You are on page 1of 2

Cu/MGT/XLPE/OSCR/LSHF/SWB/LSHF 500V CABLE

Customer : Fair-Edge Industrial Supple Sdn. Bhd.


Project : TCOT Project (Top Up)
Document No : TS-FAIR EDGE-12-18
Revision : 00
Date : 3/10/2012

Technical Specification:
Unit 1PR X 0.75mm²
Specification Reference BS EN50288-7, IEC 60332-3-22, IEC 60331-21
Conductor
- Material Plain annealed copper wire to BS EN60228
- Maximum operating temperature °C 90
- Nominal area mm² 0.8
- No. of wire / wire diameter No. / mm 7/0.37
- Shape Stranded conductor
- Nominal diameter mm 1.11
Fire proof layer Mica tape to IEC60331-21
Insulation
- Material Cross-linked polyethylene compound, XLPE
- Nominal thickness mm 0.6
- Minimum thickness mm 0.44
- Core diameter mm 2.9
- Core colour Black & White
Material of filler Not applicable
Material of binder tape Polyester (PETP) binder tape
Overall drain wire
- Material Tinned annealed copper wire
- Nominal area mm² 0.5
- No. of wire / wire diameter No. / mm 16/0.2
Overall screen
- Material Laminated Aluminium polyester (PETP) tape
- Layer x Nom. Thickness x Overlap % mm 1 x 0.026 x 30%
Bedding
- Material Low smoke halogen free compound, LSHF
- Colour Black
- Nominal thickness mm 0.9
- Minimum thickness mm 0.67
Diameter over bedding mm 7.8
Braiding
- Material Galvanized steel wire braid
- Wire diameter mm 0.30
Diameter over Braiding mm 9.0
Outer sheath
- Material Low smoke halogen free compound, LSHF
- Colour Black
- Nominal thickness mm 1.3
- Minimum thickness mm 0.84
Approximate overall diameter (±10%) mm 11.9
Approximate weight of completed cable kg/km 206
Minimum bending radius mm 119
Maximum pulling tension kgf 11

Electrical Characteristics
Maximum conductor resistance at 20°C W/km 24.5
Minimum insulation resistance at 20°C MW.km 1000
Maximum mutual capacitance at 1kHz pF/m 150
Maximum L/R ratio mH/W 25
Dielectric withstand test kV/min 2/1

Fire performance of cable


Fire resistant test (IEC60331-21): No rupture of fuses at 750°C for 90 minutes
Flame retardant test (IEC60332-3-22): Charred portion within 2.5m from ribbon burner
Flame retardant test (IEC60332-1): Distance between the lower edge of the top support and the onset of charring is greater
than 50mm

Cable Marking:
DRAKA 500V MXOLBL 1 X 2 X 0.75MM2 BS EN50288-7, IEC 60332-3-22, IEC 60331-21 YR-YYYY

Height of text: min. 3mm


Type of printing: Ink-jet printing
Line of marking: 1 line
Length Marking: Yes

Page 1 of 2
Cu/MGT/XLPE/OSCR/LSHF/SWB/LSHF 500V CABLE

Customer : Fair-Edge Industrial Supple Sdn. Bhd.


Project : TCOT Project (Top Up)
Document No : TS-FAIR EDGE-12-18
Revision : 00
Date : 3/10/2012

Technical Specification:
Unit 20PR X 1.5mm²
Specification Reference BS EN50288-7, IEC 60332-3-22, IEC 60331-21
Conductor
- Material Plain annealed copper wire to BS EN60228
- Maximum operating temperature °C 90
- Nominal area mm² 1.5
- No. of wire / wire diameter No. / mm 7/0.53
- Shape Stranded conductor
- Nominal diameter mm 1.59
Fire proof layer Mica tape to IEC60331-21
Insulation
- Material Cross-linked polyethylene compound, XLPE
- Nominal thickness mm 0.6
- Minimum thickness mm 0.44
- Core diameter mm 3.4
- Core colour Black & White with numbering (1 - 20)
Material of filler Non-hygroscopic filler
Material of binder tape Polyester (PETP) binder tape
Overall drain wire
- Material Tinned annealed copper wire
- Nominal area mm² 0.5
- No. of wire / wire diameter No. / mm 16/0.2
Overall screen
- Material Laminated Aluminium polyester (PETP) tape
- Layer x Nom. Thickness x Overlap % mm 1 x 0.026 x 30%
Bedding
- Material Low smoke halogen free compound, LSHF
- Colour Black
- Nominal thickness mm 1.8
- Minimum thickness mm 1.43
Diameter over bedding mm 33.2
Braiding
- Material Galvanized steel wire braid
- Wire diameter mm 0.40
Diameter over Braiding mm 34.8
Outer sheath
- Material Low smoke halogen free compound, LSHF
- Colour Black
- Nominal thickness mm 2.0
- Minimum thickness mm 1.40
Approximate overall diameter (±10%) mm 39.2
Approximate weight of completed cable kg/km 1991
Minimum bending radius mm 392
Maximum pulling tension kgf 420

Electrical Characteristics
Maximum conductor resistance at 20°C W/km 12.34
Minimum insulation resistance at 20°C MW.km 1000
Maximum mutual capacitance at 1kHz pF/m 150
Maximum L/R ratio mH/W 40
Dielectric withstand test kV/min 2/1

Fire performance of cable


Fire resistant test (IEC60331-21): No rupture of fuses at 750°C for 90 minutes
Flame retardant test (IEC60332-3-22): Charred portion within 2.5m from ribbon burner
Flame retardant test (IEC60332-1): Distance between the lower edge of the top support and the onset of charring is greater
than 50mm

Cable Marking:
DRAKA 500V MXOLBL 20 X 2 X 1.5MM2 BS EN50288-7, IEC 60332-3-22, IEC 60331-21 YR-YYYY

Height of text: min. 3mm


Type of printing: Ink-jet printing
Line of marking: 1 line
Length Marking: Yes

Page 2 of 2

You might also like