INVERTER-DRIVEN
MULTI-SPLIT SYSTEM HEAT RECOVERY
AIR CONDITIONERS
Models:
< 3~, 460V/60Hz > < 3~/N, 380V/60Hz > < 3~, 220V/60Hz >
< Base Unit > < Base Unit > < Base Unit >
JTOR080VPEUBS1 JTOR080VPEFBS1 JTOR080VPERBS1
JTOR100VPEUBS1 JTOR100VPEFBS1 JTOR100VPERBS1
JTOR120VPEUBS1 JTOR120VPEFBS1 JTOR120VPERBS1
JTOR140VPEUBS1 JTOR140VPEFBS1 JTOR140VPERBS1
JTOR160VPEUBS1 JTOR160VPEFBS1 JTOR160VPERBS1
JTOR180VPEUBS1 JTOR180VPEFBS1 JTOR180VPERBS1
JTOR200VPEUBS1 JTOR200VPEFBS1 JTOR200VPERBS1
JTOR220VPEUBS1 JTOR220VPEFBS1 JTOR220VPERBS1
JTOR240VPEUBS1 JTOR240VPEFBS1 JTOR240VPERBS1
< Combination Unit > < Combination Unit > < Combination Unit >
JTOR260VAEUBS1 JTOR260VAEFBS1 JTOR260VAERBS1
JTOR280VAEUBS1 JTOR280VAEFBS1 JTOR280VAERBS1
JTOR300VAEUBS1 JTOR300VAEFBS1 JTOR300VAERBS1
JTOR320VAEUBS1 JTOR320VAEFBS1 JTOR320VAERBS1
JTOR340VAEUBS1 JTOR340VAEFBS1 JTOR340VAERBS1
JTOR360VAEUBS1 JTOR360VAEFBS1 JTOR360VAERBS1
JTOR380VAEUBS1 JTOR380VAEFBS1 JTOR380VAERBS1
JTOR400VAEUBS1 JTOR400VAEFBS1 JTOR400VAERBS1
JTOR420VAEUBS1 JTOR420VAEFBS1 JTOR420VAERBS1
JTOR440VAEUBS1 JTOR440VAEFBS1 JTOR440VAERBS1
JTOR460VAEUBS1 JTOR460VAEFBS1 JTOR460VAERBS1
JTOR480VAEUBS1 JTOR480VAEFBS1 JTOR480VAERBS1
JTOR500VAEUBS1 JTOR500VAEFBS1 JTOR500VAERBS1
JTOR520VAEUBS1 JTOR520VAEFBS1 JTOR520VAERBS1
JTOR540VAEUBS1 JTOR540VAEFBS1 JTOR540VAERBS1
Issue Date:
XX. Oct. 2017
IMPORTANT NOTICE
FAN-2209 201709 i
l This heat recovery air conditioner has been designed for the following temperatures. Operate the heat
recovery air conditioner within this range.
l This system can provide Heat Recovery System.
Temperature (°C)
Cooling and Heating Operation
Cooling Operation Heating Operation
Cooling Heating
Indoor Air Inlet
15 to 23°C WB 15 to 27°C DB 15 to 23°C WB 15 to 27°C DB
Temperature
-5 to 24°C DB
-5 to 48°C DB
-6 to 15°C WB
Outdoor Air Inlet
With Low Ambient Setting* -20 to 15°C WB With Low Ambient Setting*
Temperature
-10 to 24°C DB
-10 to 48°C DB
-11 to 15°C WB
DB: Dry Bulb, WB: Wet Bulb
(*) NOTES:
1. Cooling operation at maximum 48°C DB should be available only if the outdoor air inlet temperature
increase temporarily according to the installation condition.
2. If install the units to the place where exceed ambient temperature 48°C DB continuously, the combination
ratio must be lower 130% and not to operate all of the indoor unit simultaneously.
3. The cooling capacity is deteriorated at high ambient temperature. Select the larger capacity outdoor unit
than compatible building heat load.
4. The appropriate amount (100%) of refrigerant must be charged. Excessive charging of refrigerant is
forbidden.
5. It must be avoided to install the units where affected by direct sunlight reflection and short circuit. There may
be the possibility to activate protection control and alarm system if install the units to inappropriate place.
Also the life time of the products and parts must be considerably shortened.
6. Periodic maintenance (1/certain month) must be applied to the heat exchanger fin to avoid adhesion of dirt
and clogging of sand to the outdoor unit heat exchanger.
* In case cooling operation or simultaneous operation under the inlet air temperature -5°C or lower the conditions
below must be considered at the time of installation.
● Make sure to apply Snow Protection Hood (Optional Parts).
● The minimum capacity of connectable indoor unit is 2.5HP.
● Set the function “Cooling Operation under Low Load Operation” (DSW6) from the outdoor unit
(If multiple outdoor units are connected in a system, set the function only for outdoor unit A).
● Make sure to apply new CH-Box (Optional Parts). The “Low Ambient Setting” is not available if the system is
connected with current CH unit.
This manual should be considered as a permanent part of the air conditioning equipment and should
remain with the air conditioning equipment.
ii FAN-2209 201709
SAFETY SUMMARY
CAUTION : CAUTION, used with the safety alert symbol, indicates a hazardous situation which,
if not avoided, could result in minor or moderate injury.
DANGER
● Do not perform installation work, refrigerant piping work, drain pump, drain piping and electrical wiring
connection without referring to our installation manual. If the instructions are not followed, it may result in
a water leakage, electric shock or a fire.
● Use the specified non-flammable refrigerant (R410A) to the outdoor unit in the refrigerant cycle.
Do not charge material other than R410A into the unit such as hydrocarbon refrigerants (propane or etc.),
oxygen, flammable gases (acetylene or etc.) or poisonous gases when installing, maintaining and moving.
These flammables are extremely dangerous and may cause an explosion, a fire, and injury.
● Do not pour water into the indoor or outdoor unit. These products are equipped with electrical parts.
If poured, it will cause a serious electrical shock.
● Do not open the service cover or access panel for the indoor or outdoor units without turning OFF the main
power supply.
● Do not touch or adjust safety devices inside the indoor unit or outdoor units. If these devices are touched
or readjusted, it may cause a serious accident.
● Refrigerant leakage can cause difficulty with breathing due to insufficient air. Turn OFF the main switch,
extinguish any naked flames and contact your service contractor, if refrigerant leakage occurs.
● Make sure that the refrigerant leakage test should be performed.
Refrigerant (Fluorocarbon) for this unit is incombustible, non-toxic and odorless.
However if the refrigerant is leaked and is contacted with fire, toxic gas will generate.
Also because the fluorocarbon is heavier than air, the floor surface will be filled with it, which could cause
suffocation.
● The installer and system specialist shall secure safety against refrigerant leakage according to local
regulations or standards.
● Use an ELB (Earth Leakage Breaker).
In the event of fault, there is danger of an electric shock or a fire if it is not used.
● Do not install the outdoor unit where there is high level of oil mist, flammable gases, salty air or harmful
gases such as sulfur.
● For installation, firmly connect the refrigerant pipe before the compressor starts operating.
For maintenance, relocation and disposal, remove the refrigerant pipe after the compressor stops.
● Do not perform a short-circuit of the protection device such as a pressure switch when operating.
It may cause a fire and explosion.
iv FAN-2209 201709
SAFETY SUMMARY
WARNING
● Do not use any sprays such as insecticide, lacquer, hair spray or other flammable gases within
approximately one (1) meter from the system.
● If circuit breaker or fuse is often activated, stop the system and contact your service contractor.
● Check that the ground wire is securely connected. If the unit is not correctly grounded, it lead electric
shock. Do not connect the ground wiring to gas piping, water piping, lighting conductor or ground wiring
for telephone.
● Connect a fuse of specified capacity.
● Before performing any brazing work, check to ensure that there is no flammable material around.
When using refrigerant be sure to wear leather gloves to prevent cold injuries.
● Protect the wires, electrical parts, etc. from rats or other small animals.
If not protected, rats may gnaw at unprotected parts and which may lead to a fire.
● Fix the cables securely. External forces on the terminals could lead to a fire.
● Provide a sufficiently strong foundation. If not, the unit may fall down and it may lead to injuries.
● Do not install the unit in a place where oil, vapor, organic solvent and corrosive gas (ammonia, sulfur
compound and acid) may be present in quantities.
It may cause refrigerant leakage due to corrosion, electrical shock, deteriorated performance and
breakage.
● Perform electrical work according to Installation Manual and all the relevant regulation and standards.
If the instructions are not followed, an electrical shock and fire may occur due to insufficient capacity and
inadequate performance.
● Use specified cables between units and choose the cables correctly. If not, an electrical shock or fire may
occur.
● Ensure that the wiring terminals are tightened securely with the specified torques. If not, generating fire or
electrical shock at the terminal connection part may occur.
CAUTION
● Do not step or put any material on the product.
● Do not put any foreign material on the unit or inside the unit.
● Provide a strong and correct foundation so that;
a. The outdoor unit is not on an incline.
b. Abnormal sound dose not occur.
c. The outdoor unit will not fall down due to a strong wind or earthquake.
FAN-2209 201709 v
SAFETY SUMMARY
NOTICE
● Do not install the indoor unit, outdoor unit, remote control switch and cable within approximately 3 meters
from strong electromagnetic wave radiators such as medical equipment.
● Supply electrical power to the system to energize the oil heater for 12 hours before startup after a long
shutdown.
● Make sure that the outdoor unit is not covered with snow or ice, before operation.
● In some cases, the packaged air conditioner may not be operated normally under the following cases.
* In case that electrical power for the packaged air conditioner is supplied from the same power
transformer as the device*.
* In case that the power source wires for the device* and the packaged air conditioner are located close to
each other.
Device*: (Ex) Lift, container crane, rectifier for electric railway, inverter power device, arc furnace,
electric furnace, large-sized induction motor and large-sized switch.
It consumes a large quantity of electrical power.
Regarding the cases mentioned above, surge voltage may be inducted in the power supply wiring for the
packaged air conditioner due to a rapid change in power consumption of the device and an activation of
switch.
Therefore, check the field regulations and standards before performing electrical work in order to protect
the power supply for the packaged air conditioner.
NOTE
● It is recommended that the room will be ventilated every 3 to 4 hours.
● The heating capacity of the heat recovery unit is decreased according to the outdoor air temperature.
Therefore, it is recommended that auxiliary heating equipment be used in the field when the units is
installed in a low temperature region.
vi FAN-2209 201709
- CONTENTS -
< Technical Data >
1. Features...................................................................................................................................................... 1-5
2. General Data............................................................................................................................................... 1-35
2.1 Outdoor Units..................................................................................................................................... 1-35
2.2 CH-Box............................................................................................................................................... 1-43
3. Component Data......................................................................................................................................... 1-44
4. Dimensional Data........................................................................................................................................ 1-47
4.1 Outdoor Units..................................................................................................................................... 1-47
4.2 CH-Box............................................................................................................................................... 1-50
5. Structure..................................................................................................................................................... 1-53
5.1 Outdoor Units..................................................................................................................................... 1-53
5.2 CH-Box............................................................................................................................................... 1-57
6. Selection Data............................................................................................................................................. 1-60
6.1 Selection Guide.................................................................................................................................. 1-60
6.2 Capacity Characteristic Curve............................................................................................................ 1-67
6.3 Outdoor Unit Capacity According to Temperature Condition and Connected IDU Capacity Ratio
(Part Load Data)................................................................................................................................. 1-110
6.4 Correction Factor According to Piping Length.................................................................................... 1-110
6.5 Correction Factor According to Defrosting Operation......................................................................... 1-113
6.6 Correction Factor According to Altitude.............................................................................................. 1-114
7. Electrical Data............................................................................................................................................. 1-115
8. Sound Data................................................................................................................................................. 1-118
8.1 Outdoor Units..................................................................................................................................... 1-118
8.2 CH-Box............................................................................................................................................... 1-124
9. Center of Gravity......................................................................................................................................... 1-126
10. Working Range........................................................................................................................................... 1-127
11. Optional Accessories.................................................................................................................................. 1-129
11.1 Piping Connection Kit......................................................................................................................... 1-129
11.2 CH-Box............................................................................................................................................... 1-130
11.3 Multi-Kit.............................................................................................................................................. 1-131
11.4 Drain Boss.......................................................................................................................................... 1-132
11.5 Air Inlet Grille...................................................................................................................................... 1-133
11.6 Protection Net..................................................................................................................................... 1-134
1. Features...................................................................................................................................................... 1-5
2. General Data............................................................................................................................................... 1-35
2.1 Outdoor Units..................................................................................................................................... 1-35
2.2 CH-Box............................................................................................................................................... 1-43
3. Component Data......................................................................................................................................... 1-44
4. Dimensional Data........................................................................................................................................ 1-47
4.1 Outdoor Units..................................................................................................................................... 1-47
4.2 CH-Box............................................................................................................................................... 1-50
5. Structure..................................................................................................................................................... 1-53
5.1 Outdoor Units..................................................................................................................................... 1-53
5.2 CH-Box............................................................................................................................................... 1-57
6. Selection Data............................................................................................................................................. 1-60
6.1 Selection Guide.................................................................................................................................. 1-60
6.2 Capacity Characteristic Curve............................................................................................................ 1-67
6.3 Outdoor Unit Capacity According to Temperature Condition and Connected IDU Capacity Ratio
(Part Load Data)................................................................................................................................. 1-110
6.4 Correction Factor According to Piping Length.................................................................................... 1-110
6.5 Correction Factor According to Defrosting Operation......................................................................... 1-113
6.6 Correction Factor According to Altitude.............................................................................................. 1-114
7. Electrical Data............................................................................................................................................. 1-115
8. Sound Data................................................................................................................................................. 1-118
8.1 Outdoor Units..................................................................................................................................... 1-118
8.2 CH-Box............................................................................................................................................... 1-124
9. Center of Gravity......................................................................................................................................... 1-126
10. Working Range........................................................................................................................................... 1-127
11. Optional Accessories.................................................................................................................................. 1-129
11.1 Piping Connection Kit......................................................................................................................... 1-129
11.2 CH-Box............................................................................................................................................... 1-130
11.3 Multi-Kit.............................................................................................................................................. 1-131
11.4 Drain Boss.......................................................................................................................................... 1-132
11.5 Air Inlet Grille...................................................................................................................................... 1-133
11.6 Protection Net..................................................................................................................................... 1-134
1. Features
Outdoor Unit
YORK proudly introduces the New Outdoor Unit series, the highly-efficient and reliable air-conditioning
system. Recently, increased numbers of buildings are requiring "Intelligent" facilities - communication
networks, office automation, and a comfortable environment. Particularly, comfortable space is required all
the day through the year in office buildings.
This multi-split system air conditioner can meet these requirements. The proven combination of the scroll
compressor and the inverter provides the best air conditioning for small/medium office buildings.
HP
Series
5 6 8 10 12 14 16 18 20 22 24 26 28
Current Model
- - ● ● ● ● ● ○ ○ ○ ○ ○ ○
[Heat Pump/Heat Recovery]
New Model
- - H H H H H H H H H I I
[Heat Recovery]
HP
Series
30 32 34 36 38 40 42 44 46 48 50 52 54
Current Model
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
[Heat Pump/Heat Recovery]
New Model
I I I I I I I I I I I I I
[Heat Recovery]
● Current Line-up (Single Module) ○ Current Line-up (Combination) - Not available
H New Line-up (Single Module) I New Line-up (Combination)
<New CH-Box>
Single Multiple
Series
˂6HP 6.1HP - 10HP 4 Branch 8 Branch 12 Branch 16 Branch
Current Model
● ● - - - -
(CH Unit)
New Model
H H H H H H
(CH-Box)
4: Available
4
4
Current CH Unit Current VRF (Heat Recovery)
×: Not Available
×
4
4
New CH-Box New VRF (Heat Recovery)
4
4
(3) The current CH Unit and the new CH-Boxes can not be used in the same system together.
(4) The production of current CH Unit shall be discontinued, however, it will be supplied for servicing
and maintenance until further notice. Contact us if there are order request for the current CH Unit
JTOR080VPE(U,F,R)BS1
JTOR100VPE(U,F,R)BS1
JTOR120VPE(U,F,R)BS1
JTOR140VPE(U,F,R)BS1
Base Units JTOR160VPE(U,F,R)BS1
JTOR180VPE(U,F,R)BS1
JTOR200VPE(U,F,R)BS1
JTOR220VPE(U,F,R)BS1
JTOR240VPE(U,F,R)BS1
JTOR260VAE(U,F,R)BS1
JTOR280VAE(U,F,R)BS1
JTOR300VAE(U,F,R)BS1
JTOR320VAE(U,F,R)BS1
JTOR340VAE(U,F,R)BS1
JTOR360VAE(U,F,R)BS1
JTOR380VAE(U,F,R)BS1
Combination of
JTOR400VAE(U,F,R)BS1
Base Units
JTOR420VAE(U,F,R)BS1
JTOR440VAE(U,F,R)BS1
JTOR460VAE(U,F,R)BS1
JTOR480VAE(U,F,R)BS1
JTOR500VAE(U,F,R)BS1
JTOR520VAE(U,F,R)BS1
JTOR540VAE(U,F,R)BS1
Optional
Optional Air Panel for Other
Indoor Unit + Remote Control + +
Cassette Type Optional Parts
Switch
NEW CH-Box
■ Line-Up
● Outdoor Unit
This outdoor unit series “JTOR***VPEUBS1”, “JTOR***VPERBS1” and “JTOR***VPEFBS1” can build
the capacity from 8 to 54HP by combining maximum 3 outdoor units from 8 to 24HP.
J T O R 080 V P E R B S 1
Version
Factory
S: Shimizu, Japan
Generation
Power Supply
U: 3~, 460V/60Hz
F: 3~/N, 380V/60Hz
R: 3~, 220V/60Hz
Refrigerant
E: R410A
Module and Combination
A: All Inverter Combination
P: All Inverter Module
Air Discharge
V: Vertical
Capacity
HP x 10 (Example: 080 = 8HP)
Application
R: Heat Recovery
Heat Source
O: Air Source
Market Position
T: Tier-1 Commercial VRF
Brand
J: York Brand
HP 18 20 22 24
Model JTOR180VPEUBS1 JTOR200VPEUBS1 JTOR220VPEUBS1 JTOR240VPEUBS1
< Combination of Base Units > T
HP 26 28 30 32 34
Model JTOR260VAEUBS1 JTOR280VAEUBS1 JTOR300VAEUBS1 JTOR320VAEUBS1 JTOR340VAEUBS1
JTOR120VPEUBS1 JTOR120VPEUBS1 JTOR120VPEUBS1 JTOR140VPEUBS1 JTOR160VPEUBS1
Combination
JTOR140VPEUBS1 JTOR160VPEUBS1 JTOR180VPEUBS1 JTOR180VPEUBS1 JTOR180VPEUBS1
HP 36 38 40 42 44
Model JTOR360VAEUBS1 JTOR380VAEUBS1 JTOR400VAEUBS1 JTOR420VAEUBS1 JTOR440VAEUBS1
JTOR180VPEUBS1 JTOR140VPEUBS1 JTOR180VPEUBS1 JTOR180VPEUBS1 JTOR220VPEUBS1
Combination
JTOR180VPEUBS1 JTOR240VPEUBS1 JTOR220VPEUBS1 JTOR240VPEUBS1 JTOR220VPEUBS1
HP 46 48 50 52 54
Model JTOR460VAEUBS1 JTOR480VAEUBS1 JTOR500VAEUBS1 JTOR520VAEUBS1 JTOR540VAEUBS1
JTOR220VPEUBS1 JTOR240VPEUBS1 JTOR140VPEUBS1 JTOR160VPEUBS1 JTOR180VPEUBS1
Combination JTOR240VPEUBS1 JTOR240VPEUBS1 JTOR180VPEUBS1 JTOR180VPEUBS1 JTOR180VPEUBS1
- - JTOR180VPEUBS1 JTOR180VPEUBS1 JTOR180VPEUBS1
HP 18 20 22 24
Model JTOR180VPEFBS1 JTOR200VPEFBS1 JTOR220VPEFBS1 JTOR240VPEFBS1
< Combination of Base Units > T
HP 26 28 30 32 34
Model JTOR260VAEFBS1 JTOR280VAEFBS1 JTOR300VAEFBS1 JTOR320VAEFBS1 JTOR340VAEFBS1
JTOR120VPEFBS1 JTOR120VPEFBS1 JTOR120VPEFBS1 JTOR140VPEFBS1 JTOR160VPEFBS1
Combination
JTOR140VPEFBS1 JTOR160VPEFBS1 JTOR180VPEFBS1 JTOR180VPEFBS1 JTOR180VPEFBS1
HP 36 38 40 42 44
Model JTOR360VAEFBS1 JTOR380VAEFBS1 JTOR400VAEFBS1 JTOR420VAEFBS1 JTOR440VAEFBS1
JTOR180VPEFBS1 JTOR140VPEFBS1 JTOR180VPEFBS1 JTOR180VPEFBS1 JTOR220VPEFBS1
Combination
JTOR180VPEFBS1 JTOR240VPEFBS1 JTOR220VPEFBS1 JTOR240VPEFBS1 JTOR220VPEFBS1
HP 46 48 50 52 54
Model JTOR460VAEFBS1 JTOR480VAEFBS1 JTOR500VAEFBS1 JTOR520VAEFBS1 JTOR540VAEFBS1
JTOR220VPEFBS1 JTOR240VPEFBS1 JTOR140VPEFBS1 JTOR160VPEFBS1 JTOR180VPEFBS1
Combination JTOR240VPEFBS1 JTOR240VPEFBS1 JTOR180VPEFBS1 JTOR180VPEFBS1 JTOR180VPEFBS1
- - JTOR180VPEFBS1 JTOR180VPEFBS1 JTOR180VPEFBS1
T: The outdoor unit from 26 to 54HP consists of the combination of 2 to 3 base units.
The combinations other than listed in above table is prohibited.
NOTE:
Refer to the “Caution about Outdoor Unit Installation”.
HP 18 20 22 24
Model JTOR180VPERBS1 JTOR200VPERBS1 JTOR220VPERBS1 JTOR240VPERBS1
< Combination of Base Units > T
HP 26 28 30 32 34
Model JTOR260VAERBS1 JTOR280VAERBS1 JTOR300VAERBS1 JTOR320VAERBS1 JTOR340VAERBS1
JTOR120VPERBS1 JTOR120VPERBS1 JTOR120VPERBS1 JTOR140VPERBS1 JTOR160VPERBS1
Combination
JTOR140VPERBS1 JTOR160VPERBS1 JTOR180VPERBS1 JTOR180VPERBS1 JTOR180VPERBS1
HP 36 38 40 42 44
Model JTOR360VAERBS1 JTOR380VAERBS1 JTOR400VAERBS1 JTOR420VAERBS1 JTOR440VAERBS1
JTOR180VPERBS1 JTOR140VPERBS1 JTOR180VPERBS1 JTOR180VPERBS1 JTOR220VPERBS1
Combination
JTOR180VPERBS1 JTOR240VPERBS1 JTOR220VPERBS1 JTOR240VPERBS1 JTOR220VPERBS1
HP 46 48 50 52 54
Model JTOR460VAERBS1 JTOR480VAERBS1 JTOR500VAERBS1 JTOR520VAERBS1 JTOR540VAERBS1
JTOR220VPERBS1 JTOR240VPERBS1 JTOR140VPERBS1 JTOR160VPERBS1 JTOR180VPERBS1
Combination JTOR240VPERBS1 JTOR240VPERBS1 JTOR180VPERBS1 JTOR180VPERBS1 JTOR180VPERBS1
- - JTOR180VPERBS1 JTOR180VPERBS1 JTOR180VPERBS1
T: The outdoor unit from 26 to 54HP consists of the combination of 2 to 3 base units.
The combinations other than listed in above table is prohibited.
NOTE:
Refer to the “Caution about Outdoor Unit Installation”.
● Multi-Kit
MW - NP 14 2 X 3
Type of Generation
Applicable System
X: for 3 Pipes
A: for 2 Pipes
No. of Branches
Corresponding Outdoor Units Capacity
14: 5HP 56: 18, 20HP
28: 6 - 10HP 69: 22, 24HP
45: 12 - 16HP 90: 26 - 54HP
Refrigerant Type
NP: R410A
Unit Type
MW: Line Branch Multi-Kit for Outdoor Units
MH: Header Branch Multi-Kit for Outdoor Units
● CH-Box
<Single>
J CH - AP 160 SSX
Applicable System
SSX: for Heat Recovery System (3 Pipes System)
Maximum Connectable Indoor Unit Capacity (HP)
160: 6.0HP
280: 6.1HP - 10.0HP
Refrigerant Type
AP: R410A
Unit Type
CH: Cooling/Heating Change-Over Box
Brand
York Brand
Connectable Indoor Unit Number of Connectable
Model Branch
Total Capacity Indoor Unit(*1)
JCH-AP160SSX 1 6.0HP or less (Max. 16kW) 1-7
JCH-AP280SSX 1 6.1HP - 10.0HP (Max. 28kW) 1-8
( 1)
* When multiple indoor units are connected to the same CH-Box, they are controlled within
the same operation mode.
<Multiple>
J CH - AP 16 M SSX
Applicable System
SSX: for Heat Recovery System (3 Pipes System)
Multiple
Branch
04: 4 Branch
08: 8 Branch
12: 12 Branch
16: 16 Branch
Refrigerant Type
AP: R410A
Unit Type
CH: Cooling/Heating Change-Over Box
Brand
York Brand
Connectable Indoor Unit Number of Connectable
Model Branch
Total Capacity Indoor Unit per Branch(*2)
JCH-AP04MSSX 4 16.0HP or less (Max. 44.8kW) 1-6
JCH-AP08MSSX 8 30.0HP or less (Max. 85kW) 1-6
JCH-AP12MSSX 12 30.0HP or less (Max. 85kW) 1-6
JCH-AP16MSSX 16 30.0HP or less (Max. 85kW) 1-6
( 2)
* The indoor units connected to the same branch of the CH-Box are controlled within the
same operation mode.
<CH-Box>
<Single>
JCH-AP160SSX JCH-AP280SSX
Outer Dimension: W301 x D214 x H191 mm Outer Dimension: W301 x D214 x H191 mm
<Multiple>
JCH-AP04MSSX JCH-AP08MSSX
Outer Dimension: W303 x D352 x H260mm Outer Dimension: W543 x D352x H260 mm
JCH-AP12MSSX JCH-AP16MSSX
Outer Dimension: W783 x D352 x H260 mm Outer Dimension: W1,023 x 352 x H260 mm
The line-up of new YORK VRF series indoor units has been extended up to 7 types of indoor units to meet
various building requirements. (0.6HP through 10HP)
NOTES:
1. The connectable indoor unit capacity ratio can be calculated as follows.
Connectable Indoor Unit Capacity Ratio = Total Indoor Unit Capacity / Total Outdoor Unit Capacity
2. For the system under which all the indoor units are supposed to operate simultaneously, the total indoor unit capacity
should be less than outdoor unit capacity. Otherwise, it may cause a decrease of operating performance and operating
limit in overload operation.
3. For the system under which all the indoor units are not supposed to operate simultaneously, the total indoor unit
capacity is available up to 130% against the outdoor unit capacity.
4. Maximum number of connectable indoor units differs depending on the model, capacity, environment and installation
place of connected indoor units. Refer to “Technical Catalog” for the selection.
5. When operating the outdoor unit in cold areas with temperatures of -10oC, or under the high heating load conditions,
the total indoor unit capacity should be less than 100% against the outdoor unit capacity and the total piping length
should be less than 300m.
6. The air flow volume for indoor units of 1.0HP or less is set higher than that for indoor units of 1.5HP or more. Make
sure to select appropriate indoor units when installing indoor units where cold draft may occur during heating operation.
If installing indoor units in such places, refer to the recommended number of connectable indoor units.
7. (*): For connecting Wall Type with the Expansion Valve Kit, the number of connectable indoor unit is limited according
to the total piping length between the expansion valve and the indoor unit. The total piping length must be less than
the length indicated in the table.
The load capacity per hour or the possibility of all indoor units simultaneous operation is unknown at the design stage,
the total capacity of combined indoor units should be not over 100% against the outdoor unit capacity.
(EER)
EER (COP)
COP
7.00 7.00
NOTE:
The above values indicate the EER/COP per outdoor unit when it is combined with specified indoor
units.
HP 8 10 12 14 16 18 20 22 24 26 28 30
Capacity 22.4 28.0 33.5 40.0 45.0 50.0 56.0 61.5 67.0 73.0 77.5 85.0
Cooling
(kW)
EER 5.21 4.76 4.90 4.15 4.46 4.21 3.70 3.75 3.55 4.49 4.71 4.39
Capacity 25.0 31.5 37.5 45.0 50.0 56.0 63.0 69.0 77.5 82.5 90.0 95.0
Heating
(kW)
COP 5.34 5.11 4.94 3.93 4.10 4.09 3.92 3.43 3.84 4.33 4.30 4.33
HP 32 34 36 38 40 42 44 46 48 50 52 54
Capacity 90.0 95.0 100.0 106.0 112.0 118.0 122.0 128.0 136.0 140.0 145.0 150.0
Cooling
(kW)
EER 4.18 4.32 4.21 3.79 3.92 3.77 3.79 3.66 3.54 4.19 4.28 4.21
Capacity 100.0 106.0 112.0 118.0 125.0 132.0 140.0 145.0 150.0 155.0 160.0 165.0
Heating
(kW)
COP 4.06 4.10 4.10 4.04 3.74 3.90 3.39 3.67 3.85 4.10 4.15 4.17
NOTES:
1. The cooling and heating performances are the value s when combined with our specified indoor units.
Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 27°C DB (80°F DB) Indoor Air Inlet Temperature: 20°C DB (68°F DB)
19.0°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB)
Outdoor Air Inlet Temperature: 35°C DB (95°F DB) 6°C WB (43°F WB)
Piping Length: Refer to each General Specification for details. Piping Lift: 0 Meter
2. The above values indicate the EER/COP per outdoor unit when it is combined with specified indoor units.
Bell-mouth Compressor
Long Bell-mouth
Suppress leakage
and effectively operate
in wide range.
Heat Exchanger
˂Improve Efficiency at Low Load Cooling Operation with New Path Structure˃
Adopt best effective heat exchanger path structure during low load cooling operation. Divide heat exchanger
to upper and lower parts and modify path shape to be narrower as it reaches lower part and increase
refrigerant flow speed to improve thermal conductivity. Improved energy efficiency and cooling capacity.
● Operation Condition at Low Load Cooling Operation ● Ʃ Shape Heat Exchanger: ≥14HP Type
Adopt two fan structure for improve efficiency
at low load operation. Adopt Σ shape heat
Improve cooling capacity and energy exchanger to maximize the effect of the two fan
efficiency by adopting new path structure to
increase refrigerant flow speed. structure for better energy saving.
(ph Diagram Conceptual Drawing)
Sturation Curve
Condense
Pressure: p
(Mpa) Expand Compress
Evaporate
Cooling Capacity
Enthalpy: h(kJ/kg)
Rotation Rotation
Speed Speed
15 15
10 Energy Loss Caused by Switching ON/OFF Operation. 10 Suppress Switching ON/OFF Operation
Power 5 5
Consumption
(kW)
0 0
0 60 120 180 0 60 120 180
Time (min.) Time (min.)
The verification test has been implemented with the combination of current Japanese domestic
model VRF outdoor unit (RAS-AP280DG3) and two Japanese domestic model VRF 4-way cassette
indoor units (RCI-AP140K5)
<Testing Condition>
• Indoor Unit Inlet Temperature: 27oC (Dry Bulb) / 19oC (Wet Bulb)
• Ambient Temperature at Air Volume “High”: 23oC (Dry Bulb)
• Piping Length between Indoor Unit and Outdoor Unit: 15m
• Testing Location: Environment Testing Facility at Kansai Denryoku (power supply company)
is restricted.
Power Setting
Selectable from 100%,
Maximum efficiency is secured 80%, 70%, 60% and 40% of
within the power setting range. the rated power consumption
for cooling operation.
Morning Daytime Night
Operating Hours
< Setting Example: Schedule Setting for Each Group by Central Station DX >
Group A Group B
NOTES:
1. The demand current control (%) is indicated by approximate values. The value in this control which is
calculated by the current is different precision from the value in the wattmeter.
If it is required that the maximum power consumption is managed precisely, a field-supplied demand
controller should be used.
2. The range may temporarily be higher than the power setting range (%) depending on the operating
control condition such as protection control.
3. When the above self-demand control is set, the performance is restricted because the rotation
frequency of compressor is forcibly decreased.
Outdoor Units
Max. Piping Length: 10m
Height Difference: 0.1m
NOTES:
*1: Contact your distributor or dealer if the height difference is over 50m.
*2: When the total piping length is over 300m, the maximum additional refrigerant charge is restricted.
The maximum additional refrigerant charge (table below) should not exceed the total field additional
charge (refrigerant pipe + indoor unit).
HP 5 to 10 12 14 to 18 20, 22 24 26 to 54
Max. Additional Refrigerant Charge (kg) 28.0 36.0 40.0 51.0 52.0 63.0
*3: If the piping length exceeds figure in ( )*, the connectable indoor units number should be less than
recommended number.
(1) In the case that L2 is over 40m, the size of gas and liquid lines “b” or “g” should be increased by one
size with reducers (field-supplied).
* If (a) is one size smaller than (b, g) after increasing the size, increase the size of (a) to the same size
as (b, g).
* If (a) is two sizes smaller than (b, g) after increasing the size, increase (a) one size and reduce (b, g)
one size to be the same size. (L2 will be over 40m, the size of (b, g) should not be increased.)
(2) The difference between the piping length from the first branch to the farthest indoor unit and the piping
length from the first branch to the closest indoor unit must be within 40m.
* (g+h+j)-(b+d)<40m
(): Main Piping Branch: Both of the pipes branched from a Multi-Kit are connected to the next Multi-Kits.
NOTES:
1. The connectable indoor unit capacity ratio can be calculated as follows.
Connectable Indoor Unit Capacity Ratio = Total Indoor Unit Capacity / Total Outdoor Unit Capacity
2. For the system under which all the indoor units are supposed to operate simultaneously, the total indoor
unit capacity should be less than outdoor unit capacity. Otherwise, it may cause a decrease of operating
performance and operating limit in overload operation.
3. For the system under which all the indoor units are not supposed to operate simultaneously, the total indoor
unit capacity is available up to 130% against the outdoor unit capacity.
4. When operating the outdoor unit in cold areas with temperatures of -10°C, or under the high heating load
conditions, the total indoor unit capacity should be less than 100% against the outdoor unit capacity and the
total piping length should be less than 300m.
5. The air flow volume for indoor units of 0.4 and 1.0HP is set higher than that for indoor units of 1.5HP or more.
Make sure to select appropriate indoor units when installing indoor units where cold draft may occur during
heating operation. If installing indoor units in such places, refer to the recommended number of connectable
indoor units.
6. For connecting Tempclean Indoor Unit and Outdoor Air Processing Air Conditioner, the number of the indoor
units should be within recommended connectable indoor units number.
(*1) If combination capacity of indoor units exceed 100% of outdoor unit capacity, there might be the possibility
of insufficient capacity of 130% combination ratio. If combination capacity exceed 130% contact your
distributer or dealer.
Balcony Building
< Case that Open Space is Louver > < Case that Open Space is Wall >
Ceiling Wall Ceiling Wall Air Outlet Duct Kit
Air Outlet Duct Kit
(Field-Supplied)
(Field-Supplied)
Duct
(Field-Supplied)
The recommended
The air flow direction
air outlet duct kit
can be changed to
has flanged opening,
open space by using
which makes the field
air outlet duct kit.
connection work possible.
NOTE:
Pay attention to the following case at the design and the installation. If the outlet air intakes by short-
circuit, the operation range is limited due to increasing high pressure in the cooling operation or
decreasing low pressure in the heating operation so that may cause failure of unit.
Cooling Operation
55
50
48
(*1)
45
43
40
Outdoor Air Inlet Temperature (oCDB)
35
15 5
10 0
5 -5
0 -10
NOTES:
*1. (1) Cooling operation at maximum 48oC DB is available only if the outdoor air inlet temperature
increase temporarily caused by installation condition.
(2) If install the units to the place where continuously exceed ambient temperature 48oC, the
combination ratio must be lower than 130% and not to operate all of the indoor unit simultaneously.
(3) The cooling capacity is deteriorated at high ambient temperature. Select the larger capacity outdoor
unit than compatible building heat load.
(4) The appropriate amount (100%) of refrigerant must be charged. Excessive charging of refrigerant is
forbidden.
(5) Avoid to install the units where affected by direct sunlight reflection and short circuit. There may
be the possibility to activate protection control and alarm system if install the units to inappropriate
place. The life time of the products and parts are considerably shortened.
(6) Periodic maintenance (1/certain month) must be applied to the heat exchanger fin to avoid adhesion
of dirt and clogging of sand to the outdoor unit heat exchanger.
*2. There might be the possibility of thermo-OFF when operate the outdoor unit under the low cooling
load condition and in the low outdoor air temperature (10oC DB or lower) to prevent indoor unit heat
exchanger from frost formation.
*3. Indoor air inlet temperature at heating operation from 15oC to 27oC WB is under assumption of limited
time operation such as at the time of startup in the early morning and not suitable for long time
continuous operation.
*4. There might be the possibility of thermo-OFF when operate the outdoor unit under the low heating
load condition and in the high outdoor air temperature (higher than 15oC DB) to prevent the outdoor
unit. The outdoor unit operation stops when outdoor air inlet temperature exceed 26oC DB.
*5. Operational range is different when connect to All Fresh Air Unit, Econofresh, and other special
indoor units.
*6. In case cooling operation or simultaneous operation under the inlet air temperature -5oC or lower the
conditions listed below must be considered at the time of installation.
• Make sure to apply Snow Protection Hood (Optional Part) .
• The minimum capacity of indoor unit connectable is 2.5HP
• Set the function “Cooling Operation Under Low Load Operation” (DSW6) from the outdoor unit
(If multiple outdoor units are connected in a system set the function only for outdoor unit A).
• Make sure to apply new CH-Box (Optional Part).
The “Low Ambient Setting” is not available if the system is connected with current CH unit.
Access Door
100% 100%
12 HP 12 HP
Inverter Compressor
Inverter Compressor
Control Capacity
Control Capacity
20% 10%
Max. Min. Max. Min.
Cooling Load Cooling Load
Item H-LINK ll
Number of Max. Ref. Group / System 64
Address Setting Range of Indoor Units / Ref. Group 0 to 63
Number of Max. Indoor Unit / System 160
Total Q'ty of Central Control Devices in the same
200
H-LINK
Max. Wiring Length Total 1,000m (5,000m*)
*: In case 4 (four) units of PSC-5HR is used.
■ H-LINK II System
The H-LINK II wiring system requires only two transmission wires to connect each indoor unit and outdoor
unit for up to 64 refrigerant cycles, and to connect wires for all indoor units and outdoor units.
<Specifications>
* Transmission Wire: 2-Wire
* Polarity of Transmission Wire: Non-Polar Wire
* Maximum Outdoor Units to be Connected: 64 Units per System
* Maximum Indoor Units to be Connected: 160 Units per H-LINK II System
* Maximum Wiring Length: Total 1,000m (including CS-NET)
* Recommended Cable: Twist-Pair Cable with Shield, over 0.75mm2 (Equivalent to KPEV-S)
* Voltage: DC5V
NOTE:
In case of applying H-LINK II system, the setting of dip switch for outdoor unit and indoor unit is required.
If the dip switches are not set or set incorrectly, the alarm may occur due to a transmission failure.
1 2 OFF 1 2 OFF
Outdoor
Unit
Sea Sea
* The place where the outdoor unit is washed by * The place where rain is scarce.
rain. * The place where a salt air blow onto the outdoor
* The place where a salt air is not blown onto the unit directly.
Condition outdoor unit directly. * The place where the distance between
of
* The place where the distance between seacoast seacoast and the outdoor unit is within 300m.
Installation
and the outdoor unit is 300m to 1000m. * The place where the outdoor unit faces to the
Place
* The place where the outdoor unit is installed seacoast.
behind a building as shown in the figure.
1) Do not install the units in a place where salty air or mist is directly blown to the units.
2) Install the unit so as rain can wash off salt particles onto the panels.
(ex. Do not cover the unit with sunshades.)
3) Pay attention to level of the unit so that water on the bottom base can flow smoothly because
the remained water on the bottom base of the outdoor unit worsens corrosion severely.
4) Periodically perform maintenance work by clean water to remove salt particles, etc.
5) Repair scratches which occurred during installation and maintenance work.
6) Periodically check each component. If needed, replace it with service parts.
7) Provide the drainage around foundation smoothly.
2. General Data
2.1 Outdoor Units
Model
※
JTOR080VPE(U,F,R)BS1 JTOR100VPE(U,F,R)BS1 JTOR120VPE(U,F,R)BS1
Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz
Nominal Cooling Capacity kW 22.4 28.0 33.5
Nominal Heating Capacity kW 25.0 31.5 37.5
Cabinet Color (Munsell Code) Natural Gray (1.0Y 8.5/0.5)
Sound Power Level dB(A) 80 82 82
Sound Pressure Level dB(A) 58 60 59
Outer Dimensions
Height x Width x Depth mm 1,675 x 950 x 765 1,675 x 950 x 765 1,675 x 950 x 765
Net Weight
460V/60Hz kg 200 200 220
380V/60Hz kg 195 195 215
220V/60Hz kg 190 190 210
Gross Weight
460V/60Hz kg 216 216 236
380V/60Hz kg 211 211 231
220V/60Hz kg 206 206 226
Refrigerant R410A
Flow Control Micro-Control Computer Expansion Valve
Compressor 284 + 328 + 328
Model AA50PHD AA50PHD DC80PHD
Quantity 1 1 1
Motor Output (Pole) kW 3.3 (6) 4.3 (6) 5.4 (6)
Refrigeration Oil
Type FVC68D
Charge L/Unit 6.0 6.0 6.0
Heat Exchanger Multi-Pass Cross-Finned Tube
Condenser Fan Propeller Fan
Quantity 1 1 1
Air Flow Rate m 3/min. 165 170 190
Motor Output (Pole) kW 0.26 (8) 0.28 (8) 0.42 (8)
Main Refrigerant Piping
Heat Recovery System (3 Pipes)
Liquid Line mm (in.) 9.52 (3/8) 9.52 (3/8) 12.7 (1/2)
Gas Line
Low Pressure mm (in.) 19.05 (3/4) 22.2 (7/8) 25.4 (1)
High/Low Pressure mm (in.) 15.88 (5/8) 19.05 (3/4) 22.2 (7/8)
Refrigerant Charge
kg 5.0 5.0 7.2
(before Shipment)
Packing Dimensions
Height x Width x Depth mm 1,800 x 1,030 x 810 1,800 x 1,030 x 810 1,800 x 1,030 x 810
Approximate
Packing Measurement m3 1.5 1.5 1.5
NOTES:
1. The cooling and heating performances are the values when combined with our specified indoor units.
Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB)
o o
19.0 C WB (66.2 F WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
o o
Outdoor Air Inlet Temperature: 35 C DB (95 F DB) 6oC WB (43 oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure is based on the following conditions.
1 Meter from the unit service cover surface, and 1.5 Meters from floor level.
The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
※ The 11th digit of the model name indicate the power supply of each unit.
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz
Model
※
JTOR140VPE(U,F,R)BS1 JTOR160VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1
Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz
Nominal Cooling Capacity kW 40.0 45.0 50.0
Nominal Heating Capacity kW 45.0 50.0 56.0
Cabinet Color (Munsell Code) Natural Gray (1.0Y 8.5/0.5)
Sound Power Level dB(A) 85 85 86
Sound Pressure Level dB(A) 63 63 65
Outer Dimensions
Height x Width x Depth mm 1,675 x 1,210 x 765 1,675 x 1,210 x 765 1,675 x 1,210 x 765
Net Weight
460V/60Hz kg 276 319 320
380V/60Hz kg 271 314 315
220V/60Hz kg 266 309 310
Gross Weight
460V/60Hz kg 294 337 338
380V/60Hz kg 289 332 333
220V/60Hz kg 284 327 328
Refrigerant R410A
Flow Control Micro-Computer Control Expansion Valve
Compressor 284 + 328 + 328
Model DC80PHD AA50PHD + AA50PHD AA50PHD + AA50PHD
Quantity 1 2 2
Motor Output (Pole) kW 8.0 (6) 4.5 (6) × 2 5.0 (6) × 2
Refrigeration Oil
Type FVC68D
Charge L/Unit 6.9 7.9 7.9
Heat Exchanger Multi-Pass Cross-Finned Tube
Condenser Fan Propeller Fan
Quantity 2 2 2
Air Flow Rate m 3/min. 239 256 256
Motor Output (Pole) kW 0.33 (8) x 2 0.39 (8) x 2 0.39 (8) x 2
Main Refrigerant Piping
Heat Recovery System (3 Pipes)
Liquid Line mm (in.) 12.7 (1/2) 12.7 (1/2) 15.88 (5/8)
Gas Line
Low Pressure mm (in.) 25.4 (1) 28.58 (1-1/8) 28.58 (1-1/8)
High/Low Pressure mm (in.) 22.2 (7/8) 22.2 (7/8) 22.2 (7/8)
Refrigerant Charge
kg 8.9 9.9 10.7
(before Shipment)
Packing Dimensions
Height x Width x Depth mm 1,800 x 1,290 x 810 1,800 x 1,290 x 810 1,800 x 1,290 x 810
Approximate
Packing Measurement m3 1.9 1.9 1.9
NOTES:
1. The cooling and heating performances are the values when combined with our specified indoor units.
Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB)
o o
19.0 C WB (66.2 F WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
o o
Outdoor Air Inlet Temperature: 35 C DB (95 F DB) 6oC WB (43 oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure is based on the following conditions.
1 Meter from the unit service cover surface, and 1.5 Meters from floor level.
The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
※ The 11th digit of the model name indicate the power supply of each unit.
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz
Model
※
JTOR200VPE(U,F,R)BS1 JTOR220VPE(U,F,R)BS1 JTOR240VPE(U,F,R)BS1
Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz
Nominal Cooling Capacity kW 56.0 61.5 67.0
Nominal Heating Capacity kW 63.0 69.0 77.5
Cabinet Color (Munsell Code) Natural Gray (1.0Y 8.5/0.5)
Sound Power Level dB(A) 86 84 86
Sound Pressure Level dB(A) 65 64 66
Outer Dimensions
Height x Width x Depth mm 1,675 x 1,600 x 765 1,675 x 1,600 x 765 1,675 x 1,600 x 765
Net Weight
460V/60Hz kg 360 374 375
380V/60Hz kg 355 369 370
220V/60Hz kg 350 364 365
Gross Weight
460V/60Hz kg 380 394 395
380V/60Hz kg 375 389 390
220V/60Hz kg 370 384 385
Refrigerant R410A
Flow Control Micro-Computer Control Expansion Valve
Compressor
Model AA50PHD + AA50PHD DC80PHD + DC80PHD DC80PHD + DC80PHD
Quantity 2 2 2
Motor Output (Pole) kW 5.5 (6) x 2 6.7 (6) x 2 7.1 (6) x 2
Refrigeration Oil
Type FVC68D
Charge L/Unit 8.4 8.4 8.4
Heat Exchanger Multi-Pass Cross-Finned Tube
Condenser Fan Propeller Fan
Quantity 2 2 2
Air Flow Rate m 3/min. 329 329 348
Motor Output (Pole) kW 0.48 (8) x 2 0.48 (8) x 2 0.56 (8) x 2
Main Refrigerant Piping
Heat Recovery System (3 Pipes)
Liquid Line mm (in.) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Gas Line
Low Pressure mm (in.) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8)
High/Low Pressure mm (in.) 22.2 (7/8) 25.4 (1) 25.4 (1)
Refrigerant Charge
kg 11.3 11.3 11.6
(before Shipment)
Packing Dimensions
Height x Width x Depth mm 1,800 x 1,680 x 810 1,800 x 1,680 x 810 1,800 x 1,680 x 810
Approximate
Packing Measurement m3 2.4 2.4 2.4
NOTES:
1. The cooling and heating performances are the values when combined with our specified indoor units.
Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB)
o o
19.0 C WB (66.2 F WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
o o
Outdoor Air Inlet Temperature: 35 C DB (95 F DB) 6oC WB (43 oF WB)
Piping Length: 10 Meters Piping Lift: 0 Meter
2. The sound pressure is based on the following conditions.
1 Meter from the unit service cover surface, and 1.5 Meters from floor level.
The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
※ The 11th digit of the model name indicate the power supply of each unit.
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz
2.2 CH-Box
Appearance
3. Component Data
Model ※ JTOR080VPE(U, F, R)BS1 JTOR100VPE(U, F, R)BS1 JTOR120VPE(U, F, R)BS1 JTOR140VPE(U, F, R)BS1 JTOR160VPE(U, F, R)BS1
Heat Exchanger
Rows 2 2 3 3 3
Number of Coil/Unit 1 1 1 2 2
Number/Unit 1 1 1 2 2
Quantity 1 1 1 2 2
Insulation Class E E E E E
※ The 11th digit of the model name indicate the power supply of each unit. U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz
Model ※ JTOR180VPE(U, F, R)BS1 JTOR200VPE(U, F, R)BS1 JTOR220VPE(U, F, R)BS1 JTOR240VPE(U, F, R)BS1 JTOR260VAE(U, F, R)BS1
Heat Exchanger
Type Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0 7.0
Rows 3 3 3 3 3+3
Number of Tube/Coil 174 174 174 174 174 + 174
Fin Material Aluminum
Pitch mm 1.7 1.7 1.7 1.7 1.7
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15 4.15
Total Face Area m2 3.12 3.58 3.58 3.58 2.36 + 3.12
Number of Coil/Unit 2 2 2 2 3
Outdoor Fan Large Diameter Fan (Propeller Fan)
Number/Unit 2 2 2 2 3
Outer Diameter mm 544 + 544 644 + 644 644 + 644 644 + 644 644 + 544 + 544
Revolution rpm 1164 + 1164 888 + 888 888 + 888 936 + 936 852 + 1086 + 1086
Nominal Air Flow m3/min. 256 329 329 348 190 + 239
Outdoor Fan Motor Drip-Proof Type Enclosure
Starting Method DC Motor
Nominal Output W 390 + 390 480 + 480 480 + 480 560 + 560 420 + 330 + 330
Quantity 2 2 2 2 3
Insulation Class E E E E E+E
※ The 11th digit of the model name indicate the power supply of each unit. U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz
Model ※ JTOR280VAE(U, F, R)BS1 JTOR300VAE(U, F, R)BS1 JTOR320VAE(U, F, R)BS1 JTOR340VAE(U, F, R)BS1 JTOR360VAE(U, F, R)BS1
Heat Exchanger
Type Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0 7.0
Rows 3+3 3+3 3+3 3+3 3+3
Number of Tube/Coil 174 + 174 174 + 174 174 + 174 174 + 174 174 + 174
Fin Material Aluminum
Pitch mm 1.7 1.7 1.7 1.7 1.7
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15 4.15
Total Face Area m2 2.36 + 3.12 2.36 + 3.12 3.12 + 3.12 3.12 + 3.12 3.12 + 3.12
Number of Coil/Unit 3 3 4 4 4
Outdoor Fan Large Diameter Fan (Propeller Fan)
Number/Unit 3 3 4 4 4
Outer Diameter mm 644 + 544 + 544 644 + 544 + 544 544 + 544 + 544 + 544 544 + 544 + 544 + 544 544 + 544 + 544 + 544
Revolution rpm 852 + 1164 + 1164 852 + 1164 + 1164 1086 + 1086 + 1164 + 1164 1164 + 1164 + 1164 + 1164 1164 + 1164 + 1164 + 1164
Nominal Air Flow m3/min. 190 + 256 190 + 256 239 + 256 256 + 256 256 + 256
Outdoor Fan Motor Drip-Proof Type Enclosure
Starting Method DC Motor
Nominal Output W 420 + 390 + 390 420 + 390 + 390 330 + 330 + 390 + 390 390 + 390 + 390 + 390 390 + 390 + 390 + 390
Quantity 3 3 4 4 4
Insulation Class E+E E+E E+E E+E E+E
※ The 11th digit of the model name indicate the power supply of each unit. U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz
Model ※ JTOR380VAE(U, F, R)BS1 JTOR400VAE(U, F, R)BS1 JTOR420VAE(U, F, R)BS1 JTOR440VAE(U, F, R)BS1 JTOR460VAE(U, F, R)BS1
Heat Exchanger
Type Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0 7.0
Rows 3+ 3 3+3 3+3 3+3 3+3
Number of Tube/Coil 174 + 174 174 + 174 174 + 174 174 + 174 174 + 174
Fin Material Aluminum
Pitch mm 1.7 1.7 1.7 1.7 1.7
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15 4.15
Total Face Area m2 3.12 + 3.58 3.12 + 3.58 3.12 + 3.58 3.58 + 3.58 3.58 + 3.58
Number of Coil/Unit 4 4 4 4 4
Outdoor Fan Large Diameter Fan (Propeller Fan)
Number/Unit 4 4 4 4 4
Outer Diameter mm 544 + 544 + 644 + 644 544 + 544 + 644 + 644 544 + 544 + 644 + 644 644 + 644 + 644 + 644 644 + 644 + 644 + 644
Revolution rpm 1086 + 1086 + 936 + 936 1164 + 1164 + 888 + 888 1164 + 1164 + 936 + 936 888 + 888 + 888 + 888 888 + 888 + 936 + 936
Nominal Air Flow m3/min. 239 + 348 256 + 329 256 + 348 329 + 329 329 + 348
Outdoor Fan Motor Drip-Proof Type Enclosure
Starting Method DC Motor
Nominal Output W 330 + 330 + 560 + 560 390 + 390 + 480 + 480 390 + 390 + 560 + 560 480 + 480 + 480 + 480 480 + 480 + 560 + 560
Quantity 4 4 4 4 4
Insulation Class E+E E+E E+E E+E E+E
※ The 11th digit of the model name indicate the power supply of each unit. U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz
4. Dimensional Data
4.1 Outdoor Units
Unit: mm
Unit: mm
Unit: mm
4.2 CH-Box
Model: JCH-AP160SSX
Unit: mm
Model: JCH-AP280SSX
Unit: mm
Model: JCH-AP04MSSX
Unit: mm
Model: JCH-AP08MSSX
Unit: mm
Model: JCH-AP12MSSX
Unit: mm
Model: JCH-AP16MSSX
Unit: mm
5. Structure
5.1 Outdoor Units
Unit: mm
Model: JTOR140VPE(U,F,R)BS1
Unit: mm
Unit: mm
Unit: mm
5.2 CH-Box
Model: JCH-AP160SSX
Unit: mm
Model: JCH-AP280SSX
Unit: mm
Model: JCH-AP04MSSX
Unit: mm
Model: JCH-AP08MSSX
Unit: mm
Model: JCH-AP12MSSX
Unit: mm
Model: JCH-AP16MSSX
Unit: mm
6. Selection Data
6.1 Selection Guide
(1) Meaning of Model Name of Indoor Unit
Example J T KF 028 H0 P S A Q
Factory
Q: Quigdao, China
S: Shimizu, Japan
Generation
Power Supply
S: 220~240V/50Hz
220V/60Hz
Drain Pump
P: with Drain Pump
Heater
0: Not Equipped
Capacity
kW x 10
Indoor Unit Type
Market Position
T: Tier-1 Commercial VRF
Brand
J: York Brand
Unit Type
NOTE:
In-the-Ceiling Type (High Static) DH Select the indoor units and outdoor unit
In-the-Ceiling Type (Middle Static) DM so that the total indoor unit horsepower is
In-the-Ceiling Type (Low Static) DL near to the outdoor unit horsepower.
4-Way Cassette Type KF
4-Way Cassette Compact Type KM
2-Way Cassette Type KT
Wall Type HW
Floor Concealed Type FC
Ceiling Type CS
J T O R 080 V P E R B S 1
Version
Factory
S: Shimizu, Japan
Generation
Power Supply
U: 3~, 460V/60Hz
F: 3~/N, 380V/60Hz
R: 3~, 220V/60Hz
Refrigerant
E: R410A
Module and Combination
A: All Inverter Combination
P: All Inverter Module
Air Discharge
V: Vertical
Capacity
HP x 10 (Example: 080 = 8HP)
Application
R: Heat Recovery
Heat Source
O: Air Source
Market Position
T: Tier-1 Commercial VRF
Brand
J: York Brand
Horsepower (HP) 8 10 12 14 16 18
kW 22.4 28.0 33.5 40.0 45.0 50.0
Cooling
kcal/h 19,300 24,100 28,800 34,400 38,700 43,000
Capacity
Btu/h 76,400 95,500 114,300 136,500 153,500 170,600
kW 25.0 31.5 37.5 45.0 50.0 56.0
Heating
kcal/h 21,500 27,100 32,200 38,700 43,000 48,100
Capacity
Btu/h 85,300 107,500 128,000 153,500 170,600 191,100
Horsepower (HP) 20 22 24 26 28 30
kW 56.0 61.5 67.0 73.0 77.5 85.0
Cooling
kcal/h 48,100 52,800 57,600 62,700 66,600 73,100
Capacity
Btu/h 191,100 210,000 228,600 249,100 264,400 290,000
kW 63.0 69.0 77.5 82.5 90.0 95.0
Heating
kcal/h 54,100 59,300 66,600 70,900 77,400 81,700
Capacity
Btu/h 215,000 235,000 264,400 281,500 307,100 324,200
Horsepower (HP) 32 34 36 38 40 42
kW 90.0 95.0 100.0 106.0 112.0 118.0
Cooling
kcal/h 77,400 81,700 86,000 91,200 96,300 101,500
Capacity
Btu/h 307,100 324,200 341,200 361,700 382,200 402,600
kW 100.0 106.0 112.0 118.0 125.0 132.0
Heating
kcal/h 86,000 91,200 96,300 101,500 107,600 113,600
Capacity
Btu/h 341,200 361,700 382,200 402,600 426,500 450,400
Horsepower (HP) 44 46 48 50 52 54
kW 122.0 128.0 136.0 140.0 145.0 150.0
Cooling
kcal/h 104,900 110,100 117,000 120,400 124,700 129,000
Capacity
Btu/h 416,400 436,800 464,000 477,700 494,700 511,800
kW 140.0 145.0 150.0 155.0 160.0 165.0
Heating
kcal/h 120,400 124,700 129,000 133,300 137,600 141,900
Capacity
Btu/h 477,700 494,700 511,800 528,800 545,900 563,000
Nominal Capacity of Outdoor Unit is under the condition that the total indoor unit horsepower is the same
as outdoor unit horsepower.
Temperature Condition
Cooling Heating
Outdoor Coil Air Inlet Outdoor Coil Air Inlet
Dry Bulb: 30oC Dry Bulb: 1oC
Indoor Coil Air Inlet Wet Bulb: 0oC
Dry Bulb: 27oC Indoor Coil Air Inlet
Wet Bulb: 19oC Dry Bulb: 20oC
(1)+(2)+(3)+(4)
Item Room (6) Room (7) Outdoor
+(5)+(6)+(7)
Selected Model IDU-5.0HP IDU-5.0HP - ODU-22HP
Nominal kW 14.0 14.0 67.0 61.5
Cooling Capacity kcal/h 12,000 12,000 57,500 52,800
Nominal kW 16.0 16.0 76.8 69.0
Heating Capacity kcal/h 13,800 13,800 66,000 59,300
(*1): Refer to the table in item 6.2 for Correction Factor according to the total indoor unit capacity.
(*2): Refer to the table in item 6.4 “Correction Factor According to Piping Length”.
(*3): Refer to the table in item 6.3 for Correction Factor according to the temperature condition.
(*4): Refer to the table in item 6.5 “Correction Factor According to Defrosting Operation”.
(*5): Refer to the table in item 6.6 “Correction Factor According to Altitude”.
ex.
<IDU-2.0HP>
Cooling Capacity: 55.4x(2.0[HP]÷(2.0[HP]+2.5[HP]x2+3.0[HP]+4.0[HP]+5.0[HP]x2))=4.62kW (3,967kcal/h)
Heating Capacity: 59.6x(2.0[HP]÷(2.0[HP]+2.5[HP]x2+3.0[HP]+4.0[HP]+5.0[HP]x2))=4.97kW (4,273kcal/h)
<IDU-2.5HP>
Cooling Capacity: 55.4x(2.5[HP]÷(2.0[HP]+2.5[HP]x2+3.0[HP]+4.0[HP]+5.0[HP]x2))=5.77kW (4,958kcal/h)
Heating Capacity: 59.6x(2.5[HP]÷(2.0[HP]+2.5[HP]x2+3.0[HP]+4.0[HP]+5.0[HP]x2))=6.21kW (5,341kcal/h)
<IDU-3.0HP>
Cooling Capacity: 55.4x(3.0[HP]÷(2.0[HP]+2.5[HP]x2+3.0[HP]+4.0[HP]+5.0[HP]x2))=6.93kW (5,950kcal/h)
Heating Capacity: 59.6x(3.0[HP]÷(2.0[HP]+2.5[HP]x2+3.0[HP]+4.0[HP]+5.0[HP]x2))=7.45kW (6,409kcal/h)
<IDU-4.0HP>
Cooling Capacity: 55.4x(4.0[HP]÷(2.0[HP]+2.5[HP]x2+3.0[HP]+4.0[HP]+5.0[HP]x2))=9.23kW (7,933kcal/h)
Heating Capacity: 59.6x(4.0[HP]÷(2.0[HP]+2.5[HP]x2+3.0[HP]+4.0[HP]+5.0[HP]x2))=9.93kW (8,545kcal/h)
<IDU-5.0HP>
Cooling Capacity: 55.4x(5.0[HP]÷(2.0[HP]+2.5[HP]x2+3.0[HP]+4.0[HP]+5.0[HP]x2))=11.54kW (9,917kcal/h)
Heating Capacity: 59.6x(5.0[HP]÷(2.0[HP]+2.5[HP]x2+3.0[HP]+4.0[HP]+5.0[HP]x2))=12.42kW (10,681kcal/h)
(1)+(2)+(3)+(4)
Item Room (5) Room (6) Room (7)
+(5)+(6)+(7)
Selected Model IDU-4.0HP IDU-5.0HP IDU-5.0HP -
Actual Maximum kW 9.23 11.54 11.54 55.40
Actual Cooling Capacity kcal/h 7,933 9,917 9,917 47,600
Capacity Actual Maximum kW 9.93 12.42 12.42 59.61
Heating Capacity kcal/h 8,545 10,681 10,681 51,271
Estimated kW 8.48 10.6 10.6 50.98
Design Cooling Load kcal/h 7,295 9,119 9,119 43,855
Load Estimated kW 9.54 11.9 11.9 57.27
Heating Load kcal/h 8,207 10,238 10,238 49,263
[ Standard Type ]
A x 0.50
Standard Capacity
Allowable Capacity
Outdoor Unit (HP) A (kW) B (HP) Outdoor Unit (HP) A (kW) B (HP)
8 22.4 8 26 73.0 26
10 28.0 10 28 77.5 28
12 33.5 12 32 90.0 32
14 40.0 14 34 95.0 34
16 45.0 16 50 140.0 50
20 56.0 20
A x 1.03
A
Cooling Capacity (kW)
A x 0.50
0 B x 0.50 B B x 1.30
Standard Capacity
Allowable Capacity
Outdoor Unit (HP) A (kW) B (HP) Outdoor Unit (HP) A (kW) B (HP)
18 50.0 18 42 118.0 42
22 61.5 22 44 122.0 44
24 67.0 24 46 128.0 46
30 85.0 30 48 136.0 48
36 100.0 36 52 145.0 52
38 106.0 38 54 150.0 54
40 112.0 40
A x 1.04
A x 1.03
A
Heating Capacity (kW)
A x 0.50
Standard Capacity
Allowable Capacity
Outdoor Unit (HP) A (kW) B (HP) Outdoor Unit (HP) A (kW) B (HP)
8 25.0 8 26 82.5 26
10 31.5 10 28 90.0 28
12 37.5 12 32 100.0 32
14 45.0 14 34 106.0 34
16 50.0 16 50 155.0 50
20 56.0 18
A x 1.02
A
Heating Capacity (kW)
A x 0.50
0 B x 0.50 B B x 1.30
Standard Capacity
Allowable Capacity
Outdoor Unit (HP) A (kW) B (HP) Outdoor Unit (HP) A (kW) B (HP)
18 56.0 18 40 125.0 40
22 69.0 22 42 132.0 42
24 77.5 24 44 140.0 44
30 95.0 30 46 145.0 46
36 112.0 36 48 150.0 48
38 118.0 38 54 165.0 54
The following 41 tables show the examples of outdoor unit capacity which corresponds with total
horsepower of combined indoor unit, according to the item 6.2 "Capacity Characteristic Curve".
