Professional Documents
Culture Documents
Psychometric process
In the design and analysis of air conditioning plants, the fundamental requirement is to identify
the various processes being performed on air. All these processes can be plotted easily on a
psychrometric chart. This is very useful for quick visualization and also for identifying the
changes taking place in important properties such as temperature, humidity ratio, enthalpy etc.
The important processes that air undergoes in a typical air conditioning plant are discussed below
Sensible Heat Load
QS = ma cpa ∆T
Latent Heat Load
QL = ma × hfg × Δω = ma × Δh
1. Sensible heating (1-2)
2. Sensible cooling (1-3)
3. Humidification (1-4)
4. Dehumidification (1-5)
5. Heating and humidification (1-6)
6. Cooling and dehumidification (1-7)
7. Cooling and humidification (1-8)
8. Heating and dehumidification (1-9)
The graphs shows the psychrometer processes
Moist Air Sensible Cooling
During this process, the moisture content of air remains constant but its temperature decreases
as it flows over a cooling coil. For moisture content to remain constant, the surface of the
cooling coil should be dry and its surface temperature should be greater than the dew point
temperature of air. If the cooling coil is 100% effective, then the exit temperature of air will be
equal to the coil temperature. However, in practice, the exit air temperature will be higher than
the cooling coil temperature.
Qsens = ṁ cp ΔT = ṁ Δh = ṁ (hO - hA)
tA < tO hA< hO O< A
ωO = ωA tdp = C
Adiabatic mixing
m3 = m1 + m2
Conservation of water vapor masses
m1 ω1 + m2 ω2 = m3 ω3 = (m1 + m2) ω3
m3 = m1 + m2
m1 ω1 + m2 ω2 = (m1 + m2) ω3
m11 m 2 2
3
m1 m 2
t db 3 m 3 m1 t db1 m 2 t db 2
m3 = m1 + m2
m1t db1 m2 t db 2
t db3
m1 m2
Conservation of energy
m1h1 m2 h2
h3
m1 m2
Example 2-3
3kg of air at tdb = 50oC and twb = 32oC, is mixed adiabatically with 2kg of air at tdb = 5oC and
twb = 5oC, find the enthalpy, specific humidity and the DBT of the mixture.
Solution
From pschromtric chart, define the conditions of state 1 and 2
by means of dry bulb temperature and wet bulb temperature
m1t db1 m2 t db 2
t db3
m1 m2
= (3×50 + 2×5) / (2 + 3) = 32 °C
Sensible heat hx h1
The room sensible heat ratio
Total heat h2 h1
Assume the mass of air leaving the mixing box is unity, and the fraction of the recirculate air is
x, therefore;
m4h4 = m2h2 + m3h3
x h2 + (1 - x) h3 = 1 × h4 x h2 + h3 – x h3 = h4 x (h2 – h3) = h4 – h3
h4 h3
x =
h2 h3
m3 ω3 + m2 ω2 = m4 ω4
4 3
x=
2 3
h4 h3 4 3
x= =
h2 h3 2 3
Winter air conditioning
In winter air conditioning, the air is heated, which is generally accompanied by humidification.
In winter, the outside conditions are cold and dry. As a result, there will be a continuous
transfer of sensible heat as well as moisture (latent heat) from the buildings to the outside
Example 2-6
An air conditioned room is to be maintained at 18oC and percentage saturation 40%. The fabric heat
gains are 3000 W and there are a maximum of 20 persons in the room at any time. Neglecting all other
heat gains or losses calculate the required volume flow rate of air to be supplied to the room and its
percentage saturation when the air supply temperature is 10oC. Sensible heat gains per person = 100W,
latent heat gains per person = 30W. Take the parametric pressure = 1.01325bar.
Solution
The process is heating from 10oC (supply temperature) to 18oC (design state), the process is
shown on the following figure. Point 2 represents the design state, while the point 1 shows the
supply air.
