You are on page 1of 2

No : E17-LOC-692

TECHNICAL Issue :2
Date : 02-01-2018
SPECIFICATION Pages : 7 of 20

CONSTRUCTION
Cable Type : XLPE/OSCR/LSHF/SWB/LSHF-AT-AR
Voltage : 500V
Design Standard : BSEN 50288-7
Conductor Standard : IEC 60228, BSEN 60228
Flame Propagation : IEC 60332-3-22

CABLE DESCRIPTION:
1
2
3
4
5
6

Part Description No.


Conductor Cu Plain annealed stranded circular copper conductor, Class 2 1
Insulation XLPE Cross-linked polyethylene compound
2
Pairing / Twining Two/Three/Four insulated cores are cabled together
Assembly Multiple pairs/triads/quads are cabled together, supplied with non- 3
hygroscopic filler (optional) to obtain a circular construction and covered
with a polyester tape wrapping
Overall Screen OSCR Min. 30% overlap of aluminium backed polyester tape in contact with
0.5mm² (16/0.20mm) tinned annealed drain wire followed by a polyester
tape wrapped over the screening tape
Inner Covering LSHF Low smoke zero halogen compound. Black 4
Braiding SWB Galvanised steel wire braid 5
Outer Sheath LSHF- Low smoke zero halogen compound with anti-termite and anti-rodent
AT-AR additives. Blue 6

CABLE MARKING:
Wording DRAKA 500V XOLBL-AT-AR _ x _ x _MM2 BSEN 50288-7. IEC60332-3-22 YR-YYYY
Height of text Min. 3 mm
Type of Marking Ink-jet
Length marking Sequential length marking at 1 metre interval printed on outermost surface

CORE IDENTIFICATION:
1-pair : Black, White
Multi-pair : Black, White with pair numbering (on each core)
1-triad : Black, White, Red
Multi-triad : Black, White, Red with triad numbering (on each core)

This information contained in this data sheet is subject to normal manufacturing and internal standard practice.The data and properties may be changed as
a result of our efforts to improve the quality of our products.
No : E17-LOC-692

TECHNICAL Issue :2
Date : 02-01-2018
SPECIFICATION Pages : 8 of 20

TECHNICAL DATA TABLE

XLPE/OSCR/LSHF/SWB/LSHF-AT-AR 500V

DIMENSIONAL DATA IC IC

Voltage Unom V 500 500


Size Nominal mm2 1Px1.5 2Px1.5
Conductor Type Non Compact Non Compact
Conductor Diameter Approx mm 1.56 1.56
Insulation Thickness Minimum mm 0.44 0.44
Insulation Diameter Approx mm 2.7 2.7
Inner Covering Thickness Min.Ave mm 0.9 1
Min.Spot mm 0.67 0.76
Inner Covering Diameter Approx mm 8.0 11.5
Braid Wire Diameter Nominal mm 0.3 0.3
Diameter Over Braid Approx mm 9.0 12.5
Oversheath Thickness Min.Ave mm 1.3 1.4
Min.Spot mm 1.01 1.1
External diameter of cable Approx mm 12.0 15.5
Diameter Tolerance ±1.0 mm ±1.0 mm
Mass of cable Approx Kg/Km 181 330
Standard Length Nominal M 1600 1600
Drum Size mm 900 1200
Bending Radius Minimum mm 120 155
Pulling Tension
Eye on Conductor Maximum Kgf 21 42

ELECTRICAL DATA
DC Resistance at 20 ºC Maximum Ω/Km 12.10 12.34
Mutual capacitance at 1kHz Maximum pF/m 150 150
Insulation Resistance Minimum MΩ.Km 1000 1000
L/R Ratio Maximum μH/Ω 40 40
Conductor Operating Temperature Maximum °C 90 90
AC Voltage Test for 1 minute KV 2 2

This information contained in this data sheet is subject to normal manufacturing and internal standard practice.The data and properties may be changed as
a result of our efforts to improve the quality of our products.