PROTECTIVE RELAYS ANALYSIS

ITEM DESCRIPTION EETC Specification ABB EETC COMMENTS

1 11 kV Switchgear

1 1 Directional over current & directional earth fault (L.V side)(11kV incoming feeder) Confirm

1 1 1 i – Manufacturer ABB
1 1 2 ii – Type reference identification:(exact relay order number) REF615

1 1 3 iii – Place of manufacture (Country-City) FINLAND

1 1 4 Fully numerical microprocessor based Confirm confirm


1 1 5 With time delay element Included Included
1 1 6 With multi C/Cs Included Included
1 1 7 Fault recorder (oscillography) function Included Included
1 1 8 Serial interface RS232 RS485
1 1 9 Could be Synchronized through GPS receiver of the event recorder confirm confirm
1 1 10 Number of DI Min. 16 16
1 1 11 Number of DO Min. 16 10
1 1 12 Self diagnosis function included included
1 1 13 Built in test facility Included included
1 1 14 Programmable LED included
1 1 15 Trip circuit supervision Included included
1 1 16 CT secondary circuit supervision Included included
1 1 17 VT secondary circuit supervision Included included
1 1 18 Can send records in COMTRADE format Confirm included
1 1 19 Non volatile memory for fault & event record Included included
1 1 21 LCD Display for IP & OP data. Included included
original software
1 2 Original Software and firmware for the relay should be provided in all relays Confirm
only

DISTRIBUTION FEEDERS Page 1 of 3


PROTECTIVE RELAYS ANALYSIS

ITEM DESCRIPTION EETC Specification ABB EETC COMMENTS

2 1 Outgoing feeder (including aux. tr. & capacitor bank)

2 1 1 i – Manufacturer ABB
2 1 2 ii – Type reference identification:(exact relay order number) REF615
2 1 3 iii – Place of manufacture (Country-City) FINLAND
2 1 4 Fully numerical microprocessor based Confirm Confirm
2 1 5 3 phase Over Current Included Included
2 1 6 Earth fault protection Included Included
2 1 7 With time delay element Included Included
2 1 8 With multi C/Cs Included Included
2 1 9 Fault recorder (oscillography) function Included Included
2 1 10 Serial interface RS232 RS485
2 1 11 Could be Synchronized through GPS receiver of the event recorder confirm confirm
2 1 12 Number of DI Min. 16 4
2 1 13 Number of DO Min. 16 6
2 1 14 Self diagnosis function included included
2 1 15 Built in test facility Included Included
2 1 16 Programmable LED Min 14 LEDs 11
2 1 17 Trip circuit supervision Included Included
2 1 18 CT secondary circuit supervision Included Included
2 1 19 VT secondary circuit supervision Included Included
2 1 20 Can send records in COMTRADE format Confirm Confirm
2 1 21 Non volatile memory for fault & event record Included Included
2 1 22 LCD Display for IP & OP data. Included Included
original software
2 1 23 Original Software and firmware for the relay should be provided in all relays Confirm
only

3 1 Bus tie

3 1 1 i – Manufacturer ABB

3 1 2 ii – Type reference identification:(exact relay order number) REF615


3 1 3 iii – Place of manufacture (Country-City) Finland
3 1 4 Fully numerical microprocessor based Confirm Confirm
3 1 5 3 phase non-directional Over current Included Included
3 1 6 With time delay element Included Included
3 1 7 With multi C/Cs Included Included
3 1 8 Could be Synchronized through GPS receiver of the event recorder confirm confirm

original software
3 1 9 Original Software and firmware for the relay should be provided in all relays Confirm
only

DISTRIBUTION FEEDERS Page 2 of 3


PROTECTIVE RELAYS ANALYSIS

ITEM DESCRIPTION EETC Specification ABB EETC COMMENTS

4 1 Under voltage relay for each section Confirm


4 1 1 I - Manufacturer: ABB
included in load
4 1 2 ii – Type reference identification:(exact relay order number)
shedding
4 1 3 iii – Place of manufacture (Country-City)
original software
4 1 4 Original Software and firmware for the relay should be provided in all relays Confirm
only

5 1 Load shedding relay:


5 1 1 Manufacturer: ABB
5 1 2 ii – Type reference identification:(exact relay order number) REF PLUS 542
5 1 3 iii – Place of manufacture (Country-City)
57/63 V …. 100/110 V,
5 1 4 Rated input voltage Vn (50 Hz) 100-125
± 10%
110 and/or 220 VDC, ±
5 1 5 Auxiliary DC voltage confirm
10%
5 1 6 Operating frequency Fn (programmable) 45 …. 55 Hz 60
5 1 7 Incremental step 0.05 Hz 0.01
5 1 8 Accuracy at 50 HZ ± 0.03 Hz
5 1 9 Minimum measuring voltage 0.25 Vn 0.2Vn
5 1 10 Operating time 0.05 sec ... 5 sec
5 1 11 Service temperature range - 5 … + 55 C
5 1 12 Relative humidity at 40̊ 90%
5 1 13 Could be Synchronized through GPS receiver of the event recorder confirm confirm
original software
5 2 Original Software and firmware for the relay should be provided in all relays Confirm
only

7 Trip circuit supervision relays for each C.B


7 1 1 i- Manufacturer:
7 1 2 ii – Type reference identification:(exact relay order number) included
7 1 3 iii – Place of manufacture (Country-City)
7 2 Original Software and firmware for the relay should be provided in all relays Confirm

8 Tripping relays for each C.B

8 1 1 i- Manufacturer:

8 1 2 ii – Type reference identification:(exact relay order number) included


8 1 3 iii – Place of manufacture (Country-City)
8 2 Original Software and firmware for the relay should be provided in all relays Confirm

DISTRIBUTION FEEDERS Page 3 of 3