You are on page 1of 17

Refrigeration and Air Conditioning

(ME 439)
Instructor Dr. Muhammad Asif

Lecture 8

Moist Air properties and Conditioning Processes


(Chapter 3)

Faculty of Mechanical Engineering, GIK Institute of Engineering Sciences and Technology


https://giki.edu.pk/personnel/dr-muhammad-asif/
AIR-CONDITIONING PROCESSES

- simple heating (raising the temperature)


- simple cooling (lowering the temperature)
- humidifying (adding moisture)
- dehumidifying (removing moisture).
Combination of above
- Cooling and Humidification
- Cooling and dehumidification
- Heating and humidification

2
Simple Heating and Cooling ( = constant)

During simple heating, specific humidity


remains constant, but relative humidity
decreases.

During simple cooling, specific humidity


remains constant, but relative humidity
increases.

Dry air mass balance


Water mass balance
Energy balance
3
By-pass Factor of Heating and cooling Coil
coil cannot cool/heat all of the air passing through it to the coil surface
temperature.
Energy Balance (heating coil)

Energy Balance (cooling coil)

Efficiency of Heating and Cooling Coil


The term (1-BPF) is known as efficiency of coil or contact
factor
(heating coil)

(cooling coil) 4
HUMIDIFICATION/DEHUMIDIFICATION

When the state of air is altered along t= constant


moisture in the form of vapour has to be transferred to
change in humidity ratio of air

5
Heating with Humidification
- Winter Application ; cooling towers

6
Sensible Heat factor
The ratio of the sensible heat to the total heat is known as sensible heat factor SHF

𝑆𝑒𝑛𝑠𝑖𝑏𝑙𝑒h𝑒𝑎𝑡 𝑆𝐻
𝑆𝐻𝐹 = =
𝑇𝑜𝑡𝑎𝑙 h𝑒𝑎𝑡 𝑆𝐻 + 𝐿𝐻

7
Cooling with Dehumidification
- Summer application

8
Adiabatic Mixing of Airstreams
Many A-C applications require the mixing of two airstreams.
This is particularly true for large buildings, most production and
process plants, and hospitals, which require that the
conditioned air be mixed with a certain fraction of fresh outside
air before it is routed into the living space.

When two airstreams at states 1 and 2 are mixed


adiabatically, the state of the mixture lies on the straight
line connecting the two states.

9
Cooling and humidification (Evaporative cooling)

Mass balance

Energy balance

10
EXAMPLE 1
Consider a single duct, single zone, constant speed air handling unit
in which 39.6 m3/min mixture of outdoor air and recirculated room air
at 31℃ dbt and 18.5℃ wbt enters a cooling coil. The effective
surface temperature of the coil is 4.4 ℃. The surface area of the coil
is such as would give 12.5 kW of refrigeration with the given
entering air state. Determine the dbt and wbt of the air leaving the
coil and the by-pass factor.

11
First of all mark initial state of the moist air,
Then the effective surface temperature (ADP) of the coil at 4.4℃

Now point 2 can be located on the chart

Capacity of cooling coil

12
EXAMPLE 2
Consider a room is to be maintained at 22℃, 55% RH. Outside saturated air at
3℃ is first heated and then water at 10℃ is sprayed to get the required humidity.
Calculate
1. Required mass of sprayed water per m3 of air
2. The temperature to which the air must be heated

22 C
13
At point 3 (22℃, 55% RH) W3 = 0.00904 kg/kg of dry air

At point 1 (3℃, 100% RH), W1 = 0.0047 kg/kg of dry air =W2

W3-W1= 0.00434 kg/kg of dry air

2. Temperature to which the air must be heated

Energy balance between (2-3) Or through steam table


h3 = 45 kJ/kg of dry air

hw= 2519.1 kJ/kg

h2= 36 kJ/kg of dry air

14
EXAMPLE 3
You are required to design an air conditioning plant for the LH-1 of FME, in which
seating capacity is 60 students. Let say the weather condition is now a days (winter
season) and assume for a particular day the outdoor conditions are measured with a sling
thermometer that shows 12℃ dbt, 10 ℃ WBT and 1 atm pressure. The required
conditions in the classroom are 20℃, 60% RH, and air circulation of 0.3 m3/min/person
(from ASHREA handbook). The required conditions in the classrooms are achieved by
first heating and then adiabatic humidification.
Calculate
a. Required heating capacity of the coil and surface temperature of the coil if the bypass
factor of coil is 0.4.
b. Capacity of the humidifier

15
16
Practice following exercise Problem
3-6, 3-7, 3-16, 3-24, 3-43

17

You might also like