Ar2 Doc 006 0004 00 Earthing Design Calc (Substation) Rev C
Ar2 Doc 006 0004 00 Earthing Design Calc (Substation) Rev C
ARAYAT-MEXICO PHASE 2
SOLAR FARM PROJECT
PHILIPPINES
EARTHING DESIGN
CALCULATION (SUBSTATION)
Approved By:
Document No: AR2-DOC-
Arayat-Mexico Phase 2 Solar Farm Project, Philippines 006-0004-00
Revision: C
Establish, as a basis for design, the safe limits of potential differences that can exist
in the Substation under fault conditions between points that can be contacted by the
human body.
Review grounding practices with special reference to safety, and develop criteria for
a safe design.
Provide a procedure for the design of practical grounding systems, based on these
criteria.
2. List of References
4. List of Tables
Document No: AR2-DOC-
Arayat-Mexico Phase 2 Solar Farm Project, Philippines 006-0004-00
Revision: C
L = 48.13 m
W= 31.44 m
A = 1,513.21 m2
ρ = 10 Ωm, 1m depth, wet organic soil (Table 8, IEEE Std.80-2000 and
Soil Data used from AR-DOC-006-004-00 EARTHING DESIGN
CALCULATION (SUBSTATION)
Amm2 = If 1
TCAP•10-4 ln K0 + Tm
tc αr ρr K0 + Ta
Where:
Amm2 = conductor cross section, mm2
If = rms fault current = 20.053 kA from AR-DOC-002-0009-00 & AR-
DOC-002-0010-00 Load Flow & Short Circuit Study
Tm = maximum allowable temperature = 1083° C
Ta = ambient temperature = 40°C
Tr = reference temperature for material constants, °C
αr = thermal coefficient of resistivity at reference temperature T r
Document No: AR2-DOC-
Arayat-Mexico Phase 2 Solar Farm Project, Philippines 006-0004-00
Revision: C
= 0.00393 1/ °C
ρr = resistivity of ground conductor at reference temperature Tr
= 1.72 µΩcm
K0 = 1/α0 or (1/αr ) – Tr = 234°C
tc = duration of fault current = 0.5 sec
TCAP = thermal capacity per unit volume = 3.72 J/cm2 °C
Amm2 = 20.053 1
= 20.053 1
0.1101 x 1.5699
= 20.053
0.41569
Where:
Etouch70 = tolerable touch voltage for human with 70kg body weight, V
Estep70 = tolerable step voltage for human with 70kg body weight, V
Cs = surface layer resistivity derating factor
Cs =1 – 0.09 (1 – ρ )
ρs
2hs + 0.09
Equation 27, IEEE Std. 80-2000
Document No: AR2-DOC-
Arayat-Mexico Phase 2 Solar Farm Project, Philippines 006-0004-00
Revision: C
Cs =1 – 0.09 (1 – 10 )
8534.4
2(0.15) + 0.09
= 1 – 0.09
0.39
Cs = 0.77
= 2,410.65V
= 8,976.50V
Rg = ρ 1 + 1 1 + 1
LT √ 20A 1 + h √20/A
Equation 52, IEEE Std. 80-2000
Document No: AR2-DOC-
Arayat-Mexico Phase 2 Solar Farm Project, Philippines 006-0004-00
Revision: C
Where:
Rg = Resistance of grounding system, Ω
Lt = Total effective length of grounding system conductor including grid &
grounds rods, m
A = total area enclosed by the ground grid, m2
h = depth of ground grid conductors, 0.5m
ρ = resistivity of soil (wet organic soil)
= 10Ωm
Rg = 10 1 + 1 1 + 1
Rg = 0.123Ω
Sf = Ig
3Io
Equation 63, IEEE Std. 80-2000
If ≈ 3Io
Sf = Ig then Ig = Sf • If
If
and
IG = Df • Ig
Equation 64, IEEE Std. 80-2000
IG = Df • Sf • If
Where:
IG = maximum grid current, A
Ig = rms symmetrical grid current, kA
Sf = fault current division factor between grounding grid & surrounding
earth = 0.5
If = rms fault current, 20.053 kA
Df = decrement factor for the entire duration of fault
for tf = 1 sec or more, Df = 1.0
IG = (1.0) (0.5) (20.053 kA)
= 10.03kA
Document No: AR2-DOC-
Arayat-Mexico Phase 2 Solar Farm Project, Philippines 006-0004-00
Revision: C
GPR = IG • Rg
Equation B.12, IEEE Std. 80-2000
= (10.03 kA) (0.123 Ω)
= 1,233.69 V
Etouch70 = 2,410.65V
