These valves are designed to meet the needs of HVAC and commercial
applications requiring bubble tight shut-off for liquids. Typical applications
include chiller isolation, cooling tower isolation, change-over systems, large
air handler coil control, bypass and process control applications. The large
Cv values provide for an economical control valve solution for larger flow
applications.
Jobsite Note
Valve assembly should be stored in a weather protected area prior to
installation. Reference the butterfly valve installation instruction for additional
information.
Flow/Cv
Cv 10° Cv 20° Cv 30° Cv 40° Cv 50° Cv 60° Cv 70° Cv 80° Cv 90°
0.2 9 18 39 70 116 183 275 302
Suitable Actuators
Non-Spring
F780HDU GMB(X)
E
Number of Bolt Holes 4
Lug threads 5/8-11 UNC
Close-off pressure ∆ps 50 psi F
B
Rangeability Sv 10:1 (for 30° to 70° range)
Maximum Velocity 12 FPS
Cv 302 A B C D E F
Weight 50.71 lb [23 kg] 13.8” [350] 11.2” [284] 17.0” [433] 13.1” [334] 7.4” [187] 5.5” [140]
Media Temp Range (water) -22...250°F [-30...120°C]
Leakage rate 0%
Maintenance maintenance-free Safety Notes
WARNING: For Belimo products sold in California: these products do or may
contain chemicals which are known to the State of California to cause cancer
and or birth defects or other reproductive harms. For more information see
www.p65warnings.ca.gov.
D
C
F
B
GMX24-X1
A B C D E F
15.6” [396] 11.2” [284] 19.2” [487] 15.4” [391] 7.4” [187] 5.5” [140]
Wiring Diagrams
24 VAC Transformer
INSTALLATION NOTES A 1 3 46 47
A Actuators with appliance cables are numbered. Line Blk (1) Common
Provide overload protection and disconnect as required. Volts Red (2) + Hot
Only connect common to negative (-) leg of control circuits. Position (–) Pnk (4) Y Input
2
Feedback VDC (+) Org (5) U Output
A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2
to 10 VDC.
On/Off
Control signal may be pulsed from either the Hot (Source) or Common
(Sink) 24 VAC line.
For triac sink the Common connection from the actuator must be 24 VAC Transformer (AC Only) 1 10 46 47
connected to the Hot connection of the controller. Position feedback
cannot be used with a triac sink controller; the actuator internal Line Blk (1) Common
common reference is not compatible. Volts Red (2) + Hot
IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number
Wht (3) Y1 Input
40155).
Actuators may be controlled in parallel. Current draw and input Pnk (4) Y2 Input
46 Position (–)
impedance must be observed.
Feedback VDC (+) Org (5) U Output
Master-Slave wiring required for piggy-back applications. Feedback
47
from Master to control input(s) of Slave(s). Floating Point
Meets cULus requirements without the need of an electrical ground
connection. 24 VAC Transformer A 1 3 5 46 47
! WARNING! LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing and troubleshooting of this Line Blk (1) Common
product, it may be necessary to work with live electrical components. Volts Red (2) + Hot
Have a qualified licensed electrician or other individual who has been
properly trained in handling live electrical components perform these Ω 500 Ω
1/4 watt
tasks. Failure to follow all electrical safety precautions when exposed to Control Signal (–)
live electrical components could result in death or serious injury. VDC / mA (+) Wht (3) Y Input
VDC/mA Control
Position (–)
Pnk (4) Y2 Input
Feedback VDC (+) Org (5) U Output
PWM Control
Override Control
Slave
1
Blk (1) Common
Red (2) + Hot
Master - Slave
Date created, 05/15/2019 - Subject to change. © Belimo Aircontrols (USA), Inc.