Cu/XLPE/LSHF/SWA/LSHF-AT-AR 600/1000V CABLE

Technical Specification:
Unit 3C X 2.5 mm²
Specification Reference IEC60502-1, IEC60332-3-22
Conductor
- Material Plain annealed copper wire to IEC60228 / BS6360
- Maximum operating temperature °C 90
- Nominal area mm² 2.5
- Conductor Class Class 2
- Shape Circular stranded
- Nominal diameter mm 1.98
Insulation
- Material Cross-linked polyethylene compound, XLPE
- Nominal thickness mm 0.7
- Minimum thickness mm 0.53
- Core diameter mm 3.4
- Core colour Red, Yellow, Blue
Material of filler Non-hygroscopic filler
Material of binder tape Not applicable
Bedding
- Material Low smoke halogen free compound, LSHF
- Colour Black
- Nominal thickness mm 1.0
- Minimum thickness mm 0.60
Diameter over bedding mm 9.3
Armouring
- Material Galvanised steel wire
- Wire diameter mm 0.9
Diameter over armour mm 11.0
Outer sheath
- Material Low smoke halogen free compound with anti-termite & anti-
rodent additives, LSHF-AT-AR
- Colour Black
- Nominal thickness mm 1.8
- Minimum thickness mm 1.24
Approximate overall diameter mm 14.8±1.0
Approximate weight of completed cable kg/km 440.3
Minimum bending radius mm 148
Maximum pulling tension kgf 52
Maximum side wall pressure to cable kgf/m 35
Maximum drum length m 2000
Drum Size mm 1300

Electrical Characteristics
Maximum conductor DC resistance at 20°C W/km 7.41
Maximum conductor AC resistance at 90°C W/km 9.448
Minimum insulation resistance at 20°C MW.km 2000
Dielectric withstand test kV/min 3.5/5

Fire performance of cable


Flame retardant test (IEC60332-3-22): Charred portion within 2.5m from ribbon burner
Flame retardant test (IEC60332-1): Distance between the lower edge of the top support and the onset of charring is greater
than 50mm

Cable Marking:
DRAKA ELECTRIC CABLE 600/1000V XLPE/LSHF/SWA/LSHF-AT-AR 3Cx2.5MM2 IEC60502-1, IEC60332-3-22 YR-
YYYY

Height of text: min. 3mm


Type of marking: Ink-Jet Printing
Line of marking: 1
Length Marking: Yes

TS-FAIR EDGE-17-08 Page 25 of 32