Professional Documents
Culture Documents
The common Psychometric processes which are usually encountered in practice and which
may be easily solved with the help of a psychometric chart are given below and are
indicated in Fig. 37.6.
This process involves cooling of air at constant moisture content. Process 1-2 is a horizontal
line from right to left. Evidently, such cooling of air has to be carried on by bringing it into
contact with a body or a surface temperature of which is not below the dew point
temperature of air at 1.
Heat removed = h -h kJ/kg of dry air.
2 1
Generally all the air passing through the air duct or flow passage does come in contact with
the coil surface and the temperature of the air coming out of the passage is not the
temperature of the coil surface. With reference to Fig. 37.6 (a), let t be the temperature of
c
the coil surface. Some of the air bypasses the coil surface and this bypassed air at t mixes
1
with the other part of air at temperature t and the final temperature of the mixture is, say, t .
c 2
The ratio of the bypassed air to the total air is called the bypass factor (BF).
Given the bypass factor and the coil surface temperature, actual temperature of air can be
found by using the equation.
(b) Sensible Heating Process:
This process involves of heating of air without the change of humidity or humidity content.
Heating process line is a straight line from left to right Fig. 37.6 (b)
Heat supplied/kg of air = h – h kJ/kg dry air.
2 1
Pure or simple humidification and dehumidification processes are not found in practice and
are always accompanied by heating and cooling.
These processes have practical applications in summer air conditioning. Since the actual
process is difficult to trace on the chart, only end states are shown distinctly and joined by
dotted curve. But possible processes can be shown as – (1-2) is the sensible cooling up to
the dew point temperature and then cooling of air below dew point temperature as shown by
(2-3). t is the coil surface temperature and if the coil is having a bypass factor then the
3
actual state of air may be given by point (4). t is the apparatus dew point temperature ADP
3
This process is carried on by blowing the air through an air washer spraying hot water. The
process has practical application in winter air conditioning. During this process (i) specific
humidity, dry bulb temperature, wet bulb temperature, dew point temperature and enthalpy
increase and (ii) RH may increase or decrease.
The final state 2 of the air may also be achieved by a combination of sensible heating 1-3
and then by sensible humidification process 3-2.
Heating and humidification can also be achieved by injecting into air, the steam. This
process is generally used in textile industry where high humidity is to be maintained. Rise in
dry bulb temperature is generally very little. Instead of hot water, steam will be injected.
(c) Heating and Dehumidification Process:
There are certain chemical substances like silica gel and activated alumina which have an
affinity for moisture. If air is passed over such chemicals it may be dehumidified. Usually in
doing so the moisture is condensed and gives up its latent heat, raising the dry bulb
temperature of air.
This process is reverse of adiabatic saturation process.
This is shown in Fig. 37.6(g). In figure, 1-2 adiabatic saturation process 1-3 adiabatic
dehumidification process.
The path followed during this (adiabatic dehumidification) process is along the constant wet
bulb temperature line or constant enthalpy line.
Actually there are two types of chemicals used for chemical dehumification.
They are:
1. Absorbents:
They include water solutions or brines of calcium chloride, lithium chloride, lithium bromide
and ethylene glycol. Generally these are used in absorption refrigeration systems.
2. Adsorbents:
These are the substances in solid state and while absorbing moisture from air, they do not
change chemically and physically. These are silica gel and activate alumina (porous
amorphous form of aluminium dioxide).
(d) Cooling and Humidification (Adiabatic Humidification):
This process is explained in Sec. 37.2.9 and is a constant wet bulb temperature process. Air
passing through a spray chamber with re-circulated water follows the process line 1-2 in
Fig. 37.6(g). Whereby it cools due to the evaporation of water. Such cooling of air shown
schematically in Fig. 37.6(h), will accompany humidification following only one path i.e.,
constant wet-bulb temperature line.
This principle is made use of in desert coolers for cooling buildings in hot and dry climate so
as to make them comfortable. Since the cooling cannot be achieved below the wet bulb
temperature of the outside or incoming air, at which temperature the leaving air will be
saturated, this technique of cooling has only limited use. Hence the system becomes
ineffective in monsoon season.
Perfect humidification of air is not possible in actual practice due to inefficiency of spray
chamber. Therefore, the final condition of air at outlet is represented by state 3 on the line
1-2 as shown in Fig. 37.6(i). The effectiveness or the humidifying efficiency of the spray
chamber is given by-
h respectively, mix together without any heat exchange with surroundings and also
2
enthalpy h = h – h .
3 1 2
The final condition of the mixture can be found with the help of chart as follows:
First determine the percentage of air in each stream, in the mixture. Let in stream one, this
is x%. Therefore, (100 – x) is the percentage of air mass in other stream.
Then locate the two points 1 and 2 from the given conditions of two streams. Join 1 and 2.
Next step is very important. Multiply the dry bulb temperature of each air by its percentage
in the mixture. Let this be x.t . This is the contribution of stream (1) DB degrees to the
1
mixture. Similarly for second stream (100 -x) t will be DB degrees contributing in the
2
mixture.
x t + (100 – x) t = 100 x t
1 2 3
t can be found.
3
Draw a vertical at t to meet the line 1-2 in 3. Then all other properties can be found from the
3
chart.