The total sensible heat = 3000 + (20 × 100) = 5000W
Latent heat = 20 × 30 = 600 W
The volume flow rate of air to be supplied (m3/s) = ma1 × νa1
Ψ = (ω2 / ωg) and
pg
ω2 = 0.622
pa
pa = 1.01325 – 0.02063 = 0.99262 bar
ωg = 0.622 (0.02063 / 0.99262)
ωg = 0.0129273 ω2 = 0.0129273 × Ψ = 0.0129273 × 0.4 = 0.005171 ω2 = 0.005171
This problem can be solved very quickly, if less accuracy, using the Psychrometric chart. Point 2 can
be located on the chart from the information given, and then we have
tdb3 tdb2 t t
PF , and heating efficiency = HC db2 db1
tdb3 tdb1 tdb3 tdb1
t db1 DB Temperature of the air entering the cooling coil
t db2 DB Temperature of the air leaving the cooling coil
t db3 DB Temperature of the cooling coil surface
t db2 t db3 t t
PF , and the cooling efficiency = CC db1 db2
t db1 t db3 t db1 t db3
Example 2-7
It is required to design an air-conditioning plant for a small office room for following winter
conditions :
Outdoor conditions are12ºC DBT and 10ºC WBT
Required conditions are 20ºC DBT and 60% R.H.
Amount of air circulation is 0.30 m3/min./person. Seating capacity of office are60.
The required condition is achieved first by heating and then by adiabatic humidifying.
Determine the following :
1- Heating capacity of the coil in kW and the surface temperature required if the bypass
factor of coil is 0.4.
2- The capacity of the humidifier. Solve the problem by using psychrometric chart.
Solution
Refer to the following chart, locate point 1 outdoor conditions are(12ºC DBT and 10ºC WBT)
and point 3 indoor conditions (20ºC DBT and 60% R.H). From point 1 draw a constant
specific humidity (heating)., from 3 draw a constant enthalpy line (adiabatic humidity) to
intersect the line from 1. Point 3 represent the properties of air leaving the heating coil and
entering the adiabatic humidity
From the psychrometric chart:
h1 = 29.3 kJ/kg, h2 = h3 = 42.3 kJ/kg, tdb2 = 24.5ºC,
vs1 = 0.817 m3/kg
The mass of air circulated per minute:-
V 0.3 60
m 22.03kg/min
v1 0.817
1- Heating capacity of the heating coil = ma (h2 – h1) = 22.03 (42.3 – 29.3)
= 286.4 kJ/min = 4.77 kJ/s or 4.77kW
t db 2 t db 2
The by-pass factor (BF) of heating coil is given by
t db 2 t db1
t db 2 24.5
0.4 , 0.4 ( t db 2 12 ) = tdb 2 24.5
t db 2 12
o
t db 2 (Coil surface temperature) = 32.8 C
2- The capacity of the humidifier = m( 3 1 )
HC 2.379kg / hr
Example 2-8 (Using Steam table)
120m3 of air per minute at 35°C DBT and 50% relative humidity is cooled to 20°C DBT by
passing through a cooling coil. Determine the following :
(i) Relative humidity of out coming air and its wet bulb temperature.
(ii) Capacity of cooling coil in tonnes of refrigeration.
(iii) Amount of water vapour removed per hour.
Solution
For the air at 35°C DBT and 50% R.H. :
ps
psat = 0.0563 bar (At 35ºC, from steam tables),
pg
ps = φ × psat = 0.5 × 0.0563 = 0.02815 bar.
h1 c p t db1 1 hg1 1.88 t db1 t dp1
The dew point of the outdoor temperature (psat = ps), therefore from steam table and at
psat=0.02815bar, tdp1 = 23oC, hg at 35oC = 2565.3kJ/kg, therefore
h1 1.005 35 0.01772565.3 1.8835 23 80.98kJ / kg DA
For the air at 20°C. As the saturation vapour pressure at 20ºC is 0.02337bar, less than the
vapour pressure 0.02815bar at 35ºC, so that condensation takes place and air will be saturated
at 20°C.
(i) Relative humidity of exit air is 100 per cent. (Ans.). Since the air is saturated, wet bulb
temperature is equal to dry bulb temperature = 20°C. (Ans.)
