Protocol No.:
Equipment ID: AHU-06 Performance verification of
AHU06-IOQ-ANEX6-00
Blower Motor
Mansoor Daya Chemicals Limited
Objective: To verify the performance of blower & motor as per specified limit
Acceptance Criteria: Result should meet the acceptance criteria.
.
Supply Blower motor
Description. Specified Method of Acceptance Result
Testing Criteria
Speed (RPM) 4716 Check by using RPM shall be ± 4720 RPM
As specified on calibrated 5% than
motor label. tachometer specified
Current drawn Check by using The current 5.7A
6A calibrated clamp drawn shall be
As specified on meter less than the
motor label. rated amperage
Works Perfect
IOQ-ANEX6 Page 1 of 1