Table 1. Outdoor Unit Capacity (JTOR080~120VPE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (1)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-8FSXNS
JTOR080VPE(U,F,R)BS1 RAS-10FSXNS
JTOR100VPE(U,F,R)BS1 RAS-12FSXNS
JTOR120VPE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
4.0 11.20 ( 9.63 ) 12.50 ( 10.75 )
4.1 11.48 ( 9.87 ) 12.81 ( 11.02 )
4.2 11.76 ( 10.11 ) 13.13 ( 11.29 )
4.3 12.04 ( 10.35 ) 13.44 ( 11.55 )
4.4 12.32 ( 10.59 ) 13.75 ( 11.82 )
_
4.5 12.60 ( 10.83 ) 14.06 ( 12.09 )
4.6 12.88 ( 11.07 ) 14.38 ( 12.36 )
4.7 13.16 ( 11.32 ) 14.69 ( 12.63 )
4.8 13.44 ( 11.56 ) 15.00 ( 12.90 )
4.9 13.72 ( 11.80 ) 15.31 ( 13.17 )
_
5.0 14.00 ( 12.04 ) 15.63 ( 13.44 ) 14.00 ( 12.04 ) 15.75 ( 13.54 )
5.1 14.28 ( 12.28 ) 15.94 ( 13.70 ) 14.28 ( 12.28 ) 16.07 ( 13.81 )
5.2 14.56 ( 12.52 ) 16.25 ( 13.97 ) 14.56 ( 12.52 ) 16.38 ( 14.08 )
5.3 14.84 ( 12.76 ) 16.56 ( 14.24 ) 14.84 ( 12.76 ) 16.70 ( 14.36 )
5.4 15.12 ( 13.00 ) 16.88 ( 14.51 ) 15.12 ( 13.00 ) 17.01 ( 14.63 )
5.5 15.40 ( 13.24 ) 17.19 ( 14.78 ) 15.40 ( 13.24 ) 17.33 ( 14.90 )
5.6 15.68 ( 13.48 ) 17.50 ( 15.05 ) 15.68 ( 13.48 ) 17.64 ( 15.17 )
5.7 15.96 ( 13.72 ) 17.81 ( 15.32 ) 15.96 ( 13.72 ) 17.96 ( 15.44 )
5.8 16.24 ( 13.96 ) 18.13 ( 15.58 ) 16.24 ( 13.96 ) 18.27 ( 15.71 )
5.9 16.52 ( 14.20 ) 18.44 ( 15.85 ) 16.52 ( 14.20 ) 18.59 ( 15.98 )
6.0 16.80 ( 14.45 ) 18.75 ( 16.12 ) 16.80 ( 14.45 ) 18.90 ( 16.25 ) 16.75 ( 14.40 ) 18.75 ( 16.12 )
6.1 17.08 ( 14.69 ) 19.06 ( 16.39 ) 17.08 ( 14.69 ) 19.22 ( 16.52 ) 17.03 ( 14.64 ) 19.06 ( 16.39 )
6.2 17.36 ( 14.93 ) 19.38 ( 16.66 ) 17.36 ( 14.93 ) 19.53 ( 16.79 ) 17.31 ( 14.88 ) 19.38 ( 16.66 )
6.3 17.64 ( 15.17 ) 19.69 ( 16.93 ) 17.64 ( 15.17 ) 19.85 ( 17.06 ) 17.59 ( 15.12 ) 19.69 ( 16.93 )
6.4 17.92 ( 15.41 ) 20.00 ( 17.20 ) 17.92 ( 15.41 ) 20.16 ( 17.33 ) 17.87 ( 15.36 ) 20.00 ( 17.20 )
6.5 18.20 ( 15.65 ) 20.31 ( 17.47 ) 18.20 ( 15.65 ) 20.48 ( 17.61 ) 18.15 ( 15.60 ) 20.31 ( 17.47 )
6.6 18.48 ( 15.89 ) 20.63 ( 17.73 ) 18.48 ( 15.89 ) 20.79 ( 17.88 ) 18.43 ( 15.84 ) 20.63 ( 17.73 )
6.7 18.76 ( 16.13 ) 20.94 ( 18.00 ) 18.76 ( 16.13 ) 21.11 ( 18.15 ) 18.70 ( 16.08 ) 20.94 ( 18.00 )
6.8 19.04 ( 16.37 ) 21.25 ( 18.27 ) 19.04 ( 16.37 ) 21.42 ( 18.42 ) 18.98 ( 16.32 ) 21.25 ( 18.27 )
6.9 19.32 ( 16.61 ) 21.56 ( 18.54 ) 19.32 ( 16.61 ) 21.74 ( 18.69 ) 19.26 ( 16.56 ) 21.56 ( 18.54 )
7.0 19.60 ( 16.85 ) 21.88 ( 18.81 ) 19.60 ( 16.85 ) 22.05 ( 18.96 ) 19.54 ( 16.80 ) 21.88 ( 18.81 )
7.1 19.88 ( 17.09 ) 22.19 ( 19.08 ) 19.88 ( 17.09 ) 22.37 ( 19.23 ) 19.82 ( 17.04 ) 22.19 ( 19.08 )
7.2 20.16 ( 17.33 ) 22.50 ( 19.35 ) 20.16 ( 17.33 ) 22.68 ( 19.50 ) 20.10 ( 17.28 ) 22.50 ( 19.35 )
7.3 20.44 ( 17.58 ) 22.81 ( 19.62 ) 20.44 ( 17.58 ) 23.00 ( 19.77 ) 20.38 ( 17.52 ) 22.81 ( 19.62 )
7.4 20.72 ( 17.82 ) 23.13 ( 19.88 ) 20.72 ( 17.82 ) 23.31 ( 20.04 ) 20.66 ( 17.76 ) 23.13 ( 19.88 )
7.5 21.00 ( 18.06 ) 23.44 ( 20.15 ) 21.00 ( 18.06 ) 23.63 ( 20.31 ) 20.94 ( 18.00 ) 23.44 ( 20.15 )
7.6 21.28 ( 18.30 ) 23.75 ( 20.42 ) 21.28 ( 18.30 ) 23.94 ( 20.58 ) 21.22 ( 18.24 ) 23.75 ( 20.42 )
7.7 21.56 ( 18.54 ) 24.06 ( 20.69 ) 21.56 ( 18.54 ) 24.26 ( 20.86 ) 21.50 ( 18.48 ) 24.06 ( 20.69 )
7.8 21.84 ( 18.78 ) 24.38 ( 20.96 ) 21.84 ( 18.78 ) 24.57 ( 21.13 ) 21.78 ( 18.72 ) 24.38 ( 20.96 )
7.9 22.12 ( 19.02 ) 24.69 ( 21.23 ) 22.12 ( 19.02 ) 24.89 ( 21.40 ) 22.05 ( 18.96 ) 24.69 ( 21.23 )
8.0 22.40 ( 19.26 ) 25.00 ( 21.50 ) 22.40 ( 19.26 ) 25.20 ( 21.67 ) 22.33 ( 19.20 ) 25.00 ( 21.50 )
8.1 22.68 ( 19.50 ) 25.31 ( 21.76 ) 22.68 ( 19.50 ) 25.52 ( 21.94 ) 22.61 ( 19.44 ) 25.31 ( 21.76 )
8.2 22.96 ( 19.74 ) 25.63 ( 22.03 ) 22.96 ( 19.74 ) 25.83 ( 22.21 ) 22.89 ( 19.68 ) 25.63 ( 22.03 )
8.3 23.09 ( 19.85 ) 25.76 ( 22.15 ) 23.24 ( 19.98 ) 26.15 ( 22.48 ) 23.17 ( 19.92 ) 25.94 ( 22.30 )
8.4 23.12 ( 19.88 ) 25.77 ( 22.16 ) 23.52 ( 20.22 ) 26.46 ( 22.75 ) 23.45 ( 20.16 ) 26.25 ( 22.57 )
8.5 23.15 ( 19.91 ) 25.78 ( 22.17 ) 23.80 ( 20.46 ) 26.78 ( 23.02 ) 23.73 ( 20.40 ) 26.56 ( 22.84 )
8.6 23.18 ( 19.93 ) 25.79 ( 22.18 ) 24.08 ( 20.71 ) 27.09 ( 23.29 ) 24.01 ( 20.64 ) 26.87 ( 23.11 )
8.7 23.22 ( 19.96 ) 25.80 ( 22.19 ) 24.36 ( 20.95 ) 27.41 ( 23.56 ) 24.29 ( 20.88 ) 27.19 ( 23.38 )
8.8 23.25 ( 19.99 ) 25.81 ( 22.20 ) 24.64 ( 21.19 ) 27.72 ( 23.83 ) 24.57 ( 21.12 ) 27.50 ( 23.65 )
8.9 23.28 ( 20.01 ) 25.83 ( 22.21 ) 24.92 ( 21.43 ) 28.04 ( 24.11 ) 24.85 ( 21.36 ) 27.81 ( 23.91 )
9.0 23.31 ( 20.04 ) 25.84 ( 22.22 ) 25.20 ( 21.67 ) 28.35 ( 24.38 ) 25.12 ( 21.60 ) 28.12 ( 24.18 )
9.1 23.34 ( 20.07 ) 25.85 ( 22.23 ) 25.48 ( 21.91 ) 28.67 ( 24.65 ) 25.40 ( 21.84 ) 28.44 ( 24.45 )
9.2 23.37 ( 20.10 ) 25.86 ( 22.24 ) 25.76 ( 22.15 ) 28.98 ( 24.92 ) 25.68 ( 22.08 ) 28.75 ( 24.72 )
9.3 23.40 ( 20.12 ) 25.87 ( 22.25 ) 26.04 ( 22.39 ) 29.30 ( 25.19 ) 25.96 ( 22.32 ) 29.06 ( 24.99 )
9.4 23.43 ( 20.15 ) 25.88 ( 22.26 ) 26.32 ( 22.63 ) 29.61 ( 25.46 ) 26.24 ( 22.56 ) 29.37 ( 25.26 )
9.5 23.46 ( 20.18 ) 25.90 ( 22.27 ) 26.60 ( 22.87 ) 29.93 ( 25.73 ) 26.52 ( 22.80 ) 29.69 ( 25.53 )
9.6 23.50 ( 20.20 ) 25.91 ( 22.28 ) 26.88 ( 23.11 ) 30.24 ( 26.00 ) 26.80 ( 23.04 ) 30.00 ( 25.80 )
9.7 23.53 ( 20.23 ) 25.92 ( 22.29 ) 27.16 ( 23.35 ) 30.56 ( 26.27 ) 27.08 ( 23.28 ) 30.31 ( 26.06 )
9.8 23.56 ( 20.26 ) 25.93 ( 22.30 ) 27.44 ( 23.59 ) 30.87 ( 26.54 ) 27.36 ( 23.52 ) 30.62 ( 26.33 )
9.9 23.59 ( 20.28 ) 25.94 ( 22.31 ) 27.72 ( 23.83 ) 31.19 ( 26.81 ) 27.64 ( 23.76 ) 30.94 ( 26.60 )
Table 2. Outdoor Unit Capacity (JTOR080~120VPE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (2)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-8FSXNS
JTOR080VPE(U,F,R)BS1 RAS-10FSXNS
JTOR100VPE(U,F,R)BS1 RAS-12FSXNS
JTOR120VPE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
10.0 23.62 ( 20.31 ) 25.95 ( 22.32 ) 28.00 ( 24.08 ) 31.50 ( 27.09 ) 27.92 ( 24.00 ) 31.25 ( 26.87 )
10.1 23.65 ( 20.34 ) 25.97 ( 22.33 ) 28.28 ( 24.32 ) 31.82 ( 27.36 ) 28.20 ( 24.24 ) 31.56 ( 27.14 )
10.2 23.68 ( 20.36 ) 25.98 ( 22.34 ) 28.56 ( 24.56 ) 32.13 ( 27.63 ) 28.48 ( 24.48 ) 31.88 ( 27.41 )
10.3 23.71 ( 20.39 ) 25.99 ( 22.35 ) 28.84 ( 24.80 ) 32.45 ( 27.90 ) 28.75 ( 24.72 ) 32.19 ( 27.68 )
10.4 23.74 ( 20.42 ) 26.00 ( 22.36 ) 28.87 ( 24.82 ) 32.46 ( 27.91 ) 29.03 ( 24.96 ) 32.50 ( 27.94 )
10.5 28.90 ( 24.85 ) 32.47 ( 27.92 ) 29.31 ( 25.20 ) 32.81 ( 28.21 )
10.6 28.93 ( 24.88 ) 32.48 ( 27.93 ) 29.59 ( 25.44 ) 33.13 ( 28.48 )
10.7 28.96 ( 24.90 ) 32.49 ( 27.94 ) 29.87 ( 25.68 ) 33.44 ( 28.75 )
10.8 29.00 ( 24.93 ) 32.50 ( 27.95 ) 30.15 ( 25.92 ) 33.75 ( 29.02 )
10.9 29.03 ( 24.96 ) 32.52 ( 27.96 ) 30.43 ( 26.16 ) 34.06 ( 29.29 )
11.0 29.06 ( 24.99 ) 32.53 ( 27.97 ) 30.71 ( 26.40 ) 34.38 ( 29.56 )
11.1 29.09 ( 25.01 ) 32.54 ( 27.98 ) 30.99 ( 26.64 ) 34.69 ( 29.83 )
11.2 29.12 ( 25.04 ) 32.55 ( 27.99 ) 31.27 ( 26.88 ) 35.00 ( 30.09 )
11.3 29.15 ( 25.07 ) 32.56 ( 28.00 ) 31.55 ( 27.12 ) 35.31 ( 30.36 )
11.4 29.18 ( 25.09 ) 32.57 ( 28.01 ) 31.83 ( 27.36 ) 35.63 ( 30.63 )
11.5 29.21 ( 25.12 ) 32.59 ( 28.02 ) 32.10 ( 27.60 ) 35.94 ( 30.90 )
11.6 29.24 ( 25.15 ) 32.60 ( 28.03 ) 32.38 ( 27.84 ) 36.25 ( 31.17 )
11.7 29.28 ( 25.17 ) 32.61 ( 28.04 ) 32.66 ( 28.08 ) 36.56 ( 31.44 )
11.8 29.31 ( 25.20 ) 32.62 ( 28.05 ) 32.94 ( 28.32 ) 36.88 ( 31.71 )
11.9 29.34 ( 25.23 ) 32.63 ( 28.06 ) 33.22 ( 28.56 ) 37.19 ( 31.98 )
12.0 29.37 ( 25.25 ) 32.64 ( 28.07 ) 33.50 ( 28.80 ) 37.50 ( 32.24 )
12.1 29.40 ( 25.28 ) 32.66 ( 28.08 ) 33.78 ( 29.04 ) 37.81 ( 32.51 )
12.2 29.43 ( 25.31 ) 32.67 ( 28.09 ) 34.06 ( 29.28 ) 38.13 ( 32.78 )
12.3 29.46 ( 25.33 ) 32.68 ( 28.10 ) 34.34 ( 29.52 ) 38.44 ( 33.05 )
12.4 29.49 ( 25.36 ) 32.69 ( 28.11 ) 34.52 ( 29.68 ) 38.63 ( 33.22 )
12.5 29.52 ( 25.39 ) 32.70 ( 28.12 ) 34.55 ( 29.71 ) 38.64 ( 33.23 )
12.6 29.56 ( 25.41 ) 32.71 ( 28.13 ) 34.58 ( 29.73 ) 38.65 ( 33.24 )
12.7 29.59 ( 25.44 ) 32.73 ( 28.14 ) 34.61 ( 29.76 ) 38.66 ( 33.25 )
12.8 29.62 ( 25.47 ) 32.74 ( 28.15 ) 34.64 ( 29.79 ) 38.68 ( 33.26 )
12.9 29.65 ( 25.49 ) 32.75 ( 28.16 ) 34.67 ( 29.81 ) 38.69 ( 33.27 )
13.0 29.68 ( 25.52 ) 32.76 ( 28.17 ) 34.70 ( 29.84 ) 38.70 ( 33.28 )
_
13.1 34.73 ( 29.87 ) 38.71 ( 33.29 )
13.2 34.77 ( 29.89 ) 38.72 ( 33.30 )
13.3 34.80 ( 29.92 ) 38.73 ( 33.31 )
13.4 34.83 ( 29.95 ) 38.75 ( 33.32 )
13.5 34.86 ( 29.97 ) 38.76 ( 33.32 )
13.6 34.89 ( 30.00 ) 38.77 ( 33.33 )
13.7 34.92 ( 30.03 ) 38.78 ( 33.34 )
13.8 34.95 ( 30.05 ) 38.79 ( 33.35 )
13.9 34.98 ( 30.08 ) 38.80 ( 33.36 )
14.0 35.01 ( 30.11 ) 38.81 ( 33.37 )
14.1 35.04 ( 30.13 ) 38.83 ( 33.38 )
14.2 35.08 ( 30.16 ) 38.84 ( 33.39 )
14.3 35.11 ( 30.19 ) 38.85 ( 33.40 )
_
14.4 35.14 ( 30.21 ) 38.86 ( 33.41 )
14.5 35.17 ( 30.24 ) 38.87 ( 33.42 )
14.6 35.20 ( 30.27 ) 38.88 ( 33.43 )
14.7 35.23 ( 30.29 ) 38.90 ( 33.44 )
14.8 35.26 ( 30.32 ) 38.91 ( 33.45 )
14.9 35.29 ( 30.35 ) 38.92 ( 33.46 )
15.0 35.32 ( 30.37 ) 38.93 ( 33.47 )
15.1 35.35 ( 30.40 ) 38.94 ( 33.48 )
15.2 35.39 ( 30.43 ) 38.95 ( 33.49 )
15.3 35.42 ( 30.45 ) 38.97 ( 33.50 )
15.4 35.45 ( 30.48 ) 38.98 ( 33.51 )
15.5 35.48 ( 30.51 ) 38.99 ( 33.52 )
15.6 35.51 ( 30.53 ) 39.00 ( 33.53 )
Table 3. Outdoor Unit Capacity (JTOR140~180VPE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (1)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-14FSXNS
JTOR140VPE(U,F,R)BS1 RAS-16FSXNS
JTOR160VPE(U,F,R)BS1 RAS-18FSXNS
JTOR180VPE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
7.0 20.00 ( 17.20 ) 22.50 ( 19.35 )
7.1 20.29 ( 17.44 ) 22.82 ( 19.62 )
7.2 20.57 ( 17.69 ) 23.14 ( 19.90 )
7.3 20.86 ( 17.93 ) 23.46 ( 20.18 )
7.4 21.14 ( 18.18 ) 23.79 ( 20.45 )
_
7.5 21.43 ( 18.43 ) 24.11 ( 20.73 )
7.6 21.71 ( 18.67 ) 24.43 ( 21.00 )
7.7 22.00 ( 18.92 ) 24.75 ( 21.28 )
7.8 22.29 ( 19.16 ) 25.07 ( 21.56 )
7.9 22.57 ( 19.41 ) 25.39 ( 21.83 )
_
8.0 22.86 ( 19.65 ) 25.71 ( 22.11 ) 22.50 ( 19.35 ) 25.00 ( 21.50 )
8.1 23.14 ( 19.90 ) 26.04 ( 22.39 ) 22.78 ( 19.59 ) 25.31 ( 21.76 )
8.2 23.43 ( 20.14 ) 26.36 ( 22.66 ) 23.06 ( 19.83 ) 25.62 ( 22.03 )
8.3 23.71 ( 20.39 ) 26.68 ( 22.94 ) 23.34 ( 20.07 ) 25.94 ( 22.30 )
8.4 24.00 ( 20.64 ) 27.00 ( 23.22 ) 23.62 ( 20.31 ) 26.25 ( 22.57 )
8.5 24.29 ( 20.88 ) 27.32 ( 23.49 ) 23.91 ( 20.56 ) 26.56 ( 22.84 )
8.6 24.57 ( 21.13 ) 27.64 ( 23.77 ) 24.19 ( 20.80 ) 26.87 ( 23.11 )
8.7 24.86 ( 21.37 ) 27.96 ( 24.04 ) 24.47 ( 21.04 ) 27.19 ( 23.38 )
8.8 25.14 ( 21.62 ) 28.29 ( 24.32 ) 24.75 ( 21.28 ) 27.50 ( 23.65 )
8.9 25.43 ( 21.86 ) 28.61 ( 24.60 ) 25.03 ( 21.52 ) 27.81 ( 23.91 )
9.0 25.71 ( 22.11 ) 28.93 ( 24.87 ) 25.31 ( 21.76 ) 28.12 ( 24.18 ) 25.00 ( 21.50 ) 28.00 ( 24.08 )
9.1 26.00 ( 22.36 ) 29.25 ( 25.15 ) 25.59 ( 22.01 ) 28.44 ( 24.45 ) 25.28 ( 21.73 ) 28.31 ( 24.34 )
9.2 26.29 ( 22.60 ) 29.57 ( 25.43 ) 25.87 ( 22.25 ) 28.75 ( 24.72 ) 25.56 ( 21.97 ) 28.62 ( 24.61 )
9.3 26.57 ( 22.85 ) 29.89 ( 25.70 ) 26.16 ( 22.49 ) 29.06 ( 24.99 ) 25.83 ( 22.21 ) 28.93 ( 24.88 )
9.4 26.86 ( 23.09 ) 30.21 ( 25.98 ) 26.44 ( 22.73 ) 29.37 ( 25.26 ) 26.11 ( 22.45 ) 29.24 ( 25.15 )
9.5 27.14 ( 23.34 ) 30.54 ( 26.26 ) 26.72 ( 22.97 ) 29.69 ( 25.53 ) 26.39 ( 22.69 ) 29.56 ( 25.41 )
9.6 27.43 ( 23.58 ) 30.86 ( 26.53 ) 27.00 ( 23.22 ) 30.00 ( 25.80 ) 26.67 ( 22.93 ) 29.87 ( 25.68 )
9.7 27.71 ( 23.83 ) 31.18 ( 26.81 ) 27.28 ( 23.46 ) 30.31 ( 26.06 ) 26.94 ( 23.17 ) 30.18 ( 25.95 )
9.8 28.00 ( 24.08 ) 31.50 ( 27.09 ) 27.56 ( 23.70 ) 30.62 ( 26.33 ) 27.22 ( 23.41 ) 30.49 ( 26.22 )
9.9 28.29 ( 24.32 ) 31.82 ( 27.36 ) 27.84 ( 23.94 ) 30.94 ( 26.60 ) 27.50 ( 23.65 ) 30.80 ( 26.48 )
10.0 28.57 ( 24.57 ) 32.14 ( 27.64 ) 28.12 ( 24.18 ) 31.25 ( 26.87 ) 27.78 ( 23.88 ) 31.11 ( 26.75 )
10.1 28.86 ( 24.81 ) 32.46 ( 27.91 ) 28.41 ( 24.42 ) 31.56 ( 27.14 ) 28.06 ( 24.12 ) 31.42 ( 27.02 )
10.2 29.14 ( 25.06 ) 32.79 ( 28.19 ) 28.69 ( 24.67 ) 31.87 ( 27.41 ) 28.33 ( 24.36 ) 31.73 ( 27.29 )
10.3 29.43 ( 25.30 ) 33.11 ( 28.47 ) 28.97 ( 24.91 ) 32.19 ( 27.68 ) 28.61 ( 24.60 ) 32.04 ( 27.55 )
10.4 29.71 ( 25.55 ) 33.43 ( 28.74 ) 29.25 ( 25.15 ) 32.50 ( 27.94 ) 28.89 ( 24.84 ) 32.36 ( 27.82 )
10.5 30.00 ( 25.80 ) 33.75 ( 29.02 ) 29.53 ( 25.39 ) 32.81 ( 28.21 ) 29.17 ( 25.08 ) 32.67 ( 28.09 )
10.6 30.29 ( 26.04 ) 34.07 ( 29.30 ) 29.81 ( 25.63 ) 33.12 ( 28.48 ) 29.44 ( 25.32 ) 32.98 ( 28.36 )
10.7 30.57 ( 26.29 ) 34.39 ( 29.57 ) 30.09 ( 25.88 ) 33.44 ( 28.75 ) 29.72 ( 25.56 ) 33.29 ( 28.62 )
10.8 30.86 ( 26.53 ) 34.71 ( 29.85 ) 30.37 ( 26.12 ) 33.75 ( 29.02 ) 30.00 ( 25.80 ) 33.60 ( 28.89 )
10.9 31.14 ( 26.78 ) 35.04 ( 30.13 ) 30.66 ( 26.36 ) 34.06 ( 29.29 ) 30.28 ( 26.03 ) 33.91 ( 29.16 )
11.0 31.43 ( 27.02 ) 35.36 ( 30.40 ) 30.94 ( 26.60 ) 34.37 ( 29.56 ) 30.56 ( 26.27 ) 34.22 ( 29.43 )
11.1 31.71 ( 27.27 ) 35.68 ( 30.68 ) 31.22 ( 26.84 ) 34.69 ( 29.83 ) 30.83 ( 26.51 ) 34.53 ( 29.69 )
11.2 32.00 ( 27.52 ) 36.00 ( 30.95 ) 31.50 ( 27.09 ) 35.00 ( 30.09 ) 31.11 ( 26.75 ) 34.84 ( 29.96 )
11.3 32.29 ( 27.76 ) 36.32 ( 31.23 ) 31.78 ( 27.33 ) 35.31 ( 30.36 ) 31.39 ( 26.99 ) 35.16 ( 30.23 )
11.4 32.57 ( 28.01 ) 36.64 ( 31.51 ) 32.06 ( 27.57 ) 35.62 ( 30.63 ) 31.67 ( 27.23 ) 35.47 ( 30.50 )
11.5 32.86 ( 28.25 ) 36.96 ( 31.78 ) 32.34 ( 27.81 ) 35.94 ( 30.90 ) 31.94 ( 27.47 ) 35.78 ( 30.76 )
11.6 33.14 ( 28.50 ) 37.29 ( 32.06 ) 32.62 ( 28.05 ) 36.25 ( 31.17 ) 32.22 ( 27.71 ) 36.09 ( 31.03 )
11.7 33.43 ( 28.74 ) 37.61 ( 32.34 ) 32.91 ( 28.29 ) 36.56 ( 31.44 ) 32.50 ( 27.94 ) 36.40 ( 31.30 )
11.8 33.71 ( 28.99 ) 37.93 ( 32.61 ) 33.19 ( 28.54 ) 36.87 ( 31.71 ) 32.78 ( 28.18 ) 36.71 ( 31.57 )
11.9 34.00 ( 29.23 ) 38.25 ( 32.89 ) 33.47 ( 28.78 ) 37.19 ( 31.98 ) 33.06 ( 28.42 ) 37.02 ( 31.83 )
12.0 34.29 ( 29.48 ) 38.57 ( 33.17 ) 33.75 ( 29.02 ) 37.50 ( 32.24 ) 33.33 ( 28.66 ) 37.33 ( 32.10 )
12.1 34.57 ( 29.73 ) 38.89 ( 33.44 ) 34.03 ( 29.26 ) 37.81 ( 32.51 ) 33.61 ( 28.90 ) 37.64 ( 32.37 )
12.2 34.86 ( 29.97 ) 39.21 ( 33.72 ) 34.31 ( 29.50 ) 38.12 ( 32.78 ) 33.89 ( 29.14 ) 37.96 ( 32.64 )
12.3 35.14 ( 30.22 ) 39.54 ( 33.99 ) 34.59 ( 29.75 ) 38.44 ( 33.05 ) 34.17 ( 29.38 ) 38.27 ( 32.90 )
12.4 35.43 ( 30.46 ) 39.86 ( 34.27 ) 34.87 ( 29.99 ) 38.75 ( 33.32 ) 34.44 ( 29.62 ) 38.58 ( 33.17 )
12.5 35.71 ( 30.71 ) 40.18 ( 34.55 ) 35.16 ( 30.23 ) 39.06 ( 33.59 ) 34.72 ( 29.86 ) 38.89 ( 33.44 )
12.6 36.00 ( 30.95 ) 40.50 ( 34.82 ) 35.44 ( 30.47 ) 39.37 ( 33.86 ) 35.00 ( 30.09 ) 39.20 ( 33.71 )
12.7 36.29 ( 31.20 ) 40.82 ( 35.10 ) 35.72 ( 30.71 ) 39.69 ( 34.13 ) 35.28 ( 30.33 ) 39.51 ( 33.97 )
12.8 36.57 ( 31.45 ) 41.14 ( 35.38 ) 36.00 ( 30.95 ) 40.00 ( 34.39 ) 35.56 ( 30.57 ) 39.82 ( 34.24 )
12.9 36.86 ( 31.69 ) 41.46 ( 35.65 ) 36.28 ( 31.20 ) 40.31 ( 34.66 ) 35.83 ( 30.81 ) 40.13 ( 34.51 )
Table 4. Outdoor Unit Capacity (JTOR140~180VPE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (2)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-14FSXNS
JTOR140VPE(U,F,R)BS1 RAS-16FSXNS
JTOR160VPE(U,F,R)BS1 RAS-18FSXNS
JTOR180VPE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
13.0 37.14 ( 31.94 ) 41.79 ( 35.93 ) 36.56 ( 31.44 ) 40.62 ( 34.93 ) 36.11 ( 31.05 ) 40.44 ( 34.78 )
13.1 37.43 ( 32.18 ) 42.11 ( 36.21 ) 36.84 ( 31.68 ) 40.94 ( 35.20 ) 36.39 ( 31.29 ) 40.76 ( 35.04 )
13.2 37.71 ( 32.43 ) 42.43 ( 36.48 ) 37.12 ( 31.92 ) 41.25 ( 35.47 ) 36.67 ( 31.53 ) 41.07 ( 35.31 )
13.3 38.00 ( 32.67 ) 42.75 ( 36.76 ) 37.41 ( 32.16 ) 41.56 ( 35.74 ) 36.94 ( 31.77 ) 41.38 ( 35.58 )
13.4 38.29 ( 32.92 ) 43.07 ( 37.03 ) 37.69 ( 32.41 ) 41.87 ( 36.01 ) 37.22 ( 32.01 ) 41.69 ( 35.85 )
13.5 38.57 ( 33.17 ) 43.39 ( 37.31 ) 37.97 ( 32.65 ) 42.19 ( 36.27 ) 37.50 ( 32.24 ) 42.00 ( 36.11 )
13.6 38.86 ( 33.41 ) 43.71 ( 37.59 ) 38.25 ( 32.89 ) 42.50 ( 36.54 ) 37.78 ( 32.48 ) 42.31 ( 36.38 )
13.7 39.14 ( 33.66 ) 44.04 ( 37.86 ) 38.53 ( 33.13 ) 42.81 ( 36.81 ) 38.06 ( 32.72 ) 42.62 ( 36.65 )
13.8 39.43 ( 33.90 ) 44.36 ( 38.14 ) 38.81 ( 33.37 ) 43.12 ( 37.08 ) 38.33 ( 32.96 ) 42.93 ( 36.92 )
13.9 39.71 ( 34.15 ) 44.68 ( 38.42 ) 39.09 ( 33.61 ) 43.44 ( 37.35 ) 38.61 ( 33.20 ) 43.24 ( 37.18 )
14.0 40.00 ( 34.39 ) 45.00 ( 38.69 ) 39.37 ( 33.86 ) 43.75 ( 37.62 ) 38.89 ( 33.44 ) 43.56 ( 37.45 )
14.1 40.29 ( 34.64 ) 45.32 ( 38.97 ) 39.66 ( 34.10 ) 44.06 ( 37.89 ) 39.17 ( 33.68 ) 43.87 ( 37.72 )
14.2 40.57 ( 34.89 ) 45.64 ( 39.25 ) 39.94 ( 34.34 ) 44.38 ( 38.16 ) 39.44 ( 33.92 ) 44.18 ( 37.99 )
14.3 40.86 ( 35.13 ) 45.96 ( 39.52 ) 40.22 ( 34.58 ) 44.69 ( 38.42 ) 39.72 ( 34.15 ) 44.49 ( 38.25 )
14.4 41.14 ( 35.38 ) 46.29 ( 39.80 ) 40.50 ( 34.82 ) 45.00 ( 38.69 ) 40.00 ( 34.39 ) 44.80 ( 38.52 )
14.5 41.23 ( 35.45 ) 46.36 ( 39.86 ) 40.78 ( 35.07 ) 45.31 ( 38.96 ) 40.28 ( 34.63 ) 45.11 ( 38.79 )
14.6 41.26 ( 35.47 ) 46.37 ( 39.87 ) 41.06 ( 35.31 ) 45.63 ( 39.23 ) 40.56 ( 34.87 ) 45.42 ( 39.06 )
14.7 41.29 ( 35.50 ) 46.38 ( 39.88 ) 41.34 ( 35.55 ) 45.94 ( 39.50 ) 40.83 ( 35.11 ) 45.73 ( 39.32 )
14.8 41.32 ( 35.53 ) 46.40 ( 39.89 ) 41.63 ( 35.79 ) 46.25 ( 39.77 ) 41.11 ( 35.35 ) 46.04 ( 39.59 )
14.9 41.35 ( 35.56 ) 46.41 ( 39.90 ) 41.91 ( 36.03 ) 46.56 ( 40.04 ) 41.39 ( 35.59 ) 46.36 ( 39.86 )
15.0 41.38 ( 35.58 ) 46.42 ( 39.91 ) 42.19 ( 36.27 ) 46.88 ( 40.31 ) 41.67 ( 35.83 ) 46.67 ( 40.13 )
15.1 41.42 ( 35.61 ) 46.43 ( 39.92 ) 42.47 ( 36.52 ) 47.19 ( 40.57 ) 41.94 ( 36.07 ) 46.98 ( 40.39 )
15.2 41.45 ( 35.64 ) 46.44 ( 39.93 ) 42.75 ( 36.76 ) 47.50 ( 40.84 ) 42.22 ( 36.30 ) 47.29 ( 40.66 )
15.3 41.48 ( 35.67 ) 46.45 ( 39.94 ) 43.03 ( 37.00 ) 47.81 ( 41.11 ) 42.50 ( 36.54 ) 47.60 ( 40.93 )
15.4 41.51 ( 35.69 ) 46.47 ( 39.95 ) 43.31 ( 37.24 ) 48.13 ( 41.38 ) 42.78 ( 36.78 ) 47.91 ( 41.20 )
15.5 41.54 ( 35.72 ) 46.48 ( 39.96 ) 43.59 ( 37.48 ) 48.44 ( 41.65 ) 43.06 ( 37.02 ) 48.22 ( 41.46 )
15.6 41.57 ( 35.75 ) 46.49 ( 39.97 ) 43.88 ( 37.73 ) 48.75 ( 41.92 ) 43.33 ( 37.26 ) 48.53 ( 41.73 )
15.7 41.61 ( 35.78 ) 46.50 ( 39.98 ) 44.16 ( 37.97 ) 49.06 ( 42.19 ) 43.61 ( 37.50 ) 48.84 ( 42.00 )
15.8 41.64 ( 35.80 ) 46.51 ( 40.00 ) 44.44 ( 38.21 ) 49.38 ( 42.45 ) 43.89 ( 37.74 ) 49.16 ( 42.27 )
15.9 41.67 ( 35.83 ) 46.53 ( 40.01 ) 44.72 ( 38.45 ) 49.69 ( 42.72 ) 44.17 ( 37.98 ) 49.47 ( 42.53 )
16.0 41.70 ( 35.86 ) 46.54 ( 40.02 ) 45.00 ( 38.69 ) 50.00 ( 42.99 ) 44.44 ( 38.22 ) 49.78 ( 42.80 )
16.1 41.73 ( 35.88 ) 46.55 ( 40.03 ) 45.03 ( 38.72 ) 50.02 ( 43.01 ) 44.72 ( 38.45 ) 50.09 ( 43.07 )
16.2 41.77 ( 35.91 ) 46.56 ( 40.04 ) 45.06 ( 38.74 ) 50.04 ( 43.03 ) 45.00 ( 38.69 ) 50.40 ( 43.34 )
16.3 41.80 ( 35.94 ) 46.57 ( 40.05 ) 45.08 ( 38.77 ) 50.06 ( 43.05 ) 45.28 ( 38.93 ) 50.71 ( 43.60 )
16.4 41.83 ( 35.97 ) 46.59 ( 40.06 ) 45.11 ( 38.79 ) 50.08 ( 43.06 ) 45.56 ( 39.17 ) 51.02 ( 43.87 )
16.5 41.86 ( 35.99 ) 46.60 ( 40.07 ) 45.14 ( 38.81 ) 50.10 ( 43.08 ) 45.83 ( 39.41 ) 51.33 ( 44.14 )
16.6 41.89 ( 36.02 ) 46.61 ( 40.08 ) 45.17 ( 38.84 ) 50.13 ( 43.10 ) 46.11 ( 39.65 ) 51.64 ( 44.41 )
16.7 41.92 ( 36.05 ) 46.62 ( 40.09 ) 45.20 ( 38.86 ) 50.15 ( 43.12 ) 46.39 ( 39.89 ) 51.96 ( 44.67 )
16.8 41.96 ( 36.08 ) 46.63 ( 40.10 ) 45.23 ( 38.89 ) 50.17 ( 43.14 ) 46.67 ( 40.13 ) 52.27 ( 44.94 )
16.9 41.99 ( 36.10 ) 46.65 ( 40.11 ) 45.25 ( 38.91 ) 50.19 ( 43.15 ) 46.94 ( 40.36 ) 52.58 ( 45.21 )
17.0 42.02 ( 36.13 ) 46.66 ( 40.12 ) 45.28 ( 38.93 ) 50.21 ( 43.17 ) 47.22 ( 40.60 ) 52.89 ( 45.48 )
17.1 42.05 ( 36.16 ) 46.67 ( 40.13 ) 45.31 ( 38.96 ) 50.23 ( 43.19 ) 47.50 ( 40.84 ) 53.20 ( 45.74 )
17.2 42.08 ( 36.18 ) 46.68 ( 40.14 ) 45.34 ( 38.98 ) 50.25 ( 43.21 ) 47.78 ( 41.08 ) 53.51 ( 46.01 )
17.3 42.11 ( 36.21 ) 46.69 ( 40.15 ) 45.37 ( 39.01 ) 50.27 ( 43.23 ) 48.06 ( 41.32 ) 53.82 ( 46.28 )
17.4 42.15 ( 36.24 ) 46.70 ( 40.16 ) 45.39 ( 39.03 ) 50.29 ( 43.24 ) 48.33 ( 41.56 ) 54.13 ( 46.55 )
17.5 42.18 ( 36.27 ) 46.72 ( 40.17 ) 45.42 ( 39.06 ) 50.31 ( 43.26 ) 48.61 ( 41.80 ) 54.44 ( 46.81 )
17.6 42.21 ( 36.29 ) 46.73 ( 40.18 ) 45.45 ( 39.08 ) 50.33 ( 43.28 ) 48.89 ( 42.04 ) 54.76 ( 47.08 )
17.7 42.24 ( 36.32 ) 46.74 ( 40.19 ) 45.48 ( 39.10 ) 50.35 ( 43.30 ) 49.17 ( 42.28 ) 55.07 ( 47.35 )
17.8 42.27 ( 36.35 ) 46.75 ( 40.20 ) 45.51 ( 39.13 ) 50.38 ( 43.31 ) 49.44 ( 42.51 ) 55.38 ( 47.62 )
17.9 42.30 ( 36.38 ) 46.76 ( 40.21 ) 45.53 ( 39.15 ) 50.40 ( 43.33 ) 49.72 ( 42.75 ) 55.69 ( 47.88 )
18.0 42.34 ( 36.40 ) 46.78 ( 40.22 ) 45.56 ( 39.18 ) 50.42 ( 43.35 ) 50.00 ( 42.99 ) 56.00 ( 48.15 )
18.1 42.37 ( 36.43 ) 46.79 ( 40.23 ) 45.59 ( 39.20 ) 50.44 ( 43.37 ) 50.28 ( 43.23 ) 56.31 ( 48.42 )
18.2 42.40 ( 36.46 ) 46.80 ( 40.24 ) 45.62 ( 39.23 ) 50.46 ( 43.39 ) 50.56 ( 43.47 ) 56.62 ( 48.69 )
18.3 45.65 ( 39.25 ) 50.48 ( 43.40 ) 50.83 ( 43.71 ) 56.93 ( 48.95 )
18.4 45.68 ( 39.27 ) 50.50 ( 43.42 ) 51.11 ( 43.95 ) 57.24 ( 49.22 )
18.5 45.70 ( 39.30 ) 50.52 ( 43.44 ) 51.39 ( 44.19 ) 57.56 ( 49.49 )
18.6 _ 45.73 ( 39.32 ) 50.54 ( 43.46 ) 51.52 ( 44.30 ) 57.69 ( 49.60 )
18.7 45.76 ( 39.35 ) 50.56 ( 43.48 ) 51.55 ( 44.32 ) 57.70 ( 49.61 )
18.8 45.79 ( 39.37 ) 50.58 ( 43.49 ) 51.58 ( 44.35 ) 57.71 ( 49.62 )
18.9 45.82 ( 39.39 ) 50.60 ( 43.51 ) 51.61 ( 44.38 ) 57.72 ( 49.63 )
Table 5. Outdoor Unit Capacity (JTOR140~180VPE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (3)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-14FSXNS
JTOR140VPE(U,F,R)BS1 RAS-16FSXNS
JTOR160VPE(U,F,R)BS1 RAS-18FSXNS
JTOR180VPE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
19.0 45.65 ( 39.25 ) 50.48 ( 43.40 ) 51.64 ( 44.40 ) 57.73 ( 49.64 )
19.1 45.68 ( 39.27 ) 50.50 ( 43.42 ) 51.67 ( 44.43 ) 57.74 ( 49.65 )
19.2 45.70 ( 39.30 ) 50.52 ( 43.44 ) 51.70 ( 44.46 ) 57.76 ( 49.66 )
19.3 45.73 ( 39.32 ) 50.54 ( 43.46 ) 51.73 ( 44.48 ) 57.77 ( 49.67 )
19.4 45.76 ( 39.35 ) 50.56 ( 43.48 ) 51.77 ( 44.51 ) 57.78 ( 49.68 )
19.5 45.79 ( 39.37 ) 50.58 ( 43.49 ) 51.80 ( 44.54 ) 57.79 ( 49.69 )
19.6 45.82 ( 39.39 ) 50.60 ( 43.51 ) 51.83 ( 44.56 ) 57.80 ( 49.70 )
19.7 45.84 ( 39.42 ) 50.63 ( 43.53 ) 51.86 ( 44.59 ) 57.81 ( 49.71 )
19.8 45.87 ( 39.44 ) 50.65 ( 43.55 ) 51.89 ( 44.62 ) 57.83 ( 49.72 )
19.9 45.90 ( 39.47 ) 50.67 ( 43.57 ) 51.92 ( 44.64 ) 57.84 ( 49.73 )
20.0 45.93 ( 39.49 ) 50.69 ( 43.58 ) 51.95 ( 44.67 ) 57.85 ( 49.74 )
20.1 45.96 ( 39.52 ) 50.71 ( 43.60 ) 51.98 ( 44.70 ) 57.86 ( 49.75 )
20.2 45.98 ( 39.54 ) 50.73 ( 43.62 ) 52.01 ( 44.72 ) 57.87 ( 49.76 )
20.3 46.01 ( 39.56 ) 50.75 ( 43.64 ) 52.04 ( 44.75 ) 57.88 ( 49.77 )
20.4 46.04 ( 39.59 ) 50.77 ( 43.66 ) 52.07 ( 44.78 ) 57.89 ( 49.78 )
20.5 46.07 ( 39.61 ) 50.79 ( 43.67 ) 52.10 ( 44.80 ) 57.91 ( 49.79 )
20.6 46.10 ( 39.64 ) 50.81 ( 43.69 ) 52.14 ( 44.83 ) 57.92 ( 49.80 )
20.7 46.13 ( 39.66 ) 50.83 ( 43.71 ) 52.17 ( 44.86 ) 57.93 ( 49.81 )
20.8 46.15 ( 39.68 ) 50.85 ( 43.73 ) 52.20 ( 44.88 ) 57.94 ( 49.82 )
20.9 46.18 ( 39.71 ) 50.88 ( 43.74 ) 52.23 ( 44.91 ) 57.95 ( 49.83 )
21.0 46.21 ( 39.73 ) 50.90 ( 43.76 ) 52.26 ( 44.93 ) 57.96 ( 49.84 )
21.1 46.24 ( 39.76 ) 50.92 ( 43.78 ) 52.29 ( 44.96 ) 57.97 ( 49.85 )
21.2 _ 46.27 ( 39.78 ) 50.94 ( 43.80 ) 52.32 ( 44.99 ) 57.99 ( 49.86 )
21.3 46.29 ( 39.81 ) 50.96 ( 43.82 ) 52.35 ( 45.01 ) 58.00 ( 49.87 )
21.4 46.32 ( 39.83 ) 50.98 ( 43.83 ) 52.38 ( 45.04 ) 58.01 ( 49.88 )
21.5 46.35 ( 39.85 ) 51.00 ( 43.85 ) 52.41 ( 45.07 ) 58.02 ( 49.89 )
21.6 52.44 ( 45.09 ) 58.03 ( 49.90 )
21.7 52.48 ( 45.12 ) 58.04 ( 49.91 )
21.8 52.51 ( 45.15 ) 58.06 ( 49.92 )
21.9 52.54 ( 45.17 ) 58.07 ( 49.93 )
22.0 52.57 ( 45.20 ) 58.08 ( 49.94 )
22.1 52.60 ( 45.23 ) 58.09 ( 49.95 )
22.2 52.63 ( 45.25 ) 58.10 ( 49.96 )
22.3 52.66 ( 45.28 ) 58.11 ( 49.97 )
22.4 52.69 ( 45.31 ) 58.12 ( 49.98 )
22.5 _ 52.72 ( 45.33 ) 58.14 ( 49.99 )
22.6 52.75 ( 45.36 ) 58.15 ( 50.00 )
22.7 52.78 ( 45.39 ) 58.16 ( 50.01 )
22.8 52.81 ( 45.41 ) 58.17 ( 50.02 )
22.9 52.85 ( 45.44 ) 58.18 ( 50.03 )
23.0 52.88 ( 45.47 ) 58.19 ( 50.04 )
23.1 52.91 ( 45.49 ) 58.21 ( 50.05 )
23.2 52.94 ( 45.52 ) 58.22 ( 50.06 )
23.3 52.97 ( 45.55 ) 58.23 ( 50.07 )
23.4 53.00 ( 45.57 ) 58.24 ( 50.08 )
Table 6. Outdoor Unit Capacity (JTOR200~240VPE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (1)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-20FSXNS
JTOR200VPE(U,F,R)BS1 RAS-22FSXNS
JTOR220VPE(U,F,R)BS1 RAS-24FSXNS
JTOR240VPE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
10.0 28.00 ( 24.08 ) 31.50 ( 27.09 )
10.1 28.28 ( 24.32 ) 31.81 ( 27.36 )
10.2 28.56 ( 24.56 ) 32.13 ( 27.63 )
10.3 28.84 ( 24.80 ) 32.44 ( 27.90 )
10.4 29.12 ( 25.04 ) 32.76 ( 28.17 )
_
10.5 29.40 ( 25.28 ) 33.07 ( 28.44 )
10.6 29.68 ( 25.52 ) 33.39 ( 28.71 )
10.7 29.96 ( 25.76 ) 33.70 ( 28.98 )
10.8 30.24 ( 26.00 ) 34.02 ( 29.25 )
10.9 30.52 ( 26.24 ) 34.33 ( 29.52 )
_
11.0 30.80 ( 26.48 ) 34.65 ( 29.79 ) 30.75 ( 26.44 ) 34.50 ( 29.66 )
11.1 31.08 ( 26.72 ) 34.96 ( 30.06 ) 31.03 ( 26.68 ) 34.81 ( 29.93 )
11.2 31.36 ( 26.96 ) 35.28 ( 30.34 ) 31.31 ( 26.92 ) 35.13 ( 30.20 )
11.3 31.64 ( 27.21 ) 35.59 ( 30.61 ) 31.59 ( 27.16 ) 35.44 ( 30.47 )
11.4 31.92 ( 27.45 ) 35.91 ( 30.88 ) 31.87 ( 27.40 ) 35.75 ( 30.74 )
11.5 32.20 ( 27.69 ) 36.22 ( 31.15 ) 32.15 ( 27.64 ) 36.07 ( 31.01 )
11.6 32.48 ( 27.93 ) 36.54 ( 31.42 ) 32.43 ( 27.88 ) 36.38 ( 31.28 )
11.7 32.76 ( 28.17 ) 36.85 ( 31.69 ) 32.71 ( 28.12 ) 36.70 ( 31.55 )
11.8 33.04 ( 28.41 ) 37.17 ( 31.96 ) 32.99 ( 28.36 ) 37.01 ( 31.82 )
11.9 33.32 ( 28.65 ) 37.48 ( 32.23 ) 33.27 ( 28.60 ) 37.32 ( 32.09 )
12.0 33.60 ( 28.89 ) 37.80 ( 32.50 ) 33.55 ( 28.84 ) 37.64 ( 32.36 ) 33.50 ( 28.80 ) 38.75 ( 33.32 )
12.1 33.88 ( 29.13 ) 38.11 ( 32.77 ) 33.82 ( 29.08 ) 37.95 ( 32.63 ) 33.78 ( 29.04 ) 39.07 ( 33.60 )
12.2 34.16 ( 29.37 ) 38.43 ( 33.04 ) 34.10 ( 29.32 ) 38.26 ( 32.90 ) 34.06 ( 29.28 ) 39.40 ( 33.87 )
12.3 34.44 ( 29.61 ) 38.74 ( 33.31 ) 34.38 ( 29.56 ) 38.58 ( 33.17 ) 34.34 ( 29.52 ) 39.72 ( 34.15 )
12.4 34.72 ( 29.85 ) 39.06 ( 33.59 ) 34.66 ( 29.81 ) 38.89 ( 33.44 ) 34.62 ( 29.76 ) 40.04 ( 34.43 )
12.5 35.00 ( 30.09 ) 39.37 ( 33.86 ) 34.94 ( 30.05 ) 39.20 ( 33.71 ) 34.90 ( 30.01 ) 40.36 ( 34.71 )
12.6 35.28 ( 30.34 ) 39.69 ( 34.13 ) 35.22 ( 30.29 ) 39.52 ( 33.98 ) 35.17 ( 30.25 ) 40.69 ( 34.98 )
12.7 35.56 ( 30.58 ) 40.00 ( 34.40 ) 35.50 ( 30.53 ) 39.83 ( 34.25 ) 35.45 ( 30.49 ) 41.01 ( 35.26 )
12.8 35.84 ( 30.82 ) 40.32 ( 34.67 ) 35.78 ( 30.77 ) 40.15 ( 34.52 ) 35.73 ( 30.73 ) 41.33 ( 35.54 )
12.9 36.12 ( 31.06 ) 40.63 ( 34.94 ) 36.06 ( 31.01 ) 40.46 ( 34.79 ) 36.01 ( 30.97 ) 41.66 ( 35.82 )
13.0 36.40 ( 31.30 ) 40.95 ( 35.21 ) 36.34 ( 31.25 ) 40.77 ( 35.06 ) 36.29 ( 31.21 ) 41.98 ( 36.10 )
13.1 36.68 ( 31.54 ) 41.26 ( 35.48 ) 36.62 ( 31.49 ) 41.09 ( 35.33 ) 36.57 ( 31.45 ) 42.30 ( 36.37 )
13.2 36.96 ( 31.78 ) 41.58 ( 35.75 ) 36.90 ( 31.73 ) 41.40 ( 35.60 ) 36.85 ( 31.69 ) 42.62 ( 36.65 )
13.3 37.24 ( 32.02 ) 41.89 ( 36.02 ) 37.18 ( 31.97 ) 41.71 ( 35.87 ) 37.13 ( 31.93 ) 42.95 ( 36.93 )
13.4 37.52 ( 32.26 ) 42.21 ( 36.29 ) 37.46 ( 32.21 ) 42.03 ( 36.14 ) 37.41 ( 32.17 ) 43.27 ( 37.21 )
13.5 37.80 ( 32.50 ) 42.52 ( 36.56 ) 37.74 ( 32.45 ) 42.34 ( 36.41 ) 37.69 ( 32.41 ) 43.59 ( 37.48 )
13.6 38.08 ( 32.74 ) 42.84 ( 36.84 ) 38.02 ( 32.69 ) 42.65 ( 36.68 ) 37.97 ( 32.65 ) 43.92 ( 37.76 )
13.7 38.36 ( 32.98 ) 43.15 ( 37.11 ) 38.30 ( 32.93 ) 42.97 ( 36.95 ) 38.25 ( 32.89 ) 44.24 ( 38.04 )
13.8 38.64 ( 33.22 ) 43.47 ( 37.38 ) 38.58 ( 33.17 ) 43.28 ( 37.22 ) 38.52 ( 33.13 ) 44.56 ( 38.32 )
13.9 38.92 ( 33.47 ) 43.78 ( 37.65 ) 38.86 ( 33.41 ) 43.60 ( 37.49 ) 38.80 ( 33.37 ) 44.89 ( 38.59 )
14.0 39.20 ( 33.71 ) 44.10 ( 37.92 ) 39.14 ( 33.65 ) 43.91 ( 37.76 ) 39.08 ( 33.61 ) 45.21 ( 38.87 )
14.1 39.48 ( 33.95 ) 44.42 ( 38.19 ) 39.42 ( 33.89 ) 44.22 ( 38.02 ) 39.36 ( 33.85 ) 45.53 ( 39.15 )
14.2 39.76 ( 34.19 ) 44.73 ( 38.46 ) 39.70 ( 34.13 ) 44.54 ( 38.29 ) 39.64 ( 34.09 ) 45.85 ( 39.43 )
14.3 40.04 ( 34.43 ) 45.05 ( 38.73 ) 39.97 ( 34.37 ) 44.85 ( 38.56 ) 39.92 ( 34.33 ) 46.18 ( 39.71 )
14.4 40.32 ( 34.67 ) 45.36 ( 39.00 ) 40.25 ( 34.61 ) 45.16 ( 38.83 ) 40.20 ( 34.57 ) 46.50 ( 39.98 )
14.5 40.60 ( 34.91 ) 45.68 ( 39.27 ) 40.53 ( 34.85 ) 45.48 ( 39.10 ) 40.48 ( 34.81 ) 46.82 ( 40.26 )
14.6 40.88 ( 35.15 ) 45.99 ( 39.54 ) 40.81 ( 35.09 ) 45.79 ( 39.37 ) 40.76 ( 35.05 ) 47.15 ( 40.54 )
14.7 41.16 ( 35.39 ) 46.31 ( 39.82 ) 41.09 ( 35.33 ) 46.10 ( 39.64 ) 41.04 ( 35.29 ) 47.47 ( 40.82 )
14.8 41.44 ( 35.63 ) 46.62 ( 40.09 ) 41.37 ( 35.57 ) 46.42 ( 39.91 ) 41.32 ( 35.53 ) 47.79 ( 41.09 )
14.9 41.72 ( 35.87 ) 46.94 ( 40.36 ) 41.65 ( 35.81 ) 46.73 ( 40.18 ) 41.60 ( 35.77 ) 48.11 ( 41.37 )
15.0 42.00 ( 36.11 ) 47.25 ( 40.63 ) 41.93 ( 36.05 ) 47.05 ( 40.45 ) 41.87 ( 36.01 ) 48.44 ( 41.65 )
15.1 42.28 ( 36.35 ) 47.57 ( 40.90 ) 42.21 ( 36.30 ) 47.36 ( 40.72 ) 42.15 ( 36.25 ) 48.76 ( 41.93 )
15.2 42.56 ( 36.60 ) 47.88 ( 41.17 ) 42.49 ( 36.54 ) 47.67 ( 40.99 ) 42.43 ( 36.49 ) 49.08 ( 42.20 )
15.3 42.84 ( 36.84 ) 48.20 ( 41.44 ) 42.77 ( 36.78 ) 47.99 ( 41.26 ) 42.71 ( 36.73 ) 49.41 ( 42.48 )
15.4 43.12 ( 37.08 ) 48.51 ( 41.71 ) 43.05 ( 37.02 ) 48.30 ( 41.53 ) 42.99 ( 36.97 ) 49.73 ( 42.76 )
15.5 43.40 ( 37.32 ) 48.83 ( 41.98 ) 43.33 ( 37.26 ) 48.61 ( 41.80 ) 43.27 ( 37.21 ) 50.05 ( 43.04 )
15.6 43.68 ( 37.56 ) 49.14 ( 42.25 ) 43.61 ( 37.50 ) 48.93 ( 42.07 ) 43.55 ( 37.45 ) 50.37 ( 43.31 )
15.7 43.96 ( 37.80 ) 49.46 ( 42.52 ) 43.89 ( 37.74 ) 49.24 ( 42.34 ) 43.83 ( 37.69 ) 50.70 ( 43.59 )
15.8 44.24 ( 38.04 ) 49.77 ( 42.79 ) 44.17 ( 37.98 ) 49.55 ( 42.61 ) 44.11 ( 37.93 ) 51.02 ( 43.87 )
15.9 44.52 ( 38.28 ) 50.09 ( 43.07 ) 44.45 ( 38.22 ) 49.87 ( 42.88 ) 44.39 ( 38.17 ) 51.34 ( 44.15 )
Table 7. Outdoor Unit Capacity (JTOR200~240VPE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (2)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-20FSXNS
JTOR200VPE(U,F,R)BS1 RAS-22FSXNS
JTOR220VPE(U,F,R)BS1 RAS-24FSXNS
JTOR240VPE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
16.0 44.80 ( 38.52 ) 50.40 ( 43.34 ) 44.73 ( 38.46 ) 50.18 ( 43.15 ) 44.67 ( 38.41 ) 51.67 ( 44.43 )
16.1 45.08 ( 38.76 ) 50.72 ( 43.61 ) 45.01 ( 38.70 ) 50.50 ( 43.42 ) 44.95 ( 38.65 ) 51.99 ( 44.70 )
16.2 45.36 ( 39.00 ) 51.03 ( 43.88 ) 45.29 ( 38.94 ) 50.81 ( 43.69 ) 45.22 ( 38.89 ) 52.31 ( 44.98 )
16.3 45.64 ( 39.24 ) 51.35 ( 44.15 ) 45.57 ( 39.18 ) 51.12 ( 43.96 ) 45.50 ( 39.13 ) 52.64 ( 45.26 )
16.4 45.92 ( 39.48 ) 51.66 ( 44.42 ) 45.85 ( 39.42 ) 51.44 ( 44.23 ) 45.78 ( 39.37 ) 52.96 ( 45.54 )
16.5 46.20 ( 39.72 ) 51.98 ( 44.69 ) 46.12 ( 39.66 ) 51.75 ( 44.50 ) 46.06 ( 39.61 ) 53.28 ( 45.81 )
16.6 46.48 ( 39.97 ) 52.29 ( 44.96 ) 46.40 ( 39.90 ) 52.06 ( 44.77 ) 46.34 ( 39.85 ) 53.60 ( 46.09 )
16.7 46.76 ( 40.21 ) 52.61 ( 45.23 ) 46.68 ( 40.14 ) 52.38 ( 45.04 ) 46.62 ( 40.09 ) 53.93 ( 46.37 )
16.8 47.04 ( 40.45 ) 52.92 ( 45.50 ) 46.96 ( 40.38 ) 52.69 ( 45.31 ) 46.90 ( 40.33 ) 54.25 ( 46.65 )
16.9 47.32 ( 40.69 ) 53.24 ( 45.77 ) 47.24 ( 40.62 ) 53.00 ( 45.58 ) 47.18 ( 40.57 ) 54.57 ( 46.92 )
17.0 47.60 ( 40.93 ) 53.55 ( 46.04 ) 47.52 ( 40.86 ) 53.32 ( 45.85 ) 47.46 ( 40.81 ) 54.90 ( 47.20 )
17.1 47.88 ( 41.17 ) 53.87 ( 46.32 ) 47.80 ( 41.10 ) 53.63 ( 46.12 ) 47.74 ( 41.05 ) 55.22 ( 47.48 )
17.2 48.16 ( 41.41 ) 54.18 ( 46.59 ) 48.08 ( 41.34 ) 53.95 ( 46.38 ) 48.02 ( 41.29 ) 55.54 ( 47.76 )
17.3 48.44 ( 41.65 ) 54.50 ( 46.86 ) 48.36 ( 41.58 ) 54.26 ( 46.65 ) 48.30 ( 41.53 ) 55.86 ( 48.03 )
17.4 48.72 ( 41.89 ) 54.81 ( 47.13 ) 48.64 ( 41.82 ) 54.57 ( 46.92 ) 48.57 ( 41.77 ) 56.19 ( 48.31 )
17.5 49.00 ( 42.13 ) 55.13 ( 47.40 ) 48.92 ( 42.06 ) 54.89 ( 47.19 ) 48.85 ( 42.01 ) 56.51 ( 48.59 )
17.6 49.28 ( 42.37 ) 55.44 ( 47.67 ) 49.20 ( 42.30 ) 55.20 ( 47.46 ) 49.13 ( 42.25 ) 56.83 ( 48.87 )
17.7 49.56 ( 42.61 ) 55.76 ( 47.94 ) 49.48 ( 42.54 ) 55.51 ( 47.73 ) 49.41 ( 42.49 ) 57.16 ( 49.15 )
17.8 49.84 ( 42.85 ) 56.07 ( 48.21 ) 49.76 ( 42.79 ) 55.83 ( 48.00 ) 49.69 ( 42.73 ) 57.48 ( 49.42 )
17.9 50.12 ( 43.10 ) 56.39 ( 48.48 ) 50.04 ( 43.03 ) 56.14 ( 48.27 ) 49.97 ( 42.97 ) 57.80 ( 49.70 )
18.0 50.40 ( 43.34 ) 56.70 ( 48.75 ) 50.32 ( 43.27 ) 56.45 ( 48.54 ) 50.25 ( 43.21 ) 58.12 ( 49.98 )
18.1 50.68 ( 43.58 ) 57.02 ( 49.02 ) 50.60 ( 43.51 ) 56.77 ( 48.81 ) 50.53 ( 43.45 ) 58.45 ( 50.26 )
18.2 50.96 ( 43.82 ) 57.33 ( 49.29 ) 50.88 ( 43.75 ) 57.08 ( 49.08 ) 50.81 ( 43.69 ) 58.77 ( 50.53 )
18.3 51.24 ( 44.06 ) 57.65 ( 49.57 ) 51.16 ( 43.99 ) 57.40 ( 49.35 ) 51.09 ( 43.93 ) 59.09 ( 50.81 )
18.4 51.52 ( 44.30 ) 57.96 ( 49.84 ) 51.44 ( 44.23 ) 57.71 ( 49.62 ) 51.37 ( 44.17 ) 59.42 ( 51.09 )
18.5 51.80 ( 44.54 ) 58.28 ( 50.11 ) 51.72 ( 44.47 ) 58.02 ( 49.89 ) 51.65 ( 44.41 ) 59.74 ( 51.37 )
18.6 52.08 ( 44.78 ) 58.59 ( 50.38 ) 52.00 ( 44.71 ) 58.34 ( 50.16 ) 51.92 ( 44.65 ) 60.06 ( 51.64 )
18.7 52.36 ( 45.02 ) 58.91 ( 50.65 ) 52.27 ( 44.95 ) 58.65 ( 50.43 ) 52.20 ( 44.89 ) 60.39 ( 51.92 )
18.8 52.64 ( 45.26 ) 59.22 ( 50.92 ) 52.55 ( 45.19 ) 58.96 ( 50.70 ) 52.48 ( 45.13 ) 60.71 ( 52.20 )
18.9 52.92 ( 45.50 ) 59.54 ( 51.19 ) 52.83 ( 45.43 ) 59.28 ( 50.97 ) 52.76 ( 45.37 ) 61.03 ( 52.48 )
19.0 53.20 ( 45.74 ) 59.85 ( 51.46 ) 53.11 ( 45.67 ) 59.59 ( 51.24 ) 53.04 ( 45.61 ) 61.35 ( 52.76 )
19.1 53.48 ( 45.98 ) 60.17 ( 51.73 ) 53.39 ( 45.91 ) 59.90 ( 51.51 ) 53.32 ( 45.85 ) 61.68 ( 53.03 )
19.2 53.76 ( 46.23 ) 60.48 ( 52.00 ) 53.67 ( 46.15 ) 60.22 ( 51.78 ) 53.60 ( 46.09 ) 62.00 ( 53.31 )
19.3 54.04 ( 46.47 ) 60.80 ( 52.27 ) 53.95 ( 46.39 ) 60.53 ( 52.05 ) 53.88 ( 46.33 ) 62.32 ( 53.59 )
19.4 54.32 ( 46.71 ) 61.11 ( 52.55 ) 54.23 ( 46.63 ) 60.85 ( 52.32 ) 54.16 ( 46.57 ) 62.65 ( 53.87 )
19.5 54.60 ( 46.95 ) 61.43 ( 52.82 ) 54.51 ( 46.87 ) 61.16 ( 52.59 ) 54.44 ( 46.81 ) 62.97 ( 54.14 )
19.6 54.88 ( 47.19 ) 61.74 ( 53.09 ) 54.79 ( 47.11 ) 61.47 ( 52.86 ) 54.72 ( 47.05 ) 63.29 ( 54.42 )
19.7 55.16 ( 47.43 ) 62.06 ( 53.36 ) 55.07 ( 47.35 ) 61.79 ( 53.13 ) 55.00 ( 47.29 ) 63.61 ( 54.70 )
19.8 55.44 ( 47.67 ) 62.37 ( 53.63 ) 55.35 ( 47.59 ) 62.10 ( 53.40 ) 55.27 ( 47.53 ) 63.94 ( 54.98 )
19.9 55.72 ( 47.91 ) 62.69 ( 53.90 ) 55.63 ( 47.83 ) 62.41 ( 53.67 ) 55.55 ( 47.77 ) 64.26 ( 55.25 )
20.0 56.00 ( 48.15 ) 63.00 ( 54.17 ) 55.91 ( 48.07 ) 62.73 ( 53.94 ) 55.83 ( 48.01 ) 64.58 ( 55.53 )
20.1 56.28 ( 48.39 ) 63.32 ( 54.44 ) 56.19 ( 48.31 ) 63.04 ( 54.21 ) 56.11 ( 48.25 ) 64.91 ( 55.81 )
20.2 56.56 ( 48.63 ) 63.63 ( 54.71 ) 56.47 ( 48.55 ) 63.35 ( 54.48 ) 56.39 ( 48.49 ) 65.23 ( 56.09 )
20.3 56.84 ( 48.87 ) 63.95 ( 54.98 ) 56.75 ( 48.79 ) 63.67 ( 54.74 ) 56.67 ( 48.73 ) 65.55 ( 56.36 )
20.4 57.12 ( 49.11 ) 64.26 ( 55.25 ) 57.03 ( 49.03 ) 63.98 ( 55.01 ) 56.95 ( 48.97 ) 65.87 ( 56.64 )
20.5 57.40 ( 49.36 ) 64.58 ( 55.52 ) 57.31 ( 49.27 ) 64.30 ( 55.28 ) 57.23 ( 49.21 ) 66.20 ( 56.92 )
20.6 57.68 ( 49.60 ) 64.89 ( 55.80 ) 57.59 ( 49.52 ) 64.61 ( 55.55 ) 57.51 ( 49.45 ) 66.52 ( 57.20 )
20.7 57.71 ( 49.62 ) 64.90 ( 55.81 ) 57.87 ( 49.76 ) 64.92 ( 55.82 ) 57.79 ( 49.69 ) 66.84 ( 57.48 )
20.8 57.74 ( 49.65 ) 64.91 ( 55.82 ) 58.15 ( 50.00 ) 65.24 ( 56.09 ) 58.07 ( 49.93 ) 67.17 ( 57.75 )
20.9 57.77 ( 49.68 ) 64.93 ( 55.83 ) 58.43 ( 50.24 ) 65.55 ( 56.36 ) 58.35 ( 50.17 ) 67.49 ( 58.03 )
21.0 57.80 ( 49.70 ) 64.94 ( 55.84 ) 58.70 ( 50.48 ) 65.86 ( 56.63 ) 58.63 ( 50.41 ) 67.81 ( 58.31 )
21.1 57.84 ( 49.73 ) 64.95 ( 55.85 ) 58.98 ( 50.72 ) 66.18 ( 56.90 ) 58.90 ( 50.65 ) 68.14 ( 58.59 )
21.2 57.87 ( 49.76 ) 64.96 ( 55.86 ) 59.26 ( 50.96 ) 66.49 ( 57.17 ) 59.18 ( 50.89 ) 68.46 ( 58.86 )
21.3 57.90 ( 49.78 ) 64.97 ( 55.87 ) 59.54 ( 51.20 ) 66.80 ( 57.44 ) 59.46 ( 51.13 ) 68.78 ( 59.14 )
21.4 57.93 ( 49.81 ) 64.98 ( 55.88 ) 59.82 ( 51.44 ) 67.12 ( 57.71 ) 59.74 ( 51.37 ) 69.10 ( 59.42 )
21.5 57.96 ( 49.84 ) 65.00 ( 55.89 ) 60.10 ( 51.68 ) 67.43 ( 57.98 ) 60.02 ( 51.61 ) 69.43 ( 59.70 )
21.6 57.99 ( 49.86 ) 65.01 ( 55.90 ) 60.38 ( 51.92 ) 67.75 ( 58.25 ) 60.30 ( 51.85 ) 69.75 ( 59.97 )
21.7 58.02 ( 49.89 ) 65.02 ( 55.91 ) 60.66 ( 52.16 ) 68.06 ( 58.52 ) 60.58 ( 52.09 ) 70.07 ( 60.25 )
21.8 58.05 ( 49.92 ) 65.03 ( 55.92 ) 60.94 ( 52.40 ) 68.37 ( 58.79 ) 60.86 ( 52.33 ) 70.40 ( 60.53 )
21.9 58.08 ( 49.94 ) 65.04 ( 55.93 ) 61.22 ( 52.64 ) 68.69 ( 59.06 ) 61.14 ( 52.57 ) 70.72 ( 60.81 )
Table 8. Outdoor Unit Capacity (JTOR200~240VPE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (3)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-20FSXNS
JTOR200VPE(U,F,R)BS1 RAS-22FSXNS
JTOR220VPE(U,F,R)BS1 RAS-24FSXNS
JTOR240VPE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
22.0 58.12 ( 49.97 ) 65.05 ( 55.94 ) 61.50 ( 52.88 ) 69.00 ( 59.33 ) 61.42 ( 52.81 ) 71.04 ( 61.08 )
22.1 58.15 ( 50.00 ) 65.07 ( 55.95 ) 61.78 ( 53.12 ) 69.31 ( 59.60 ) 61.70 ( 53.05 ) 71.36 ( 61.36 )
22.2 58.18 ( 50.02 ) 65.08 ( 55.96 ) 62.06 ( 53.36 ) 69.63 ( 59.87 ) 61.98 ( 53.29 ) 71.69 ( 61.64 )
22.3 58.21 ( 50.05 ) 65.09 ( 55.97 ) 62.34 ( 53.60 ) 69.94 ( 60.14 ) 62.25 ( 53.53 ) 72.01 ( 61.92 )
22.4 58.24 ( 50.08 ) 65.10 ( 55.98 ) 62.62 ( 53.84 ) 70.25 ( 60.41 ) 62.53 ( 53.77 ) 72.33 ( 62.20 )
22.5 58.27 ( 50.10 ) 65.11 ( 55.99 ) 62.90 ( 54.08 ) 70.57 ( 60.68 ) 62.81 ( 54.01 ) 72.66 ( 62.47 )
22.6 58.30 ( 50.13 ) 65.12 ( 56.00 ) 63.18 ( 54.32 ) 70.88 ( 60.95 ) 63.09 ( 54.25 ) 72.98 ( 62.75 )
22.7 58.33 ( 50.16 ) 65.14 ( 56.01 ) 63.36 ( 54.48 ) 71.07 ( 61.11 ) 63.37 ( 54.49 ) 73.30 ( 63.03 )
22.8 58.36 ( 50.18 ) 65.15 ( 56.02 ) 63.39 ( 54.50 ) 71.09 ( 61.12 ) 63.65 ( 54.73 ) 73.63 ( 63.31 )
22.9 58.40 ( 50.21 ) 65.16 ( 56.03 ) 63.42 ( 54.53 ) 71.10 ( 61.13 ) 63.93 ( 54.97 ) 73.95 ( 63.58 )
23.0 58.43 ( 50.24 ) 65.17 ( 56.04 ) 63.45 ( 54.56 ) 71.11 ( 61.14 ) 64.21 ( 55.21 ) 74.27 ( 63.86 )
23.1 58.46 ( 50.26 ) 65.18 ( 56.05 ) 63.48 ( 54.58 ) 71.12 ( 61.15 ) 64.49 ( 55.45 ) 74.59 ( 64.14 )
23.2 58.49 ( 50.29 ) 65.19 ( 56.06 ) 63.51 ( 54.61 ) 71.13 ( 61.16 ) 64.77 ( 55.69 ) 74.92 ( 64.42 )
23.3 58.52 ( 50.32 ) 65.21 ( 56.07 ) 63.54 ( 54.64 ) 71.14 ( 61.17 ) 65.05 ( 55.93 ) 75.24 ( 64.69 )
23.4 58.55 ( 50.34 ) 65.22 ( 56.08 ) 63.57 ( 54.66 ) 71.16 ( 61.18 ) 65.33 ( 56.17 ) 75.56 ( 64.97 )
23.5 58.58 ( 50.37 ) 65.23 ( 56.09 ) 63.61 ( 54.69 ) 71.17 ( 61.19 ) 65.60 ( 56.41 ) 75.89 ( 65.25 )
23.6 58.61 ( 50.40 ) 65.24 ( 56.10 ) 63.64 ( 54.72 ) 71.18 ( 61.20 ) 65.88 ( 56.65 ) 76.21 ( 65.53 )
23.7 58.64 ( 50.43 ) 65.25 ( 56.11 ) 63.67 ( 54.74 ) 71.19 ( 61.21 ) 66.16 ( 56.89 ) 76.53 ( 65.81 )
23.8 58.68 ( 50.45 ) 65.26 ( 56.12 ) 63.70 ( 54.77 ) 71.20 ( 61.22 ) 66.44 ( 57.13 ) 76.85 ( 66.08 )
23.9 58.71 ( 50.48 ) 65.28 ( 56.13 ) 63.73 ( 54.80 ) 71.21 ( 61.23 ) 66.72 ( 57.37 ) 77.18 ( 66.36 )
24.0 58.74 ( 50.51 ) 65.29 ( 56.14 ) 63.76 ( 54.82 ) 71.23 ( 61.24 ) 67.00 ( 57.61 ) 77.50 ( 66.64 )
24.1 58.77 ( 50.53 ) 65.30 ( 56.15 ) 63.79 ( 54.85 ) 71.24 ( 61.25 ) 67.03 ( 57.63 ) 77.52 ( 66.66 )
24.2 58.80 ( 50.56 ) 65.31 ( 56.16 ) 63.82 ( 54.88 ) 71.25 ( 61.26 ) 67.06 ( 57.66 ) 77.54 ( 66.68 )
24.3 58.83 ( 50.59 ) 65.32 ( 56.17 ) 63.85 ( 54.90 ) 71.26 ( 61.27 ) 67.08 ( 57.68 ) 77.56 ( 66.69 )
24.4 58.86 ( 50.61 ) 65.33 ( 56.18 ) 63.89 ( 54.93 ) 71.27 ( 61.28 ) 67.11 ( 57.71 ) 77.59 ( 66.71 )
24.5 58.89 ( 50.64 ) 65.35 ( 56.19 ) 63.92 ( 54.96 ) 71.28 ( 61.29 ) 67.14 ( 57.73 ) 77.61 ( 66.73 )
24.6 58.92 ( 50.67 ) 65.36 ( 56.20 ) 63.95 ( 54.99 ) 71.30 ( 61.30 ) 67.17 ( 57.75 ) 77.63 ( 66.75 )
24.7 58.96 ( 50.69 ) 65.37 ( 56.21 ) 63.98 ( 55.01 ) 71.31 ( 61.31 ) 67.20 ( 57.78 ) 77.65 ( 66.77 )
24.8 58.99 ( 50.72 ) 65.38 ( 56.22 ) 64.01 ( 55.04 ) 71.32 ( 61.32 ) 67.22 ( 57.80 ) 77.67 ( 66.79 )
24.9 59.02 ( 50.75 ) 65.39 ( 56.23 ) 64.04 ( 55.07 ) 71.33 ( 61.33 ) 67.25 ( 57.83 ) 77.69 ( 66.80 )
25.0 59.05 ( 50.77 ) 65.40 ( 56.24 ) 64.07 ( 55.09 ) 71.34 ( 61.34 ) 67.28 ( 57.85 ) 77.72 ( 66.82 )
25.1 59.08 ( 50.80 ) 65.42 ( 56.25 ) 64.10 ( 55.12 ) 71.35 ( 61.35 ) 67.31 ( 57.87 ) 77.74 ( 66.84 )
25.2 59.11 ( 50.83 ) 65.43 ( 56.26 ) 64.13 ( 55.15 ) 71.37 ( 61.36 ) 67.34 ( 57.90 ) 77.76 ( 66.86 )
25.3 59.14 ( 50.85 ) 65.44 ( 56.27 ) 64.17 ( 55.17 ) 71.38 ( 61.37 ) 67.36 ( 57.92 ) 77.78 ( 66.88 )
25.4 59.17 ( 50.88 ) 65.45 ( 56.28 ) 64.20 ( 55.20 ) 71.39 ( 61.38 ) 67.39 ( 57.95 ) 77.80 ( 66.90 )
25.5 59.20 ( 50.91 ) 65.46 ( 56.29 ) 64.23 ( 55.23 ) 71.40 ( 61.39 ) 67.42 ( 57.97 ) 77.82 ( 66.92 )
25.6 59.24 ( 50.93 ) 65.47 ( 56.30 ) 64.26 ( 55.25 ) 71.41 ( 61.40 ) 67.45 ( 57.99 ) 77.84 ( 66.93 )
25.7 59.27 ( 50.96 ) 65.49 ( 56.31 ) 64.29 ( 55.28 ) 71.42 ( 61.41 ) 67.47 ( 58.02 ) 77.87 ( 66.95 )
25.8 59.30 ( 50.99 ) 65.50 ( 56.32 ) 64.32 ( 55.31 ) 71.43 ( 61.42 ) 67.50 ( 58.04 ) 77.89 ( 66.97 )
25.9 59.33 ( 51.01 ) 65.51 ( 56.33 ) 64.35 ( 55.33 ) 71.45 ( 61.43 ) 67.53 ( 58.07 ) 77.91 ( 66.99 )
26.0 59.36 ( 51.04 ) 65.52 ( 56.34 ) 64.38 ( 55.36 ) 71.46 ( 61.44 ) 67.56 ( 58.09 ) 77.93 ( 67.01 )
26.1 64.41 ( 55.39 ) 71.47 ( 61.45 ) 67.59 ( 58.11 ) 77.95 ( 67.03 )
26.2 64.44 ( 55.41 ) 71.48 ( 61.46 ) 67.61 ( 58.14 ) 77.97 ( 67.05 )
26.3 64.48 ( 55.44 ) 71.49 ( 61.47 ) 67.64 ( 58.16 ) 78.00 ( 67.06 )
26.4 64.51 ( 55.47 ) 71.50 ( 61.48 ) 67.67 ( 58.19 ) 78.02 ( 67.08 )
26.5 64.54 ( 55.49 ) 71.52 ( 61.49 ) 67.70 ( 58.21 ) 78.04 ( 67.10 )
26.6 64.57 ( 55.52 ) 71.53 ( 61.50 ) 67.73 ( 58.23 ) 78.06 ( 67.12 )
26.7 64.60 ( 55.55 ) 71.54 ( 61.51 ) 67.75 ( 58.26 ) 78.08 ( 67.14 )
26.8 64.63 ( 55.57 ) 71.55 ( 61.52 ) 67.78 ( 58.28 ) 78.10 ( 67.16 )
26.9 64.66 ( 55.60 ) 71.56 ( 61.53 ) 67.81 ( 58.31 ) 78.12 ( 67.17 )
27.0 _ 64.69 ( 55.63 ) 71.57 ( 61.54 ) 67.84 ( 58.33 ) 78.15 ( 67.19 )
27.1 64.72 ( 55.65 ) 71.59 ( 61.55 ) 67.87 ( 58.35 ) 78.17 ( 67.21 )
27.2 64.76 ( 55.68 ) 71.60 ( 61.56 ) 67.89 ( 58.38 ) 78.19 ( 67.23 )
27.3 64.79 ( 55.71 ) 71.61 ( 61.57 ) 67.92 ( 58.40 ) 78.21 ( 67.25 )
27.4 64.82 ( 55.73 ) 71.62 ( 61.58 ) 67.95 ( 58.43 ) 78.23 ( 67.27 )
27.5 64.85 ( 55.76 ) 71.63 ( 61.59 ) 67.98 ( 58.45 ) 78.25 ( 67.29 )
27.6 64.88 ( 55.79 ) 71.64 ( 61.60 ) 68.01 ( 58.47 ) 78.28 ( 67.30 )
27.7 64.91 ( 55.81 ) 71.66 ( 61.61 ) 68.03 ( 58.50 ) 78.30 ( 67.32 )
27.8 64.94 ( 55.84 ) 71.67 ( 61.62 ) 68.06 ( 58.52 ) 78.32 ( 67.34 )
27.9 64.97 ( 55.87 ) 71.68 ( 61.63 ) 68.09 ( 58.55 ) 78.34 ( 67.36 )
Table 9. Outdoor Unit Capacity (JTOR200~240VPE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (4)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-20FSXNS
JTOR200VPE(U,F,R)BS1 RAS-22FSXNS
JTOR220VPE(U,F,R)BS1 RAS-24FSXNS
JTOR240VPE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
28.0 65.00 ( 55.89 ) 71.69 ( 61.64 ) 68.12 ( 58.57 ) 78.36 ( 67.38 )
28.1 65.03 ( 55.92 ) 71.70 ( 61.65 ) 68.14 ( 58.59 ) 78.38 ( 67.40 )
28.2 65.07 ( 55.95 ) 71.71 ( 61.66 ) 68.17 ( 58.62 ) 78.40 ( 67.42 )
28.3 65.10 ( 55.97 ) 71.73 ( 61.67 ) 68.20 ( 58.64 ) 78.43 ( 67.43 )
28.4 65.13 ( 56.00 ) 71.74 ( 61.68 ) 68.23 ( 58.67 ) 78.45 ( 67.45 )
28.5 65.16 ( 56.03 ) 71.75 ( 61.69 ) 68.26 ( 58.69 ) 78.47 ( 67.47 )
28.6 65.19 ( 56.05 ) 71.76 ( 61.70 ) 68.28 ( 58.71 ) 78.49 ( 67.49 )
28.7 68.31 ( 58.74 ) 78.51 ( 67.51 )
28.8 68.34 ( 58.76 ) 78.53 ( 67.53 )
28.9 68.37 ( 58.79 ) 78.55 ( 67.55 )
29.0 68.40 ( 58.81 ) 78.58 ( 67.56 )
29.1 68.42 ( 58.83 ) 78.60 ( 67.58 )
29.2 68.45 ( 58.86 ) 78.62 ( 67.60 )
29.3 68.48 ( 58.88 ) 78.64 ( 67.62 )
29.4 68.51 ( 58.91 ) 78.66 ( 67.64 )
29.5 68.54 ( 58.93 ) 78.68 ( 67.66 )
29.6 _ 68.56 ( 58.95 ) 78.71 ( 67.67 )
29.7 68.59 ( 58.98 ) 78.73 ( 67.69 )
29.8 68.62 ( 59.00 ) 78.75 ( 67.71 )
29.9 68.65 ( 59.03 ) 78.77 ( 67.73 )
_
30.0 68.68 ( 59.05 ) 78.79 ( 67.75 )
30.1 68.70 ( 59.07 ) 78.81 ( 67.77 )
30.2 68.73 ( 59.10 ) 78.83 ( 67.79 )
30.3 68.76 ( 59.12 ) 78.86 ( 67.80 )
30.4 68.79 ( 59.15 ) 78.88 ( 67.82 )
30.5 68.81 ( 59.17 ) 78.90 ( 67.84 )
30.6 68.84 ( 59.19 ) 78.92 ( 67.86 )
30.7 68.87 ( 59.22 ) 78.94 ( 67.88 )
30.8 68.90 ( 59.24 ) 78.96 ( 67.90 )
30.9 68.93 ( 59.27 ) 78.99 ( 67.92 )
31.0 68.95 ( 59.29 ) 79.01 ( 67.93 )
31.1 68.98 ( 59.31 ) 79.03 ( 67.95 )
31.2 69.01 ( 59.34 ) 79.05 ( 67.97 )
Table 10. Outdoor Unit Capacity (JTOR260~300VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (1)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-26FSXNS
JTOR260VAE(U,F,R)BS1 RAS-28FSXNS
JTOR280VAE(U,F,R)BS1 RAS-30FSXNS
JTOR300VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
13.0 36.50 ( 31.38 ) 41.25 ( 35.47 )
13.1 36.78 ( 31.63 ) 41.57 ( 35.74 )
13.2 37.06 ( 31.87 ) 41.88 ( 36.01 )
13.3 37.34 ( 32.11 ) 42.20 ( 36.29 )
13.4 37.62 ( 32.35 ) 42.52 ( 36.56 )
_
13.5 37.90 ( 32.59 ) 42.84 ( 36.83 )
13.6 38.18 ( 32.83 ) 43.15 ( 37.11 )
13.7 38.47 ( 33.07 ) 43.47 ( 37.38 )
13.8 38.75 ( 33.32 ) 43.79 ( 37.65 )
13.9 39.03 ( 33.56 ) 44.11 ( 37.92 )
_
14.0 39.31 ( 33.80 ) 44.42 ( 38.20 ) 38.75 ( 33.32 ) 45.00 ( 38.69 )
14.1 39.59 ( 34.04 ) 44.74 ( 38.47 ) 39.03 ( 33.56 ) 45.32 ( 38.97 )
14.2 39.87 ( 34.28 ) 45.06 ( 38.74 ) 39.30 ( 33.79 ) 45.64 ( 39.25 )
14.3 40.15 ( 34.52 ) 45.38 ( 39.02 ) 39.58 ( 34.03 ) 45.96 ( 39.52 )
14.4 40.43 ( 34.76 ) 45.69 ( 39.29 ) 39.86 ( 34.27 ) 46.29 ( 39.80 )
14.5 40.71 ( 35.01 ) 46.01 ( 39.56 ) 40.13 ( 34.51 ) 46.61 ( 40.07 )
14.6 40.99 ( 35.25 ) 46.33 ( 39.83 ) 40.41 ( 34.75 ) 46.93 ( 40.35 )
14.7 41.27 ( 35.49 ) 46.64 ( 40.11 ) 40.69 ( 34.98 ) 47.25 ( 40.63 )
14.8 41.55 ( 35.73 ) 46.96 ( 40.38 ) 40.96 ( 35.22 ) 47.57 ( 40.90 )
14.9 41.83 ( 35.97 ) 47.28 ( 40.65 ) 41.24 ( 35.46 ) 47.89 ( 41.18 )
15.0 42.12 ( 36.21 ) 47.60 ( 40.93 ) 41.52 ( 35.70 ) 48.21 ( 41.46 ) 42.50 ( 36.54 ) 47.50 ( 40.84 )
15.1 42.40 ( 36.45 ) 47.91 ( 41.20 ) 41.79 ( 35.94 ) 48.54 ( 41.73 ) 42.78 ( 36.79 ) 47.82 ( 41.11 )
15.2 42.68 ( 36.70 ) 48.23 ( 41.47 ) 42.07 ( 36.17 ) 48.86 ( 42.01 ) 43.07 ( 37.03 ) 48.13 ( 41.39 )
15.3 42.96 ( 36.94 ) 48.55 ( 41.74 ) 42.35 ( 36.41 ) 49.18 ( 42.29 ) 43.35 ( 37.27 ) 48.45 ( 41.66 )
15.4 43.24 ( 37.18 ) 48.87 ( 42.02 ) 42.62 ( 36.65 ) 49.50 ( 42.56 ) 43.63 ( 37.52 ) 48.77 ( 41.93 )
15.5 43.52 ( 37.42 ) 49.18 ( 42.29 ) 42.90 ( 36.89 ) 49.82 ( 42.84 ) 43.92 ( 37.76 ) 49.08 ( 42.20 )
15.6 43.80 ( 37.66 ) 49.50 ( 42.56 ) 43.18 ( 37.13 ) 50.14 ( 43.12 ) 44.20 ( 38.01 ) 49.40 ( 42.48 )
15.7 44.08 ( 37.90 ) 49.82 ( 42.84 ) 43.46 ( 37.36 ) 50.46 ( 43.39 ) 44.48 ( 38.25 ) 49.72 ( 42.75 )
15.8 44.36 ( 38.14 ) 50.13 ( 43.11 ) 43.73 ( 37.60 ) 50.79 ( 43.67 ) 44.77 ( 38.49 ) 50.03 ( 43.02 )
15.9 44.64 ( 38.39 ) 50.45 ( 43.38 ) 44.01 ( 37.84 ) 51.11 ( 43.94 ) 45.05 ( 38.74 ) 50.35 ( 43.29 )
16.0 44.92 ( 38.63 ) 50.77 ( 43.65 ) 44.29 ( 38.08 ) 51.43 ( 44.22 ) 45.33 ( 38.98 ) 50.67 ( 43.57 )
16.1 45.20 ( 38.87 ) 51.09 ( 43.93 ) 44.56 ( 38.32 ) 51.75 ( 44.50 ) 45.62 ( 39.22 ) 50.98 ( 43.84 )
16.2 45.48 ( 39.11 ) 51.40 ( 44.20 ) 44.84 ( 38.55 ) 52.07 ( 44.77 ) 45.90 ( 39.47 ) 51.30 ( 44.11 )
16.3 45.77 ( 39.35 ) 51.72 ( 44.47 ) 45.12 ( 38.79 ) 52.39 ( 45.05 ) 46.18 ( 39.71 ) 51.62 ( 44.38 )
16.4 46.05 ( 39.59 ) 52.04 ( 44.75 ) 45.39 ( 39.03 ) 52.71 ( 45.33 ) 46.47 ( 39.95 ) 51.93 ( 44.65 )
16.5 46.33 ( 39.83 ) 52.36 ( 45.02 ) 45.67 ( 39.27 ) 53.04 ( 45.60 ) 46.75 ( 40.20 ) 52.25 ( 44.93 )
16.6 46.61 ( 40.08 ) 52.67 ( 45.29 ) 45.95 ( 39.51 ) 53.36 ( 45.88 ) 47.03 ( 40.44 ) 52.57 ( 45.20 )
16.7 46.89 ( 40.32 ) 52.99 ( 45.56 ) 46.22 ( 39.74 ) 53.68 ( 46.16 ) 47.32 ( 40.69 ) 52.88 ( 45.47 )
16.8 47.17 ( 40.56 ) 53.31 ( 45.84 ) 46.50 ( 39.98 ) 54.00 ( 46.43 ) 47.60 ( 40.93 ) 53.20 ( 45.74 )
16.9 47.45 ( 40.80 ) 53.62 ( 46.11 ) 46.78 ( 40.22 ) 54.32 ( 46.71 ) 47.88 ( 41.17 ) 53.52 ( 46.02 )
17.0 47.73 ( 41.04 ) 53.94 ( 46.38 ) 47.05 ( 40.46 ) 54.64 ( 46.98 ) 48.17 ( 41.42 ) 53.83 ( 46.29 )
17.1 48.01 ( 41.28 ) 54.26 ( 46.65 ) 47.33 ( 40.70 ) 54.96 ( 47.26 ) 48.45 ( 41.66 ) 54.15 ( 46.56 )
17.2 48.29 ( 41.52 ) 54.58 ( 46.93 ) 47.61 ( 40.93 ) 55.29 ( 47.54 ) 48.73 ( 41.90 ) 54.47 ( 46.83 )
17.3 48.57 ( 41.77 ) 54.89 ( 47.20 ) 47.88 ( 41.17 ) 55.61 ( 47.81 ) 49.02 ( 42.15 ) 54.78 ( 47.11 )
17.4 48.85 ( 42.01 ) 55.21 ( 47.47 ) 48.16 ( 41.41 ) 55.93 ( 48.09 ) 49.30 ( 42.39 ) 55.10 ( 47.38 )
17.5 49.13 ( 42.25 ) 55.53 ( 47.75 ) 48.44 ( 41.65 ) 56.25 ( 48.37 ) 49.58 ( 42.63 ) 55.42 ( 47.65 )
17.6 49.42 ( 42.49 ) 55.85 ( 48.02 ) 48.71 ( 41.89 ) 56.57 ( 48.64 ) 49.87 ( 42.88 ) 55.73 ( 47.92 )
17.7 49.70 ( 42.73 ) 56.16 ( 48.29 ) 48.99 ( 42.12 ) 56.89 ( 48.92 ) 50.15 ( 43.12 ) 56.05 ( 48.19 )
17.8 49.98 ( 42.97 ) 56.48 ( 48.56 ) 49.27 ( 42.36 ) 57.21 ( 49.20 ) 50.43 ( 43.36 ) 56.37 ( 48.47 )
17.9 50.26 ( 43.21 ) 56.80 ( 48.84 ) 49.54 ( 42.60 ) 57.54 ( 49.47 ) 50.72 ( 43.61 ) 56.68 ( 48.74 )
18.0 50.54 ( 43.46 ) 57.12 ( 49.11 ) 49.82 ( 42.84 ) 57.86 ( 49.75 ) 51.00 ( 43.85 ) 57.00 ( 49.01 )
18.1 50.82 ( 43.70 ) 57.43 ( 49.38 ) 50.10 ( 43.08 ) 58.18 ( 50.02 ) 51.28 ( 44.10 ) 57.32 ( 49.28 )
18.2 51.10 ( 43.94 ) 57.75 ( 49.66 ) 50.37 ( 43.31 ) 58.50 ( 50.30 ) 51.57 ( 44.34 ) 57.63 ( 49.56 )
18.3 51.38 ( 44.18 ) 58.07 ( 49.93 ) 50.65 ( 43.55 ) 58.82 ( 50.58 ) 51.85 ( 44.58 ) 57.95 ( 49.83 )
18.4 51.66 ( 44.42 ) 58.38 ( 50.20 ) 50.93 ( 43.79 ) 59.14 ( 50.85 ) 52.13 ( 44.83 ) 58.27 ( 50.10 )
18.5 51.94 ( 44.66 ) 58.70 ( 50.47 ) 51.21 ( 44.03 ) 59.46 ( 51.13 ) 52.42 ( 45.07 ) 58.58 ( 50.37 )
18.6 52.22 ( 44.90 ) 59.02 ( 50.75 ) 51.48 ( 44.27 ) 59.79 ( 51.41 ) 52.70 ( 45.31 ) 58.90 ( 50.64 )
18.7 52.50 ( 45.15 ) 59.34 ( 51.02 ) 51.76 ( 44.50 ) 60.11 ( 51.68 ) 52.98 ( 45.56 ) 59.22 ( 50.92 )
18.8 52.78 ( 45.39 ) 59.65 ( 51.29 ) 52.04 ( 44.74 ) 60.43 ( 51.96 ) 53.27 ( 45.80 ) 59.53 ( 51.19 )
18.9 53.07 ( 45.63 ) 59.97 ( 51.57 ) 52.31 ( 44.98 ) 60.75 ( 52.24 ) 53.55 ( 46.04 ) 59.85 ( 51.46 )
Table 11. Outdoor Unit Capacity (JTOR260~300VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (2)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-26FSXNS
JTOR260VAE(U,F,R)BS1 RAS-28FSXNS
JTOR280VAE(U,F,R)BS1 RAS-30FSXNS
JTOR300VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
19.0 53.35 ( 45.87 ) 60.29 ( 51.84 ) 52.59 ( 45.22 ) 61.07 ( 52.51 ) 53.83 ( 46.29 ) 60.17 ( 51.73 )
19.1 53.63 ( 46.11 ) 60.61 ( 52.11 ) 52.87 ( 45.46 ) 61.39 ( 52.79 ) 54.12 ( 46.53 ) 60.48 ( 52.01 )
19.2 53.91 ( 46.35 ) 60.92 ( 52.38 ) 53.14 ( 45.69 ) 61.71 ( 53.06 ) 54.40 ( 46.78 ) 60.80 ( 52.28 )
