Psychrometric Process

The change of state of moist air is called a psychrometric process. Such a


process may involve one or combination of the following process.
 Cooling
 Heating
 Dehumidifying
 Humidifying

 Summer Air Conditioning- involves of cooling and dehumidifying


 Winter Air conditioning- involves heating and humidifying.

1
Adiabatic
Adiabatic saturation process humidification

(desert cooler or adiabatic


humidification)

2
Adiabatic humidification

3
The inlet condition of air through a washer is 40%RH
and 40 degree C. Out let condition of air is 80% RH
and 29 degree C. Find moisture added per Kg of air ?

4
5
Form chart
Moisture added per Kg of dry air is= (w2-w1)
 = (0.0205-0.019)
 = 0.0015KJ/ Kg of dry air

6
Basic process in Conditioning of Air
`

7 Manoj PJ Associate professor(MECH)


Sensible heating and Sensible cooling
Heating or cooling of air without addition or
subtraction of moisture is termed as sensible heating or
cooling.
Or
Heating or cooling with out phase change .

8
9
10
By pass factor.

Bypass factor represents the fraction of uncontacted air


in terms of the states 1, 2, 3.

11
B*Cp*T1 +(1 – B)Cp*T2 = 1*Cp* T3
B= (T3-T2)/(T1-T2)
Or
B*h1 +(1 –B)h2 = 1*h3 h = specific enthalpy
C = humid specific heat
B= (h3-h2)/(h1-h2) B = kg of air

12
Also in heating

13
14
Chemical Dehumidification
Example –silica gel

15
Humidification by steam injection.

16
`

17 Manoj PJ Associate professor(MECH)