Protocol No.:
Equipment ID: AHU-06 Performance verification of
AHU06-IOQ-ANEX6-00
Blower Motor
Mansoor Daya Chemicals Limited
Objective: To verify the performance of blower & motor as per specified limit
Acceptance Criteria: Result should meet the acceptance criteria.
.
Supply Blower motor
Description. Specified Method of Acceptance Result
Testing Criteria
Speed (RPM) 4716 Check by using RPM shall be ± 4720 RPM
As specified on calibrated 5% than
motor label. tachometer specified
Current drawn Check by using The current 5.7A
6A calibrated clamp drawn shall be
As specified on meter less than the
motor label. rated amperage

Voltage 400/450V Checked by using Voltage shall be 330V


As specified on calibrated clamp ± 5%
motor label. meter
Direction of As per arrow mark Visual For Information Clockwise
rotation pasted on the observation only
motor casting

Exhaust Blower motor


Description. Specified Method of Acceptance Result
Testing Criteria
Speed (RPM) 3407 Check by using RPM shall be ± 3456RPM
As specified on calibrated 5% than
motor label. tachometer specified
Current drawn 3.4A Check by using The current 3.13A
calibrated clamp drawn shall be
As specified on meter less than the
motor label. rated amperage

Voltage 400/450V Checked by using Voltage shall be 320V


As specified on calibrated clamp ± 5%
motor label. meter
Direction of As per arrow mark Visual For Information Clockwise
rotation pasted on the observation only
motor casting

Remarks / Deviation(s), if any:

Works Perfect

Checked By / Date: Verified By / Date: