110V 25A DC POWER SUPPLY SYSTEM
MODEL : NPT110-25 D
SERIAL NO : 2210884
Comments : ______________________________________________________________
______________________________________________________________
______________________________________________________________
______________________________________________________________
1-9
NIMAC POWER SYSTEMS (M) SDN BHD
110V 25A DC SYSTEM
i SCOPE
The procedure describes the methods for inspecting and checking of the
DC Power Supply System to ensure that it meets the operational requirement.
ii REFERENCE DOCUMENT
Operation and Maintenance manual.
iv TECHNICAL RECORD
Drawings.
1.1 Inspect the casing and front panel for any damages, missing or loose parts PASS/FAIL
1.2 Check for cleanliness of equipment. It should be free from dust, rust and corrosion. PASS/FAIL
1.6 Check that all identifying labels are properly fitted. PASS/FAIL
1.7 Check that the components are in accordance with the bill of material PASS/FAIL
1.9 Check the mechnical components such as bolts, nuts, cabinet construction PASS/FAIL
and gland plate for any damage.
1.10 Check that options, if any, are mounted according to specifications. PASS/FAIL
2-9
NIMAC POWER SYSTEMS (M) SDN BHD
110V 25A DC SYSTEM
CHARGER NO.1
ITEM DESCRIPTION CONDITION CRITERIA RESET SIGNAL REMARKS
2.0 SIMULATION OF
INDICATION
2.1 MAINS ON Switch on circuit breaker, 'MAINS ON' and AUTO/MAN NA PASS/FAIL
CB1
3.0 SIMULATION OF
ALARM
3.1 LED TEST Depress 'LED TEST' button All alarm LEDs lits. NA NA PASS/FAIL
3.2 CHARGER FAIL Adjust DC voltage at ' CHARGER FAIL ' LED AUTO/MAN IND/COM PASS/FAIL
card to 117.0 VDC lits at ± 1.5 % of 117.0V
(115.25V-118.76V) and the
state of remote alarm
contact will change.
RESULT: __________V
3.3 DC LOW VOLTAGE Adjust DC voltage at 'DC LOW VOLT' LED AUTO/MAN IND/COM PASS/FAIL
card to 102.6 VDC lits at ± 1.5% of 102.6V
(101.06V-104.14V) and the
state of remote alarm
contact will change.
RESULT: __________V
3.4 DC HIGH VOLTAGE Adjust DC voltage at 'DC HIGH VOLT' LED AUTO/MAN IND/COM PASS/FAIL
card to 139.5 VDC lits at ± 1.5% of 139.5V
(137.4V-141.6V) and the
state of remote alarm
contact will change.
RESULT: __________V
3.5 AC FAIL Switch off AC Mains 'AC FAIL' alarm LED lits AUTO/MAN IND/COM PASS/FAIL
or remove AC supply. and the state of remote
LED will lit only when alarm contact will change.
battery is connected.
3-9
NIMAC POWER SYSTEMS (M) SDN BHD
110V 25A DC SYSTEM
CHARGER NO.1
ITEM DESCRIPTION CONDITION CRITERIA RESET SIGNAL REMARKS
3.0 SIMULATION OF
ALARM
3.6 DC EARTH Connect a rheostat to (+ve) Alarms LED lits at leakage AUTO/MAN IND/COM PASS/FAIL
FAULT or (-ve) & ground. Adjust to current of 10mA ±0.5mA
rheostat until the leakage (9.5-10.5mA) and the state
current reading is 10mA of remote alarm contact
will change.
RESULTS:
+ve : ___________mA
-ve : ___________mA
4-9
NIMAC POWER SYSTEMS (M) SDN BHD
110V 25A DC SYSTEM
CHARGER NO.1
ITEM DESCRIPTION CONDITION CRITERIA COMMENT REMARKS
5-9
NIMAC POWER SYSTEMS (M) SDN BHD
110V 25A DC SYSTEM
CHARGER NO.2
ITEM DESCRIPTION CONDITION CRITERIA RESET SIGNAL REMARKS
2.0 SIMULATION OF
INDICATION
2.1 MAINS ON Switch on circuit breaker, 'MAINS ON' and AUTO/MAN NA PASS/FAIL
CB1
3.0 SIMULATION OF
ALARM
3.1 LED TEST Depress 'LED TEST' button All alarm LEDs lits. NA NA PASS/FAIL
3.2 CHARGER FAIL Adjust DC voltage at ' CHARGER FAIL ' LED AUTO/MAN IND/COM PASS/FAIL
card to 117.0 VDC lits at ± 1.5 % of 117.0V
(115.25V-118.76V) and the
state of remote alarm
contact will change.
RESULT: __________V
3.3 DC LOW VOLTAGE Adjust DC voltage at 'DC LOW VOLT' LED AUTO/MAN IND/COM PASS/FAIL
card to 102.6 VDC lits at ± 1.5% of 102.6V
(101.06V-104.14V) and the
state of remote alarm
contact will change.
RESULT: __________V
3.4 DC HIGH VOLTAGE Adjust DC voltage at 'DC HIGH VOLT' LED AUTO/MAN IND/COM PASS/FAIL
card to 139.5 VDC lits at ± 1.5% of 139.5V
(137.4V-141.6V) and the
state of remote alarm
contact will change.
RESULT: __________V
3.5 AC FAIL Switch off AC Mains 'AC FAIL' alarm LED lits AUTO/MAN IND/COM PASS/FAIL
or remove AC supply. and the state of remote
LED will lit only when alarm contact will change.
battery is connected.
6-9
NIMAC POWER SYSTEMS (M) SDN BHD
110V 25A DC SYSTEM
CHARGER NO.2
ITEM DESCRIPTION CONDITION CRITERIA RESET SIGNAL REMARKS
3.0 SIMULATION OF
ALARM
3.6 DC EARTH Connect a rheostat to (+ve) Alarms LED lits at leakage AUTO/MAN IND/COM PASS/FAIL
FAULT or (-ve) & ground. Adjust to current of 10mA ±0.5mA
rheostat until the leakage (9.5-10.5mA) and the state
current reading is 10mA of remote alarm contact
will change.
RESULTS:
+ve : ___________mA
-ve : ___________mA
7-9
NIMAC POWER SYSTEMS (M) SDN BHD
110V 25A DC SYSTEM
CHARGER NO.2
ITEM DESCRIPTION CONDITION CRITERIA COMMENT REMARKS
8-9
NIMAC POWER SYSTEMS (M) SDN BHD
110V 25A DC SYSTEM
9.0 BOOST INTERLOCKING a. i) Switch off Charger Charger No. 2 disable PASS/FAIL
SYSTEM TEST No.1 followed by from manual boost
activating Charger 2
to Manual boost
mode.
9-9