19.3 54.19 ( 46.59 ) 61.24 ( 52.66 ) 53.42 ( 45.93 ) 62.04 ( 53.34 ) 54.68 ( 47.02 ) 61.12 ( 52.55 )
19.4 54.47 ( 46.84 ) 61.56 ( 52.93 ) 53.70 ( 46.17 ) 62.36 ( 53.62 ) 54.97 ( 47.26 ) 61.43 ( 52.82 )
19.5 54.75 ( 47.08 ) 61.87 ( 53.20 ) 53.97 ( 46.41 ) 62.68 ( 53.89 ) 55.25 ( 47.51 ) 61.75 ( 53.10 )
19.6 55.03 ( 47.32 ) 62.19 ( 53.48 ) 54.25 ( 46.65 ) 63.00 ( 54.17 ) 55.53 ( 47.75 ) 62.07 ( 53.37 )
19.7 55.31 ( 47.56 ) 62.51 ( 53.75 ) 54.53 ( 46.88 ) 63.32 ( 54.45 ) 55.82 ( 47.99 ) 62.38 ( 53.64 )
19.8 55.59 ( 47.80 ) 62.83 ( 54.02 ) 54.80 ( 47.12 ) 63.64 ( 54.72 ) 56.10 ( 48.24 ) 62.70 ( 53.91 )
19.9 55.87 ( 48.04 ) 63.14 ( 54.29 ) 55.08 ( 47.36 ) 63.96 ( 55.00 ) 56.38 ( 48.48 ) 63.02 ( 54.18 )
20.0 56.15 ( 48.28 ) 63.46 ( 54.57 ) 55.36 ( 47.60 ) 64.29 ( 55.28 ) 56.67 ( 48.72 ) 63.33 ( 54.46 )
20.1 56.43 ( 48.53 ) 63.78 ( 54.84 ) 55.63 ( 47.84 ) 64.61 ( 55.55 ) 56.95 ( 48.97 ) 63.65 ( 54.73 )
20.2 56.72 ( 48.77 ) 64.10 ( 55.11 ) 55.91 ( 48.07 ) 64.93 ( 55.83 ) 57.23 ( 49.21 ) 63.97 ( 55.00 )
20.3 57.00 ( 49.01 ) 64.41 ( 55.39 ) 56.19 ( 48.31 ) 65.25 ( 56.10 ) 57.52 ( 49.46 ) 64.28 ( 55.27 )
20.4 57.28 ( 49.25 ) 64.73 ( 55.66 ) 56.46 ( 48.55 ) 65.57 ( 56.38 ) 57.80 ( 49.70 ) 64.60 ( 55.55 )
20.5 57.56 ( 49.49 ) 65.05 ( 55.93 ) 56.74 ( 48.79 ) 65.89 ( 56.66 ) 58.08 ( 49.94 ) 64.92 ( 55.82 )
20.6 57.84 ( 49.73 ) 65.37 ( 56.20 ) 57.02 ( 49.03 ) 66.21 ( 56.93 ) 58.37 ( 50.19 ) 65.23 ( 56.09 )
20.7 58.12 ( 49.97 ) 65.68 ( 56.48 ) 57.29 ( 49.26 ) 66.54 ( 57.21 ) 58.65 ( 50.43 ) 65.55 ( 56.36 )
20.8 58.40 ( 50.21 ) 66.00 ( 56.75 ) 57.57 ( 49.50 ) 66.86 ( 57.49 ) 58.93 ( 50.67 ) 65.87 ( 56.64 )
20.9 58.68 ( 50.46 ) 66.32 ( 57.02 ) 57.85 ( 49.74 ) 67.18 ( 57.76 ) 59.22 ( 50.92 ) 66.18 ( 56.91 )
21.0 58.96 ( 50.70 ) 66.63 ( 57.30 ) 58.12 ( 49.98 ) 67.50 ( 58.04 ) 59.50 ( 51.16 ) 66.50 ( 57.18 )
21.1 59.24 ( 50.94 ) 66.95 ( 57.57 ) 58.40 ( 50.22 ) 67.82 ( 58.32 ) 59.78 ( 51.40 ) 66.82 ( 57.45 )
21.2 59.52 ( 51.18 ) 67.27 ( 57.84 ) 58.68 ( 50.45 ) 68.14 ( 58.59 ) 60.07 ( 51.65 ) 67.13 ( 57.72 )
21.3 59.80 ( 51.42 ) 67.59 ( 58.11 ) 58.96 ( 50.69 ) 68.46 ( 58.87 ) 60.35 ( 51.89 ) 67.45 ( 58.00 )
21.4 60.08 ( 51.66 ) 67.90 ( 58.39 ) 59.23 ( 50.93 ) 68.79 ( 59.15 ) 60.63 ( 52.14 ) 67.77 ( 58.27 )
21.5 60.37 ( 51.90 ) 68.22 ( 58.66 ) 59.51 ( 51.17 ) 69.11 ( 59.42 ) 60.92 ( 52.38 ) 68.08 ( 58.54 )
21.6 60.65 ( 52.15 ) 68.54 ( 58.93 ) 59.79 ( 51.41 ) 69.43 ( 59.70 ) 61.20 ( 52.62 ) 68.40 ( 58.81 )
21.7 60.93 ( 52.39 ) 68.86 ( 59.21 ) 60.06 ( 51.64 ) 69.75 ( 59.97 ) 61.48 ( 52.87 ) 68.72 ( 59.09 )
21.8 61.21 ( 52.63 ) 69.17 ( 59.48 ) 60.34 ( 51.88 ) 70.07 ( 60.25 ) 61.77 ( 53.11 ) 69.03 ( 59.36 )
21.9 61.49 ( 52.87 ) 69.49 ( 59.75 ) 60.62 ( 52.12 ) 70.39 ( 60.53 ) 62.05 ( 53.35 ) 69.35 ( 59.63 )
22.0 61.77 ( 53.11 ) 69.81 ( 60.02 ) 60.89 ( 52.36 ) 70.71 ( 60.80 ) 62.33 ( 53.60 ) 69.67 ( 59.90 )
22.1 62.05 ( 53.35 ) 70.13 ( 60.30 ) 61.17 ( 52.60 ) 71.04 ( 61.08 ) 62.62 ( 53.84 ) 69.98 ( 60.17 )
22.2 62.33 ( 53.59 ) 70.44 ( 60.57 ) 61.45 ( 52.83 ) 71.36 ( 61.36 ) 62.90 ( 54.08 ) 70.30 ( 60.45 )
22.3 62.61 ( 53.84 ) 70.76 ( 60.84 ) 61.72 ( 53.07 ) 71.68 ( 61.63 ) 63.18 ( 54.33 ) 70.62 ( 60.72 )
22.4 62.89 ( 54.08 ) 71.08 ( 61.12 ) 62.00 ( 53.31 ) 72.00 ( 61.91 ) 63.47 ( 54.57 ) 70.93 ( 60.99 )
22.5 63.17 ( 54.32 ) 71.39 ( 61.39 ) 62.28 ( 53.55 ) 72.32 ( 62.19 ) 63.75 ( 54.82 ) 71.25 ( 61.26 )
22.6 63.45 ( 54.56 ) 71.71 ( 61.66 ) 62.55 ( 53.79 ) 72.64 ( 62.46 ) 64.03 ( 55.06 ) 71.57 ( 61.54 )
22.7 63.73 ( 54.80 ) 72.03 ( 61.93 ) 62.83 ( 54.02 ) 72.96 ( 62.74 ) 64.32 ( 55.30 ) 71.88 ( 61.81 )
22.8 64.02 ( 55.04 ) 72.35 ( 62.21 ) 63.11 ( 54.26 ) 73.29 ( 63.01 ) 64.60 ( 55.55 ) 72.20 ( 62.08 )
22.9 64.30 ( 55.28 ) 72.66 ( 62.48 ) 63.38 ( 54.50 ) 73.61 ( 63.29 ) 64.88 ( 55.79 ) 72.52 ( 62.35 )
23.0 64.58 ( 55.53 ) 72.98 ( 62.75 ) 63.66 ( 54.74 ) 73.93 ( 63.57 ) 65.17 ( 56.03 ) 72.83 ( 62.63 )
23.1 64.86 ( 55.77 ) 73.30 ( 63.03 ) 63.94 ( 54.98 ) 74.25 ( 63.84 ) 65.45 ( 56.28 ) 73.15 ( 62.90 )
23.2 65.14 ( 56.01 ) 73.62 ( 63.30 ) 64.21 ( 55.21 ) 74.57 ( 64.12 ) 65.73 ( 56.52 ) 73.47 ( 63.17 )
23.3 65.42 ( 56.25 ) 73.93 ( 63.57 ) 64.49 ( 55.45 ) 74.89 ( 64.40 ) 66.02 ( 56.76 ) 73.78 ( 63.44 )
23.4 65.70 ( 56.49 ) 74.25 ( 63.84 ) 64.77 ( 55.69 ) 75.21 ( 64.67 ) 66.30 ( 57.01 ) 74.10 ( 63.71 )
23.5 65.98 ( 56.73 ) 74.57 ( 64.12 ) 65.04 ( 55.93 ) 75.54 ( 64.95 ) 66.58 ( 57.25 ) 74.42 ( 63.99 )
23.6 66.26 ( 56.97 ) 74.88 ( 64.39 ) 65.32 ( 56.17 ) 75.86 ( 65.23 ) 66.87 ( 57.49 ) 74.73 ( 64.26 )
23.7 66.54 ( 57.22 ) 75.20 ( 64.66 ) 65.60 ( 56.40 ) 76.18 ( 65.50 ) 67.15 ( 57.74 ) 75.05 ( 64.53 )
23.8 66.82 ( 57.46 ) 75.52 ( 64.93 ) 65.87 ( 56.64 ) 76.50 ( 65.78 ) 67.43 ( 57.98 ) 75.37 ( 64.80 )
23.9 67.10 ( 57.70 ) 75.84 ( 65.21 ) 66.15 ( 56.88 ) 76.82 ( 66.05 ) 67.72 ( 58.23 ) 75.68 ( 65.08 )
24.0 67.38 ( 57.94 ) 76.15 ( 65.48 ) 66.43 ( 57.12 ) 77.14 ( 66.33 ) 68.00 ( 58.47 ) 76.00 ( 65.35 )
24.1 67.67 ( 58.18 ) 76.47 ( 65.75 ) 66.71 ( 57.36 ) 77.46 ( 66.61 ) 68.28 ( 58.71 ) 76.32 ( 65.62 )
24.2 67.95 ( 58.42 ) 76.79 ( 66.03 ) 66.98 ( 57.59 ) 77.79 ( 66.88 ) 68.57 ( 58.96 ) 76.63 ( 65.89 )
24.3 68.23 ( 58.66 ) 77.11 ( 66.30 ) 67.26 ( 57.83 ) 78.11 ( 67.16 ) 68.85 ( 59.20 ) 76.95 ( 66.17 )
24.4 68.51 ( 58.91 ) 77.42 ( 66.57 ) 67.54 ( 58.07 ) 78.43 ( 67.44 ) 69.13 ( 59.44 ) 77.27 ( 66.44 )
24.5 68.79 ( 59.15 ) 77.74 ( 66.84 ) 67.81 ( 58.31 ) 78.75 ( 67.71 ) 69.42 ( 59.69 ) 77.58 ( 66.71 )
24.6 69.07 ( 59.39 ) 78.06 ( 67.12 ) 68.09 ( 58.55 ) 79.07 ( 67.99 ) 69.70 ( 59.93 ) 77.90 ( 66.98 )
24.7 69.35 ( 59.63 ) 78.38 ( 67.39 ) 68.37 ( 58.78 ) 79.39 ( 68.27 ) 69.98 ( 60.17 ) 78.22 ( 67.25 )
24.8 69.63 ( 59.87 ) 78.69 ( 67.66 ) 68.64 ( 59.02 ) 79.71 ( 68.54 ) 70.27 ( 60.42 ) 78.53 ( 67.53 )
24.9 69.91 ( 60.11 ) 79.01 ( 67.94 ) 68.92 ( 59.26 ) 80.04 ( 68.82 ) 70.55 ( 60.66 ) 78.85 ( 67.80 )
Table 12. Outdoor Unit Capacity (JTOR260~300VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (3)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-26FSXNS
JTOR260VAE(U,F,R)BS1 RAS-28FSXNS
JTOR280VAE(U,F,R)BS1 RAS-30FSXNS
JTOR300VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
25.0 70.19 ( 60.35 ) 79.33 ( 68.21 ) 69.20 ( 59.50 ) 80.36 ( 69.09 ) 70.83 ( 60.91 ) 79.17 ( 68.07 )
25.1 70.47 ( 60.60 ) 79.64 ( 68.48 ) 69.47 ( 59.74 ) 80.68 ( 69.37 ) 71.12 ( 61.15 ) 79.48 ( 68.34 )
25.2 70.75 ( 60.84 ) 79.96 ( 68.75 ) 69.75 ( 59.97 ) 81.00 ( 69.65 ) 71.40 ( 61.39 ) 79.80 ( 68.62 )
25.3 71.03 ( 61.08 ) 80.28 ( 69.03 ) 70.03 ( 60.21 ) 81.32 ( 69.92 ) 71.68 ( 61.64 ) 80.12 ( 68.89 )
25.4 71.32 ( 61.32 ) 80.60 ( 69.30 ) 70.30 ( 60.45 ) 81.64 ( 70.20 ) 71.97 ( 61.88 ) 80.43 ( 69.16 )
25.5 71.60 ( 61.56 ) 80.91 ( 69.57 ) 70.58 ( 60.69 ) 81.96 ( 70.48 ) 72.25 ( 62.12 ) 80.75 ( 69.43 )
25.6 71.88 ( 61.80 ) 81.23 ( 69.85 ) 70.86 ( 60.93 ) 82.29 ( 70.75 ) 72.53 ( 62.37 ) 81.07 ( 69.70 )
25.7 72.16 ( 62.04 ) 81.55 ( 70.12 ) 71.13 ( 61.16 ) 82.61 ( 71.03 ) 72.82 ( 62.61 ) 81.38 ( 69.98 )
25.8 72.44 ( 62.29 ) 81.87 ( 70.39 ) 71.41 ( 61.40 ) 82.93 ( 71.31 ) 73.10 ( 62.85 ) 81.70 ( 70.25 )
25.9 72.72 ( 62.53 ) 82.18 ( 70.66 ) 71.69 ( 61.64 ) 83.25 ( 71.58 ) 73.38 ( 63.10 ) 82.02 ( 70.52 )
26.0 73.00 ( 62.77 ) 82.50 ( 70.94 ) 71.96 ( 61.88 ) 83.57 ( 71.86 ) 73.67 ( 63.34 ) 82.33 ( 70.79 )
26.1 73.28 ( 63.01 ) 82.82 ( 71.21 ) 72.24 ( 62.12 ) 83.89 ( 72.13 ) 73.95 ( 63.59 ) 82.65 ( 71.07 )
26.2 73.56 ( 63.25 ) 83.13 ( 71.48 ) 72.52 ( 62.35 ) 84.21 ( 72.41 ) 74.23 ( 63.83 ) 82.97 ( 71.34 )
26.3 73.84 ( 63.49 ) 83.45 ( 71.76 ) 72.79 ( 62.59 ) 84.54 ( 72.69 ) 74.52 ( 64.07 ) 83.28 ( 71.61 )
26.4 74.12 ( 63.73 ) 83.77 ( 72.03 ) 73.07 ( 62.83 ) 84.86 ( 72.96 ) 74.80 ( 64.32 ) 83.60 ( 71.88 )
26.5 74.40 ( 63.98 ) 84.09 ( 72.30 ) 73.35 ( 63.07 ) 85.18 ( 73.24 ) 75.08 ( 64.56 ) 83.92 ( 72.16 )
26.6 74.68 ( 64.22 ) 84.40 ( 72.57 ) 73.62 ( 63.31 ) 85.50 ( 73.52 ) 75.37 ( 64.80 ) 84.23 ( 72.43 )
26.7 74.97 ( 64.46 ) 84.72 ( 72.85 ) 73.90 ( 63.54 ) 85.82 ( 73.79 ) 75.65 ( 65.05 ) 84.55 ( 72.70 )
26.8 75.20 ( 64.66 ) 84.98 ( 73.07 ) 74.18 ( 63.78 ) 86.14 ( 74.07 ) 75.93 ( 65.29 ) 84.87 ( 72.97 )
26.9 75.23 ( 64.68 ) 84.99 ( 73.08 ) 74.46 ( 64.02 ) 86.46 ( 74.35 ) 76.22 ( 65.53 ) 85.18 ( 73.24 )
27.0 75.26 ( 64.71 ) 85.00 ( 73.09 ) 74.73 ( 64.26 ) 86.79 ( 74.62 ) 76.50 ( 65.78 ) 85.50 ( 73.52 )
27.1 75.29 ( 64.74 ) 85.01 ( 73.10 ) 75.01 ( 64.50 ) 87.11 ( 74.90 ) 76.78 ( 66.02 ) 85.82 ( 73.79 )
27.2 75.32 ( 64.76 ) 85.02 ( 73.11 ) 75.29 ( 64.73 ) 87.43 ( 75.18 ) 77.07 ( 66.27 ) 86.13 ( 74.06 )
27.3 75.35 ( 64.79 ) 85.04 ( 73.12 ) 75.56 ( 64.97 ) 87.75 ( 75.45 ) 77.35 ( 66.51 ) 86.45 ( 74.33 )
27.4 75.38 ( 64.82 ) 85.05 ( 73.13 ) 75.84 ( 65.21 ) 88.07 ( 75.73 ) 77.63 ( 66.75 ) 86.77 ( 74.61 )
27.5 75.41 ( 64.84 ) 85.06 ( 73.14 ) 76.12 ( 65.45 ) 88.39 ( 76.00 ) 77.92 ( 67.00 ) 87.08 ( 74.88 )
27.6 75.45 ( 64.87 ) 85.07 ( 73.15 ) 76.39 ( 65.69 ) 88.71 ( 76.28 ) 78.20 ( 67.24 ) 87.40 ( 75.15 )
27.7 75.48 ( 64.90 ) 85.08 ( 73.16 ) 76.67 ( 65.92 ) 89.04 ( 76.56 ) 78.48 ( 67.48 ) 87.72 ( 75.42 )
27.8 75.51 ( 64.93 ) 85.09 ( 73.17 ) 76.95 ( 66.16 ) 89.36 ( 76.83 ) 78.77 ( 67.73 ) 88.03 ( 75.70 )
27.9 75.54 ( 64.95 ) 85.11 ( 73.18 ) 77.22 ( 66.40 ) 89.68 ( 77.11 ) 79.05 ( 67.97 ) 88.35 ( 75.97 )
28.0 75.57 ( 64.98 ) 85.12 ( 73.19 ) 77.50 ( 66.64 ) 90.00 ( 77.39 ) 79.33 ( 68.21 ) 88.67 ( 76.24 )
28.1 75.60 ( 65.01 ) 85.13 ( 73.20 ) 77.78 ( 66.88 ) 90.32 ( 77.66 ) 79.62 ( 68.46 ) 88.98 ( 76.51 )
28.2 75.63 ( 65.03 ) 85.14 ( 73.21 ) 78.05 ( 67.11 ) 90.64 ( 77.94 ) 79.90 ( 68.70 ) 89.30 ( 76.78 )
28.3 75.66 ( 65.06 ) 85.15 ( 73.22 ) 78.33 ( 67.35 ) 90.96 ( 78.22 ) 80.18 ( 68.95 ) 89.62 ( 77.06 )
28.4 75.70 ( 65.09 ) 85.17 ( 73.23 ) 78.61 ( 67.59 ) 91.29 ( 78.49 ) 80.47 ( 69.19 ) 89.93 ( 77.33 )
28.5 75.73 ( 65.11 ) 85.18 ( 73.24 ) 78.88 ( 67.83 ) 91.61 ( 78.77 ) 80.75 ( 69.43 ) 90.25 ( 77.60 )
28.6 75.76 ( 65.14 ) 85.19 ( 73.25 ) 79.16 ( 68.07 ) 91.93 ( 79.04 ) 81.03 ( 69.68 ) 90.57 ( 77.87 )
28.7 75.79 ( 65.17 ) 85.20 ( 73.26 ) 79.44 ( 68.30 ) 92.25 ( 79.32 ) 81.32 ( 69.92 ) 90.88 ( 78.15 )
28.8 75.82 ( 65.19 ) 85.21 ( 73.27 ) 79.71 ( 68.54 ) 92.57 ( 79.60 ) 81.60 ( 70.16 ) 91.20 ( 78.42 )
28.9 75.85 ( 65.22 ) 85.22 ( 73.28 ) 79.84 ( 68.65 ) 92.71 ( 79.71 ) 81.88 ( 70.41 ) 91.52 ( 78.69 )
29.0 75.88 ( 65.25 ) 85.24 ( 73.29 ) 79.87 ( 68.68 ) 92.72 ( 79.72 ) 82.17 ( 70.65 ) 91.83 ( 78.96 )
29.1 75.91 ( 65.27 ) 85.25 ( 73.30 ) 79.90 ( 68.71 ) 92.73 ( 79.73 ) 82.45 ( 70.89 ) 92.15 ( 79.23 )
29.2 75.94 ( 65.30 ) 85.26 ( 73.31 ) 79.94 ( 68.73 ) 92.74 ( 79.74 ) 82.73 ( 71.14 ) 92.47 ( 79.51 )
29.3 75.98 ( 65.33 ) 85.27 ( 73.32 ) 79.97 ( 68.76 ) 92.75 ( 79.75 ) 83.02 ( 71.38 ) 92.78 ( 79.78 )
29.4 76.01 ( 65.35 ) 85.28 ( 73.33 ) 80.00 ( 68.79 ) 92.77 ( 79.76 ) 83.30 ( 71.63 ) 93.10 ( 80.05 )
29.5 76.04 ( 65.38 ) 85.29 ( 73.34 ) 80.03 ( 68.81 ) 92.78 ( 79.78 ) 83.58 ( 71.87 ) 93.42 ( 80.32 )
29.6 76.07 ( 65.41 ) 85.31 ( 73.35 ) 80.06 ( 68.84 ) 92.79 ( 79.79 ) 83.87 ( 72.11 ) 93.73 ( 80.60 )
29.7 76.10 ( 65.44 ) 85.32 ( 73.36 ) 80.09 ( 68.86 ) 92.80 ( 79.80 ) 84.15 ( 72.36 ) 94.05 ( 80.87 )
29.8 76.13 ( 65.46 ) 85.33 ( 73.37 ) 80.12 ( 68.89 ) 92.81 ( 79.81 ) 84.43 ( 72.60 ) 94.37 ( 81.14 )
29.9 76.16 ( 65.49 ) 85.34 ( 73.38 ) 80.15 ( 68.92 ) 92.83 ( 79.82 ) 84.72 ( 72.84 ) 94.68 ( 81.41 )
30.0 76.19 ( 65.52 ) 85.35 ( 73.39 ) 80.18 ( 68.94 ) 92.84 ( 79.83 ) 85.00 ( 73.09 ) 95.00 ( 81.69 )
30.1 76.23 ( 65.54 ) 85.37 ( 73.40 ) 80.21 ( 68.97 ) 92.85 ( 79.84 ) 85.03 ( 73.11 ) 95.02 ( 81.70 )
30.2 76.26 ( 65.57 ) 85.38 ( 73.41 ) 80.24 ( 69.00 ) 92.86 ( 79.85 ) 85.06 ( 73.14 ) 95.04 ( 81.72 )
30.3 76.29 ( 65.60 ) 85.39 ( 73.42 ) 80.27 ( 69.02 ) 92.87 ( 79.86 ) 85.09 ( 73.16 ) 95.06 ( 81.74 )
30.4 76.32 ( 65.62 ) 85.40 ( 73.43 ) 80.30 ( 69.05 ) 92.89 ( 79.87 ) 85.11 ( 73.18 ) 95.08 ( 81.76 )
30.5 76.35 ( 65.65 ) 85.41 ( 73.44 ) 80.34 ( 69.08 ) 92.90 ( 79.88 ) 85.14 ( 73.21 ) 95.11 ( 81.78 )
30.6 76.38 ( 65.68 ) 85.42 ( 73.45 ) 80.37 ( 69.10 ) 92.91 ( 79.89 ) 85.17 ( 73.23 ) 95.13 ( 81.79 )
30.7 76.41 ( 65.70 ) 85.44 ( 73.46 ) 80.40 ( 69.13 ) 92.92 ( 79.90 ) 85.20 ( 73.26 ) 95.15 ( 81.81 )
30.8 76.44 ( 65.73 ) 85.45 ( 73.47 ) 80.43 ( 69.16 ) 92.93 ( 79.91 ) 85.23 ( 73.28 ) 95.17 ( 81.83 )
30.9 76.48 ( 65.76 ) 85.46 ( 73.48 ) 80.46 ( 69.18 ) 92.95 ( 79.92 ) 85.26 ( 73.31 ) 95.19 ( 81.85 )
Table 13. Outdoor Unit Capacity (JTOR260~300VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (4)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-26FSXNS
JTOR260VAE(U,F,R)BS1 RAS-28FSXNS
JTOR280VAE(U,F,R)BS1 RAS-30FSXNS
JTOR300VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
31.0 76.51 ( 65.78 ) 85.47 ( 73.49 ) 80.49 ( 69.21 ) 92.96 ( 79.93 ) 85.28 ( 73.33 ) 95.21 ( 81.87 )
31.1 76.54 ( 65.81 ) 85.48 ( 73.50 ) 80.52 ( 69.23 ) 92.97 ( 79.94 ) 85.31 ( 73.35 ) 95.23 ( 81.88 )
31.2 76.57 ( 65.84 ) 85.49 ( 73.51 ) 80.55 ( 69.26 ) 92.98 ( 79.95 ) 85.34 ( 73.38 ) 95.25 ( 81.90 )
31.3 76.60 ( 65.86 ) 85.51 ( 73.52 ) 80.58 ( 69.29 ) 92.99 ( 79.96 ) 85.37 ( 73.40 ) 95.27 ( 81.92 )
31.4 76.63 ( 65.89 ) 85.52 ( 73.53 ) 80.61 ( 69.31 ) 93.00 ( 79.97 ) 85.40 ( 73.43 ) 95.30 ( 81.94 )
31.5 76.66 ( 65.92 ) 85.53 ( 73.54 ) 80.64 ( 69.34 ) 93.02 ( 79.98 ) 85.43 ( 73.45 ) 95.32 ( 81.96 )
31.6 76.69 ( 65.94 ) 85.54 ( 73.55 ) 80.67 ( 69.37 ) 93.03 ( 79.99 ) 85.45 ( 73.48 ) 95.34 ( 81.98 )
31.7 76.72 ( 65.97 ) 85.55 ( 73.56 ) 80.70 ( 69.39 ) 93.04 ( 80.00 ) 85.48 ( 73.50 ) 95.36 ( 81.99 )
31.8 76.76 ( 66.00 ) 85.56 ( 73.57 ) 80.74 ( 69.42 ) 93.05 ( 80.01 ) 85.51 ( 73.53 ) 95.38 ( 82.01 )
31.9 76.79 ( 66.03 ) 85.58 ( 73.58 ) 80.77 ( 69.45 ) 93.06 ( 80.02 ) 85.54 ( 73.55 ) 95.40 ( 82.03 )
32.0 76.82 ( 66.05 ) 85.59 ( 73.59 ) 80.80 ( 69.47 ) 93.08 ( 80.03 ) 85.57 ( 73.57 ) 95.42 ( 82.05 )
32.1 76.85 ( 66.08 ) 85.60 ( 73.60 ) 80.83 ( 69.50 ) 93.09 ( 80.04 ) 85.60 ( 73.60 ) 95.44 ( 82.07 )
32.2 76.88 ( 66.11 ) 85.61 ( 73.61 ) 80.86 ( 69.53 ) 93.10 ( 80.05 ) 85.62 ( 73.62 ) 95.46 ( 82.08 )
32.3 76.91 ( 66.13 ) 85.62 ( 73.62 ) 80.89 ( 69.55 ) 93.11 ( 80.06 ) 85.65 ( 73.65 ) 95.49 ( 82.10 )
32.4 76.94 ( 66.16 ) 85.64 ( 73.63 ) 80.92 ( 69.58 ) 93.12 ( 80.07 ) 85.68 ( 73.67 ) 95.51 ( 82.12 )
32.5 76.97 ( 66.19 ) 85.65 ( 73.64 ) 80.95 ( 69.60 ) 93.14 ( 80.08 ) 85.71 ( 73.70 ) 95.53 ( 82.14 )
32.6 77.01 ( 66.21 ) 85.66 ( 73.65 ) 80.98 ( 69.63 ) 93.15 ( 80.09 ) 85.74 ( 73.72 ) 95.55 ( 82.16 )
32.7 77.04 ( 66.24 ) 85.67 ( 73.66 ) 81.01 ( 69.66 ) 93.16 ( 80.10 ) 85.77 ( 73.74 ) 95.57 ( 82.18 )
32.8 77.07 ( 66.27 ) 85.68 ( 73.67 ) 81.04 ( 69.68 ) 93.17 ( 80.11 ) 85.79 ( 73.77 ) 95.59 ( 82.19 )
32.9 77.10 ( 66.29 ) 85.69 ( 73.68 ) 81.07 ( 69.71 ) 93.18 ( 80.12 ) 85.82 ( 73.79 ) 95.61 ( 82.21 )
33.0 77.13 ( 66.32 ) 85.71 ( 73.69 ) 81.10 ( 69.74 ) 93.20 ( 80.13 ) 85.85 ( 73.82 ) 95.63 ( 82.23 )
33.1 77.16 ( 66.35 ) 85.72 ( 73.70 ) 81.14 ( 69.76 ) 93.21 ( 80.14 ) 85.88 ( 73.84 ) 95.65 ( 82.25 )
33.2 77.19 ( 66.37 ) 85.73 ( 73.71 ) 81.17 ( 69.79 ) 93.22 ( 80.15 ) 85.91 ( 73.87 ) 95.68 ( 82.27 )
33.3 77.22 ( 66.40 ) 85.74 ( 73.72 ) 81.20 ( 69.82 ) 93.23 ( 80.16 ) 85.94 ( 73.89 ) 95.70 ( 82.28 )
33.4 77.26 ( 66.43 ) 85.75 ( 73.73 ) 81.23 ( 69.84 ) 93.24 ( 80.17 ) 85.96 ( 73.92 ) 95.72 ( 82.30 )
33.5 77.29 ( 66.45 ) 85.76 ( 73.74 ) 81.26 ( 69.87 ) 93.25 ( 80.18 ) 85.99 ( 73.94 ) 95.74 ( 82.32 )
33.6 77.32 ( 66.48 ) 85.78 ( 73.75 ) 81.29 ( 69.90 ) 93.27 ( 80.19 ) 86.02 ( 73.96 ) 95.76 ( 82.34 )
33.7 77.35 ( 66.51 ) 85.79 ( 73.76 ) 81.32 ( 69.92 ) 93.28 ( 80.21 ) 86.05 ( 73.99 ) 95.78 ( 82.36 )
33.8 77.38 ( 66.53 ) 85.80 ( 73.77 ) 81.35 ( 69.95 ) 93.29 ( 80.22 ) 86.08 ( 74.01 ) 95.80 ( 82.38 )
33.9 81.38 ( 69.98 ) 93.30 ( 80.23 ) 86.11 ( 74.04 ) 95.82 ( 82.39 )
34.0 81.41 ( 70.00 ) 93.31 ( 80.24 ) 86.13 ( 74.06 ) 95.84 ( 82.41 )
34.1 81.44 ( 70.03 ) 93.33 ( 80.25 ) 86.16 ( 74.09 ) 95.87 ( 82.43 )
34.2 81.47 ( 70.05 ) 93.34 ( 80.26 ) 86.19 ( 74.11 ) 95.89 ( 82.45 )
34.3 81.50 ( 70.08 ) 93.35 ( 80.27 ) 86.22 ( 74.13 ) 95.91 ( 82.47 )
34.4 81.53 ( 70.11 ) 93.36 ( 80.28 ) 86.25 ( 74.16 ) 95.93 ( 82.48 )
34.5 81.57 ( 70.13 ) 93.37 ( 80.29 ) 86.28 ( 74.18 ) 95.95 ( 82.50 )
34.6 81.60 ( 70.16 ) 93.39 ( 80.30 ) 86.30 ( 74.21 ) 95.97 ( 82.52 )
34.7 81.63 ( 70.19 ) 93.40 ( 80.31 ) 86.33 ( 74.23 ) 95.99 ( 82.54 )
34.8 81.66 ( 70.21 ) 93.41 ( 80.32 ) 86.36 ( 74.26 ) 96.01 ( 82.56 )
34.9 81.69 ( 70.24 ) 93.42 ( 80.33 ) 86.39 ( 74.28 ) 96.03 ( 82.57 )
35.0 81.72 ( 70.27 ) 93.43 ( 80.34 ) 86.42 ( 74.30 ) 96.06 ( 82.59 )
35.1 81.75 ( 70.29 ) 93.45 ( 80.35 ) 86.45 ( 74.33 ) 96.08 ( 82.61 )
35.2 81.78 ( 70.32 ) 93.46 ( 80.36 ) 86.47 ( 74.35 ) 96.10 ( 82.63 )
35.3 81.81 ( 70.35 ) 93.47 ( 80.37 ) 86.50 ( 74.38 ) 96.12 ( 82.65 )
35.4 _ 81.84 ( 70.37 ) 93.48 ( 80.38 ) 86.53 ( 74.40 ) 96.14 ( 82.67 )
35.5 81.87 ( 70.40 ) 93.49 ( 80.39 ) 86.56 ( 74.43 ) 96.16 ( 82.68 )
35.6 81.90 ( 70.42 ) 93.50 ( 80.40 ) 86.59 ( 74.45 ) 96.18 ( 82.70 )
35.7 81.93 ( 70.45 ) 93.52 ( 80.41 ) 86.62 ( 74.48 ) 96.20 ( 82.72 )
35.8 81.97 ( 70.48 ) 93.53 ( 80.42 ) 86.64 ( 74.50 ) 96.22 ( 82.74 )
35.9 82.00 ( 70.50 ) 93.54 ( 80.43 ) 86.67 ( 74.52 ) 96.25 ( 82.76 )
36.0 82.03 ( 70.53 ) 93.55 ( 80.44 ) 86.70 ( 74.55 ) 96.27 ( 82.77 )
36.1 82.06 ( 70.56 ) 93.56 ( 80.45 ) 86.73 ( 74.57 ) 96.29 ( 82.79 )
36.2 82.09 ( 70.58 ) 93.58 ( 80.46 ) 86.76 ( 74.60 ) 96.31 ( 82.81 )
36.3 82.12 ( 70.61 ) 93.59 ( 80.47 ) 86.79 ( 74.62 ) 96.33 ( 82.83 )
36.4 82.15 ( 70.64 ) 93.60 ( 80.48 ) 86.81 ( 74.65 ) 96.35 ( 82.85 )
36.5 86.84 ( 74.67 ) 96.37 ( 82.87 )
36.6 86.87 ( 74.69 ) 96.39 ( 82.88 )
36.7 _ 86.90 ( 74.72 ) 96.41 ( 82.90 )
36.8 86.93 ( 74.74 ) 96.44 ( 82.92 )
36.9 86.96 ( 74.77 ) 96.46 ( 82.94 )
Table 14. Outdoor Unit Capacity (JTOR260~300VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (5)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-26FSXNS
JTOR260VAE(U,F,R)BS1 RAS-28FSXNS
JTOR280VAE(U,F,R)BS1 RAS-30FSXNS
JTOR300VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
37.0 86.98 ( 74.79 ) 96.48 ( 82.96 )
37.1 87.01 ( 74.82 ) 96.50 ( 82.97 )
37.2 87.04 ( 74.84 ) 96.52 ( 82.99 )
37.3 87.07 ( 74.87 ) 96.54 ( 83.01 )
37.4 87.10 ( 74.89 ) 96.56 ( 83.03 )
37.5 87.13 ( 74.91 ) 96.58 ( 83.05 )
37.6 87.15 ( 74.94 ) 96.60 ( 83.06 )
37.7 87.18 ( 74.96 ) 96.63 ( 83.08 )
37.8 87.21 ( 74.99 ) 96.65 ( 83.10 )
37.9 87.24 ( 75.01 ) 96.67 ( 83.12 )
38.0 _ _ 87.27 ( 75.04 ) 96.69 ( 83.14 )
38.1 87.30 ( 75.06 ) 96.71 ( 83.16 )
38.2 87.32 ( 75.08 ) 96.73 ( 83.17 )
38.3 87.35 ( 75.11 ) 96.75 ( 83.19 )
38.4 87.38 ( 75.13 ) 96.77 ( 83.21 )
38.5 87.41 ( 75.16 ) 96.79 ( 83.23 )
38.6 87.44 ( 75.18 ) 96.82 ( 83.25 )
38.7 87.47 ( 75.21 ) 96.84 ( 83.26 )
38.8 87.49 ( 75.23 ) 96.86 ( 83.28 )
38.9 87.52 ( 75.26 ) 96.88 ( 83.30 )
39.0 87.55 ( 75.28 ) 96.90 ( 83.32 )
Table 15. Outdoor Unit Capacity (JTOR320~360VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (1)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-32FSXNS
JTOR320VAE(U,F,R)BS1 RAS-34FSXNS
JTOR340VAE(U,F,R)BS1 RAS-36FSXNS
JTOR360VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
16.0 45.00 ( 38.69 ) 50.00 ( 42.99 )
16.1 45.28 ( 38.93 ) 50.31 ( 43.26 )
16.2 45.56 ( 39.18 ) 50.62 ( 43.53 )
16.3 45.84 ( 39.42 ) 50.94 ( 43.80 )
16.4 46.12 ( 39.66 ) 51.25 ( 44.07 )
_
16.5 46.41 ( 39.90 ) 51.56 ( 44.34 )
16.6 46.69 ( 40.14 ) 51.87 ( 44.60 )
16.7 46.97 ( 40.39 ) 52.19 ( 44.87 )
16.8 47.25 ( 40.63 ) 52.50 ( 45.14 )
16.9 47.53 ( 40.87 ) 52.81 ( 45.41 )
_
17.0 47.81 ( 41.11 ) 53.12 ( 45.68 ) 47.50 ( 40.84 ) 53.00 ( 45.57 )
17.1 48.09 ( 41.35 ) 53.44 ( 45.95 ) 47.78 ( 41.08 ) 53.31 ( 45.84 )
17.2 48.37 ( 41.60 ) 53.75 ( 46.22 ) 48.06 ( 41.32 ) 53.62 ( 46.11 )
17.3 48.66 ( 41.84 ) 54.06 ( 46.49 ) 48.34 ( 41.56 ) 53.94 ( 46.38 )
17.4 48.94 ( 42.08 ) 54.37 ( 46.75 ) 48.62 ( 41.80 ) 54.25 ( 46.64 )
17.5 49.22 ( 42.32 ) 54.69 ( 47.02 ) 48.90 ( 42.04 ) 54.56 ( 46.91 )
17.6 49.50 ( 42.56 ) 55.00 ( 47.29 ) 49.18 ( 42.28 ) 54.87 ( 47.18 )
17.7 49.78 ( 42.80 ) 55.31 ( 47.56 ) 49.46 ( 42.52 ) 55.18 ( 47.45 )
17.8 50.06 ( 43.05 ) 55.62 ( 47.83 ) 49.74 ( 42.76 ) 55.49 ( 47.72 )
17.9 50.34 ( 43.29 ) 55.94 ( 48.10 ) 50.01 ( 43.00 ) 55.81 ( 47.98 )
18.0 50.62 ( 43.53 ) 56.25 ( 48.37 ) 50.29 ( 43.25 ) 56.12 ( 48.25 ) 50.00 ( 42.99 ) 56.00 ( 48.15 )
18.1 50.91 ( 43.77 ) 56.56 ( 48.63 ) 50.57 ( 43.49 ) 56.43 ( 48.52 ) 50.28 ( 43.23 ) 56.31 ( 48.42 )
18.2 51.19 ( 44.01 ) 56.87 ( 48.90 ) 50.85 ( 43.73 ) 56.74 ( 48.79 ) 50.56 ( 43.47 ) 56.62 ( 48.69 )
18.3 51.47 ( 44.26 ) 57.19 ( 49.17 ) 51.13 ( 43.97 ) 57.05 ( 49.06 ) 50.83 ( 43.71 ) 56.93 ( 48.95 )
18.4 51.75 ( 44.50 ) 57.50 ( 49.44 ) 51.41 ( 44.21 ) 57.36 ( 49.32 ) 51.11 ( 43.95 ) 57.24 ( 49.22 )
18.5 52.03 ( 44.74 ) 57.81 ( 49.71 ) 51.69 ( 44.45 ) 57.68 ( 49.59 ) 51.39 ( 44.19 ) 57.56 ( 49.49 )
18.6 52.31 ( 44.98 ) 58.12 ( 49.98 ) 51.97 ( 44.69 ) 57.99 ( 49.86 ) 51.67 ( 44.43 ) 57.87 ( 49.76 )
18.7 52.59 ( 45.22 ) 58.44 ( 50.25 ) 52.25 ( 44.93 ) 58.30 ( 50.13 ) 51.94 ( 44.66 ) 58.18 ( 50.02 )
18.8 52.87 ( 45.46 ) 58.75 ( 50.52 ) 52.53 ( 45.17 ) 58.61 ( 50.40 ) 52.22 ( 44.90 ) 58.49 ( 50.29 )
18.9 53.16 ( 45.71 ) 59.06 ( 50.78 ) 52.81 ( 45.41 ) 58.92 ( 50.67 ) 52.50 ( 45.14 ) 58.80 ( 50.56 )
19.0 53.44 ( 45.95 ) 59.37 ( 51.05 ) 53.09 ( 45.65 ) 59.24 ( 50.93 ) 52.78 ( 45.38 ) 59.11 ( 50.83 )
19.1 53.72 ( 46.19 ) 59.69 ( 51.32 ) 53.37 ( 45.89 ) 59.55 ( 51.20 ) 53.06 ( 45.62 ) 59.42 ( 51.09 )
19.2 54.00 ( 46.43 ) 60.00 ( 51.59 ) 53.65 ( 46.13 ) 59.86 ( 51.47 ) 53.33 ( 45.86 ) 59.73 ( 51.36 )
19.3 54.28 ( 46.67 ) 60.31 ( 51.86 ) 53.93 ( 46.37 ) 60.17 ( 51.74 ) 53.61 ( 46.10 ) 60.04 ( 51.63 )
19.4 54.56 ( 46.92 ) 60.62 ( 52.13 ) 54.21 ( 46.61 ) 60.48 ( 52.01 ) 53.89 ( 46.34 ) 60.36 ( 51.90 )
19.5 54.84 ( 47.16 ) 60.94 ( 52.40 ) 54.49 ( 46.85 ) 60.79 ( 52.27 ) 54.17 ( 46.57 ) 60.67 ( 52.16 )
19.6 55.12 ( 47.40 ) 61.25 ( 52.67 ) 54.76 ( 47.09 ) 61.11 ( 52.54 ) 54.44 ( 46.81 ) 60.98 ( 52.43 )
19.7 55.41 ( 47.64 ) 61.56 ( 52.93 ) 55.04 ( 47.33 ) 61.42 ( 52.81 ) 54.72 ( 47.05 ) 61.29 ( 52.70 )
19.8 55.69 ( 47.88 ) 61.87 ( 53.20 ) 55.32 ( 47.57 ) 61.73 ( 53.08 ) 55.00 ( 47.29 ) 61.60 ( 52.97 )
19.9 55.97 ( 48.12 ) 62.19 ( 53.47 ) 55.60 ( 47.81 ) 62.04 ( 53.35 ) 55.28 ( 47.53 ) 61.91 ( 53.23 )
20.0 56.25 ( 48.37 ) 62.50 ( 53.74 ) 55.88 ( 48.05 ) 62.35 ( 53.61 ) 55.56 ( 47.77 ) 62.22 ( 53.50 )
20.1 56.53 ( 48.61 ) 62.81 ( 54.01 ) 56.16 ( 48.29 ) 62.66 ( 53.88 ) 55.83 ( 48.01 ) 62.53 ( 53.77 )
20.2 56.81 ( 48.85 ) 63.12 ( 54.28 ) 56.44 ( 48.53 ) 62.98 ( 54.15 ) 56.11 ( 48.25 ) 62.84 ( 54.04 )
20.3 57.09 ( 49.09 ) 63.44 ( 54.55 ) 56.72 ( 48.77 ) 63.29 ( 54.42 ) 56.39 ( 48.49 ) 63.16 ( 54.30 )
20.4 57.37 ( 49.33 ) 63.75 ( 54.82 ) 57.00 ( 49.01 ) 63.60 ( 54.69 ) 56.67 ( 48.72 ) 63.47 ( 54.57 )
20.5 57.66 ( 49.58 ) 64.06 ( 55.08 ) 57.28 ( 49.25 ) 63.91 ( 54.95 ) 56.94 ( 48.96 ) 63.78 ( 54.84 )
20.6 57.94 ( 49.82 ) 64.37 ( 55.35 ) 57.56 ( 49.49 ) 64.22 ( 55.22 ) 57.22 ( 49.20 ) 64.09 ( 55.11 )
20.7 58.22 ( 50.06 ) 64.69 ( 55.62 ) 57.84 ( 49.73 ) 64.54 ( 55.49 ) 57.50 ( 49.44 ) 64.40 ( 55.37 )
20.8 58.50 ( 50.30 ) 65.00 ( 55.89 ) 58.12 ( 49.97 ) 64.85 ( 55.76 ) 57.78 ( 49.68 ) 64.71 ( 55.64 )
20.9 58.78 ( 50.54 ) 65.31 ( 56.16 ) 58.40 ( 50.21 ) 65.16 ( 56.03 ) 58.06 ( 49.92 ) 65.02 ( 55.91 )
21.0 59.06 ( 50.78 ) 65.63 ( 56.43 ) 58.68 ( 50.45 ) 65.47 ( 56.29 ) 58.33 ( 50.16 ) 65.33 ( 56.18 )
21.1 59.34 ( 51.03 ) 65.94 ( 56.70 ) 58.96 ( 50.69 ) 65.78 ( 56.56 ) 58.61 ( 50.40 ) 65.64 ( 56.44 )
21.2 59.63 ( 51.27 ) 66.25 ( 56.96 ) 59.24 ( 50.93 ) 66.09 ( 56.83 ) 58.89 ( 50.64 ) 65.96 ( 56.71 )
21.3 59.91 ( 51.51 ) 66.56 ( 57.23 ) 59.51 ( 51.17 ) 66.41 ( 57.10 ) 59.17 ( 50.87 ) 66.27 ( 56.98 )
21.4 60.19 ( 51.75 ) 66.88 ( 57.50 ) 59.79 ( 51.41 ) 66.72 ( 57.37 ) 59.44 ( 51.11 ) 66.58 ( 57.25 )
21.5 60.47 ( 51.99 ) 67.19 ( 57.77 ) 60.07 ( 51.65 ) 67.03 ( 57.63 ) 59.72 ( 51.35 ) 66.89 ( 57.51 )
21.6 60.75 ( 52.24 ) 67.50 ( 58.04 ) 60.35 ( 51.89 ) 67.34 ( 57.90 ) 60.00 ( 51.59 ) 67.20 ( 57.78 )
21.7 61.03 ( 52.48 ) 67.81 ( 58.31 ) 60.63 ( 52.13 ) 67.65 ( 58.17 ) 60.28 ( 51.83 ) 67.51 ( 58.05 )
21.8 61.31 ( 52.72 ) 68.13 ( 58.58 ) 60.91 ( 52.37 ) 67.96 ( 58.44 ) 60.56 ( 52.07 ) 67.82 ( 58.32 )
21.9 61.59 ( 52.96 ) 68.44 ( 58.85 ) 61.19 ( 52.61 ) 68.28 ( 58.71 ) 60.83 ( 52.31 ) 68.13 ( 58.58 )
Table 16. Outdoor Unit Capacity (JTOR320~360VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (2)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-32FSXNS
JTOR320VAE(U,F,R)BS1 RAS-34FSXNS
JTOR340VAE(U,F,R)BS1 RAS-36FSXNS
JTOR360VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
22.0 61.88 ( 53.20 ) 68.75 ( 59.11 ) 61.47 ( 52.86 ) 68.59 ( 58.98 ) 61.11 ( 52.55 ) 68.44 ( 58.85 )
22.1 62.16 ( 53.44 ) 69.06 ( 59.38 ) 61.75 ( 53.10 ) 68.90 ( 59.24 ) 61.39 ( 52.78 ) 68.76 ( 59.12 )
22.2 62.44 ( 53.69 ) 69.38 ( 59.65 ) 62.03 ( 53.34 ) 69.21 ( 59.51 ) 61.67 ( 53.02 ) 69.07 ( 59.39 )
22.3 62.72 ( 53.93 ) 69.69 ( 59.92 ) 62.31 ( 53.58 ) 69.52 ( 59.78 ) 61.94 ( 53.26 ) 69.38 ( 59.65 )
22.4 63.00 ( 54.17 ) 70.00 ( 60.19 ) 62.59 ( 53.82 ) 69.84 ( 60.05 ) 62.22 ( 53.50 ) 69.69 ( 59.92 )
22.5 63.28 ( 54.41 ) 70.31 ( 60.46 ) 62.87 ( 54.06 ) 70.15 ( 60.32 ) 62.50 ( 53.74 ) 70.00 ( 60.19 )
22.6 63.56 ( 54.65 ) 70.63 ( 60.73 ) 63.15 ( 54.30 ) 70.46 ( 60.58 ) 62.78 ( 53.98 ) 70.31 ( 60.46 )
22.7 63.84 ( 54.90 ) 70.94 ( 61.00 ) 63.43 ( 54.54 ) 70.77 ( 60.85 ) 63.06 ( 54.22 ) 70.62 ( 60.72 )
22.8 64.13 ( 55.14 ) 71.25 ( 61.26 ) 63.71 ( 54.78 ) 71.08 ( 61.12 ) 63.33 ( 54.46 ) 70.93 ( 60.99 )
22.9 64.41 ( 55.38 ) 71.56 ( 61.53 ) 63.99 ( 55.02 ) 71.39 ( 61.39 ) 63.61 ( 54.70 ) 71.24 ( 61.26 )
23.0 64.69 ( 55.62 ) 71.88 ( 61.80 ) 64.26 ( 55.26 ) 71.71 ( 61.66 ) 63.89 ( 54.93 ) 71.56 ( 61.53 )
23.1 64.97 ( 55.86 ) 72.19 ( 62.07 ) 64.54 ( 55.50 ) 72.02 ( 61.92 ) 64.17 ( 55.17 ) 71.87 ( 61.79 )
23.2 65.25 ( 56.10 ) 72.50 ( 62.34 ) 64.82 ( 55.74 ) 72.33 ( 62.19 ) 64.44 ( 55.41 ) 72.18 ( 62.06 )
23.3 65.53 ( 56.35 ) 72.81 ( 62.61 ) 65.10 ( 55.98 ) 72.64 ( 62.46 ) 64.72 ( 55.65 ) 72.49 ( 62.33 )
23.4 65.81 ( 56.59 ) 73.12 ( 62.88 ) 65.38 ( 56.22 ) 72.95 ( 62.73 ) 65.00 ( 55.89 ) 72.80 ( 62.60 )
23.5 66.09 ( 56.83 ) 73.44 ( 63.14 ) 65.66 ( 56.46 ) 73.26 ( 63.00 ) 65.28 ( 56.13 ) 73.11 ( 62.86 )
23.6 66.37 ( 57.07 ) 73.75 ( 63.41 ) 65.94 ( 56.70 ) 73.58 ( 63.26 ) 65.56 ( 56.37 ) 73.42 ( 63.13 )
23.7 66.66 ( 57.31 ) 74.06 ( 63.68 ) 66.22 ( 56.94 ) 73.89 ( 63.53 ) 65.83 ( 56.61 ) 73.73 ( 63.40 )
23.8 66.94 ( 57.56 ) 74.37 ( 63.95 ) 66.50 ( 57.18 ) 74.20 ( 63.80 ) 66.11 ( 56.85 ) 74.04 ( 63.67 )
23.9 67.22 ( 57.80 ) 74.69 ( 64.22 ) 66.78 ( 57.42 ) 74.51 ( 64.07 ) 66.39 ( 57.08 ) 74.36 ( 63.93 )
24.0 67.50 ( 58.04 ) 75.00 ( 64.49 ) 67.06 ( 57.66 ) 74.82 ( 64.34 ) 66.67 ( 57.32 ) 74.67 ( 64.20 )
24.1 67.78 ( 58.28 ) 75.31 ( 64.76 ) 67.34 ( 57.90 ) 75.14 ( 64.60 ) 66.94 ( 57.56 ) 74.98 ( 64.47 )
24.2 68.06 ( 58.52 ) 75.62 ( 65.03 ) 67.62 ( 58.14 ) 75.45 ( 64.87 ) 67.22 ( 57.80 ) 75.29 ( 64.74 )
24.3 68.34 ( 58.77 ) 75.94 ( 65.29 ) 67.90 ( 58.38 ) 75.76 ( 65.14 ) 67.50 ( 58.04 ) 75.60 ( 65.00 )
24.4 68.62 ( 59.01 ) 76.25 ( 65.56 ) 68.18 ( 58.62 ) 76.07 ( 65.41 ) 67.78 ( 58.28 ) 75.91 ( 65.27 )
24.5 68.91 ( 59.25 ) 76.56 ( 65.83 ) 68.46 ( 58.86 ) 76.38 ( 65.68 ) 68.06 ( 58.52 ) 76.22 ( 65.54 )
24.6 69.19 ( 59.49 ) 76.87 ( 66.10 ) 68.74 ( 59.10 ) 76.69 ( 65.95 ) 68.33 ( 58.76 ) 76.53 ( 65.81 )
24.7 69.47 ( 59.73 ) 77.19 ( 66.37 ) 69.01 ( 59.34 ) 77.01 ( 66.21 ) 68.61 ( 58.99 ) 76.84 ( 66.07 )
24.8 69.75 ( 59.97 ) 77.50 ( 66.64 ) 69.29 ( 59.58 ) 77.32 ( 66.48 ) 68.89 ( 59.23 ) 77.16 ( 66.34 )
24.9 70.03 ( 60.22 ) 77.81 ( 66.91 ) 69.57 ( 59.82 ) 77.63 ( 66.75 ) 69.17 ( 59.47 ) 77.47 ( 66.61 )
25.0 70.31 ( 60.46 ) 78.12 ( 67.18 ) 69.85 ( 60.06 ) 77.94 ( 67.02 ) 69.44 ( 59.71 ) 77.78 ( 66.88 )
25.1 70.59 ( 60.70 ) 78.44 ( 67.44 ) 70.13 ( 60.30 ) 78.25 ( 67.29 ) 69.72 ( 59.95 ) 78.09 ( 67.14 )
25.2 70.87 ( 60.94 ) 78.75 ( 67.71 ) 70.41 ( 60.54 ) 78.56 ( 67.55 ) 70.00 ( 60.19 ) 78.40 ( 67.41 )
25.3 71.16 ( 61.18 ) 79.06 ( 67.98 ) 70.69 ( 60.78 ) 78.88 ( 67.82 ) 70.28 ( 60.43 ) 78.71 ( 67.68 )
25.4 71.44 ( 61.43 ) 79.37 ( 68.25 ) 70.97 ( 61.02 ) 79.19 ( 68.09 ) 70.56 ( 60.67 ) 79.02 ( 67.95 )
25.5 71.72 ( 61.67 ) 79.69 ( 68.52 ) 71.25 ( 61.26 ) 79.50 ( 68.36 ) 70.83 ( 60.91 ) 79.33 ( 68.21 )
25.6 72.00 ( 61.91 ) 80.00 ( 68.79 ) 71.53 ( 61.50 ) 79.81 ( 68.63 ) 71.11 ( 61.14 ) 79.64 ( 68.48 )
25.7 72.28 ( 62.15 ) 80.31 ( 69.06 ) 71.81 ( 61.74 ) 80.12 ( 68.89 ) 71.39 ( 61.38 ) 79.96 ( 68.75 )
25.8 72.56 ( 62.39 ) 80.62 ( 69.33 ) 72.09 ( 61.98 ) 80.44 ( 69.16 ) 71.67 ( 61.62 ) 80.27 ( 69.02 )
25.9 72.84 ( 62.63 ) 80.94 ( 69.59 ) 72.37 ( 62.22 ) 80.75 ( 69.43 ) 71.94 ( 61.86 ) 80.58 ( 69.28 )
26.0 73.12 ( 62.88 ) 81.25 ( 69.86 ) 72.65 ( 62.47 ) 81.06 ( 69.70 ) 72.22 ( 62.10 ) 80.89 ( 69.55 )
26.1 73.41 ( 63.12 ) 81.56 ( 70.13 ) 72.93 ( 62.71 ) 81.37 ( 69.97 ) 72.50 ( 62.34 ) 81.20 ( 69.82 )
26.2 73.69 ( 63.36 ) 81.87 ( 70.40 ) 73.21 ( 62.95 ) 81.68 ( 70.23 ) 72.78 ( 62.58 ) 81.51 ( 70.09 )
26.3 73.97 ( 63.60 ) 82.19 ( 70.67 ) 73.49 ( 63.19 ) 81.99 ( 70.50 ) 73.06 ( 62.82 ) 81.82 ( 70.35 )
26.4 74.25 ( 63.84 ) 82.50 ( 70.94 ) 73.76 ( 63.43 ) 82.31 ( 70.77 ) 73.33 ( 63.06 ) 82.13 ( 70.62 )
26.5 74.53 ( 64.09 ) 82.81 ( 71.21 ) 74.04 ( 63.67 ) 82.62 ( 71.04 ) 73.61 ( 63.29 ) 82.44 ( 70.89 )
26.6 74.81 ( 64.33 ) 83.12 ( 71.47 ) 74.32 ( 63.91 ) 82.93 ( 71.31 ) 73.89 ( 63.53 ) 82.76 ( 71.16 )
26.7 75.09 ( 64.57 ) 83.44 ( 71.74 ) 74.60 ( 64.15 ) 83.24 ( 71.57 ) 74.17 ( 63.77 ) 83.07 ( 71.42 )
26.8 75.37 ( 64.81 ) 83.75 ( 72.01 ) 74.88 ( 64.39 ) 83.55 ( 71.84 ) 74.44 ( 64.01 ) 83.38 ( 71.69 )
26.9 75.66 ( 65.05 ) 84.06 ( 72.28 ) 75.16 ( 64.63 ) 83.86 ( 72.11 ) 74.72 ( 64.25 ) 83.69 ( 71.96 )
27.0 75.94 ( 65.29 ) 84.37 ( 72.55 ) 75.44 ( 64.87 ) 84.18 ( 72.38 ) 75.00 ( 64.49 ) 84.00 ( 72.23 )
27.1 76.22 ( 65.54 ) 84.69 ( 72.82 ) 75.72 ( 65.11 ) 84.49 ( 72.65 ) 75.28 ( 64.73 ) 84.31 ( 72.49 )
27.2 76.50 ( 65.78 ) 85.00 ( 73.09 ) 76.00 ( 65.35 ) 84.80 ( 72.91 ) 75.56 ( 64.97 ) 84.62 ( 72.76 )
27.3 76.78 ( 66.02 ) 85.31 ( 73.36 ) 76.28 ( 65.59 ) 85.11 ( 73.18 ) 75.83 ( 65.20 ) 84.93 ( 73.03 )
27.4 77.06 ( 66.26 ) 85.62 ( 73.62 ) 76.56 ( 65.83 ) 85.42 ( 73.45 ) 76.11 ( 65.44 ) 85.24 ( 73.30 )
27.5 77.34 ( 66.50 ) 85.94 ( 73.89 ) 76.84 ( 66.07 ) 85.74 ( 73.72 ) 76.39 ( 65.68 ) 85.56 ( 73.56 )
27.6 77.62 ( 66.75 ) 86.25 ( 74.16 ) 77.12 ( 66.31 ) 86.05 ( 73.99 ) 76.67 ( 65.92 ) 85.87 ( 73.83 )
27.7 77.91 ( 66.99 ) 86.56 ( 74.43 ) 77.40 ( 66.55 ) 86.36 ( 74.26 ) 76.94 ( 66.16 ) 86.18 ( 74.10 )
27.8 78.19 ( 67.23 ) 86.88 ( 74.70 ) 77.68 ( 66.79 ) 86.67 ( 74.52 ) 77.22 ( 66.40 ) 86.49 ( 74.37 )
27.9 78.47 ( 67.47 ) 87.19 ( 74.97 ) 77.96 ( 67.03 ) 86.98 ( 74.79 ) 77.50 ( 66.64 ) 86.80 ( 74.63 )
Table 17. Outdoor Unit Capacity (JTOR320~360VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (3)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-32FSXNS
JTOR320VAE(U,F,R)BS1 RAS-34FSXNS
JTOR340VAE(U,F,R)BS1 RAS-36FSXNS
JTOR360VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
28.0 78.75 ( 67.71 ) 87.50 ( 75.24 ) 78.24 ( 67.27 ) 87.29 ( 75.06 ) 77.78 ( 66.88 ) 87.11 ( 74.90 )
28.1 79.03 ( 67.95 ) 87.81 ( 75.51 ) 78.51 ( 67.51 ) 87.61 ( 75.33 ) 78.06 ( 67.12 ) 87.42 ( 75.17 )
28.2 79.31 ( 68.20 ) 88.13 ( 75.77 ) 78.79 ( 67.75 ) 87.92 ( 75.60 ) 78.33 ( 67.35 ) 87.73 ( 75.44 )
28.3 79.59 ( 68.44 ) 88.44 ( 76.04 ) 79.07 ( 67.99 ) 88.23 ( 75.86 ) 78.61 ( 67.59 ) 88.04 ( 75.70 )
28.4 79.88 ( 68.68 ) 88.75 ( 76.31 ) 79.35 ( 68.23 ) 88.54 ( 76.13 ) 78.89 ( 67.83 ) 88.36 ( 75.97 )
28.5 80.16 ( 68.92 ) 89.06 ( 76.58 ) 79.63 ( 68.47 ) 88.85 ( 76.40 ) 79.17 ( 68.07 ) 88.67 ( 76.24 )
28.6 80.44 ( 69.16 ) 89.38 ( 76.85 ) 79.91 ( 68.71 ) 89.16 ( 76.67 ) 79.44 ( 68.31 ) 88.98 ( 76.51 )
28.7 80.72 ( 69.41 ) 89.69 ( 77.12 ) 80.19 ( 68.95 ) 89.48 ( 76.94 ) 79.72 ( 68.55 ) 89.29 ( 76.77 )
28.8 81.00 ( 69.65 ) 90.00 ( 77.39 ) 80.47 ( 69.19 ) 89.79 ( 77.20 ) 80.00 ( 68.79 ) 89.60 ( 77.04 )
28.9 81.28 ( 69.89 ) 90.31 ( 77.65 ) 80.75 ( 69.43 ) 90.10 ( 77.47 ) 80.28 ( 69.03 ) 89.91 ( 77.31 )
29.0 81.56 ( 70.13 ) 90.63 ( 77.92 ) 81.03 ( 69.67 ) 90.41 ( 77.74 ) 80.56 ( 69.27 ) 90.22 ( 77.58 )
29.1 81.84 ( 70.37 ) 90.94 ( 78.19 ) 81.31 ( 69.91 ) 90.72 ( 78.01 ) 80.83 ( 69.50 ) 90.53 ( 77.84 )
29.2 82.13 ( 70.61 ) 91.25 ( 78.46 ) 81.59 ( 70.15 ) 91.04 ( 78.28 ) 81.11 ( 69.74 ) 90.84 ( 78.11 )
29.3 82.41 ( 70.86 ) 91.56 ( 78.73 ) 81.87 ( 70.39 ) 91.35 ( 78.54 ) 81.39 ( 69.98 ) 91.16 ( 78.38 )
29.4 82.69 ( 71.10 ) 91.88 ( 79.00 ) 82.15 ( 70.63 ) 91.66 ( 78.81 ) 81.67 ( 70.22 ) 91.47 ( 78.65 )
29.5 82.97 ( 71.34 ) 92.19 ( 79.27 ) 82.43 ( 70.87 ) 91.97 ( 79.08 ) 81.94 ( 70.46 ) 91.78 ( 78.91 )
29.6 83.25 ( 71.58 ) 92.50 ( 79.54 ) 82.71 ( 71.11 ) 92.28 ( 79.35 ) 82.22 ( 70.70 ) 92.09 ( 79.18 )
29.7 83.53 ( 71.82 ) 92.81 ( 79.80 ) 82.99 ( 71.35 ) 92.59 ( 79.62 ) 82.50 ( 70.94 ) 92.40 ( 79.45 )
29.8 83.81 ( 72.07 ) 93.13 ( 80.07 ) 83.26 ( 71.59 ) 92.91 ( 79.88 ) 82.78 ( 71.18 ) 92.71 ( 79.72 )
29.9 84.09 ( 72.31 ) 93.44 ( 80.34 ) 83.54 ( 71.84 ) 93.22 ( 80.15 ) 83.06 ( 71.41 ) 93.02 ( 79.98 )
30.0 84.38 ( 72.55 ) 93.75 ( 80.61 ) 83.82 ( 72.08 ) 93.53 ( 80.42 ) 83.33 ( 71.65 ) 93.33 ( 80.25 )
30.1 84.66 ( 72.79 ) 94.06 ( 80.88 ) 84.10 ( 72.32 ) 93.84 ( 80.69 ) 83.61 ( 71.89 ) 93.64 ( 80.52 )
30.2 84.94 ( 73.03 ) 94.38 ( 81.15 ) 84.38 ( 72.56 ) 94.15 ( 80.96 ) 83.89 ( 72.13 ) 93.96 ( 80.79 )
30.3 85.22 ( 73.27 ) 94.69 ( 81.42 ) 84.66 ( 72.80 ) 94.46 ( 81.23 ) 84.17 ( 72.37 ) 94.27 ( 81.05 )
30.4 85.50 ( 73.52 ) 95.00 ( 81.69 ) 84.94 ( 73.04 ) 94.78 ( 81.49 ) 84.44 ( 72.61 ) 94.58 ( 81.32 )
30.5 85.78 ( 73.76 ) 95.31 ( 81.95 ) 85.22 ( 73.28 ) 95.09 ( 81.76 ) 84.72 ( 72.85 ) 94.89 ( 81.59 )
30.6 86.06 ( 74.00 ) 95.63 ( 82.22 ) 85.50 ( 73.52 ) 95.40 ( 82.03 ) 85.00 ( 73.09 ) 95.20 ( 81.86 )
30.7 86.34 ( 74.24 ) 95.94 ( 82.49 ) 85.78 ( 73.76 ) 95.71 ( 82.30 ) 85.28 ( 73.33 ) 95.51 ( 82.12 )
30.8 86.63 ( 74.48 ) 96.25 ( 82.76 ) 86.06 ( 74.00 ) 96.02 ( 82.57 ) 85.56 ( 73.56 ) 95.82 ( 82.39 )
30.9 86.91 ( 74.73 ) 96.56 ( 83.03 ) 86.34 ( 74.24 ) 96.34 ( 82.83 ) 85.83 ( 73.80 ) 96.13 ( 82.66 )
31.0 87.19 ( 74.97 ) 96.88 ( 83.30 ) 86.62 ( 74.48 ) 96.65 ( 83.10 ) 86.11 ( 74.04 ) 96.44 ( 82.93 )
31.1 87.47 ( 75.21 ) 97.19 ( 83.57 ) 86.90 ( 74.72 ) 96.96 ( 83.37 ) 86.39 ( 74.28 ) 96.76 ( 83.19 )
31.2 87.75 ( 75.45 ) 97.50 ( 83.83 ) 87.18 ( 74.96 ) 97.27 ( 83.64 ) 86.67 ( 74.52 ) 97.07 ( 83.46 )
31.3 88.03 ( 75.69 ) 97.81 ( 84.10 ) 87.46 ( 75.20 ) 97.58 ( 83.91 ) 86.94 ( 74.76 ) 97.38 ( 83.73 )
31.4 88.31 ( 75.94 ) 98.13 ( 84.37 ) 87.74 ( 75.44 ) 97.89 ( 84.17 ) 87.22 ( 75.00 ) 97.69 ( 84.00 )
31.5 88.59 ( 76.18 ) 98.44 ( 84.64 ) 88.01 ( 75.68 ) 98.21 ( 84.44 ) 87.50 ( 75.24 ) 98.00 ( 84.26 )
31.6 88.88 ( 76.42 ) 98.75 ( 84.91 ) 88.29 ( 75.92 ) 98.52 ( 84.71 ) 87.78 ( 75.48 ) 98.31 ( 84.53 )
31.7 89.16 ( 76.66 ) 99.06 ( 85.18 ) 88.57 ( 76.16 ) 98.83 ( 84.98 ) 88.06 ( 75.71 ) 98.62 ( 84.80 )
31.8 89.44 ( 76.90 ) 99.38 ( 85.45 ) 88.85 ( 76.40 ) 99.14 ( 85.25 ) 88.33 ( 75.95 ) 98.93 ( 85.07 )
31.9 89.72 ( 77.14 ) 99.69 ( 85.72 ) 89.13 ( 76.64 ) 99.45 ( 85.51 ) 88.61 ( 76.19 ) 99.24 ( 85.33 )
32.0 90.00 ( 77.39 ) 100.00 ( 85.98 ) 89.41 ( 76.88 ) 99.76 ( 85.78 ) 88.89 ( 76.43 ) 99.56 ( 85.60 )
32.1 90.03 ( 77.41 ) 100.02 ( 86.00 ) 89.69 ( 77.12 ) 100.08 ( 86.05 ) 89.17 ( 76.67 ) 99.87 ( 85.87 )
32.2 90.06 ( 77.43 ) 100.04 ( 86.02 ) 89.97 ( 77.36 ) 100.39 ( 86.32 ) 89.44 ( 76.91 ) 100.18 ( 86.14 )
32.3 90.08 ( 77.46 ) 100.06 ( 86.04 ) 90.25 ( 77.60 ) 100.70 ( 86.59 ) 89.72 ( 77.15 ) 100.49 ( 86.40 )
32.4 90.11 ( 77.48 ) 100.08 ( 86.06 ) 90.53 ( 77.84 ) 101.01 ( 86.85 ) 90.00 ( 77.39 ) 100.80 ( 86.67 )
32.5 90.14 ( 77.51 ) 100.10 ( 86.07 ) 90.81 ( 78.08 ) 101.32 ( 87.12 ) 90.28 ( 77.62 ) 101.11 ( 86.94 )
32.6 90.17 ( 77.53 ) 100.13 ( 86.09 ) 91.09 ( 78.32 ) 101.64 ( 87.39 ) 90.56 ( 77.86 ) 101.42 ( 87.21 )
32.7 90.20 ( 77.56 ) 100.15 ( 86.11 ) 91.37 ( 78.56 ) 101.95 ( 87.66 ) 90.83 ( 78.10 ) 101.73 ( 87.47 )
32.8 90.23 ( 77.58 ) 100.17 ( 86.13 ) 91.65 ( 78.80 ) 102.26 ( 87.93 ) 91.11 ( 78.34 ) 102.04 ( 87.74 )
32.9 90.25 ( 77.60 ) 100.19 ( 86.15 ) 91.93 ( 79.04 ) 102.57 ( 88.19 ) 91.39 ( 78.58 ) 102.36 ( 88.01 )
33.0 90.28 ( 77.63 ) 100.21 ( 86.16 ) 92.21 ( 79.28 ) 102.88 ( 88.46 ) 91.67 ( 78.82 ) 102.67 ( 88.28 )
33.1 90.31 ( 77.65 ) 100.23 ( 86.18 ) 92.49 ( 79.52 ) 103.19 ( 88.73 ) 91.94 ( 79.06 ) 102.98 ( 88.54 )
33.2 90.34 ( 77.68 ) 100.25 ( 86.20 ) 92.76 ( 79.76 ) 103.51 ( 89.00 ) 92.22 ( 79.30 ) 103.29 ( 88.81 )
33.3 90.37 ( 77.70 ) 100.27 ( 86.22 ) 93.04 ( 80.00 ) 103.82 ( 89.27 ) 92.50 ( 79.54 ) 103.60 ( 89.08 )
33.4 90.39 ( 77.72 ) 100.29 ( 86.24 ) 93.32 ( 80.24 ) 104.13 ( 89.54 ) 92.78 ( 79.77 ) 103.91 ( 89.35 )
33.5 90.42 ( 77.75 ) 100.31 ( 86.25 ) 93.60 ( 80.48 ) 104.44 ( 89.80 ) 93.06 ( 80.01 ) 104.22 ( 89.61 )
33.6 90.45 ( 77.77 ) 100.33 ( 86.27 ) 93.88 ( 80.72 ) 104.75 ( 90.07 ) 93.33 ( 80.25 ) 104.53 ( 89.88 )
33.7 90.48 ( 77.80 ) 100.35 ( 86.29 ) 94.16 ( 80.96 ) 105.06 ( 90.34 ) 93.61 ( 80.49 ) 104.84 ( 90.15 )
33.8 90.51 ( 77.82 ) 100.38 ( 86.31 ) 94.44 ( 81.20 ) 105.38 ( 90.61 ) 93.89 ( 80.73 ) 105.16 ( 90.42 )
33.9 90.53 ( 77.85 ) 100.40 ( 86.32 ) 94.72 ( 81.45 ) 105.69 ( 90.88 ) 94.17 ( 80.97 ) 105.47 ( 90.69 )
Table 18. Outdoor Unit Capacity (JTOR320~360VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (4)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-32FSXNS
JTOR320VAE(U,F,R)BS1 RAS-34FSXNS
JTOR340VAE(U,F,R)BS1 RAS-36FSXNS
JTOR360VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
34.0 90.56 ( 77.87 ) 100.42 ( 86.34 ) 95.00 ( 81.69 ) 106.00 ( 91.14 ) 94.44 ( 81.21 ) 105.78 ( 90.95 )
34.1 90.59 ( 77.89 ) 100.44 ( 86.36 ) 95.28 ( 81.93 ) 106.31 ( 91.41 ) 94.72 ( 81.45 ) 106.09 ( 91.22 )
34.2 90.62 ( 77.92 ) 100.46 ( 86.38 ) 95.56 ( 82.17 ) 106.62 ( 91.68 ) 95.00 ( 81.69 ) 106.40 ( 91.49 )
34.3 90.65 ( 77.94 ) 100.48 ( 86.40 ) 95.84 ( 82.41 ) 106.94 ( 91.95 ) 95.28 ( 81.92 ) 106.71 ( 91.76 )
34.4 90.68 ( 77.97 ) 100.50 ( 86.41 ) 96.12 ( 82.65 ) 107.25 ( 92.22 ) 95.56 ( 82.16 ) 107.02 ( 92.02 )
34.5 90.70 ( 77.99 ) 100.52 ( 86.43 ) 96.40 ( 82.89 ) 107.56 ( 92.48 ) 95.83 ( 82.40 ) 107.33 ( 92.29 )
34.6 90.73 ( 78.01 ) 100.54 ( 86.45 ) 96.68 ( 83.13 ) 107.87 ( 92.75 ) 96.11 ( 82.64 ) 107.64 ( 92.56 )
34.7 90.76 ( 78.04 ) 100.56 ( 86.47 ) 96.96 ( 83.37 ) 108.18 ( 93.02 ) 96.39 ( 82.88 ) 107.96 ( 92.83 )
34.8 90.79 ( 78.06 ) 100.58 ( 86.49 ) 97.24 ( 83.61 ) 108.49 ( 93.29 ) 96.67 ( 83.12 ) 108.27 ( 93.09 )
34.9 90.82 ( 78.09 ) 100.60 ( 86.50 ) 97.51 ( 83.85 ) 108.81 ( 93.56 ) 96.94 ( 83.36 ) 108.58 ( 93.36 )
35.0 90.84 ( 78.11 ) 100.63 ( 86.52 ) 97.79 ( 84.09 ) 109.12 ( 93.82 ) 97.22 ( 83.60 ) 108.89 ( 93.63 )
35.1 90.87 ( 78.14 ) 100.65 ( 86.54 ) 97.87 ( 84.16 ) 109.19 ( 93.89 ) 97.50 ( 83.83 ) 109.20 ( 93.90 )
35.2 90.90 ( 78.16 ) 100.67 ( 86.56 ) 97.91 ( 84.18 ) 109.20 ( 93.90 ) 97.78 ( 84.07 ) 109.51 ( 94.16 )
35.3 90.93 ( 78.18 ) 100.69 ( 86.58 ) 97.94 ( 84.21 ) 109.21 ( 93.91 ) 98.06 ( 84.31 ) 109.82 ( 94.43 )
35.4 90.96 ( 78.21 ) 100.71 ( 86.59 ) 97.97 ( 84.24 ) 109.22 ( 93.92 ) 98.33 ( 84.55 ) 110.13 ( 94.70 )
35.5 90.98 ( 78.23 ) 100.73 ( 86.61 ) 98.00 ( 84.26 ) 109.24 ( 93.93 ) 98.61 ( 84.79 ) 110.44 ( 94.97 )
35.6 91.01 ( 78.26 ) 100.75 ( 86.63 ) 98.03 ( 84.29 ) 109.25 ( 93.94 ) 98.89 ( 85.03 ) 110.76 ( 95.23 )
35.7 91.04 ( 78.28 ) 100.77 ( 86.65 ) 98.06 ( 84.32 ) 109.26 ( 93.95 ) 99.17 ( 85.27 ) 111.07 ( 95.50 )
35.8 91.07 ( 78.31 ) 100.79 ( 86.67 ) 98.09 ( 84.34 ) 109.27 ( 93.96 ) 99.44 ( 85.51 ) 111.38 ( 95.77 )
35.9 91.10 ( 78.33 ) 100.81 ( 86.68 ) 98.12 ( 84.37 ) 109.28 ( 93.97 ) 99.72 ( 85.75 ) 111.69 ( 96.04 )
36.0 91.13 ( 78.35 ) 100.83 ( 86.70 ) 98.15 ( 84.40 ) 109.29 ( 93.98 ) 100.00 ( 85.98 ) 112.00 ( 96.30 )
36.1 91.15 ( 78.38 ) 100.85 ( 86.72 ) 98.19 ( 84.42 ) 109.30 ( 93.99 ) 100.28 ( 86.22 ) 112.31 ( 96.57 )
36.2 91.18 ( 78.40 ) 100.88 ( 86.74 ) 98.22 ( 84.45 ) 109.32 ( 94.00 ) 100.56 ( 86.46 ) 112.62 ( 96.84 )
36.3 91.21 ( 78.43 ) 100.90 ( 86.75 ) 98.25 ( 84.48 ) 109.33 ( 94.00 ) 100.83 ( 86.70 ) 112.93 ( 97.11 )
36.4 91.24 ( 78.45 ) 100.92 ( 86.77 ) 98.28 ( 84.50 ) 109.34 ( 94.01 ) 101.11 ( 86.94 ) 113.24 ( 97.37 )
36.5 91.27 ( 78.47 ) 100.94 ( 86.79 ) 98.31 ( 84.53 ) 109.35 ( 94.02 ) 101.39 ( 87.18 ) 113.56 ( 97.64 )
36.6 91.29 ( 78.50 ) 100.96 ( 86.81 ) 98.34 ( 84.56 ) 109.36 ( 94.03 ) 101.67 ( 87.42 ) 113.87 ( 97.91 )
36.7 91.32 ( 78.52 ) 100.98 ( 86.83 ) 98.37 ( 84.58 ) 109.37 ( 94.04 ) 101.94 ( 87.66 ) 114.18 ( 98.18 )
36.8 91.35 ( 78.55 ) 101.00 ( 86.84 ) 98.40 ( 84.61 ) 109.39 ( 94.05 ) 102.22 ( 87.90 ) 114.49 ( 98.44 )
36.9 91.38 ( 78.57 ) 101.02 ( 86.86 ) 98.43 ( 84.64 ) 109.40 ( 94.06 ) 102.50 ( 88.13 ) 114.80 ( 98.71 )
37.0 91.41 ( 78.60 ) 101.04 ( 86.88 ) 98.46 ( 84.66 ) 109.41 ( 94.07 ) 102.78 ( 88.37 ) 115.11 ( 98.98 )
37.1 91.43 ( 78.62 ) 101.06 ( 86.90 ) 98.50 ( 84.69 ) 109.42 ( 94.08 ) 103.01 ( 88.57 ) 115.36 ( 99.19 )
37.2 91.46 ( 78.64 ) 101.08 ( 86.92 ) 98.53 ( 84.72 ) 109.43 ( 94.09 ) 103.04 ( 88.60 ) 115.37 ( 99.20 )
37.3 91.49 ( 78.67 ) 101.10 ( 86.93 ) 98.56 ( 84.74 ) 109.44 ( 94.10 ) 103.07 ( 88.62 ) 115.39 ( 99.21 )
37.4 91.52 ( 78.69 ) 101.13 ( 86.95 ) 98.59 ( 84.77 ) 109.45 ( 94.11 ) 103.10 ( 88.65 ) 115.40 ( 99.22 )
37.5 91.55 ( 78.72 ) 101.15 ( 86.97 ) 98.62 ( 84.80 ) 109.47 ( 94.12 ) 103.13 ( 88.68 ) 115.41 ( 99.23 )
37.6 91.58 ( 78.74 ) 101.17 ( 86.99 ) 98.65 ( 84.82 ) 109.48 ( 94.13 ) 103.16 ( 88.70 ) 115.42 ( 99.24 )
37.7 91.60 ( 78.76 ) 101.19 ( 87.01 ) 98.68 ( 84.85 ) 109.49 ( 94.14 ) 103.19 ( 88.73 ) 115.43 ( 99.25 )
37.8 91.63 ( 78.79 ) 101.21 ( 87.02 ) 98.71 ( 84.88 ) 109.50 ( 94.15 ) 103.22 ( 88.76 ) 115.44 ( 99.26 )
37.9 91.66 ( 78.81 ) 101.23 ( 87.04 ) 98.74 ( 84.90 ) 109.51 ( 94.16 ) 103.25 ( 88.78 ) 115.45 ( 99.27 )
38.0 91.69 ( 78.84 ) 101.25 ( 87.06 ) 98.78 ( 84.93 ) 109.52 ( 94.17 ) 103.28 ( 88.81 ) 115.47 ( 99.28 )
38.1 91.72 ( 78.86 ) 101.27 ( 87.08 ) 98.81 ( 84.96 ) 109.54 ( 94.18 ) 103.31 ( 88.83 ) 115.48 ( 99.29 )
38.2 91.74 ( 78.89 ) 101.29 ( 87.10 ) 98.84 ( 84.98 ) 109.55 ( 94.19 ) 103.35 ( 88.86 ) 115.49 ( 99.30 )
38.3 91.77 ( 78.91 ) 101.31 ( 87.11 ) 98.87 ( 85.01 ) 109.56 ( 94.20 ) 103.38 ( 88.89 ) 115.50 ( 99.31 )
38.4 91.80 ( 78.93 ) 101.33 ( 87.13 ) 98.90 ( 85.04 ) 109.57 ( 94.21 ) 103.41 ( 88.91 ) 115.51 ( 99.32 )
38.5 91.83 ( 78.96 ) 101.35 ( 87.15 ) 98.93 ( 85.06 ) 109.58 ( 94.22 ) 103.44 ( 88.94 ) 115.52 ( 99.33 )
38.6 91.86 ( 78.98 ) 101.38 ( 87.17 ) 98.96 ( 85.09 ) 109.59 ( 94.23 ) 103.47 ( 88.97 ) 115.54 ( 99.34 )
38.7 91.88 ( 79.01 ) 101.40 ( 87.18 ) 98.99 ( 85.12 ) 109.60 ( 94.24 ) 103.50 ( 88.99 ) 115.55 ( 99.35 )
38.8 91.91 ( 79.03 ) 101.42 ( 87.20 ) 99.02 ( 85.14 ) 109.62 ( 94.25 ) 103.53 ( 89.02 ) 115.56 ( 99.36 )
38.9 91.94 ( 79.05 ) 101.44 ( 87.22 ) 99.05 ( 85.17 ) 109.63 ( 94.26 ) 103.56 ( 89.05 ) 115.57 ( 99.37 )
39.0 91.97 ( 79.08 ) 101.46 ( 87.24 ) 99.09 ( 85.20 ) 109.64 ( 94.27 ) 103.59 ( 89.07 ) 115.58 ( 99.38 )
39.1 92.00 ( 79.10 ) 101.48 ( 87.26 ) 99.12 ( 85.22 ) 109.65 ( 94.28 ) 103.62 ( 89.10 ) 115.59 ( 99.39 )
39.2 92.03 ( 79.13 ) 101.50 ( 87.27 ) 99.15 ( 85.25 ) 109.66 ( 94.29 ) 103.65 ( 89.13 ) 115.60 ( 99.40 )
39.3 92.05 ( 79.15 ) 101.52 ( 87.29 ) 99.18 ( 85.28 ) 109.67 ( 94.30 ) 103.69 ( 89.15 ) 115.62 ( 99.41 )
39.4 92.08 ( 79.18 ) 101.54 ( 87.31 ) 99.21 ( 85.31 ) 109.69 ( 94.31 ) 103.72 ( 89.18 ) 115.63 ( 99.42 )
39.5 92.11 ( 79.20 ) 101.56 ( 87.33 ) 99.24 ( 85.33 ) 109.70 ( 94.32 ) 103.75 ( 89.21 ) 115.64 ( 99.43 )
39.6 92.14 ( 79.22 ) 101.58 ( 87.35 ) 99.27 ( 85.36 ) 109.71 ( 94.33 ) 103.78 ( 89.23 ) 115.65 ( 99.44 )
39.7 92.17 ( 79.25 ) 101.60 ( 87.36 ) 99.30 ( 85.39 ) 109.72 ( 94.34 ) 103.81 ( 89.26 ) 115.66 ( 99.45 )
39.8 92.19 ( 79.27 ) 101.63 ( 87.38 ) 99.33 ( 85.41 ) 109.73 ( 94.35 ) 103.84 ( 89.29 ) 115.67 ( 99.46 )
39.9 92.22 ( 79.30 ) 101.65 ( 87.40 ) 99.37 ( 85.44 ) 109.74 ( 94.36 ) 103.87 ( 89.31 ) 115.68 ( 99.47 )
Table 19. Outdoor Unit Capacity (JTOR320~360VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (5)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-32FSXNS
JTOR320VAE(U,F,R)BS1 RAS-34FSXNS
JTOR340VAE(U,F,R)BS1 RAS-36FSXNS
JTOR360VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
40.0 92.25 ( 79.32 ) 101.67 ( 87.42 ) 99.40 ( 85.47 ) 109.76 ( 94.37 ) 103.90 ( 89.34 ) 115.70 ( 99.48 )
40.1 92.28 ( 79.34 ) 101.69 ( 87.44 ) 99.43 ( 85.49 ) 109.77 ( 94.38 ) 103.93 ( 89.37 ) 115.71 ( 99.49 )
40.2 92.31 ( 79.37 ) 101.71 ( 87.45 ) 99.46 ( 85.52 ) 109.78 ( 94.39 ) 103.96 ( 89.39 ) 115.72 ( 99.50 )
40.3 92.33 ( 79.39 ) 101.73 ( 87.47 ) 99.49 ( 85.55 ) 109.79 ( 94.40 ) 103.99 ( 89.42 ) 115.73 ( 99.51 )
40.4 92.36 ( 79.42 ) 101.75 ( 87.49 ) 99.52 ( 85.57 ) 109.80 ( 94.41 ) 104.02 ( 89.45 ) 115.74 ( 99.52 )
40.5 92.39 ( 79.44 ) 101.77 ( 87.51 ) 99.55 ( 85.60 ) 109.81 ( 94.42 ) 104.06 ( 89.47 ) 115.75 ( 99.53 )
40.6 92.42 ( 79.47 ) 101.79 ( 87.53 ) 99.58 ( 85.63 ) 109.82 ( 94.43 ) 104.09 ( 89.50 ) 115.77 ( 99.54 )
40.7 92.45 ( 79.49 ) 101.81 ( 87.54 ) 99.61 ( 85.65 ) 109.84 ( 94.44 ) 104.12 ( 89.52 ) 115.78 ( 99.55 )
40.8 92.48 ( 79.51 ) 101.83 ( 87.56 ) 99.64 ( 85.68 ) 109.85 ( 94.45 ) 104.15 ( 89.55 ) 115.79 ( 99.56 )
40.9 92.50 ( 79.54 ) 101.85 ( 87.58 ) 99.68 ( 85.71 ) 109.86 ( 94.46 ) 104.18 ( 89.58 ) 115.80 ( 99.57 )
41.0 92.53 ( 79.56 ) 101.88 ( 87.60 ) 99.71 ( 85.73 ) 109.87 ( 94.47 ) 104.21 ( 89.60 ) 115.81 ( 99.58 )
41.1 92.56 ( 79.59 ) 101.90 ( 87.61 ) 99.74 ( 85.76 ) 109.88 ( 94.48 ) 104.24 ( 89.63 ) 115.82 ( 99.59 )
41.2 92.59 ( 79.61 ) 101.92 ( 87.63 ) 99.77 ( 85.79 ) 109.89 ( 94.49 ) 104.27 ( 89.66 ) 115.83 ( 99.60 )
41.3 92.62 ( 79.64 ) 101.94 ( 87.65 ) 99.80 ( 85.81 ) 109.91 ( 94.50 ) 104.30 ( 89.68 ) 115.85 ( 99.61 )
41.4 92.64 ( 79.66 ) 101.96 ( 87.67 ) 99.83 ( 85.84 ) 109.92 ( 94.51 ) 104.33 ( 89.71 ) 115.86 ( 99.62 )
41.5 92.67 ( 79.68 ) 101.98 ( 87.69 ) 99.86 ( 85.87 ) 109.93 ( 94.52 ) 104.36 ( 89.74 ) 115.87 ( 99.63 )
41.6 92.70 ( 79.71 ) 102.00 ( 87.70 ) 99.89 ( 85.89 ) 109.94 ( 94.53 ) 104.40 ( 89.76 ) 115.88 ( 99.64 )
41.7 99.92 ( 85.92 ) 109.95 ( 94.54 ) 104.43 ( 89.79 ) 115.89 ( 99.65 )
41.8 99.95 ( 85.95 ) 109.96 ( 94.55 ) 104.46 ( 89.82 ) 115.90 ( 99.66 )
41.9 99.99 ( 85.97 ) 109.97 ( 94.56 ) 104.49 ( 89.84 ) 115.92 ( 99.67 )
42.0 100.02 ( 86.00 ) 109.99 ( 94.57 ) 104.52 ( 89.87 ) 115.93 ( 99.68 )
42.1 100.05 ( 86.03 ) 110.00 ( 94.58 ) 104.55 ( 89.90 ) 115.94 ( 99.69 )
42.2 100.08 ( 86.05 ) 110.01 ( 94.59 ) 104.58 ( 89.92 ) 115.95 ( 99.70 )
42.3 100.11 ( 86.08 ) 110.02 ( 94.60 ) 104.61 ( 89.95 ) 115.96 ( 99.71 )
42.4 100.14 ( 86.11 ) 110.03 ( 94.61 ) 104.64 ( 89.98 ) 115.97 ( 99.72 )
42.5 100.17 ( 86.13 ) 110.04 ( 94.62 ) 104.67 ( 90.00 ) 115.98 ( 99.73 )
42.6 100.20 ( 86.16 ) 110.06 ( 94.63 ) 104.70 ( 90.03 ) 116.00 ( 99.74 )
42.7 100.23 ( 86.19 ) 110.07 ( 94.64 ) 104.73 ( 90.06 ) 116.01 ( 99.75 )
42.8 100.27 ( 86.21 ) 110.08 ( 94.65 ) 104.77 ( 90.08 ) 116.02 ( 99.76 )
42.9 100.30 ( 86.24 ) 110.09 ( 94.66 ) 104.80 ( 90.11 ) 116.03 ( 99.77 )
43.0 100.33 ( 86.27 ) 110.10 ( 94.67 ) 104.83 ( 90.14 ) 116.04 ( 99.78 )
43.1 100.36 ( 86.29 ) 110.11 ( 94.68 ) 104.86 ( 90.16 ) 116.05 ( 99.79 )
43.2 100.39 ( 86.32 ) 110.12 ( 94.69 ) 104.89 ( 90.19 ) 116.07 ( 99.80 )
43.3 100.42 ( 86.35 ) 110.14 ( 94.70 ) 104.92 ( 90.21 ) 116.08 ( 99.81 )
43.4 100.45 ( 86.37 ) 110.15 ( 94.71 ) 104.95 ( 90.24 ) 116.09 ( 99.82 )
43.5 100.48 ( 86.40 ) 110.16 ( 94.72 ) 104.98 ( 90.27 ) 116.10 ( 99.83 )
43.6 100.51 ( 86.43 ) 110.17 ( 94.73 ) 105.01 ( 90.29 ) 116.11 ( 99.84 )
43.7 100.54 ( 86.45 ) 110.18 ( 94.74 ) 105.04 ( 90.32 ) 116.12 ( 99.85 )
43.8 _ 100.58 ( 86.48 ) 110.19 ( 94.75 ) 105.07 ( 90.35 ) 116.13 ( 99.86 )
43.9 100.61 ( 86.51 ) 110.21 ( 94.76 ) 105.10 ( 90.37 ) 116.15 ( 99.87 )
44.0 100.64 ( 86.53 ) 110.22 ( 94.77 ) 105.14 ( 90.40 ) 116.16 ( 99.88 )
44.1 100.67 ( 86.56 ) 110.23 ( 94.78 ) 105.17 ( 90.43 ) 116.17 ( 99.89 )
44.2 100.70 ( 86.59 ) 110.24 ( 94.79 ) 105.20 ( 90.45 ) 116.18 ( 99.90 )
44.3 105.23 ( 90.48 ) 116.19 ( 99.91 )
44.4 105.26 ( 90.51 ) 116.20 ( 99.92 )
44.5 105.29 ( 90.53 ) 116.21 ( 99.93 )
44.6 105.32 ( 90.56 ) 116.23 ( 99.94 )
44.7 105.35 ( 90.59 ) 116.24 ( 99.95 )
44.8 105.38 ( 90.61 ) 116.25 ( 99.96 )
44.9 105.41 ( 90.64 ) 116.26 ( 99.97 )
45.0 105.44 ( 90.67 ) 116.27 ( 99.98 )
45.1 _ 105.48 ( 90.69 ) 116.28 ( 99.99 )
45.2 105.51 ( 90.72 ) 116.30 ( 100.00 )
45.3 105.54 ( 90.75 ) 116.31 ( 100.01 )
45.4 105.57 ( 90.77 ) 116.32 ( 100.02 )
45.5 105.60 ( 90.80 ) 116.33 ( 100.03 )
45.6 105.63 ( 90.83 ) 116.34 ( 100.04 )
45.7 105.66 ( 90.85 ) 116.35 ( 100.05 )
45.8 105.69 ( 90.88 ) 116.36 ( 100.06 )
45.9 105.72 ( 90.90 ) 116.38 ( 100.07 )
Table 20. Outdoor Unit Capacity (JTOR320~360VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (6)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-32FSXNS
JTOR320VAE(U,F,R)BS1 RAS-34FSXNS
JTOR340VAE(U,F,R)BS1 RAS-36FSXNS
JTOR360VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
46.0 105.75 ( 90.93 ) 116.39 ( 100.08 )
46.1 105.78 ( 90.96 ) 116.40 ( 100.09 )
46.2 105.81 ( 90.98 ) 116.41 ( 100.10 )
46.3 105.85 ( 91.01 ) 116.42 ( 100.11 )
46.4 _ _ 105.88 ( 91.04 ) 116.43 ( 100.12 )
46.5 105.91 ( 91.06 ) 116.45 ( 100.13 )
46.6 105.94 ( 91.09 ) 116.46 ( 100.13 )
46.7 105.97 ( 91.12 ) 116.47 ( 100.14 )
46.8 106.00 ( 91.14 ) 116.48 ( 100.15 )
