Diso Opus Operational Procedure with Parameter List.

Press down Arrow Key (↓),



Press Right arrow key (→) 3 times,

System shown 4: SETUP,

Press down arrow key (↓),

System Shown 41: Password,

Press Enter key & Type 505442 (Password),

After type aforesaid Password Press Enter key

Press (→) right arrow key 3 times,

System shown 44: SCALE,

Press down arrow key (↓),

System Shown 441: Calibration Para,

Press enter key

Unit t

Press enter key

Acct. diam. (i.e. Bin capacity) 60.000

Press enter key

Digit increment 0.010

Press enter key

Setting diff. 4d

Press enter key

Zeroing Range 10%

Press enter key

1

Over range 110%

Press enter key

Mech. Factor 3.000

Press enter key

Adjustment factor 1.000

Press enter key

Related capacity 22000Kg

Press enter key

No. of L/C 1

Press enter key

L/C –C (mv/v) 2.85

Press enter key

Deadweight 6.230t (Automatically calculate, manually not possible)

Press enter key

L.f.t. NO

Press OK Key

After few seconds again press OK Key and system return back from parameter
section.
And System showed 441: Calibration para.


Then press (→) right arrow key 4 times & System shown 445: CALIBRATION

Press down arrow key (↓),

System shown 4451: Deadweight

Press enter key

2

System Bin’s Taring job automatically done and send to Deadweight data in 441:
Calibration para Dead weight section.


Press Right arrow key (→) 2 times,

System shown 4453: Range

Press enter key

Then Put the Actual Value of Known weights by manually type through keypad in
Range Block, then Press Enter Key.

After few seconds system shown Rage Ok and return back by Return key (↑) for
normal weighing display G: 0.00 T