0.622 p g 0.622 0.02337
2 g 0.0147kg / kg DA
p pg 1.013 0.02337
h2 c p t db 2 2 h g 2 1.88 t db 2 t dp 2 , t db t dp Saturated
0.00434
Spray water = 0.005124 kg/m 3
0.847
(ii) Temperature to which the air must be heated tdb2 : Now
h2 + (ω3 – ω2) h4 = h3
From the steam tables at 22oC, psat = 0.01452 bar : hg = 2524 kJ/kg and tdp = tsat = 12.5ºC
1.005(22 – tdb2 ) + 0.00904[2524 + 1.88(22 – 12.5)] – 0.0047 [2524 + 1.88( tdb2 – 12.5)] – (0.00434 ×
4.187 × 10) = 0
∴ tdb2 = 32.7ºC
Example 2-10
Air at 10oC and 90% R.H, the air is heated, humidified and reheated to 35oC DBT and 22.5oC
WBT, before the air is reheated sensibly to final conditions and after adiabatic humidification
the RH is 90%. Find :-
1- The temperature of air leaving the heating process.
2- The heat required for heating processes.
3- The quantity of water required in the humidifier
5- Humidification efficiency.
Solution
First, the initial state (1) and final state (4) are fixed in psychrometric chart. The properties of
air leaving the heater are unknown, so a line is drawn horizontally (sensible) from initial state in
the direction of temperature increase. From final state a line is drawn horizontally (Reheating
process) towards 90% RH to fix the conditions of air leaving the humidifier and before reheated
(3). Since the humidification is adiabatically, a line of constant enthalpy is drawn from the
conditions of the air leaving humidifier to define the conditions of air leaving the heating coil
(2). The processes are located on psychometric, chart shown in the figure below.
From Chart:-
1- The temperature of air leaving the heating process (tdb3 = 31.5oC)
2- The heat required for heating processes QH = (h2 - h1) + (h4 - h3)
h3 h2 (Adiabatic humidification)
QH h4 h1
From chart h4 = 67kJ/kg and h1 = 27kJ/kg
Q H 67 27 50kJ / kg
4- From 3 draw a horizontal line towards temperature decrease to represent the sensible cooling
process (cooling coil) till the temp. of air equal 15oC. The conditioning air processes is shown in the
chart below.
From chart the cooling coil surface temperature tdb 4 is equal 11.5oC.
t db 4 t db 4 15 11.5
1- Cooling coil bypass factor = 0.175
t db3 t db 4 31.5 11.5
A meeting room is to be maintained at 22oC DBT and 70% RH, the outdoor conditions are 30oC DBT
and 75% RH. The volume of air circulated in the room is 200m3/min. The conditioning air is obtained
using cooling coil (cooling and dehumidifying) has 14oC surface temperature, then the air is passed
through heating coil. Find:-
1- Cooling coil capacity, and bypass factor.
2- The amount of water removed from the air by dehumidifier.
3- Heating coil capacity and its surface temperature if the efficiency is 0.8.
Solution
1- Locate the room and outdoor conditions, (22oC DBT and 70% RH) and (30oC DBT and 75% RH)
respectively.
2- From outdoor conditions draw a line towards the cooling coil surface temp (14oC). The properties
of air leaving the cooling coil is unknown.
3- From indoor conditions draw a horizontal line (heating process) to cross with the line of cooling
coil process.
4- The intersection will define the properties of air leaving the cooling coil and enters the heating coil.
The conditioning processes is shown in the chart
1- Cooling coil capacity (CCC) = ṁ (h2 – h1)
From chart h1 = 82kJ/kg, h2 = 41kJ/kg, and v1 0.8625m 3 / kg
V 200
m 3.86kg / s CCC 3.8641 82 158.26kW (-ve)
v1 60 0.8625
Removing heat
CCC 158.26kW
t db 2 t db 2 16.4 14
Cooling coil bypass factor = 0.15
t db1 t db 2 30 14