Table 21. Outdoor Unit Capacity (JTOR380~420VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (1)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-38FSXNS
JTOR380VAE(U,F,R)BS1 RAS-40FSXNS
JTOR400VAE(U,F,R)BS1 RAS-42FSXNS
JTOR420VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
19.0 53.00 ( 45.57 ) 59.00 ( 50.73 )
19.1 53.28 ( 45.81 ) 59.31 ( 51.00 )
19.2 53.56 ( 46.05 ) 59.62 ( 51.26 )
19.3 53.84 ( 46.29 ) 59.93 ( 51.53 )
19.4 54.12 ( 46.53 ) 60.24 ( 51.80 )
_
19.5 54.39 ( 46.77 ) 60.55 ( 52.07 )
19.6 54.67 ( 47.01 ) 60.86 ( 52.33 )
19.7 54.95 ( 47.25 ) 61.17 ( 52.60 )
19.8 55.23 ( 47.49 ) 61.48 ( 52.87 )
19.9 55.51 ( 47.73 ) 61.79 ( 53.13 )
_
20.0 55.79 ( 47.97 ) 62.11 ( 53.40 ) 56.00 ( 48.15 ) 62.50 ( 53.74 )
20.1 56.07 ( 48.21 ) 62.42 ( 53.67 ) 56.28 ( 48.39 ) 62.81 ( 54.01 )
20.2 56.35 ( 48.45 ) 62.73 ( 53.93 ) 56.56 ( 48.63 ) 63.12 ( 54.28 )
20.3 56.63 ( 48.69 ) 63.04 ( 54.20 ) 56.84 ( 48.87 ) 63.44 ( 54.55 )
20.4 56.91 ( 48.93 ) 63.35 ( 54.47 ) 57.12 ( 49.11 ) 63.75 ( 54.82 )
20.5 57.18 ( 49.17 ) 63.66 ( 54.74 ) 57.40 ( 49.36 ) 64.06 ( 55.08 )
20.6 57.46 ( 49.41 ) 63.97 ( 55.00 ) 57.68 ( 49.60 ) 64.37 ( 55.35 )
20.7 57.74 ( 49.65 ) 64.28 ( 55.27 ) 57.96 ( 49.84 ) 64.69 ( 55.62 )
20.8 58.02 ( 49.89 ) 64.59 ( 55.54 ) 58.24 ( 50.08 ) 65.00 ( 55.89 )
20.9 58.30 ( 50.13 ) 64.90 ( 55.80 ) 58.52 ( 50.32 ) 65.31 ( 56.16 )
21.0 58.58 ( 50.37 ) 65.21 ( 56.07 ) 58.80 ( 50.56 ) 65.63 ( 56.43 ) 59.00 ( 50.73 ) 66.00 ( 56.75 )
21.1 58.86 ( 50.61 ) 65.52 ( 56.34 ) 59.08 ( 50.80 ) 65.94 ( 56.70 ) 59.28 ( 50.97 ) 66.31 ( 57.02 )
21.2 59.14 ( 50.85 ) 65.83 ( 56.60 ) 59.36 ( 51.04 ) 66.25 ( 56.96 ) 59.56 ( 51.21 ) 66.63 ( 57.29 )
21.3 59.42 ( 51.09 ) 66.14 ( 56.87 ) 59.64 ( 51.28 ) 66.56 ( 57.23 ) 59.84 ( 51.46 ) 66.94 ( 57.56 )
21.4 59.69 ( 51.33 ) 66.45 ( 57.14 ) 59.92 ( 51.52 ) 66.88 ( 57.50 ) 60.12 ( 51.70 ) 67.26 ( 57.83 )
21.5 59.97 ( 51.57 ) 66.76 ( 57.41 ) 60.20 ( 51.76 ) 67.19 ( 57.77 ) 60.40 ( 51.94 ) 67.57 ( 58.10 )
21.6 60.25 ( 51.81 ) 67.07 ( 57.67 ) 60.48 ( 52.00 ) 67.50 ( 58.04 ) 60.69 ( 52.18 ) 67.89 ( 58.37 )
21.7 60.53 ( 52.05 ) 67.38 ( 57.94 ) 60.76 ( 52.24 ) 67.81 ( 58.31 ) 60.97 ( 52.42 ) 68.20 ( 58.64 )
21.8 60.81 ( 52.29 ) 67.69 ( 58.21 ) 61.04 ( 52.48 ) 68.12 ( 58.58 ) 61.25 ( 52.66 ) 68.51 ( 58.91 )
21.9 61.09 ( 52.53 ) 68.01 ( 58.47 ) 61.32 ( 52.73 ) 68.44 ( 58.85 ) 61.53 ( 52.91 ) 68.83 ( 59.18 )
22.0 61.37 ( 52.77 ) 68.32 ( 58.74 ) 61.60 ( 52.97 ) 68.75 ( 59.11 ) 61.81 ( 53.15 ) 69.14 ( 59.45 )
22.1 61.65 ( 53.01 ) 68.63 ( 59.01 ) 61.88 ( 53.21 ) 69.06 ( 59.38 ) 62.09 ( 53.39 ) 69.46 ( 59.72 )
22.2 61.93 ( 53.25 ) 68.94 ( 59.28 ) 62.16 ( 53.45 ) 69.37 ( 59.65 ) 62.37 ( 53.63 ) 69.77 ( 59.99 )
22.3 62.21 ( 53.49 ) 69.25 ( 59.54 ) 62.44 ( 53.69 ) 69.69 ( 59.92 ) 62.65 ( 53.87 ) 70.09 ( 60.26 )
22.4 62.48 ( 53.73 ) 69.56 ( 59.81 ) 62.72 ( 53.93 ) 70.00 ( 60.19 ) 62.93 ( 54.11 ) 70.40 ( 60.53 )
22.5 62.76 ( 53.97 ) 69.87 ( 60.08 ) 63.00 ( 54.17 ) 70.31 ( 60.46 ) 63.21 ( 54.35 ) 70.71 ( 60.80 )
22.6 63.04 ( 54.21 ) 70.18 ( 60.34 ) 63.28 ( 54.41 ) 70.62 ( 60.73 ) 63.50 ( 54.60 ) 71.03 ( 61.07 )
22.7 63.32 ( 54.45 ) 70.49 ( 60.61 ) 63.56 ( 54.65 ) 70.94 ( 61.00 ) 63.78 ( 54.84 ) 71.34 ( 61.34 )
22.8 63.60 ( 54.69 ) 70.80 ( 60.88 ) 63.84 ( 54.89 ) 71.25 ( 61.26 ) 64.06 ( 55.08 ) 71.66 ( 61.61 )
22.9 63.88 ( 54.93 ) 71.11 ( 61.14 ) 64.12 ( 55.13 ) 71.56 ( 61.53 ) 64.34 ( 55.32 ) 71.97 ( 61.88 )
23.0 64.16 ( 55.17 ) 71.42 ( 61.41 ) 64.40 ( 55.37 ) 71.87 ( 61.80 ) 64.62 ( 55.56 ) 72.29 ( 62.15 )
23.1 64.44 ( 55.41 ) 71.73 ( 61.68 ) 64.68 ( 55.61 ) 72.19 ( 62.07 ) 64.90 ( 55.80 ) 72.60 ( 62.42 )
23.2 64.72 ( 55.65 ) 72.04 ( 61.95 ) 64.96 ( 55.86 ) 72.50 ( 62.34 ) 65.18 ( 56.05 ) 72.91 ( 62.70 )
23.3 64.99 ( 55.89 ) 72.35 ( 62.21 ) 65.24 ( 56.10 ) 72.81 ( 62.61 ) 65.46 ( 56.29 ) 73.23 ( 62.97 )
23.4 65.27 ( 56.13 ) 72.66 ( 62.48 ) 65.52 ( 56.34 ) 73.12 ( 62.88 ) 65.74 ( 56.53 ) 73.54 ( 63.24 )
23.5 65.55 ( 56.37 ) 72.97 ( 62.75 ) 65.80 ( 56.58 ) 73.44 ( 63.14 ) 66.02 ( 56.77 ) 73.86 ( 63.51 )
23.6 65.83 ( 56.60 ) 73.28 ( 63.01 ) 66.08 ( 56.82 ) 73.75 ( 63.41 ) 66.30 ( 57.01 ) 74.17 ( 63.78 )
23.7 66.11 ( 56.84 ) 73.59 ( 63.28 ) 66.36 ( 57.06 ) 74.06 ( 63.68 ) 66.59 ( 57.25 ) 74.49 ( 64.05 )
23.8 66.39 ( 57.08 ) 73.91 ( 63.55 ) 66.64 ( 57.30 ) 74.37 ( 63.95 ) 66.87 ( 57.49 ) 74.80 ( 64.32 )
23.9 66.67 ( 57.32 ) 74.22 ( 63.81 ) 66.92 ( 57.54 ) 74.69 ( 64.22 ) 67.15 ( 57.74 ) 75.11 ( 64.59 )
24.0 66.95 ( 57.56 ) 74.53 ( 64.08 ) 67.20 ( 57.78 ) 75.00 ( 64.49 ) 67.43 ( 57.98 ) 75.43 ( 64.86 )
24.1 67.23 ( 57.80 ) 74.84 ( 64.35 ) 67.48 ( 58.02 ) 75.31 ( 64.76 ) 67.71 ( 58.22 ) 75.74 ( 65.13 )
24.2 67.51 ( 58.04 ) 75.15 ( 64.62 ) 67.76 ( 58.26 ) 75.62 ( 65.03 ) 67.99 ( 58.46 ) 76.06 ( 65.40 )
24.3 67.78 ( 58.28 ) 75.46 ( 64.88 ) 68.04 ( 58.50 ) 75.94 ( 65.29 ) 68.27 ( 58.70 ) 76.37 ( 65.67 )
24.4 68.06 ( 58.52 ) 75.77 ( 65.15 ) 68.32 ( 58.74 ) 76.25 ( 65.56 ) 68.55 ( 58.94 ) 76.69 ( 65.94 )
24.5 68.34 ( 58.76 ) 76.08 ( 65.42 ) 68.60 ( 58.99 ) 76.56 ( 65.83 ) 68.83 ( 59.19 ) 77.00 ( 66.21 )
24.6 68.62 ( 59.00 ) 76.39 ( 65.68 ) 68.88 ( 59.23 ) 76.87 ( 66.10 ) 69.11 ( 59.43 ) 77.31 ( 66.48 )
24.7 68.90 ( 59.24 ) 76.70 ( 65.95 ) 69.16 ( 59.47 ) 77.19 ( 66.37 ) 69.40 ( 59.67 ) 77.63 ( 66.75 )
24.8 69.18 ( 59.48 ) 77.01 ( 66.22 ) 69.44 ( 59.71 ) 77.50 ( 66.64 ) 69.68 ( 59.91 ) 77.94 ( 67.02 )
24.9 69.46 ( 59.72 ) 77.32 ( 66.48 ) 69.72 ( 59.95 ) 77.81 ( 66.91 ) 69.96 ( 60.15 ) 78.26 ( 67.29 )
Table 22. Outdoor Unit Capacity (JTOR380~420VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (2)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-38FSXNS
JTOR380VAE(U,F,R)BS1 RAS-40FSXNS
JTOR400VAE(U,F,R)BS1 RAS-42FSXNS
JTOR420VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
25.0 69.74 ( 59.96 ) 77.63 ( 66.75 ) 70.00 ( 60.19 ) 78.12 ( 67.18 ) 70.24 ( 60.39 ) 78.57 ( 67.56 )
25.1 70.02 ( 60.20 ) 77.94 ( 67.02 ) 70.28 ( 60.43 ) 78.44 ( 67.44 ) 70.52 ( 60.64 ) 78.89 ( 67.83 )
25.2 70.29 ( 60.44 ) 78.25 ( 67.29 ) 70.56 ( 60.67 ) 78.75 ( 67.71 ) 70.80 ( 60.88 ) 79.20 ( 68.10 )
25.3 70.57 ( 60.68 ) 78.56 ( 67.55 ) 70.84 ( 60.91 ) 79.06 ( 67.98 ) 71.08 ( 61.12 ) 79.51 ( 68.37 )
25.4 70.85 ( 60.92 ) 78.87 ( 67.82 ) 71.12 ( 61.15 ) 79.37 ( 68.25 ) 71.36 ( 61.36 ) 79.83 ( 68.64 )
25.5 71.13 ( 61.16 ) 79.18 ( 68.09 ) 71.40 ( 61.39 ) 79.69 ( 68.52 ) 71.64 ( 61.60 ) 80.14 ( 68.91 )
25.6 71.41 ( 61.40 ) 79.49 ( 68.35 ) 71.68 ( 61.63 ) 80.00 ( 68.79 ) 71.92 ( 61.84 ) 80.46 ( 69.18 )
25.7 71.69 ( 61.64 ) 79.81 ( 68.62 ) 71.96 ( 61.87 ) 80.31 ( 69.06 ) 72.20 ( 62.08 ) 80.77 ( 69.45 )
25.8 71.97 ( 61.88 ) 80.12 ( 68.89 ) 72.24 ( 62.12 ) 80.62 ( 69.33 ) 72.49 ( 62.33 ) 81.09 ( 69.72 )
25.9 72.25 ( 62.12 ) 80.43 ( 69.15 ) 72.52 ( 62.36 ) 80.94 ( 69.59 ) 72.77 ( 62.57 ) 81.40 ( 69.99 )
26.0 72.53 ( 62.36 ) 80.74 ( 69.42 ) 72.80 ( 62.60 ) 81.25 ( 69.86 ) 73.05 ( 62.81 ) 81.71 ( 70.26 )
26.1 72.81 ( 62.60 ) 81.05 ( 69.69 ) 73.08 ( 62.84 ) 81.56 ( 70.13 ) 73.33 ( 63.05 ) 82.03 ( 70.53 )
26.2 73.08 ( 62.84 ) 81.36 ( 69.96 ) 73.36 ( 63.08 ) 81.87 ( 70.40 ) 73.61 ( 63.29 ) 82.34 ( 70.80 )
26.3 73.36 ( 63.08 ) 81.67 ( 70.22 ) 73.64 ( 63.32 ) 82.19 ( 70.67 ) 73.89 ( 63.53 ) 82.66 ( 71.07 )
26.4 73.64 ( 63.32 ) 81.98 ( 70.49 ) 73.92 ( 63.56 ) 82.50 ( 70.94 ) 74.17 ( 63.78 ) 82.97 ( 71.34 )
26.5 73.92 ( 63.56 ) 82.29 ( 70.76 ) 74.20 ( 63.80 ) 82.81 ( 71.21 ) 74.45 ( 64.02 ) 83.29 ( 71.61 )
26.6 74.20 ( 63.80 ) 82.60 ( 71.02 ) 74.48 ( 64.04 ) 83.12 ( 71.47 ) 74.73 ( 64.26 ) 83.60 ( 71.88 )
26.7 74.48 ( 64.04 ) 82.91 ( 71.29 ) 74.76 ( 64.28 ) 83.44 ( 71.74 ) 75.01 ( 64.50 ) 83.91 ( 72.15 )
26.8 74.76 ( 64.28 ) 83.22 ( 71.56 ) 75.04 ( 64.52 ) 83.75 ( 72.01 ) 75.30 ( 64.74 ) 84.23 ( 72.42 )
26.9 75.04 ( 64.52 ) 83.53 ( 71.82 ) 75.32 ( 64.76 ) 84.06 ( 72.28 ) 75.58 ( 64.98 ) 84.54 ( 72.69 )
27.0 75.32 ( 64.76 ) 83.84 ( 72.09 ) 75.60 ( 65.00 ) 84.37 ( 72.55 ) 75.86 ( 65.23 ) 84.86 ( 72.96 )
27.1 75.59 ( 65.00 ) 84.15 ( 72.36 ) 75.88 ( 65.25 ) 84.69 ( 72.82 ) 76.14 ( 65.47 ) 85.17 ( 73.23 )
27.2 75.87 ( 65.24 ) 84.46 ( 72.63 ) 76.16 ( 65.49 ) 85.00 ( 73.09 ) 76.42 ( 65.71 ) 85.49 ( 73.50 )
27.3 76.15 ( 65.48 ) 84.77 ( 72.89 ) 76.44 ( 65.73 ) 85.31 ( 73.36 ) 76.70 ( 65.95 ) 85.80 ( 73.77 )
27.4 76.43 ( 65.72 ) 85.08 ( 73.16 ) 76.72 ( 65.97 ) 85.62 ( 73.62 ) 76.98 ( 66.19 ) 86.11 ( 74.04 )
27.5 76.71 ( 65.96 ) 85.39 ( 73.43 ) 77.00 ( 66.21 ) 85.94 ( 73.89 ) 77.26 ( 66.43 ) 86.43 ( 74.32 )
27.6 76.99 ( 66.20 ) 85.71 ( 73.69 ) 77.28 ( 66.45 ) 86.25 ( 74.16 ) 77.54 ( 66.67 ) 86.74 ( 74.59 )
27.7 77.27 ( 66.44 ) 86.02 ( 73.96 ) 77.56 ( 66.69 ) 86.56 ( 74.43 ) 77.82 ( 66.92 ) 87.06 ( 74.86 )
27.8 77.55 ( 66.68 ) 86.33 ( 74.23 ) 77.84 ( 66.93 ) 86.88 ( 74.70 ) 78.10 ( 67.16 ) 87.37 ( 75.13 )
27.9 77.83 ( 66.92 ) 86.64 ( 74.49 ) 78.12 ( 67.17 ) 87.19 ( 74.97 ) 78.39 ( 67.40 ) 87.69 ( 75.40 )
28.0 78.11 ( 67.16 ) 86.95 ( 74.76 ) 78.40 ( 67.41 ) 87.50 ( 75.24 ) 78.67 ( 67.64 ) 88.00 ( 75.67 )
28.1 78.38 ( 67.40 ) 87.26 ( 75.03 ) 78.68 ( 67.65 ) 87.81 ( 75.51 ) 78.95 ( 67.88 ) 88.31 ( 75.94 )
28.2 78.66 ( 67.64 ) 87.57 ( 75.30 ) 78.96 ( 67.89 ) 88.13 ( 75.77 ) 79.23 ( 68.12 ) 88.63 ( 76.21 )
28.3 78.94 ( 67.88 ) 87.88 ( 75.56 ) 79.24 ( 68.13 ) 88.44 ( 76.04 ) 79.51 ( 68.37 ) 88.94 ( 76.48 )
28.4 79.22 ( 68.12 ) 88.19 ( 75.83 ) 79.52 ( 68.37 ) 88.75 ( 76.31 ) 79.79 ( 68.61 ) 89.26 ( 76.75 )
28.5 79.50 ( 68.36 ) 88.50 ( 76.10 ) 79.80 ( 68.62 ) 89.06 ( 76.58 ) 80.07 ( 68.85 ) 89.57 ( 77.02 )
28.6 79.78 ( 68.60 ) 88.81 ( 76.36 ) 80.08 ( 68.86 ) 89.38 ( 76.85 ) 80.35 ( 69.09 ) 89.89 ( 77.29 )
28.7 80.06 ( 68.84 ) 89.12 ( 76.63 ) 80.36 ( 69.10 ) 89.69 ( 77.12 ) 80.63 ( 69.33 ) 90.20 ( 77.56 )
28.8 80.34 ( 69.08 ) 89.43 ( 76.90 ) 80.64 ( 69.34 ) 90.00 ( 77.39 ) 80.91 ( 69.57 ) 90.51 ( 77.83 )
28.9 80.62 ( 69.32 ) 89.74 ( 77.16 ) 80.92 ( 69.58 ) 90.31 ( 77.65 ) 81.20 ( 69.82 ) 90.83 ( 78.10 )
29.0 80.89 ( 69.56 ) 90.05 ( 77.43 ) 81.20 ( 69.82 ) 90.63 ( 77.92 ) 81.48 ( 70.06 ) 91.14 ( 78.37 )
29.1 81.17 ( 69.80 ) 90.36 ( 77.70 ) 81.48 ( 70.06 ) 90.94 ( 78.19 ) 81.76 ( 70.30 ) 91.46 ( 78.64 )
29.2 81.45 ( 70.04 ) 90.67 ( 77.97 ) 81.76 ( 70.30 ) 91.25 ( 78.46 ) 82.04 ( 70.54 ) 91.77 ( 78.91 )
29.3 81.73 ( 70.28 ) 90.98 ( 78.23 ) 82.04 ( 70.54 ) 91.56 ( 78.73 ) 82.32 ( 70.78 ) 92.09 ( 79.18 )
29.4 82.01 ( 70.52 ) 91.29 ( 78.50 ) 82.32 ( 70.78 ) 91.88 ( 79.00 ) 82.60 ( 71.02 ) 92.40 ( 79.45 )
29.5 82.29 ( 70.76 ) 91.61 ( 78.77 ) 82.60 ( 71.02 ) 92.19 ( 79.27 ) 82.88 ( 71.26 ) 92.71 ( 79.72 )
29.6 82.57 ( 71.00 ) 91.92 ( 79.03 ) 82.88 ( 71.26 ) 92.50 ( 79.54 ) 83.16 ( 71.51 ) 93.03 ( 79.99 )
29.7 82.85 ( 71.24 ) 92.23 ( 79.30 ) 83.16 ( 71.50 ) 92.81 ( 79.80 ) 83.44 ( 71.75 ) 93.34 ( 80.26 )
29.8 83.13 ( 71.48 ) 92.54 ( 79.57 ) 83.44 ( 71.75 ) 93.13 ( 80.07 ) 83.72 ( 71.99 ) 93.66 ( 80.53 )
29.9 83.41 ( 71.72 ) 92.85 ( 79.83 ) 83.72 ( 71.99 ) 93.44 ( 80.34 ) 84.00 ( 72.23 ) 93.97 ( 80.80 )
30.0 83.68 ( 71.96 ) 93.16 ( 80.10 ) 84.00 ( 72.23 ) 93.75 ( 80.61 ) 84.29 ( 72.47 ) 94.29 ( 81.07 )
30.1 83.96 ( 72.20 ) 93.47 ( 80.37 ) 84.28 ( 72.47 ) 94.06 ( 80.88 ) 84.57 ( 72.71 ) 94.60 ( 81.34 )
30.2 84.24 ( 72.44 ) 93.78 ( 80.64 ) 84.56 ( 72.71 ) 94.38 ( 81.15 ) 84.85 ( 72.96 ) 94.91 ( 81.61 )
30.3 84.52 ( 72.68 ) 94.09 ( 80.90 ) 84.84 ( 72.95 ) 94.69 ( 81.42 ) 85.13 ( 73.20 ) 95.23 ( 81.88 )
30.4 84.80 ( 72.91 ) 94.40 ( 81.17 ) 85.12 ( 73.19 ) 95.00 ( 81.69 ) 85.41 ( 73.44 ) 95.54 ( 82.15 )
30.5 85.08 ( 73.15 ) 94.71 ( 81.44 ) 85.40 ( 73.43 ) 95.31 ( 81.95 ) 85.69 ( 73.68 ) 95.86 ( 82.42 )
30.6 85.36 ( 73.39 ) 95.02 ( 81.70 ) 85.68 ( 73.67 ) 95.63 ( 82.22 ) 85.97 ( 73.92 ) 96.17 ( 82.69 )
30.7 85.64 ( 73.63 ) 95.33 ( 81.97 ) 85.96 ( 73.91 ) 95.94 ( 82.49 ) 86.25 ( 74.16 ) 96.49 ( 82.96 )
30.8 85.92 ( 73.87 ) 95.64 ( 82.24 ) 86.24 ( 74.15 ) 96.25 ( 82.76 ) 86.53 ( 74.41 ) 96.80 ( 83.23 )
30.9 86.19 ( 74.11 ) 95.95 ( 82.50 ) 86.52 ( 74.39 ) 96.56 ( 83.03 ) 86.81 ( 74.65 ) 97.11 ( 83.50 )
Table 23. Outdoor Unit Capacity (JTOR380~420VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (3)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-38FSXNS
JTOR380VAE(U,F,R)BS1 RAS-40FSXNS
JTOR400VAE(U,F,R)BS1 RAS-42FSXNS
JTOR420VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
31.0 86.47 ( 74.35 ) 96.26 ( 82.77 ) 86.80 ( 74.63 ) 96.88 ( 83.30 ) 87.10 ( 74.89 ) 97.43 ( 83.77 )
31.1 86.75 ( 74.59 ) 96.57 ( 83.04 ) 87.08 ( 74.88 ) 97.19 ( 83.57 ) 87.38 ( 75.13 ) 97.74 ( 84.04 )
31.2 87.03 ( 74.83 ) 96.88 ( 83.31 ) 87.36 ( 75.12 ) 97.50 ( 83.83 ) 87.66 ( 75.37 ) 98.06 ( 84.31 )
31.3 87.31 ( 75.07 ) 97.19 ( 83.57 ) 87.64 ( 75.36 ) 97.81 ( 84.10 ) 87.94 ( 75.61 ) 98.37 ( 84.58 )
31.4 87.59 ( 75.31 ) 97.51 ( 83.84 ) 87.92 ( 75.60 ) 98.13 ( 84.37 ) 88.22 ( 75.85 ) 98.69 ( 84.85 )
31.5 87.87 ( 75.55 ) 97.82 ( 84.11 ) 88.20 ( 75.84 ) 98.44 ( 84.64 ) 88.50 ( 76.10 ) 99.00 ( 85.12 )
31.6 88.15 ( 75.79 ) 98.13 ( 84.37 ) 88.48 ( 76.08 ) 98.75 ( 84.91 ) 88.78 ( 76.34 ) 99.31 ( 85.39 )
31.7 88.43 ( 76.03 ) 98.44 ( 84.64 ) 88.76 ( 76.32 ) 99.06 ( 85.18 ) 89.06 ( 76.58 ) 99.63 ( 85.67 )
31.8 88.71 ( 76.27 ) 98.75 ( 84.91 ) 89.04 ( 76.56 ) 99.37 ( 85.45 ) 89.34 ( 76.82 ) 99.94 ( 85.94 )
31.9 88.98 ( 76.51 ) 99.06 ( 85.17 ) 89.32 ( 76.80 ) 99.69 ( 85.72 ) 89.62 ( 77.06 ) 100.26 ( 86.21 )
32.0 89.26 ( 76.75 ) 99.37 ( 85.44 ) 89.60 ( 77.04 ) 100.00 ( 85.98 ) 89.90 ( 77.30 ) 100.57 ( 86.48 )
32.1 89.54 ( 76.99 ) 99.68 ( 85.71 ) 89.88 ( 77.28 ) 100.31 ( 86.25 ) 90.19 ( 77.55 ) 100.89 ( 86.75 )
32.2 89.82 ( 77.23 ) 99.99 ( 85.98 ) 90.16 ( 77.52 ) 100.63 ( 86.52 ) 90.47 ( 77.79 ) 101.20 ( 87.02 )
32.3 90.10 ( 77.47 ) 100.30 ( 86.24 ) 90.44 ( 77.76 ) 100.94 ( 86.79 ) 90.75 ( 78.03 ) 101.51 ( 87.29 )
32.4 90.38 ( 77.71 ) 100.61 ( 86.51 ) 90.72 ( 78.01 ) 101.25 ( 87.06 ) 91.03 ( 78.27 ) 101.83 ( 87.56 )
32.5 90.66 ( 77.95 ) 100.92 ( 86.78 ) 91.00 ( 78.25 ) 101.56 ( 87.33 ) 91.31 ( 78.51 ) 102.14 ( 87.83 )
32.6 90.94 ( 78.19 ) 101.23 ( 87.04 ) 91.28 ( 78.49 ) 101.88 ( 87.60 ) 91.59 ( 78.75 ) 102.46 ( 88.10 )
32.7 91.22 ( 78.43 ) 101.54 ( 87.31 ) 91.56 ( 78.73 ) 102.19 ( 87.87 ) 91.87 ( 79.00 ) 102.77 ( 88.37 )
32.8 91.49 ( 78.67 ) 101.85 ( 87.58 ) 91.84 ( 78.97 ) 102.50 ( 88.13 ) 92.15 ( 79.24 ) 103.09 ( 88.64 )
32.9 91.77 ( 78.91 ) 102.16 ( 87.84 ) 92.12 ( 79.21 ) 102.81 ( 88.40 ) 92.43 ( 79.48 ) 103.40 ( 88.91 )
33.0 92.05 ( 79.15 ) 102.47 ( 88.11 ) 92.40 ( 79.45 ) 103.13 ( 88.67 ) 92.71 ( 79.72 ) 103.71 ( 89.18 )
33.1 92.33 ( 79.39 ) 102.78 ( 88.38 ) 92.68 ( 79.69 ) 103.44 ( 88.94 ) 93.00 ( 79.96 ) 104.03 ( 89.45 )
33.2 92.61 ( 79.63 ) 103.09 ( 88.65 ) 92.96 ( 79.93 ) 103.75 ( 89.21 ) 93.28 ( 80.20 ) 104.34 ( 89.72 )
33.3 92.89 ( 79.87 ) 103.41 ( 88.91 ) 93.24 ( 80.17 ) 104.06 ( 89.48 ) 93.56 ( 80.44 ) 104.66 ( 89.99 )
33.4 93.17 ( 80.11 ) 103.72 ( 89.18 ) 93.52 ( 80.41 ) 104.38 ( 89.75 ) 93.84 ( 80.69 ) 104.97 ( 90.26 )
33.5 93.45 ( 80.35 ) 104.03 ( 89.45 ) 93.80 ( 80.65 ) 104.69 ( 90.02 ) 94.12 ( 80.93 ) 105.29 ( 90.53 )
33.6 93.73 ( 80.59 ) 104.34 ( 89.71 ) 94.08 ( 80.89 ) 105.00 ( 90.28 ) 94.40 ( 81.17 ) 105.60 ( 90.80 )
33.7 94.01 ( 80.83 ) 104.65 ( 89.98 ) 94.36 ( 81.13 ) 105.31 ( 90.55 ) 94.68 ( 81.41 ) 105.91 ( 91.07 )
33.8 94.28 ( 81.07 ) 104.96 ( 90.25 ) 94.64 ( 81.38 ) 105.63 ( 90.82 ) 94.96 ( 81.65 ) 106.23 ( 91.34 )
33.9 94.56 ( 81.31 ) 105.27 ( 90.51 ) 94.92 ( 81.62 ) 105.94 ( 91.09 ) 95.24 ( 81.89 ) 106.54 ( 91.61 )
34.0 94.84 ( 81.55 ) 105.58 ( 90.78 ) 95.20 ( 81.86 ) 106.25 ( 91.36 ) 95.52 ( 82.14 ) 106.86 ( 91.88 )
34.1 95.12 ( 81.79 ) 105.89 ( 91.05 ) 95.48 ( 82.10 ) 106.56 ( 91.63 ) 95.80 ( 82.38 ) 107.17 ( 92.15 )
34.2 95.40 ( 82.03 ) 106.20 ( 91.32 ) 95.76 ( 82.34 ) 106.88 ( 91.90 ) 96.09 ( 82.62 ) 107.49 ( 92.42 )
34.3 95.68 ( 82.27 ) 106.51 ( 91.58 ) 96.04 ( 82.58 ) 107.19 ( 92.16 ) 96.37 ( 82.86 ) 107.80 ( 92.69 )
34.4 95.96 ( 82.51 ) 106.82 ( 91.85 ) 96.32 ( 82.82 ) 107.50 ( 92.43 ) 96.65 ( 83.10 ) 108.11 ( 92.96 )
34.5 96.24 ( 82.75 ) 107.13 ( 92.12 ) 96.60 ( 83.06 ) 107.81 ( 92.70 ) 96.93 ( 83.34 ) 108.43 ( 93.23 )
34.6 96.52 ( 82.99 ) 107.44 ( 92.38 ) 96.88 ( 83.30 ) 108.13 ( 92.97 ) 97.21 ( 83.59 ) 108.74 ( 93.50 )
34.7 96.79 ( 83.23 ) 107.75 ( 92.65 ) 97.16 ( 83.54 ) 108.44 ( 93.24 ) 97.49 ( 83.83 ) 109.06 ( 93.77 )
34.8 97.07 ( 83.47 ) 108.06 ( 92.92 ) 97.44 ( 83.78 ) 108.75 ( 93.51 ) 97.77 ( 84.07 ) 109.37 ( 94.04 )
34.9 97.35 ( 83.71 ) 108.37 ( 93.18 ) 97.72 ( 84.02 ) 109.06 ( 93.78 ) 98.05 ( 84.31 ) 109.69 ( 94.31 )
35.0 97.63 ( 83.95 ) 108.68 ( 93.45 ) 98.00 ( 84.26 ) 109.38 ( 94.05 ) 98.33 ( 84.55 ) 110.00 ( 94.58 )
35.1 97.91 ( 84.19 ) 108.99 ( 93.72 ) 98.28 ( 84.51 ) 109.69 ( 94.31 ) 98.61 ( 84.79 ) 110.31 ( 94.85 )
35.2 98.19 ( 84.43 ) 109.31 ( 93.99 ) 98.56 ( 84.75 ) 110.00 ( 94.58 ) 98.90 ( 85.03 ) 110.63 ( 95.12 )
35.3 98.47 ( 84.67 ) 109.62 ( 94.25 ) 98.84 ( 84.99 ) 110.31 ( 94.85 ) 99.18 ( 85.28 ) 110.94 ( 95.39 )
35.4 98.75 ( 84.91 ) 109.93 ( 94.52 ) 99.12 ( 85.23 ) 110.63 ( 95.12 ) 99.46 ( 85.52 ) 111.26 ( 95.66 )
35.5 99.03 ( 85.15 ) 110.24 ( 94.79 ) 99.40 ( 85.47 ) 110.94 ( 95.39 ) 99.74 ( 85.76 ) 111.57 ( 95.93 )
35.6 99.31 ( 85.39 ) 110.55 ( 95.05 ) 99.68 ( 85.71 ) 111.25 ( 95.66 ) 100.02 ( 86.00 ) 111.89 ( 96.20 )
35.7 99.58 ( 85.63 ) 110.86 ( 95.32 ) 99.96 ( 85.95 ) 111.56 ( 95.93 ) 100.30 ( 86.24 ) 112.20 ( 96.47 )
35.8 99.86 ( 85.87 ) 111.17 ( 95.59 ) 100.24 ( 86.19 ) 111.88 ( 96.20 ) 100.58 ( 86.48 ) 112.51 ( 96.74 )
35.9 100.14 ( 86.11 ) 111.48 ( 95.85 ) 100.52 ( 86.43 ) 112.19 ( 96.46 ) 100.86 ( 86.73 ) 112.83 ( 97.02 )
36.0 100.42 ( 86.35 ) 111.79 ( 96.12 ) 100.80 ( 86.67 ) 112.50 ( 96.73 ) 101.14 ( 86.97 ) 113.14 ( 97.29 )
36.1 100.70 ( 86.59 ) 112.10 ( 96.39 ) 101.08 ( 86.91 ) 112.81 ( 97.00 ) 101.42 ( 87.21 ) 113.46 ( 97.56 )
36.2 100.98 ( 86.83 ) 112.41 ( 96.66 ) 101.36 ( 87.15 ) 113.13 ( 97.27 ) 101.70 ( 87.45 ) 113.77 ( 97.83 )
36.3 101.26 ( 87.07 ) 112.72 ( 96.92 ) 101.64 ( 87.39 ) 113.44 ( 97.54 ) 101.99 ( 87.69 ) 114.09 ( 98.10 )
36.4 101.54 ( 87.31 ) 113.03 ( 97.19 ) 101.92 ( 87.64 ) 113.75 ( 97.81 ) 102.27 ( 87.93 ) 114.40 ( 98.37 )
36.5 101.82 ( 87.55 ) 113.34 ( 97.46 ) 102.20 ( 87.88 ) 114.06 ( 98.08 ) 102.55 ( 88.18 ) 114.71 ( 98.64 )
36.6 102.09 ( 87.79 ) 113.65 ( 97.72 ) 102.48 ( 88.12 ) 114.38 ( 98.34 ) 102.83 ( 88.42 ) 115.03 ( 98.91 )
36.7 102.37 ( 88.03 ) 113.96 ( 97.99 ) 102.76 ( 88.36 ) 114.69 ( 98.61 ) 103.11 ( 88.66 ) 115.34 ( 99.18 )
36.8 102.65 ( 88.27 ) 114.27 ( 98.26 ) 103.04 ( 88.60 ) 115.00 ( 98.88 ) 103.39 ( 88.90 ) 115.66 ( 99.45 )
36.9 102.93 ( 88.51 ) 114.58 ( 98.52 ) 103.32 ( 88.84 ) 115.31 ( 99.15 ) 103.67 ( 89.14 ) 115.97 ( 99.72 )
Table 24. Outdoor Unit Capacity (JTOR380~420VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (4)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-38FSXNS
JTOR380VAE(U,F,R)BS1 RAS-40FSXNS
JTOR400VAE(U,F,R)BS1 RAS-42FSXNS
JTOR420VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
37.0 103.21 ( 88.75 ) 114.89 ( 98.79 ) 103.60 ( 89.08 ) 115.63 ( 99.42 ) 103.95 ( 89.38 ) 116.29 ( 99.99 )
37.1 103.49 ( 88.98 ) 115.21 ( 99.06 ) 103.88 ( 89.32 ) 115.94 ( 99.69 ) 104.23 ( 89.62 ) 116.60 ( 100.26 )
37.2 103.77 ( 89.22 ) 115.52 ( 99.33 ) 104.16 ( 89.56 ) 116.25 ( 99.96 ) 104.51 ( 89.87 ) 116.91 ( 100.53 )
37.3 104.05 ( 89.46 ) 115.83 ( 99.59 ) 104.44 ( 89.80 ) 116.56 ( 100.23 ) 104.80 ( 90.11 ) 117.23 ( 100.80 )
37.4 104.33 ( 89.70 ) 116.14 ( 99.86 ) 104.72 ( 90.04 ) 116.88 ( 100.49 ) 105.08 ( 90.35 ) 117.54 ( 101.07 )
37.5 104.61 ( 89.94 ) 116.45 ( 100.13 ) 105.00 ( 90.28 ) 117.19 ( 100.76 ) 105.36 ( 90.59 ) 117.86 ( 101.34 )
37.6 104.88 ( 90.18 ) 116.76 ( 100.39 ) 105.28 ( 90.52 ) 117.50 ( 101.03 ) 105.64 ( 90.83 ) 118.17 ( 101.61 )
37.7 105.16 ( 90.42 ) 117.07 ( 100.66 ) 105.56 ( 90.77 ) 117.81 ( 101.30 ) 105.92 ( 91.07 ) 118.49 ( 101.88 )
37.8 105.44 ( 90.66 ) 117.38 ( 100.93 ) 105.84 ( 91.01 ) 118.13 ( 101.57 ) 106.20 ( 91.32 ) 118.80 ( 102.15 )
37.9 105.72 ( 90.90 ) 117.69 ( 101.19 ) 106.12 ( 91.25 ) 118.44 ( 101.84 ) 106.48 ( 91.56 ) 119.11 ( 102.42 )
38.0 106.00 ( 91.14 ) 118.00 ( 101.46 ) 106.40 ( 91.49 ) 118.75 ( 102.11 ) 106.76 ( 91.80 ) 119.43 ( 102.69 )
38.1 106.03 ( 91.17 ) 118.02 ( 101.48 ) 106.68 ( 91.73 ) 119.06 ( 102.38 ) 107.04 ( 92.04 ) 119.74 ( 102.96 )
38.2 106.06 ( 91.19 ) 118.04 ( 101.50 ) 106.96 ( 91.97 ) 119.38 ( 102.64 ) 107.32 ( 92.28 ) 120.06 ( 103.23 )
38.3 106.08 ( 91.22 ) 118.06 ( 101.52 ) 107.24 ( 92.21 ) 119.69 ( 102.91 ) 107.60 ( 92.52 ) 120.37 ( 103.50 )
38.4 106.11 ( 91.24 ) 118.08 ( 101.53 ) 107.52 ( 92.45 ) 120.00 ( 103.18 ) 107.89 ( 92.77 ) 120.69 ( 103.77 )
38.5 106.14 ( 91.26 ) 118.10 ( 101.55 ) 107.80 ( 92.69 ) 120.31 ( 103.45 ) 108.17 ( 93.01 ) 121.00 ( 104.04 )
38.6 106.17 ( 91.29 ) 118.12 ( 101.57 ) 108.08 ( 92.93 ) 120.63 ( 103.72 ) 108.45 ( 93.25 ) 121.31 ( 104.31 )
38.7 106.20 ( 91.31 ) 118.14 ( 101.59 ) 108.36 ( 93.17 ) 120.94 ( 103.99 ) 108.73 ( 93.49 ) 121.63 ( 104.58 )
38.8 106.22 ( 91.34 ) 118.17 ( 101.60 ) 108.64 ( 93.41 ) 121.25 ( 104.26 ) 109.01 ( 93.73 ) 121.94 ( 104.85 )
38.9 106.25 ( 91.36 ) 118.19 ( 101.62 ) 108.92 ( 93.65 ) 121.56 ( 104.52 ) 109.29 ( 93.97 ) 122.26 ( 105.12 )
39.0 106.28 ( 91.38 ) 118.21 ( 101.64 ) 109.20 ( 93.90 ) 121.88 ( 104.79 ) 109.57 ( 94.21 ) 122.57 ( 105.39 )
39.1 106.31 ( 91.41 ) 118.23 ( 101.66 ) 109.48 ( 94.14 ) 122.19 ( 105.06 ) 109.85 ( 94.46 ) 122.89 ( 105.66 )
39.2 106.33 ( 91.43 ) 118.25 ( 101.68 ) 109.76 ( 94.38 ) 122.50 ( 105.33 ) 110.13 ( 94.70 ) 123.20 ( 105.93 )
39.3 106.36 ( 91.46 ) 118.27 ( 101.69 ) 110.04 ( 94.62 ) 122.81 ( 105.60 ) 110.41 ( 94.94 ) 123.51 ( 106.20 )
39.4 106.39 ( 91.48 ) 118.29 ( 101.71 ) 110.32 ( 94.86 ) 123.13 ( 105.87 ) 110.70 ( 95.18 ) 123.83 ( 106.47 )
39.5 106.42 ( 91.50 ) 118.31 ( 101.73 ) 110.60 ( 95.10 ) 123.44 ( 106.14 ) 110.98 ( 95.42 ) 124.14 ( 106.74 )
39.6 106.45 ( 91.53 ) 118.33 ( 101.75 ) 110.88 ( 95.34 ) 123.75 ( 106.41 ) 111.26 ( 95.66 ) 124.46 ( 107.01 )
39.7 106.47 ( 91.55 ) 118.35 ( 101.76 ) 111.16 ( 95.58 ) 124.06 ( 106.67 ) 111.54 ( 95.91 ) 124.77 ( 107.28 )
39.8 106.50 ( 91.58 ) 118.37 ( 101.78 ) 111.44 ( 95.82 ) 124.38 ( 106.94 ) 111.82 ( 96.15 ) 125.09 ( 107.55 )
39.9 106.53 ( 91.60 ) 118.39 ( 101.80 ) 111.72 ( 96.06 ) 124.69 ( 107.21 ) 112.10 ( 96.39 ) 125.40 ( 107.82 )
40.0 106.56 ( 91.62 ) 118.41 ( 101.82 ) 112.00 ( 96.30 ) 125.00 ( 107.48 ) 112.38 ( 96.63 ) 125.71 ( 108.09 )
40.1 106.59 ( 91.65 ) 118.43 ( 101.84 ) 112.03 ( 96.33 ) 125.02 ( 107.50 ) 112.66 ( 96.87 ) 126.03 ( 108.37 )
40.2 106.61 ( 91.67 ) 118.46 ( 101.85 ) 112.06 ( 96.35 ) 125.04 ( 107.52 ) 112.94 ( 97.11 ) 126.34 ( 108.64 )
40.3 106.64 ( 91.70 ) 118.48 ( 101.87 ) 112.08 ( 96.37 ) 125.06 ( 107.53 ) 113.22 ( 97.35 ) 126.66 ( 108.91 )
40.4 106.67 ( 91.72 ) 118.50 ( 101.89 ) 112.11 ( 96.40 ) 125.08 ( 107.55 ) 113.50 ( 97.60 ) 126.97 ( 109.18 )
40.5 106.70 ( 91.74 ) 118.52 ( 101.91 ) 112.14 ( 96.42 ) 125.10 ( 107.57 ) 113.79 ( 97.84 ) 127.29 ( 109.45 )
40.6 106.73 ( 91.77 ) 118.54 ( 101.92 ) 112.17 ( 96.45 ) 125.13 ( 107.59 ) 114.07 ( 98.08 ) 127.60 ( 109.72 )
40.7 106.75 ( 91.79 ) 118.56 ( 101.94 ) 112.20 ( 96.47 ) 125.15 ( 107.61 ) 114.35 ( 98.32 ) 127.91 ( 109.99 )
40.8 106.78 ( 91.82 ) 118.58 ( 101.96 ) 112.22 ( 96.50 ) 125.17 ( 107.62 ) 114.63 ( 98.56 ) 128.23 ( 110.26 )
40.9 106.81 ( 91.84 ) 118.60 ( 101.98 ) 112.25 ( 96.52 ) 125.19 ( 107.64 ) 114.91 ( 98.80 ) 128.54 ( 110.53 )
41.0 106.84 ( 91.86 ) 118.62 ( 102.00 ) 112.28 ( 96.54 ) 125.21 ( 107.66 ) 115.19 ( 99.05 ) 128.86 ( 110.80 )
41.1 106.86 ( 91.89 ) 118.64 ( 102.01 ) 112.31 ( 96.57 ) 125.23 ( 107.68 ) 115.47 ( 99.29 ) 129.17 ( 111.07 )
41.2 106.89 ( 91.91 ) 118.66 ( 102.03 ) 112.34 ( 96.59 ) 125.25 ( 107.70 ) 115.75 ( 99.53 ) 129.49 ( 111.34 )
41.3 106.92 ( 91.94 ) 118.68 ( 102.05 ) 112.36 ( 96.62 ) 125.27 ( 107.71 ) 116.03 ( 99.77 ) 129.80 ( 111.61 )
41.4 106.95 ( 91.96 ) 118.70 ( 102.07 ) 112.39 ( 96.64 ) 125.29 ( 107.73 ) 116.31 ( 100.01 ) 130.11 ( 111.88 )
41.5 106.98 ( 91.98 ) 118.72 ( 102.08 ) 112.42 ( 96.66 ) 125.31 ( 107.75 ) 116.60 ( 100.25 ) 130.43 ( 112.15 )
41.6 107.00 ( 92.01 ) 118.75 ( 102.10 ) 112.45 ( 96.69 ) 125.33 ( 107.77 ) 116.88 ( 100.50 ) 130.74 ( 112.42 )
41.7 107.03 ( 92.03 ) 118.77 ( 102.12 ) 112.48 ( 96.71 ) 125.35 ( 107.79 ) 117.16 ( 100.74 ) 131.06 ( 112.69 )
41.8 107.06 ( 92.06 ) 118.79 ( 102.14 ) 112.50 ( 96.74 ) 125.38 ( 107.80 ) 117.44 ( 100.98 ) 131.37 ( 112.96 )
41.9 107.09 ( 92.08 ) 118.81 ( 102.16 ) 112.53 ( 96.76 ) 125.40 ( 107.82 ) 117.72 ( 101.22 ) 131.69 ( 113.23 )
42.0 107.12 ( 92.10 ) 118.83 ( 102.17 ) 112.56 ( 96.78 ) 125.42 ( 107.84 ) 118.00 ( 101.46 ) 132.00 ( 113.50 )
42.1 107.14 ( 92.13 ) 118.85 ( 102.19 ) 112.59 ( 96.81 ) 125.44 ( 107.86 ) 118.03 ( 101.49 ) 132.02 ( 113.52 )
42.2 107.17 ( 92.15 ) 118.87 ( 102.21 ) 112.62 ( 96.83 ) 125.46 ( 107.87 ) 118.06 ( 101.51 ) 132.04 ( 113.54 )
42.3 107.20 ( 92.17 ) 118.89 ( 102.23 ) 112.64 ( 96.86 ) 125.48 ( 107.89 ) 118.08 ( 101.53 ) 132.06 ( 113.55 )
42.4 107.23 ( 92.20 ) 118.91 ( 102.24 ) 112.67 ( 96.88 ) 125.50 ( 107.91 ) 118.11 ( 101.56 ) 132.08 ( 113.57 )
42.5 107.26 ( 92.22 ) 118.93 ( 102.26 ) 112.70 ( 96.90 ) 125.52 ( 107.93 ) 118.14 ( 101.58 ) 132.10 ( 113.59 )
42.6 107.28 ( 92.25 ) 118.95 ( 102.28 ) 112.73 ( 96.93 ) 125.54 ( 107.95 ) 118.17 ( 101.61 ) 132.13 ( 113.61 )
42.7 107.31 ( 92.27 ) 118.97 ( 102.30 ) 112.76 ( 96.95 ) 125.56 ( 107.96 ) 118.20 ( 101.63 ) 132.15 ( 113.63 )
42.8 107.34 ( 92.29 ) 118.99 ( 102.32 ) 112.78 ( 96.98 ) 125.58 ( 107.98 ) 118.22 ( 101.65 ) 132.17 ( 113.64 )
42.9 107.37 ( 92.32 ) 119.01 ( 102.33 ) 112.81 ( 97.00 ) 125.60 ( 108.00 ) 118.25 ( 101.68 ) 132.19 ( 113.66 )
Table 25. Outdoor Unit Capacity (JTOR380~420VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (5)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-38FSXNS
JTOR380VAE(U,F,R)BS1 RAS-40FSXNS
JTOR400VAE(U,F,R)BS1 RAS-42FSXNS
JTOR420VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
43.0 107.39 ( 92.34 ) 119.04 ( 102.35 ) 112.84 ( 97.02 ) 125.63 ( 108.02 ) 118.28 ( 101.70 ) 132.21 ( 113.68 )
43.1 107.42 ( 92.37 ) 119.06 ( 102.37 ) 112.87 ( 97.05 ) 125.65 ( 108.04 ) 118.31 ( 101.73 ) 132.23 ( 113.70 )
43.2 107.45 ( 92.39 ) 119.08 ( 102.39 ) 112.90 ( 97.07 ) 125.67 ( 108.05 ) 118.34 ( 101.75 ) 132.25 ( 113.72 )
43.3 107.48 ( 92.41 ) 119.10 ( 102.41 ) 112.92 ( 97.10 ) 125.69 ( 108.07 ) 118.37 ( 101.78 ) 132.27 ( 113.73 )
43.4 107.51 ( 92.44 ) 119.12 ( 102.42 ) 112.95 ( 97.12 ) 125.71 ( 108.09 ) 118.39 ( 101.80 ) 132.29 ( 113.75 )
43.5 107.53 ( 92.46 ) 119.14 ( 102.44 ) 112.98 ( 97.15 ) 125.73 ( 108.11 ) 118.42 ( 101.82 ) 132.31 ( 113.77 )
43.6 107.56 ( 92.49 ) 119.16 ( 102.46 ) 113.01 ( 97.17 ) 125.75 ( 108.13 ) 118.45 ( 101.85 ) 132.34 ( 113.79 )
43.7 107.59 ( 92.51 ) 119.18 ( 102.48 ) 113.04 ( 97.19 ) 125.77 ( 108.14 ) 118.48 ( 101.87 ) 132.36 ( 113.81 )
43.8 107.62 ( 92.53 ) 119.20 ( 102.49 ) 113.06 ( 97.22 ) 125.79 ( 108.16 ) 118.51 ( 101.90 ) 132.38 ( 113.82 )
43.9 107.65 ( 92.56 ) 119.22 ( 102.51 ) 113.09 ( 97.24 ) 125.81 ( 108.18 ) 118.53 ( 101.92 ) 132.40 ( 113.84 )
44.0 107.67 ( 92.58 ) 119.24 ( 102.53 ) 113.12 ( 97.27 ) 125.83 ( 108.20 ) 118.56 ( 101.94 ) 132.42 ( 113.86 )
44.1 107.70 ( 92.61 ) 119.26 ( 102.55 ) 113.15 ( 97.29 ) 125.85 ( 108.22 ) 118.59 ( 101.97 ) 132.44 ( 113.88 )
44.2 107.73 ( 92.63 ) 119.28 ( 102.57 ) 113.18 ( 97.31 ) 125.88 ( 108.23 ) 118.62 ( 101.99 ) 132.46 ( 113.90 )
44.3 107.76 ( 92.65 ) 119.30 ( 102.58 ) 113.20 ( 97.34 ) 125.90 ( 108.25 ) 118.65 ( 102.02 ) 132.48 ( 113.91 )
44.4 107.79 ( 92.68 ) 119.32 ( 102.60 ) 113.23 ( 97.36 ) 125.92 ( 108.27 ) 118.67 ( 102.04 ) 132.50 ( 113.93 )
44.5 107.81 ( 92.70 ) 119.35 ( 102.62 ) 113.26 ( 97.39 ) 125.94 ( 108.29 ) 118.70 ( 102.07 ) 132.52 ( 113.95 )
44.6 107.84 ( 92.73 ) 119.37 ( 102.64 ) 113.29 ( 97.41 ) 125.96 ( 108.30 ) 118.73 ( 102.09 ) 132.54 ( 113.97 )
44.7 107.87 ( 92.75 ) 119.39 ( 102.65 ) 113.32 ( 97.43 ) 125.98 ( 108.32 ) 118.76 ( 102.11 ) 132.57 ( 113.99 )
44.8 107.90 ( 92.77 ) 119.41 ( 102.67 ) 113.34 ( 97.46 ) 126.00 ( 108.34 ) 118.79 ( 102.14 ) 132.59 ( 114.00 )
44.9 107.92 ( 92.80 ) 119.43 ( 102.69 ) 113.37 ( 97.48 ) 126.02 ( 108.36 ) 118.81 ( 102.16 ) 132.61 ( 114.02 )
45.0 107.95 ( 92.82 ) 119.45 ( 102.71 ) 113.40 ( 97.51 ) 126.04 ( 108.38 ) 118.84 ( 102.19 ) 132.63 ( 114.04 )
45.1 107.98 ( 92.85 ) 119.47 ( 102.73 ) 113.43 ( 97.53 ) 126.06 ( 108.39 ) 118.87 ( 102.21 ) 132.65 ( 114.06 )
45.2 108.01 ( 92.87 ) 119.49 ( 102.74 ) 113.46 ( 97.55 ) 126.08 ( 108.41 ) 118.90 ( 102.23 ) 132.67 ( 114.08 )
45.3 108.04 ( 92.89 ) 119.51 ( 102.76 ) 113.48 ( 97.58 ) 126.10 ( 108.43 ) 118.93 ( 102.26 ) 132.69 ( 114.09 )
45.4 108.06 ( 92.92 ) 119.53 ( 102.78 ) 113.51 ( 97.60 ) 126.13 ( 108.45 ) 118.96 ( 102.28 ) 132.71 ( 114.11 )
45.5 108.09 ( 92.94 ) 119.55 ( 102.80 ) 113.54 ( 97.63 ) 126.15 ( 108.47 ) 118.98 ( 102.31 ) 132.73 ( 114.13 )
45.6 108.12 ( 92.97 ) 119.57 ( 102.81 ) 113.57 ( 97.65 ) 126.17 ( 108.48 ) 119.01 ( 102.33 ) 132.75 ( 114.15 )
45.7 108.15 ( 92.99 ) 119.59 ( 102.83 ) 113.60 ( 97.67 ) 126.19 ( 108.50 ) 119.04 ( 102.36 ) 132.78 ( 114.17 )
45.8 108.18 ( 93.01 ) 119.61 ( 102.85 ) 113.62 ( 97.70 ) 126.21 ( 108.52 ) 119.07 ( 102.38 ) 132.80 ( 114.18 )
45.9 108.20 ( 93.04 ) 119.64 ( 102.87 ) 113.65 ( 97.72 ) 126.23 ( 108.54 ) 119.10 ( 102.40 ) 132.82 ( 114.20 )
46.0 108.23 ( 93.06 ) 119.66 ( 102.89 ) 113.68 ( 97.75 ) 126.25 ( 108.56 ) 119.12 ( 102.43 ) 132.84 ( 114.22 )
46.1 108.26 ( 93.09 ) 119.68 ( 102.90 ) 113.71 ( 97.77 ) 126.27 ( 108.57 ) 119.15 ( 102.45 ) 132.86 ( 114.24 )
46.2 108.29 ( 93.11 ) 119.70 ( 102.92 ) 113.74 ( 97.80 ) 126.29 ( 108.59 ) 119.18 ( 102.48 ) 132.88 ( 114.26 )
46.3 108.32 ( 93.13 ) 119.72 ( 102.94 ) 113.76 ( 97.82 ) 126.31 ( 108.61 ) 119.21 ( 102.50 ) 132.90 ( 114.27 )
46.4 108.34 ( 93.16 ) 119.74 ( 102.96 ) 113.79 ( 97.84 ) 126.33 ( 108.63 ) 119.24 ( 102.52 ) 132.92 ( 114.29 )
46.5 108.37 ( 93.18 ) 119.76 ( 102.97 ) 113.82 ( 97.87 ) 126.35 ( 108.65 ) 119.26 ( 102.55 ) 132.94 ( 114.31 )
46.6 108.40 ( 93.21 ) 119.78 ( 102.99 ) 113.85 ( 97.89 ) 126.38 ( 108.66 ) 119.29 ( 102.57 ) 132.96 ( 114.33 )
46.7 108.43 ( 93.23 ) 119.80 ( 103.01 ) 113.88 ( 97.92 ) 126.40 ( 108.68 ) 119.32 ( 102.60 ) 132.98 ( 114.35 )
46.8 108.45 ( 93.25 ) 119.82 ( 103.03 ) 113.90 ( 97.94 ) 126.42 ( 108.70 ) 119.35 ( 102.62 ) 133.01 ( 114.36 )
46.9 108.48 ( 93.28 ) 119.84 ( 103.05 ) 113.93 ( 97.96 ) 126.44 ( 108.72 ) 119.38 ( 102.65 ) 133.03 ( 114.38 )
47.0 108.51 ( 93.30 ) 119.86 ( 103.06 ) 113.96 ( 97.99 ) 126.46 ( 108.73 ) 119.40 ( 102.67 ) 133.05 ( 114.40 )
47.1 108.54 ( 93.33 ) 119.88 ( 103.08 ) 113.99 ( 98.01 ) 126.48 ( 108.75 ) 119.43 ( 102.69 ) 133.07 ( 114.42 )
47.2 108.57 ( 93.35 ) 119.90 ( 103.10 ) 114.02 ( 98.04 ) 126.50 ( 108.77 ) 119.46 ( 102.72 ) 133.09 ( 114.44 )
47.3 108.59 ( 93.37 ) 119.93 ( 103.12 ) 114.04 ( 98.06 ) 126.52 ( 108.79 ) 119.49 ( 102.74 ) 133.11 ( 114.45 )
47.4 108.62 ( 93.40 ) 119.95 ( 103.13 ) 114.07 ( 98.08 ) 126.54 ( 108.81 ) 119.52 ( 102.77 ) 133.13 ( 114.47 )
47.5 108.65 ( 93.42 ) 119.97 ( 103.15 ) 114.10 ( 98.11 ) 126.56 ( 108.82 ) 119.55 ( 102.79 ) 133.15 ( 114.49 )
47.6 108.68 ( 93.45 ) 119.99 ( 103.17 ) 114.13 ( 98.13 ) 126.58 ( 108.84 ) 119.57 ( 102.81 ) 133.17 ( 114.51 )
47.7 108.71 ( 93.47 ) 120.01 ( 103.19 ) 114.16 ( 98.16 ) 126.60 ( 108.86 ) 119.60 ( 102.84 ) 133.19 ( 114.53 )
47.8 108.73 ( 93.49 ) 120.03 ( 103.21 ) 114.18 ( 98.18 ) 126.63 ( 108.88 ) 119.63 ( 102.86 ) 133.22 ( 114.54 )
47.9 108.76 ( 93.52 ) 120.05 ( 103.22 ) 114.21 ( 98.20 ) 126.65 ( 108.90 ) 119.66 ( 102.89 ) 133.24 ( 114.56 )
48.0 108.79 ( 93.54 ) 120.07 ( 103.24 ) 114.24 ( 98.23 ) 126.67 ( 108.91 ) 119.69 ( 102.91 ) 133.26 ( 114.58 )
48.1 108.82 ( 93.57 ) 120.09 ( 103.26 ) 114.27 ( 98.25 ) 126.69 ( 108.93 ) 119.71 ( 102.94 ) 133.28 ( 114.60 )
48.2 108.85 ( 93.59 ) 120.11 ( 103.28 ) 114.30 ( 98.28 ) 126.71 ( 108.95 ) 119.74 ( 102.96 ) 133.30 ( 114.62 )
48.3 108.87 ( 93.61 ) 120.13 ( 103.30 ) 114.32 ( 98.30 ) 126.73 ( 108.97 ) 119.77 ( 102.98 ) 133.32 ( 114.63 )
48.4 108.90 ( 93.64 ) 120.15 ( 103.31 ) 114.35 ( 98.33 ) 126.75 ( 108.99 ) 119.80 ( 103.01 ) 133.34 ( 114.65 )
48.5 108.93 ( 93.66 ) 120.17 ( 103.33 ) 114.38 ( 98.35 ) 126.77 ( 109.00 ) 119.83 ( 103.03 ) 133.36 ( 114.67 )
48.6 108.96 ( 93.69 ) 120.19 ( 103.35 ) 114.41 ( 98.37 ) 126.79 ( 109.02 ) 119.85 ( 103.06 ) 133.38 ( 114.69 )
48.7 108.98 ( 93.71 ) 120.22 ( 103.37 ) 114.44 ( 98.40 ) 126.81 ( 109.04 ) 119.88 ( 103.08 ) 133.40 ( 114.71 )
48.8 109.01 ( 93.73 ) 120.24 ( 103.38 ) 114.46 ( 98.42 ) 126.83 ( 109.06 ) 119.91 ( 103.10 ) 133.42 ( 114.72 )
48.9 109.04 ( 93.76 ) 120.26 ( 103.40 ) 114.49 ( 98.45 ) 126.85 ( 109.07 ) 119.94 ( 103.13 ) 133.45 ( 114.74 )
Table 26. Outdoor Unit Capacity (JTOR380~420VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (6)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-38FSXNS
JTOR380VAE(U,F,R)BS1 RAS-40FSXNS
JTOR400VAE(U,F,R)BS1 RAS-42FSXNS
JTOR420VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
49.0 109.07 ( 93.78 ) 120.28 ( 103.42 ) 114.52 ( 98.47 ) 126.88 ( 109.09 ) 119.97 ( 103.15 ) 133.47 ( 114.76 )
49.1 109.10 ( 93.81 ) 120.30 ( 103.44 ) 114.55 ( 98.49 ) 126.90 ( 109.11 ) 119.99 ( 103.18 ) 133.49 ( 114.78 )
49.2 109.12 ( 93.83 ) 120.32 ( 103.46 ) 114.58 ( 98.52 ) 126.92 ( 109.13 ) 120.02 ( 103.20 ) 133.51 ( 114.80 )
49.3 109.15 ( 93.85 ) 120.34 ( 103.47 ) 114.60 ( 98.54 ) 126.94 ( 109.15 ) 120.05 ( 103.23 ) 133.53 ( 114.81 )
49.4 109.18 ( 93.88 ) 120.36 ( 103.49 ) 114.63 ( 98.57 ) 126.96 ( 109.16 ) 120.08 ( 103.25 ) 133.55 ( 114.83 )
49.5 114.66 ( 98.59 ) 126.98 ( 109.18 ) 120.11 ( 103.27 ) 133.57 ( 114.85 )
49.6 114.69 ( 98.61 ) 127.00 ( 109.20 ) 120.14 ( 103.30 ) 133.59 ( 114.87 )
49.7 114.72 ( 98.64 ) 127.02 ( 109.22 ) 120.16 ( 103.32 ) 133.61 ( 114.89 )
49.8 114.74 ( 98.66 ) 127.04 ( 109.24 ) 120.19 ( 103.35 ) 133.63 ( 114.90 )
49.9 114.77 ( 98.69 ) 127.06 ( 109.25 ) 120.22 ( 103.37 ) 133.66 ( 114.92 )
50.0 114.80 ( 98.71 ) 127.08 ( 109.27 ) 120.25 ( 103.39 ) 133.68 ( 114.94 )
50.1 114.83 ( 98.73 ) 127.10 ( 109.29 ) 120.28 ( 103.42 ) 133.70 ( 114.96 )
50.2 114.86 ( 98.76 ) 127.13 ( 109.31 ) 120.30 ( 103.44 ) 133.72 ( 114.98 )
50.3 114.88 ( 98.78 ) 127.15 ( 109.33 ) 120.33 ( 103.47 ) 133.74 ( 114.99 )
50.4 114.91 ( 98.81 ) 127.17 ( 109.34 ) 120.36 ( 103.49 ) 133.76 ( 115.01 )
50.5 114.94 ( 98.83 ) 127.19 ( 109.36 ) 120.39 ( 103.52 ) 133.78 ( 115.03 )
50.6 114.97 ( 98.85 ) 127.21 ( 109.38 ) 120.42 ( 103.54 ) 133.80 ( 115.05 )
50.7 115.00 ( 98.88 ) 127.23 ( 109.40 ) 120.44 ( 103.56 ) 133.82 ( 115.07 )
50.8 115.02 ( 98.90 ) 127.25 ( 109.42 ) 120.47 ( 103.59 ) 133.84 ( 115.08 )
50.9 115.05 ( 98.93 ) 127.27 ( 109.43 ) 120.50 ( 103.61 ) 133.86 ( 115.10 )
51.0 115.08 ( 98.95 ) 127.29 ( 109.45 ) 120.53 ( 103.64 ) 133.89 ( 115.12 )
51.1 115.11 ( 98.98 ) 127.31 ( 109.47 ) 120.56 ( 103.66 ) 133.91 ( 115.14 )
51.2 115.14 ( 99.00 ) 127.33 ( 109.49 ) 120.58 ( 103.68 ) 133.93 ( 115.16 )
51.3 115.16 ( 99.02 ) 127.35 ( 109.50 ) 120.61 ( 103.71 ) 133.95 ( 115.18 )
51.4 115.19 ( 99.05 ) 127.38 ( 109.52 ) 120.64 ( 103.73 ) 133.97 ( 115.19 )
51.5 115.22 ( 99.07 ) 127.40 ( 109.54 ) 120.67 ( 103.76 ) 133.99 ( 115.21 )
51.6 115.25 ( 99.10 ) 127.42 ( 109.56 ) 120.70 ( 103.78 ) 134.01 ( 115.23 )
51.7 115.28 ( 99.12 ) 127.44 ( 109.58 ) 120.73 ( 103.81 ) 134.03 ( 115.25 )
51.8 115.30 ( 99.14 ) 127.46 ( 109.59 ) 120.75 ( 103.83 ) 134.05 ( 115.27 )
51.9 115.33 ( 99.17 ) 127.48 ( 109.61 ) 120.78 ( 103.85 ) 134.07 ( 115.28 )
52.0 115.36 ( 99.19 ) 127.50 ( 109.63 ) 120.81 ( 103.88 ) 134.10 ( 115.30 )
_
52.1 120.84 ( 103.90 ) 134.12 ( 115.32 )
52.2 120.87 ( 103.93 ) 134.14 ( 115.34 )
52.3 120.89 ( 103.95 ) 134.16 ( 115.36 )
52.4 120.92 ( 103.97 ) 134.18 ( 115.37 )
52.5 120.95 ( 104.00 ) 134.20 ( 115.39 )
52.6 120.98 ( 104.02 ) 134.22 ( 115.41 )
52.7 121.01 ( 104.05 ) 134.24 ( 115.43 )
52.8 121.03 ( 104.07 ) 134.26 ( 115.45 )
52.9 121.06 ( 104.09 ) 134.28 ( 115.46 )
53.0 121.09 ( 104.12 ) 134.30 ( 115.48 )
53.1 121.12 ( 104.14 ) 134.33 ( 115.50 )
53.2 121.15 ( 104.17 ) 134.35 ( 115.52 )
53.3 121.17 ( 104.19 ) 134.37 ( 115.54 )
_
53.4 121.20 ( 104.22 ) 134.39 ( 115.55 )
53.5 121.23 ( 104.24 ) 134.41 ( 115.57 )
53.6 121.26 ( 104.26 ) 134.43 ( 115.59 )
53.7 121.29 ( 104.29 ) 134.45 ( 115.61 )
53.8 121.32 ( 104.31 ) 134.47 ( 115.63 )
53.9 121.34 ( 104.34 ) 134.49 ( 115.64 )
54.0 121.37 ( 104.36 ) 134.51 ( 115.66 )
54.1 121.40 ( 104.38 ) 134.54 ( 115.68 )
54.2 121.43 ( 104.41 ) 134.56 ( 115.70 )
54.3 121.46 ( 104.43 ) 134.58 ( 115.72 )
54.4 121.48 ( 104.46 ) 134.60 ( 115.73 )
54.5 121.51 ( 104.48 ) 134.62 ( 115.75 )
54.6 121.54 ( 104.51 ) 134.64 ( 115.77 )
Table 27. Outdoor Unit Capacity (JTOR440~480VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (1)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-44FSXNS
JTOR440VAE(U,F,R)BS1 RAS-46FSXNS
JTOR460VAE(U,F,R)BS1 RAS-48FSXNS
JTOR480VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
22.0 61.00 ( 52.45 ) 70.00 ( 60.19 )
22.1 61.28 ( 52.69 ) 70.32 ( 60.46 )
22.2 61.55 ( 52.93 ) 70.64 ( 60.74 )
22.3 61.83 ( 53.17 ) 70.95 ( 61.01 )
22.4 62.11 ( 53.40 ) 71.27 ( 61.28 )
_
22.5 62.39 ( 53.64 ) 71.59 ( 61.56 )
22.6 62.66 ( 53.88 ) 71.91 ( 61.83 )
22.7 62.94 ( 54.12 ) 72.23 ( 62.10 )
22.8 63.22 ( 54.36 ) 72.55 ( 62.38 )
22.9 63.50 ( 54.60 ) 72.86 ( 62.65 )
_
23.0 63.77 ( 54.83 ) 73.18 ( 62.93 ) 64.00 ( 55.03 ) 72.50 ( 62.34 )
23.1 64.05 ( 55.07 ) 73.50 ( 63.20 ) 64.28 ( 55.27 ) 72.82 ( 62.61 )
23.2 64.33 ( 55.31 ) 73.82 ( 63.47 ) 64.56 ( 55.51 ) 73.13 ( 62.88 )
23.3 64.60 ( 55.55 ) 74.14 ( 63.75 ) 64.83 ( 55.75 ) 73.45 ( 63.15 )
23.4 64.88 ( 55.79 ) 74.45 ( 64.02 ) 65.11 ( 55.99 ) 73.76 ( 63.42 )
23.5 65.16 ( 56.03 ) 74.77 ( 64.29 ) 65.39 ( 56.23 ) 74.08 ( 63.69 )
23.6 65.44 ( 56.27 ) 75.09 ( 64.57 ) 65.67 ( 56.47 ) 74.39 ( 63.97 )
23.7 65.71 ( 56.50 ) 75.41 ( 64.84 ) 65.95 ( 56.70 ) 74.71 ( 64.24 )
23.8 65.99 ( 56.74 ) 75.73 ( 65.11 ) 66.23 ( 56.94 ) 75.02 ( 64.51 )
23.9 66.27 ( 56.98 ) 76.05 ( 65.39 ) 66.50 ( 57.18 ) 75.34 ( 64.78 )
24.0 66.55 ( 57.22 ) 76.36 ( 65.66 ) 66.78 ( 57.42 ) 75.65 ( 65.05 ) 68.00 ( 58.47 ) 75.00 ( 64.49 )
24.1 66.82 ( 57.46 ) 76.68 ( 65.93 ) 67.06 ( 57.66 ) 75.97 ( 65.32 ) 68.28 ( 58.71 ) 75.31 ( 64.76 )
24.2 67.10 ( 57.70 ) 77.00 ( 66.21 ) 67.34 ( 57.90 ) 76.28 ( 65.59 ) 68.57 ( 58.96 ) 75.62 ( 65.03 )
24.3 67.38 ( 57.93 ) 77.32 ( 66.48 ) 67.62 ( 58.14 ) 76.60 ( 65.86 ) 68.85 ( 59.20 ) 75.94 ( 65.29 )
24.4 67.65 ( 58.17 ) 77.64 ( 66.76 ) 67.90 ( 58.38 ) 76.91 ( 66.13 ) 69.13 ( 59.44 ) 76.25 ( 65.56 )
24.5 67.93 ( 58.41 ) 77.95 ( 67.03 ) 68.17 ( 58.62 ) 77.23 ( 66.40 ) 69.42 ( 59.69 ) 76.56 ( 65.83 )
24.6 68.21 ( 58.65 ) 78.27 ( 67.30 ) 68.45 ( 58.86 ) 77.54 ( 66.68 ) 69.70 ( 59.93 ) 76.87 ( 66.10 )
24.7 68.49 ( 58.89 ) 78.59 ( 67.58 ) 68.73 ( 59.10 ) 77.86 ( 66.95 ) 69.98 ( 60.17 ) 77.19 ( 66.37 )
24.8 68.76 ( 59.13 ) 78.91 ( 67.85 ) 69.01 ( 59.34 ) 78.17 ( 67.22 ) 70.27 ( 60.42 ) 77.50 ( 66.64 )
24.9 69.04 ( 59.36 ) 79.23 ( 68.12 ) 69.29 ( 59.58 ) 78.49 ( 67.49 ) 70.55 ( 60.66 ) 77.81 ( 66.91 )
25.0 69.32 ( 59.60 ) 79.55 ( 68.40 ) 69.57 ( 59.82 ) 78.80 ( 67.76 ) 70.83 ( 60.91 ) 78.12 ( 67.18 )
25.1 69.60 ( 59.84 ) 79.86 ( 68.67 ) 69.84 ( 60.05 ) 79.12 ( 68.03 ) 71.12 ( 61.15 ) 78.44 ( 67.44 )
25.2 69.87 ( 60.08 ) 80.18 ( 68.94 ) 70.12 ( 60.29 ) 79.43 ( 68.30 ) 71.40 ( 61.39 ) 78.75 ( 67.71 )
25.3 70.15 ( 60.32 ) 80.50 ( 69.22 ) 70.40 ( 60.53 ) 79.75 ( 68.57 ) 71.68 ( 61.64 ) 79.06 ( 67.98 )
25.4 70.43 ( 60.56 ) 80.82 ( 69.49 ) 70.68 ( 60.77 ) 80.07 ( 68.84 ) 71.97 ( 61.88 ) 79.37 ( 68.25 )
25.5 70.70 ( 60.79 ) 81.14 ( 69.76 ) 70.96 ( 61.01 ) 80.38 ( 69.11 ) 72.25 ( 62.12 ) 79.69 ( 68.52 )
25.6 70.98 ( 61.03 ) 81.45 ( 70.04 ) 71.23 ( 61.25 ) 80.70 ( 69.39 ) 72.53 ( 62.37 ) 80.00 ( 68.79 )
25.7 71.26 ( 61.27 ) 81.77 ( 70.31 ) 71.51 ( 61.49 ) 81.01 ( 69.66 ) 72.82 ( 62.61 ) 80.31 ( 69.06 )
25.8 71.54 ( 61.51 ) 82.09 ( 70.59 ) 71.79 ( 61.73 ) 81.33 ( 69.93 ) 73.10 ( 62.85 ) 80.62 ( 69.33 )
25.9 71.81 ( 61.75 ) 82.41 ( 70.86 ) 72.07 ( 61.97 ) 81.64 ( 70.20 ) 73.38 ( 63.10 ) 80.94 ( 69.59 )
26.0 72.09 ( 61.99 ) 82.73 ( 71.13 ) 72.35 ( 62.21 ) 81.96 ( 70.47 ) 73.67 ( 63.34 ) 81.25 ( 69.86 )
26.1 72.37 ( 62.23 ) 83.05 ( 71.41 ) 72.63 ( 62.45 ) 82.27 ( 70.74 ) 73.95 ( 63.59 ) 81.56 ( 70.13 )
26.2 72.65 ( 62.46 ) 83.36 ( 71.68 ) 72.90 ( 62.69 ) 82.59 ( 71.01 ) 74.23 ( 63.83 ) 81.87 ( 70.40 )
26.3 72.92 ( 62.70 ) 83.68 ( 71.95 ) 73.18 ( 62.93 ) 82.90 ( 71.28 ) 74.52 ( 64.07 ) 82.19 ( 70.67 )
26.4 73.20 ( 62.94 ) 84.00 ( 72.23 ) 73.46 ( 63.16 ) 83.22 ( 71.55 ) 74.80 ( 64.32 ) 82.50 ( 70.94 )
26.5 73.48 ( 63.18 ) 84.32 ( 72.50 ) 73.74 ( 63.40 ) 83.53 ( 71.83 ) 75.08 ( 64.56 ) 82.81 ( 71.21 )
26.6 73.75 ( 63.42 ) 84.64 ( 72.77 ) 74.02 ( 63.64 ) 83.85 ( 72.10 ) 75.37 ( 64.80 ) 83.12 ( 71.47 )
26.7 74.03 ( 63.66 ) 84.95 ( 73.05 ) 74.30 ( 63.88 ) 84.16 ( 72.37 ) 75.65 ( 65.05 ) 83.44 ( 71.74 )
26.8 74.31 ( 63.89 ) 85.27 ( 73.32 ) 74.57 ( 64.12 ) 84.48 ( 72.64 ) 75.93 ( 65.29 ) 83.75 ( 72.01 )
26.9 74.59 ( 64.13 ) 85.59 ( 73.59 ) 74.85 ( 64.36 ) 84.79 ( 72.91 ) 76.22 ( 65.53 ) 84.06 ( 72.28 )
27.0 74.86 ( 64.37 ) 85.91 ( 73.87 ) 75.13 ( 64.60 ) 85.11 ( 73.18 ) 76.50 ( 65.78 ) 84.37 ( 72.55 )
27.1 75.14 ( 64.61 ) 86.23 ( 74.14 ) 75.41 ( 64.84 ) 85.42 ( 73.45 ) 76.78 ( 66.02 ) 84.69 ( 72.82 )
27.2 75.42 ( 64.85 ) 86.55 ( 74.42 ) 75.69 ( 65.08 ) 85.74 ( 73.72 ) 77.07 ( 66.27 ) 85.00 ( 73.09 )
27.3 75.70 ( 65.09 ) 86.86 ( 74.69 ) 75.97 ( 65.32 ) 86.05 ( 73.99 ) 77.35 ( 66.51 ) 85.31 ( 73.36 )
27.4 75.97 ( 65.32 ) 87.18 ( 74.96 ) 76.24 ( 65.56 ) 86.37 ( 74.26 ) 77.63 ( 66.75 ) 85.62 ( 73.62 )
27.5 76.25 ( 65.56 ) 87.50 ( 75.24 ) 76.52 ( 65.80 ) 86.68 ( 74.54 ) 77.92 ( 67.00 ) 85.94 ( 73.89 )
27.6 76.53 ( 65.80 ) 87.82 ( 75.51 ) 76.80 ( 66.04 ) 87.00 ( 74.81 ) 78.20 ( 67.24 ) 86.25 ( 74.16 )
27.7 76.80 ( 66.04 ) 88.14 ( 75.78 ) 77.08 ( 66.28 ) 87.32 ( 75.08 ) 78.48 ( 67.48 ) 86.56 ( 74.43 )
27.8 77.08 ( 66.28 ) 88.45 ( 76.06 ) 77.36 ( 66.51 ) 87.63 ( 75.35 ) 78.77 ( 67.73 ) 86.88 ( 74.70 )
27.9 77.36 ( 66.52 ) 88.77 ( 76.33 ) 77.63 ( 66.75 ) 87.95 ( 75.62 ) 79.05 ( 67.97 ) 87.19 ( 74.97 )
Table 28. Outdoor Unit Capacity (JTOR440~480VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (2)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-44FSXNS
JTOR440VAE(U,F,R)BS1 RAS-46FSXNS
JTOR460VAE(U,F,R)BS1 RAS-48FSXNS
JTOR480VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
28.0 77.64 ( 66.76 ) 89.09 ( 76.60 ) 77.91 ( 66.99 ) 88.26 ( 75.89 ) 79.33 ( 68.21 ) 87.50 ( 75.24 )
28.1 77.91 ( 66.99 ) 89.41 ( 76.88 ) 78.19 ( 67.23 ) 88.58 ( 76.16 ) 79.62 ( 68.46 ) 87.81 ( 75.51 )
28.2 78.19 ( 67.23 ) 89.73 ( 77.15 ) 78.47 ( 67.47 ) 88.89 ( 76.43 ) 79.90 ( 68.70 ) 88.13 ( 75.77 )
28.3 78.47 ( 67.47 ) 90.05 ( 77.43 ) 78.75 ( 67.71 ) 89.21 ( 76.70 ) 80.18 ( 68.95 ) 88.44 ( 76.04 )
28.4 78.75 ( 67.71 ) 90.36 ( 77.70 ) 79.03 ( 67.95 ) 89.52 ( 76.97 ) 80.47 ( 69.19 ) 88.75 ( 76.31 )
28.5 79.02 ( 67.95 ) 90.68 ( 77.97 ) 79.30 ( 68.19 ) 89.84 ( 77.25 ) 80.75 ( 69.43 ) 89.06 ( 76.58 )
28.6 79.30 ( 68.19 ) 91.00 ( 78.25 ) 79.58 ( 68.43 ) 90.15 ( 77.52 ) 81.03 ( 69.68 ) 89.38 ( 76.85 )
28.7 79.58 ( 68.42 ) 91.32 ( 78.52 ) 79.86 ( 68.67 ) 90.47 ( 77.79 ) 81.32 ( 69.92 ) 89.69 ( 77.12 )
28.8 79.85 ( 68.66 ) 91.64 ( 78.79 ) 80.14 ( 68.91 ) 90.78 ( 78.06 ) 81.60 ( 70.16 ) 90.00 ( 77.39 )
28.9 80.13 ( 68.90 ) 91.95 ( 79.07 ) 80.42 ( 69.15 ) 91.10 ( 78.33 ) 81.88 ( 70.41 ) 90.31 ( 77.65 )
29.0 80.41 ( 69.14 ) 92.27 ( 79.34 ) 80.70 ( 69.39 ) 91.41 ( 78.60 ) 82.17 ( 70.65 ) 90.63 ( 77.92 )
29.1 80.69 ( 69.38 ) 92.59 ( 79.61 ) 80.97 ( 69.63 ) 91.73 ( 78.87 ) 82.45 ( 70.89 ) 90.94 ( 78.19 )
29.2 80.96 ( 69.62 ) 92.91 ( 79.89 ) 81.25 ( 69.86 ) 92.04 ( 79.14 ) 82.73 ( 71.14 ) 91.25 ( 78.46 )
29.3 81.24 ( 69.85 ) 93.23 ( 80.16 ) 81.53 ( 70.10 ) 92.36 ( 79.41 ) 83.02 ( 71.38 ) 91.56 ( 78.73 )
29.4 81.52 ( 70.09 ) 93.55 ( 80.43 ) 81.81 ( 70.34 ) 92.67 ( 79.69 ) 83.30 ( 71.63 ) 91.88 ( 79.00 )
29.5 81.80 ( 70.33 ) 93.86 ( 80.71 ) 82.09 ( 70.58 ) 92.99 ( 79.96 ) 83.58 ( 71.87 ) 92.19 ( 79.27 )
29.6 82.07 ( 70.57 ) 94.18 ( 80.98 ) 82.37 ( 70.82 ) 93.30 ( 80.23 ) 83.87 ( 72.11 ) 92.50 ( 79.54 )
29.7 82.35 ( 70.81 ) 94.50 ( 81.26 ) 82.64 ( 71.06 ) 93.62 ( 80.50 ) 84.15 ( 72.36 ) 92.81 ( 79.80 )
29.8 82.63 ( 71.05 ) 94.82 ( 81.53 ) 82.92 ( 71.30 ) 93.93 ( 80.77 ) 84.43 ( 72.60 ) 93.13 ( 80.07 )
29.9 82.90 ( 71.29 ) 95.14 ( 81.80 ) 83.20 ( 71.54 ) 94.25 ( 81.04 ) 84.72 ( 72.84 ) 93.44 ( 80.34 )
30.0 83.18 ( 71.52 ) 95.45 ( 82.08 ) 83.48 ( 71.78 ) 94.57 ( 81.31 ) 85.00 ( 73.09 ) 93.75 ( 80.61 )
30.1 83.46 ( 71.76 ) 95.77 ( 82.35 ) 83.76 ( 72.02 ) 94.88 ( 81.58 ) 85.28 ( 73.33 ) 94.06 ( 80.88 )
30.2 83.74 ( 72.00 ) 96.09 ( 82.62 ) 84.03 ( 72.26 ) 95.20 ( 81.85 ) 85.57 ( 73.57 ) 94.38 ( 81.15 )
30.3 84.01 ( 72.24 ) 96.41 ( 82.90 ) 84.31 ( 72.50 ) 95.51 ( 82.12 ) 85.85 ( 73.82 ) 94.69 ( 81.42 )
30.4 84.29 ( 72.48 ) 96.73 ( 83.17 ) 84.59 ( 72.74 ) 95.83 ( 82.40 ) 86.13 ( 74.06 ) 95.00 ( 81.69 )
30.5 84.57 ( 72.72 ) 97.05 ( 83.44 ) 84.87 ( 72.97 ) 96.14 ( 82.67 ) 86.42 ( 74.30 ) 95.31 ( 81.95 )
30.6 84.85 ( 72.95 ) 97.36 ( 83.72 ) 85.15 ( 73.21 ) 96.46 ( 82.94 ) 86.70 ( 74.55 ) 95.62 ( 82.22 )
30.7 85.12 ( 73.19 ) 97.68 ( 83.99 ) 85.43 ( 73.45 ) 96.77 ( 83.21 ) 86.98 ( 74.79 ) 95.94 ( 82.49 )
30.8 85.40 ( 73.43 ) 98.00 ( 84.26 ) 85.70 ( 73.69 ) 97.09 ( 83.48 ) 87.27 ( 75.04 ) 96.25 ( 82.76 )
30.9 85.68 ( 73.67 ) 98.32 ( 84.54 ) 85.98 ( 73.93 ) 97.40 ( 83.75 ) 87.55 ( 75.28 ) 96.56 ( 83.03 )
31.0 85.95 ( 73.91 ) 98.64 ( 84.81 ) 86.26 ( 74.17 ) 97.72 ( 84.02 ) 87.83 ( 75.52 ) 96.87 ( 83.30 )
31.1 86.23 ( 74.15 ) 98.95 ( 85.09 ) 86.54 ( 74.41 ) 98.03 ( 84.29 ) 88.12 ( 75.77 ) 97.19 ( 83.57 )
31.2 86.51 ( 74.38 ) 99.27 ( 85.36 ) 86.82 ( 74.65 ) 98.35 ( 84.56 ) 88.40 ( 76.01 ) 97.50 ( 83.83 )
31.3 86.79 ( 74.62 ) 99.59 ( 85.63 ) 87.10 ( 74.89 ) 98.66 ( 84.83 ) 88.68 ( 76.25 ) 97.81 ( 84.10 )
31.4 87.06 ( 74.86 ) 99.91 ( 85.91 ) 87.37 ( 75.13 ) 98.98 ( 85.11 ) 88.97 ( 76.50 ) 98.12 ( 84.37 )
31.5 87.34 ( 75.10 ) 100.23 ( 86.18 ) 87.65 ( 75.37 ) 99.29 ( 85.38 ) 89.25 ( 76.74 ) 98.44 ( 84.64 )
31.6 87.62 ( 75.34 ) 100.55 ( 86.45 ) 87.93 ( 75.61 ) 99.61 ( 85.65 ) 89.53 ( 76.98 ) 98.75 ( 84.91 )
31.7 87.90 ( 75.58 ) 100.86 ( 86.73 ) 88.21 ( 75.85 ) 99.92 ( 85.92 ) 89.82 ( 77.23 ) 99.06 ( 85.18 )
31.8 88.17 ( 75.81 ) 101.18 ( 87.00 ) 88.49 ( 76.09 ) 100.24 ( 86.19 ) 90.10 ( 77.47 ) 99.37 ( 85.45 )
31.9 88.45 ( 76.05 ) 101.50 ( 87.27 ) 88.77 ( 76.32 ) 100.55 ( 86.46 ) 90.38 ( 77.72 ) 99.69 ( 85.72 )
32.0 88.73 ( 76.29 ) 101.82 ( 87.55 ) 89.04 ( 76.56 ) 100.87 ( 86.73 ) 90.67 ( 77.96 ) 100.00 ( 85.98 )
32.1 89.00 ( 76.53 ) 102.14 ( 87.82 ) 89.32 ( 76.80 ) 101.18 ( 87.00 ) 90.95 ( 78.20 ) 100.31 ( 86.25 )
32.2 89.28 ( 76.77 ) 102.45 ( 88.10 ) 89.60 ( 77.04 ) 101.50 ( 87.27 ) 91.23 ( 78.45 ) 100.63 ( 86.52 )
32.3 89.56 ( 77.01 ) 102.77 ( 88.37 ) 89.88 ( 77.28 ) 101.82 ( 87.55 ) 91.52 ( 78.69 ) 100.94 ( 86.79 )
32.4 89.84 ( 77.25 ) 103.09 ( 88.64 ) 90.16 ( 77.52 ) 102.13 ( 87.82 ) 91.80 ( 78.93 ) 101.25 ( 87.06 )
32.5 90.11 ( 77.48 ) 103.41 ( 88.92 ) 90.43 ( 77.76 ) 102.45 ( 88.09 ) 92.08 ( 79.18 ) 101.56 ( 87.33 )
32.6 90.39 ( 77.72 ) 103.73 ( 89.19 ) 90.71 ( 78.00 ) 102.76 ( 88.36 ) 92.37 ( 79.42 ) 101.88 ( 87.60 )
32.7 90.67 ( 77.96 ) 104.05 ( 89.46 ) 90.99 ( 78.24 ) 103.08 ( 88.63 ) 92.65 ( 79.66 ) 102.19 ( 87.87 )
32.8 90.95 ( 78.20 ) 104.36 ( 89.74 ) 91.27 ( 78.48 ) 103.39 ( 88.90 ) 92.93 ( 79.91 ) 102.50 ( 88.13 )
32.9 91.22 ( 78.44 ) 104.68 ( 90.01 ) 91.55 ( 78.72 ) 103.71 ( 89.17 ) 93.22 ( 80.15 ) 102.81 ( 88.40 )
33.0 91.50 ( 78.68 ) 105.00 ( 90.28 ) 91.83 ( 78.96 ) 104.02 ( 89.44 ) 93.50 ( 80.40 ) 103.13 ( 88.67 )
33.1 91.78 ( 78.91 ) 105.32 ( 90.56 ) 92.10 ( 79.20 ) 104.34 ( 89.71 ) 93.78 ( 80.64 ) 103.44 ( 88.94 )
33.2 92.05 ( 79.15 ) 105.64 ( 90.83 ) 92.38 ( 79.43 ) 104.65 ( 89.98 ) 94.07 ( 80.88 ) 103.75 ( 89.21 )
33.3 92.33 ( 79.39 ) 105.95 ( 91.10 ) 92.66 ( 79.67 ) 104.97 ( 90.26 ) 94.35 ( 81.13 ) 104.06 ( 89.48 )
33.4 92.61 ( 79.63 ) 106.27 ( 91.38 ) 92.94 ( 79.91 ) 105.28 ( 90.53 ) 94.63 ( 81.37 ) 104.38 ( 89.75 )
33.5 92.89 ( 79.87 ) 106.59 ( 91.65 ) 93.22 ( 80.15 ) 105.60 ( 90.80 ) 94.92 ( 81.61 ) 104.69 ( 90.02 )
33.6 93.16 ( 80.11 ) 106.91 ( 91.93 ) 93.50 ( 80.39 ) 105.91 ( 91.07 ) 95.20 ( 81.86 ) 105.00 ( 90.28 )
33.7 93.44 ( 80.34 ) 107.23 ( 92.20 ) 93.77 ( 80.63 ) 106.23 ( 91.34 ) 95.48 ( 82.10 ) 105.31 ( 90.55 )
33.8 93.72 ( 80.58 ) 107.55 ( 92.47 ) 94.05 ( 80.87 ) 106.54 ( 91.61 ) 95.77 ( 82.34 ) 105.63 ( 90.82 )
33.9 94.00 ( 80.82 ) 107.86 ( 92.75 ) 94.33 ( 81.11 ) 106.86 ( 91.88 ) 96.05 ( 82.59 ) 105.94 ( 91.09 )
Table 29. Outdoor Unit Capacity (JTOR440~480VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (3)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-44FSXNS
JTOR440VAE(U,F,R)BS1 RAS-46FSXNS
JTOR460VAE(U,F,R)BS1 RAS-48FSXNS
JTOR480VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
34.0 94.27 ( 81.06 ) 108.18 ( 93.02 ) 94.61 ( 81.35 ) 107.17 ( 92.15 ) 96.33 ( 82.83 ) 106.25 ( 91.36 )
34.1 94.55 ( 81.30 ) 108.50 ( 93.29 ) 94.89 ( 81.59 ) 107.49 ( 92.42 ) 96.62 ( 83.08 ) 106.56 ( 91.63 )
34.2 94.83 ( 81.54 ) 108.82 ( 93.57 ) 95.17 ( 81.83 ) 107.80 ( 92.70 ) 96.90 ( 83.32 ) 106.88 ( 91.90 )
