Professional Documents
Culture Documents
In the evaporative cooling method (state change of water from liquid to gas),
heat energy is absorbed from the air by the water (this energy is known as
latent heat of vaporization). Therefore, the process of evaporative cooling
increases both absolute and relative humidity and decreases air temperature.
As long as the RH of the greenhouse air is less than saturation point, air
movements by fans in an evaporative cooler transfer water molecules into the
air, causing the water in the evaporative cooling system to lose temperature
and cooled down until equilibrium is reached. At this point, the amount of heat
removed by the evaporating water will be supplied by the air. Water
evaporation in the greenhouse continues until it saturates the air. Therefore,
the potential of cooling by evaporative method depends on the RH of the air and
the efficiency of the evaporative system itself.
Example 1: Moist air enters a farrowing house at 34F db and 60% RH,
replacing air removed from space by an exhaust fan. If air leaves at
2700cfm, 68F db, and 65% RH, how much latent heat and sensible heat
are added per hour to the air inside the building?
Solution:
(Approximate answer)
where
is the sensible heat flow,
is the specific heat equal to 0.2388
is the air density at standard condition, equal to 0.075
is the measured air flow
is the temperature difference, equal to
(Approximate answer)
where
is the latent heat flow,
is the latent heat of vaporization and is equal to 1060
is the air density at standard condition, equal to 0.075
is the measured air flow
is the humidity ratio difference. It is the
difference in water content of air between first and 2 nd measurement
location.
( )
is the saturation pressure of the air stream at the dew point
temperature
is the saturation pressure of the air stream at ambient temperature
is humidity expressed as a value between 0 and 1, not as %RH
From thermodynamic table, the following values are extracted and calculated:
( )
( )
…(Exact answer)
Solution:
7. RH of the mixture:
Using Psychrometric chart at the temperature of the air mixture and the
corresponding moisture content, the RH of the mixture can be found at 47%.
( )
{
A schematic design based on the concept of mixing two volumes of moist air
with different levels of relative humidity is shown in fig. 11. Air conditioners are
usually designed to create 40% to 60% relative humidity. Assuming two equal
mass ( ̇ ̇ ̇ ) and same temperature ( ) flow of moist
air with 85% relative humidity of the outside environment and 50% relative
humidity at the outlet of air conditioner, writing mass conservation equation for
this systems yields the expressions in (16). Based on this analysis, relative
humidity of the mixed air will be equal to 67% with temperature equal to .
The thermodynamic values for this system are given in Table 8.
̇ ̇ ̇
̇ ̇ ̇
̇ ̇ ̇
(16)
̇ ̇ ̇
̇
̇
Figure 3. Mixing two volumes of moist air with different levels of relative humidity
50 %
85 %
67 %
The greater the difference between the wet bulb and dry bulb
temperatures, the greater the achievable temperature reduction. Here’s how to
calculate temperature reductions achievable with direct, indirect,
indirect/direct, and indirect/indirect evaporative cooling. These examples use a
starting dry bulb (DB) temperature of 86 degrees F and wet bulb (WB)
temperature of 66 degrees F.
With direct evaporative cooling, the dry bulb temperature is reduced while
the web bulb temperature remains the same.
1. Temp drop achievable = (dry bulb - wet bulb ) x (efficiency* of the media)
Example: (86 degrees - 66 degrees) x .9 = 18 degrees
2. Achievable temp = dry bulb - temp drop achievable
Example: 86 degrees - 18 degrees = 68 degrees DB/66 degrees WB**
3. Starting DB: 86 degrees
Ending DB: 68 degrees
*Efficiency is usually 90%
Because cooling is achieved by adding moisture to the supply air stream, the
new dry bulb/web bulb temperatures are found on the wet bulb gradient.
Appendix A
Psychrometric Chart
With direct evaporative cooling, the dry bulb temperature is reduced while
the web bulb temperature remains constant.
1. Start with the dry bulb (DB) and wet bulb (WB) design conditions for the
location you are interested in. For example, Portland’s 1% design conditions
are 86 degrees DB and 66 degrees WB.
2. Find where 86 degrees on the dry bulb line intersects with 66 degrees on the
wet bulb line (see Figure 2). That is the starting point.
Because cooling is achieved by adding moisture to the supply air stream, the
new dry bulb/wet bulb temperatures are found on the wet bulb gradient.
References:
Schnelle, M.A., Cole, J.C., Dole, J.M. 2003. Mist Propagation Systems and Humidity
Chambers for the Nursery and Greenhouse. Oklahoma Cooperative Extension
Service- F-6708. Oklahoma State University. Stillwater, OK.
Giacomelli, A., William, J.R. 1993. Greenhouse covering systems. HortTechnology 3,50-58.
Duan, Z., Zhan, C., Zhang, X., Mustafa, M., Zhao, X., Alimohammadisagvand, B., Hasan, A.
2012. Indirect evaporative cooling: Past, present and future potentials.
Renewable and Sustainable Energy Reviews 16, 6823-6850.