Result:
GPR < Etouch70 Proceed to Step 12 Detailed Design
(Steps 8 to 10 are provided to show Mesh and Step Voltage Values)
Step 8:
Em = ρ • Km • Ki • IG
Lm
Equation 80, IEEE Std. 80-2000
Where:
Em = mesh voltage at the center of the corner mesh, V
ρ = soil resistivity = 10 Ωm
IG = maximum grid current = 10.03 kA
Lm = effective length of Lc + Lr for mesh voltage, m
Km = spacing factor for mesh voltage
Km = 1 In D2 + (D+2+h)2 - h + Kii • In 8
2π 16hd 8Dh 4d Kh π(2n –1)
Kh = √ 1 + (0.5/1) = 1.225m
Kii = corrective weighting factor that adjusts for the effects of inner
conductors on the corner mesh. For grids with ground rods along the
perimeter or with ground rods in the grid corners, Kii = 1
n = geometric factor composed of factors na, nb, nc & nd
n = na • nb • nc • nd
Equation 84 IEEE Std. 80-2000
na = 2 (Lc / Lp)
Equation 85 IEEE Std. 80-2000
nb = 1 for square grids
nc = 1 for square & rectangular grids
nd = 1 for square, rectangular & L-shaped grids
Lc = total length of the conductor in the horizontal grid = 715m
Lp = peripheral length of the grid = 159.14m
na = 2 (715) = 8.99
159.14
n = 8.99(1) (1) (1) = 8.99
Km = 1 In 62 + (6 + 2 + 0.5)2 - 0.5
2π (16) (0.5) (0.01262) 8 (6) (0.5) 4 (0.01262)
+ 1 • In 8
1.225 π (2x8.99 - 1)
= 1 (5.86 - 1.55)
2π
Km = 0.69
Lm = Lc + 1.55 + 1.22 Lr LR
√ Lx2 + Ly2
Equation 91 IEEE Std. 80-2000
For grids with ground rods in the corners, as well as along the perimeter &
throughout the grid:
Lr = length of ground rod at each location = 3m
LR = total length of ground rods, = 56x3 = 168m
√48.132 + 31.442
= 986.10m
Es = ρ • Ks • Ki • IG
Ls
Equation 92 IEEE Std. 80-2000
Where:
Es = Step voltage between a point above the outer corner of the grid and
a point 1 m diagonally outside the grid
Ks = spacing factor for step voltage
Ls = effective length of LC & LR for step voltage
Ks = 1 1 + 1 + 1 (1 – 0.5n-2)
π 2h D+h D
Equation 94 IEEE Std. 80-2000
= 1 1 + 1 + 1 (1 – 0.58.99-2)
π 2 (0.5) 6+0.5 6
Document No: AR2-DOC-
Arayat-Mexico Phase 2 Solar Farm Project, Philippines 006-0004-00
Revision: C
= 1 1 + (0.154) + (0.165)
π
Ks = 0.42
Ls = 0.75Lc + 0.85LR
Equation 93 IEEE Std. 80-2000
= 0.75 (715) + 0.85 (168)
= 679.05 m
Step 9: Em Vs Etouch70
Em = 138.26 V
Etouch70 = 2,410.65V
Em < Etouch70 ok
Es = 122.21V
Estep70 = 8,976.50V
Es < Estep70 ok
The conditions for Mesh & Step Voltage requirement have been satisfied.
A safe design has been obtained & final details can now be added to the design.
.
Document No: AR2-DOC-
Arayat-Mexico Phase 2 Solar Farm Project, Philippines 006-0004-00
Revision: C
ANNEX A
Note:
Area considered for the calculation includes Phase-1 Substation area since
the grounding conductors for Phase-1 and Phase-2 Substations are
connected.
Document No: AR2-DOC-
Arayat-Mexico Phase 2 Solar Farm Project, Philippines 006-0004-00
Revision: C
2. Soil Data
Reference Document:
AR-DOC-006-004-00 EARTHING DESIGN CALCULATION (SUBSTATION)
3. Fault Current
Reference Document:
AR-DOC-002-0009-00 & AR-DOC-002-0010-00 Load Flow & Short Circuit
Study
Document No: AR2-DOC-
Arayat-Mexico Phase 2 Solar Farm Project, Philippines 006-0004-00
Revision: C
Peripheral
Length of buried Area enclosed by
Item Length of
Location ground the grounding
No. ground
conductors, m grid, m2
conductors, m
Substation Area (48.13m x 16.94m)
1 369 82.01
(Phase-2) 815.32
ANNEX B
1. BILL OF MATERIALS
Ground 125mm2
Item Ground Well
Location Rod Ground
No. Qty
Qty Conductor
TOTAL 56 4 715