34.3 95.10 ( 81.78 ) 109.14 ( 93.84 ) 95.44 ( 82.07 ) 108.12 ( 92.97 ) 97.18 ( 83.56 ) 107.19 ( 92.16 )
34.4 95.38 ( 82.01 ) 109.45 ( 94.11 ) 95.72 ( 82.31 ) 108.43 ( 93.24 ) 97.47 ( 83.81 ) 107.50 ( 92.43 )
34.5 95.66 ( 82.25 ) 109.77 ( 94.39 ) 96.00 ( 82.55 ) 108.75 ( 93.51 ) 97.75 ( 84.05 ) 107.81 ( 92.70 )
34.6 95.94 ( 82.49 ) 110.09 ( 94.66 ) 96.28 ( 82.78 ) 109.07 ( 93.78 ) 98.03 ( 84.29 ) 108.13 ( 92.97 )
34.7 96.21 ( 82.73 ) 110.41 ( 94.93 ) 96.56 ( 83.02 ) 109.38 ( 94.05 ) 98.32 ( 84.54 ) 108.44 ( 93.24 )
34.8 96.49 ( 82.97 ) 110.73 ( 95.21 ) 96.83 ( 83.26 ) 109.70 ( 94.32 ) 98.60 ( 84.78 ) 108.75 ( 93.51 )
34.9 96.77 ( 83.21 ) 111.05 ( 95.48 ) 97.11 ( 83.50 ) 110.01 ( 94.59 ) 98.88 ( 85.02 ) 109.06 ( 93.78 )
35.0 97.05 ( 83.44 ) 111.36 ( 95.76 ) 97.39 ( 83.74 ) 110.33 ( 94.86 ) 99.17 ( 85.27 ) 109.38 ( 94.05 )
35.1 97.32 ( 83.68 ) 111.68 ( 96.03 ) 97.67 ( 83.98 ) 110.64 ( 95.13 ) 99.45 ( 85.51 ) 109.69 ( 94.31 )
35.2 97.60 ( 83.92 ) 112.00 ( 96.30 ) 97.95 ( 84.22 ) 110.96 ( 95.41 ) 99.73 ( 85.76 ) 110.00 ( 94.58 )
35.3 97.88 ( 84.16 ) 112.32 ( 96.58 ) 98.23 ( 84.46 ) 111.27 ( 95.68 ) 100.02 ( 86.00 ) 110.31 ( 94.85 )
35.4 98.15 ( 84.40 ) 112.64 ( 96.85 ) 98.50 ( 84.70 ) 111.59 ( 95.95 ) 100.30 ( 86.24 ) 110.63 ( 95.12 )
35.5 98.43 ( 84.64 ) 112.95 ( 97.12 ) 98.78 ( 84.94 ) 111.90 ( 96.22 ) 100.58 ( 86.49 ) 110.94 ( 95.39 )
35.6 98.71 ( 84.87 ) 113.27 ( 97.40 ) 99.06 ( 85.18 ) 112.22 ( 96.49 ) 100.87 ( 86.73 ) 111.25 ( 95.66 )
35.7 98.99 ( 85.11 ) 113.59 ( 97.67 ) 99.34 ( 85.42 ) 112.53 ( 96.76 ) 101.15 ( 86.97 ) 111.56 ( 95.93 )
35.8 99.26 ( 85.35 ) 113.91 ( 97.94 ) 99.62 ( 85.66 ) 112.85 ( 97.03 ) 101.43 ( 87.22 ) 111.88 ( 96.20 )
35.9 99.54 ( 85.59 ) 114.23 ( 98.22 ) 99.90 ( 85.89 ) 113.16 ( 97.30 ) 101.72 ( 87.46 ) 112.19 ( 96.46 )
36.0 99.82 ( 85.83 ) 114.55 ( 98.49 ) 100.17 ( 86.13 ) 113.48 ( 97.57 ) 102.00 ( 87.70 ) 112.50 ( 96.73 )
36.1 100.10 ( 86.07 ) 114.86 ( 98.76 ) 100.45 ( 86.37 ) 113.79 ( 97.84 ) 102.28 ( 87.95 ) 112.81 ( 97.00 )
36.2 100.37 ( 86.31 ) 115.18 ( 99.04 ) 100.73 ( 86.61 ) 114.11 ( 98.12 ) 102.57 ( 88.19 ) 113.13 ( 97.27 )
36.3 100.65 ( 86.54 ) 115.50 ( 99.31 ) 101.01 ( 86.85 ) 114.42 ( 98.39 ) 102.85 ( 88.44 ) 113.44 ( 97.54 )
36.4 100.93 ( 86.78 ) 115.82 ( 99.59 ) 101.29 ( 87.09 ) 114.74 ( 98.66 ) 103.13 ( 88.68 ) 113.75 ( 97.81 )
36.5 101.20 ( 87.02 ) 116.14 ( 99.86 ) 101.57 ( 87.33 ) 115.05 ( 98.93 ) 103.42 ( 88.92 ) 114.06 ( 98.08 )
36.6 101.48 ( 87.26 ) 116.45 ( 100.13 ) 101.84 ( 87.57 ) 115.37 ( 99.20 ) 103.70 ( 89.17 ) 114.38 ( 98.34 )
36.7 101.76 ( 87.50 ) 116.77 ( 100.41 ) 102.12 ( 87.81 ) 115.68 ( 99.47 ) 103.98 ( 89.41 ) 114.69 ( 98.61 )
36.8 102.04 ( 87.74 ) 117.09 ( 100.68 ) 102.40 ( 88.05 ) 116.00 ( 99.74 ) 104.27 ( 89.65 ) 115.00 ( 98.88 )
36.9 102.31 ( 87.97 ) 117.41 ( 100.95 ) 102.68 ( 88.29 ) 116.32 ( 100.01 ) 104.55 ( 89.90 ) 115.31 ( 99.15 )
37.0 102.59 ( 88.21 ) 117.73 ( 101.23 ) 102.96 ( 88.53 ) 116.63 ( 100.28 ) 104.83 ( 90.14 ) 115.63 ( 99.42 )
37.1 102.87 ( 88.45 ) 118.05 ( 101.50 ) 103.23 ( 88.77 ) 116.95 ( 100.56 ) 105.12 ( 90.38 ) 115.94 ( 99.69 )
37.2 103.15 ( 88.69 ) 118.36 ( 101.77 ) 103.51 ( 89.01 ) 117.26 ( 100.83 ) 105.40 ( 90.63 ) 116.25 ( 99.96 )
37.3 103.42 ( 88.93 ) 118.68 ( 102.05 ) 103.79 ( 89.24 ) 117.58 ( 101.10 ) 105.68 ( 90.87 ) 116.56 ( 100.23 )
37.4 103.70 ( 89.17 ) 119.00 ( 102.32 ) 104.07 ( 89.48 ) 117.89 ( 101.37 ) 105.97 ( 91.11 ) 116.88 ( 100.49 )
37.5 103.98 ( 89.40 ) 119.32 ( 102.60 ) 104.35 ( 89.72 ) 118.21 ( 101.64 ) 106.25 ( 91.36 ) 117.19 ( 100.76 )
37.6 104.25 ( 89.64 ) 119.64 ( 102.87 ) 104.63 ( 89.96 ) 118.52 ( 101.91 ) 106.53 ( 91.60 ) 117.50 ( 101.03 )
37.7 104.53 ( 89.88 ) 119.95 ( 103.14 ) 104.90 ( 90.20 ) 118.84 ( 102.18 ) 106.82 ( 91.85 ) 117.81 ( 101.30 )
37.8 104.81 ( 90.12 ) 120.27 ( 103.42 ) 105.18 ( 90.44 ) 119.15 ( 102.45 ) 107.10 ( 92.09 ) 118.13 ( 101.57 )
37.9 105.09 ( 90.36 ) 120.59 ( 103.69 ) 105.46 ( 90.68 ) 119.47 ( 102.72 ) 107.38 ( 92.33 ) 118.44 ( 101.84 )
38.0 105.36 ( 90.60 ) 120.91 ( 103.96 ) 105.74 ( 90.92 ) 119.78 ( 102.99 ) 107.67 ( 92.58 ) 118.75 ( 102.11 )
38.1 105.64 ( 90.83 ) 121.23 ( 104.24 ) 106.02 ( 91.16 ) 120.10 ( 103.27 ) 107.95 ( 92.82 ) 119.06 ( 102.38 )
38.2 105.92 ( 91.07 ) 121.55 ( 104.51 ) 106.30 ( 91.40 ) 120.41 ( 103.54 ) 108.23 ( 93.06 ) 119.38 ( 102.64 )
38.3 106.20 ( 91.31 ) 121.86 ( 104.78 ) 106.57 ( 91.64 ) 120.73 ( 103.81 ) 108.52 ( 93.31 ) 119.69 ( 102.91 )
38.4 106.47 ( 91.55 ) 122.18 ( 105.06 ) 106.85 ( 91.88 ) 121.04 ( 104.08 ) 108.80 ( 93.55 ) 120.00 ( 103.18 )
38.5 106.75 ( 91.79 ) 122.50 ( 105.33 ) 107.13 ( 92.12 ) 121.36 ( 104.35 ) 109.08 ( 93.79 ) 120.31 ( 103.45 )
38.6 107.03 ( 92.03 ) 122.82 ( 105.60 ) 107.41 ( 92.35 ) 121.67 ( 104.62 ) 109.37 ( 94.04 ) 120.63 ( 103.72 )
38.7 107.30 ( 92.27 ) 123.14 ( 105.88 ) 107.69 ( 92.59 ) 121.99 ( 104.89 ) 109.65 ( 94.28 ) 120.94 ( 103.99 )
38.8 107.58 ( 92.50 ) 123.45 ( 106.15 ) 107.97 ( 92.83 ) 122.30 ( 105.16 ) 109.93 ( 94.53 ) 121.25 ( 104.26 )
38.9 107.86 ( 92.74 ) 123.77 ( 106.43 ) 108.24 ( 93.07 ) 122.62 ( 105.43 ) 110.22 ( 94.77 ) 121.56 ( 104.52 )
39.0 108.14 ( 92.98 ) 124.09 ( 106.70 ) 108.52 ( 93.31 ) 122.93 ( 105.70 ) 110.50 ( 95.01 ) 121.88 ( 104.79 )
39.1 108.41 ( 93.22 ) 124.41 ( 106.97 ) 108.80 ( 93.55 ) 123.25 ( 105.98 ) 110.78 ( 95.26 ) 122.19 ( 105.06 )
39.2 108.69 ( 93.46 ) 124.73 ( 107.25 ) 109.08 ( 93.79 ) 123.57 ( 106.25 ) 111.07 ( 95.50 ) 122.50 ( 105.33 )
39.3 108.97 ( 93.70 ) 125.05 ( 107.52 ) 109.36 ( 94.03 ) 123.88 ( 106.52 ) 111.35 ( 95.74 ) 122.81 ( 105.60 )
39.4 109.25 ( 93.93 ) 125.36 ( 107.79 ) 109.63 ( 94.27 ) 124.20 ( 106.79 ) 111.63 ( 95.99 ) 123.13 ( 105.87 )
39.5 109.52 ( 94.17 ) 125.68 ( 108.07 ) 109.91 ( 94.51 ) 124.51 ( 107.06 ) 111.92 ( 96.23 ) 123.44 ( 106.14 )
39.6 109.80 ( 94.41 ) 126.00 ( 108.34 ) 110.19 ( 94.75 ) 124.83 ( 107.33 ) 112.20 ( 96.47 ) 123.75 ( 106.41 )
39.7 110.08 ( 94.65 ) 126.32 ( 108.61 ) 110.47 ( 94.99 ) 125.14 ( 107.60 ) 112.48 ( 96.72 ) 124.06 ( 106.67 )
39.8 110.35 ( 94.89 ) 126.64 ( 108.89 ) 110.75 ( 95.23 ) 125.46 ( 107.87 ) 112.77 ( 96.96 ) 124.38 ( 106.94 )
39.9 110.63 ( 95.13 ) 126.95 ( 109.16 ) 111.03 ( 95.47 ) 125.77 ( 108.14 ) 113.05 ( 97.21 ) 124.69 ( 107.21 )
Table 30. Outdoor Unit Capacity (JTOR440~480VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (4)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-44FSXNS
JTOR440VAE(U,F,R)BS1 RAS-46FSXNS
JTOR460VAE(U,F,R)BS1 RAS-48FSXNS
JTOR480VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
40.0 110.91 ( 95.36 ) 127.27 ( 109.43 ) 111.30 ( 95.70 ) 126.09 ( 108.42 ) 113.33 ( 97.45 ) 125.00 ( 107.48 )
40.1 111.19 ( 95.60 ) 127.59 ( 109.71 ) 111.58 ( 95.94 ) 126.40 ( 108.69 ) 113.62 ( 97.69 ) 125.31 ( 107.75 )
40.2 111.46 ( 95.84 ) 127.91 ( 109.98 ) 111.86 ( 96.18 ) 126.72 ( 108.96 ) 113.90 ( 97.94 ) 125.63 ( 108.02 )
40.3 111.74 ( 96.08 ) 128.23 ( 110.26 ) 112.14 ( 96.42 ) 127.03 ( 109.23 ) 114.18 ( 98.18 ) 125.94 ( 108.29 )
40.4 112.02 ( 96.32 ) 128.55 ( 110.53 ) 112.42 ( 96.66 ) 127.35 ( 109.50 ) 114.47 ( 98.42 ) 126.25 ( 108.56 )
40.5 112.30 ( 96.56 ) 128.86 ( 110.80 ) 112.70 ( 96.90 ) 127.66 ( 109.77 ) 114.75 ( 98.67 ) 126.56 ( 108.82 )
40.6 112.57 ( 96.80 ) 129.18 ( 111.08 ) 112.97 ( 97.14 ) 127.98 ( 110.04 ) 115.03 ( 98.91 ) 126.88 ( 109.09 )
40.7 112.85 ( 97.03 ) 129.50 ( 111.35 ) 113.25 ( 97.38 ) 128.29 ( 110.31 ) 115.32 ( 99.15 ) 127.19 ( 109.36 )
40.8 113.13 ( 97.27 ) 129.82 ( 111.62 ) 113.53 ( 97.62 ) 128.61 ( 110.58 ) 115.60 ( 99.40 ) 127.50 ( 109.63 )
40.9 113.40 ( 97.51 ) 130.14 ( 111.90 ) 113.81 ( 97.86 ) 128.92 ( 110.85 ) 115.88 ( 99.64 ) 127.81 ( 109.90 )
41.0 113.68 ( 97.75 ) 130.45 ( 112.17 ) 114.09 ( 98.10 ) 129.24 ( 111.13 ) 116.17 ( 99.89 ) 128.13 ( 110.17 )
41.1 113.96 ( 97.99 ) 130.77 ( 112.44 ) 114.37 ( 98.34 ) 129.55 ( 111.40 ) 116.45 ( 100.13 ) 128.44 ( 110.44 )
41.2 114.24 ( 98.23 ) 131.09 ( 112.72 ) 114.64 ( 98.58 ) 129.87 ( 111.67 ) 116.73 ( 100.37 ) 128.75 ( 110.71 )
41.3 114.51 ( 98.46 ) 131.41 ( 112.99 ) 114.92 ( 98.81 ) 130.18 ( 111.94 ) 117.02 ( 100.62 ) 129.06 ( 110.97 )
41.4 114.79 ( 98.70 ) 131.73 ( 113.27 ) 115.20 ( 99.05 ) 130.50 ( 112.21 ) 117.30 ( 100.86 ) 129.38 ( 111.24 )
41.5 115.07 ( 98.94 ) 132.05 ( 113.54 ) 115.48 ( 99.29 ) 130.82 ( 112.48 ) 117.58 ( 101.10 ) 129.69 ( 111.51 )
41.6 115.35 ( 99.18 ) 132.36 ( 113.81 ) 115.76 ( 99.53 ) 131.13 ( 112.75 ) 117.87 ( 101.35 ) 130.00 ( 111.78 )
41.7 115.62 ( 99.42 ) 132.68 ( 114.09 ) 116.03 ( 99.77 ) 131.45 ( 113.02 ) 118.15 ( 101.59 ) 130.31 ( 112.05 )
41.8 115.90 ( 99.66 ) 133.00 ( 114.36 ) 116.31 ( 100.01 ) 131.76 ( 113.29 ) 118.43 ( 101.83 ) 130.63 ( 112.32 )
41.9 116.18 ( 99.89 ) 133.32 ( 114.63 ) 116.59 ( 100.25 ) 132.08 ( 113.56 ) 118.72 ( 102.08 ) 130.94 ( 112.59 )
42.0 116.45 ( 100.13 ) 133.64 ( 114.91 ) 116.87 ( 100.49 ) 132.39 ( 113.84 ) 119.00 ( 102.32 ) 131.25 ( 112.85 )
42.1 116.73 ( 100.37 ) 133.95 ( 115.18 ) 117.15 ( 100.73 ) 132.71 ( 114.11 ) 119.28 ( 102.57 ) 131.56 ( 113.12 )
42.2 117.01 ( 100.61 ) 134.27 ( 115.45 ) 117.43 ( 100.97 ) 133.02 ( 114.38 ) 119.57 ( 102.81 ) 131.88 ( 113.39 )
42.3 117.29 ( 100.85 ) 134.59 ( 115.73 ) 117.70 ( 101.21 ) 133.34 ( 114.65 ) 119.85 ( 103.05 ) 132.19 ( 113.66 )
42.4 117.56 ( 101.09 ) 134.91 ( 116.00 ) 117.98 ( 101.45 ) 133.65 ( 114.92 ) 120.13 ( 103.30 ) 132.50 ( 113.93 )
42.5 117.84 ( 101.32 ) 135.23 ( 116.27 ) 118.26 ( 101.69 ) 133.97 ( 115.19 ) 120.42 ( 103.54 ) 132.81 ( 114.20 )
42.6 118.12 ( 101.56 ) 135.55 ( 116.55 ) 118.54 ( 101.93 ) 134.28 ( 115.46 ) 120.70 ( 103.78 ) 133.13 ( 114.47 )
42.7 118.40 ( 101.80 ) 135.86 ( 116.82 ) 118.82 ( 102.16 ) 134.60 ( 115.73 ) 120.98 ( 104.03 ) 133.44 ( 114.74 )
42.8 118.67 ( 102.04 ) 136.18 ( 117.10 ) 119.10 ( 102.40 ) 134.91 ( 116.00 ) 121.27 ( 104.27 ) 133.75 ( 115.00 )
42.9 118.95 ( 102.28 ) 136.50 ( 117.37 ) 119.37 ( 102.64 ) 135.23 ( 116.28 ) 121.55 ( 104.51 ) 134.06 ( 115.27 )
43.0 119.23 ( 102.52 ) 136.82 ( 117.64 ) 119.65 ( 102.88 ) 135.54 ( 116.55 ) 121.83 ( 104.76 ) 134.38 ( 115.54 )
43.1 119.50 ( 102.76 ) 137.14 ( 117.92 ) 119.93 ( 103.12 ) 135.86 ( 116.82 ) 122.12 ( 105.00 ) 134.69 ( 115.81 )
43.2 119.78 ( 102.99 ) 137.45 ( 118.19 ) 120.21 ( 103.36 ) 136.17 ( 117.09 ) 122.40 ( 105.25 ) 135.00 ( 116.08 )
43.3 120.06 ( 103.23 ) 137.77 ( 118.46 ) 120.49 ( 103.60 ) 136.49 ( 117.36 ) 122.68 ( 105.49 ) 135.31 ( 116.35 )
43.4 120.34 ( 103.47 ) 138.09 ( 118.74 ) 120.77 ( 103.84 ) 136.80 ( 117.63 ) 122.97 ( 105.73 ) 135.63 ( 116.62 )
43.5 120.61 ( 103.71 ) 138.41 ( 119.01 ) 121.04 ( 104.08 ) 137.12 ( 117.90 ) 123.25 ( 105.98 ) 135.94 ( 116.89 )
43.6 120.89 ( 103.95 ) 138.73 ( 119.28 ) 121.32 ( 104.32 ) 137.43 ( 118.17 ) 123.53 ( 106.22 ) 136.25 ( 117.15 )
43.7 121.17 ( 104.19 ) 139.05 ( 119.56 ) 121.60 ( 104.56 ) 137.75 ( 118.44 ) 123.82 ( 106.46 ) 136.56 ( 117.42 )
43.8 121.45 ( 104.42 ) 139.36 ( 119.83 ) 121.88 ( 104.80 ) 138.07 ( 118.71 ) 124.10 ( 106.71 ) 136.88 ( 117.69 )
43.9 121.72 ( 104.66 ) 139.68 ( 120.10 ) 122.16 ( 105.04 ) 138.38 ( 118.99 ) 124.38 ( 106.95 ) 137.19 ( 117.96 )
44.0 122.00 ( 104.90 ) 140.00 ( 120.38 ) 122.43 ( 105.27 ) 138.70 ( 119.26 ) 124.67 ( 107.19 ) 137.50 ( 118.23 )
44.1 122.03 ( 104.92 ) 140.02 ( 120.40 ) 122.71 ( 105.51 ) 139.01 ( 119.53 ) 124.95 ( 107.44 ) 137.81 ( 118.50 )
44.2 122.06 ( 104.95 ) 140.04 ( 120.41 ) 122.99 ( 105.75 ) 139.33 ( 119.80 ) 125.23 ( 107.68 ) 138.13 ( 118.77 )
44.3 122.08 ( 104.97 ) 140.06 ( 120.43 ) 123.27 ( 105.99 ) 139.64 ( 120.07 ) 125.52 ( 107.92 ) 138.44 ( 119.03 )
44.4 122.11 ( 105.00 ) 140.08 ( 120.45 ) 123.55 ( 106.23 ) 139.96 ( 120.34 ) 125.80 ( 108.17 ) 138.75 ( 119.30 )
44.5 122.14 ( 105.02 ) 140.11 ( 120.47 ) 123.83 ( 106.47 ) 140.27 ( 120.61 ) 126.08 ( 108.41 ) 139.06 ( 119.57 )
44.6 122.17 ( 105.04 ) 140.13 ( 120.49 ) 124.10 ( 106.71 ) 140.59 ( 120.88 ) 126.37 ( 108.66 ) 139.38 ( 119.84 )
44.7 122.19 ( 105.07 ) 140.15 ( 120.51 ) 124.38 ( 106.95 ) 140.90 ( 121.15 ) 126.65 ( 108.90 ) 139.69 ( 120.11 )
44.8 122.22 ( 105.09 ) 140.17 ( 120.52 ) 124.66 ( 107.19 ) 141.22 ( 121.43 ) 126.93 ( 109.14 ) 140.00 ( 120.38 )
44.9 122.25 ( 105.12 ) 140.19 ( 120.54 ) 124.94 ( 107.43 ) 141.53 ( 121.70 ) 127.22 ( 109.39 ) 140.31 ( 120.65 )
45.0 122.28 ( 105.14 ) 140.21 ( 120.56 ) 125.22 ( 107.67 ) 141.85 ( 121.97 ) 127.50 ( 109.63 ) 140.63 ( 120.92 )
45.1 122.31 ( 105.16 ) 140.23 ( 120.58 ) 125.50 ( 107.91 ) 142.16 ( 122.24 ) 127.78 ( 109.87 ) 140.94 ( 121.18 )
45.2 122.33 ( 105.19 ) 140.25 ( 120.60 ) 125.77 ( 108.15 ) 142.48 ( 122.51 ) 128.07 ( 110.12 ) 141.25 ( 121.45 )
45.3 122.36 ( 105.21 ) 140.28 ( 120.62 ) 126.05 ( 108.39 ) 142.79 ( 122.78 ) 128.35 ( 110.36 ) 141.56 ( 121.72 )
45.4 122.39 ( 105.23 ) 140.30 ( 120.63 ) 126.33 ( 108.62 ) 143.11 ( 123.05 ) 128.63 ( 110.60 ) 141.88 ( 121.99 )
45.5 122.42 ( 105.26 ) 140.32 ( 120.65 ) 126.61 ( 108.86 ) 143.42 ( 123.32 ) 128.92 ( 110.85 ) 142.19 ( 122.26 )
45.6 122.44 ( 105.28 ) 140.34 ( 120.67 ) 126.89 ( 109.10 ) 143.74 ( 123.59 ) 129.20 ( 111.09 ) 142.50 ( 122.53 )
45.7 122.47 ( 105.31 ) 140.36 ( 120.69 ) 127.17 ( 109.34 ) 144.05 ( 123.86 ) 129.48 ( 111.34 ) 142.81 ( 122.80 )
45.8 122.50 ( 105.33 ) 140.38 ( 120.71 ) 127.44 ( 109.58 ) 144.37 ( 124.14 ) 129.77 ( 111.58 ) 143.13 ( 123.07 )
45.9 122.53 ( 105.35 ) 140.40 ( 120.72 ) 127.72 ( 109.82 ) 144.68 ( 124.41 ) 130.05 ( 111.82 ) 143.44 ( 123.33 )
Table 31. Outdoor Unit Capacity (JTOR440~480VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (5)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-44FSXNS
JTOR440VAE(U,F,R)BS1 RAS-46FSXNS
JTOR460VAE(U,F,R)BS1 RAS-48FSXNS
JTOR480VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
46.0 122.55 ( 105.38 ) 140.42 ( 120.74 ) 128.00 ( 110.06 ) 145.00 ( 124.68 ) 130.33 ( 112.07 ) 143.75 ( 123.60 )
46.1 122.58 ( 105.40 ) 140.45 ( 120.76 ) 128.03 ( 110.08 ) 145.02 ( 124.70 ) 130.62 ( 112.31 ) 144.06 ( 123.87 )
46.2 122.61 ( 105.43 ) 140.47 ( 120.78 ) 128.06 ( 110.11 ) 145.04 ( 124.71 ) 130.90 ( 112.55 ) 144.38 ( 124.14 )
46.3 122.64 ( 105.45 ) 140.49 ( 120.80 ) 128.08 ( 110.13 ) 145.06 ( 124.73 ) 131.18 ( 112.80 ) 144.69 ( 124.41 )
46.4 122.67 ( 105.47 ) 140.51 ( 120.82 ) 128.11 ( 110.16 ) 145.08 ( 124.75 ) 131.47 ( 113.04 ) 145.00 ( 124.68 )
46.5 122.69 ( 105.50 ) 140.53 ( 120.83 ) 128.14 ( 110.18 ) 145.11 ( 124.77 ) 131.75 ( 113.28 ) 145.31 ( 124.95 )
46.6 122.72 ( 105.52 ) 140.55 ( 120.85 ) 128.17 ( 110.20 ) 145.13 ( 124.79 ) 132.03 ( 113.53 ) 145.63 ( 125.21 )
46.7 122.75 ( 105.54 ) 140.57 ( 120.87 ) 128.19 ( 110.23 ) 145.15 ( 124.80 ) 132.32 ( 113.77 ) 145.94 ( 125.48 )
46.8 122.78 ( 105.57 ) 140.59 ( 120.89 ) 128.22 ( 110.25 ) 145.17 ( 124.82 ) 132.60 ( 114.02 ) 146.25 ( 125.75 )
46.9 122.80 ( 105.59 ) 140.62 ( 120.91 ) 128.25 ( 110.28 ) 145.19 ( 124.84 ) 132.88 ( 114.26 ) 146.56 ( 126.02 )
47.0 122.83 ( 105.62 ) 140.64 ( 120.93 ) 128.28 ( 110.30 ) 145.21 ( 124.86 ) 133.17 ( 114.50 ) 146.88 ( 126.29 )
47.1 122.86 ( 105.64 ) 140.66 ( 120.94 ) 128.31 ( 110.32 ) 145.23 ( 124.88 ) 133.45 ( 114.75 ) 147.19 ( 126.56 )
47.2 122.89 ( 105.66 ) 140.68 ( 120.96 ) 128.33 ( 110.35 ) 145.25 ( 124.89 ) 133.73 ( 114.99 ) 147.50 ( 126.83 )
47.3 122.92 ( 105.69 ) 140.70 ( 120.98 ) 128.36 ( 110.37 ) 145.27 ( 124.91 ) 134.02 ( 115.23 ) 147.81 ( 127.10 )
47.4 122.94 ( 105.71 ) 140.72 ( 121.00 ) 128.39 ( 110.40 ) 145.29 ( 124.93 ) 134.30 ( 115.48 ) 148.13 ( 127.36 )
47.5 122.97 ( 105.74 ) 140.74 ( 121.02 ) 128.42 ( 110.42 ) 145.32 ( 124.95 ) 134.58 ( 115.72 ) 148.44 ( 127.63 )
47.6 123.00 ( 105.76 ) 140.76 ( 121.03 ) 128.45 ( 110.44 ) 145.34 ( 124.97 ) 134.87 ( 115.96 ) 148.75 ( 127.90 )
47.7 123.03 ( 105.78 ) 140.78 ( 121.05 ) 128.47 ( 110.47 ) 145.36 ( 124.98 ) 135.15 ( 116.21 ) 149.06 ( 128.17 )
47.8 123.05 ( 105.81 ) 140.81 ( 121.07 ) 128.50 ( 110.49 ) 145.38 ( 125.00 ) 135.43 ( 116.45 ) 149.38 ( 128.44 )
47.9 123.08 ( 105.83 ) 140.83 ( 121.09 ) 128.53 ( 110.51 ) 145.40 ( 125.02 ) 135.72 ( 116.70 ) 149.69 ( 128.71 )
48.0 123.11 ( 105.85 ) 140.85 ( 121.11 ) 128.56 ( 110.54 ) 145.42 ( 125.04 ) 136.00 ( 116.94 ) 150.00 ( 128.98 )
48.1 123.14 ( 105.88 ) 140.87 ( 121.13 ) 128.58 ( 110.56 ) 145.44 ( 125.06 ) 136.03 ( 116.96 ) 150.02 ( 128.99 )
48.2 123.16 ( 105.90 ) 140.89 ( 121.14 ) 128.61 ( 110.59 ) 145.46 ( 125.08 ) 136.06 ( 116.99 ) 150.04 ( 129.01 )
48.3 123.19 ( 105.93 ) 140.91 ( 121.16 ) 128.64 ( 110.61 ) 145.48 ( 125.09 ) 136.09 ( 117.01 ) 150.06 ( 129.03 )
48.4 123.22 ( 105.95 ) 140.93 ( 121.18 ) 128.67 ( 110.63 ) 145.50 ( 125.11 ) 136.11 ( 117.04 ) 150.08 ( 129.05 )
48.5 123.25 ( 105.97 ) 140.95 ( 121.20 ) 128.70 ( 110.66 ) 145.53 ( 125.13 ) 136.14 ( 117.06 ) 150.10 ( 129.07 )
48.6 123.28 ( 106.00 ) 140.98 ( 121.22 ) 128.72 ( 110.68 ) 145.55 ( 125.15 ) 136.17 ( 117.09 ) 150.13 ( 129.08 )
48.7 123.30 ( 106.02 ) 141.00 ( 121.24 ) 128.75 ( 110.71 ) 145.57 ( 125.17 ) 136.20 ( 117.11 ) 150.15 ( 129.10 )
48.8 123.33 ( 106.05 ) 141.02 ( 121.25 ) 128.78 ( 110.73 ) 145.59 ( 125.18 ) 136.23 ( 117.13 ) 150.17 ( 129.12 )
48.9 123.36 ( 106.07 ) 141.04 ( 121.27 ) 128.81 ( 110.75 ) 145.61 ( 125.20 ) 136.26 ( 117.16 ) 150.19 ( 129.14 )
49.0 123.39 ( 106.09 ) 141.06 ( 121.29 ) 128.83 ( 110.78 ) 145.63 ( 125.22 ) 136.28 ( 117.18 ) 150.21 ( 129.16 )
49.1 123.41 ( 106.12 ) 141.08 ( 121.31 ) 128.86 ( 110.80 ) 145.65 ( 125.24 ) 136.31 ( 117.21 ) 150.23 ( 129.17 )
49.2 123.44 ( 106.14 ) 141.10 ( 121.33 ) 128.89 ( 110.83 ) 145.67 ( 125.26 ) 136.34 ( 117.23 ) 150.25 ( 129.19 )
49.3 123.47 ( 106.16 ) 141.12 ( 121.35 ) 128.92 ( 110.85 ) 145.69 ( 125.27 ) 136.37 ( 117.26 ) 150.27 ( 129.21 )
49.4 123.50 ( 106.19 ) 141.15 ( 121.36 ) 128.95 ( 110.87 ) 145.71 ( 125.29 ) 136.40 ( 117.28 ) 150.29 ( 129.23 )
49.5 123.53 ( 106.21 ) 141.17 ( 121.38 ) 128.97 ( 110.90 ) 145.74 ( 125.31 ) 136.43 ( 117.30 ) 150.31 ( 129.25 )
49.6 123.55 ( 106.24 ) 141.19 ( 121.40 ) 129.00 ( 110.92 ) 145.76 ( 125.33 ) 136.45 ( 117.33 ) 150.33 ( 129.26 )
49.7 123.58 ( 106.26 ) 141.21 ( 121.42 ) 129.03 ( 110.95 ) 145.78 ( 125.35 ) 136.48 ( 117.35 ) 150.35 ( 129.28 )
49.8 123.61 ( 106.28 ) 141.23 ( 121.44 ) 129.06 ( 110.97 ) 145.80 ( 125.36 ) 136.51 ( 117.38 ) 150.38 ( 129.30 )
49.9 123.64 ( 106.31 ) 141.25 ( 121.45 ) 129.09 ( 110.99 ) 145.82 ( 125.38 ) 136.54 ( 117.40 ) 150.40 ( 129.32 )
50.0 123.66 ( 106.33 ) 141.27 ( 121.47 ) 129.11 ( 111.02 ) 145.84 ( 125.40 ) 136.57 ( 117.43 ) 150.42 ( 129.34 )
50.1 123.69 ( 106.36 ) 141.29 ( 121.49 ) 129.14 ( 111.04 ) 145.86 ( 125.42 ) 136.60 ( 117.45 ) 150.44 ( 129.35 )
50.2 123.72 ( 106.38 ) 141.32 ( 121.51 ) 129.17 ( 111.07 ) 145.88 ( 125.44 ) 136.62 ( 117.47 ) 150.46 ( 129.37 )
50.3 123.75 ( 106.40 ) 141.34 ( 121.53 ) 129.20 ( 111.09 ) 145.90 ( 125.45 ) 136.65 ( 117.50 ) 150.48 ( 129.39 )
50.4 123.77 ( 106.43 ) 141.36 ( 121.55 ) 129.22 ( 111.11 ) 145.92 ( 125.47 ) 136.68 ( 117.52 ) 150.50 ( 129.41 )
50.5 123.80 ( 106.45 ) 141.38 ( 121.56 ) 129.25 ( 111.14 ) 145.95 ( 125.49 ) 136.71 ( 117.55 ) 150.52 ( 129.42 )
50.6 123.83 ( 106.47 ) 141.40 ( 121.58 ) 129.28 ( 111.16 ) 145.97 ( 125.51 ) 136.74 ( 117.57 ) 150.54 ( 129.44 )
50.7 123.86 ( 106.50 ) 141.42 ( 121.60 ) 129.31 ( 111.18 ) 145.99 ( 125.53 ) 136.77 ( 117.60 ) 150.56 ( 129.46 )
50.8 123.89 ( 106.52 ) 141.44 ( 121.62 ) 129.34 ( 111.21 ) 146.01 ( 125.54 ) 136.79 ( 117.62 ) 150.58 ( 129.48 )
50.9 123.91 ( 106.55 ) 141.46 ( 121.64 ) 129.36 ( 111.23 ) 146.03 ( 125.56 ) 136.82 ( 117.65 ) 150.60 ( 129.50 )
51.0 123.94 ( 106.57 ) 141.48 ( 121.66 ) 129.39 ( 111.26 ) 146.05 ( 125.58 ) 136.85 ( 117.67 ) 150.63 ( 129.51 )
51.1 123.97 ( 106.59 ) 141.51 ( 121.67 ) 129.42 ( 111.28 ) 146.07 ( 125.60 ) 136.88 ( 117.69 ) 150.65 ( 129.53 )
51.2 124.00 ( 106.62 ) 141.53 ( 121.69 ) 129.45 ( 111.30 ) 146.09 ( 125.62 ) 136.91 ( 117.72 ) 150.67 ( 129.55 )
51.3 124.02 ( 106.64 ) 141.55 ( 121.71 ) 129.47 ( 111.33 ) 146.11 ( 125.64 ) 136.94 ( 117.74 ) 150.69 ( 129.57 )
51.4 124.05 ( 106.67 ) 141.57 ( 121.73 ) 129.50 ( 111.35 ) 146.13 ( 125.65 ) 136.96 ( 117.77 ) 150.71 ( 129.59 )
51.5 124.08 ( 106.69 ) 141.59 ( 121.75 ) 129.53 ( 111.38 ) 146.16 ( 125.67 ) 136.99 ( 117.79 ) 150.73 ( 129.60 )
51.6 124.11 ( 106.71 ) 141.61 ( 121.76 ) 129.56 ( 111.40 ) 146.18 ( 125.69 ) 137.02 ( 117.82 ) 150.75 ( 129.62 )
51.7 124.14 ( 106.74 ) 141.63 ( 121.78 ) 129.59 ( 111.42 ) 146.20 ( 125.71 ) 137.05 ( 117.84 ) 150.77 ( 129.64 )
51.8 124.16 ( 106.76 ) 141.65 ( 121.80 ) 129.61 ( 111.45 ) 146.22 ( 125.73 ) 137.08 ( 117.86 ) 150.79 ( 129.66 )
51.9 124.19 ( 106.78 ) 141.68 ( 121.82 ) 129.64 ( 111.47 ) 146.24 ( 125.74 ) 137.11 ( 117.89 ) 150.81 ( 129.68 )
Table 32. Outdoor Unit Capacity (JTOR440~480VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (6)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-44FSXNS
JTOR440VAE(U,F,R)BS1 RAS-46FSXNS
JTOR460VAE(U,F,R)BS1 RAS-48FSXNS
JTOR480VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
52.0 124.22 ( 106.81 ) 141.70 ( 121.84 ) 129.67 ( 111.50 ) 146.26 ( 125.76 ) 137.13 ( 117.91 ) 150.83 ( 129.69 )
52.1 124.25 ( 106.83 ) 141.72 ( 121.86 ) 129.70 ( 111.52 ) 146.28 ( 125.78 ) 137.16 ( 117.94 ) 150.85 ( 129.71 )
52.2 124.27 ( 106.86 ) 141.74 ( 121.87 ) 129.73 ( 111.54 ) 146.30 ( 125.80 ) 137.19 ( 117.96 ) 150.88 ( 129.73 )
52.3 124.30 ( 106.88 ) 141.76 ( 121.89 ) 129.75 ( 111.57 ) 146.32 ( 125.82 ) 137.22 ( 117.99 ) 150.90 ( 129.75 )
52.4 124.33 ( 106.90 ) 141.78 ( 121.91 ) 129.78 ( 111.59 ) 146.34 ( 125.83 ) 137.25 ( 118.01 ) 150.92 ( 129.76 )
52.5 124.36 ( 106.93 ) 141.80 ( 121.93 ) 129.81 ( 111.62 ) 146.37 ( 125.85 ) 137.28 ( 118.04 ) 150.94 ( 129.78 )
52.6 124.38 ( 106.95 ) 141.82 ( 121.95 ) 129.84 ( 111.64 ) 146.39 ( 125.87 ) 137.30 ( 118.06 ) 150.96 ( 129.80 )
52.7 124.41 ( 106.98 ) 141.85 ( 121.97 ) 129.86 ( 111.66 ) 146.41 ( 125.89 ) 137.33 ( 118.08 ) 150.98 ( 129.82 )
52.8 124.44 ( 107.00 ) 141.87 ( 121.98 ) 129.89 ( 111.69 ) 146.43 ( 125.91 ) 137.36 ( 118.11 ) 151.00 ( 129.84 )
52.9 124.47 ( 107.02 ) 141.89 ( 122.00 ) 129.92 ( 111.71 ) 146.45 ( 125.92 ) 137.39 ( 118.13 ) 151.02 ( 129.85 )
53.0 124.50 ( 107.05 ) 141.91 ( 122.02 ) 129.95 ( 111.74 ) 146.47 ( 125.94 ) 137.42 ( 118.16 ) 151.04 ( 129.87 )
53.1 124.52 ( 107.07 ) 141.93 ( 122.04 ) 129.98 ( 111.76 ) 146.49 ( 125.96 ) 137.45 ( 118.18 ) 151.06 ( 129.89 )
53.2 124.55 ( 107.09 ) 141.95 ( 122.06 ) 130.00 ( 111.78 ) 146.51 ( 125.98 ) 137.47 ( 118.21 ) 151.08 ( 129.91 )
53.3 124.58 ( 107.12 ) 141.97 ( 122.07 ) 130.03 ( 111.81 ) 146.53 ( 126.00 ) 137.50 ( 118.23 ) 151.10 ( 129.93 )
53.4 124.61 ( 107.14 ) 141.99 ( 122.09 ) 130.06 ( 111.83 ) 146.56 ( 126.01 ) 137.53 ( 118.25 ) 151.13 ( 129.94 )
53.5 124.63 ( 107.17 ) 142.02 ( 122.11 ) 130.09 ( 111.85 ) 146.58 ( 126.03 ) 137.56 ( 118.28 ) 151.15 ( 129.96 )
53.6 124.66 ( 107.19 ) 142.04 ( 122.13 ) 130.11 ( 111.88 ) 146.60 ( 126.05 ) 137.59 ( 118.30 ) 151.17 ( 129.98 )
53.7 124.69 ( 107.21 ) 142.06 ( 122.15 ) 130.14 ( 111.90 ) 146.62 ( 126.07 ) 137.62 ( 118.33 ) 151.19 ( 130.00 )
53.8 124.72 ( 107.24 ) 142.08 ( 122.17 ) 130.17 ( 111.93 ) 146.64 ( 126.09 ) 137.64 ( 118.35 ) 151.21 ( 130.02 )
53.9 124.75 ( 107.26 ) 142.10 ( 122.18 ) 130.20 ( 111.95 ) 146.66 ( 126.11 ) 137.67 ( 118.38 ) 151.23 ( 130.03 )
54.0 124.77 ( 107.29 ) 142.12 ( 122.20 ) 130.23 ( 111.97 ) 146.68 ( 126.12 ) 137.70 ( 118.40 ) 151.25 ( 130.05 )
54.1 124.80 ( 107.31 ) 142.14 ( 122.22 ) 130.25 ( 112.00 ) 146.70 ( 126.14 ) 137.73 ( 118.43 ) 151.27 ( 130.07 )
54.2 124.83 ( 107.33 ) 142.16 ( 122.24 ) 130.28 ( 112.02 ) 146.72 ( 126.16 ) 137.76 ( 118.45 ) 151.29 ( 130.09 )
54.3 124.86 ( 107.36 ) 142.18 ( 122.26 ) 130.31 ( 112.05 ) 146.74 ( 126.18 ) 137.79 ( 118.47 ) 151.31 ( 130.11 )
54.4 124.88 ( 107.38 ) 142.21 ( 122.28 ) 130.34 ( 112.07 ) 146.77 ( 126.20 ) 137.81 ( 118.50 ) 151.33 ( 130.12 )
54.5 124.91 ( 107.40 ) 142.23 ( 122.29 ) 130.37 ( 112.09 ) 146.79 ( 126.21 ) 137.84 ( 118.52 ) 151.35 ( 130.14 )
54.6 124.94 ( 107.43 ) 142.25 ( 122.31 ) 130.39 ( 112.12 ) 146.81 ( 126.23 ) 137.87 ( 118.55 ) 151.38 ( 130.16 )
54.7 124.97 ( 107.45 ) 142.27 ( 122.33 ) 130.42 ( 112.14 ) 146.83 ( 126.25 ) 137.90 ( 118.57 ) 151.40 ( 130.18 )
54.8 124.99 ( 107.48 ) 142.29 ( 122.35 ) 130.45 ( 112.17 ) 146.85 ( 126.27 ) 137.93 ( 118.60 ) 151.42 ( 130.19 )
54.9 125.02 ( 107.50 ) 142.31 ( 122.37 ) 130.48 ( 112.19 ) 146.87 ( 126.29 ) 137.96 ( 118.62 ) 151.44 ( 130.21 )
55.0 125.05 ( 107.52 ) 142.33 ( 122.38 ) 130.50 ( 112.21 ) 146.89 ( 126.30 ) 137.98 ( 118.64 ) 151.46 ( 130.23 )
55.1 125.08 ( 107.55 ) 142.35 ( 122.40 ) 130.53 ( 112.24 ) 146.91 ( 126.32 ) 138.01 ( 118.67 ) 151.48 ( 130.25 )
55.2 125.11 ( 107.57 ) 142.38 ( 122.42 ) 130.56 ( 112.26 ) 146.93 ( 126.34 ) 138.04 ( 118.69 ) 151.50 ( 130.27 )
55.3 125.13 ( 107.60 ) 142.40 ( 122.44 ) 130.59 ( 112.29 ) 146.95 ( 126.36 ) 138.07 ( 118.72 ) 151.52 ( 130.28 )
55.4 125.16 ( 107.62 ) 142.42 ( 122.46 ) 130.62 ( 112.31 ) 146.98 ( 126.38 ) 138.10 ( 118.74 ) 151.54 ( 130.30 )
55.5 125.19 ( 107.64 ) 142.44 ( 122.48 ) 130.64 ( 112.33 ) 147.00 ( 126.39 ) 138.13 ( 118.77 ) 151.56 ( 130.32 )
55.6 125.22 ( 107.67 ) 142.46 ( 122.49 ) 130.67 ( 112.36 ) 147.02 ( 126.41 ) 138.15 ( 118.79 ) 151.58 ( 130.34 )
55.7 125.24 ( 107.69 ) 142.48 ( 122.51 ) 130.70 ( 112.38 ) 147.04 ( 126.43 ) 138.18 ( 118.81 ) 151.60 ( 130.36 )
55.8 125.27 ( 107.71 ) 142.50 ( 122.53 ) 130.73 ( 112.40 ) 147.06 ( 126.45 ) 138.21 ( 118.84 ) 151.63 ( 130.37 )
55.9 125.30 ( 107.74 ) 142.52 ( 122.55 ) 130.75 ( 112.43 ) 147.08 ( 126.47 ) 138.24 ( 118.86 ) 151.65 ( 130.39 )
56.0 125.33 ( 107.76 ) 142.55 ( 122.57 ) 130.78 ( 112.45 ) 147.10 ( 126.48 ) 138.27 ( 118.89 ) 151.67 ( 130.41 )
56.1 125.36 ( 107.79 ) 142.57 ( 122.59 ) 130.81 ( 112.48 ) 147.12 ( 126.50 ) 138.30 ( 118.91 ) 151.69 ( 130.43 )
56.2 125.38 ( 107.81 ) 142.59 ( 122.60 ) 130.84 ( 112.50 ) 147.14 ( 126.52 ) 138.32 ( 118.94 ) 151.71 ( 130.45 )
56.3 125.41 ( 107.83 ) 142.61 ( 122.62 ) 130.87 ( 112.52 ) 147.16 ( 126.54 ) 138.35 ( 118.96 ) 151.73 ( 130.46 )
56.4 125.44 ( 107.86 ) 142.63 ( 122.64 ) 130.89 ( 112.55 ) 147.19 ( 126.56 ) 138.38 ( 118.99 ) 151.75 ( 130.48 )
56.5 125.47 ( 107.88 ) 142.65 ( 122.66 ) 130.92 ( 112.57 ) 147.21 ( 126.57 ) 138.41 ( 119.01 ) 151.77 ( 130.50 )
56.6 125.49 ( 107.91 ) 142.67 ( 122.68 ) 130.95 ( 112.60 ) 147.23 ( 126.59 ) 138.44 ( 119.03 ) 151.79 ( 130.52 )
56.7 125.52 ( 107.93 ) 142.69 ( 122.69 ) 130.98 ( 112.62 ) 147.25 ( 126.61 ) 138.47 ( 119.06 ) 151.81 ( 130.54 )
56.8 125.55 ( 107.95 ) 142.72 ( 122.71 ) 131.01 ( 112.64 ) 147.27 ( 126.63 ) 138.49 ( 119.08 ) 151.83 ( 130.55 )
56.9 125.58 ( 107.98 ) 142.74 ( 122.73 ) 131.03 ( 112.67 ) 147.29 ( 126.65 ) 138.52 ( 119.11 ) 151.85 ( 130.57 )
57.0 125.60 ( 108.00 ) 142.76 ( 122.75 ) 131.06 ( 112.69 ) 147.31 ( 126.67 ) 138.55 ( 119.13 ) 151.88 ( 130.59 )
57.1 125.63 ( 108.02 ) 142.78 ( 122.77 ) 131.09 ( 112.72 ) 147.33 ( 126.68 ) 138.58 ( 119.16 ) 151.90 ( 130.61 )
57.2 125.66 ( 108.05 ) 142.80 ( 122.79 ) 131.12 ( 112.74 ) 147.35 ( 126.70 ) 138.61 ( 119.18 ) 151.92 ( 130.62 )
57.3 131.14 ( 112.76 ) 147.37 ( 126.72 ) 138.64 ( 119.20 ) 151.94 ( 130.64 )
57.4 131.17 ( 112.79 ) 147.40 ( 126.74 ) 138.66 ( 119.23 ) 151.96 ( 130.66 )
57.5 131.20 ( 112.81 ) 147.42 ( 126.76 ) 138.69 ( 119.25 ) 151.98 ( 130.68 )
57.6 _ 131.23 ( 112.84 ) 147.44 ( 126.77 ) 138.72 ( 119.28 ) 152.00 ( 130.70 )
57.7 131.26 ( 112.86 ) 147.46 ( 126.79 ) 138.75 ( 119.30 ) 152.02 ( 130.71 )
57.8 131.28 ( 112.88 ) 147.48 ( 126.81 ) 138.78 ( 119.33 ) 152.04 ( 130.73 )
57.9 131.31 ( 112.91 ) 147.50 ( 126.83 ) 138.81 ( 119.35 ) 152.06 ( 130.75 )
Table 33. Outdoor Unit Capacity (JTOR440~480VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (7)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-44FSXNS
JTOR440VAE(U,F,R)BS1 RAS-46FSXNS
JTOR460VAE(U,F,R)BS1 RAS-48FSXNS
JTOR480VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
58.0 131.34 ( 112.93 ) 147.52 ( 126.85 ) 138.83 ( 119.38 ) 152.08 ( 130.77 )
58.1 131.37 ( 112.96 ) 147.54 ( 126.86 ) 138.86 ( 119.40 ) 152.10 ( 130.79 )
58.2 131.39 ( 112.98 ) 147.56 ( 126.88 ) 138.89 ( 119.42 ) 152.13 ( 130.80 )
58.3 131.42 ( 113.00 ) 147.58 ( 126.90 ) 138.92 ( 119.45 ) 152.15 ( 130.82 )
58.4 131.45 ( 113.03 ) 147.61 ( 126.92 ) 138.95 ( 119.47 ) 152.17 ( 130.84 )
58.5 131.48 ( 113.05 ) 147.63 ( 126.94 ) 138.98 ( 119.50 ) 152.19 ( 130.86 )
58.6 131.51 ( 113.07 ) 147.65 ( 126.95 ) 139.00 ( 119.52 ) 152.21 ( 130.88 )
58.7 131.53 ( 113.10 ) 147.67 ( 126.97 ) 139.03 ( 119.55 ) 152.23 ( 130.89 )
58.8 131.56 ( 113.12 ) 147.69 ( 126.99 ) 139.06 ( 119.57 ) 152.25 ( 130.91 )
58.9 131.59 ( 113.15 ) 147.71 ( 127.01 ) 139.09 ( 119.59 ) 152.27 ( 130.93 )
59.0 131.62 ( 113.17 ) 147.73 ( 127.03 ) 139.12 ( 119.62 ) 152.29 ( 130.95 )
59.1 131.65 ( 113.19 ) 147.75 ( 127.04 ) 139.15 ( 119.64 ) 152.31 ( 130.97 )
59.2 131.67 ( 113.22 ) 147.77 ( 127.06 ) 139.17 ( 119.67 ) 152.33 ( 130.98 )
59.3 131.70 ( 113.24 ) 147.79 ( 127.08 ) 139.20 ( 119.69 ) 152.35 ( 131.00 )
59.4 131.73 ( 113.27 ) 147.82 ( 127.10 ) 139.23 ( 119.72 ) 152.38 ( 131.02 )
59.5 131.76 ( 113.29 ) 147.84 ( 127.12 ) 139.26 ( 119.74 ) 152.40 ( 131.04 )
59.6 131.78 ( 113.31 ) 147.86 ( 127.13 ) 139.29 ( 119.76 ) 152.42 ( 131.05 )
59.7 131.81 ( 113.34 ) 147.88 ( 127.15 ) 139.32 ( 119.79 ) 152.44 ( 131.07 )
59.8 131.84 ( 113.36 ) 147.90 ( 127.17 ) 139.34 ( 119.81 ) 152.46 ( 131.09 )
59.9 139.37 ( 119.84 ) 152.48 ( 131.11 )
60.0 139.40 ( 119.86 ) 152.50 ( 131.13 )
60.1 139.43 ( 119.89 ) 152.52 ( 131.14 )
60.2 _ 139.46 ( 119.91 ) 152.54 ( 131.16 )
60.3 139.49 ( 119.94 ) 152.56 ( 131.18 )
60.4 139.51 ( 119.96 ) 152.58 ( 131.20 )
60.5 139.54 ( 119.98 ) 152.60 ( 131.22 )
60.6 139.57 ( 120.01 ) 152.63 ( 131.23 )
60.7 139.60 ( 120.03 ) 152.65 ( 131.25 )
60.8 139.63 ( 120.06 ) 152.67 ( 131.27 )
60.9 139.66 ( 120.08 ) 152.69 ( 131.29 )
61.0 139.68 ( 120.11 ) 152.71 ( 131.31 )
61.1 139.71 ( 120.13 ) 152.73 ( 131.32 )
_
61.2 139.74 ( 120.15 ) 152.75 ( 131.34 )
61.3 139.77 ( 120.18 ) 152.77 ( 131.36 )
61.4 139.80 ( 120.20 ) 152.79 ( 131.38 )
61.5 139.83 ( 120.23 ) 152.81 ( 131.40 )
61.6 139.85 ( 120.25 ) 152.83 ( 131.41 )
61.7 139.88 ( 120.28 ) 152.85 ( 131.43 )
61.8 139.91 ( 120.30 ) 152.88 ( 131.45 )
61.9 139.94 ( 120.33 ) 152.90 ( 131.47 )
62.0 139.97 ( 120.35 ) 152.92 ( 131.48 )
62.1 140.00 ( 120.37 ) 152.94 ( 131.50 )
62.2 140.02 ( 120.40 ) 152.96 ( 131.52 )
62.3 140.05 ( 120.42 ) 152.98 ( 131.54 )
62.4 140.08 ( 120.45 ) 153.00 ( 131.56 )
Table 34. Outdoor Unit Capacity (JTOR500~540VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (1)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-50FSXNS
JTOR500VAE(U,F,R)BS1 RAS-52FSXNS
JTOR520VAE(U,F,R)BS1 RAS-54FSXNS
JTOR540VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
25.0 70.00 ( 60.19 ) 77.50 ( 66.64 )
25.1 70.28 ( 60.43 ) 77.81 ( 66.90 )
25.2 70.56 ( 60.67 ) 78.12 ( 67.17 )
25.3 70.84 ( 60.91 ) 78.43 ( 67.44 )
25.4 71.12 ( 61.15 ) 78.74 ( 67.70 )
_
25.5 71.40 ( 61.39 ) 79.05 ( 67.97 )
25.6 71.68 ( 61.63 ) 79.36 ( 68.24 )
25.7 71.96 ( 61.87 ) 79.67 ( 68.50 )
25.8 72.24 ( 62.12 ) 79.98 ( 68.77 )
25.9 72.52 ( 62.36 ) 80.29 ( 69.04 )
_
26.0 72.80 ( 62.60 ) 80.60 ( 69.30 ) 72.50 ( 62.34 ) 80.00 ( 68.79 )
26.1 73.08 ( 62.84 ) 80.91 ( 69.57 ) 72.78 ( 62.58 ) 80.31 ( 69.05 )
26.2 73.36 ( 63.08 ) 81.22 ( 69.84 ) 73.06 ( 62.82 ) 80.62 ( 69.32 )
26.3 73.64 ( 63.32 ) 81.53 ( 70.10 ) 73.34 ( 63.06 ) 80.92 ( 69.58 )
26.4 73.92 ( 63.56 ) 81.84 ( 70.37 ) 73.62 ( 63.30 ) 81.23 ( 69.85 )
26.5 74.20 ( 63.80 ) 82.15 ( 70.64 ) 73.89 ( 63.54 ) 81.54 ( 70.11 )
26.6 74.48 ( 64.04 ) 82.46 ( 70.90 ) 74.17 ( 63.78 ) 81.85 ( 70.38 )
26.7 74.76 ( 64.28 ) 82.77 ( 71.17 ) 74.45 ( 64.02 ) 82.15 ( 70.64 )
26.8 75.04 ( 64.52 ) 83.08 ( 71.44 ) 74.73 ( 64.26 ) 82.46 ( 70.90 )
26.9 75.32 ( 64.76 ) 83.39 ( 71.70 ) 75.01 ( 64.50 ) 82.77 ( 71.17 )
27.0 75.60 ( 65.00 ) 83.70 ( 71.97 ) 75.29 ( 64.74 ) 83.08 ( 71.43 ) 75.00 ( 64.49 ) 82.50 ( 70.94 )
27.1 75.88 ( 65.25 ) 84.01 ( 72.24 ) 75.57 ( 64.98 ) 83.38 ( 71.70 ) 75.28 ( 64.73 ) 82.81 ( 71.20 )
27.2 76.16 ( 65.49 ) 84.32 ( 72.50 ) 75.85 ( 65.22 ) 83.69 ( 71.96 ) 75.56 ( 64.97 ) 83.11 ( 71.46 )
27.3 76.44 ( 65.73 ) 84.63 ( 72.77 ) 76.12 ( 65.46 ) 84.00 ( 72.23 ) 75.83 ( 65.20 ) 83.42 ( 71.73 )
27.4 76.72 ( 65.97 ) 84.94 ( 73.04 ) 76.40 ( 65.70 ) 84.31 ( 72.49 ) 76.11 ( 65.44 ) 83.72 ( 71.99 )
27.5 77.00 ( 66.21 ) 85.25 ( 73.30 ) 76.68 ( 65.94 ) 84.62 ( 72.76 ) 76.39 ( 65.68 ) 84.03 ( 72.25 )
27.6 77.28 ( 66.45 ) 85.56 ( 73.57 ) 76.96 ( 66.18 ) 84.92 ( 73.02 ) 76.67 ( 65.92 ) 84.33 ( 72.51 )
27.7 77.56 ( 66.69 ) 85.87 ( 73.83 ) 77.24 ( 66.41 ) 85.23 ( 73.29 ) 76.94 ( 66.16 ) 84.64 ( 72.78 )
27.8 77.84 ( 66.93 ) 86.18 ( 74.10 ) 77.52 ( 66.65 ) 85.54 ( 73.55 ) 77.22 ( 66.40 ) 84.94 ( 73.04 )
27.9 78.12 ( 67.17 ) 86.49 ( 74.37 ) 77.80 ( 66.89 ) 85.85 ( 73.81 ) 77.50 ( 66.64 ) 85.25 ( 73.30 )
28.0 78.40 ( 67.41 ) 86.80 ( 74.63 ) 78.08 ( 67.13 ) 86.15 ( 74.08 ) 77.78 ( 66.88 ) 85.56 ( 73.56 )
28.1 78.68 ( 67.65 ) 87.11 ( 74.90 ) 78.36 ( 67.37 ) 86.46 ( 74.34 ) 78.06 ( 67.12 ) 85.86 ( 73.83 )
28.2 78.96 ( 67.89 ) 87.42 ( 75.17 ) 78.63 ( 67.61 ) 86.77 ( 74.61 ) 78.33 ( 67.35 ) 86.17 ( 74.09 )
28.3 79.24 ( 68.13 ) 87.73 ( 75.43 ) 78.91 ( 67.85 ) 87.08 ( 74.87 ) 78.61 ( 67.59 ) 86.47 ( 74.35 )
28.4 79.52 ( 68.37 ) 88.04 ( 75.70 ) 79.19 ( 68.09 ) 87.38 ( 75.14 ) 78.89 ( 67.83 ) 86.78 ( 74.62 )
28.5 79.80 ( 68.62 ) 88.35 ( 75.97 ) 79.47 ( 68.33 ) 87.69 ( 75.40 ) 79.17 ( 68.07 ) 87.08 ( 74.88 )
28.6 80.08 ( 68.86 ) 88.66 ( 76.23 ) 79.75 ( 68.57 ) 88.00 ( 75.67 ) 79.44 ( 68.31 ) 87.39 ( 75.14 )
28.7 80.36 ( 69.10 ) 88.97 ( 76.50 ) 80.03 ( 68.81 ) 88.31 ( 75.93 ) 79.72 ( 68.55 ) 87.69 ( 75.40 )
28.8 80.64 ( 69.34 ) 89.28 ( 76.77 ) 80.31 ( 69.05 ) 88.62 ( 76.20 ) 80.00 ( 68.79 ) 88.00 ( 75.67 )
28.9 80.92 ( 69.58 ) 89.59 ( 77.03 ) 80.59 ( 69.29 ) 88.92 ( 76.46 ) 80.28 ( 69.03 ) 88.31 ( 75.93 )
29.0 81.20 ( 69.82 ) 89.90 ( 77.30 ) 80.87 ( 69.53 ) 89.23 ( 76.72 ) 80.56 ( 69.27 ) 88.61 ( 76.19 )
29.1 81.48 ( 70.06 ) 90.21 ( 77.57 ) 81.14 ( 69.77 ) 89.54 ( 76.99 ) 80.83 ( 69.50 ) 88.92 ( 76.45 )
29.2 81.76 ( 70.30 ) 90.52 ( 77.83 ) 81.42 ( 70.01 ) 89.85 ( 77.25 ) 81.11 ( 69.74 ) 89.22 ( 76.72 )
29.3 82.04 ( 70.54 ) 90.83 ( 78.10 ) 81.70 ( 70.25 ) 90.15 ( 77.52 ) 81.39 ( 69.98 ) 89.53 ( 76.98 )
29.4 82.32 ( 70.78 ) 91.14 ( 78.37 ) 81.98 ( 70.49 ) 90.46 ( 77.78 ) 81.67 ( 70.22 ) 89.83 ( 77.24 )
29.5 82.60 ( 71.02 ) 91.45 ( 78.63 ) 82.26 ( 70.73 ) 90.77 ( 78.05 ) 81.94 ( 70.46 ) 90.14 ( 77.51 )
29.6 82.88 ( 71.26 ) 91.76 ( 78.90 ) 82.54 ( 70.97 ) 91.08 ( 78.31 ) 82.22 ( 70.70 ) 90.44 ( 77.77 )
29.7 83.16 ( 71.50 ) 92.07 ( 79.17 ) 82.82 ( 71.21 ) 91.38 ( 78.58 ) 82.50 ( 70.94 ) 90.75 ( 78.03 )
29.8 83.44 ( 71.75 ) 92.38 ( 79.43 ) 83.10 ( 71.45 ) 91.69 ( 78.84 ) 82.78 ( 71.18 ) 91.06 ( 78.29 )
29.9 83.72 ( 71.99 ) 92.69 ( 79.70 ) 83.37 ( 71.69 ) 92.00 ( 79.11 ) 83.06 ( 71.41 ) 91.36 ( 78.56 )
30.0 84.00 ( 72.23 ) 93.00 ( 79.97 ) 83.65 ( 71.93 ) 92.31 ( 79.37 ) 83.33 ( 71.65 ) 91.67 ( 78.82 )
30.1 84.28 ( 72.47 ) 93.31 ( 80.23 ) 83.93 ( 72.17 ) 92.62 ( 79.63 ) 83.61 ( 71.89 ) 91.97 ( 79.08 )
30.2 84.56 ( 72.71 ) 93.62 ( 80.50 ) 84.21 ( 72.41 ) 92.92 ( 79.90 ) 83.89 ( 72.13 ) 92.28 ( 79.34 )
30.3 84.84 ( 72.95 ) 93.93 ( 80.77 ) 84.49 ( 72.65 ) 93.23 ( 80.16 ) 84.17 ( 72.37 ) 92.58 ( 79.61 )
30.4 85.12 ( 73.19 ) 94.24 ( 81.03 ) 84.77 ( 72.89 ) 93.54 ( 80.43 ) 84.44 ( 72.61 ) 92.89 ( 79.87 )
30.5 85.40 ( 73.43 ) 94.55 ( 81.30 ) 85.05 ( 73.13 ) 93.85 ( 80.69 ) 84.72 ( 72.85 ) 93.19 ( 80.13 )
30.6 85.68 ( 73.67 ) 94.86 ( 81.56 ) 85.33 ( 73.37 ) 94.15 ( 80.96 ) 85.00 ( 73.09 ) 93.50 ( 80.40 )
30.7 85.96 ( 73.91 ) 95.17 ( 81.83 ) 85.61 ( 73.61 ) 94.46 ( 81.22 ) 85.28 ( 73.33 ) 93.81 ( 80.66 )
30.8 86.24 ( 74.15 ) 95.48 ( 82.10 ) 85.88 ( 73.85 ) 94.77 ( 81.49 ) 85.56 ( 73.56 ) 94.11 ( 80.92 )
30.9 86.52 ( 74.39 ) 95.79 ( 82.36 ) 86.16 ( 74.09 ) 95.08 ( 81.75 ) 85.83 ( 73.80 ) 94.42 ( 81.18 )
Table 35. Outdoor Unit Capacity (JTOR500~540VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (2)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-50FSXNS
JTOR500VAE(U,F,R)BS1 RAS-52FSXNS
JTOR520VAE(U,F,R)BS1 RAS-54FSXNS
JTOR540VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
31.0 86.80 ( 74.63 ) 96.10 ( 82.63 ) 86.44 ( 74.33 ) 95.38 ( 82.02 ) 86.11 ( 74.04 ) 94.72 ( 81.45 )
31.1 87.08 ( 74.88 ) 96.41 ( 82.90 ) 86.72 ( 74.57 ) 95.69 ( 82.28 ) 86.39 ( 74.28 ) 95.03 ( 81.71 )
31.2 87.36 ( 75.12 ) 96.72 ( 83.16 ) 87.00 ( 74.81 ) 96.00 ( 82.55 ) 86.67 ( 74.52 ) 95.33 ( 81.97 )
31.3 87.64 ( 75.36 ) 97.03 ( 83.43 ) 87.28 ( 75.05 ) 96.31 ( 82.81 ) 86.94 ( 74.76 ) 95.64 ( 82.23 )
31.4 87.92 ( 75.60 ) 97.34 ( 83.70 ) 87.56 ( 75.29 ) 96.62 ( 83.07 ) 87.22 ( 75.00 ) 95.94 ( 82.50 )
31.5 88.20 ( 75.84 ) 97.65 ( 83.96 ) 87.84 ( 75.53 ) 96.92 ( 83.34 ) 87.50 ( 75.24 ) 96.25 ( 82.76 )
31.6 88.48 ( 76.08 ) 97.96 ( 84.23 ) 88.12 ( 75.77 ) 97.23 ( 83.60 ) 87.78 ( 75.48 ) 96.56 ( 83.02 )
31.7 88.76 ( 76.32 ) 98.27 ( 84.50 ) 88.39 ( 76.01 ) 97.54 ( 83.87 ) 88.06 ( 75.71 ) 96.86 ( 83.29 )
31.8 89.04 ( 76.56 ) 98.58 ( 84.76 ) 88.67 ( 76.25 ) 97.85 ( 84.13 ) 88.33 ( 75.95 ) 97.17 ( 83.55 )
31.9 89.32 ( 76.80 ) 98.89 ( 85.03 ) 88.95 ( 76.48 ) 98.15 ( 84.40 ) 88.61 ( 76.19 ) 97.47 ( 83.81 )
32.0 89.60 ( 77.04 ) 99.20 ( 85.30 ) 89.23 ( 76.72 ) 98.46 ( 84.66 ) 88.89 ( 76.43 ) 97.78 ( 84.07 )
32.1 89.88 ( 77.28 ) 99.51 ( 85.56 ) 89.51 ( 76.96 ) 98.77 ( 84.93 ) 89.17 ( 76.67 ) 98.08 ( 84.34 )
32.2 90.16 ( 77.52 ) 99.82 ( 85.83 ) 89.79 ( 77.20 ) 99.08 ( 85.19 ) 89.44 ( 76.91 ) 98.39 ( 84.60 )
32.3 90.44 ( 77.76 ) 100.13 ( 86.10 ) 90.07 ( 77.44 ) 99.38 ( 85.46 ) 89.72 ( 77.15 ) 98.69 ( 84.86 )
32.4 90.72 ( 78.01 ) 100.44 ( 86.36 ) 90.35 ( 77.68 ) 99.69 ( 85.72 ) 90.00 ( 77.39 ) 99.00 ( 85.12 )
32.5 91.00 ( 78.25 ) 100.75 ( 86.63 ) 90.62 ( 77.92 ) 100.00 ( 85.98 ) 90.28 ( 77.62 ) 99.31 ( 85.39 )
32.6 91.28 ( 78.49 ) 101.06 ( 86.90 ) 90.90 ( 78.16 ) 100.31 ( 86.25 ) 90.56 ( 77.86 ) 99.61 ( 85.65 )
32.7 91.56 ( 78.73 ) 101.37 ( 87.16 ) 91.18 ( 78.40 ) 100.62 ( 86.51 ) 90.83 ( 78.10 ) 99.92 ( 85.91 )
32.8 91.84 ( 78.97 ) 101.68 ( 87.43 ) 91.46 ( 78.64 ) 100.92 ( 86.78 ) 91.11 ( 78.34 ) 100.22 ( 86.18 )
32.9 92.12 ( 79.21 ) 101.99 ( 87.70 ) 91.74 ( 78.88 ) 101.23 ( 87.04 ) 91.39 ( 78.58 ) 100.53 ( 86.44 )
33.0 92.40 ( 79.45 ) 102.30 ( 87.96 ) 92.02 ( 79.12 ) 101.54 ( 87.31 ) 91.67 ( 78.82 ) 100.83 ( 86.70 )
33.1 92.68 ( 79.69 ) 102.61 ( 88.23 ) 92.30 ( 79.36 ) 101.85 ( 87.57 ) 91.94 ( 79.06 ) 101.14 ( 86.96 )
33.2 92.96 ( 79.93 ) 102.92 ( 88.50 ) 92.58 ( 79.60 ) 102.15 ( 87.84 ) 92.22 ( 79.30 ) 101.44 ( 87.23 )
33.3 93.24 ( 80.17 ) 103.23 ( 88.76 ) 92.86 ( 79.84 ) 102.46 ( 88.10 ) 92.50 ( 79.54 ) 101.75 ( 87.49 )
33.4 93.52 ( 80.41 ) 103.54 ( 89.03 ) 93.13 ( 80.08 ) 102.77 ( 88.37 ) 92.78 ( 79.77 ) 102.06 ( 87.75 )
33.5 93.80 ( 80.65 ) 103.85 ( 89.29 ) 93.41 ( 80.32 ) 103.08 ( 88.63 ) 93.06 ( 80.01 ) 102.36 ( 88.01 )
33.6 94.08 ( 80.89 ) 104.16 ( 89.56 ) 93.69 ( 80.56 ) 103.38 ( 88.89 ) 93.33 ( 80.25 ) 102.67 ( 88.28 )
33.7 94.36 ( 81.13 ) 104.47 ( 89.83 ) 93.97 ( 80.80 ) 103.69 ( 89.16 ) 93.61 ( 80.49 ) 102.97 ( 88.54 )
33.8 94.64 ( 81.38 ) 104.78 ( 90.09 ) 94.25 ( 81.04 ) 104.00 ( 89.42 ) 93.89 ( 80.73 ) 103.28 ( 88.80 )
33.9 94.92 ( 81.62 ) 105.09 ( 90.36 ) 94.53 ( 81.28 ) 104.31 ( 89.69 ) 94.17 ( 80.97 ) 103.58 ( 89.07 )
34.0 95.20 ( 81.86 ) 105.40 ( 90.63 ) 94.81 ( 81.52 ) 104.62 ( 89.95 ) 94.44 ( 81.21 ) 103.89 ( 89.33 )
34.1 95.48 ( 82.10 ) 105.71 ( 90.89 ) 95.09 ( 81.76 ) 104.92 ( 90.22 ) 94.72 ( 81.45 ) 104.19 ( 89.59 )
34.2 95.76 ( 82.34 ) 106.02 ( 91.16 ) 95.37 ( 82.00 ) 105.23 ( 90.48 ) 95.00 ( 81.69 ) 104.50 ( 89.85 )
34.3 96.04 ( 82.58 ) 106.33 ( 91.43 ) 95.64 ( 82.24 ) 105.54 ( 90.75 ) 95.28 ( 81.92 ) 104.81 ( 90.12 )
34.4 96.32 ( 82.82 ) 106.64 ( 91.69 ) 95.92 ( 82.48 ) 105.85 ( 91.01 ) 95.56 ( 82.16 ) 105.11 ( 90.38 )
34.5 96.60 ( 83.06 ) 106.95 ( 91.96 ) 96.20 ( 82.72 ) 106.15 ( 91.28 ) 95.83 ( 82.40 ) 105.42 ( 90.64 )
34.6 96.88 ( 83.30 ) 107.26 ( 92.23 ) 96.48 ( 82.96 ) 106.46 ( 91.54 ) 96.11 ( 82.64 ) 105.72 ( 90.90 )
34.7 97.16 ( 83.54 ) 107.57 ( 92.49 ) 96.76 ( 83.20 ) 106.77 ( 91.81 ) 96.39 ( 82.88 ) 106.03 ( 91.17 )
34.8 97.44 ( 83.78 ) 107.88 ( 92.76 ) 97.04 ( 83.44 ) 107.08 ( 92.07 ) 96.67 ( 83.12 ) 106.33 ( 91.43 )
34.9 97.72 ( 84.02 ) 108.19 ( 93.03 ) 97.32 ( 83.68 ) 107.38 ( 92.33 ) 96.94 ( 83.36 ) 106.64 ( 91.69 )
35.0 98.00 ( 84.26 ) 108.50 ( 93.29 ) 97.60 ( 83.92 ) 107.69 ( 92.60 ) 97.22 ( 83.60 ) 106.94 ( 91.96 )
35.1 98.28 ( 84.51 ) 108.81 ( 93.56 ) 97.88 ( 84.16 ) 108.00 ( 92.86 ) 97.50 ( 83.83 ) 107.25 ( 92.22 )
35.2 98.56 ( 84.75 ) 109.12 ( 93.83 ) 98.15 ( 84.40 ) 108.31 ( 93.13 ) 97.78 ( 84.07 ) 107.56 ( 92.48 )
35.3 98.84 ( 84.99 ) 109.43 ( 94.09 ) 98.43 ( 84.64 ) 108.62 ( 93.39 ) 98.06 ( 84.31 ) 107.86 ( 92.74 )
35.4 99.12 ( 85.23 ) 109.74 ( 94.36 ) 98.71 ( 84.88 ) 108.92 ( 93.66 ) 98.33 ( 84.55 ) 108.17 ( 93.01 )
35.5 99.40 ( 85.47 ) 110.05 ( 94.63 ) 98.99 ( 85.12 ) 109.23 ( 93.92 ) 98.61 ( 84.79 ) 108.47 ( 93.27 )
35.6 99.68 ( 85.71 ) 110.36 ( 94.89 ) 99.27 ( 85.36 ) 109.54 ( 94.19 ) 98.89 ( 85.03 ) 108.78 ( 93.53 )
35.7 99.96 ( 85.95 ) 110.67 ( 95.16 ) 99.55 ( 85.60 ) 109.85 ( 94.45 ) 99.17 ( 85.27 ) 109.08 ( 93.79 )
35.8 100.24 ( 86.19 ) 110.98 ( 95.43 ) 99.83 ( 85.84 ) 110.15 ( 94.72 ) 99.44 ( 85.51 ) 109.39 ( 94.06 )
35.9 100.52 ( 86.43 ) 111.29 ( 95.69 ) 100.11 ( 86.08 ) 110.46 ( 94.98 ) 99.72 ( 85.75 ) 109.69 ( 94.32 )
36.0 100.80 ( 86.67 ) 111.60 ( 95.96 ) 100.38 ( 86.32 ) 110.77 ( 95.24 ) 100.00 ( 85.98 ) 110.00 ( 94.58 )
36.1 101.08 ( 86.91 ) 111.91 ( 96.23 ) 100.66 ( 86.55 ) 111.08 ( 95.51 ) 100.28 ( 86.22 ) 110.31 ( 94.85 )
36.2 101.36 ( 87.15 ) 112.22 ( 96.49 ) 100.94 ( 86.79 ) 111.38 ( 95.77 ) 100.56 ( 86.46 ) 110.61 ( 95.11 )
36.3 101.64 ( 87.39 ) 112.53 ( 96.76 ) 101.22 ( 87.03 ) 111.69 ( 96.04 ) 100.83 ( 86.70 ) 110.92 ( 95.37 )
36.4 101.92 ( 87.64 ) 112.84 ( 97.02 ) 101.50 ( 87.27 ) 112.00 ( 96.30 ) 101.11 ( 86.94 ) 111.22 ( 95.63 )
36.5 102.20 ( 87.88 ) 113.15 ( 97.29 ) 101.78 ( 87.51 ) 112.31 ( 96.57 ) 101.39 ( 87.18 ) 111.53 ( 95.90 )
36.6 102.48 ( 88.12 ) 113.46 ( 97.56 ) 102.06 ( 87.75 ) 112.62 ( 96.83 ) 101.67 ( 87.42 ) 111.83 ( 96.16 )
36.7 102.76 ( 88.36 ) 113.77 ( 97.82 ) 102.34 ( 87.99 ) 112.92 ( 97.10 ) 101.94 ( 87.66 ) 112.14 ( 96.42 )
36.8 103.04 ( 88.60 ) 114.08 ( 98.09 ) 102.62 ( 88.23 ) 113.23 ( 97.36 ) 102.22 ( 87.90 ) 112.44 ( 96.68 )
36.9 103.32 ( 88.84 ) 114.39 ( 98.36 ) 102.89 ( 88.47 ) 113.54 ( 97.63 ) 102.50 ( 88.13 ) 112.75 ( 96.95 )
Table 36. Outdoor Unit Capacity (JTOR500~540VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (3)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-50FSXNS
JTOR500VAE(U,F,R)BS1 RAS-52FSXNS
JTOR520VAE(U,F,R)BS1 RAS-54FSXNS
JTOR540VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
37.0 103.60 ( 89.08 ) 114.70 ( 98.62 ) 103.17 ( 88.71 ) 113.85 ( 97.89 ) 102.78 ( 88.37 ) 113.06 ( 97.21 )
37.1 103.88 ( 89.32 ) 115.01 ( 98.89 ) 103.45 ( 88.95 ) 114.15 ( 98.15 ) 103.06 ( 88.61 ) 113.36 ( 97.47 )
37.2 104.16 ( 89.56 ) 115.32 ( 99.16 ) 103.73 ( 89.19 ) 114.46 ( 98.42 ) 103.33 ( 88.85 ) 113.67 ( 97.74 )
37.3 104.44 ( 89.80 ) 115.63 ( 99.42 ) 104.01 ( 89.43 ) 114.77 ( 98.68 ) 103.61 ( 89.09 ) 113.97 ( 98.00 )
37.4 104.72 ( 90.04 ) 115.94 ( 99.69 ) 104.29 ( 89.67 ) 115.08 ( 98.95 ) 103.89 ( 89.33 ) 114.28 ( 98.26 )
37.5 105.00 ( 90.28 ) 116.25 ( 99.96 ) 104.57 ( 89.91 ) 115.38 ( 99.21 ) 104.17 ( 89.57 ) 114.58 ( 98.52 )
37.6 105.28 ( 90.52 ) 116.56 ( 100.22 ) 104.85 ( 90.15 ) 115.69 ( 99.48 ) 104.44 ( 89.81 ) 114.89 ( 98.79 )
37.7 105.56 ( 90.77 ) 116.87 ( 100.49 ) 105.13 ( 90.39 ) 116.00 ( 99.74 ) 104.72 ( 90.04 ) 115.19 ( 99.05 )
37.8 105.84 ( 91.01 ) 117.18 ( 100.76 ) 105.40 ( 90.63 ) 116.31 ( 100.01 ) 105.00 ( 90.28 ) 115.50 ( 99.31 )
37.9 106.12 ( 91.25 ) 117.49 ( 101.02 ) 105.68 ( 90.87 ) 116.62 ( 100.27 ) 105.28 ( 90.52 ) 115.81 ( 99.57 )
38.0 106.40 ( 91.49 ) 117.80 ( 101.29 ) 105.96 ( 91.11 ) 116.92 ( 100.54 ) 105.56 ( 90.76 ) 116.11 ( 99.84 )
38.1 106.68 ( 91.73 ) 118.11 ( 101.56 ) 106.24 ( 91.35 ) 117.23 ( 100.80 ) 105.83 ( 91.00 ) 116.42 ( 100.10 )
38.2 106.96 ( 91.97 ) 118.42 ( 101.82 ) 106.52 ( 91.59 ) 117.54 ( 101.06 ) 106.11 ( 91.24 ) 116.72 ( 100.36 )
38.3 107.24 ( 92.21 ) 118.73 ( 102.09 ) 106.80 ( 91.83 ) 117.85 ( 101.33 ) 106.39 ( 91.48 ) 117.03 ( 100.63 )
38.4 107.52 ( 92.45 ) 119.04 ( 102.36 ) 107.08 ( 92.07 ) 118.15 ( 101.59 ) 106.67 ( 91.72 ) 117.33 ( 100.89 )
38.5 107.80 ( 92.69 ) 119.35 ( 102.62 ) 107.36 ( 92.31 ) 118.46 ( 101.86 ) 106.94 ( 91.96 ) 117.64 ( 101.15 )
38.6 108.08 ( 92.93 ) 119.66 ( 102.89 ) 107.63 ( 92.55 ) 118.77 ( 102.12 ) 107.22 ( 92.19 ) 117.94 ( 101.41 )
38.7 108.36 ( 93.17 ) 119.97 ( 103.16 ) 107.91 ( 92.79 ) 119.08 ( 102.39 ) 107.50 ( 92.43 ) 118.25 ( 101.68 )
38.8 108.64 ( 93.41 ) 120.28 ( 103.42 ) 108.19 ( 93.03 ) 119.38 ( 102.65 ) 107.78 ( 92.67 ) 118.56 ( 101.94 )
38.9 108.92 ( 93.65 ) 120.59 ( 103.69 ) 108.47 ( 93.27 ) 119.69 ( 102.92 ) 108.06 ( 92.91 ) 118.86 ( 102.20 )
39.0 109.20 ( 93.90 ) 120.90 ( 103.96 ) 108.75 ( 93.51 ) 120.00 ( 103.18 ) 108.33 ( 93.15 ) 119.17 ( 102.46 )
39.1 109.48 ( 94.14 ) 121.21 ( 104.22 ) 109.03 ( 93.75 ) 120.31 ( 103.45 ) 108.61 ( 93.39 ) 119.47 ( 102.73 )
39.2 109.76 ( 94.38 ) 121.52 ( 104.49 ) 109.31 ( 93.99 ) 120.62 ( 103.71 ) 108.89 ( 93.63 ) 119.78 ( 102.99 )
39.3 110.04 ( 94.62 ) 121.83 ( 104.75 ) 109.59 ( 94.23 ) 120.92 ( 103.98 ) 109.17 ( 93.87 ) 120.08 ( 103.25 )
39.4 110.32 ( 94.86 ) 122.14 ( 105.02 ) 109.87 ( 94.47 ) 121.23 ( 104.24 ) 109.44 ( 94.11 ) 120.39 ( 103.52 )
39.5 110.60 ( 95.10 ) 122.45 ( 105.29 ) 110.14 ( 94.71 ) 121.54 ( 104.50 ) 109.72 ( 94.34 ) 120.69 ( 103.78 )
39.6 110.88 ( 95.34 ) 122.76 ( 105.55 ) 110.42 ( 94.95 ) 121.85 ( 104.77 ) 110.00 ( 94.58 ) 121.00 ( 104.04 )
39.7 111.16 ( 95.58 ) 123.07 ( 105.82 ) 110.70 ( 95.19 ) 122.15 ( 105.03 ) 110.28 ( 94.82 ) 121.31 ( 104.30 )
39.8 111.44 ( 95.82 ) 123.38 ( 106.09 ) 110.98 ( 95.43 ) 122.46 ( 105.30 ) 110.56 ( 95.06 ) 121.61 ( 104.57 )
39.9 111.72 ( 96.06 ) 123.69 ( 106.35 ) 111.26 ( 95.67 ) 122.77 ( 105.56 ) 110.83 ( 95.30 ) 121.92 ( 104.83 )
40.0 112.00 ( 96.30 ) 124.00 ( 106.62 ) 111.54 ( 95.91 ) 123.08 ( 105.83 ) 111.11 ( 95.54 ) 122.22 ( 105.09 )
40.1 112.28 ( 96.54 ) 124.31 ( 106.89 ) 111.82 ( 96.15 ) 123.38 ( 106.09 ) 111.39 ( 95.78 ) 122.53 ( 105.35 )
40.2 112.56 ( 96.78 ) 124.62 ( 107.15 ) 112.10 ( 96.39 ) 123.69 ( 106.36 ) 111.67 ( 96.02 ) 122.83 ( 105.62 )
40.3 112.84 ( 97.02 ) 124.93 ( 107.42 ) 112.38 ( 96.63 ) 124.00 ( 106.62 ) 111.94 ( 96.25 ) 123.14 ( 105.88 )
40.4 113.12 ( 97.27 ) 125.24 ( 107.69 ) 112.65 ( 96.86 ) 124.31 ( 106.89 ) 112.22 ( 96.49 ) 123.44 ( 106.14 )
40.5 113.40 ( 97.51 ) 125.55 ( 107.95 ) 112.93 ( 97.10 ) 124.62 ( 107.15 ) 112.50 ( 96.73 ) 123.75 ( 106.41 )
40.6 113.68 ( 97.75 ) 125.86 ( 108.22 ) 113.21 ( 97.34 ) 124.92 ( 107.41 ) 112.78 ( 96.97 ) 124.06 ( 106.67 )
40.7 113.96 ( 97.99 ) 126.17 ( 108.49 ) 113.49 ( 97.58 ) 125.23 ( 107.68 ) 113.06 ( 97.21 ) 124.36 ( 106.93 )
40.8 114.24 ( 98.23 ) 126.48 ( 108.75 ) 113.77 ( 97.82 ) 125.54 ( 107.94 ) 113.33 ( 97.45 ) 124.67 ( 107.19 )
40.9 114.52 ( 98.47 ) 126.79 ( 109.02 ) 114.05 ( 98.06 ) 125.85 ( 108.21 ) 113.61 ( 97.69 ) 124.97 ( 107.46 )
41.0 114.80 ( 98.71 ) 127.10 ( 109.29 ) 114.33 ( 98.30 ) 126.15 ( 108.47 ) 113.89 ( 97.93 ) 125.28 ( 107.72 )
41.1 115.08 ( 98.95 ) 127.41 ( 109.55 ) 114.61 ( 98.54 ) 126.46 ( 108.74 ) 114.17 ( 98.17 ) 125.58 ( 107.98 )
41.2 115.36 ( 99.19 ) 127.72 ( 109.82 ) 114.88 ( 98.78 ) 126.77 ( 109.00 ) 114.44 ( 98.40 ) 125.89 ( 108.24 )
41.3 115.64 ( 99.43 ) 128.03 ( 110.09 ) 115.16 ( 99.02 ) 127.08 ( 109.27 ) 114.72 ( 98.64 ) 126.19 ( 108.51 )
41.4 115.92 ( 99.67 ) 128.34 ( 110.35 ) 115.44 ( 99.26 ) 127.38 ( 109.53 ) 115.00 ( 98.88 ) 126.50 ( 108.77 )
41.5 116.20 ( 99.91 ) 128.65 ( 110.62 ) 115.72 ( 99.50 ) 127.69 ( 109.80 ) 115.28 ( 99.12 ) 126.81 ( 109.03 )
41.6 116.48 ( 100.15 ) 128.96 ( 110.89 ) 116.00 ( 99.74 ) 128.00 ( 110.06 ) 115.56 ( 99.36 ) 127.11 ( 109.30 )
41.7 116.76 ( 100.40 ) 129.27 ( 111.15 ) 116.28 ( 99.98 ) 128.31 ( 110.32 ) 115.83 ( 99.60 ) 127.42 ( 109.56 )
41.8 117.04 ( 100.64 ) 129.58 ( 111.42 ) 116.56 ( 100.22 ) 128.62 ( 110.59 ) 116.11 ( 99.84 ) 127.72 ( 109.82 )
41.9 117.32 ( 100.88 ) 129.89 ( 111.69 ) 116.84 ( 100.46 ) 128.92 ( 110.85 ) 116.39 ( 100.08 ) 128.03 ( 110.08 )
42.0 117.60 ( 101.12 ) 130.20 ( 111.95 ) 117.12 ( 100.70 ) 129.23 ( 111.12 ) 116.67 ( 100.32 ) 128.33 ( 110.35 )
42.1 117.88 ( 101.36 ) 130.51 ( 112.22 ) 117.39 ( 100.94 ) 129.54 ( 111.38 ) 116.94 ( 100.55 ) 128.64 ( 110.61 )
42.2 118.16 ( 101.60 ) 130.82 ( 112.48 ) 117.67 ( 101.18 ) 129.85 ( 111.65 ) 117.22 ( 100.79 ) 128.94 ( 110.87 )
42.3 118.44 ( 101.84 ) 131.13 ( 112.75 ) 117.95 ( 101.42 ) 130.15 ( 111.91 ) 117.50 ( 101.03 ) 129.25 ( 111.13 )
42.4 118.72 ( 102.08 ) 131.44 ( 113.02 ) 118.23 ( 101.66 ) 130.46 ( 112.18 ) 117.78 ( 101.27 ) 129.56 ( 111.40 )
42.5 119.00 ( 102.32 ) 131.75 ( 113.28 ) 118.51 ( 101.90 ) 130.77 ( 112.44 ) 118.06 ( 101.51 ) 129.86 ( 111.66 )
42.6 119.28 ( 102.56 ) 132.06 ( 113.55 ) 118.79 ( 102.14 ) 131.08 ( 112.71 ) 118.33 ( 101.75 ) 130.17 ( 111.92 )
