :
Y2
W1
4
IF REMOTE TEMPERATURE SENSING
INDOOR SENSOR REMOTE SENSOR FUNCTION IS REQUIRED.
Y1
SENSOR
ACCU CONTROL PANEL REMOTE G
Note: SENSOR

Keep DIP SWITCH 1, 2 & 3 in OFF COMPRESSOR FAULT SIGNAL


(VOLT-FREE CONTACT) ATB
24V(R)
24V(C)

position only. COMP 1

COMP 2
( OPTIONAL CONNECTION )
FAULT 1
FAULT 2
W2

(COMMON)

AHU CONTROL PANEL

LVTB
R
24V ac
C
SUPPLY FAN CONTROL
G
STG1 COOLING
Y1
STG2 COOLING
Y2
LEGEND: STG1 HEATER
W1
ATB AUXILIARY TERMINAL BLOCK STG2 HEATER
W2
LVTB LOW VOLTAGE TERMINAL BLOCK

32
INSTALLATION INSTRUCTIONS
A. GENERAL
Blower units are shipped completely wired. Only external power, interconnecting control wiring between outdoor and
indoor units and refrigerant pipe connections are needed to complete the installation. For detailed instructions/informa-
tions, please refer to corresponding IOM manual.

B. UNIT LOCATION & ACCESS SPACE


The placement of the unit in relationship to the building is very important. A minimum of 36 inches clearance must be
kept on the service access side and return air side.
When making tubing connections, be sure to provide clearance for electrical connections.

C. TUBING INSTALLATION
Do not remove plugs from the compression fittings until tubing has been run and is ready for connection.
a. Make sure the tubing is round, without dent or burrs.
b. Cut tubing to the length required with a tube cutter carefully. Do not use a hacksaw.
c. Remove burr from inside and outside using file or deburring tool.
NOTE: Always use a gear type tube bender when making bends in suction line.
When installing tubing through walls or along side of any structural members, be sure the tubing is isolated from these
members or walls to avoid any transmission of vibration that may occur, while unit is running.

ELECTRICAL
STEP 1: INSTALLATION
A) Please ensure power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements.
Caution: Operation of the unit on improper power supply will result in damage to the unit.
NOTE: Use copper wires of proper rating for all field wiring.
Warning
Before servicing or installation of the unit, always TURN OFF all power to the unit. There may be more than one discon-
nect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death.
B) Ground & power wires
Connect power wires to terminal block per wiring diagram.
Connect ground wire to the ground lug inside the control box.
C) Control wiring between outdoor & indoor unit
Use 16 gauge color-coded wire between the indoor and outdoor units (control wiring).

STEP 2: START-UP
Refer to outdoor unit installation instructions for system start-up instructions and refrigerant charging method details.

STEP 3: SEQUENCE OF OPERATION


With power supplied to indoor and outdoor units, the unit starts responding to the thermostat mode requirement.
Cooling mode: When thermostat calls for cooling, the blower motor in the indoor unit is switched on. The compressor
contactor is energized to start the compressor and condenser fan.
As the conditioned space approaches the thermostat cooling set point, the unit cycles off.
Heating mode: When thermostat calls for heating, the blower motor in the indoor unit is switched on. The contactor for
electric heater is switched on to energize the heaters. If the room temperature is not satisfied and there are two heaters
installed, the second heater also will be energized.
Once, the conditioned space approaches the desired temperature set point, the heating stages cycles off.
Fan mode: In this mode the indoor unit blower motor is switched on alone.

33
PL-AP-BY2-10-2M-E