42.7 119.56 ( 102.80 ) 132.37 ( 113.82 ) 119.07 ( 102.38 ) 131.38 ( 112.97 ) 118.61 ( 101.99 ) 130.47 ( 112.19 )
42.8 119.84 ( 103.04 ) 132.68 ( 114.08 ) 119.35 ( 102.62 ) 131.69 ( 113.24 ) 118.89 ( 102.23 ) 130.78 ( 112.45 )
42.9 120.12 ( 103.28 ) 132.99 ( 114.35 ) 119.63 ( 102.86 ) 132.00 ( 113.50 ) 119.17 ( 102.46 ) 131.08 ( 112.71 )
Table 37. Outdoor Unit Capacity (JTOR500~540VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (4)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-50FSXNS
JTOR500VAE(U,F,R)BS1 RAS-52FSXNS
JTOR520VAE(U,F,R)BS1 RAS-54FSXNS
JTOR540VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
43.0 120.40 ( 103.53 ) 133.30 ( 114.62 ) 119.90 ( 103.10 ) 132.31 ( 113.76 ) 119.44 ( 102.70 ) 131.39 ( 112.97 )
43.1 120.68 ( 103.77 ) 133.61 ( 114.88 ) 120.18 ( 103.34 ) 132.62 ( 114.03 ) 119.72 ( 102.94 ) 131.69 ( 113.24 )
43.2 120.96 ( 104.01 ) 133.92 ( 115.15 ) 120.46 ( 103.58 ) 132.92 ( 114.29 ) 120.00 ( 103.18 ) 132.00 ( 113.50 )
43.3 121.24 ( 104.25 ) 134.23 ( 115.42 ) 120.74 ( 103.82 ) 133.23 ( 114.56 ) 120.28 ( 103.42 ) 132.31 ( 113.76 )
43.4 121.52 ( 104.49 ) 134.54 ( 115.68 ) 121.02 ( 104.06 ) 133.54 ( 114.82 ) 120.56 ( 103.66 ) 132.61 ( 114.03 )
43.5 121.80 ( 104.73 ) 134.85 ( 115.95 ) 121.30 ( 104.30 ) 133.85 ( 115.09 ) 120.83 ( 103.90 ) 132.92 ( 114.29 )
43.6 122.08 ( 104.97 ) 135.16 ( 116.22 ) 121.58 ( 104.54 ) 134.15 ( 115.35 ) 121.11 ( 104.14 ) 133.22 ( 114.55 )
43.7 122.36 ( 105.21 ) 135.47 ( 116.48 ) 121.86 ( 104.78 ) 134.46 ( 115.62 ) 121.39 ( 104.38 ) 133.53 ( 114.81 )
43.8 122.64 ( 105.45 ) 135.78 ( 116.75 ) 122.13 ( 105.02 ) 134.77 ( 115.88 ) 121.67 ( 104.61 ) 133.83 ( 115.08 )
43.9 122.92 ( 105.69 ) 136.09 ( 117.02 ) 122.41 ( 105.26 ) 135.08 ( 116.15 ) 121.94 ( 104.85 ) 134.14 ( 115.34 )
44.0 123.20 ( 105.93 ) 136.40 ( 117.28 ) 122.69 ( 105.50 ) 135.38 ( 116.41 ) 122.22 ( 105.09 ) 134.44 ( 115.60 )
44.1 123.48 ( 106.17 ) 136.71 ( 117.55 ) 122.97 ( 105.74 ) 135.69 ( 116.67 ) 122.50 ( 105.33 ) 134.75 ( 115.86 )
44.2 123.76 ( 106.41 ) 137.02 ( 117.82 ) 123.25 ( 105.98 ) 136.00 ( 116.94 ) 122.78 ( 105.57 ) 135.06 ( 116.13 )
44.3 124.04 ( 106.66 ) 137.33 ( 118.08 ) 123.53 ( 106.22 ) 136.31 ( 117.20 ) 123.06 ( 105.81 ) 135.36 ( 116.39 )
44.4 124.32 ( 106.90 ) 137.64 ( 118.35 ) 123.81 ( 106.46 ) 136.62 ( 117.47 ) 123.33 ( 106.05 ) 135.67 ( 116.65 )
44.5 124.60 ( 107.14 ) 137.95 ( 118.62 ) 124.09 ( 106.70 ) 136.92 ( 117.73 ) 123.61 ( 106.29 ) 135.97 ( 116.92 )
44.6 124.88 ( 107.38 ) 138.26 ( 118.88 ) 124.37 ( 106.93 ) 137.23 ( 118.00 ) 123.89 ( 106.53 ) 136.28 ( 117.18 )
44.7 125.16 ( 107.62 ) 138.57 ( 119.15 ) 124.64 ( 107.17 ) 137.54 ( 118.26 ) 124.17 ( 106.76 ) 136.58 ( 117.44 )
44.8 125.44 ( 107.86 ) 138.88 ( 119.42 ) 124.92 ( 107.41 ) 137.85 ( 118.53 ) 124.44 ( 107.00 ) 136.89 ( 117.70 )
44.9 125.72 ( 108.10 ) 139.19 ( 119.68 ) 125.20 ( 107.65 ) 138.15 ( 118.79 ) 124.72 ( 107.24 ) 137.19 ( 117.97 )
45.0 126.00 ( 108.34 ) 139.50 ( 119.95 ) 125.48 ( 107.89 ) 138.46 ( 119.06 ) 125.00 ( 107.48 ) 137.50 ( 118.23 )
45.1 126.28 ( 108.58 ) 139.81 ( 120.21 ) 125.76 ( 108.13 ) 138.77 ( 119.32 ) 125.28 ( 107.72 ) 137.81 ( 118.49 )
45.2 126.56 ( 108.82 ) 140.12 ( 120.48 ) 126.04 ( 108.37 ) 139.08 ( 119.58 ) 125.56 ( 107.96 ) 138.11 ( 118.75 )
45.3 126.84 ( 109.06 ) 140.43 ( 120.75 ) 126.32 ( 108.61 ) 139.38 ( 119.85 ) 125.83 ( 108.20 ) 138.42 ( 119.02 )
45.4 127.12 ( 109.30 ) 140.74 ( 121.01 ) 126.60 ( 108.85 ) 139.69 ( 120.11 ) 126.11 ( 108.44 ) 138.72 ( 119.28 )
45.5 127.40 ( 109.54 ) 141.05 ( 121.28 ) 126.88 ( 109.09 ) 140.00 ( 120.38 ) 126.39 ( 108.67 ) 139.03 ( 119.54 )
45.6 127.68 ( 109.79 ) 141.36 ( 121.55 ) 127.15 ( 109.33 ) 140.31 ( 120.64 ) 126.67 ( 108.91 ) 139.33 ( 119.81 )
45.7 127.96 ( 110.03 ) 141.67 ( 121.81 ) 127.43 ( 109.57 ) 140.62 ( 120.91 ) 126.94 ( 109.15 ) 139.64 ( 120.07 )
45.8 128.24 ( 110.27 ) 141.98 ( 122.08 ) 127.71 ( 109.81 ) 140.92 ( 121.17 ) 127.22 ( 109.39 ) 139.94 ( 120.33 )
45.9 128.52 ( 110.51 ) 142.29 ( 122.35 ) 127.99 ( 110.05 ) 141.23 ( 121.44 ) 127.50 ( 109.63 ) 140.25 ( 120.59 )
46.0 128.80 ( 110.75 ) 142.60 ( 122.61 ) 128.27 ( 110.29 ) 141.54 ( 121.70 ) 127.78 ( 109.87 ) 140.56 ( 120.86 )
46.1 129.08 ( 110.99 ) 142.91 ( 122.88 ) 128.55 ( 110.53 ) 141.85 ( 121.97 ) 128.06 ( 110.11 ) 140.86 ( 121.12 )
46.2 129.36 ( 111.23 ) 143.22 ( 123.15 ) 128.83 ( 110.77 ) 142.15 ( 122.23 ) 128.33 ( 110.35 ) 141.17 ( 121.38 )
46.3 129.64 ( 111.47 ) 143.53 ( 123.41 ) 129.11 ( 111.01 ) 142.46 ( 122.49 ) 128.61 ( 110.59 ) 141.47 ( 121.64 )
46.4 129.92 ( 111.71 ) 143.84 ( 123.68 ) 129.38 ( 111.25 ) 142.77 ( 122.76 ) 128.89 ( 110.82 ) 141.78 ( 121.91 )
46.5 130.20 ( 111.95 ) 144.15 ( 123.95 ) 129.66 ( 111.49 ) 143.08 ( 123.02 ) 129.17 ( 111.06 ) 142.08 ( 122.17 )
46.6 130.48 ( 112.19 ) 144.46 ( 124.21 ) 129.94 ( 111.73 ) 143.38 ( 123.29 ) 129.44 ( 111.30 ) 142.39 ( 122.43 )
46.7 130.76 ( 112.43 ) 144.77 ( 124.48 ) 130.22 ( 111.97 ) 143.69 ( 123.55 ) 129.72 ( 111.54 ) 142.69 ( 122.70 )
46.8 131.04 ( 112.67 ) 145.08 ( 124.75 ) 130.50 ( 112.21 ) 144.00 ( 123.82 ) 130.00 ( 111.78 ) 143.00 ( 122.96 )
46.9 131.32 ( 112.91 ) 145.39 ( 125.01 ) 130.78 ( 112.45 ) 144.31 ( 124.08 ) 130.28 ( 112.02 ) 143.31 ( 123.22 )
47.0 131.60 ( 113.16 ) 145.70 ( 125.28 ) 131.06 ( 112.69 ) 144.62 ( 124.35 ) 130.56 ( 112.26 ) 143.61 ( 123.48 )
47.1 131.88 ( 113.40 ) 146.01 ( 125.55 ) 131.34 ( 112.93 ) 144.92 ( 124.61 ) 130.83 ( 112.50 ) 143.92 ( 123.75 )
47.2 132.16 ( 113.64 ) 146.32 ( 125.81 ) 131.62 ( 113.17 ) 145.23 ( 124.88 ) 131.11 ( 112.74 ) 144.22 ( 124.01 )
47.3 132.44 ( 113.88 ) 146.63 ( 126.08 ) 131.89 ( 113.41 ) 145.54 ( 125.14 ) 131.39 ( 112.97 ) 144.53 ( 124.27 )
47.4 132.72 ( 114.12 ) 146.94 ( 126.35 ) 132.17 ( 113.65 ) 145.85 ( 125.41 ) 131.67 ( 113.21 ) 144.83 ( 124.53 )
47.5 133.00 ( 114.36 ) 147.25 ( 126.61 ) 132.45 ( 113.89 ) 146.15 ( 125.67 ) 131.94 ( 113.45 ) 145.14 ( 124.80 )
47.6 133.28 ( 114.60 ) 147.56 ( 126.88 ) 132.73 ( 114.13 ) 146.46 ( 125.93 ) 132.22 ( 113.69 ) 145.44 ( 125.06 )
47.7 133.56 ( 114.84 ) 147.87 ( 127.15 ) 133.01 ( 114.37 ) 146.77 ( 126.20 ) 132.50 ( 113.93 ) 145.75 ( 125.32 )
47.8 133.84 ( 115.08 ) 148.18 ( 127.41 ) 133.29 ( 114.61 ) 147.08 ( 126.46 ) 132.78 ( 114.17 ) 146.06 ( 125.59 )
47.9 134.12 ( 115.32 ) 148.49 ( 127.68 ) 133.57 ( 114.85 ) 147.38 ( 126.73 ) 133.06 ( 114.41 ) 146.36 ( 125.85 )
48.0 134.40 ( 115.56 ) 148.80 ( 127.94 ) 133.85 ( 115.09 ) 147.69 ( 126.99 ) 133.33 ( 114.65 ) 146.67 ( 126.11 )
48.1 134.68 ( 115.80 ) 149.11 ( 128.21 ) 134.13 ( 115.33 ) 148.00 ( 127.26 ) 133.61 ( 114.88 ) 146.97 ( 126.37 )
48.2 134.96 ( 116.04 ) 149.42 ( 128.48 ) 134.40 ( 115.57 ) 148.31 ( 127.52 ) 133.89 ( 115.12 ) 147.28 ( 126.64 )
48.3 135.24 ( 116.29 ) 149.73 ( 128.74 ) 134.68 ( 115.81 ) 148.62 ( 127.79 ) 134.17 ( 115.36 ) 147.58 ( 126.90 )
48.4 135.52 ( 116.53 ) 150.04 ( 129.01 ) 134.96 ( 116.05 ) 148.92 ( 128.05 ) 134.44 ( 115.60 ) 147.89 ( 127.16 )
48.5 135.80 ( 116.77 ) 150.35 ( 129.28 ) 135.24 ( 116.29 ) 149.23 ( 128.32 ) 134.72 ( 115.84 ) 148.19 ( 127.42 )
48.6 136.08 ( 117.01 ) 150.66 ( 129.54 ) 135.52 ( 116.53 ) 149.54 ( 128.58 ) 135.00 ( 116.08 ) 148.50 ( 127.69 )
48.7 136.36 ( 117.25 ) 150.97 ( 129.81 ) 135.80 ( 116.77 ) 149.85 ( 128.84 ) 135.28 ( 116.32 ) 148.81 ( 127.95 )
48.8 136.64 ( 117.49 ) 151.28 ( 130.08 ) 136.08 ( 117.01 ) 150.15 ( 129.11 ) 135.56 ( 116.56 ) 149.11 ( 128.21 )
48.9 136.92 ( 117.73 ) 151.59 ( 130.34 ) 136.36 ( 117.24 ) 150.46 ( 129.37 ) 135.83 ( 116.80 ) 149.42 ( 128.48 )
Table 38. Outdoor Unit Capacity (JTOR500~540VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (5)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-50FSXNS
JTOR500VAE(U,F,R)BS1 RAS-52FSXNS
JTOR520VAE(U,F,R)BS1 RAS-54FSXNS
JTOR540VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
49.0 137.20 ( 117.97 ) 151.90 ( 130.61 ) 136.63 ( 117.48 ) 150.77 ( 129.64 ) 136.11 ( 117.03 ) 149.72 ( 128.74 )
49.1 137.48 ( 118.21 ) 152.21 ( 130.88 ) 136.91 ( 117.72 ) 151.08 ( 129.90 ) 136.39 ( 117.27 ) 150.03 ( 129.00 )
49.2 137.76 ( 118.45 ) 152.52 ( 131.14 ) 137.19 ( 117.96 ) 151.38 ( 130.17 ) 136.67 ( 117.51 ) 150.33 ( 129.26 )
49.3 138.04 ( 118.69 ) 152.83 ( 131.41 ) 137.47 ( 118.20 ) 151.69 ( 130.43 ) 136.94 ( 117.75 ) 150.64 ( 129.53 )
49.4 138.32 ( 118.93 ) 153.14 ( 131.68 ) 137.75 ( 118.44 ) 152.00 ( 130.70 ) 137.22 ( 117.99 ) 150.94 ( 129.79 )
49.5 138.60 ( 119.17 ) 153.45 ( 131.94 ) 138.03 ( 118.68 ) 152.31 ( 130.96 ) 137.50 ( 118.23 ) 151.25 ( 130.05 )
49.6 138.88 ( 119.42 ) 153.76 ( 132.21 ) 138.31 ( 118.92 ) 152.62 ( 131.23 ) 137.78 ( 118.47 ) 151.56 ( 130.31 )
49.7 139.16 ( 119.66 ) 154.07 ( 132.48 ) 138.59 ( 119.16 ) 152.92 ( 131.49 ) 138.06 ( 118.71 ) 151.86 ( 130.58 )
49.8 139.44 ( 119.90 ) 154.38 ( 132.74 ) 138.87 ( 119.40 ) 153.23 ( 131.75 ) 138.33 ( 118.95 ) 152.17 ( 130.84 )
49.9 139.72 ( 120.14 ) 154.69 ( 133.01 ) 139.14 ( 119.64 ) 153.54 ( 132.02 ) 138.61 ( 119.18 ) 152.47 ( 131.10 )
50.0 140.00 ( 120.38 ) 155.00 ( 133.28 ) 139.42 ( 119.88 ) 153.85 ( 132.28 ) 138.89 ( 119.42 ) 152.78 ( 131.37 )
50.1 140.28 ( 120.62 ) 155.31 ( 133.54 ) 139.70 ( 120.12 ) 154.15 ( 132.55 ) 139.17 ( 119.66 ) 153.08 ( 131.63 )
50.2 140.56 ( 120.86 ) 155.62 ( 133.81 ) 139.98 ( 120.36 ) 154.46 ( 132.81 ) 139.44 ( 119.90 ) 153.39 ( 131.89 )
50.3 140.84 ( 121.10 ) 155.93 ( 134.08 ) 140.26 ( 120.60 ) 154.77 ( 133.08 ) 139.72 ( 120.14 ) 153.69 ( 132.15 )
50.4 141.12 ( 121.34 ) 156.24 ( 134.34 ) 140.54 ( 120.84 ) 155.08 ( 133.34 ) 140.00 ( 120.38 ) 154.00 ( 132.42 )
50.5 141.40 ( 121.58 ) 156.55 ( 134.61 ) 140.82 ( 121.08 ) 155.38 ( 133.61 ) 140.28 ( 120.62 ) 154.31 ( 132.68 )
50.6 141.68 ( 121.82 ) 156.86 ( 134.88 ) 141.10 ( 121.32 ) 155.69 ( 133.87 ) 140.56 ( 120.86 ) 154.61 ( 132.94 )
50.7 141.96 ( 122.06 ) 157.17 ( 135.14 ) 141.38 ( 121.56 ) 156.00 ( 134.14 ) 140.83 ( 121.09 ) 154.92 ( 133.20 )
50.8 142.24 ( 122.30 ) 157.48 ( 135.41 ) 141.65 ( 121.80 ) 156.31 ( 134.40 ) 141.11 ( 121.33 ) 155.22 ( 133.47 )
50.9 142.52 ( 122.55 ) 157.79 ( 135.67 ) 141.93 ( 122.04 ) 156.62 ( 134.66 ) 141.39 ( 121.57 ) 155.53 ( 133.73 )
51.0 142.80 ( 122.79 ) 158.10 ( 135.94 ) 142.21 ( 122.28 ) 156.92 ( 134.93 ) 141.67 ( 121.81 ) 155.83 ( 133.99 )
51.1 143.08 ( 123.03 ) 158.41 ( 136.21 ) 142.49 ( 122.52 ) 157.23 ( 135.19 ) 141.94 ( 122.05 ) 156.14 ( 134.26 )
51.2 143.36 ( 123.27 ) 158.72 ( 136.47 ) 142.77 ( 122.76 ) 157.54 ( 135.46 ) 142.22 ( 122.29 ) 156.44 ( 134.52 )
51.3 143.64 ( 123.51 ) 159.03 ( 136.74 ) 143.05 ( 123.00 ) 157.85 ( 135.72 ) 142.50 ( 122.53 ) 156.75 ( 134.78 )
51.4 143.92 ( 123.75 ) 159.34 ( 137.01 ) 143.33 ( 123.24 ) 158.15 ( 135.99 ) 142.78 ( 122.77 ) 157.06 ( 135.04 )
51.5 144.20 ( 123.99 ) 159.65 ( 137.27 ) 143.61 ( 123.48 ) 158.46 ( 136.25 ) 143.06 ( 123.01 ) 157.36 ( 135.31 )
51.6 144.23 ( 124.02 ) 159.66 ( 137.28 ) 143.88 ( 123.72 ) 158.77 ( 136.52 ) 143.33 ( 123.24 ) 157.67 ( 135.57 )
51.7 144.26 ( 124.04 ) 159.67 ( 137.29 ) 144.16 ( 123.96 ) 159.08 ( 136.78 ) 143.61 ( 123.48 ) 157.97 ( 135.83 )
51.8 144.29 ( 124.07 ) 159.68 ( 137.30 ) 144.44 ( 124.20 ) 159.38 ( 137.05 ) 143.89 ( 123.72 ) 158.28 ( 136.09 )
51.9 144.32 ( 124.10 ) 159.70 ( 137.31 ) 144.72 ( 124.44 ) 159.69 ( 137.31 ) 144.17 ( 123.96 ) 158.58 ( 136.36 )
52.0 144.36 ( 124.12 ) 159.71 ( 137.32 ) 145.00 ( 124.68 ) 160.00 ( 137.58 ) 144.44 ( 124.20 ) 158.89 ( 136.62 )
52.1 144.39 ( 124.15 ) 159.72 ( 137.33 ) 145.28 ( 124.92 ) 160.31 ( 137.84 ) 144.72 ( 124.44 ) 159.19 ( 136.88 )
52.2 144.42 ( 124.18 ) 159.73 ( 137.34 ) 145.56 ( 125.16 ) 160.62 ( 138.10 ) 145.00 ( 124.68 ) 159.50 ( 137.15 )
52.3 144.45 ( 124.20 ) 159.74 ( 137.35 ) 145.84 ( 125.40 ) 160.92 ( 138.37 ) 145.28 ( 124.92 ) 159.81 ( 137.41 )
52.4 144.48 ( 124.23 ) 159.75 ( 137.36 ) 146.12 ( 125.64 ) 161.23 ( 138.63 ) 145.56 ( 125.16 ) 160.11 ( 137.67 )
52.5 144.51 ( 124.26 ) 159.76 ( 137.37 ) 146.39 ( 125.88 ) 161.54 ( 138.90 ) 145.83 ( 125.39 ) 160.42 ( 137.93 )
52.6 144.54 ( 124.28 ) 159.78 ( 137.38 ) 146.67 ( 126.12 ) 161.85 ( 139.16 ) 146.11 ( 125.63 ) 160.72 ( 138.20 )
52.7 144.57 ( 124.31 ) 159.79 ( 137.39 ) 146.95 ( 126.36 ) 162.15 ( 139.43 ) 146.39 ( 125.87 ) 161.03 ( 138.46 )
52.8 144.60 ( 124.34 ) 159.80 ( 137.40 ) 147.23 ( 126.60 ) 162.46 ( 139.69 ) 146.67 ( 126.11 ) 161.33 ( 138.72 )
52.9 144.64 ( 124.36 ) 159.81 ( 137.41 ) 147.51 ( 126.84 ) 162.77 ( 139.96 ) 146.94 ( 126.35 ) 161.64 ( 138.98 )
53.0 144.67 ( 124.39 ) 159.82 ( 137.42 ) 147.79 ( 127.08 ) 163.08 ( 140.22 ) 147.22 ( 126.59 ) 161.94 ( 139.25 )
53.1 144.70 ( 124.42 ) 159.83 ( 137.43 ) 148.07 ( 127.31 ) 163.38 ( 140.49 ) 147.50 ( 126.83 ) 162.25 ( 139.51 )
53.2 144.73 ( 124.44 ) 159.85 ( 137.44 ) 148.35 ( 127.55 ) 163.69 ( 140.75 ) 147.78 ( 127.07 ) 162.56 ( 139.77 )
53.3 144.76 ( 124.47 ) 159.86 ( 137.45 ) 148.63 ( 127.79 ) 164.00 ( 141.01 ) 148.06 ( 127.30 ) 162.86 ( 140.04 )
53.4 144.79 ( 124.50 ) 159.87 ( 137.46 ) 148.90 ( 128.03 ) 164.31 ( 141.28 ) 148.33 ( 127.54 ) 163.17 ( 140.30 )
53.5 144.82 ( 124.52 ) 159.88 ( 137.47 ) 149.18 ( 128.27 ) 164.62 ( 141.54 ) 148.61 ( 127.78 ) 163.47 ( 140.56 )
53.6 144.85 ( 124.55 ) 159.89 ( 137.48 ) 149.36 ( 128.43 ) 164.80 ( 141.71 ) 148.89 ( 128.02 ) 163.78 ( 140.82 )
53.7 144.88 ( 124.58 ) 159.90 ( 137.49 ) 149.39 ( 128.46 ) 164.82 ( 141.72 ) 149.17 ( 128.26 ) 164.08 ( 141.09 )
53.8 144.92 ( 124.60 ) 159.91 ( 137.50 ) 149.42 ( 128.48 ) 164.83 ( 141.73 ) 149.44 ( 128.50 ) 164.39 ( 141.35 )
53.9 144.95 ( 124.63 ) 159.93 ( 137.51 ) 149.46 ( 128.51 ) 164.84 ( 141.74 ) 149.72 ( 128.74 ) 164.69 ( 141.61 )
54.0 144.98 ( 124.66 ) 159.94 ( 137.52 ) 149.49 ( 128.54 ) 164.85 ( 141.75 ) 150.00 ( 128.98 ) 165.00 ( 141.87 )
54.1 145.01 ( 124.69 ) 159.95 ( 137.53 ) 149.52 ( 128.56 ) 164.86 ( 141.76 ) 150.28 ( 129.22 ) 165.31 ( 142.14 )
54.2 145.04 ( 124.71 ) 159.96 ( 137.54 ) 149.55 ( 128.59 ) 164.87 ( 141.77 ) 150.56 ( 129.45 ) 165.61 ( 142.40 )
54.3 145.07 ( 124.74 ) 159.97 ( 137.55 ) 149.58 ( 128.62 ) 164.88 ( 141.78 ) 150.83 ( 129.69 ) 165.92 ( 142.66 )
54.4 145.10 ( 124.77 ) 159.98 ( 137.56 ) 149.61 ( 128.64 ) 164.90 ( 141.78 ) 151.11 ( 129.93 ) 166.22 ( 142.93 )
54.5 145.13 ( 124.79 ) 159.99 ( 137.57 ) 149.64 ( 128.67 ) 164.91 ( 141.79 ) 151.39 ( 130.17 ) 166.53 ( 143.19 )
54.6 145.16 ( 124.82 ) 160.01 ( 137.58 ) 149.67 ( 128.69 ) 164.92 ( 141.80 ) 151.67 ( 130.41 ) 166.83 ( 143.45 )
54.7 145.20 ( 124.85 ) 160.02 ( 137.59 ) 149.70 ( 128.72 ) 164.93 ( 141.81 ) 151.94 ( 130.65 ) 167.14 ( 143.71 )
54.8 145.23 ( 124.87 ) 160.03 ( 137.60 ) 149.73 ( 128.75 ) 164.94 ( 141.82 ) 152.22 ( 130.89 ) 167.44 ( 143.98 )
54.9 145.26 ( 124.90 ) 160.04 ( 137.61 ) 149.77 ( 128.77 ) 164.95 ( 141.83 ) 152.50 ( 131.13 ) 167.75 ( 144.24 )
Table 39. Outdoor Unit Capacity (JTOR500~540VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (6)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-50FSXNS
JTOR500VAE(U,F,R)BS1 RAS-52FSXNS
JTOR520VAE(U,F,R)BS1 RAS-54FSXNS
JTOR540VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
55.0 145.29 ( 124.93 ) 160.05 ( 137.62 ) 149.80 ( 128.80 ) 164.96 ( 141.84 ) 152.78 ( 131.37 ) 168.06 ( 144.50 )
55.1 145.32 ( 124.95 ) 160.06 ( 137.63 ) 149.83 ( 128.83 ) 164.98 ( 141.85 ) 153.06 ( 131.60 ) 168.36 ( 144.76 )
55.2 145.35 ( 124.98 ) 160.07 ( 137.64 ) 149.86 ( 128.85 ) 164.99 ( 141.86 ) 153.33 ( 131.84 ) 168.67 ( 145.03 )
55.3 145.38 ( 125.01 ) 160.09 ( 137.65 ) 149.89 ( 128.88 ) 165.00 ( 141.87 ) 153.61 ( 132.08 ) 168.97 ( 145.29 )
55.4 145.41 ( 125.03 ) 160.10 ( 137.66 ) 149.92 ( 128.91 ) 165.01 ( 141.88 ) 153.89 ( 132.32 ) 169.28 ( 145.55 )
55.5 145.44 ( 125.06 ) 160.11 ( 137.67 ) 149.95 ( 128.93 ) 165.02 ( 141.89 ) 154.17 ( 132.56 ) 169.58 ( 145.82 )
55.6 145.48 ( 125.09 ) 160.12 ( 137.68 ) 149.98 ( 128.96 ) 165.03 ( 141.90 ) 154.44 ( 132.80 ) 169.89 ( 146.08 )
55.7 145.51 ( 125.11 ) 160.13 ( 137.69 ) 150.01 ( 128.99 ) 165.04 ( 141.91 ) 154.52 ( 132.87 ) 169.96 ( 146.14 )
55.8 145.54 ( 125.14 ) 160.14 ( 137.70 ) 150.04 ( 129.01 ) 165.06 ( 141.92 ) 154.56 ( 132.89 ) 169.97 ( 146.15 )
55.9 145.57 ( 125.17 ) 160.16 ( 137.71 ) 150.08 ( 129.04 ) 165.07 ( 141.93 ) 154.59 ( 132.92 ) 169.98 ( 146.16 )
56.0 145.60 ( 125.19 ) 160.17 ( 137.72 ) 150.11 ( 129.07 ) 165.08 ( 141.94 ) 154.62 ( 132.95 ) 169.99 ( 146.17 )
56.1 145.63 ( 125.22 ) 160.18 ( 137.73 ) 150.14 ( 129.09 ) 165.09 ( 141.95 ) 154.65 ( 132.97 ) 170.00 ( 146.18 )
56.2 145.66 ( 125.25 ) 160.19 ( 137.74 ) 150.17 ( 129.12 ) 165.10 ( 141.96 ) 154.68 ( 133.00 ) 170.02 ( 146.19 )
56.3 145.69 ( 125.27 ) 160.20 ( 137.75 ) 150.20 ( 129.15 ) 165.11 ( 141.97 ) 154.71 ( 133.03 ) 170.03 ( 146.20 )
56.4 145.72 ( 125.30 ) 160.21 ( 137.76 ) 150.23 ( 129.17 ) 165.12 ( 141.98 ) 154.74 ( 133.05 ) 170.04 ( 146.21 )
56.5 145.76 ( 125.33 ) 160.22 ( 137.77 ) 150.26 ( 129.20 ) 165.14 ( 141.99 ) 154.77 ( 133.08 ) 170.05 ( 146.22 )
56.6 145.79 ( 125.35 ) 160.24 ( 137.78 ) 150.29 ( 129.23 ) 165.15 ( 142.00 ) 154.80 ( 133.11 ) 170.06 ( 146.23 )
56.7 145.82 ( 125.38 ) 160.25 ( 137.79 ) 150.32 ( 129.25 ) 165.16 ( 142.01 ) 154.83 ( 133.13 ) 170.07 ( 146.24 )
56.8 145.85 ( 125.41 ) 160.26 ( 137.80 ) 150.35 ( 129.28 ) 165.17 ( 142.02 ) 154.86 ( 133.16 ) 170.08 ( 146.25 )
56.9 145.88 ( 125.43 ) 160.27 ( 137.81 ) 150.38 ( 129.31 ) 165.18 ( 142.03 ) 154.90 ( 133.19 ) 170.09 ( 146.26 )
57.0 145.91 ( 125.46 ) 160.28 ( 137.82 ) 150.42 ( 129.33 ) 165.19 ( 142.04 ) 154.93 ( 133.21 ) 170.11 ( 146.26 )
57.1 145.94 ( 125.49 ) 160.29 ( 137.83 ) 150.45 ( 129.36 ) 165.20 ( 142.05 ) 154.96 ( 133.24 ) 170.12 ( 146.27 )
57.2 145.97 ( 125.51 ) 160.30 ( 137.84 ) 150.48 ( 129.39 ) 165.21 ( 142.06 ) 154.99 ( 133.27 ) 170.13 ( 146.28 )
57.3 146.00 ( 125.54 ) 160.32 ( 137.85 ) 150.51 ( 129.41 ) 165.23 ( 142.07 ) 155.02 ( 133.29 ) 170.14 ( 146.29 )
57.4 146.04 ( 125.57 ) 160.33 ( 137.86 ) 150.54 ( 129.44 ) 165.24 ( 142.08 ) 155.05 ( 133.32 ) 170.15 ( 146.30 )
57.5 146.07 ( 125.59 ) 160.34 ( 137.87 ) 150.57 ( 129.47 ) 165.25 ( 142.09 ) 155.08 ( 133.35 ) 170.16 ( 146.31 )
57.6 146.10 ( 125.62 ) 160.35 ( 137.88 ) 150.60 ( 129.49 ) 165.26 ( 142.10 ) 155.11 ( 133.37 ) 170.17 ( 146.32 )
57.7 146.13 ( 125.65 ) 160.36 ( 137.89 ) 150.63 ( 129.52 ) 165.27 ( 142.11 ) 155.14 ( 133.40 ) 170.19 ( 146.33 )
57.8 146.16 ( 125.67 ) 160.37 ( 137.90 ) 150.66 ( 129.55 ) 165.28 ( 142.12 ) 155.17 ( 133.42 ) 170.20 ( 146.34 )
57.9 146.19 ( 125.70 ) 160.38 ( 137.91 ) 150.69 ( 129.57 ) 165.29 ( 142.13 ) 155.20 ( 133.45 ) 170.21 ( 146.35 )
58.0 146.22 ( 125.73 ) 160.40 ( 137.92 ) 150.73 ( 129.60 ) 165.31 ( 142.14 ) 155.23 ( 133.48 ) 170.22 ( 146.36 )
58.1 146.25 ( 125.76 ) 160.41 ( 137.93 ) 150.76 ( 129.63 ) 165.32 ( 142.15 ) 155.27 ( 133.50 ) 170.23 ( 146.37 )
58.2 146.28 ( 125.78 ) 160.42 ( 137.94 ) 150.79 ( 129.65 ) 165.33 ( 142.16 ) 155.30 ( 133.53 ) 170.24 ( 146.38 )
58.3 146.32 ( 125.81 ) 160.43 ( 137.95 ) 150.82 ( 129.68 ) 165.34 ( 142.17 ) 155.33 ( 133.56 ) 170.25 ( 146.39 )
58.4 146.35 ( 125.84 ) 160.44 ( 137.96 ) 150.85 ( 129.71 ) 165.35 ( 142.18 ) 155.36 ( 133.58 ) 170.26 ( 146.40 )
58.5 146.38 ( 125.86 ) 160.45 ( 137.97 ) 150.88 ( 129.73 ) 165.36 ( 142.19 ) 155.39 ( 133.61 ) 170.28 ( 146.41 )
58.6 146.41 ( 125.89 ) 160.47 ( 137.98 ) 150.91 ( 129.76 ) 165.37 ( 142.20 ) 155.42 ( 133.64 ) 170.29 ( 146.42 )
58.7 146.44 ( 125.92 ) 160.48 ( 137.99 ) 150.94 ( 129.79 ) 165.39 ( 142.21 ) 155.45 ( 133.66 ) 170.30 ( 146.43 )
58.8 146.47 ( 125.94 ) 160.49 ( 137.99 ) 150.97 ( 129.81 ) 165.40 ( 142.22 ) 155.48 ( 133.69 ) 170.31 ( 146.44 )
58.9 146.50 ( 125.97 ) 160.50 ( 138.00 ) 151.00 ( 129.84 ) 165.41 ( 142.23 ) 155.51 ( 133.72 ) 170.32 ( 146.45 )
59.0 146.53 ( 126.00 ) 160.51 ( 138.01 ) 151.04 ( 129.87 ) 165.42 ( 142.24 ) 155.54 ( 133.74 ) 170.33 ( 146.46 )
59.1 146.56 ( 126.02 ) 160.52 ( 138.02 ) 151.07 ( 129.89 ) 165.43 ( 142.25 ) 155.57 ( 133.77 ) 170.34 ( 146.47 )
59.2 146.60 ( 126.05 ) 160.53 ( 138.03 ) 151.10 ( 129.92 ) 165.44 ( 142.26 ) 155.60 ( 133.80 ) 170.36 ( 146.48 )
59.3 146.63 ( 126.08 ) 160.55 ( 138.04 ) 151.13 ( 129.95 ) 165.45 ( 142.26 ) 155.64 ( 133.82 ) 170.37 ( 146.49 )
59.4 146.66 ( 126.10 ) 160.56 ( 138.05 ) 151.16 ( 129.97 ) 165.47 ( 142.27 ) 155.67 ( 133.85 ) 170.38 ( 146.50 )
59.5 146.69 ( 126.13 ) 160.57 ( 138.06 ) 151.19 ( 130.00 ) 165.48 ( 142.28 ) 155.70 ( 133.88 ) 170.39 ( 146.51 )
59.6 146.72 ( 126.16 ) 160.58 ( 138.07 ) 151.22 ( 130.03 ) 165.49 ( 142.29 ) 155.73 ( 133.90 ) 170.40 ( 146.52 )
59.7 146.75 ( 126.18 ) 160.59 ( 138.08 ) 151.25 ( 130.05 ) 165.50 ( 142.30 ) 155.76 ( 133.93 ) 170.41 ( 146.53 )
59.8 146.78 ( 126.21 ) 160.60 ( 138.09 ) 151.28 ( 130.08 ) 165.51 ( 142.31 ) 155.79 ( 133.96 ) 170.42 ( 146.54 )
59.9 146.81 ( 126.24 ) 160.61 ( 138.10 ) 151.31 ( 130.11 ) 165.52 ( 142.32 ) 155.82 ( 133.98 ) 170.43 ( 146.55 )
60.0 146.84 ( 126.26 ) 160.63 ( 138.11 ) 151.35 ( 130.13 ) 165.53 ( 142.33 ) 155.85 ( 134.01 ) 170.45 ( 146.56 )
60.1 146.88 ( 126.29 ) 160.64 ( 138.12 ) 151.38 ( 130.16 ) 165.55 ( 142.34 ) 155.88 ( 134.04 ) 170.46 ( 146.57 )
60.2 146.91 ( 126.32 ) 160.65 ( 138.13 ) 151.41 ( 130.19 ) 165.56 ( 142.35 ) 155.91 ( 134.06 ) 170.47 ( 146.58 )
60.3 146.94 ( 126.34 ) 160.66 ( 138.14 ) 151.44 ( 130.21 ) 165.57 ( 142.36 ) 155.94 ( 134.09 ) 170.48 ( 146.59 )
60.4 146.97 ( 126.37 ) 160.67 ( 138.15 ) 151.47 ( 130.24 ) 165.58 ( 142.37 ) 155.98 ( 134.11 ) 170.49 ( 146.60 )
60.5 147.00 ( 126.40 ) 160.68 ( 138.16 ) 151.50 ( 130.27 ) 165.59 ( 142.38 ) 156.01 ( 134.14 ) 170.50 ( 146.61 )
60.6 147.03 ( 126.42 ) 160.69 ( 138.17 ) 151.53 ( 130.29 ) 165.60 ( 142.39 ) 156.04 ( 134.17 ) 170.51 ( 146.62 )
60.7 147.06 ( 126.45 ) 160.71 ( 138.18 ) 151.56 ( 130.32 ) 165.61 ( 142.40 ) 156.07 ( 134.19 ) 170.52 ( 146.63 )
60.8 147.09 ( 126.48 ) 160.72 ( 138.19 ) 151.59 ( 130.35 ) 165.63 ( 142.41 ) 156.10 ( 134.22 ) 170.54 ( 146.63 )
60.9 147.12 ( 126.50 ) 160.73 ( 138.20 ) 151.62 ( 130.37 ) 165.64 ( 142.42 ) 156.13 ( 134.25 ) 170.55 ( 146.64 )
Table 40. Outdoor Unit Capacity (JTOR500~540VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (7)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-50FSXNS
JTOR500VAE(U,F,R)BS1 RAS-52FSXNS
JTOR520VAE(U,F,R)BS1 RAS-54FSXNS
JTOR540VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
61.0 147.16 ( 126.53 ) 160.74 ( 138.21 ) 151.66 ( 130.40 ) 165.65 ( 142.43 ) 156.16 ( 134.27 ) 170.56 ( 146.65 )
61.1 147.19 ( 126.56 ) 160.75 ( 138.22 ) 151.69 ( 130.43 ) 165.66 ( 142.44 ) 156.19 ( 134.30 ) 170.57 ( 146.66 )
61.2 147.22 ( 126.58 ) 160.76 ( 138.23 ) 151.72 ( 130.45 ) 165.67 ( 142.45 ) 156.22 ( 134.33 ) 170.58 ( 146.67 )
61.3 147.25 ( 126.61 ) 160.78 ( 138.24 ) 151.75 ( 130.48 ) 165.68 ( 142.46 ) 156.25 ( 134.35 ) 170.59 ( 146.68 )
61.4 147.28 ( 126.64 ) 160.79 ( 138.25 ) 151.78 ( 130.51 ) 165.69 ( 142.47 ) 156.28 ( 134.38 ) 170.60 ( 146.69 )
61.5 147.31 ( 126.66 ) 160.80 ( 138.26 ) 151.81 ( 130.53 ) 165.70 ( 142.48 ) 156.31 ( 134.41 ) 170.62 ( 146.70 )
61.6 147.34 ( 126.69 ) 160.81 ( 138.27 ) 151.84 ( 130.56 ) 165.72 ( 142.49 ) 156.35 ( 134.43 ) 170.63 ( 146.71 )
61.7 147.37 ( 126.72 ) 160.82 ( 138.28 ) 151.87 ( 130.59 ) 165.73 ( 142.50 ) 156.38 ( 134.46 ) 170.64 ( 146.72 )
61.8 147.40 ( 126.75 ) 160.83 ( 138.29 ) 151.90 ( 130.61 ) 165.74 ( 142.51 ) 156.41 ( 134.49 ) 170.65 ( 146.73 )
61.9 147.44 ( 126.77 ) 160.84 ( 138.30 ) 151.93 ( 130.64 ) 165.75 ( 142.52 ) 156.44 ( 134.51 ) 170.66 ( 146.74 )
62.0 147.47 ( 126.80 ) 160.86 ( 138.31 ) 151.96 ( 130.67 ) 165.76 ( 142.53 ) 156.47 ( 134.54 ) 170.67 ( 146.75 )
62.1 147.50 ( 126.83 ) 160.87 ( 138.32 ) 152.00 ( 130.69 ) 165.77 ( 142.54 ) 156.50 ( 134.57 ) 170.68 ( 146.76 )
62.2 147.53 ( 126.85 ) 160.88 ( 138.33 ) 152.03 ( 130.72 ) 165.78 ( 142.55 ) 156.53 ( 134.59 ) 170.69 ( 146.77 )
62.3 147.56 ( 126.88 ) 160.89 ( 138.34 ) 152.06 ( 130.75 ) 165.80 ( 142.56 ) 156.56 ( 134.62 ) 170.71 ( 146.78 )
62.4 147.59 ( 126.91 ) 160.90 ( 138.35 ) 152.09 ( 130.77 ) 165.81 ( 142.57 ) 156.59 ( 134.65 ) 170.72 ( 146.79 )
62.5 147.62 ( 126.93 ) 160.91 ( 138.36 ) 152.12 ( 130.80 ) 165.82 ( 142.58 ) 156.62 ( 134.67 ) 170.73 ( 146.80 )
62.6 147.65 ( 126.96 ) 160.92 ( 138.37 ) 152.15 ( 130.83 ) 165.83 ( 142.59 ) 156.65 ( 134.70 ) 170.74 ( 146.81 )
62.7 147.68 ( 126.99 ) 160.94 ( 138.38 ) 152.18 ( 130.85 ) 165.84 ( 142.60 ) 156.69 ( 134.73 ) 170.75 ( 146.82 )
62.8 147.72 ( 127.01 ) 160.95 ( 138.39 ) 152.21 ( 130.88 ) 165.85 ( 142.61 ) 156.72 ( 134.75 ) 170.76 ( 146.83 )
62.9 147.75 ( 127.04 ) 160.96 ( 138.40 ) 152.24 ( 130.91 ) 165.86 ( 142.62 ) 156.75 ( 134.78 ) 170.77 ( 146.84 )
63.0 147.78 ( 127.07 ) 160.97 ( 138.41 ) 152.27 ( 130.93 ) 165.88 ( 142.63 ) 156.78 ( 134.80 ) 170.79 ( 146.85 )
63.1 147.81 ( 127.09 ) 160.98 ( 138.42 ) 152.31 ( 130.96 ) 165.89 ( 142.64 ) 156.81 ( 134.83 ) 170.80 ( 146.86 )
63.2 147.84 ( 127.12 ) 160.99 ( 138.43 ) 152.34 ( 130.99 ) 165.90 ( 142.65 ) 156.84 ( 134.86 ) 170.81 ( 146.87 )
63.3 147.87 ( 127.15 ) 161.00 ( 138.44 ) 152.37 ( 131.01 ) 165.91 ( 142.66 ) 156.87 ( 134.88 ) 170.82 ( 146.88 )
63.4 147.90 ( 127.17 ) 161.02 ( 138.45 ) 152.40 ( 131.04 ) 165.92 ( 142.67 ) 156.90 ( 134.91 ) 170.83 ( 146.89 )
63.5 147.93 ( 127.20 ) 161.03 ( 138.46 ) 152.43 ( 131.07 ) 165.93 ( 142.68 ) 156.93 ( 134.94 ) 170.84 ( 146.90 )
63.6 147.96 ( 127.23 ) 161.04 ( 138.47 ) 152.46 ( 131.09 ) 165.94 ( 142.69 ) 156.96 ( 134.96 ) 170.85 ( 146.91 )
63.7 148.00 ( 127.25 ) 161.05 ( 138.48 ) 152.49 ( 131.12 ) 165.96 ( 142.70 ) 156.99 ( 134.99 ) 170.86 ( 146.92 )
63.8 148.03 ( 127.28 ) 161.06 ( 138.49 ) 152.52 ( 131.15 ) 165.97 ( 142.71 ) 157.02 ( 135.02 ) 170.88 ( 146.93 )
63.9 148.06 ( 127.31 ) 161.07 ( 138.50 ) 152.55 ( 131.17 ) 165.98 ( 142.72 ) 157.06 ( 135.04 ) 170.89 ( 146.94 )
64.0 148.09 ( 127.33 ) 161.09 ( 138.51 ) 152.58 ( 131.20 ) 165.99 ( 142.73 ) 157.09 ( 135.07 ) 170.90 ( 146.95 )
64.1 148.12 ( 127.36 ) 161.10 ( 138.52 ) 152.62 ( 131.23 ) 166.00 ( 142.74 ) 157.12 ( 135.10 ) 170.91 ( 146.96 )
64.2 148.15 ( 127.39 ) 161.11 ( 138.53 ) 152.65 ( 131.25 ) 166.01 ( 142.75 ) 157.15 ( 135.12 ) 170.92 ( 146.97 )
64.3 148.18 ( 127.41 ) 161.12 ( 138.54 ) 152.68 ( 131.28 ) 166.02 ( 142.75 ) 157.18 ( 135.15 ) 170.93 ( 146.98 )
64.4 148.21 ( 127.44 ) 161.13 ( 138.55 ) 152.71 ( 131.31 ) 166.04 ( 142.76 ) 157.21 ( 135.18 ) 170.94 ( 146.99 )
64.5 148.24 ( 127.47 ) 161.14 ( 138.56 ) 152.74 ( 131.33 ) 166.05 ( 142.77 ) 157.24 ( 135.20 ) 170.95 ( 146.99 )
64.6 148.28 ( 127.49 ) 161.15 ( 138.57 ) 152.77 ( 131.36 ) 166.06 ( 142.78 ) 157.27 ( 135.23 ) 170.97 ( 147.00 )
64.7 148.31 ( 127.52 ) 161.17 ( 138.58 ) 152.80 ( 131.39 ) 166.07 ( 142.79 ) 157.30 ( 135.26 ) 170.98 ( 147.01 )
64.8 148.34 ( 127.55 ) 161.18 ( 138.59 ) 152.83 ( 131.41 ) 166.08 ( 142.80 ) 157.33 ( 135.28 ) 170.99 ( 147.02 )
64.9 148.37 ( 127.57 ) 161.19 ( 138.60 ) 152.86 ( 131.44 ) 166.09 ( 142.81 ) 157.36 ( 135.31 ) 171.00 ( 147.03 )
65.0 148.40 ( 127.60 ) 161.20 ( 138.61 ) 152.89 ( 131.47 ) 166.10 ( 142.82 ) 157.40 ( 135.34 ) 171.01 ( 147.04 )
65.1 152.93 ( 131.49 ) 166.12 ( 142.83 ) 157.43 ( 135.36 ) 171.02 ( 147.05 )
65.2 152.96 ( 131.52 ) 166.13 ( 142.84 ) 157.46 ( 135.39 ) 171.03 ( 147.06 )
65.3 152.99 ( 131.55 ) 166.14 ( 142.85 ) 157.49 ( 135.42 ) 171.05 ( 147.07 )
65.4 153.02 ( 131.57 ) 166.15 ( 142.86 ) 157.52 ( 135.44 ) 171.06 ( 147.08 )
65.5 153.05 ( 131.60 ) 166.16 ( 142.87 ) 157.55 ( 135.47 ) 171.07 ( 147.09 )
65.6 153.08 ( 131.63 ) 166.17 ( 142.88 ) 157.58 ( 135.49 ) 171.08 ( 147.10 )
65.7 153.11 ( 131.65 ) 166.18 ( 142.89 ) 157.61 ( 135.52 ) 171.09 ( 147.11 )
65.8 153.14 ( 131.68 ) 166.19 ( 142.90 ) 157.64 ( 135.55 ) 171.10 ( 147.12 )
65.9 153.17 ( 131.71 ) 166.21 ( 142.91 ) 157.67 ( 135.57 ) 171.11 ( 147.13 )
66.0 _ 153.20 ( 131.73 ) 166.22 ( 142.92 ) 157.70 ( 135.60 ) 171.12 ( 147.14 )
66.1 153.24 ( 131.76 ) 166.23 ( 142.93 ) 157.73 ( 135.63 ) 171.14 ( 147.15 )
66.2 153.27 ( 131.79 ) 166.24 ( 142.94 ) 157.77 ( 135.65 ) 171.15 ( 147.16 )
66.3 153.30 ( 131.81 ) 166.25 ( 142.95 ) 157.80 ( 135.68 ) 171.16 ( 147.17 )
66.4 153.33 ( 131.84 ) 166.26 ( 142.96 ) 157.83 ( 135.71 ) 171.17 ( 147.18 )
66.5 153.36 ( 131.87 ) 166.27 ( 142.97 ) 157.86 ( 135.73 ) 171.18 ( 147.19 )
66.6 153.39 ( 131.89 ) 166.29 ( 142.98 ) 157.89 ( 135.76 ) 171.19 ( 147.20 )
66.7 153.42 ( 131.92 ) 166.30 ( 142.99 ) 157.92 ( 135.79 ) 171.20 ( 147.21 )
66.8 153.45 ( 131.95 ) 166.31 ( 143.00 ) 157.95 ( 135.81 ) 171.22 ( 147.22 )
66.9 153.48 ( 131.97 ) 166.32 ( 143.01 ) 157.98 ( 135.84 ) 171.23 ( 147.23 )
Table 41. Outdoor Unit Capacity (JTOR500~540VAE(U,F,R)BS1) with Total Horsepower of Combined Indoor Unit (8)
Total Outdoor Unit Capacity: kW (×1000kcal/h)
RAS-50FSXNS
JTOR500VAE(U,F,R)BS1 RAS-52FSXNS
JTOR520VAE(U,F,R)BS1 RAS-54FSXNS
JTOR540VAE(U,F,R)BS1
Cooling Heating Cooling Heating Cooling Heating
67.0 153.51 ( 132.00 ) 166.33 ( 143.02 ) 158.01 ( 135.87 ) 171.24 ( 147.24 )
67.1 153.55 ( 132.03 ) 166.34 ( 143.03 ) 158.04 ( 135.89 ) 171.25 ( 147.25 )
67.2 153.58 ( 132.05 ) 166.35 ( 143.04 ) 158.07 ( 135.92 ) 171.26 ( 147.26 )
67.3 153.61 ( 132.08 ) 166.37 ( 143.05 ) 158.10 ( 135.95 ) 171.27 ( 147.27 )
67.4 153.64 ( 132.10 ) 166.38 ( 143.06 ) 158.14 ( 135.97 ) 171.28 ( 147.28 )
67.5 153.67 ( 132.13 ) 166.39 ( 143.07 ) 158.17 ( 136.00 ) 171.29 ( 147.29 )
67.6 153.70 ( 132.16 ) 166.40 ( 143.08 ) 158.20 ( 136.03 ) 171.31 ( 147.30 )
67.7 158.23 ( 136.05 ) 171.32 ( 147.31 )
67.8 158.26 ( 136.08 ) 171.33 ( 147.32 )
67.9 158.29 ( 136.11 ) 171.34 ( 147.33 )
68.0 158.32 ( 136.13 ) 171.35 ( 147.34 )
68.1 158.35 ( 136.16 ) 171.36 ( 147.35 )
68.2 158.38 ( 136.18 ) 171.37 ( 147.35 )
68.3 158.41 ( 136.21 ) 171.38 ( 147.36 )
68.4 158.44 ( 136.24 ) 171.40 ( 147.37 )
68.5 158.48 ( 136.26 ) 171.41 ( 147.38 )
68.6 _ 158.51 ( 136.29 ) 171.42 ( 147.39 )
68.7 158.54 ( 136.32 ) 171.43 ( 147.40 )
68.8 158.57 ( 136.34 ) 171.44 ( 147.41 )
68.9 158.60 ( 136.37 ) 171.45 ( 147.42 )
_
69.0 158.63 ( 136.40 ) 171.46 ( 147.43 )
69.1 158.66 ( 136.42 ) 171.48 ( 147.44 )
69.2 158.69 ( 136.45 ) 171.49 ( 147.45 )
69.3 158.72 ( 136.48 ) 171.50 ( 147.46 )
69.4 158.75 ( 136.50 ) 171.51 ( 147.47 )
69.5 158.78 ( 136.53 ) 171.52 ( 147.48 )
69.6 158.81 ( 136.56 ) 171.53 ( 147.49 )
69.7 158.85 ( 136.58 ) 171.54 ( 147.50 )
69.8 158.88 ( 136.61 ) 171.55 ( 147.51 )
69.9 158.91 ( 136.64 ) 171.57 ( 147.52 )
70.0 158.94 ( 136.66 ) 171.58 ( 147.53 )
70.1 158.97 ( 136.69 ) 171.59 ( 147.54 )
70.2 159.00 ( 136.72 ) 171.60 ( 147.55 )
6.3 Outdoor Unit Capacity According to Temperature Condition and Connected IDU Capacity
Ratio (Part Load Data)
NOTE:
If EL is more than 100m, increase both Liquid Pipe and Gas Pipe by 1 size.
NOTE:
The correction factor is not available for the special condition like a snowfall or a operation in a transitional
period.
7. Electrical Data
VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
HZ: Frequency (Hz) IPT: Input (kW)
STC: Starting Current (A)
NOTES:
1. The above compressor data is based on 100% capacity combination of the indoor units at rated operating frequency.
2. The above performance data is based on the equivalent piping length of each unit horsepower and 0m piping lift.
3. These data are based on the same conditions as the nominal heating and cooling capacities.
4. The compressor is started by an inverter, resulting in extremely low starting current.
VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
HZ: Frequency (Hz) IPT: Input (kW)
STC: Starting Current (A)
NOTES:
1. The above compressor data is based on 100% capacity combination of the indoor units at rated operating frequency.
2. The above performance data is based on the equivalent piping length of each unit horsepower and 0m piping lift.
3. These data are based on the same conditions as the nominal heating and cooling capacities.
4. The compressor is started by an inverter, resulting in extremely low starting current.
VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
HZ: Frequency (Hz) IPT: Input (kW)
STC: Starting Current (A)
NOTES:
1. The above compressor data is based on 100% capacity combination of the indoor units at rated operating frequency.
2. The above performance data is based on the equivalent piping length of each unit horsepower and 0m piping lift.
3. These data are based on the same conditions as the nominal heating and cooling capacities.
4. The compressor is started by an inverter, resulting in extremely low starting current.
8. Sound Data
8.1 Outdoor Units
NOTE:
The readings were taken in an anechoic chamber. Sound in actural status may get bigger due to surrounding noise or echo.
Take noise source into consideration to look for proper installation location.
(Noise on the back surface will go up 6 to 7dB higher than the front surface.)
NOTE:
The readings were taken in an anechoic chamber. Sound in actural status may get bigger due to surrounding noise or echo.
Take noise source into consideration to look for proper installation location.
(Noise on the back surface will go up 6 to 7dB higher than the front surface.)
NOTE:
The readings were taken in an anechoic chamber. Sound in actural status may get bigger due to surrounding noise or echo.
Take noise source into consideration to look for proper installation location.
(Noise on the back surface will go up 6 to 7dB higher than the front surface.)
NOTE:
The readings were taken in an anechoic chamber. Sound in actural status may get bigger due to surrounding noise or echo.
Take noise source into consideration to look for proper installation location.
(Noise on the back surface will go up 6 to 7dB higher than the front surface.)
NOTE:
The readings were taken in an anechoic chamber. Sound in actural status may get bigger due to surrounding noise or echo.
Take noise source into consideration to look for proper installation location.
(Noise on the back surface will go up 6 to 7dB higher than the front surface.)
NOTE:
The readings were taken in an anechoic chamber. Sound in actural status may get bigger due to surrounding noise or echo.
Take noise source into consideration to look for proper installation location.
(Noise on the back surface will go up 6 to 7dB higher than the front surface.)
8.2 CH-Box
NOTES:
1. The readings were taken in anechoic chamber. Sound in actual status may get bigger due to surroundings noise or echo.
Take noise source into consideration to look for proper installation location.
2. CH-Box operation sound may be heard even if the indoor unit has stopped while the outdoor units are in operation and the other
indoor units are at Thermo-ON.
3. “Operation Sound” is the CH-Box operation sound when the whole system is in either cooling or heating operation.
(Not in cooling and heating operation)
4. “Maximum Sound” is the maximum value of CH-Box operation spund while the unit is in cooling and heating operation or
defrosting.
5. The maximum sound may be exceeded during transient operation such as switching to Defrosting Mode.
Ensure the installation place.
Do not install the CH-Box in a place near bedreooms or hospital rooms.
(Refer to the Installation Manual.)
NOTES:
1. The readings were taken in anechoic chamber. Sound in actual status may get bigger due to surroundings noise or echo.
Take noise source into consideration to look for proper installation location.
2. CH-Box operation sound may be heard even if the indoor unit has stopped while the outdoor units are in operation and the other
indoor units are at Thermo-ON.
3. “Operation Sound” is the CH-Box operation sound when the whole system is in either cooling or heating operation.
(Not in cooling and heating operation)
4. “Maximum Sound” is the maximum value of CH-Box operation sound while the unit is in cooling and heating operation or
defrosting.
5. The maximum sound may be exceeded during transient operation such as switching to Defrosting Mode.
Ensure the installation place.
Do not install the CH-Box in a place near bedreooms or hospital rooms.
(Refer to the Installation Manual.)
9. Center of Gravity
Power Supply
Working Voltage: 90% to 110% of the Rated Voltage
Voltage Imbalance: Within a 3% Deviation from Each Voltage at the Main Terminal of Outdoor Unit
Starting Voltage: Higher than 85% of the Rated Voltage
Temperature Range
The temperature ranges are given in the following table.
Cooling Operation
55
50
48
(*1)
45
43
40
Outdoor Air Inlet Temperature (oCDB)
35
Continuous Operation Range (*2)
Heating Operation
30 20
(at Pull-down Operation)
Operation Range
25 15
Outdoor Air Inlet Temperature (oCWB)
15 5
10 0
5 -5
0 -10
NOTES:
*1.(1) Cooling operation at maximum 48oC DB is available only if the outdoor air inlet temperature increase
temporarily caused by installation condition.
(2) If install the units to the place where continuously exceed ambient temperature 48oC, the
combination ratio must be lower than 130% and not to operate all of the indoor unit simultaneously.
(3) The cooling capacity is deteriorated at high ambient temperature. Select the larger capacity outdoor
unit than compatible building heat load.
(4) The appropriate amount (100%) of refrigerant must be charged. Excessive charging of refrigerant is
forbidden.
(5) Avoid to install the units where affected by direct sunlight reflection and short circuit. There may
be the possibility to activate protection control and alarm system if install the units to inappropriate
place. The life time of the products and parts are considerably shortened.
(6) Periodic maintenance (1/certain month) must be applied to the heat exchanger fin to avoid adhesion
of dirt and clogging of sand to the outdoor unit heat exchanger.
*2. There might be the possibility of thermo-OFF when operate the outdoor unit under the low cooling
load condition and in the low outdoor air temperature (10oC DB or lower) to prevent indoor unit heat
exchanger from frost formation.
*3. Indoor air inlet temperature at heating operation from 15oC to 27oC WB is under assumption of limited
time operation such as at the time of startup in the early morning and not suitable for long time
continuous operation.
*4. There might be the possibility of thermo-OFF when operate the outdoor unit under the low heating
load condition and in the high outdoor air temperature (higher than 15oC DB) to prevent the outdoor
unit. The outdoor unit operation stops when outdoor air inlet temperature exceed 26oC DB.
*5. Operational range is different when connect to All Fresh Air Unit, Econofresh, and other special
indoor units.
*6. In case cooling operation or simultaneous operation under the inlet air temperature -5oC or lower the
conditions listed below must be considered at the time of installation.
• Make sure to apply Snow Protection Hood (Optional Part) .
• The minimum capacity of indoor unit connectable is 2.5HP
• Set the function “Cooling Operation Under Low Load Operation” (DSW6) from the outdoor unit
(If multiple outdoor units are connected in a system set the function only for outdoor unit A).
• Make sure to apply new CH-Box (Optional Parts).
The “Low Ambient Setting” is not available if the system is connected with current CH unit.
Accessory
Indoor Unit B
Pipe
Indoor Unit C
Foundation
P
Low Pressure Gas Piping
(Field-Supplied)
Accessory Pipe <View from P>
Piping Connection Kit 1 (L-Shape)
(Low Pressure Gas)
Foundation
Accessory
Low Pressure Gas Piping Pipe
Piping Connection Kit 1
(Field-Supplied)
(High/Low Pressure Gas)
Accessory Pipe
High/Low Pressure Gas Piping
(L-Shape)
(Field-Supplied)
Piping Connection Kit 2
(Low Pressure Gas)
Piping Connection Kit 2 Liquid Piping
(High/Low Pressure Gas) High/Low Pressure Gas Piping
(Field-Supplied) ˃ 500mm (Field-Supplied)
Accesory Pipe
(Z-Shape)
High/Low Pressure Gas Piping
(Field-Supplied) Outdoor Unit B
Base
Low Pressure Gas Piping (Field-Supplied)
(Field-Supplied)
11.2 CH-Box
Suspension Bolt
Models: JCH-AP160SSX
JCH-AP280SSX (M10 x 2)
Number of
Connectable Indoor Unit
Branch H xDimension Net Weight
Model Connectable
W x D (mm) (kg) Total Capacity
Indoor Unit(*1)
JCH-AP160SSX 1 191x301x214 6.0 6.0HP or less (Max. 16kW) 1-7
JCH-AP280SSX 1 191x301x214 6.0 6.1HP - 10.0HP (Max. 28kW) 1-8
( 1)
* When multiple indoor units are connected to the same CH-Box, they are controlled with the same operation
mode.
NOTE:
When switching the refrigerant flow channel at Operation ON/OFF, Thermo-ON/OFF, Defrost Operation and
Operation Mode, refrigerant flow noise may be heard from CH-Box.
Therefore, install the unit in place such as under the roof of corridor so that the sound may not be heard in
the room.
Models: JCH-AP04MSSX
JCH-AP08MSSX
JCH-AP12MSSX
JCH-AP16MSSX
Suspension Bracket
(Four Places) (M10 x 4)
W
D
Number of
Connectable Indoor Unit Connectable
Branch H xDimension Net Weight
Model W x D (mm) (kg) Total Capacity Indoor Unit
per Branch(*2)
JCH-AP04MSSX 4 260x303x352 14.0 16.0HP or less (Max. 44.8kW) 1-6
JCH-AP08MSSX 8 260x543x352 25.0 30.0HP or less (Max. 85kW) 1-6
JCH-AP12MSSX 12 260x783x352 36.0 30.0HP or less (Max. 85kW) 1-6
JCH-AP16MSSX 16 260x1023x352 47.0 30.0HP or less (Max. 85kW) 1-6
( 2)
* The indoor units connected to the same branch of the CH-Box are controlled with the same
operation mode.
NOTE:
When switching the refrigerant flow channel at Operation ON/OFF, Thermo-ON/OFF, Defrost Operation and
Operation Mode, refrigerant flow noise may be heard from CH-Box.
Therefore, install the unit in place such as under the roof of corridor so that the sound may not be heard in
the room.
1-130 FAN-2209 201709
OPTIONAL ACCESSORIES
11.3 Multi-Kit
First Branch
Outdoor Unit HP Model Remarks
5 MW-NP142X3
6 - 10 MW-NP282X3
12 - 16 MW-NP452X3
For 3 pipes
18, 20 MW-NP562X3
22, 24 MW-NP692X3
26 - 54 MW-NP902X3
• Quantity
Applicable Outdoor Unit HP Q'ty
8 - 18 1
20 - 36 2
38, 40 3
42 - 48 4
50 - 54 3
Left Side
14 - 18 PSN-TP20BB PSN-TP20R x 2
20 - 24 PSN-TP20BC PSN-TP20R x 2
Right Side Rear Side
Screws (3 pcs.)
(Accessory)
Existing Screws
(3 pcs.) Outdoor Unit
1675
with Outdoor Unit
1 3
Air Inlet Grille Air Inlet Grille
(For Rear Side (For Left Side
Installation) Installation)
2 12.5 950 12.5 765
Air Inlet Grille
(For Right Side
Installation)
< Right Side > < Rear Side > < Left Side >
Outdoor Unit
1675
1
Air Inlet Grille
2 (For Rear Side
Air Inlet Grille Installation)
(For Right Side
Installation) 12.5 1210 12.5 765
< Right Side > < Rear Side > < Left Side >
1
Air Inlet Grille
2 (For Rear Side
Air Inlet Grille Installation)
(For Right Side
Installation) 12.5 1600 12.5 765
Outdoor Unit
< Right Side > < Rear Side > < Left Side >
Left Side
Protection Net
HP
1 Rear Side 2 Right Side 3 Left Side
14 - 18 PN-TP20BB PN-TP20R x 2
20 - 24 PN-TP20BC PN-TP20R x 2
Right Side Rear Side
1675
1
2 Protection Net
Protection Net (For Rear Side
(For Right Side Installation)
Installation)
Outdoor Unit
950 765
< Right Side > < Rear Side > < Left Side >
1
2 Protection Net
Protection Net (For Rear Side
(For Right Side Installation)
Installation) Outdoor Unit
1210 765
< Right Side > < Rear Side > < Left Side >
2 1
Protection Net
Protection Net
(For Right Side
(For Rear Side
Installation) Installation)
Outdoor Unit
1600 85 765
100 100
< Right Side > < Rear Side > < Left Side >
Model: JTOR140VPE(U,F,R)BS1
12.1.2 CH-Box
Model: JCH-AP04MSSX
Model: JCH-AP08MSSX
Model: JCH-AP12MSSX
Model: JCH-AP16MSSX
■ Cycle Control
Control
Heating Operation
Control Device Cooling Operation * Defrosting
Cooling and Heating Operation
Control Category Purpose of Control Control Category Purpose of Control Condition
Inverter Frequency Control Inverter Frequency Control
All of the
Inverter Frequency of Total I.U. is carried out to make I.U. Total I.U. is carried out to make I.U.
compressors:
Compressor Operating Capacity air inlet temperature to Operating Capacity air inlet temperature to
ON
temperature setpoint. temperature setpoint.
Controls supercooling
Electronic Expansion PI control is carried out to I.U. Heat
of I.U. liquid thermistor
Valve for I.U. I.U. Heat Exchanger SH achieve the targeted value I.U. Heat Exchanger SC Exchanger SH
to achieve the targeted
Heat Exchanger of I.U. heat exchanger SH. Control
value.
JTOR260VAE(U,F,R)BS1
Inverter Compressor
NOTE:
Inverter Compressor 1 Inverter Compressor
When turning ON the outdoor unit A, the inverter compressor 1
Inverter / Constant Compressor 2 or 2 with the shortest operating time will operate preferentially.
NOTE:
Inverter Compressor 1 Inverter Compressor 1 When turning ON the outdoor units, the inverter compressor of each
Constant Compressor 2 Constant Compressor 2 outdoor unit with the shortest operating time will operate preferentially.
JTOR500VAE(U,F,R)BS1
NOTE:
When turning ON the outdoor units, the inverter compressor of the outdoor unit A and B with the shortest operating time will
operate preferentially.
JTOR520, 540VAE(U,F,R)BS1
NOTE:
When turning ON the outdoor units, the inverter compressor of each outdoor unit with the shortest operating
time will operate preferentially.
JTOR160 - 200VPE(U,F,R)BS1
NOTE:
Refer to page 1-146 for the maximum frequency.
* Max.
Frequency
Target Frequency (Hz)
JTOR220, 240VPE(U,F,R)BS1
(B)
2 (Two) Inverter Compressors
Compressor
Operation 1 (One) Inverter
Status Compressor
NOTE:
Refer to page 1-146 for the maximum frequency.
* Max.
Frequency
Target Frequency (Hz)
JTOR260 - 480VAE(U,F,R)BS1
(C)
Outdoor Unit 2 (Two) Outdoor Units
Operation 1 (One)
Status Outdoor Unit
* Max.
Frequency
Frequency of
Inverter Comp.
(Hz)
Target Frequency (Hz)
NOTE:
Refer to page 1-146 for the maximum frequency.
JTOR500 - 540VAE(U,F,R)BS1
* Max.
Frequency
Frequency of
Inverter Comp.
(Hz)
Target Frequency (Hz)
NOTE:
Refer to page 1-146 for the maximum frequency.
Combination of Maximum
Model
Base Units Frequency [Hz]
JTOR080VPE(U,F,R)BS1 — 75
JTOR100VPE(U,F,R)BS1 — 90
JTOR120VPE(U,F,R)BS1 — 110
JTOR140VPE(U,F,R)BS1 — 130
JTOR160VPE(U,F,R)BS1 — 175
JTOR180VPE(U,F,R)BS1 — 200
JTOR200VPE(U,F,R)BS1 — 200
JTOR220VPE(U,F,R)BS1 — 250
JTOR240VPE(U,F,R)BS1 — 260
14 130
JTOR260VAE(U,F,R)BS1
12 110
16 175
JTOR280VAE(U,F,R)BS1
12 110
18 200
JTOR300VAE(U,F,R)BS1
12 110
18 200
JTOR320VAE(U,F,R)BS1
14 130
18 200
JTOR340VAE(U,F,R)BS1
16 175
18 200
JTOR360VAE(U,F,R)BS1
18 200
24 260
JTOR380VAE(U,F,R)BS1
14 130
22 250
JTOR400VAE(U,F,R)BS1
18 200
24 260
JTOR420VAE(U,F,R)BS1
18 200
22 250
JTOR440VAE(U,F,R)BS1
22 250
24 260
JTOR460VAE(U,F,R)BS1
22 250
24 260
JTOR480VAE(U,F,R)BS1
24 260
18 200
JTOR500VAE(U,F,R)BS1 18 200
14 130
18 200
JTOR520VAE(U,F,R)BS1 18 200
16 175
18 200
JTOR540VAE(U,F,R)BS1 18 200
18 200
NOTE:
The frequency in the table above indicates the total frequency of a outdoor unit if the unit is installed two
compressors.
NOTE:
The temperature of the thermistor in the wired controller is utilized instead of indoor unit air inlet
temperature when the thermistor in the wired controller is set by functional setting mode.
Cooling Mode Mainly Cooling Mode Mainly Heating Mode Heating Mode Defrosting Mode
Heat Exchanger Mode
COND D1 D1-1 D4 EVAP DEF1
Cooling Mode Mainly Cooling Mode Mainly Heating Mode Heating Mode
Heat Exchanger Mode
COND D1 D2 D3 D4 EVAP
Defrosting Mode
Heat Exchanger Mode
DEF2 DEF1
with CH-Box without CH-Box
RVR2 ON ON ON ON ON
Reversing Valve
RVR1 OFF OFF OFF OFF OFF
MV1 Heat Exchanger SH Heat Exchanger SH Heat Exchanger SH Heat Exchanger SH Heat Exchanger SH
Expansion Valve
MVB Tchg - Tsc Tchg - Tsc Tchg - Tsc Tchg - Tsc Tchg - Tsc
EVAP
RVR2 ON ON ON ON ON
Reversing Valve
RVR1 OFF OFF OFF OFF OFF
MV1 Closed Heat Exchanger SH Heat Exchanger SH Heat Exchanger SH Heat Exchanger SH
Expansion Valve
MVB Closed Tchg - Tsc Tchg - Tsc Tchg - Tsc Tchg - Tsc
Defrosting Mode
Heat Exchanger Mode
DEF2 DEF1
with CH-Box without CH-Box
NOTES:
1. Condition of Heat Exchanger
COND : Use as Condenser
EVAP : Use as Evaporator
cond : Avoid the use of Heat Exchanger (under the high pressure condition)
evap : Avoid the use of Heat Ec\xchanger (under the low pressure condition)
to Transmission Circuit of
Thermistor for Inlet Air
Combination Outdoor Unit Multiple Signals
Thermistor of Outlet Air
Thermistor for Ambient Temperature “TA” (THM7) Single Signal
Thermistor for Gas Pipe
Thermistor for Liquid Pipe Discharge Gas Thermistor “TD1” (THM8) Operation Signal
Thermistor for Evaporation Liquid Line Temperature “TE” (THM10)
Wireless Remote
Control Switch Thermistor for Evaporation Gas Line Temperature “TG” (THM12)
Communication
Protection
Wireless Communication Circuit
Circuit A D A D
Communication Conversion
Circuit Circuit
Remote Control Switch
Communication
Inverter Power
Communication
Communication
MCU
Circuit
Circuit
MCU
Symbol Name
THM Thermistor
MCU Microcontroller
MC1 DC Motor (for Inverter Compressor)
MOF DC Motor (for Outdoor Fan)
MIF Motor (for Indoor Fan)
MS Motor (for Auto-Louver)
MD Motor (for Drain Pump)
MV Electronic Expansion Valve (for Indoor Unit)
MV1 Electronic Expansion Valve (for Outdoor Unit)
MVB Electronic Expansion Valve for Supercooling Heat Exchanger
SVA Solenoid Valve
SVG Solenoid Valve
RVR1 Reversing Valve
RVR2 Reversing Valve
CH1 Crankcase Heater
■ Cooling Operation
I.U.: Indoor Unit
O.U.: Outdoor Unit
Low
LOW Indication
Higher than
Set Temp.
(Thermo-ON) > -5oC
Cooling I.U.
Outdoor PID Control for I.U.
Operation Air Intake
Temp. Electronic Expansion Valve
Temp.
Lower than < -5oC
Set Temp.
(Thermo-OFF)
Thermo-OFF
No
3 min.
Yes
to 1
■ Cooling Operation
1
I.U.: Indoor Unit
Start of
Auto-Louver
Press only for Air Panel
AUTO-LOUVER < Alternately > or Indoor Unit
Switch with Auto-Louver
Stop of
Auto-Louver
Press
RUN/STOP
Switch No
Yes
After 3 min. MD : Operation: OFF
20 sec.
for Unit with Drain Pump
■ Dry Operation
Set
Operation Mode DRY Indication
at “DRY”.
Press
RUN/STOP RUN indicator lights.
Switch
Higher than
Set Temp.
(Thermo-ON)
I.U. Air > -5oC
DRY Operation Intake MIF Operation at Low Fan Speed Outdoor PID Control for I.U.
Temp. Temp. Electric Expansion Valve
< -5oC
Lower than
Set Temp.
(Thermo-OFF)
MIF Operation at SLo Fan Speed
No
3 min.
Yes
to 2
■ Dry Operation
2
I.U.: Indoor Unit
Start of
Auto-Louver
Press only for Air Panel
AUTO-LOUVER < Alternately > or Indoor Unit
Switch with Auto-Louver
Stop of
Auto-Louver
Press
RUN/STOP
Switch No
After 3 min.
MD Operation: OFF
20 sec.
Yes
for Unit with Drain Pump
Power to
Power to I.U. PCB: OFF LCD Indication: OFF
I.U.: OFF
Power Supply
Cooling Operation or
Dry Operation
Is compressor operated
No for more than *15 min. or
the accumulated operation time of
compressor exceeded
30 min.?
* The judging time varies depending on indoor unit model.
Yes
Cooling Operation or
Dry Operation
< 0 oC
Is it continuous for No
more than 3 min.?
Yes
Is it continuous
for more than 3 min.? No
(6 min. in case of DRY
Operation)
Yes
No
> 3o C
■ Heating Operation
Set
Operation Mode HEAT Indication
at "HEAT".
Press
RUN/STOP RUN indicator lights.
Switch
Lower than
Setting Temp.
Heating (Thermo-ON) PID Control for I.U.
I.U. Intake
Operation Air Temp. and O.U. Electronic
Expansion Valve
Higher than
Setting Temp.
(Thermo-OFF)
Operate H1 auxiliary
Power to Y52H Power to 52H
electrical heater
Indoor Fan Stop
Y52H: Relay for auxiliary electrical heater
52H: Electromagnetic contactor for auxiliary electrical heater
Yes
Pd < 2.2MPa
No After 3 to 48 sec.
MIF Operation at
< 25oC > 30oC
Set Fan Speed
MIF Operation at I.U. Air
SLo Fan Speed Outlet Temp.
Permitting Downward
Air Flow by Auto-Louver
MIF Operation at 25 to less than 30oC only for Indoor Unit
Lo Fan Speed with Auto-Louver
To 3
■ Heating Operation
3
I.U.: Indoor Unit
O.U. Outdoor Unit
Start of
Auto-Louver
Press only for Air Panel
Auto-Louver < Alternately > or Indoor Unit
Switch with Auto-Louver
Stop of
Auto-Louver
Cut the power to Y52H Cut the power to 52H Auxiliary electrical heater H1 : OFF
Press
RUN/STOP
Switch
I.U. Air < 50oC
Indoor Fan Motor MIF : OFF
Outlet Temp.
STOP
■ Defrosting Operation
Heating Operation
Defrosting Operation 1
RVR2 : OFF
Fixed Opening
Degree of Electronic
Expansion Valve
Defrosting
Completion
1: Defrosting operation signal is
transmitted to the indoor unit during
RVR2 : ON
the defrosting operation. After the
signal is received, “DEFROST” will be
indicated on LCD of remote control
Heating Operation
switch and the indoor fan will stop.
1000 0 7
900 Temperature
Reset the accumulated -2 (°C)
800 operation hour
-5
700 -6
600
500 -10
400
300 -15 Defrosting Operation Area
200
-18
100 -20
0
-20 -10 0 10 20
-24
Outdoor Temperature (°C) -25
Heating Operation
> 65oC
Thermo-OFF
No Is it continuous
more than 3 min.?
Yes
< 60oC
No Is setting temp.
lower than inlet air temp.
of Indoor Unit?
Yes
Thermo-ON
■ Protection Control
• Whenever protection control sequences are activated, the corresponding code is displayed on the
7-segment LED array of the main control board.
• Protection control code is displayed when a unit protection mode has been initiated. The code will
disappear once the cause of protection has been addressed.
Indicated Contents
Indication Protection Control Contents Code During Degeneration Control
P01 Pressure Ratio Protection Control Pc1
P02 High Pressure Increase Protection Control Pc2
P03 Inverter Current Protection Control Pc3
P04 Inverter Fin Temperature Increase Protection Control Pc4
P05 Discharge Temperature Increase Protection Control Pc5
P06 Low Pressure Decrease Protection Control
P09 High Pressure Decrease Protection Control
―
P0A Demand Current Control
P0d Low Pressure Increase Protection Control
˂Details of Control˃
NOTE:
Normal Operation
1. With a combination of base units, the control in the
Pressure Ratio e ≥ 8.5 figure is performed for the entire number of outdoor
units to be connected.
Frequency Forced Decrease 2. The pressure ratio is calculated in each outdoor unit,
(1.0Hz/sec.) and this control uses the maximum value.
Pressure Ratio e < 8.2 Pressure Ratio e= (Pd [MPa]+0.1) / (Ps [MPa]+0.06)
e ≥ 8.5 e= (Pd [psi]+15) / (Ps [psi]+9)
Pd: Detected Value of High Pressure Sensor [MPa (psi)]
Prohibition of Frequency Increase
Ps: Detected Value of Low Pressure Sensor [MPa (psi)]
(Only Frequency Decrease Permitted)
˂Details of Control˃
Normal Operation
Pressure Ratio e < 1.5
for 1 min.
Pressure Ratio e < 1.5 for 1 min. Abnormal Stoppage
Frequency Forced Increase
(Cause Code of I.U. Stoppage: d1 -11)
(0.25Hz/sec.)
Pressure Ratio e ≥ 1.6
Pressure Ratio
e ≤ 1.5
Prohibition of Frequency Decrease
(Only Frequency Increase Permitted) NOTE:
1. With a combination of base units, the control in the figure
is performed for the entire number of outdoor units to be
Pressure Ratio e ≥ 1.7 connected.
2. The pressure ratio is calculated in each outdoor unit, and
this control uses the minimum value.
˂Details of Control˃
Normal Operation
Pd ≥ P1
˂Details of Control˃
NOTE:
1. With a combination of base units, the control in the figure is performed for each outdoor unit connected. When there is
outdoor unit in Prohibition of Frequency Increase, all the outdoor units in operation are prohibited to increase frequency.
When there is outdoor unit in Frequency Forced Decrease, all the outdoor units in operation are forced to decrease
frequency.
2. In case of two inverter PCB installed in an outdoor unit, the max. current value detected at each inverter PCB is utilized.
Iinv: Detected Value of Inverter Secondary Current Sensor[A]
NOTE:
1. With a combination of base units, the control in the figure is performed for each outdoor unit connected. When there is
outdoor unit in Prohibition of Frequency Increase, all the outdoor units in operation are prohibited to increase frequency.
When there is outdoor unit in Frequency Forced Decrease, all the outdoor units in operation are forced to decrease
frequency.
2. In case of two inverter PCB installed in an outdoor unit, the max. current value detected at each inverter PCB is utilized.
Isep: Inverter Primary Current[A]
NOTE:
1. In case of combination of base units, the control in the figure is performed for each outdoor unit connected. When there is
outdoor unit in Prohibition of Frequency Increase, all the outdoor units in operation are prohibited to increase frequency.
When there is outdoor unit in Frequency Forced Decrease, all the outdoor units in operation are forced to decrease
frequency.
2. In case of two inverter PCB installed in an outdoor unit, the max. temperature detected at each inverter PCB is utilized.
Tfin: Inverter Fin Temperature Sensor Detected Value [°C(°F)]
Td ≥ 112°C(234°F)
Ps ≥ 1.3MPa (189psi)
NOTE:
1. With a combination of base units, the control in the figure is performed for the entire number of outdoor units to be connected.
2. Low pressure is detected in each outdoor unit, and this control uses the maximum value.
Ps: Detected Value of Low Pressure Sensor [MPa(psi)]
Forced Decrease 1 1 1 1
1
Forced Increase 1 1 1 1
Higher Rank Order
of Protection Prohibited Increase 2 1 2 * 1
Control Function
Prohibited Decrease 2 2 2 2
*: Discharge Temperature Increase Protection Control (P05) is higher than the following protection controls.
a) Low Pressure Decrease Protection Control (P06)
b) Demand Current Control (P0A)
Normal Operation
Normal: Td > 112°C(234°F)
Degeneration: Td > 110°C(230°F) Td > 140°C(284°F) for 5 sec. or
Td > 132°C(270°F) for 10 min.
Frequency Forced Decrease
(1.0Hz/sec.)
Normal: Td < 110°C(230°F) Normal: Td > 112°C(234°F)
Degeneration: Td < 108°C(226°F) Degeneration: Td > 110°C(230°F)
Prohibition of Frequency Increase
(Except Frequency Decrease Only)
Abnormal Stoppage
(Cause Code of I.U. Stoppage: d1-15)
Normal: Td < 105°C(221°F)
Degeneration: Td < 100°C( 212°F)
˂Activating Condition˃
This control function is started the compressor runs below the specified speed for 1 hour continuously
(refer to the table below).
˂Detail of Control˃
Compressor:
Increase the compressor speed above the required value to return the oil to the compressor
Expansion Valve:
(In the Case of Cooling Operation) Open the expansion valve of the indoor unit under thermo-ON.
(In the Case of Heating Operation) Open the expansion valve of the outdoor unit.
˂Deactivating Condition˃
This control function is canceled when the oil return control continues for more than 60 sec. (for cooling
operation) /120sec. (for heating operation).
• Compressor Protection
The compressor is protected by the following devices and their combinations.
(1) High Pressure Switch: This switch cuts out the operation of the compressor when the discharge
pressure exceeds the setting.
(2) Oil Heater: This band type heater protects against oil foaming during cold starting, as it is energized
while the compressor is stopped.
ELECTRICAL WIRING DIAGRAM (FOR MODEL: JTOR200VPEUBS1, JTOR220VPEUBS1 and JTOR240VPEUBS1; 460V/60HZ)
ELECTRICAL WIRING DIAGRAM (FOR MODEL: JTOR080VPEFBS1, JTOR100VPEFBS1 and JTOR120VPEFBS1; 380V/60HZ)
ELECTRICAL WIRING DIAGRAM (FOR MODEL: JTOR200VPEFBS1, JTOR220VPEFBS1 and JTOR240VPEFBS1; 380V/60HZ)
ELECTRICAL WIRING DIAGRAM (FOR MODEL: JTOR080VPERBS1, JTOR100VPERBS1 and JTOR120VPERBS1; 220V/60HZ)
ELECTRICAL WIRING DIAGRAM (FOR MODEL: JTOR200VPERBS1, JTOR220VPERBS1 and JTOR240VPERBS1; 220V/60HZ)
12.5.2 CH-Box
Special Notes
1. Provide a service access door near the unit 10. During heating operation, the outdoor heat
piping connection part on the false ceiling for the exchanger produces dew condensation or
cassette type units. melted frost water.
2. Consider the air distribution from the unit to the Install the outdoor unit where such water can
space of the room, and select a suitable location be drained, or provide a drain passage.
so that uniform air temperature in the room can 11. Heating Performance: The heating capacity
be obtained. normally decreases when outdoor temperatures
Cassette and Ceiling Types - Avoid unit decrease. Therefore, provide an auxiliary
installation in a room where the ceiling height heating unit if outdoor temperatures are very
(distance between the floor to the false ceiling) low.
exceeds three meters. If the indoor unit is 12. In the case that an outdoor temperature is
installed in a room with a ceiling more than three low and humidity is high, the outdoor heat
meters in height, it is recommended that an air exchanger will be covered with frost, resulting
circulation fan be installed separately to obtain in lower heating capacity. In order to remove
uniform air temperature in the room, especially the frost, the unit operation mode automatically
during the heating operation. changes to the defrosting mode. During
3. Check to ensure that the ceiling slab is strong this defrosting operation, the unit stops for
enough and that the false ceiling is flat and level. approximately 3 to 10 minutes.
4. Avoid obstacles which may restrict the air intake 13. As this unit is heat pump type by circulating hot
or the discharge flow. air in the whole room space, it takes some time
5. Do not install the unit in a machinery shop or to raise the room temperature.
kitchen where vapor from oil or its mist can enter 14. The operating sound data is based on an
the unit. anechoic chamber. Therefore, the actual
The oil will deposit on the heat exchanger, operating sound will be higher due to reflected
which may reduce the unit performance, cause sound from the floor and wall.
deformation, and in the worst case, break the 15. In the case that the unit is operated for
plastic parts of the unit. a long time at an indoor temperature of over
6. Pay attention to the following points when the 27oC DB, or at an indoor humidity of over 80%,
unit is installed in a hospital or other facilities dew condensation may occur on the cabinets,
where electromagnetic wave is radiated from resulting in dew drops.
medical equipment. If dew condensation occurs, it is required to
(A) Do not install the unit where the add thermal insulator on the cabinets.
electromagnetic wave is directly radiated to 16. Provide snow-protection hoods to prevent snow
the electrical box, remote control cable or from clogging the outdoor heat exchanger.
remote control switch. If the unit is operated in an area where it snows
(B) Install the unit and components as far from heavily, provide a base under the outdoor
an electromagnetic wave radiator (at least unit, which should be 50cm higher than the
three meters) as possible. presumable maximum snow height.
(C) Prepare a steel box and install the remote 17. It is recommended that periodical service and
control switch in it. Prepare a steel conduit maintenance be performed by authorized
pipe and wire the remote control cable in it. service engineers before air conditioning
And then, connect earth wire with the box seasons, in order to avoid performance
and the pipe. decrease due to dust or dirt.
(D) Install a noise filter when the power supply 18. This heat pump air conditioner has been
emits harmful noise. designed for normal air conditioning for men.
7. Do not install the units in an acid or alkaline Do not use the product for other purposes such
environment, as the heat exchanger will be as for food, animals, plants, high precision
damaged by corrosive action. In the case that machines or work of art. Also do not use the
outdoor units are installed near the sea, it is product for vehicles or vessels. It will results in
recommended that optional corrosion-resistant- water leakage or electrical leakage.
type outdoor unit be used. 19. It is recommended that the system be installed
8. Do not install the units in a flammable by authorized engineers. If not, it may cause
environment, as there is a danger of an water leakage, electric shock or fire.
explosion. 20. In a place where fibers or dusts are floating, the
9. Regarding cassette type indoor units, consider air filter or heat exchangers or the drain pipe
the direct and reflected sound level, when may be clogged, resulting in water leakage
selecting the unit for spaces where extremely from the drain pan.
low sound is required.
CAPACITY - The total capacity of the multi-split OUTDOOR FAN AND FAN MOTOR - The
system inverter-driven heat pump air conditioner outdoor fan(s) shall be the plastic propeller type,
o
shall be kW or greater with C air dynamically balanced, and the fan shall be directly
o o
inlet dry bulb, C air inlet wet bulb, C driven by a W motor for vertical-flow air
3
outdoor air inlet temperature and m /min. discharge. The fan motor shall be permanently
indoor air flow. The total compressor power inputs lubricated and be protected from ingress of water.
shall not exceed kW. The total heating
capacity of the split-type air conditioners shall be OUTDOOR HEAT EXCHANGER - The heat
o
kW or greater, with C indoor heat exchanger shall be the multi-pass, cross-finned
o
exchanger air inlet dry bulb, C outdoor heat tube type, equipped with highly-efficient aluminum
o
exchanger air inlet dry bulb, C outdoor heat fins, mechanically bonded to oxygen-free copper
exchanger air inlet wet bulb, and m3/min. tubes. The coil shall be cleaned, dehydrated and
indoor air flow. tested for leakage at the factory.
The total compressor power input shall not exceed
kW. CONTROL - All electrical control devices, shall be
enclosed in the indoor and outdoor units.
The room where the packaged air conditioner is installed, the refrigerant gas should be controlled not to
exceed the limit concentration in case of the refrigerant leakage.
250
(Countermeasures
Not Needed)
150
50
After calculation, the room to install this unit is proved not to keep the gas concentration lower than the limit
value. However, the air conditioner should be installed in this room from unavoidable circumstances, each
of the following countermeasures should be taken.
Outdoor Unit
Refrigerant Flow
Refrigerant Cycle
Indoor Unit
1) The gas leakage detector & alarm system and interlocking mechanical ventilation equipment (with
ventilation capacity over 0.42m3/min per refrigerating ton) should be installed. Refer to the following
figure.
2) Provide the opening for ventilation between rooms* in order not to exceed the permissible
concentration.
* It is opening without door or opening at the top or bottom of door with floor space more than 0.15%.
Outdoor Unit
Indoor Unit
The Smallest
Room
Medium-sized
Small Room Room Large Room
NOTES:
1. The quantity of refrigerant gas leakage against each room should be calculated as 60kg each.
2. The refrigerant concentration must be below 0.42 kg/m3 for each room.
The installer and system specialist shall secure against leakage according to local regulations or
standards. The following standards may be applicable, if local regulations are not available.
International Organization for Standardization, ISO5149 or European Standard, EN378 or Japan
Standard, KHKS0010.
- CONTENTS -
INVERTER-DRIVEN
MULTI-SPLIT SYSTEM HEAT RECOVERY
AIR CONDITIONERS
Models:
< 3~, 460V/60Hz > < 3~/N, 380V/60Hz > < 3~, 220V/60Hz >
< Base Unit > < Base Unit > < Base Unit >
JTOR080VPEUBS1 JTOR080VPEFBS1 JTOR080VPERBS1
JTOR100VPEUBS1 JTOR100VPEFBS1 JTOR100VPERBS1
JTOR120VPEUBS1 JTOR120VPEFBS1 JTOR120VPERBS1
JTOR140VPEUBS1 JTOR140VPEFBS1 JTOR140VPERBS1
JTOR160VPEUBS1 JTOR160VPEFBS1 JTOR160VPERBS1
JTOR180VPEUBS1 JTOR180VPEFBS1 JTOR180VPERBS1
JTOR200VPEUBS1 JTOR200VPEFBS1 JTOR200VPERBS1
JTOR220VPEUBS1 JTOR220VPEFBS1 JTOR220VPERBS1
JTOR240VPEUBS1 JTOR240VPEFBS1 JTOR240VPERBS1
< Combination Unit > < Combination Unit > < Combination Unit >
JTOR260VAEUBS1 JTOR260VAEFBS1 JTOR260VAERBS1
JTOR280VAEUBS1 JTOR280VAEFBS1 JTOR280VAERBS1
JTOR300VAEUBS1 JTOR300VAEFBS1 JTOR300VAERBS1
JTOR320VAEUBS1 JTOR320VAEFBS1 JTOR320VAERBS1
JTOR340VAEUBS1 JTOR340VAEFBS1 JTOR340VAERBS1
JTOR360VAEUBS1 JTOR360VAEFBS1 JTOR360VAERBS1
JTOR380VAEUBS1 JTOR380VAEFBS1 JTOR380VAERBS1
JTOR400VAEUBS1 JTOR400VAEFBS1 JTOR400VAERBS1
JTOR420VAEUBS1 JTOR420VAEFBS1 JTOR420VAERBS1
JTOR440VAEUBS1 JTOR440VAEFBS1 JTOR440VAERBS1
JTOR460VAEUBS1 JTOR460VAEFBS1 JTOR460VAERBS1
JTOR480VAEUBS1 JTOR480VAEFBS1 JTOR480VAERBS1
JTOR500VAEUBS1 JTOR500VAEFBS1 JTOR500VAERBS1
JTOR520VAEUBS1 JTOR520VAEFBS1 JTOR520VAERBS1
JTOR540VAEUBS1 JTOR540VAEFBS1 JTOR540VAERBS1
Issue Date:
15. Dec. 2017
IMPORTANT NOTICE
FAN-2207 201709 i
l This heat recovery air conditioner has been designed for the following temperatures. Operate the heat
recovery air conditioner within this range.
l This system can provide Heat Recovery System.
Temperature (°C)
Cooling and Heating Operation
Cooling Operation Heating Operation
Cooling Heating
Indoor Air Inlet
15 to 23°C WB 15 to 27°C DB 15 to 23°C WB 15 to 27°C DB
Temperature
-5 to 24°C DB
-5 to 48°C DB
-6 to 15°C WB
Outdoor Air Inlet
With Low Ambient Setting* -20 to 15°C WB With Low Ambient Setting*
Temperature
-10 to 24°C DB
-10 to 48°C DB
-11 to 15°C WB
DB: Dry Bulb, WB: Wet Bulb
(*) NOTES:
1. Cooling operation at maximum 48°C DB should be available only if the outdoor air inlet temperature
increase temporarily according to the installation condition.
2. If install the units to the place where exceed ambient temperature 48°C DB continuously, the combination
ratio must be lower 130%, and not to operate all of the indoor unit simultaneously.
3. The cooling capacity is deteriorated at high ambient temperature. Select the larger capacity outdoor unit
than compatible building heat load.
4. The appropriate amount (100%) of refrigerant must be charged. Excessive charging of refrigerant is
forbidden.
5. It must be avoided to install the units where affected by direct sunlight reflection and short circuit. There may
be the possibility to activate protection control and alarm system if install the units to inappropriate place.
Also the life time of the products and parts must be considerably shortened.
6. Periodic maintenance (1/certain month) must be applied to the heat exchanger fin to avoid adhesion of dirt
and clogging of sand to the outdoor unit heat exchanger.
7. Refer to the technical catalog for the detail.
* In case cooling operation or simultaneous operation under the inlet air temperature -5°C or lower the conditions
below must be considered at the time of installation.
● Make sure to apply Snow Protection Hood (Optional Parts).
● The minimum capacity of connectable indoor unit is 2.5HP.
● Set the function “Cooling Operation under Low Load Operation” (DSW6) from the outdoor unit
(If multiple outdoor units are connected in a system, set the function only for outdoor unit A).
● Make sure to apply new CH-Box (Optional Parts). The “Low Ambient Setting” is not available if the system is
connected with current CH unit.
This manual should be considered as a permanent part of the air conditioning equipment and should
remain with the air conditioning equipment.
ii FAN-2207 201709
TABLE OF CONTENTS
iv FAN-2207 201709
1. Safety Summary
CAUTION : CAUTION, used with the safety alert symbol, indicates a hazardous situation which,
if not avoided, could result in minor or moderate injury.
FAN-2207 201709 1
DANGER
l Do not perform installation work, refrigerant piping work, drain pump, drain piping and electrical wiring
connection without referring to our installation manual. If the instructions are not followed, it may result in
a water leakage, electric shock or a fire.
l Provide a sufficiently strong foundation. If not, the unit may fall down and it may lead to injuries.
l Be sure to use Nitrogen Gas for air-tight test. If other gases such as oxygen gas, acetylene gas or
fluorocarbon gas are accidentally used, it may cause explosion or gas intoxication.
l Do not install the outdoor unit where there is high level of oil mist, flammable gases, salty air or harmful
gases such as sulfur.
l Do not install the outdoor unit to a space where the flammable gases may occur or leak. It may cause fire.
l If the indoor unit is installed in a small room and the refrigerant gas leakage occurs, the leaked refrigerant
gas fills the room and it may cause suffocation. Do not exceed the maximum permissible concentration of
the refrigerant gas in the room. Consult with distributor for countermeasure such a ventilation system, etc.
l Make sure that the refrigerant leakage test should be performed.
Refrigerant (Fluorocarbon) for this unit is incombustible, non-toxic and odorless.
However if the refrigerant is leaked and is contacted with fire, toxic gas will generate.
Also because the fluorocarbon is heavier than air, the floor surface will be filled with it, which could cause
suffocation.
l Use the specified non-flammable refrigerant (R410A) to the outdoor unit in the refrigerant cycle.
Do not charge material other than R410A into the unit such as hydrocarbon refrigerants (propane or etc.),
oxygen, flammable gases (acetylene or etc.) or poisonous gases when installing, maintaining and moving.
These flammables are extremely dangerous and may cause an explosion, a fire, and injury.
l The installer and system specialist shall secure safety against refrigerant leakage according to local
regulations or standards.
l Refrigerant leakage can cause difficulty with breathing due to insufficient air. Turn OFF the main switch,
extinguish any naked flames and contact your service contractor, if refrigerant leakage occurs.
l For installation, firmly connect the refrigerant pipe before the compressor starts operating.
For maintenance, relocation and disposal, remove the refrigerant pipe after the compressor stops.
If the compressor is operated under the condition that the stop valves are opened without refrigerant pipe,
it may cause abnormal high pressure in refrigerant cycle and may cause explosion, fire or injury.
l Remove gas inside the closing pipe when the brazing work is performed.
If the brazing filler metal is melted with remaining gas inside, the pipes will be blown off and it may cause
injury.
l Do not expose surrounding parts and the oil return pipe of the compressor to the fire when a burner is
used. If the oil return pipe is exposed to the fire, high temperature oil will spurt and it will cause a fire or
injury.
l Do not pour water into the indoor or outdoor unit. These products are equipped with electrical parts.
If poured, it will cause a serious electrical shock.
l Do not touch or adjust safety devices inside the indoor unit or outdoor units. If these devices are touched
or readjusted, it may cause a serious accident.
l Do not perform a short-circuit of the protection device such as a pressure switch when operating.
It may cause a fire and explosion.
l The electrical wiring work must be performed by authorized installers. If not performing the electrical work
completely or a capacity shortage of the power circuit, it may cause an electric shock or fire.
l Perform electrical work according to Installation Manual and all the relevant regulation and standards.
If the instructions are not followed, an electrical shock and fire may occur due to insufficient capacity and
inadequate performance.
l Use specified cables between units and choose the cables correctly. If not, an electrical shock or fire may
occur.
l Ensure that the wiring terminals are tightened securely with the specified torques. If not, generating fire or
electrical shock at the terminal connection part may occur.
2 FAN-2207 201709
DANGER
l Clamp wires adequately by the cord clamp after the wiring is connected to the terminal block. In addition,
run securely wires through the wiring hole. If not completed, it may cause fire by biting wires.
l Fix the cables securely. External forces on the terminals could lead to a fire.
l Turn OFF the power source completely when handling the service connector.
It may cause an electric shock.
l Do not open the service cover or access panel for the indoor or outdoor units without turning OFF the main
power supply.
l An electrical shock will occur by residual voltage.
Disconnect the power source completely before starting the maintenance for electrical parts.
Check to ensure that no residual voltage is existed after disconnecting the power source.
l In some cases, the packaged air conditioner may not be operated normally under the following cases.
* In case that electrical power for the packaged air conditioner is supplied from the same power
transformer as the device*.
* In case that the power source wires for the device* and the packaged air conditioner are located close to
each other.
Device*: (Ex) Lift, container crane, rectifier for electric railway, inverter power device, arc furnace,
electric furnace, large-sized induction motor and large-sized switch.
It consumes a large quantity of electrical power.
Regarding the cases mentioned above, surge voltage may be inducted in the power supply wiring for the
packaged air conditioner due to a rapid change in power consumption of the device and an activation of
switch.
Therefore, check the field regulations and standards before performing electrical work in order to protect
the power supply for the packaged air conditioner.
l Check that the ground wire is securely connected. If the unit is not correctly grounded, it lead electric
shock. Do not connect the ground wiring to gas piping, water piping, lighting conductor or ground wiring
for telephone.
l Use an ELB (Earth Leakage Breaker).
In the event of fault, there is danger of an electric shock or a fire if it is not used.
FAN-2207 201709 3
WARNING
l Do not install the unit in a place where oil, vapor, organic solvent and corrosive gas (ammonia, sulfur
compound and acid) may be present in quantities.
It may cause refrigerant leakage due to corrosion, electrical shock, deteriorated performance and
breakage.
l Do not use any sprays such as insecticide, lacquer, hair spray or other flammable gases within
approximately one (1) meter from the system.
l If circuit breaker or fuse is often activated, stop the system and contact your service contractor.
l Connect the fuse of specified capacity.
l Protect the wires, electrical parts, etc. from rats or other small animals.
If not protected, rats may gnaw at unprotected parts and which may lead to a fire.
l Before performing any brazing work, check to ensure that there is no flammable material around.
l Do not apply excessive force to the flare nut when tightening. If applied, the flare nut may crack due to
aged degradation and refrigerant leakage may occur. Use the specified tightening torque.
CAUTION
l Do not put any foreign material on the unit or inside the unit.
l Do not step or put any material on the product.
It may cause injury by falling down.
l Provide a strong and correct foundation so that;
a. The outdoor unit is not on an incline.
b. Abnormal sound dose not occur.
c. The outdoor unit will not fall down due to a strong wind or earthquake.
l When using refrigerant be sure to wear leather gloves to prevent cold injuries.
l Do not handle the unit by one person. Do not use the PP band to transport the unit although the unit is
packed by PP band. Additionally, do not handle by bare hands. The fin of heat exchanger may cause
injuries.
4 FAN-2207 201709
NOTICE
l Do not install the indoor unit, outdoor unit, wired controller and cable within approximately 3 meters from
strong electromagnetic wave radiators such as medical equipment.
l Supply electrical power to the system to energize the oil heater for 12 hours before startup after a long
shutdown.
l Make sure that the outdoor unit is not covered with snow or ice, before operation.
l The piping connection kit may be damaged if its slope exceeds +15o.
l Do not apply an excessive force to the spindle valve at the end of opening. Otherwise, the spindle valve
flies out by refrigerant pressure. At the test run, fully open the gas and liquid valves, otherwise, the
devices will be damaged. (It is closed before shipment.)
l In the case that the pipes are pulled out from the piping cover, after the insulation work is completed, cover
the gap between the piping cover and pipes by a packing (field-supplied). If the gap is not covered, the
unit may be damaged if snow, rain water or small animals enter the unit.
l Check to ensure that each wire is correctly connected at the power source. If it is incorrectly connected,
the unit will not be operated and the alarm code is indicated. In this case, connect the wires correctly.
NOTE
l It is recommended that the room will be ventilated every 3 to 4 hours.
l The heating capacity of the heat recovery unit is decreased according to the outdoor air temperature.
Therefore, it is recommended that auxiliary heating equipment be used in the field when the units is
installed in a low temperature region.
FAN-2207 201709 5
2. Structure
2.1 Outdoor Unit & Refrigerant Cycle
Regarding structure drawings and refrigerant cycle diagram, please refer to Technical Catalogue.
Use tools and measuring instruments only for the new refrigerant R410A which is directly touch to refrigerant.
NOTICE
l The refrigerant R410A is adopted. The refrigerant oil tends to be affected by foreign matters such as
moisture, oxide film, or fat. Perform the installation work with care to prevent moisture, dust or different
refrigerant from entering the refrigerant cycle. Otherwise foreign materials may get mixed into the cycle
from such parts as expansion valve and the operation may be unavailable.
l To the different refrigerant or refrigerant oil from being mixed into the cycle, the sizes of the charging
connections have been changed from R407C type and R22 type.
It is necessary to prepare the following tools before performing the installation work.
l Use refrigerant pipes and joints which can be used for R410A.
6 FAN-2207 201709
G: Interchangeability is available with current R22 l: only for Refrigerant R410A (No Interchangeability with R22)
5: Prohibited F: only for Refrigerant R407C (No Interchangeability with R22)
Interchangeability
with R22 Reason of Non-Interchangeability and Attention
Measuring Instrument and Tool Use
(H: Strictly Required)
R410A R407C
Pipe Cutter Cutting Pipe
Chamfering G G - Removing Burrs
Reamer
Flaring Tool Gl G * The flaring tools for R407C are applicable to R22. Flaring for Tubes
* If using flaring tube, make dimension of tube larger Dimensional Control
Extrusion for R410A.
l - for Extruded Portion
Adjustment Gauge * In case of material 1/2H, flaring is not available. of Tube after Flaring
* In case of material 1/2H, bending is not available. Bending
Pipe Bender G G
Use elbow for bend and braze.
* In case of material 1/2H, expanding of tube is not Expanding Tubes
Refrigerant Expanding Tool G G
available. Use socket for connecting tube.
Pipe
l G * For f12.7, f15.88, spanner size is up 2mm. Connection of
Torque Wrench * For f6.35, f9.52, f19.05, spanner size is the Flare Nut
G G
same.
Brazing Tool G G * Perform correct brazing work. Brazing for Tubes
* Strict Control against Contamin Prevention from
Nitrogen Gas G G (Blow nitrogen during brazing.) Oxidation during
Brazing
* Use a synthetic oil which is equivalent to the oil Applying Oil to
Lubrication Oil
l F used in the refrigeration cycle. the Flared Surface
(for Flare Surface)
* Synthetic oil absorbs moisture quickly.
* Check refrigerant cylinder color. Refrigerant Charging
Refrigerant
l F H Liquid refrigerant charging is required regarding
Cylinder
zeotoropic refrigerant.
Vacuum Pump G G H The current ones are applicable. However, it is Vacuum Pumping
S required to mount a vacuum pump adapter which
Adapter for l can prevent from reverse flow when a vacuum
F
Vacuum Pump pump stops, resulting in no reverse oil flow.
* No interchangeability is available due to higher Vacuum Pumping,
Vacuum Manifold Valve l F pressures when compared with R22. Vacuum Holding,
Drying H Do not use current ones to the different refrigerant. Refrigerant Charging
l If used, mineral oil will flow into the cycle and and Check of
Refrigerant cause sludges, resulting in clogging or compressor Pressures
Charge failure.
Charging Hose l F Connection diameter is different; R410A: UNF1/2,
R407C: UNF7/16.
Charging Cylinder 5 5 * Use the weight scale. -
Measuring
Weight Scale G G - Instrument for
Refrigerant Charging
Refrigerant Gas S * The current gas leakage detector (R22) is not Gas Leakage Check
l F
Leakage Detector applicable due to different detecting method.
S: Interchangeability with R407C.
FAN-2207 201709 7
3. Before Installation
J T O R 080 V P E R B S 1
Version
Factory
S: Shimizu, Japan
Generation
Power Supply
U: 3~, 460V/60Hz
F: 3~/N, 380V/60Hz
R: 3~, 220V/60Hz
Refrigerant
E: R410A
Module and Combination
A: All Inverter Combination
P: All Inverter Module
Air Discharge
V: Vertical
Capacity
HP x 10 (Example: 080 = 8HP)
Application
R: Heat Recovery
Heat Source
O: Air Source
Market Position
T: Tier-1 Commercial VRF
Brand
J: York Brand
8 FAN-2207 201709
HP 18 20 22 24
Model JTOR180VPEUBS1 JTOR200VPEUBS1 JTOR220VPEUBS1 JTOR240VPEUBS1
< Combination of Base Units > T
HP 26 28 30 32 34
Model JTOR260VAEUBS1 JTOR280VAEUBS1 JTOR300VAEUBS1 JTOR320VAEUBS1 JTOR340VAEUBS1
JTOR120VPEUBS1 JTOR120VPEUBS1 JTOR120VPEUBS1 JTOR140VPEUBS1 JTOR160VPEUBS1
Combination
JTOR140VPEUBS1 JTOR160VPEUBS1 JTOR180VPEUBS1 JTOR180VPEUBS1 JTOR180VPEUBS1
HP 36 38 40 42 44
Model JTOR360VAEUBS1 JTOR380VAEUBS1 JTOR400VAEUBS1 JTOR420VAEUBS1 JTOR440VAEUBS1
JTOR180VPEUBS1 JTOR140VPEUBS1 JTOR180VPEUBS1 JTOR180VPEUBS1 JTOR220VPEUBS1
Combination
JTOR180VPEUBS1 JTOR240VPEUBS1 JTOR220VPEUBS1 JTOR240VPEUBS1 JTOR220VPEUBS1
HP 46 48 50 52 54
Model JTOR460VAEUBS1 JTOR480VAEUBS1 JTOR500VAEUBS1 JTOR520VAEUBS1 JTOR540VAEUBS1
JTOR220VPEUBS1 JTOR240VPEUBS1 JTOR140VPEUBS1 JTOR160VPEUBS1 JTOR180VPEUBS1
Combination JTOR240VPEUBS1 JTOR240VPEUBS1 JTOR180VPEUBS1 JTOR180VPEUBS1 JTOR180VPEUBS1
- - JTOR180VPEUBS1 JTOR180VPEUBS1 JTOR180VPEUBS1
HP 18 20 22 24
Model JTOR180VPEFBS1 JTOR200VPEFBS1 JTOR220VPEFBS1 JTOR240VPEFBS1
< Combination of Base Units > T
HP 26 28 30 32 34
Model JTOR260VAEFBS1 JTOR280VAEFBS1 JTOR300VAEFBS1 JTOR320VAEFBS1 JTOR340VAEFBS1
JTOR120VPEFBS1 JTOR120VPEFBS1 JTOR120VPEFBS1 JTOR140VPEFBS1 JTOR160VPEFBS1
Combination
JTOR140VPEFBS1 JTOR160VPEFBS1 JTOR180VPEFBS1 JTOR180VPEFBS1 JTOR180VPEFBS1
HP 36 38 40 42 44
Model JTOR360VAEFBS1 JTOR380VAEFBS1 JTOR400VAEFBS1 JTOR420VAEFBS1 JTOR440VAEFBS1
JTOR180VPEFBS1 JTOR140VPEFBS1 JTOR180VPEFBS1 JTOR180VPEFBS1 JTOR220VPEFBS1
Combination
JTOR180VPEFBS1 JTOR240VPEFBS1 JTOR220VPEFBS1 JTOR240VPEFBS1 JTOR220VPEFBS1
HP 46 48 50 52 54
Model JTOR460VAEFBS1 JTOR480VAEFBS1 JTOR500VAEFBS1 JTOR520VAEFBS1 JTOR540VAEFBS1
JTOR220VPEFBS1 JTOR240VPEFBS1 JTOR140VPEFBS1 JTOR160VPEFBS1 JTOR180VPEFBS1
Combination JTOR240VPEFBS1 JTOR240VPEFBS1 JTOR180VPEFBS1 JTOR180VPEFBS1 JTOR180VPEFBS1
- - JTOR180VPEFBS1 JTOR180VPEFBS1 JTOR180VPEFBS1
FAN-2207 201709 9
HP 18 20 22 24
Model JTOR180VPERBS1 JTOR200VPERBS1 JTOR220VPERBS1 JTOR240VPERBS1
< Combination of Base Units > T
HP 26 28 30 32 34
Model JTOR260VAERBS1 JTOR280VAERBS1 JTOR300VAERBS1 JTOR320VAERBS1 JTOR340VAERBS1
JTOR120VPERBS1 JTOR120VPERBS1 JTOR120VPERBS1 JTOR140VPERBS1 JTOR160VPERBS1
Combination
JTOR140VPERBS1 JTOR160VPERBS1 JTOR180VPERBS1 JTOR180VPERBS1 JTOR180VPERBS1
HP 36 38 40 42 44
Model JTOR360VAERBS1 JTOR380VAERBS1 JTOR400VAERBS1 JTOR420VAERBS1 JTOR440VAERBS1
JTOR180VPERBS1 JTOR140VPERBS1 JTOR180VPERBS1 JTOR180VPERBS1 JTOR220VPERBS1
Combination
JTOR180VPERBS1 JTOR240VPERBS1 JTOR220VPERBS1 JTOR240VPERBS1 JTOR220VPERBS1
HP 46 48 50 52 54
Model JTOR460VAERBS1 JTOR480VAERBS1 JTOR500VAERBS1 JTOR520VAERBS1 JTOR540VAERBS1
JTOR220VPERBS1 JTOR240VPERBS1 JTOR140VPERBS1 JTOR160VPERBS1 JTOR180VPERBS1
Combination JTOR240VPERBS1 JTOR240VPERBS1 JTOR180VPERBS1 JTOR180VPERBS1 JTOR180VPERBS1
- - JTOR180VPERBS1 JTOR180VPERBS1 JTOR180VPERBS1
T: The outdoor unit from 26 to 54HP consists of the combination of 2 to 3 base units.
The combinations other than listed in above table is prohibited.
NOTE:
Refer to the “Caution about Outdoor Unit Installation”.
10 FAN-2207 201709
3.1.1 CH-Box
<CH-Box>
<Single>
J CH - AP 160 SSX
Applicable System
SSX: for Heat Recovery System (3 Pipes System)
Maximum Connectable Indoor Unit Capacity (HP)
160: 6.0HP
280: 6.1HP - 10.0HP
Refrigerant Type
AP: R410A
Unit Type
CH: Cooling/Heating Change-Over Box
Brand
York Brand
Connectable Indoor Unit Number of Connectable
Model Branch
Total Capacity Indoor Unit(*1)
JCH-AP160SSX 1 6.0HP or less (Max. 16kW) 1-7
JCH-AP280SSX 1 6.1HP - 10.0HP (Max. 28kW) 1-8
( 1)
* When multiple indoor units are connected to the same CH-Box, they are controlled within
the same operation mode.
<Multiple>
J CH - AP 16 M SSX
Applicable System
SSX: for Heat Recovery System (3 Pipes System)
Multiple
Branch
04: 4 Branch
08: 8 Branch
12: 12 Branch
16: 16 Branch
Refrigerant Type
AP: R410A
Unit Type
CH: Cooling/Heating Change-Over Box
Brand
York Brand
Connectable Indoor Unit Number of Connectable
Model Branch
Total Capacity Indoor Unit per Branch(*2)
JCH-AP04MSSX 4 16.0HP or less (Max. 44.8kW) 1-6
JCH-AP08MSSX 8 30.0HP or less (Max. 85kW) 1-6
JCH-AP12MSSX 12 30.0HP or less (Max. 85kW) 1-6
JCH-AP16MSSX 16 30.0HP or less (Max. 85kW) 1-6
( 2)
* The indoor units connected to the same branch of the CH-Box are controlled within the
same operation mode.
FAN-2207 201709 11
12 FAN-2207 201709
NOTES:
1. The connectable indoor unit capacity ratio can be calculated as follows.
Connectable Indoor Unit Capacity Ratio = Total Indoor Unit Capacity / Total Outdoor Unit Capacity
2. For the system under which all the indoor units are supposed to operate simultaneously, the total indoor unit capacity
should be less than outdoor unit capacity. Otherwise, it may cause a decrease of operating performance and operating
limit in overload operation.
3. For the system under which all the indoor units are not supposed to operate simultaneously, the total indoor unit
capacity is available up to 130% against the outdoor unit capacity.
4. Maximum number of connectable indoor units differs depending on the model, capacity, environment and installation
place of connected indoor units. Refer to “Technical Catalog” for the selection.
5. When operating the outdoor unit in cold areas with temperatures of -10oC, or under the high heating load conditions,
the total indoor unit capacity should be less than 100% against the outdoor unit capacity and the total piping length
should be less than 300m.
6. The air flow volume for indoor units of 0.6 to 1.0HP is set higher than that for indoor units of 1.5HP or more. Make sure
to select appropriate indoor units when installing indoor units where cold draft may occur during heating operation. If
installing indoor units in such places, refer to the recommended number of connectable indoor units.
7. (*): For connecting Wall Type with the Expansion Valve Kit, the number of connectable indoor unit is limited according
to the total piping length between the expansion valve and the indoor unit. The total piping length must be less than
the length indicated in the table.
The load capacity per hour or the possibility of all indoor units simultaneous operation is unknown at the design stage,
the total capacity of combined indoor units should be not over 100% against the outdoor unit capacity.
FAN-2207 201709 13
l Do not hang the unit with the sling belts at the wooden base.
CORRECT INCORRECT
Sling Belt
Sling Belt
Long Hole
Apply sling belts
through long holes
Wooden Base
Wooden Base
l The unit shall not be handled by one person. Do not use the PP band to move the unit although
the unit is packed by PP band. Additionally, do not touch the heat exchanger with bare hands.
The fin of heat exchanger may cause injuries.
l Transportation and Storage
The corrugated paper frame is not sufficiently strong. Therefore follow the instructions below in
order to prevent the unit deformation.
* Do not step or put any material on the product. It may cause injury.
* Apply two sling belts onto the outdoor unit, when lifting it with a crane.
l Transportation and Wire Rope
Plastic Bands
* To protect the unit, do not remove any
Corrugated
packing. Paper Frame
* Do not stack or put any material on Attach four 15mm thick
the product. corrugated corner pads
Do not remove
* Apply wire ropes on both sides of the corrugated paper
as shown.
unit as shown in the figure. frame and plastic
bands.
Banding Wire
Wooden Base
14 FAN-2207 201709
Take special care when hanging or moving the outdoor unit because its center of mass is eccentric as shown
in the figure below.
• Center of Gravity
Center of Gravity
a
d
e f c
b
Front Side of Unit
(mm)
460V/60Hz
Outdoor Unit 220V/60Hz
380V/60Hz
(HP)
a b c d e f a b c d e f
8
10 1800 1030 810 700 590 370 1800 1030 810 680 600 370
12
14 1800 1290 810 730 690 370 1800 1290 810 730 690 370
16
1800 1290 810 720 730 340 1800 1290 810 710 730 350
18
20
22 1800 1680 810 710 870 350 1800 1680 810 700 870 350
24
FAN-2207 201709 15
• Hanging Method
(1) Hang the unit under packing condition with 2 sling belts as shown in Fig. 4.1.
(2) Do not use a wire rope.
(3) Ensure a balance of unit.
(4) Check the safety and lift up the unit gently in order not to incline the unit.
Sling Belt
(kg)
380V/60Hz 220V/60Hz
HP
8 10 12 14 16 18 20 22 24 8 10 12 14 16 18 20 22 24
Net Weight 195 195 215 271 314 315 355 369 370 190 190 210 266 309 310 350 364 365
Gross Weight 211 211 231 289 332 333 375 389 390 206 206 226 284 327 328 370 384 385
460V/60Hz
HP
8 10 12 14 16 18 20 22 24
Net Weight 200 200 220 276 319 320 360 374 375
Gross Weight 216 216 236 294 337 338 380 394 395
(5) Hang the unit without wooden base with 2 sling belts as shown in Fig. 4.2.
Sling Belt
Long Hole
Apply sling belt through
the long hole.
16 FAN-2207 201709
When using forklift, do not insert forks into Do not apply excessive force to the square holes
the holes on the unit side. The unit may be with forks or other materials. The bottom of the
damaged. unit may be deformed.
* Do not push the bottom base by a fork.
* Do not use a roller.
CORRECT
Ratchet
Wrench
Outdoor Unit
INCORRECT
Outdoor Unit
Wrench
Wooden Base
Wooden Base
NOTE
In case of transportation after unpacking, protect the unit with corrugated paper boards or cloths.
Mast
Fork
Outdoor unit is Outdoor unit is NOT
Contacted to Backrest Contacted to Backrest
Prevent the outdoor unit from contacting to the backrest of forklift during transportation. If not, the heat
exchanger fin may be broken due to sudden starting or stopping.
Do not put any foreign material into the outdoor unit and check to ensure that nothing exists in the
outdoor unit before the installation and test run. Otherwise, a fire or failure, etc. may occur.
FAN-2207 201709 17
Accessory 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP Remarks
Connection for
Refrigerant
- - - - -
Low Pressure
ID22.2 ID22.2 ID25.4 ID25.4
Gas Pipe →OD19.05 →OD25.4 →OD28.58 →OD28.58
Connection for
Accessory Refrigerant
- - - - -
Pipe High / Low
ID22.2 ID22.2 ID22.2 ID22.2
Pressure Gas Pipe →OD15.88 →OD19.05 →OD25.4 →OD25.4
Connection for
Refrigerant - - - - - - -
Liquid Pipe OD9.52 OD12.7
→OD12.7 →OD15.88
Caution Label
Open/Close
For Indication
Indication for ×3 ×3 ×3 ×3 ×3 ×3 ×3 ×3 ×3 with Fixing Band
of “Open”
Stop Valve
NOTE
If any of these accessories is not packed with the unit, please contact your contractor.
18 FAN-2207 201709
5.2 Installation
l Provide a sufficiently strong foundation. If not, the unit may fall down and it may lead to injuries.
l Do not install the outdoor unit where the flammable gases may occur or leak. Otherwise, it may
cause a fire.
l If the indoor unit is installed in a small room and the refrigerant gas leakage occurs, the leaked
refrigerant gas fills the room and it may cause suffocation. Do not exceed the maximum
permissible concentration of the refrigerant gas in the room. Consult with distributor for
countermeasure such as ventilation system, etc.
NOTES:
1. Do not install the outdoor unit where there is a high level of oil mist, flammable gases, salty air or harmful
gases such as sulphur and an acid or alkaline environment.
2. Do not install the outdoor unit where the electromagnetic wave is radiated directly to the electrical box.
3. Install the outdoor unit as far from the electromagnetic wave radiator as possible, at least 3 meters away
from it.
Air Inlet
Hood
FAN-2207 201709 19
(Unit: mm)
1500
Min.
Vent Hole
h2
Front Rear
Side Side
h1
1500
500
765
- In the case of no walls on the front side and the rear side, the service space is required as follows.
* Front Side: Min. 500mm
* Rear Side: Min. 300mm
* Right and Left Sides: Min. 10mm (In the case that the snow protection hood (optional part) or
the air outlet duct (field-supplied) is amounted to the unit, the spaces of
min. 50mm are required.)
- If the wall on the front side is over 1,500mm high, the space of (500 + h2/2) mm for the front side is
required.
- If the wall on the rear side is over 500mm high, the space of (300 + h1/2) mm for the rear side is required.
- When the units are surrounded by walls on more than 2 sides, the space indicated in the figure above is
required.
- For walls on more than 2 sides, secure the service space as shown in the following figures.
- If the space between the unit and an obstacle above the unit is less than 1,500mm or the space above
the unit is closed, set up the duct at the air outlet side in order to prevent short circuit.
- When there are obstacles above the unit, the four (front, rear, right and left) sides of the unit shall be
open in principle.
20 FAN-2207 201709
1) Walls on 2 Sides
In case that the units are installed adjacent to tall buildings and there are no walls on 2 sides, the
minimum rear side space must be 300mm.
Front Side Front Side Front Side Front Side Front Side
Min. 500 + h2/2
Min. 400 Min. 400
<Top View> <Top View>
*1): In the case that the field-supplied snow protection hood or <Top View>
the air outlet duct is adopted, the space of minimum 50mm is required.
“ ”
This indicates the direction of the unit
(Front Side) when installing the units.
2) Walls on 3 Sides
• Single Installation (Unit: mm)
Min. 10*1)
< Installation in the Same Direction> < Rear to Rear Installation >
No limit for side wall height. No limit for side wall height.
<Top View> <Top View>
*1): In the case that the field-supplied snow protection hood or the air outlet duct is adopted, the space of minimum 50mm is required.
FAN-2207 201709 21
3) Walls on 4 Sides
• Single Installation
No limit for
side wall height.
Min. 300 + h1/2 (Unit: mm)
▼ No limit for
Min. 800
*2)
Front Side side wall height.
Open
Min. 500 + h2/2
<Top View>
< Installation in the Same Direction> < Rear to Rear Installation >
*2): Partly open a wall if the unit is surrounded by walls on four sides.
NOTES:
1. Keep the upper side open to prevent mutual interference of inlet and outlet air of each outdoor unit.
2. The figure dimensions indicate sufficient spaces around outdoor units for operation and maintenance at
typical installation conditions as follows. [ Operation Mode: Cooling Operation, Outside Temp.: 35oC ]
In case that the outdoor unit ambient temperature is higher and also the short circuit is likely to occur
compared to the installation condition, find an appropriate dimension by calculating air flow current.
3. For the multiple installation, 1 group shall consist of 6 outdoor units (max.).
Keep 1-meter interval between each unit group.
22 FAN-2207 201709
5.4 Foundation
• Concrete Foundations
(1) The height of the foundation should be over 150mm above the ground.
(2) Provide a drainage around the foundation for smooth drainage.
Filling Mortar
Min. 150
Drainage (Example)
(Width 100 x Depth 20)
* Provide concrete foundation as shown in the figure. * Do not provide concrete foundation
as shown below. The foot of the
outdoor unit may be deformed.
Min. 100mm
Foot
Foot
Foundation
Min. 100mm Foundation Min. 100mm
Min. 100mm
Min. 100mm (Center of Outdoor Unit) The concrete foundations are
installed to each corner of
The concrete foundations are The concrete foundations are the outdoor unit.
installed along the outdoor unit installed along the outdoor unit In this case, the foot of the
width direction. depth direction. outdoor unit may be deformed.
(3) Install the outdoor unit in the front-rear and right-left direction horizontally. (Use a level gauge.)
Check to ensure that the gradient in four directions (front, rear, right and left) is within 10mm.
Front Side
Right Side and Rear Side
and Left Side
FAN-2207 201709 23
(5) When installing the outdoor unit, fix the unit with anchor bolts and vibration proof mat (field-supplied).
Refer to Fig. 5.1 regarding the location of fixing holes.
(Unit: mm)
Outdoor Unit Dimension
8 - 12HP
Hole for M12 Anchor Bolt
(4 - 38 x 15 Long Hole)
Min. 120
20 - 24HP
Hole for M12 Anchor Bolt
(6 - 38 x 15 Long Hole)
24 FAN-2207 201709
(Unit: mm)
Outdoor Unit Dimension
8 - 12HP
14 - 18HP
20 - 24HP
FAN-2207 201709 25
Name Model
Drain Boss DBS-TP10A
Component Formation of Drain Boss
Model Parts Name Material / Color Q'ty Application
Drain Boss PP / Black 2 Connecting for Drain Piping
DBS-TP10A Drain Cap PP / Black 2 Embolization for Drain Hole
Rubber Cap CR / Black 4 Sealing for Boss and Cap
Quantity
Applicable
Q'ty
Outdoor Unit HP
8 - 18 1
20 - 36 2
38, 40 3
42 - 48 4
50 - 54 3
NOTE
1. When installing the unit above a passage way, drain water sometimes turns to ice on a cold morning.
Therefore, avoid discharging the water into places which people often pass through, because it is slippery.
2. When drain piping is necessary for the outdoor unit, use the drain boss set (Optional, DBS-TP10A).
Do not use drain boss and drain pan kit in the cold area. The drain water in the drain pipe may be frozen
and then the drain pipe may crack.
26 FAN-2207 201709
l Use the specified non-flammable refrigerant R410A to the outdoor unit in the refrigerant cycle.
Do not charge material other than R410A into the unit such as hydrocarbon refrigerants (propane
or etc.), oxygen, flammable gases (acetylene or etc.) or poisonous gases when installing,
maintaining and moving the unit. These flammables are extremely dangerous and may cause an
explosion, fire, and injury.
l Check to ensure that no pressure exists inside the stop valve before removing the flange.
l Make sure that the refrigerant leakage test is performed. The refrigerant (Fluorocarbon R410A)
for this unit is nonflammable, non-toxic and odorless. However, if the refrigerant leaks and
contacts fire, toxic gas will generate. Also because the fluorocarbon is heavier than air, the floor
surface will be filled with it, which could cause suffocation.
l For installation, firmly connect the refrigerant pipe before the compressor starts operating.
For maintenance, relocation and disposal, remove the refrigerant pipe after the compressor
stops.
If the compressor is operated under the condition that the stop valves are opened without
refrigerant pipe, it may cause abnormal high pressure in refrigerant cycle and may cause an
explosion, fire or injury.
l Before performing any brazing work, check to ensure that there is no flammable material around.
If not, it may cause a fire.
l If the indoor unit is installed in a small room and the refrigerant gas leakage occurs, the leaked
refrigerant gas fills the room and it may cause suffocation. Do not exceed the maximum
permissible concentration of the refrigerant gas in the room. Consult with distributor for an
appropriate ventilation system, etc.
l Check the design pressure for this product is 4.15MPa.
The pressure of refrigerant R410A is 1.4 times higher than that of refrigerant R407C. The
thickness of copper pipe differs depending on its materials, so use the specified piping.
If the specified materials are not used, it may cause explosion, injury, leakage, or fire.
l Ensure to connect the piping among the units in the same refrigerant cycle.
l Wear leather gloves when handling the refrigerant.
If the refrigerant splashes directly to hands, it may be the cause of frostbite.
l Do not apply an excessive force to the flare nut when tightening it. Otherwise, the flare nut may
crack due to aged degradation and refrigerant leakage may occur. Use the specified tightening
torque.
NOTICE
l The refrigerant R410A is adopted. The refrigerant R410A and the refrigerant oil tend to be
affected by foreign matters such as moisture, oxide film, or fat. Perform the installation work
with care to prevent moisture, dust or different refrigerant from entering the refrigerant cycle.
Otherwise, foreign materials may get mixed into the cycle from such parts as expansion valve
and the operation may be unavailable.
l Perform the drain piping work in order to drain water securely. If not, the drain water can flow
back to the unit and it may cause leakage to the room.
FAN-2207 201709 27
Hole Hole
• Brazing Work
(1) The brazing work must be performed by a authorized installer in order to prevent any trouble.
(2) For piping connection, perform securely non-oxidation brazing with nitrogen substitution. If brazing
the pipes without the nitrogen substitution, a large amount of oxidized scale will be generated in the
pipes. This oxidized scale may cause clogging in the expansion valve, solenoid valve, accumulator
and compressor, which can prevent the unit from operating properly.
Do not use field-supplied antioxidant, etc., which may corrode pipes and deteriorate the refrigerant oil.
Pressure Reducing Valve
(Stop Valve)
Nitrogen Gas
Pipe Valve
Piping Connection on-site (φ6.35)
NOTE:
Do not cover the outlet. If the inner Cover the gap with
Nitrogen
pressure exceeds atmospheric pressure, taping or a rubber plug
Gas
a pinhole may generate and the refrigerant to prevent air from entering
gas will leak from the brazing part. the pipe interior.
NOTES:
1. Make sure to use nitrogen. Nitrogen gas pressure shall be 0.02 MPa or less.
DO NOT use the following gases.
Oxygen: flammable and causes oxidation degradation of the refrigerant oil.
Carbon Dioxide: may cause decrease in drier performance.
Freon Gas: emits harmful gases if exposed to fire.
(3) Use a quality brazing filler metal specified in JIS. Select a flux whose chlorine concentration is low.
(4) Remove the flux completely after the brazing work.
NOTE:
When the brazing work is performed, perform brazing to minimum portion by appropriate temperature
to suppress generating oxidized scale.
28 FAN-2207 201709
Do not apply
the refrigerant oil
to the outside of
the flaring part.
(4) Be sure to use the accessory flare nuts for indoor unit connections.
(5) In case that the temperature and humidity inside the ceiling exceed 27oC/RH80%, apply additional
insulation (approx. 10mm in thickness) to the accessory insulation. It prevents dew condensation on
the surface of the insulation (refrigerant pipe only).
(6) Perform the air-tight test (4.15MPa for the test pressure).
(7) Perform cold insulation work by insulating and taping the flare connection and reducer connection.
Also insulate all the refrigerant pipes.
FAN-2207 201709 29
● When connecting the indoor unit and outdoor unit refrigerant pipes, the refrigerant pipes shall be supported
appropriately. Do not let contact them with the weak strength portion of a wall or a ceiling. If not, it may
cause abnormal sound due to piping vibration.
● Precautions during installing and fixing the pipes.
CORRECT
within + 15o
Outdoor Unit
Multi-Kit
Indoor Unit
Install multi-kits horizontally.
Example: Recommended From each Indoor Unit to Multi-Kit, use hard copper pipes that bend to prevent kinking.
NOTE
When on-site piping with joint such as elbow or socket is buried, provide a service access door to
facilitate the check for connecting part.
Do not apply an excessive force to the flare nut when tightening it. Otherwise, the flare nut may
crack due to aged deterioration and refrigerant leakage may occur. Use the specified tightening
torque.
30 FAN-2207 201709
FAN-2207 201709 31
90o + 2o
(mm)
+0
45 o Diameter A
+ 2o -0.4
(fd)
fA R410A
6.35 9.1
9.52 13.2
0.4 ~ 0.8R
12.7 16.6 (T) It is impossible to perform the flaring
15.88 19.7 work with 1/2H material. In this case,
fd 19.05 (T) use an accessory pipe (with a flare).
• Joint Selection
If 1/2H material is used, the flaring work cannot be performed. In this case, use a joint selected from the
table below.
< Minimum Thickness of Joint (mm) > < Flare Nut Dimension B (mm) >
Diameter R410A Diameter R410A B
32 FAN-2207 201709
Piping Outlet Outdoor Unit Outdoor Unit Outdoor Unit Outdoor Unit Outdoor Unit Outdoor Unit Piping Outlet
Direction A B C C B A Direction
: Keep the straight-line distance of 500mm or more for piping after the piping connection kit.
FAN-2207 201709 33
Select the pipe size according to the item 6.5.1 - 6.5.3 “Piping Size between Outdoor Units”.
For refrigerant piping work, the optional piping connection kit is required to branch the pipe between outdoor
units.
The arrangement for outdoor units should be determined depending on the piping direction when the
refrigerant piping work and installation work are planned. When the outdoor unit is installed, perform the
installation work according to the following restrictions.
(1) Piping length between piping connection kit 1 and each outdoor unit should be
LA < LB < LC < LD <10m.
Keep the straight-line distance of 500mm or more after the piping connection kit 1.
Upstream Side
(2) Place the piping connection kit lower than the outdoor unit piping connection.
In case that the piping connection kit is placed higher than the outdoor unit piping connection, keep
300mm (max.) between the piping connection kit and the bottom of the outdoor unit. Also, provide the
oil trap (min. 200mm) between the piping connection kit and the outdoor unit.
Max. Max.
Max.
Indoor Unit Side 300mm 300mm
300mm
The refrigerant oil is stagnated to the unit stopped.
34 FAN-2207 201709
(3) In case that the piping length between outdoor units is 2m or more, the oil trap for the gas pipe should
be provided so that accumulation of refrigerant oil may not occur.
(4) Place the outdoor unit pipe horizontally or with the pipe slanted downward towards the indoor unit side
so that accumulation of refrigerant oil may not occur in the pipe.
(5) For servicing, in case that the pipe is placed frontward of the outdoor unit, secure min. 500mm
between the outdoor unit and piping connection kits. (When the compressor is replaced, a space of
min. 500mm is required.)
Outdoor Unit Outdoor Unit Outdoor Unit
Min. 500mm
Piping Piping
Connection Kit Connection Kit
within + 15o
NOTICE
The refrigerant system may be damaged if the slope of the piping connection kit exceeds +15o.
FAN-2207 201709 35
● Prepare the refrigerant pipe in the field for the piping work.
Refer to Fig. 6.1 for the position of piping connection.
(Unit: mm)
Piping Cover
N
Square Hole of Piping Cover
(Knockout Hole)
D
E
100
J (Liquid Piping Connection)
253
248
F
K (Low Pressure Gas Piping Connection)
92
L (High/Low Pressure Gas Piping Connection)
Power Source Wiring Outlet M 127
(φ65 Knockout Hole) Low Pressure Gas
High/Low Pressure Gas Piping and Liquid Piping Outlet Piping Outlet
* The figures illustrate the examples of a small cabinet. (Knockout Square Hole) (Knockout Square Hole)
36 FAN-2207 201709
● Piping Direction
Fix the pipes adequately in order to avoid vibration and excessive
force to the valve.
(1) The pipes can be installed in three directions (front, rear or
bottom side) from the bottom base.
For vibration protection, properly fix the piping connection and
check that no excessive force is applied to the stop valve. Front Side
Bottom Base
(2) Operation of the stop valve should be performed according to Item 6.5.4.
(3) Connect the pipes according to Table 6.1 and 6.2.
(4) Completely seal the penetration part at the bottom of the pipes with insulation in order to prevent rain
water from entering the conduit.
● For Piping from Bottom Base ● For Piping from Front or Rear Side Piping Cover
Low Pressure
Gas Pipe
Power Source
Cover gaps with packings (field-supplied). Wiring Liquid High/Low Pressure
Install accessory rubber bushes to the wiring outlets. Pipe Gas Pipe
NOTICE
After removing the pipes and completing insulation work, cover the gap between the pipe cover and the
pipes with packing (field-supplied). If the gap is not covered, the unit may be damaged if snow, rain water or
animals enter the unit.
FAN-2207 201709 37
Outdoor Unit
a
Refrigerant Piping
To Indoor Units
(fmm)
Outdoor Unit
8 10 12 14 16
(HP)
Low Pressure 19.05 22.2 25.4 25.4 28.58
Gas (19.05 - 22.2) (22.2 - 25.4) (25.4 - 28.58) (25.4 - 28.58) (28.58 - 31.75)
High/Low 15.88 19.05 22.2 22.2 22.2
Piping Size a
Pressure Gas (15.88-19.05) (19.05 - 22.2) (22.2 - 25.4) (22.2 - 25.4) (22.2 - 25.4)
9.52 9.52 12.7 12.7 12.7
Liquid
(9.52 - 12.7) (9.52 - 12.7) (12.7 - 15.88) (12.7 - 15.88) (12.7 - 15.88)
Outdoor Unit
18 20 22 24
(HP)
Low Pressure 28.58 28.58 28.58 28.58
Gas (28.58 - 31.75) (28.58 - 31.75) (28.58 - 31.75) (28.58 - 31.75)
High/Low 22.2 22.2 25.4 25.4
Piping Size a
Pressure Gas (22.2 - 25.4) (22.2 - 25.4) (25.4 - 28.58) (25.4 - 28.58)
15.88 15.88 15.88 15.88
Liquid
(15.88-19.05) (15.88-19.05) (15.88-19.05) (15.88-19.05)
If the specified main refrigerant piping on the table is not available on site, follow the allowable piping size in parentheses.
When using the main refrigerant piping indicated in parentheses, prepare an appropriate reducer on site.
38 FAN-2207 201709
a b b a
c c
To Indoor Units Piping Connection Kit Piping Connection Kit To Indoor Units
(fmm)
Outdoor Unit
26 28 30 32 34 36
(HP)
Combination Outdoor Unit A 14 16 18 18 18 18
Unit Outdoor Unit B 12 12 12 14 16 18
Piping Connection Kit MC-NP21SX
Low Pressure 31.75 31.75 31.75 31.75 31.75 38.1
Gas (31.75-34.9) (31.75-34.9) (31.75-34.9) (31.75-34.9) (31.75-34.9) (38.1-41.3)
High/Low 25.4 28.58 28.58 28.58 28.58 28.58
a
Pressure Gas (25.4-28.58) (28.58-31.75) (28.58-31.75) (28.58-31.75) (28.58-31.75) (28.58-31.75)
19.05 19.05 19.05 19.05 19.05 19.05
Liquid
(19.05-22.2) (19.05-22.2) (19.05-22.2) (19.05-22.2) (19.05-22.2) (19.05-22.2)
Low Pressure 25.4 28.58 28.58 28.58 28.58 28.58
Gas (25.4-28.58) (28.58-31.75) (28.58-31.75) (28.58-31.75) (28.58-31.75) (28.58-31.75)
High/Low 22.2 22.2 22.2 22.2 22.2 22.2
Piping Size b
Pressure Gas (22.2-25.4) (22.2-25.4) (22.2-25.4) (22.2-25.4) (22.2-25.4) (22.2-25.4)
12.7 12.7 15.88 15.88 15.88 15.88
Liquid
(12.7-15.88) (12.7-15.88) (15.88-19.05) (15.88-19.05) (15.88-19.05) (15.88-19.05)
Low Pressure 25.4 25.4 25.4 25.4 28.58 28.58
Gas (25.4-28.58) (25.4-28.58) (25.4-28.58) (25.4-28.58) (28.58-31.75) (28.58-31.75)
High/Low 22.2 22.2 22.2 22.2 22.2 22.2
c
Pressure Gas (22.2-25.4) (22.2-25.4) (22.2-25.4) (22.2-25.4) (22.2-25.4) (22.2-25.4)
12.7 12.7 12.7 12.7 12.7 15.88
Liquid
(12.7-15.88) (12.7-15.88) (12.7-15.88) (12.7-15.88) (12.7-15.88) (15.88-19.05)
Outdoor Unit
38 40 42 44 46 48
(HP)
Combination Outdoor Unit A 24 22 24 22 24 24
Unit Outdoor Unit B 14 18 18 22 22 24
Piping Connection Kit MC-NP21SX
Low Pressure 38.1 38.1 38.1 38.1 38.1 38.1
Gas (38.1-41.3) (38.1-41.3) (38.1-41.3) (38.1-41.3) (38.1-41.3) (38.1-41.3)
High/Low 31.75 31.75 31.75 31.75 31.75 31.75
a
Pressure Gas (31.75-34.9) (31.75-34.9) (31.75-34.9) (31.75-34.9) (31.75-34.9) (31.75-34.9)
19.05 19.05 19.05 19.05 19.05 19.05
Liquid
(19.05-22.2) (19.05-22.2) (19.05-22.2) (19.05-22.2) (19.05-22.2) (19.05-22.2)
Low Pressure 28.58 28.58 28.58 28.58 28.58 28.58
Gas (28.58-31.75) (28.58-31.75) (28.58-31.75) (28.58-31.75) (28.58-31.75) (28.58-31.75)
High/Low 25.4 25.4 25.4 25.4 25.4 25.4
Piping Size b
Pressure Gas (25.4-28.58) (25.4-28.58) (25.4-28.58) (25.4-28.58) (25.4-28.58) (25.4-28.58)
15.88 15.88 15.88 15.88 15.88 15.88
Liquid
(15.88-19.05) (15.88-19.05) (15.88-19.05) (15.88-19.05) (15.88-19.05) (15.88-19.05)
Low Pressure 25.4 28.58 28.58 28.58 28.58 28.58
Gas (25.4-28.58) (28.58-31.75) (28.58-31.75) (28.58-31.75) (28.58-31.75) (28.58-31.75)
High/Low 22.2 22.2 22.2 25.4 25.4 25.4
c
Pressure Gas (22.2-25.4) (22.2-25.4) (22.2-25.4) (25.4-28.58) (25.4-28.58) (25.4-28.58)
12.7 15.88 15.88 15.88 15.88 15.88
Liquid
(12.7-15.88) (15.88-19.05) (15.88-19.05) (15.88-19.05) (15.88-19.05) (15.88-19.05)
* Perform the installation of the outdoor unit and piping connection according to the figure.
Refer to the table for the outdoor unit model, the piping connection kit model and the piping diameter.
* If the specified main refrigerant piping on the table is not available on site, follow the allowable piping size in parentheses.
When using the main refrigerant piping indicated in parentheses, prepare an appropriate reducer on site.
FAN-2207 201709 39
a c d d c a
b e e b
Piping Connection Kit 1 Piping Connection Kit 2 Piping Connection Kit 2 Piping Connection Kit 1
To Indoor Units To Indoor Units
(fmm)
Model 50 52 54
Outdoor Unit A 18 18 18
Combination
Outdoor Unit B 18 18 18
Unit
Outdoor Unit C 14 16 18
Piping Connection Kit MC-NP30SX
Low Pressure 38.1 38.1 38.1
Gas (38.1-41.3) (38.1-41.3) (38.1-41.3)
High/Low 31.75 31.75 31.75
a
Pressure Gas (31.75-34.9) (31.75-34.9) (31.75-34.9)
19.05 19.05 19.05
Liquid
(19.05-22.2) (19.05-22.2) (19.05-22.2)
Low Pressure 31.75 31.75 31.75
Gas (31.75-34.9) (31.75-34.9) (31.75-34.9)
High/Low 28.58 28.58 28.58
b
Pressure Gas (28.58-31.75) (28.58-31.75) (28.58-31.75)
19.05 19.05 19.05
Liquid
(19.05-22.2) (19.05-22.2) (19.05-22.2)
Low Pressure 28.58 28.58 28.58
Gas (28.58-31.75) (28.58-31.75) (28.58-31.75)
High/Low 22.2 22.2 22.2
Piping Size c
Pressure Gas (22.2-25.4) (22.2-25.4) (22.2-25.4)
15.88 15.88 15.88
Liquid
(15.88-19.05) (15.88-19.05) (15.88-19.05)
Low Pressure 28.58 28.58 28.58
Gas (28.58-31.75) (28.58-31.75) (28.58-31.75)
High/Low 22.2 22.2 22.2
d
Pressure Gas (22.2-25.4) (22.2-25.4) (22.2-25.4)
15.88 15.88 15.88
Liquid
(15.88-19.05) (15.88-19.05) (15.88-19.05)
Low Pressure 25.4 28.58 28.58
Gas (25.4-28.58) (28.58-31.75) (28.58-31.75)
High/Low 22.2 22.2 22.2
e
Pressure Gas (22.2-25.4) (22.2-25.4) (22.2-25.4)
12.7 12.7 15.88
Liquid
(12.7-15.88) (12.7-15.88) (15.88-19.05)
* Perform the installation of the outdoor unit and piping connection according to the figure.
Refer to the table for the outdoor unit model, the piping connection kit model and the piping diameter.
* If the specified main refrigerant piping on the table is not available on site, follow the allowable piping size in parentheses.
When using the main refrigerant piping indicated in parentheses, prepare an appropriate reducer on site.
40 FAN-2207 201709
Service Port
Stop Valve for Gas Valve
(High/Low Pressure)
Stop Valve for Liquid Valve
Stop Valve for Stop Valve for Gas Pipe (Body)
Liquid Valve (High/Low Pressure)
Stop Valve for Gas Valve
(Low Pressure) Heat Exchanger Fin
Heat Stop Valve for Gas Pipe (Body)
Exchanger (Low Pressure)
Stop Valve Cover
(Read the precautions.)
Field-Work Side
l Ensure that there is no gas inside the pipe when removing the closing pipe.
Otherwise, the pipe may be blown out and it may lead to injury.
l Do not expose surrounding parts and the oil return pipe of the compressor to flames when torch
is used. If the oil return piping is exposed to the fire, high temperature oil will spurt and cause a
fire or injury.
Flare Nut
l Do not apply an excessive force to the spindle valve after fully opening the spindle.
The back seat construction is not provided.
l At the test run, fully open the spindle. If it is not fully opened, the devices will be damaged.
FAN-2207 201709 41
Refrigerant Pressure
Cap
Tightening Torque: 49.0 - 58.0 N-m
Spindle Valve
Counterclockwise...Open
Clockwise...............Close Tightening Torque (N-m)
Tightening Torque: (a) N-m
Spindle Valve (a)
Outdoor Unit
(HP) High/Low Low Pressure
Pressure Gas Gas
8 - 12 18.0 - 22.0 18.0 - 22.0
14 - 24 18.0 - 22.0 25.0 - 31.0
Cap
Tightening Torque: (b) N-m
O-ring
Hexagonal Wrench Refrigerant Pressure
To open or close
spindle valve
Wrench Size: (e)
Spindle Valve
Counterclockwise...Open
Clockwise...............Close
Tightening Torque: (c) N-m
Flare Nut
Tightening Torque: (d) N-m
Refrigerant Piping
l Do not apply an excessive force to the spindle valve after fully opening the spindle.
The back seat construction is not provided.
l At the test run, fully open the spindle. If it is not fully opened, the devices will be damaged.
42 FAN-2207 201709
FAN-2207 201709 43
Flaring Flaring
Liquid Pipe 90° Elbow B Liquid Pipe 90° Elbow B
(Field Supplied) (Field Supplied) (Field Supplied) (Field Supplied)
90° Elbow B 90° Elbow B
(Field Supplied) (Field Supplied)
Gas Pipe
Accessory Pipe (B) Accessory Pipe (A) Accessory Pipe (B) (Field Supplied)
Flaring
Flaring
Accessory Pipe (C) 90° Elbow B 90° Elbow B
Liquid Pipe
90° Elbow B (Field Supplied) (Field Supplied) (Field Supplied)
(Field Supplied)
90° Elbow B
90° Elbow A
(Field Supplied) (Field Supplied)
Gas Pipe Gas Pipe
Accessory Pipe (A) Gas Pipe
(Field Supplied) (Field Supplied)
(Field Supplied)
Flaring
Flaring
90° Elbow B Accessory Pipe (C) 90° Elbow B
Liquid Pipe
(Field Supplied) (Field Supplied) 90° Elbow B (Field Supplied)
(Field Supplied)
90° Elbow B
90° Elbow A
(Field Supplied) (Field Supplied)
Gas Pipe Accessory Pipe (A) Gas Pipe
Accessory Pipe (A)
(Field Supplied) (Field Supplied)
Flaring Flaring
Liquid Pipe 90° Elbow B Liquid Pipe 90° Elbow B
(Field Supplied) (Field Supplied) (Field Supplied) (Field Supplied)
90° Elbow B 90° Elbow B
(Field Supplied) (Field Supplied)
Gas Pipe Gas Pipe
Gas Pipe Accessory Pipe (B)
(Field Supplied) (Field Supplied)
(Field Supplied)
NOTES:
1. Ensure that the closing pipe of the gas stop valve is removed firstly.
2. Refer to the item 6.2 for the flaring work.
NOTE
When connecting the outdoor unit gas stop valve and the field-supplied
refrigerant pipe, do not apply excessive force to the stop valve pipe as
illustrated on the right.
This may loosen the stop valve spindle.
44 FAN-2207 201709
● Construction Example
The following figures show the examples of 3 units combination.
Regarding the piping work for Combination Unit, refer to “Installation & Maintenance Manual” attached to
the piping connection kit.
Accessory
Indoor Unit B
Pipe
Indoor Unit C
Foundation
P
Low Pressure Gas Piping
(Field-Supplied)
Accessory Pipe <View from P>
Piping Connection Kit 1 (L-Shape)
(Low Pressure Gas)
Foundation
Accessory
Low Pressure Gas Piping Pipe
Piping Connection Kit 1
(Field-Supplied)
(High/Low Pressure Gas)
Accessory Pipe
High/Low Pressure Gas Piping
(L-Shape)
(Field-Supplied)
Piping Connection Kit 2
(Low Pressure Gas)
Piping Connection Kit 2 Liquid Piping
(High/Low Pressure Gas) High/Low Pressure Gas Piping
(Field-Supplied) ˃ 500mm (Field-Supplied)
Accesory Pipe
(Z-Shape)
High/Low Pressure Gas Piping
(Field-Supplied) Outdoor Unit B
Base
Low Pressure Gas Piping (Field-Supplied)
(Field-Supplied)
NOTE:
The figure shows the case that the refrigerant pipes are pulled out from the front side piping cover.
They can be also pulled out from the bottom base hole.
FAN-2207 201709 45
For selecting the pipe sizes between the outdoor unit and the piping connection kit 1 , between the piping
connection kits 2 and for piping connection kit A , refer to the items from 6.5.1 to 6.5.3 “Piping Size between
Outdoor Units”.
5 5 5
E E E
CH CH CH
4
7 7 7 5 High/Low Pressure Gas Pipe
Three Pipes Portion
Indoor Indoor Indoor
Unit Unit Unit 5 Low Pressure Gas Pipe
C
5
CH-M CH-M
E 7 7 7 7 5 Liquid Pipe
Indoor Indoor Indoor Indoor 6 7 Gas Pipe
Unit Unit Unit Unit 6 7 Gas Pipe
6 7 Liquid Pipe
C 6 7 Liquid Pipe
• • • *3
5 6 6
CH Two Pipes Portsion
E D D Two Pipes Portsion
6 7 7 7
Indoor Indoor Indoor Refer to page 54 “ E CH-Box” for details of branch number
Unit Unit Unit
D
: High/Low Pressure Gas Pipe,
7 7 Low Pressure Gas Pipe, Liquid Pipe
Terminal
Indoor Indoor Unit : Gas Pipe, Liquid Pipe
Unit
: Low Pressure Gas Pipe, Liquid Pipe
(Exclusive Use of Cooling Operation)
CH : CH-Box (Single Branch Type)
CH-M : CH-Box (Multiple Branch Type)
E F
5 5 5
CH CH CH
7 7 7 7 7 7
Indoor Indoor Indoor Indoor Indoor Indoor
Unit Unit Unit Unit Unit Unit
Header branch cannot be connected to upstream or downstream piping of CH-Box (multiple branch type).
46 FAN-2207 201709
C Multi-Kit after First Branch (3 Pipes Portion) E For 2 Pipes Portion < Header Branch >
Total Total No. of Header
Model Model
Indoor Unit HP Indoor Unit HP Branches
<6 MW-NP142X3 5 - 10 8 JMH-NP288X
6 - 11.99 MW-NP282X3
12 - 17.99 MW-NP452X3
18 - 21.99 MW-NP562X3 F For 3 Pipes Portion < Header Branch >
22 - 25.99 MW-NP692X3 Total No. of Header
Model
> 26 MW-NP902X3 Indoor Unit HP Branches
5-8 4 JMH-NP224A
5 - 10 8 JMH-NP288A
FAN-2207 201709 47
6 [Pipe Diameter for 2 Pipes and Multi-Kit] 7 [Pipe Diameter between Multi-Kit and Indoor Unit]
Total Indoor Unit Indoor Unit HP Gas Liquid
Gas Liquid
HP 1.5 or less 12.7 6.35 (*)
<6 15.88 9.52 2.0 15.88 6.35 (*)
6 - 8.99 19.05 9.52 2.5 to 6.0 15.88 9.52
9 - 11.99 22.2 9.52 8.0 19.05 9.52
12 - 15.99 25.4 12.7 10.0 22.2 9.52
16 - 17.99 28.58 12.7 16.0 28.58 12.7
18 - 25.99 28.58 15.88 20.0 28.58 15.88
(*): When the liquid piping length is longer than 15m, use
f9.52 pipe and reducer (field-supplied).
NOTE:
The pipe diameter should be the same as the indoor unit
piping connection size.
48 FAN-2207 201709
< Example 1 > Line Branch (Including Main Pipe Branch) < Example 2 > Using Piping Connection Kit
a c e d f h
First Branch
b Piping Connection Kit
g
Indoor Terminal Indoor Terminal
Multi-Kit Unit Indoor Unit First Branch Unit Indoor Unit
Multi-Kit
A B A B
NOTE:
The main pipe branch is the piping branch method where
Multi-Kits are connected to the pipes both after the first branch.
a b
c Indoor Unit
Main Pipe d e
Branch
f
FAN-2207 201709 49
Indicate what installer must comply with. This is not an example of compliance. Describe the limitation
shown in the drawing.
< For two and three units combination > Upstream Side
First Branch
L3
CH-M CH
L3
H6 H6
Indoor Indoor Indoor Indoor
Unit Unit Unit Unit
L3
e f
H4 g h i H1
Indoor Indoor Indoor
Unit Unit Unit
H2
e f
CH L1
i L2
g h L3
L3
Indoor Indoor
Indoor Unit Unit H3
Unit
(Exclusive Use of
Cooling Operation) Terminal
Indoor Unit
Header Branch Header Branch (CH-Box in Common Use)
CH
e
L3 CH CH CH f g h
L4 Indoor Indoor Indoor
Indoor Indoor Indoor Unit Unit Unit
Unit Unit Unit
: High/Low Pressure Gas Pipe, Low Pressure Gas Pipe, Liquid Pipe
: Gas Pipe, Liquid Pipe
: Low Pressure Gas Pipe, Liquid Pipe
CH : CH-Box (Single Branch Type)
CH-M : CH-Box (Multiple Branch Type)
50 FAN-2207 201709
NOTES:
1. For 2 and 3 outdoor unit combination, the outdoor unit “A” should be connected to the piping connection kit 1.
(Refer to the items 6.5.2 for the outdoor unit models.)
The details of piping connection kit shall be referred to the installation manual of itself.
2. The piping length between outdoor units should be La < Lb < Lc < 10m.
(If the piping length is incorrect, it may cause failure of outdoor unit due to flowing back the refrigerant.)
3. Keep the straight line distance of 500mm or more after the piping connection kit.
4. For the exclusive cooling operation, connect indoor units with low pressure gas pipe and liquid pipe (without CH-
Box). The total capacity of the exclusive cooling operation should be smaller than 50% of the total indoor unit
capacity.
5. The condition of refrigerant piping installation is different depending on the connected indoor unit quantities.
Refer to the table 3.2 “System Combination” in item 3.2 for details.
6. Allowable total piping length may become shorter than 1,000m due to the limitation of maximum additional refrigerant
amount as following table.
HP 8, 10 12 14 - 18 20, 22 24 26 - 54
Max. Additional Refrigerant Charge (kg) 28 36 40 51 52 63
7. If the piping length (L3) between each multi-kit and indoor unit is considerably longer than other indoor unit,
refrigerant may not flow well and also performance may be deteriorated compared to other models.
(Recommended Piping Length: within 15m)
8. For the maximum pipe length of 100m or more, the liquid pipe size of the main pipe (the piping connection kit 1 to the
first branch) should be increased by one size with reducer (field-supplied).
9. In the case that the pipe length between the first branch and the terminal indoor unit is more than 40m, make sure to
follow “Piping Branch Restriction“ when installing.
10. Install the bent pipe or (horizontal) loop pipe to the on-site installed pipe in order to absorb the stretch of the
refrigerant pipe caused by the temperature change.
11. (*) in the table above is optional.
12. In the case that the height difference between the CH-Box and the indoor unit is large, performance may be
deteriorated.
13. The header branch cannot be connected to either before or after the multiple branch type CH-Box.
FAN-2207 201709 51
(1) In the case that the piping length L2 is over 40m, the size of gas and liquid lines “b and c” or “g and h”
should be increased by one size with reducers (field-supplied).
*If (a) is smaller than (b, g) after increasing the size, increase the size of (a) to the same size as (b, g).
(2) The difference between the piping length from the first branch to the farthest indoor unit and the piping
length from the first branch to the closest indoor unit must be within 40m.
*(g+h+j)-(b+d)<40m
Piping Length from the Multi-Kit at the first branch
to the terminal Indoor Unit is within 40 ~ 90m
L2
a b c e
d f
First Branch Terminal
Multi-Kit The Closest Indoor Unit Indoor Unit
from the First Branchޓ
L2
g
j Terminal
h Indoor Unit
i k
(1) In the case that L2 is over 40m, the size of gas and liquid lines “b, d and f” should be increased by one
size with reducers (field-supplied).
*If (a) is smaller than (b) after increasing the size, increase the size of (a) to the same size as (b).
b d f h
a
c e g i Terminal
First Branch Indoor Unit
Multi-Kit
The Closest Indoor Unit The Farthest Indoor Unit
from the First Branch from the First Branch
(T): Main Piping Branch: Both of the pipes branched from a Multi-Kit are connected to the next Multi-Kits.
Header branch can be used with line branch. Header branch can also be used after the second branch.
Do not connect a line branch to a header branch. When using header branch, make sure that the piping
length L2 from the Multi-Kit at the first branch to the farthest indoor unit is within 40m.
Within 40m
Line Branch
Header Branch
Header Branch
Indoor Unit
Within 40m
52 FAN-2207 201709
NOTES:
1. The connectable indoor unit capacity ratio can be calculated as follows.
Connectable Indoor Unit Capacity Ratio = Total Indoor Unit Capacity / Total Outdoor Unit Capacity
2. For the system under which all the indoor units are supposed to operate simultaneously, the total
indoor unit capacity should be less than outdoor unit capacity. Otherwise, it may cause a decrease of
operating performance and operating limit in overload operation.
3. For the system under which all the indoor units are not supposed to operate simultaneously, the total
indoor unit capacity is available up to 130% against the outdoor unit capacity.
4. When operating the outdoor unit in cold areas with temperatures of -10oC, or under the high heating
load conditions, the total indoor unit capacity should be less than 100% against the outdoor unit
capacity and the total piping length should be less than 300m.
5. The air flow volume for indoor units of 0.8 and 1.0HP is set higher than that for indoor units of
1.5HP or more. Make sure to select appropriate indoor units when installing indoor units where
cold draft may occur during heating operation. If installing indoor units in such places, refer to the
recommended number of connectable indoor units.
6. For connecting Tempclean Indoor Unit and Outdoor Air Processing Air Conditioner, the number of the
indoor units should be within recommended connectable indoor units number.
7. If combination capacity of indoor units exceed 100% of outdoor unit capacity, there might be the
possibility of insufficient capacity of 130% combination ratio. Refer to the technical catalog for the
detail. If combination capacity exceed 130% contact your distributer or dealer.
* Contact your distributer or dealer if the capacity of combination ratio exceed 130%.
The system configuration exceed combination ratio of 130% without consultation with distributer or
dealer is not acceptable. It may cause activation of alarm and operation failure.
The load capacity per hour or the possibility of all indoor units simultaneous operation is unknown at the design
stage, the total capacity of combined indoor units should be not over 100% against the outdoor unit capacity.
FAN-2207 201709 53
7. Electrical Wiring
l Turn OFF the main power switch of the indoor unit and the outdoor unit and wait for more than
3 minutes before electrical wiring work or a periodical check is performed.
l Check to ensure that the indoor fan and the outdoor fan have stopped before electrical wiring work
or a periodical check is performed.
l Protect the wires, electrical parts, etc. from rats or other small animals.
If not, rats may gnaw at unprotected parts, which may lead to a fire.
l Avoid the wirings from touching the refrigerant pipes, plate edges and electrical parts inside the
unit. If not, the wires will be damaged and at the worst, a fire will occur.
l Use a medium sensing speed type ELB (Earth Leakage Breaker, activation speed of 0.1 sec. or
less). If not, it will cause an electric shock or a fire.
l Fix the cables securely. External forces on the terminals could lead to a fire.
l Tighten screws according to the following torque.
M4: 1.0 to 1.3 N-m
M5: 2.0 to 2.5 N-m
M6: 4.0 to 5.0 N-m
M8: 9.0 to 11.0 N-m
M10: 18.0 to 23.0 N-m
l Set DSW7 on the PCB1 according to each power supply shown in the figure below.
No setting is required.
220V Unit: 220V Setting Before Shipment
380V Unit: 380V Setting Before Shipment
400V Unit: 400V Setting Before Shipment
460V Unit: 460V Setting Before Shipment
Setting is required.
380-415V Unit: 415V Setting Before Shipment
Heat Pump ON ON ON
(2 Pipes) OFF OFF OFF
1 2 3 4 1 2 3 4 1 2 3 4
l The electrical wiring work must be performed by authorized installers in order to prevent an electric
shock or a fire.
l Perform the electrical work according to the regulation of each region and “Installation &
Maintenance Manual”, and the dedicated electrical circuit must be used. If the electrical wiring
work is performed incorrectly or there is a capacity shortage of the power circuit, it will cause an
electric shock or a fire.
l Use the specified cables for wiring between the outdoor unit and indoor units. Selecting incorrect
cables will cause an electric shock or a fire.
l Tightly secure the wirings to the terminal block according to the specified torque. If tightening the
terminals is not completed, heat generation, an electric shock or a fire will occur at the terminal
connections.
l Tightly clamp the wires with a cord clamp after the wiring to the terminal block has been completed.
In addition, run securely the wires through the wiring hole. If not, the wires will be pinched and it
may cause a fire.
l Turn OFF the power source when handling the service connector. Otherwise, it may cause an
electric shock.
54 FAN-2207 201709
l The ELB (earth leakage breaker), FUSE and S (main switch) must be installed for each outdoor unit
and also for each indoor unit group. If not, it may cause an electrical shock or fire.
l Perform the electrical work according to the regulation of each region and “Installation &
Maintenance Manual”, and the dedicated electrical circuit must be used. If the electrical wiring
work is performed incorrectly or there is a capacity shortage of the power circuit, it will cause an
electric shock or a fire.
l Check that the ground wire is securely connected. If the unit is not correctly grounded, it may lead
to an electrical shock.
Do not connect the ground wiring to a gas piping, water piping, lighting conductor or ground wiring
for telephone.
l The power sources for the indoor unit and outdoor unit should be supplied respectively.
l The power source for each indoor unit group should be supplied respectively.
FAN-2207 201709 55
10 10 10
S
FUSE
Indoor Indoor
ELB Unit 11 Unit 11
(2) The recommended wire size and main switch( 1 ~ 8 ) are shown in Table 7.1.
Please refer to the indoor units and CH-Box installation manual for other cables ( 9 ~ 11 ).
• Select the capacity of power transformer according to the maximum running current.
• When the power supply wiring is too long, select the minimum wiring size whose voltage drop is within
2%.
• Power supply voltage should comply with the following requirements.
Supply Voltage: Rated Voltage within ±10%
Starting Voltage: Rated Voltage within -15%
Operating Voltage: Rated Voltage within ±10%
Imbalance between Phases: within 3%
• Calculate short-circuit current from the power transformer and electrical wiring length and size, and
select the appropriate rated capacity for ELB (earth leakage breaker).
• Select ELB which can be used for the high harmonic wave.
l Do not connect the earth wire to the gas pipe, water pipe or lightening conductor.
Gas Pipe: An explosion and ignition may occur when gas leaks.
Water Pipe: Earth wire becomes ineffective when a hard vinyl pipe is used.
Lightning Conductor: The earth electric potential abnormally increases
when a lightening conductor is used.
56 FAN-2207 201709
(3) The recommended wiring, ELB, breaker size are shown in Table 7.1 and 7.2.
Table 7.1 Electrical Data and Recommended Wiring, Breaker Size/1 Outdoor Unit
3
1 ELB
Maximum Main Switch
Power
Running Nominal
Model Power Supply Supply Line Nominal Nominal 2 Fuse
Current Sensitive
Current Current
Current
(A) (fmm) (A) (mA) (A) (A)
JTOR080VPEUBS1 14.0 MLFC 2.0SQ 20 30 20 20
JTOR100VPEUBS1 19.0 MLFC 3.5SQ 30 30 25 25
JTOR120VPEUBS1 21.0 MLFC 3.5SQ 30 30 25 25
JTOR140VPEUBS1 26.0 MLFC 5.5SQ 30 30 32 32
JTOR160VPEUBS1 460V/60Hz 29.5 MLFC 5.5SQ 40 30 40 40
JTOR180VPEUBS1 33.5 MLFC 5.5SQ 40 30 40 40
JTOR200VPEUBS1 39.5 MLFC 8.0SQ 50 30 50 50
JTOR220VPEUBS1 40.0 MLFC 8.0SQ 50 30 50 50
JTOR240VPEUBS1 47.5 MLFC 14.0SQ 60 30 63 63
JTOR080VPEFBS1 15.5 MLFC 2.0SQ 20 30 20 20
JTOR100VPEFBS1 21.5 MLFC 3.5SQ 30 30 25 25
JTOR120VPEFBS1 24.0 MLFC 3.5SQ 30 30 25 25
JTOR140VPEFBS1 29.5 MLFC 5.5SQ 30 30 32 32
JTOR160VPEFBS1 380V/60Hz 33.0 MLFC 5.5SQ 40 30 40 40
JTOR180VPEFBS1 37.5 MLFC 5.5SQ 40 30 40 40
JTOR200VPEFBS1 44.5 MLFC 8.0SQ 50 30 50 50
JTOR220VPEFBS1 45.0 MLFC 8.0SQ 50 30 50 50
JTOR240VPEFBS1 53.0 MLFC 14.0SQ 60 30 63 63
JTOR080VPERBS1 25.5 MLFC 3.5SQ 30 30 30 30
JTOR100VPERBS1 35.0 MLFC 5.5SQ 40 30 60 40
JTOR120VPERBS1 39.0 MLFC 8.0SQ 40 30 60 40
JTOR140VPERBS1 48.0 MLFC 14.0SQ 50 30 60 50
JTOR160VPERBS1 220V/60Hz 54.5 MLFC 14.0SQ 60 30 60 60
JTOR180VPERBS1 61.5 MLFC 14.0SQ 75 30 75 75
JTOR200VPERBS1 72.5 MLFC 22.0SQ 75 30 75 75
JTOR220VPERBS1 73.5 MLFC 22.0SQ 75 30 75 75
JTOR240VPERBS1 87.0 MLFC 22.0SQ 100 30 100 100
ELB: Earthleakage Breaker, MLFC: Flame Retardant Polyflex Wire
Install main switch and ELB for each system separately. Select the high response type of ELB that acts
within 0.1 second.
FAN-2207 201709 57
58 FAN-2207 201709
NOTES:
1) Follow the local codes and regulations when selecting field wires.
2) The wire sizes marked with *1 in the table of the previous page are selected at the maximum current of the unit
according to the European Standard, EN60 335-1. Use the wires which are not lighter than the ordinary tough
rubber sheathed flexible cord (code designation H05RN-F) or ordinary polychloroprene sheathed flexible cord (code
designation H05RN-F).
3) The wire sizes marked with *2 in the table of the previous page are selected at the maximum current of the unit
according to the wire, MLFC (Flame Retardant Polyflex Wire) manufactured by Hitachi Cable Ltd., Japan.
4) Use a shielded cable for the transmitting circuit and connect it to the ground.
5) In the case that power cables are connected in series, add apply maximum current to each unit and select appropriate
wires in the table below.
NOTE:
Use 2-core cable (equivalent to following cables: VCTF, VCT, CVV, MVVS, VVR or VVF, size: 0.75mm2 to 1.25mm2
(manufactured by HITACHI Cable Co. Ltd.)) or 2-core twist pair cable (equivalent to following cables: KPEV or KPEV-S
(manufactured by HITACHI Cable Co. Ltd.)) for the control cable between the outdoor unit and the indoor unit.
The total transition wiring length between the indoor unit and the outdoor unit should be less than 1000m and the total
transition wiring length between outdoor units should be less than 30m.
Install a multi-pole main switch with a space of 3.5mm or more between each phase.
FAN-2207 201709 59
60 FAN-2207 201709
Earth Terminal
(Connect
Attach securely cable.)
Attach insulation sleeve.
insulation sleeve.
Earth Wire
Ground Wiring Terminal
(Connect cable securely) Rubber Bush
Ground Wiring Cable Clamp
Cable Band (Accessory)
Control Wiring
(2) Detail of Terminal Block for Control Circuit
Power Source Wiring
Screw (M3.5) PCB1 Terminal Block
for Control Circuit
(5) Details of Wiring Outlets inside the Electrical Box (Rubber Bush Section)
Rubber Bush (Wiring Outlet)
Using a cutter knife, cut
an X in the rubber bush
Correct Incorrect on site as shown below. Make sure that the power source wiring
passes through the center of the rubber bush.
Correct Incorrect
Snow or water
may enter.
Rubber Bush
Rubber Bush
Electrical Box Rubber
(Metal) Make sure that the rubber bush Bush If the power source wiring does not pass through
is in place. properly, snow or water may enter in the unit.
FAN-2207 201709 61
Be sure to note the following points to run the cables under the unit using conduit tube.
(The pipe cover needs to be removed before performing piping and wiring works.)
NOTES:
1. Do not run the power supply wiring and transmission wiring through the same conduit tube.
Moreover, keep at least 5cm between the power supply wiring and transmission wiring.
2. Pull out each wiring from each corresponding knockout hole. Cut can “X” in rubber bush (accessory)
and securely attach it to the knockout hole for cable protection.
Check that the rubber bush is surely attached.
3. Attach the pipe cover to prevent rats or other small animals from entering the unit.
4. Prevent the wirings from touching or rub against the refrigerant pipes, plate edges and electrical parts
inside the unit.
5. When the power source cable (cabtyre cable) whose size exceeds 38mm2 is used, peel the sheath part
of the cable put into the unit and run it. At this time, do not damage the coated insulating coated part.
6. Completely seal the end of conduit tube with sealing materials to prevent the rain from entering the
conduit tube.
7. Make a drain hole at the lowest part of the conduit tube.
NOTE
Fix the rubber bushes with adhesive when conduit
Cover gaps with packings (field-supplied).
tubes to the outdoor unit are not used. Install accessory rubber bushes to the wiring outlets.
62 FAN-2207 201709
• Transmission Wiring
Refrigerant Group 1 (Heat Pump System) Refrigerant Group 2 (Heat Recovery System)
Transmission Wire
for Main ~ Sub
Transmission Wire
for H-LINK System CH-Box No.1 CH-Box No.2
TB1 TB2 TB1 TB2
L1 L N 1 2 3 4
2
L1 L N 1 2 3 4
2
2 1 B A N L 2 L1 2 1 B A N L2 L1 2 1 B A N L2 L1 2 1 B A N L2 L1 2 1 B A N L2 L1 2 1 B A N L2 L1
TB2 TB1 TB2 TB1 TB2 TB1 TB2 TB1 TB2 TB1 TB2 TB1
Unit No. 0 Unit No.1 Unit No. 2 Unit No. 0 Unit No.1 Unit No. 2
Indoor Unit Indoor Unit Indoor Unit Indoor Unit Indoor Unit Indoor Unit
NOTES:
1. For the combination units (26-54HP), DSW settings of Main and Sub are required.
2. Alarm occurs if the transmission wires between main outdoor unit and sub outdoor units are connected to
the terminals 1 and 2 for H-LINK system.
3. In case that alarm is indicated on the LCD of Main outdoor unit, follow the "7-segment" indication of the Main
outdoor unit for checking.
4. Perform function setting at Main outdoor unit.
5. Maximum number of refrigerant groups with one central controller is 64 (for H-LINK II).
Maximum number of indoor units to be connected is 160 (for H-LINK II).
FAN-2207 201709 63
ELB ELB
Main
Switch
3N CH-Box 1 CH-Box 2 CH-Box 3
380V/60Hz FUSE
TB1 TB2 TB1 TB2 TB1 TB2
L1 N 1 2 3 4 L1 N 1 2 3 4 L1 N 1 2 3 4
ELB ELB
3N
380V/60Hz
Distribution Box
or Pull Box
FUSE L1 L2 N L1 L2 N L1 L2 N L1 L2 N L1 L2 N
TB1 TB1 TB1 TB1 TB1
ELB ELB No. 0 No. 1 No. 2 No. 3 No. 4
Indoor Unit Indoor Unit Indoor Unit Indoor Unit Indoor Unit
1 TB2 TB2 TB2 TB2 TB2
220-240V/50Hz A B 1 2 A B 1 2 A B 1 2 A B 1 2 A B 1 2
220V/60Hz
ELB ELB
Main
Switch For Mexico model For Mexico model
3 Except for Mexico model
CH-Box 1 CH-Box 2 CH-Box 3
220V/60Hz FUSE
TB1 TB2 TB1 TB2 TB1 TB2 TB1
460V/60Hz R S R S R S R S
L1 L2 1 2 3 4 L1 L2 1 2 3 4 L1 L2 1 2 3 4 L1 N
ELB ELB
3
220V/60Hz
460V/60Hz Distribution Box
or Pull Box
FUSE R S Mp R S Mp R S Mp R S Mp R S Mp
TB1 TB1 TB1 TB1 TB1
ELB ELB No. 0 No. 1 No. 2 No. 3 No. 4
Indoor Unit Indoor Unit Indoor Unit Indoor Unit Indoor Unit
TB2 TB2 TB2 TB2 TB2
1 A B 1 2 A B 1 2 A B 1 2 A B 1 2 A B 1 2
220V/60Hz
7-Segment
(7SEG)
Screw
Screw
Make sure to re-attach the access door into the electrical box cover and to close the front cover after the job
is finished.
NOTICE
● Shut the access door after performing the service work, otherwise a malfunction may occur due to water
or foreign materials entering.
● Operate the switches and push switches with an insulated stick (such as a closed ball-point pen) to avoid
electrical shocking.
FAN-2207 201709 65
NOTE
l By using switch DSW4, the unit is started 10 to 20 seconds after the switch
is operated.
l For service and maintenance, number this outdoor unit to distinguish it
from the other outdoor units.
And write down the number in the box right.
Arrangement of Dip Switches (PCB1) DSW1 (PCB1) Ref. Cycle No. Setting DSW3 (PCB1) Function Setting
Display Setting is required. No setting is required.
(7SEG)
Setting Before Shipment Setting Before Shipment Setting Before Shipment
except Middle East only Middle East
SEG2 SEG1 Setting Position
ON ON
RSW1
PSW2 DSW1 0 1 2 3 4 1 2 3 4
DSW4 DSW7 9 1
ON
23
78
PSW5 PSW1 PSW3
DSW2 DSW3 4 56 DSW4 (PCB1) Test Run and Service Setting
Enter
1 2 3 4 5 6
PSW4 DSW5 DSW6 Setting is required. For Test Run, Function Setting
Tens Digit Last Digit
DSW8 Setting Before and External Input/Output Setting
DSW1 Set the unit number of outdoor unit at each Shipment
RSW1
refrigerant cycle. ON
DSW10 (Setting before shipment is unit 0.)
1 2 3 4 5 6
DSW2 (PCB1) Capacity Setting
Setting Item Pin No.
No setting is required. Test Cooling Operation 1
Test Heating Operation 1, 2
< Standard Type >
Compressor Forced Stop 4
Capacity 8HP 10HP 12HP 14HP 16HP
Function Setting 4, 5
ON ON ON ON ON External Input/Output Setting 4, 6
DSW2
Setting
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 DSW5 (PCB1) Emergency Operation
Capacity 18HP 20HP 22HP 24HP Turn ON the dip switch
No setting is required.
when use the below
ON ON ON ON Setting Before
DSW2 functions.
Setting Shipment
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Setting Item Pin No.
ON Except No.1 Comp.
1
(MC1) Operation
< High Efficiency Type > 1 2 3 4 5 6 Except No.2 Comp.
Capacity 5HP 6HP 8HP 10HP 2
(MC2) Operation
ON ON ON ON
DSW2
Setting DSW8 (PCB1) High Static Pressure Mode
Setting
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Capacity 12HP 14HP 16HP 18HP Setting is required. Turn ON the dip switch
when use the below functions.
ON ON ON ON Setting Before
DSW2
Shipment Setting Item Pin No.
Setting
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 ON HSP Setting: 30Pa 1
HSP Setting: 60Pa 2
1 2 3 HSP Setting: 80Pa 1, 2
DSW6 (PCB1) Outdoor Unit No. Setting/Function Setting
Setting is required.
IMPORTANT NOTICE
Combination Setting
Unit A Unit B Unit C Unit D When adopting the air outlet duct
Single Setting (field-supplied), make sure to set DSW8.
(Setting Before Shipment) (No.0 Unit) (No.1 Unit) (No.2 Unit) (No.3 Unit)
ON ON ON ON ON
DSW10 (PCB1) Transmission Setting
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 Set DSW10-1 correctly
Setting is required.
for end resistance cancellation.
Turn ON the dip switch when use the below functions. Setting Before
Setting Item Pin No.
Shipment
Setting Item Pin No. IMPORTANT NOTICE End Resistance Setting *1 1
ON
The outdoor unit is not single, the combination setting Fuse Recovery *2 2
Outdoor Unit No. Setting 1, 2, 3
is necessary. Be sure to do this setting.
1 2 *1: Turn OFF No.1 pin for all of
Cooling Operation Under the outdoor units in the same H-LINK
Make sure to apply Snow Protection Hood system except one outdoor unit.
Low Load Operation 4
(Optional Parts). *2: If the fuse (EF1) is melted,
(Low Ambient Setting)
set No.2 pin to ON for recovery.
DSW7 (PCB1) Power Supply Voltage and System Setting INV No. Setting
DSW101 (INV1, 2) /Service Setting
No setting is required.
No setting is required.
220V Unit: 220V Setting Before Shipment
380V Unit: 380V Setting Before Shipment INV1 INV2
400V Unit: 400V Setting Before Shipment
Setting Before Shipment Setting Before Shipment
460V Unit: 460V Setting Before Shipment
ON ON
Setting is required.
380-415V Unit: 415V Setting Before Shipment 1 2 3 4 5 6 1 2 3 4 5 6
Power Supply Voltage and System Setting Turn ON the dip switch when
use the below functions.
220V 380V 400V 415V 460V
Setting Item Pin No.
ON ON ON ON ON
Heat Pump Cancellation of Current Detection 1
(2 Pipes)
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
IMPORTANT NOTICE
ON ON ON ON ON
Heat Recovery If Cancellation of Current Detection is set,
(3 Pipes) make sure to return the setting, after
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 service works.
ON ON ON ON
OFF OFF OFF OFF
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
23
78
ON OFF
OFF 901 Set by inserting 456
1 2 3 4 5 6 slotted screwdriver 1 2 3 4 5 6
23
78
23
23
78
78
78
SET FREE
Series
Refrigerant Cycle for UTOPIA Series Maximum Number of Connectable
Outdoor Unit
This Outdoor Unit Outdoor Unit Outdoor Units and Indoor Units
(for H-LINK II)
Transmission Line Outdoor Unit 64
(No Polarity) Indoor Unit 160
H-LINK or H-LINK II
Set to the same refrigerant NOTE:
cycle No. For installing the outdoor unit
and the indoor unit on the same
transmission wire, which cannot
Indoor be used for H-LINK II, maximum
Unit number of connectable indoor units
Wired Controller Centralized Controller is 128.
FAN-2207 201709 67
In the case of one refrigerant cycle in the same H-LINK or H-LINK II, set all No. 1 pins of DSW10 in the “OFF”
position except the main outdoor unit A.
12 12 12
Indoor
Unit
In the case of more than one refrigerant cycles in the same H-LINK or H-LINK II, set all No. 1 pins of
DSW10 in the “OFF” position except the main outdoor unit A.
12 12 12 12 12 12 12
Transmission Line
(No Polarity) Cancel the end terminal setting.
H-LINK or H-LINK II
Wired Controller
68 FAN-2207 201709
• Function Setting
FAN-2207 201709 69
70 FAN-2207 201709
Procedure
Recommended
Manufacturer
Completion of Applying Check of
Pass Forming Agent
Ref. Piping Nitrogen Gas Pressure Decrease
Yokogawa
Guproflex
Repairing of & CO.,Ltd
Leakage Part
Be sure to use Nitrogen Gas for air-tight test. If other gases such as oxygen gas, acetylene gas or
fluorocarbon gas are accidentally used, it may cause an explosion or gas intoxication.
● For Piping from Bottom Base ● For Piping from Front or Rear Side Piping Cover
Control Wiring Liquid Pipe Cover gaps with packings (field-supplied).
Transition Wiring High/Low Pressure Gas Pipe Install accessory rubber bushes to the wiring outlets.
Power Source Low Pressure Gas Pipe Piping Control Wiring
Wiring Cover
Transition Wiring
Low Pressure
Gas Pipe
Power Source
Cover gaps with packings (field-supplied). Wiring
Install accessory rubber bushes to the wiring outlets. Liquid High/Low Pressure
Pipe Gas Pipe
FAN-2207 201709 71
8.2 Vacuuming
[Step 2]
(1) Vacuum until the pressure reaches 1000 microns (1.0 mmHg).
(2) Pressurize with nitrogen up to 0.3 MPaG (50 PSIG) for 15 minutes.
(3) Release pressure to atmosphere level as less than 0.03 MPaG (5 PSIG).
[Step 3]
(1) Vacuum until the pressure reaches 500 microns (0.5 mmHg).
(2) Stop vacuum pump.
(3) Check that the vacuum 500 microns (0.5 mmHg) can maintain for one hour.
NOTICE
1. If tool or measuring instruments come into contact with the refrigerant, use the tools or the measuring
instruments exclusively for R410A.
2. Do not perform vacuuming pumping work with valves of the outdoor units open.
Otherwise, the refrigerant charged before shipment may leak and it may result in failure.
If moisture remains inside the pipes, the compressor may be damaged.
72 FAN-2207 201709
NOTES:
1. Some refrigerant charge calculations differ when installing Wall Type (RPK-FSXNSH3 Series) with the expansion
valve kit. Refer to the item “Additional Refrigerant Calculation for Wall Type (RPK-FSXNSH3 Series) with the
Expansion Valve Kit” .
2. Ensure that the total additional refrigerant charge quantity should not exceed the max. additional refrigerant charge
quantity shown below.
< Max. Additional Refrigerant Charge Quantity >
Outdoor Unit Capacity (HP) 8, 10 12 14 - 18 20, 22 24 26 - 54
Max. Additional Ref. Charge (kg) 28.0 36.0 40.0 51.0 52.0 63.0
FAN-2207 201709 73
(4) Regarding the fluorocarbon, follow the specification label or refrigerant label attached to the product. After
the additional refrigerant charge, record the total refrigerant (= refrigerant before shipment + additional
refrigerant in the field) in the refrigerant label (*).
(*): In case of the combination of base units, record the total refrigerant in the main unit label.
NOTE:
When the refrigerant is recovered or charged because of repairing, operating or adjusting the unit, record the
refrigerant quantity again.
NOTICE
1. Emissions of the fluorocarbons without any reason are prohibited.
2. For disposal and maintenance of this product, collection of fluorocarbons is required.
74 FAN-2207 201709
Do not apply an excessive force to the spindle valve after fully opening the spindle. Otherwise,
the spindle valve flies out due to refrigerant pressure. At the test run, open fully the spindle valve,
otherwise, the devices will be damaged. (It is closed before shipment.)
(b) Operate the compressor in the cooling mode and charge the additional refrigerant from the check
joint of the liquid stop valve (acceptable error must be within 0.5 kg). At this time, keep the liquid
stop valve slightly opened
(c) After the refrigerant is charged, fully open the liquid stop valve and the gas stop valve.
(d) Calculate securely the additional refrigerant quantity for charging. If the quantity of additional
refrigerant is not correct, it may cause compressor failure. The additional refrigerant must be
charged in a liquid condition.
(e) Refrigerant charge from check joint of gas stop valve may lead to compressor failure. Be sure to
charge refrigerant from the check joint of liquid stop valve.
FAN-2207 201709 75
Manifold
Outdoor Unit C Outdoor Unit B Outdoor Unit A Gauge Nitrogen Tank
Stop Valve Stop Valve Stop Valve (for Nitrogen Blow during Brazing
(for High/Low (for High/Low (for High/Low and Airtight Test)
Pressure Gas) Pressure Gas) Pressure Gas)
Stop Valve Stop Valve Stop Valve
(for Low (for Low (for Low
Pressure Gas) Pressure Gas) Pressure Gas)
Insulation
Multi-Kit [Cover the gas and liquid pipe with insulation.]
Charge the correct refrigerant Insulate the flare nut and union
quantity according to Table 8.1. of the piping connection with
If not, a compressor may be insulation.
damaged due to an excess or
insufficient refrigerant charge.
Check to ensure that there
is no gas leakage. If a large
Refrigerant charge from check refrigerant leakage occurs, it will
joint of gas stop valve may lead cause difficulty with breathing or
to compressor failure. Be sure harmful gases would occur if a
to charge refrigerant from the fire was being used in the room.
check joint of liquid stop valve.
76 FAN-2207 201709
The room where the packaged air conditioner is installed, the refrigerant gas should be controlled not to
exceed the limit concentration in case of the refrigerant leakage.
The refrigerant R410A of incombustible and non-toxic is adopted with this unit. If by any chance the
refrigerant gas is leaked and filled in the room, the possibility of suffocation may occur.
The outdoor unit is multi-type air conditioner by connecting multiple indoor units with long distance piping.
Accordingly, the refrigerant charging quantity is larger than general individual unit. Before the indoor unit
installation, confirm that the room can keep the lower gas concentration than the limit value in order to take
the emergency countermeasures even if the gas leakage is occurred.
250
(Countermeasures
Not Needed)
150
50
FAN-2207 201709 77
After calculation, the room to install this unit is proved not to keep the gas concentration lower than the limit
value. However, the air conditioner should be installed in this room from unavoidable circumstances, each of
the following countermeasures should be taken.
Outdoor Unit
Refrigerant Flow
Refrigerant Cycle
Indoor Unit
(1) The gas leakage detector & alarm system and interlocking mechanical ventilation equipment (with
ventilation capacity over 0.42m3/min per refrigerating ton) should be installed. Refer to the following
figure.
Outdoor Unit Refrigerating Refrigerating
Outdoor Unit
(HP) Ton Ton
8 3.08 32 12.31
10 3.69 34 13.12
12 4.52 36 13.94
14 5.34 38 14.38
16 6.15 40 15.60
18 6.97 42 16.01
20 7.59 44 17.26
22 8.63 46 17.67
24 9.04 48 18.08
26 9.86 50 19.28
28 10.67 52 19.61
30 11.49 54 19.93
(2) Provide the opening for ventilation between rooms* in order not to exceed the permissible
concentration.
* It is opening without door or opening at the top or bottom of door with floor space more than 0.15%.
< Example > Refrigerant Piping
Refrigerant Charge: 60kg
Outdoor Unit
Indoor Unit
The Smallest
Room
Medium-sized
Small Room Room Large Room
NOTES:
1. The quantity of refrigerant gas leakage against each room should be calculated as 60kg each.
2. The refrigerant concentration must be below 0.42 kg/m3 for each room.
The installer and system specialist shall secure against leakage according to local regulations or standards.
The following standards may be applicable, if local regulations are not available.
International Organization for Standardization, ISO5149 or European Standard, EN378 or Japan Standard,
KHKS0010.
78 FAN-2207 201709
9. Test Run
Test run should be performed according to the Item 9.2. And use the Table 9.1 for recording test run.
l Check to ensure that each wire is correctly connected at each phase of power suplly. If it is
incorrectly connected, the unit will not operate and the alarm code will be indicated. In this case,
connect each wire correctly.
l Do not operate the system until all the check points have been cleared.
As for the test run of indoor unit, check “Installation & Maintenance Manual” attached to the indoor
unit.
FAN-2207 201709 79
(5) Be sure to close the service cover at the front lower side when the test run is performed.
(6) Combination Unit Model Label
In case of the combination of base units, attach the combination unit model label to a visible spot
of the main unit (outdoor unit A) so that the outdoor unit A can be identified easily.
Do not attach it to the sub unit (outdoor unit B and C).
NOTICE
1. Confirm that field-supplied electrical components (main switch fuse, fuse-free breaker, earth leakage
breakers, wires, conduit connectors and wire terminals) have been properly selected according to the
electrical data shown in Table 7.1 and 7.2, and ensure that the components comply with national and local
codes.
2. Use shielded wires (>0.75mm2) for field wiring to avoid electrical noise obstacle. (Total length of shielded
wire shall be less then 1000m, and size of shielded wire shall comply with local codes.)
3. Check the terminal for power source wiring (terminals “L1” to “L1” and “N” to “N” of each terminal block:
AC 400V, 380-415V, 380V, terminals “R” to “L1” and “S” to “L2” of each terminal block: AC 220V).
If not, some components will be damaged.
80 FAN-2207 201709
FAN-2207 201709 81
Do NOT operate the air conditioners to check the electrical wiring, etc until the preparation of
the test run is completed.
82 FAN-2207 201709
8. Check Pressure
Discharge Pressure: MPa
Suction Pressure: MPa
9. Check Voltage
Rated Voltage: V
Operating Voltage: L1-L2 V, L1-L3 V, L2-L3 V
Starting Voltage: V
V
Phase Imbalance: 1- =
Vm
21. Does the drain water flow smoothly from the drain pipe?
FAN-2207 201709 83
84 FAN-2207 201709
FAN-2207 201709 85
86 FAN-2207 201709
Johnson Controls reserve the right to change product features without prior notice.
P5417049
NOTE
Hand over this installation manual to the next installation work personal.
2. Transportation
Transport the product as close to the installation location as practical before unpacking.
3. Before Installation
Confirm the number of the following parts by referring to the model printed on the package before unpacking.
Do NOT put any foreign material into the parts. Check to confirm that no foreign materials are inside the parts
before installation.
NOTICE:
If any of these parts are missing, please contact your distributor. Do not discard any foam packaging as it is
used as insulation for the joint kits after pressure testing is complete.
Model MC-NP30SX
MC-NP20SX MC-NP21SX
Piping Connection Kit 1 Piping Connection Kit 2
Name of Parts Qty. Qty. Qty. Qty.
Branch Pipe for
Low Pressure
Gas Line 1 1 1 1
Branch Pipe for
High/Low Pressure
Gas Line 1 1 1 1
Insulation for
Liquid Line
1 set 1 set 1 set 1 set
Reducer for 1 1 1 1
Low Pressure
Gas Line Connection
(For Connecting Pipe
1 1 1 1
Accessory
(Field-Supplied))
- - -
None None 1 None
Reducer for 1 1 1 1
High/Low Pressure
Gas Line Connection
(For Connecting Pipe
1 1 1 1
(Field-Supplied))
2 2 1 2
Reducer for
Liquid Line Connection 1 1 1 1
(For Connecting Pipe
(Field-Supplied)) - - -
None None 1 None
Tape
3 3 3 3
P5417030
4. Installation Work
4.1 Piping Connection Size
The ends of the multi-kits are finished as shown in the following figures. Cut the end of the pipe to correspond to
the pipe size.
Allow adequate space for elbow, angled, and irregular piping arrangements to compensate for
expansion and contraction brought on by temperature change.
OD 25.4
ID 19.05 ID 19.05 ID 12.7 ID 9.52 ID 25.4
OD 25.4
ID 22.2 ID 22.2 ID 22.2 ID 22.2 ID 15.88 ID 22.2
ID 25.4
457 457 378 ID 19.05
ID 22.2
ID 25.4 ID 25.4 ID 25.4 ID 25.4 ID 15.88
ID 19.05
ID 19.05 OD 25.4 OD 19.05
ID 28.58 ID 28.58
ID 19.05
MC- ID 15.88
NP20SX
ID 25.4 ID 12.7
OD 25.4
80
ID 19.05 ID 22.2
84
84
80
ID 28.58
95
(To Piping Connection Kit 2) (To Piping Connection Kit 2) (To Piping Connection Kit 2)
ID 28.58 ID 28.58
ID 31.75 ID 25.4 ID 31.75 ID 25.4 ID 15.88 ID 9.52 ID 25.4 ID 25.4 OD 19.05
472 472 378
Piping Connection Kit 1
ID 22.2 ID 22.2
ID 28.58 ID 28.58 ID 12.7 ID 15.88
ID 31.75 ID 31.75 ID 25.4
ID 15.88 ID 12.7
ID 38.1 ID 31.75
ID 38.1 ID 19.05 ID 28.58
ID 9.52
OD 31.75
95
OD 28.58
95
80
ID 25.4 ID 9.52
80
ID 25.4
95
Upward
Straight Section Inclination
within +15o
Min. 500mm Caution Label
o
+15
Downward Inclination
Horizontally A (View from A)
INCORRECT
Use the field-supplied connecting pipe in accordance with the installation and maintenance manual for the outdoor
units. If necessary, use a reducer (accessory).
Liquid Piping
(Field-Supplied) Piping Connection Kit 2
(Liquid)
Accessory Outdoor Unit B
Pipe
Outdoor Unit C
Low Pressure
Gas Piping
(Field-Supplied) Foundation
P
Piping Connection Kit 1
(Low Pressure Gas) View from P
(21)
(43)
f5 - 28 (50)
(70)
70 or less
(2) Use clean copper pipes without any moisture or foreign materials on inner surface of pipes. When
connecting refrigerant pipe, cut the copper pipes with a copper tube cutter as shown below. Also deburr
the cutting edge using deburring tool to ensure that no burr goes inside the pipe. Blow-out the pipes with
nitrogen or compressed air to ensure that no dust remains inside the pipe. Do NOT use a saw, a grindstone
or other tools which causes a large amount of powder residue when cutting.
Pipe
Deburring
Connection
Part
(3) When cutting the pipe, allow for an adequate depth for brazing as shown in the following table.
(mm)
Diameter Min. Insertion Depth
(A) (B) B
Over 5, Below 8 6
Over 8, Below 12 7
Over 12, Below 16 8
A
When installing pipe through the Do NOT place the pipe directly In case of rain attach a cap or
wall, secure a cap at the end of on the ground. put a plastic bag over the pipe end.
the pipe.
INCORRECT CORRECT INCORRECT CORRECT INCORRECT
Hole
Attach a cap Rain water
or plastic bag can enter.
Attach a cap with rubber
Attach a cap or vinyl tape. band.
or vinyl tape.
CORRECT
(4) Make sure that all stop valves for the outdoor unit are closed completely.
(5) Blow-out the inside of the pipes with nitrogen gas before brazing. Bleed nitrogen gas through piping during
brazing. Pressure not to exceed 0.02MPa.
Make sure that a test for leakage of refrigerant gases has been performed. The refrigerant used for this
unit (HFC R410A), is a non-flammable, non-toxic, and odorless gas. However if refrigerant should leak
and make contact with sparks, and catch on fire, toxic gas will be generated. Fluorocarbon, which is
heavier than air, will form on the floor surface and could cause suffocation.
NOTICE
When polyethylene foam is applied, a thickness of 10mm for liquid piping and 15 to 20mm for gas piping is
recommended. (Use a grade of insulation with heat resistance of 100ºC for gas piping.)
● Perform insulation work only when the surface temperature of the pipe material has cooled to room
temperature. Anything done immediately after brazing can cause the insulation to melt.
● During piping work, always cover over or plug the open end to keep the inside free of dust and moisture.
After installation, it is recommended that the customer retain this manual for future reference.
P5417030, 2017
NOTE
Hand over this installation manual to the next installation work personal.
2. Transportation
Transport the product as close to the installation location as practical before unpacking.
3. Before Installation
Confirm the number of the following parts by referring to the model printed on the package before unpacking.
Do NOT put any foreign material into the parts. Check to confirm that no foreign materials are inside the parts
before installation.
NOTICE:
If any of these parts are missing, please contact your distributor. Do not discard any foam packaging as it is
used as insulation for the joint kits after pressure testing is complete.
Model MW-NP142X3 MW-NP282X3 MW-NP452X3 MW-NP562X3 MW-NP692X3 MW-NP902X3
Name of Parts Qty. Qty. Qty. Qty. Qty. Qty.
Insulation for
Low Pressure
Gas Line 1 set 1 set 1 set 1 set 1 set 1 set
Insulation for
High/Low
Pressure
Gas Line 1 set 1 set 1 set 1 set 1 set 1 set
Insulation for
Liquid Line 1 set 1 set 1 set 1 set 1 set 1 set
Accessory
Tape
3 3 3 3 3 3
P5416979
4. Installation Work
4.1 Piping Connection Size
The ends of the multi-kits are finished as shown in the following figures. Cut the end of the pipe to correspond to
the pipe size.
Allow adequate space for elbow, angled, and irregular piping arrangements to compensate for expansion
and contraction brought on by temperature change.
MW-NP142X3 ID 12.7
ID 9.52
MW-NP282X3 ID 9.52
MW-NP562X3 ID 22.2
ID 15.88
(To Outdoor Unit) ID 19.05 ID 19.05
ID 12.7
ID 15.88 ID 6.35
ID 15.88 (To Outdoor Unit) ID 9.52
ID 12.7 (To Outdoor Unit)
(To Indoor Unit) ID 12.7
(To Indoor Unit) (To Indoor Unit)
MW-NP902X3
ID 22.2 ID 19.05
ID 15.88
(To Outdoor Unit) ID 19.05
(To Outdoor Unit) ID 22.2
ID 12.7
ID 6.35
ID 28.58 ID 15.88 ID 9.52
OD 6.35
MW-NP142X3
ID 9.52
(Qty. 2)
OD 6.35
MW-NP282X3
ID 9.52
Upward
Total Straight Section
Inclination
Min. 500mm within 30o
o
30
Horizontally
Downward A Inclination
(View from A)
INCORRECT
Upward
Downward
Example: Recommended From each Indoor Unit to Multi-Kit, use hard copper pipes that bend to prevent kinking.
[ Fixing for Liquid Piping, Low Pressure Gas Piping and High/Low Pressure Gas Piping ]
Low Pressure
Gas Piping Installing Part for Piping
High/Low Pressure
Gas Piping NOTICE:
Due to the properties of hard copper piping,
expansion and contraction take place during
seasons of heat and cold. Do not strap gas
Liquid Piping refrigerant and piping containing liquids together
as kinks.
(21)
(43)
f5 - 28 (50)
(70)
70 or less
(2) Use clean copper pipes without any moisture or foreign materials on inner surface of pipes. When
connecting refrigerant pipe, cut the copper pipes with a copper tube cutter as shown below. Also deburr
the cutting edge using deburring tool to ensure that no burr goes inside the pipe. Blow-out the pipes with
nitrogen or compressed air to ensure that no dust remains inside the pipe. Do NOT use a saw, a grindstone
or other tools which causes a large amount of powder residue when cutting.
Pipe
Deburring
Connection
Part
(3) When cutting the pipe, allow for an adequate depth for brazing as shown in the following table.
(mm)
Diameter Min. Insertion Depth
B
(A) (B)
Over 5, Below 8 6
Over 8, Below 12 7
Over 12, Below 16 8
A
Over 16, Below 25 10
Over 25, Below 35 12
Total Straight Section
Over 35, Below 45 14 Min. 500mm
When installing pipe through the Do NOT place the pipe directly In case of rain attach a cap or
wall, secure a cap at the end of on the ground. put a plastic bag over the pipe end.
the pipe.
INCORRECT CORRECT INCORRECT CORRECT INCORRECT
Hole
Attach a cap Rain water
or plastic bag can enter.
Attach a cap with rubber
Attach a cap or vinyl tape. band.
or vinyl tape.
CORRECT
(4) Make sure that all stop valves for the outdoor unit are closed completely.
(5) Blow-out the inside of the pipes with nitrogen gas before brazing. Bleed nitrogen gas through piping during
brazing. Pressure not to exceed 0.02MPa.
Make sure that a test for leakage of refrigerant gases has been performed. The refrigerant used for this
unit (HFC R410A), is a non-flammable, non-toxic, and odorless gas. However if refrigerant should leak
and make contact with sparks, and catch on fire, toxic gas will be generated. Fluorocarbon, which is
heavier than air, will form on the floor surface and could cause suffocation.
NOTICE
When polyethylene foam is applied, a thickness of 10mm for liquid piping and 15 to 20mm for gas piping is
recommended. (Use a grade of insulation with heat resistance of 100ºC for gas piping.)
Insulation Tape
(Field-Supplied)
After positioning all insulation with tape,
follow up and secure it permanently
with a second application of tape.
● Perform insulation work only when the surface temperature of the pipe material has cooled to room
temperature. Anything done immediately after brazing can cause insulation to melt.
● During piping work, always cover over or plug the open end to keep the inside free of dust and moisture.
After installation, it is recommended that the customer retain this manual for future reference.
P5416979, 2017
NOTE
Hand over this installation manual to the next installation work personal.
2. Transportation
Transport the product as close to the installation location as practical before unpacking.
3. Before Installation
Confirm the number of the following parts by referring to the model printed on the package before unpacking.
Do NOT put any foreign material into the parts. Check to confirm that no foreign materials are inside the parts
before installation.
NOTICE:
If any of these parts are missing, please contact your distributor. Do not discard any foam packaging as it is
used as insulation for the joint kits after pressure testing is complete.
Model MW-NP282A3 MW-NP452A3 MW-NP692A3 MW-NP902A3
Name of Parts Qty. Qty. Qty. Qty.
1 1 1 1
Insulation for
High/Low Pressure
Gas Line
1 set 1 set 1 set 1 set
Insulation for
Liquid Line
1 set 1 set 1 set 1 set
Accessory
Reducer for
High/Low Pressure Gas None 1 1 1
Line Connection
(For Connecting Pipe
(Field-Supplied))
None None None 1
Reducer for
Liquid Line Connection
(For Connecting Pipe
(Field-Supplied)) 2 1 1 1
Tape
2 2 2 2
P5416978
4. Installation Work
4.1 Piping Connection Size
The ends of the multi-kits are finished as shown in the following figures. Cut the end of the pipe to correspond to
the pipe size.
Allow adequate space for elbow, angled, and irregular piping arrangements to compensate for expansion
and contraction brought on by temperature change.
MW-NP282A3
ID 9.52
ID 19.05 OD 6.35
ID 6.35
ID 15.88
(To Outdoor Unit) (To Indoor Unit)
ID 12.7 (To Outdoor Unit)
(To Indoor Unit)
(Qty. 2)
MW-NP452A3 ID 12.7
ID 22.2
ID 22.2 ID 12.7
(To Outdoor Unit) ID 9.52
ID 19.05 OD 6.35
ID 6.35 ID 19.05
MW-NP692A3 ID 22.2
ID 15.88
(To Outdoor Unit) ID 19.05 ID 22.2 ID 12.7
OD 6.35
ID 12.7
ID 6.35 ID 19.05
ID 15.88 ID 9.52
MW-NP902A3
ID 9.52 ID 25.4
(To Outdoor Unit) OD 28.58 ID 15.88 OD 6.35
(To Outdoor Unit) ID 15.88
ID 28.58 ID 12.7
Upward
Total Straight Section
Inclination
Min. 500mm within 30o
o
30
Horizontally
Downward A Inclination
(View from A)
INCORRECT
Upward
Downward
Example: Recommended From each Indoor Unit to Multi-Kit, use hard copper pipes that bend to prevent kinking.
[ Fixing for Liquid Piping, Low Pressure Gas Piping and High/Low Pressure Gas Piping ]
High/Low Pressure
Gas Piping Installing Part for Piping
NOTICE:
Due to the properties of hard copper piping,
expansion and contraction take place during
seasons of heat and cold. Do not strap gas
Liquid Piping
refrigerant and piping containing liquids together
as kinks.
(21)
(43)
f5 - 28 (50)
(70)
70 or less
(2) Use clean copper pipes without any moisture or foreign materials on inner surface of pipes. When
connecting refrigerant pipe, cut the copper pipes with a copper tube cutter as shown below. Also deburr
the cutting edge using deburring tool to ensure that no burr goes inside the pipe. Blow-out the pipes with
nitrogen or compressed air to ensure that no dust remains inside the pipe. Do NOT use a saw, a grindstone
or other tools which causes a large amount of powder residue when cutting.
Pipe
Deburring
Connection
Part
(3) When cutting the pipe, allow for an adequate depth for brazing as shown in the following table.
(mm)
Diameter Min. Insertion Depth
(A) (B) B
Over 5, Below 8 6
Over 8, Below 12 7
Over 12, Below 16 8
A
When installing pipe through the Do NOT place the pipe directly In case of rain attach a cap or
wall, secure a cap at the end of on the ground. put a plastic bag over the pipe end.
the pipe.
INCORRECT CORRECT INCORRECT CORRECT INCORRECT
Hole
Attach a cap Rain water
or plastic bag can enter.
Attach a cap with rubber
Attach a cap or vinyl tape. band.
or vinyl tape.
CORRECT
(4) Make sure that all stop valves for the outdoor unit are closed completely.
(5) Blow-out the inside of the pipes with nitrogen gas before brazing. Bleed nitrogen gas through piping during
brazing. Pressure not to exceed 0.02MPa.
Make sure that a test for leakage of refrigerant gases has been performed. The refrigerant used for this
unit (HFC R410A), is a non-flammable, non-toxic, and odorless gas. However if refrigerant should leak
and make contact with sparks, and catch on fire, toxic gas will be generated. Fluorocarbon, which is
heavier than air, will form on the floor surface and could cause suffocation.
NOTICE
When polyethylene foam is applied, a thickness of 10mm for liquid piping and 15 to 20mm for gas piping is
recommended. (Use a grade of insulation with heat resistance of 100ºC for gas piping.)
Insulation Tape
(Field-Supplied)
After positioning all insulation with tape,
follow up and secure it permanently
with a second application of tape.
● Perform insulation work only when the surface temperature of the pipe material has cooled to room
temperature. Anything done immediately after brazing can cause the insulation to melt.
● During piping work, always cover over or plug the open end to keep the inside free of dust and moisture.
After installation, it is recommended that the customer retain this manual for future reference.
P5416978, 2017
NOTE
Hand over this installation manual to the next
installation work personnel. Do not put any material on the product.
Insulation for
Low Pressure Gas Line
1
Insulation for
High Pressure Gas Line
1
OD15.88 x ID19.05
Expander for
Low Pressure Gas Line 2
OD15.88 x ID12.7 OD12.7 x ID9.52
Expander for
High Pressure Gas Line 1 8
OD6.35 x ID9.52
Expander for Liquid Line
10
Tape
62
Unit: mm, ID: Inner Diameter, OD: Outer Diameter
NOTE : If any of these parts is not contained, please contact your distributor.
FAN-1593 201607
4. Installation Work
4.1 Piping Connection Size
The ends of the multi-kits are finished as shown in
the following figures. Cut the end of the pipe to meet Piping shall be supported with adequate space.
with the pipe size. Bent pipes and bypass piping (horizontal loop)
shall also be installed in order to absorb piping
elasticity caused by temperature changes.
ID19.05
ID15.88 ID22.2 φ22.2
ID15.88 φ15.88
ID12.7
ID19.05
ID15.88 ID22.2 φ22.2
ID15.88 φ15.88
ID12.7
φ19.05
ID9.52
φ9.52
Liquid Line
ID9.52 ID6.35 φ9.52
(For Closing)
(For Low Pressure Gas Line) (For High Pressure Gas Line) (For Liquid Line)
OD12.7 ID9.52
Closing Pipe
OD12.7 OD12.7 OD6.35
Deburring
(3) Make sure that all stop valves of the outdoor
Connection unit are closed completely.
Part
(4) Blow the inside of the pipes with nitrogen gas
when brazing.
(2) When cutting the pipe, secure the adequate
depth for brazing as shown in the following
table.
(mm)
Check for the refrigerant leakage carefully.
A: Outer Diameter B: Minimum Depth If large amount of refrigerant leakage occurs,
Over 5, Below 8 6 it will cause to breathe with difficulty or to
Over 8, Below 12 7 generate harmful gas due to the fire.
Over 12, Below 16 8
Over 16, Below 25 10 (5) The air tight test pressure of this product is
4.15MPa.
Over 25, Below 35 12
Over 35, Below 45 14
(6) Apply the insulation supplied with this multi-kits
to each branch (liquid side and gas side) with a
B tape. Also apply the field-supplied insulation to
the field-supplied pipes.
NOTE
A
b) Seal the joint part of insulation with a tape b) Cut the insulation for liquid pipe as many as
(accessory). required to attach for the joint part.
Tape Tape
(Accessory) (Accessory)
Insulation for
Header Multi-Kit
(Accessory)
c) Attach the insulation (accessory) onto the closing c) Seal the joint part of the closing pipe with a tape
pipe. Then seal the joint part with a tape (accessory). (accessory) after attaching the liquid pipe insulation.
Insulation for Gas
Line Closing Pipe
(Accessory) Tape
(Accessory)
Horizontally
Platform (Field-Supplied)
● Perform the insulation work when the pipe surface temperature decreases to the room temperature.
If insulation work is performed immediately after brazing, insulation may melt.
● If the ends of pipe are open to the atmosphere for a while after performing piping work, securely put
caps or plastic bags over the pipe ends for avoiding moisture or dust.
Johnson Controls reserve the right change product features without notice. P5416738
NOTE
Hand over this installation manual to the next
installation work personnal. Do not put any material on the product.
Branch Pipe
for Gas Line
1 1
Branch Pipe
for Liquid Line
1 1
Insulation
for Gas Line
1 1
Insulation
for Liquid Line
1 1
For Gas Line For Liquid Line For Liquid Header For Gas Line For Liquid Line For Liquid Header
Closing φ12.7 φ6.35 φ9.52 φ12.7 φ6.35 φ9.52
Pipe
2 2 1 6 6 1
Accessories
Expander
for Gas Line
None 2
Expander
for Liquid Line
4 8
Insulation for
Closing Pipe
2 sets 6 sets
Insulation for
Liquid Line
4 sets 8 sets
Tape
24 48
NOTE : If any of these parts is not contained, please contact your distributor.
FAN-1591 201607
4. Installation Work
4.1 Piping Connection Size
The ends of the multi-kits are finished as shown in
the following figures. Cut the end of the pipe to meet
Piping shall be supported with adequate space.
with the pipe size.
Bent pipes and bypass piping (horizontal loop)
shall also be installed in order to absorb piping
elasticity caused by temperature changes.
φ19.05
ID15.88
OD12.7
ID19.05 φ19.05 φ9.52
φ9.52
ID9.52
Q'ty: 2
JMH-NP224A
ID6.35 (For Liquid Line) (For Liquid Line)
ID9.52
φ15.88 ID9.52
ID15.88
ID12.7
OD6.35 OD6.35
φ9.52
(For Closing)
Q'ty: 4 Q'ty: 2
(For Gas Line) (For Gas Line)
ID19.05
ID15.88 φ19.05
ID19.05
OD12.7
ID22.2 φ22.2 OD15.88
φ9.52
ID9.52
Q'ty: 2 Q'ty: 6
JMH-NP288A
ID9.52 (For Liquid Line) (For Liquid Line)
φ15.88
ID6.35
ID15.88 ID9.52
ID12.7
OD6.35 OD6.35
φ9.52
(For Closing)
Q'ty: 8 Q'ty: 6
Pipe Cutter
CORRECT INCORRECT
Pipe Attach a cap Rain water
or vinyl tape can enter.
with rubber
band.
Deburring
Connection
Part
(3) Make sure that all stop valves of the outdoor unit
are closed completely.
(4) Blow the inside of the pipes with nitrogen gas
(2) When cutting the pipe, secure the adequate when brazing.
depth for brazing as shown in the following table.
(mm)
A: Outer Diameter B: Minimum Depth Check for the refrigerant leakage carefully. If
Over 5, Below 8 6 large amount of refrigerant leakage occurs, it will
Over 8, Below 12 7 cause to breathe with difficulty or to generate
Over 12, Below 16 8 harmful gas due to the fire.
Over 16, Below 25 10
Over 25, Below 35 12 (5) The air tight test pressure of this product is
Over 35, Below 45 14
4.15MPa.
(6) Apply the insulation supplied with this multi-kits
to each branch (liquid side and gas side) with a
B
tape. Also apply the field-supplied insulation to
the field-supplied pipes.
NOTE
A
b) Seal the joint part of insulation with a tape b) Cut the insulation for liquid pipe as many as
(accessory). required to attach for the joint part.
Tape Tape
(Accessory) (Accessory)
Insulation for
Header Multi-Kit
(Accessory)
c) Attach the insulation (accessory) onto the closing c) Seal the joint part of the closing pipe with a tape
pipe. Then seal the joint part with a tape (accessory). (accessory) after attaching the liquid pipe insulation.
Insulation for Gas
Line Closing Pipe
(Accessory) Tape
(Accessory)
Horizontally
Platform (Field-Supplied)
● Perform the insulation work when the pipe surface temperature decreases to the room temperature.
If insulation work is performed immediately after brazing, insulation may melt.
● If the ends of pipe are open to the atmosphere for a while after performing piping work, securely put
caps or plastic bags over the pipe ends for avoiding moisture or dust.
Installation
HITACHI Manual
Installation for Drain
Manual Boss
for Multi-Kits
Drain Model:
Boss Model: DBS-TP10A
DBS-TP10A
NOTE
This drain boss is for the drain pipe connection in order to use outdoor unit bottom base as a drain pan.
2. Before Installation
Confirm the number of the following parts by referring to the model printed on the package before unpacking.
Drain Boss 43
1 2 Connecting for Drain Piping
(VP20 Equivalent) Outer Diameter φ 25
(Inner Diameter φ 20)
3. Installation Work
Place the outdoor unit on the flat foundation or block and fix it at least 100mm higher than the ground.
For smooth drainage, install the outdoor unit with slightly inclined on the drainage side (rear side).
(1) Put the 2 rubber cap in the 1 drain boss (to the upper part of Drain Boss
the drain boss projection) in the arrow direction. 2 Rubber Cap (1,2)
(2) Put the drain boss in the hole for the drain boss of the outdoor
unit bottom base until it is securely fixed. (approx. 40o)
(The drain boss in the shape of taper can be fit into the bottom base and stopped by itself.)
3.2 Installation of Drain Cap
The drain cap is a component to cover a hole.
(The hole for drain boss of the outdoor unit is not included.) Projection Hole for Drain Boss
(1) Put the 2 rubber cap in the 3 drain cap (to the upper part of 3 Drain Cap
the drain boss projection) in the arrow direction. 2 Rubber Cap Drain Cap
(2,3)
(2) Put the drain cap in the hole for the drain boss of the outdoor
o
unit bottom base until it is securely fixed. (approx. 40 )
(The drain cap in the shape of taper can be fit into the bottom base and stopped by itself.)
Use a rubber cap when fixing the drain boss and drain cap. (No rubber cap may lead to water leakage.)
After fixing, ensure that there is no water leakage from the drain cap after pouring water into the bottom
base and then draining it from the drain boss.
P5414717
52
(Front Side)
125
(73) Bottom Base
Model: 8HP
Bottom Base
(73)
2 3 Drain Cap
1 2 Drain Boss Position (2 Places)
Drain Pipe
(Outdoor Unit Rear Side) 1 2 Drain Boss
(Field-Supplied)
Securely fix the drain boss, rubber cap and drain cap at the bottom base without being loosened when
connecting the drain pipe.
Do not use drain boss kit in an area where drain water may be frozen.
(The drain water in the drain pipe may be frozen and then the drain pipe may crack.)
(1) In a snow area, water from the heat exchanger may be frozen on the surface of the bottom base. This may
lead to poor drainage. Therefore, do not use the drain boss kit in this area.
(2) In the drainage method according to this manual, some of the defrost drain water dripped from the inlet
protection grille may be flowed out over the bottom base of the product.
To prevent this, provide a drain pan larger than the bottom surface of the product. Fix the drain pan and the
discharge pipe between the bottom part of the product and the foundation prior to discharge.
P5414717
This air inlet grille is to caution not to touch the outdoor unit heat exchanger reaching from air inlet. It is not
designed to prevent people reaching to the heat exchanger. Install it as instructed in this manual.
IMPORTANT NOTICE:
● Read and understand this manual before using this air inlet grille.
● Perform the test run after installation to check for abnormalities.
● Forward this information to the building owner and request that they maintain all the equipment manuals.
● Signal words are used to identify levels of hazard seriousness.
Definitions for identifying hazard levels are provided below with their respective signal words.
1. Applicable Unit
NOTICE:
The applicable outdoor unit may be different depending on the product series. Be sure to confirm with the
product catalog before installation.
2. Installation Work
(1) Be sure to securely tighten the air inlet grille with the supplied screws (accessories).
If the screws are not securely tightened, it may cause vibration or abnormal sound.
If they are over-tightened, the screw threads may be stripped. When tightening the screws, make sure
to follow the tightening torque below.
● Tightening Torque: 2.0+0.5 N●m
(2) Secure enough service space with consideration for attaching/detaching the air inlet grille.
● Service Space with Air Inlet Grille: Service Space for Outdoor Unit + Min. 150mm
(3) The air inlet grille may accumulate ice or snow during cold weather.
(4) Apply touch-up coating to the screw fixing part on the outdoor unit to prevent rust formation (local
supply).
3. Before Installation
Check that all the following accessories are packed with the unit before installation.
Unit: mm
Qty.
No. Accessory Remarks
PSN-TP20BA PSN-TP20BB
852 1 -
Air Inlet Grille
1 (for Rear Side a
Installation) 1227
a
1112 - 1
( ) indicate
2
M5 x 12L 11 11
Screw the number of
(with Washer) (1) (1)
spare part
3
Self-Tapping M4 x 13L
2 2 for drilling
Screw (without Washer)
4. Installation Procedures
Before installation, confirm the outdoor unit model. If the air inlet grille is available for your model, follow the
installation procedures.
(1) Open holes on rear side the outdoor unit ( P x 2) using the self-tapping screw 3 .
Unit: mm
a 287 Outdoor Unit
a
(Representative Model)
RAS-8 - 12FSNS, RAS-5, 6FSNP
P RAS-8 - 12FSXNS, RAS-5, 6FSXNP
330
JTOH080 - 120VPE(U,F,R)BS1
119
JTOR080 - 120VPE(U,F,R)BS1
RAS-14 - 18FSNS, RAS-8 - 14FSNP
RAS-14 - 18FSXNS, RAS-8 - 14FSXNP
460
JTOH140 - 180VPE(U,F,R)BS1
JTOR140 - 180VPE(U,F,R)BS1
(2) Hook the “A” part (edges of air inlet grille) between the heat exchanger and bottom base of unit. Mount
the air inlet grille using the screws ( 2 x 10).
1
Heat Exchanger
2
Air Inlet Grille
Bottom Base
Outdoor Unit
A
PSN-TP20BA: two places
PSN-TP20BB: three places
5. Installation Appearance
PSN-TP20BA Unit: mm
Screws
(Accessory)
Air Inlet Grille
[for Left Side
Installation]
Air Inlet Grille (Other Air Inlet
1675
[for Side Grille Option)
Installation]
(Other Air Inlet Air Inlet Grille
Grille Option) [for Rear Side
Installation]
Outdoor Unit
950 765
< Right Side > < Rear Side > < Left Side >
PSN-TP20BB
Screws
(Accessory)
Air Inlet Grille
[for Left Side
Installation]
Air Inlet Grille 1675 (Other Air Inlet
[for Side Grille Option)
Installation]
(Other Air Inlet Air Inlet Grille
Grille Option) [for Rear Side
Installation]
Outdoor Unit
1210 765
< Right Side > < Rear Side > < Left Side >
Available Combinations
Model
Heat RAS-8 - 12FSNS, RAS-5, 6FSNP RAS-14 - 18FSNS, RAS-8 - 14FSNP
Applicable Outdoor Unit
Pump JTOH080 - 120VPE(U,F,R)BS1 JTOH140 - 180VPE(U,F,R)BS1
(Representative Model)
Heat RAS-8 - 12FSXNS, RAS-5, 6FSXNP RAS-14 - 18FSXNS, RAS-8 - 14FSXNP
Recovery JTOR080 - 120VPE(U,F,R)BS1 JTOR140 - 180VPE(U,F,R)BS1
NOTICE:
● This manual applies only to the combination indicated with .
For other air inlet grille options, refer to each model’s installation manual.
● Install the required air inlet grille only if all installation requirements can be met.
P5416988-rev.1, 2017
This air inlet grille is to caution not to touch the outdoor unit heat exchanger reaching from air inlet. It is not
designed to prevent people reaching to the heat exchanger. Install it as instructed in this manual.
IMPORTANT NOTICE:
● Read and understand this manual before using this air inlet grille.
● Perform the test run after installation to check for abnormalities.
● Forward this information to the building owner and request that they maintain all the equipment manuals.
● Signal words are used to identify levels of hazard seriousness.
Definitions for identifying hazard levels are provided below with their respective signal words.
1. Applicable Unit
NOTICE:
The applicable outdoor unit may be different depending on the product series. Be sure to confirm with the
product catalog before installation.
2. Installation Work
(1) Be sure to securely tighten the air inlet grille with the supplied screws (accessories).
If the screws are not securely tightened, it may cause vibration or abnormal sound.
If they are over-tightened, the screw threads may be stripped. When tightening the screws, make sure
to follow the tightening torque below.
● Tightening Torque: 2.0+0.5 N●m
(2) Secure enough service space with consideration for attaching/detaching the air inlet grille.
● Service Space with Air Inlet Grille: Service Space for Outdoor Unit + Min. 150mm
(3) The air inlet grille may accumulate ice or snow during cold weather.
(4) Apply touch-up coating to the screw fixing part on the outdoor unit to prevent rust formation (local
supply).
3. Before Installation
Check that all the following accessories are packed with the unit before installation.
Unit: mm
Qty.
No. Accessory Remarks
PSN-TP20BC
701
2 Stay 1
( ) indicate the
3
M5 x 12L 25
Screw number of spare
(with Washer) (1)
part
4
Self-Tapping M4 x 13L
3 for drilling
Screw (without Washer)
4. Installation Procedures
Before installation, confirm the outdoor unit model. If the air inlet grille is available for your model, follow the
installation procedures.
(1) Open holes on rear side the outdoor unit ( P x 6) using the self-tapping screw 4 .
Unit: mm
(2) Attach the Stay ( 2 ) to the outdoor unit by fixing the screws ( 3 x 4) to the middle holes (x 2) on the
top of the outdoor unit from step (1) and to the existing holes (x 2) on the bottom of the outdoor unit.
Outdoor Unit
3
(3) Hook the “A” part (edges of air inlet grille) between the heat exchanger and bottom base of unit. Mount
the air inlet grille using the screws ( 3 x 20).
Heat Exchanger
Bottom Base
A
(each two places)
5. Installation Appearance
Unit: mm
Center Stay
Screws
(Accessory)
< Right Side > < Rear Side > < Left Side >
Available Combinations
Model
Heat RAS-20 - 24FSNS, RAS-16, 18FSNP
Applicable Outdoor Unit
Pump JTOH200 - 240VPE(U,F,R)BS1
(Representative Model)
Heat RAS-20 - 24FSXNS, RAS-16, 18FSXNP
Recovery JTOR200 - 240VPE(U,F,R)BS1
NOTICE:
● This manual applies only to the combination indicated with .
For other air inlet grille options, refer to each model’s installation manual.
● Install the required air inlet grille only if all installation requirements can be met.
P5416991-rev.1, 2017
This air inlet grille is to caution not to touch the outdoor unit heat exchanger reaching from air inlet. It is not
designed to prevent people reaching to the heat exchanger. Install it as instructed in this manual.
IMPORTANT NOTICE:
● Read and understand this manual before using this air inlet grille.
● Perform the test run after installation to check for abnormalities.
● Forward this information to the building owner and request that they maintain all the equipment manuals.
● Signal words are used to identify levels of hazard seriousness.
Definitions for identifying hazard levels are provided below with their respective signal words.
1. Applicable Unit
NOTICE:
The applicable outdoor unit may be different depending on the product series. Be sure to confirm with the
product catalog before installation.
2. Installation Work
(1) Be sure to securely tighten the air inlet grille with the supplied screws (accessories).
If the screws are not securely tightened, it may cause vibration or abnormal sound.
If they are over-tightened, the screw threads may be stripped. When tightening the screws, make sure
to follow the tightening torque below.
● Tightening Torque: 2.0+0.5 N●m
(2) Secure enough service space with consideration for attaching/detaching the air inlet grille.
● Service Space with Air Inlet Grille: Service Space for Outdoor Unit + Min. 150mm
(3) The air inlet grille may accumulate ice or snow during cold weather.
(4) Apply touch-up coating to the screw fixing part on the outdoor unit to prevent rust formation (local
supply).
3. Before Installation
Check that all the following accessories are packed with the unit before installation.
Unit: mm
Qty.
No. Accessory Remarks
PSN-TP20L
503
( ) indicate
2
M5 x 12L 7
Screw the number of
(with Washer) (1)
spare part
4. Installation Procedures
Before installation, confirm the outdoor unit model. If the air inlet grille is available for your model, follow the
installation procedures.
Remove three screws fixing the side cover to the the outdoor unit.
Hook the “A” part (edges of air inlet grille) between the heat exchanger and bottom base of unit. Mount the
air inlet grille using the screws ( 2 x 6).
Side Cover
Heat Exchanger
A
(two places) Air Inlet Grille
2 Screws (Accessory, x3)
Replace with the fixing
scres to the side cover.
Bottom Base
5. Installation Appearance
The following examples illustrate a small cabinet.
Unit: mm
1675
Air Inlet Grille [for Left Side
[for Side Installation]
Installation]
(Other Air Inlet
Grille Option)
< Right Side > < Rear Side > < Left Side >
Available Combinations
Model
RAS-8 - 12FSNS RAS-14 - 18FSNS RAS-20 - 24FSNS
Applicable Heat
RAS-5, 6FSNP RAS-8 - 14FSNP RAS-16, 18FSNP
Outdoor Unit Pump
JTOH080 - 120VPE(U,F,R)BS1 JTOH140 - 180VPE(U,F,R)BS1 JTOH200- 240VPE(U,F,R)BS1
(Representative
Model) RAS-8 - 12FSXNS RAS-14 - 18FSXNS RAS-20 - 24FSXNS
Heat
RAS-5, 6FSXNP RAS-8 - 14FSXNP RAS-16, 18FSXNP
Recovery
JTOR080 - 120VPE(U,F,R)BS1 JTOR140 - 180VPE(U,F,R)BS1 JTOR200 - 240VPE(U,F,R)BS1
Air Inlet Grille for
PSN-TP20BA PSN-TP20BB PSN-TP20BC
Rear Side
Air Inlet Grille for
PSN-TP20L PSN-TP20R
Left Side
Air Inlet Grille for
PSN-TP20R
Right Side
NOTICE:
● This manual applies only to the combination indicated with .
For other air inlet grille options, refer to each model’s installation manual.
● Install the required air inlet grille only if all installation requirements can be met.
P5416990-rev.1, 2017
This air inlet grille is to caution not to touch the outdoor unit heat exchanger reaching from air inlet. It is not
designed to prevent people reaching to the heat exchanger. Install it as instructed in this manual.
IMPORTANT NOTICE:
● Read and understand this manual before using this air inlet grille.
● Perform the test run after installation to check for abnormalities.
● Forward this information to the building owner and request that they maintain all the equipment manuals.
● Signal words are used to identify levels of hazard seriousness.
Definitions for identifying hazard levels are provided below with their respective signal words.
1. Applicable Unit
NOTICE:
The applicable outdoor unit may be different depending on the product series. Be sure to confirm with the
product catalog before installation.
2. Installation Work
(1) Be sure to securely tighten the air inlet grille with the supplied screws (accessories).
If the screws are not securely tightened, it may cause vibration or abnormal sound.
If they are over-tightened, the screw threads may be stripped. When tightening the screws, make sure
to follow the tightening torque below.
● Tightening Torque: 2.0+0.5 N●m
(2) Secure enough service space with consideration for attaching/detaching the air inlet grille.
● Service Space with Air Inlet Grille: Service Space for Outdoor Unit + Min. 150mm
(3) The air inlet grille may accumulate ice or snow during cold weather.
(4) Apply touch-up coating to the screw fixing part on the outdoor unit to prevent rust formation (local
supply).
3. Before Installation
Check that all the following accessories are packed with the unit before installation.
Unit: mm
Qty.
No. Accessory Remarks
PSN-TP20L
613
( ) indicate
2
M5 x 12L 7
Screw the number of
(with Washer) (1)
spare part
4. Installation Procedures
Before installation, confirm the outdoor unit model. If the air inlet grille is available for your model, follow the
installation procedures.
Remove three screws fixing the side cover to the outdoor unit.
Hook the “A” part (edges of air inlet grille) between the heat exchanger and bottom base of unit. Mount the
air inlet grille using the screws ( 2 x 6).
1
Side Cover
Screws (Accessory, x3) 2
Bottom Base
5. Installation Appearance
The following examples illustrate a small cabinet.
Unit: mm
1675
Air Inlet Grille [for Left Side
[for Side Installation]
Installation] (Other Air Inlet
Grille Option)
< Right Side > < Rear Side > < Left Side >
Available Combinations
Model
RAS-8 - 12FSNS RAS-14 - 18FSNS RAS-20 - 24FSNS
Applicable Heat
RAS-5, 6FSNP RAS-8 - 14FSNP RAS-16, 18FSNP
Outdoor Unit Pump
JTOH080 - 120VPE(U,F,R)BS1 JTOH140 - 180VPE(U,F,R)BS1 JTOH200- 240VPE(U,F,R)BS1
(Representative
Model) RAS-8 - 12FSXNS RAS-14 - 18FSXNS RAS-20 - 24FSXNS
Heat
RAS-5, 6FSXNP RAS-8 - 14FSXNP RAS-16, 18FSXNP
Recovery
JTOR080 - 120VPE(U,F,R)BS1 JTOR140 - 180VPE(U,F,R)BS1 JTOR200 - 240VPE(U,F,R)BS1
Air Inlet Grille for
PSN-TP20BA PSN-TP20BB PSN-TP20BC
Rear Side
Air Inlet Grille for
PSN-TP20L PSN-TP20R
Left Side
Air Inlet Grille for
PSN-TP20R
Right Side
NOTICE:
● This manual applies only to the combination indicated with .
For other air inlet grille options, refer to each model’s installation manual.
● Install the required air inlet grille only if all installation requirements can be met.
P5416989-rev.1, 2017
This protection net is to protect the outdoor unit heat exchanger from external damages such as being hit
by a ball. Install it as instructed in this manual.
IMPORTANT NOTICE:
● Read and understand this manual before using this protection net.
● Perform the test run after installation to check for abnormalities.
● Forward this information to the building owner and request that they maintain all the equipment manuals.
● Signal words are used to identify levels of hazard seriousness.
Definitions for identifying hazard levels are provided below with their respective signal words.
1. Applicable Unit
NOTICE:
The applicable outdoor unit may be different depending on the product series. Be sure to confirm with the
product catalog before installation.
2. Installation Work
(1) Be sure to securely tighten the protection net with the supplied screws (accessories).
If the screws are not securely tightened, it may cause vibration or abnormal sound.
If they are over-tightened, the screw threads may be stripped. When tightening the screws, make sure
to follow the tightening torque below.
● Tightening Torque: 2.0+0.5 N●m
(2) Secure enough service space with consideration for attaching/detaching the protection net.
● Service Space with Protection Net: Service Space for Outdoor Unit + Min. 150mm
(3) Do not step on the protection net or the outdoor unit to prevent falls and injury.
(4) Fallen leaves or other debris may be caught by the protection net and cause airflow restrictions. Be
sure to check for accumulation and clean the protection net periodically.
(5) The protection net may accumulate ice or snow during cold weather.
(6) Apply touch-up coating to the screw fixing part on the outdoor unit to prevent rust formation (local
supply).
NOTICE:
Do not use the snow protection hood for the rear side inlet if the protection net is installed.
3. Before Installation
Check that all the following accessories are packed with the unit before installation.
Unit: mm
Qty.
No. Accessory Remarks
PN-TP20BA PN-TP20BB
852 1 -
Protection Net
1 (for Rear Side a
1415
Installation)
1112 - 1
a
( ) indicate
2
M5 x 12L 11 11
Screw the number of
(with Washer) (1) (1)
spare part
3
Self-Tapping M4 x 13L
2 2 for drilling
Screw (without Washer)
4. Installation Procedures
Before installation, confirm the outdoor unit model. If the protection net is available for your model, follow
the installation procedures.
(1) Drill holes on rear side the outdoor unit ( P x 2) using the self-tapping screws ( 3 ).
Unit: mm
a 287 Outdoor Unit
a
(Representative Model)
P RAS-8 - 12FSNS, RAS-5, 6FSNP
RAS-8 - 12FSXNS, RAS-5, 6FSXNP
330
JTOH080 - 120VPE(U,F,R)BS1
119
JTOR080 - 120VPE(U,F,R)BS1
RAS-14 - 18FSNS, RAS-8 - 14FSNP
RAS-14 - 18FSXNS, RAS-8 - 14FSXNP
460
JTOH140 - 180VPE(U,F,R)BS1
JTOR140 - 180VPE(U,F,R)BS1
(2) Hook the “A” part (edges of protection net) between the heat exchanger and bottom base of unit.
Mount the protection net using the screws ( 2 x 10).
2 Heat Exchanger
Protection Net
5. Installation Appearance
Unit: mm
PN-TP20BA
Screws
Protection Net
[for Left Side
Installation]
Protection Net (Other Protection
1675
[for Side Net Option)
Installation]
(Other Protection Protection Net
Net Option) [for Rear Side
Installation]
Outdoor Unit
100 950 100 100 765
< Right Side > < Rear Side > < Left Side >
PN-TP20BB
Screws
Protection Net
[for Side
Installation]
Protection Net 1675 (Other Protection
[for Side Net Option)
Installation]
(Other Protection Protection Net
Net Option) [for Rear Side
Installation]
Outdoor Unit
100 1210 100 100 765
< Right Side > < Rear Side > < Left Side >
Available Combinations
Model
Heat RAS-8 - 12FSNS, RAS-5, 6FSNP RAS-14 - 18FSNS, RAS-8 - 14FSNP
Applicable Outdoor Unit
Pump JTOH080 - 120VPE(U,F,R)BS1 JTOH140 - 180VPE(U,F,R)BS1
(Representative Model)
Heat RAS-8 - 12FSXNS, RAS-5, 6FSXNP RAS-14 - 18FSXNS, RAS-8 - 14FSXNP
Recovery JTOR080 - 120VPE(U,F,R)BS1 JTOR140 - 180VPE(U,F,R)BS1
NOTICE:
● This manual applies only to the combination indicated with .
For other protection net options, refer to each model’s installation manual.
● Install the required protection net only if all installation requirements can be met.
P5416992-rev.1, 2017
This protection net is to protect the outdoor unit heat exchanger from external damages such as being hit
by a ball. Install it as instructed in this manual.
IMPORTANT NOTICE:
● Read and understand this manual before using this protection net.
● Perform the test run after installation to check for abnormalities.
● Forward this information to the building owner and request that they maintain all the equipment manuals.
● Signal words are used to identify levels of hazard seriousness.
Definitions for identifying hazard levels are provided below with their respective signal words.
1. Applicable Unit
NOTICE:
The applicable outdoor unit may be different depending on the product series. Be sure to confirm with the
product catalog before installation.
2. Installation Work
(1) Be sure to securely tighten the protection net with the supplied screws (accessories).
If the screws are not securely tightened, it may cause vibration or abnormal sound.
If they are over-tightened, the screw threads may be stripped. When tightening the screws, make sure
to follow the tightening torque below.
● Tightening Torque: 2.0+0.5 N●m
(2) Secure enough service space with consideration for attaching/detaching the protection net.
● Service Space with Protection Net: Service Space for Outdoor Unit + Min. 150mm
(3) Do not step on the protection net or the outdoor unit to prevent falls and injury.
(4) Fallen leaves or other debris may be caught by the protection net and cause airflow restrictions. Be
sure to check for accumulation and clean the protection net periodically.
(5) The protection net may accumulate ice or snow during cold weather.
(6) Apply touch-up coating to the screw fixing part on the outdoor unit to prevent rust formation (local
supply).
NOTICE:
Do not use the snow protection hood for the rear side inlet if the protection net is installed.
3. Before Installation
Check that all the following accessories are packed with the unit before installation.
Unit: mm
Qty.
No. Accessory Remarks
PN-TP20BC
Protection Net
1 (for Rear Side 2
1415
Installation)
702
2 Stay 1
( ) indicate
3
M5 x 12L 25
Screw the number of
(with Washer) (1)
spare part
4
Self-Tapping M4 x 13L
3 for drilling
Screw (without Washer)
4. Installation Procedures
Before installation, confirm the outdoor unit model. If the protection net is available for your model, follow
the installation procedures.
(1) Drill holes on rear side the outdoor unit ( P x 6) with Self-Tapping Screw ( 4 ) by using a charging
driver or etc..
Unit: mm
(2) Attach the stay ( 2 ) to the outdoor unit by fixing the screws ( 3 x 4) to the middle holes (x 2) on the top
of the outdoor unit from step (1) and to the existing holes (x 2) on the bottom of the outdoor unit.
Outdoor Unit
3
(3) Hook the “A” part (edges of protection net) between the heat exchanger and bottom base of unit.
Mount the air protection net using the screws ( 3 x 20).
Heat Exchanger
Protection Net
A Bottom Base
(each two places)
5. Installation Appearance
Unit: mm
Screws
Protection Net
Protection Net [for Side
[for Side Installation]
Installation]
1675
(Other Protection
(Other Protection Net Option)
Net Option)
Protection Net
[for Rear Side
Outdoor Unit Installation]
100 1600 100 100 765
< Right Side > < Rear Side > < Left Side >
Available Combinations
Model
Heat RAS-20 - 24FSNS, RAS-16, 18FSNP
Applicable Outdoor Unit
Pump JTOH200 - 240VPE(U,F,R)BS1
(Representative Model)
Heat RAS-20 - 24FSXNS, RAS-16, 18FSXNP
Recovery JTOR200 - 240VPE(U,F,R)BS1
NOTICE:
● This manual applies only to the combination indicated with .
For other protection net options, refer to each model’s installation manual.
● Install the required protection net only if all installation requirements can be met.
P5416993-rev.1, 2017
This protection net is to protect the outdoor unit heat exchanger from external damages such as being hit
by a ball. Install it following the directions below.
IMPORTANT NOTICE:
● Read and understand this manual before using this protection net.
● Perform the test run after installation to check for abnormalities.
● Forward this information to the building owner and request that they maintain all the equipment manuals.
● Signal words are used to identify levels of hazard seriousness.
Definitions for identifying hazard levels are provided below with their respective signal words.
1. Applicable Unit
NOTICE:
The applicable outdoor unit may be different depending on the product series. Be sure to confirm with the
product catalog before installation.
2. Installation Work
(1) Be sure to securely tighten the protection net with the supplied screws (accessories).
If the screws are not securely tightened, it may cause vibration or abnormal sound.
If they are over-tightened, the screw threads may be stripped. When tightening the screws, make sure
to follow the tightening torque below.
● Tightening Torque: 2.0+0.5 N●m
(2) Secure enough service space with consideration for attaching/detaching the protection net.
● Service Space with Protection Net: Service Space for Outdoor Unit + Min. 150mm
(3) Do not step on the protection net or the outdoor unit to prevent falls and injury.
(4) Fallen leaves or other debris may be caught by the protection net and cause airflow restrictions. Be
sure to check for accumulation and clean the protection net periodically.
(5) The protection net may accumulate ice or snow during cold weather.
(6) Apply touch-up coating to the screw fixing part on the outdoor unit to prevent rust formation (local
supply).
NOTICE:
Do not use the snow protection hood for the rear side inlet if the protection net is installed.
3. Before Installation
Check that all the following accessories are packed with the unit before installation.
Unit: mm
Qty.
No. Accessory Remarks
PN-TP20L
Protection Net
1 (for Left Side 1
1183
Installation)
503
( ) indicate
2
M5 x 12L 7
Screw the number of
(with Washer) (1)
spare part
4. Installation Procedures
Before installation, confirm the outdoor unit model. If the protection net is available for your model, follow
the installation procedures.
Remove the three screws fixing the side cover to the the outdoor unit.
Insert the two screws 2 at the top of the outdoor unit left side but do not tighten. Hook the protection net (for
left side installation) 1 over the two screws. Securely tighten the other four screws 2 . Finally, tighten the
top two screws completely.
Outdoor Unit
Protection Net
(for Left Side Installation)
Side Cover
1
Scres (Accessory, x3) 2
Replace with the fixing
screws to the side cover.
5. Installation Appearance
The following examples illustrate a small cabinet.
Unit: mm
Securing
Screw
(Accessory)
1675
(Other Protection
Net Option) Protection Net
[for Rear Side
Installation]
(Other Protection
Outdoor Unit Net Option)
100 100 100 765
Available Combinations
Model
RAS-8 - 12FSNS RAS-14 - 18FSNS RAS-20 - 24FSNS
Applicable Heat
RAS-5, 6FSNP RAS-8 - 14FSNP RAS-16, 18FSNP
Outdoor Unit Pump
JTOH080 - 120VPE(U,F,R)BS1 JTOH140 - 180VPE(U,F,R)BS1 JTOH200- 240VPE(U,F,R)BS1
(Representative
Model) RAS-8 - 12FSXNS RAS-14 - 18FSXNS RAS-20 - 24FSXNS
Heat
RAS-5, 6FSXNP RAS-8 - 14FSXNP RAS-16, 18FSXNP
Recovery
JTOR080 - 120VPE(U,F,R)BS1 JTOR140 - 180VPE(U,F,R)BS1 JTOR200 - 240VPE(U,F,R)BS1
Protection Net for
PN-TP20BA PN-TP20BB PN-TP20BC
Rear Side
Protection Net for
PN-TP20L PN-TP20R
Left Side
Protection Net for
PN-TP20R
Right Side
NOTICE:
● This manual applies only to the combination indicated with .
For other protection net options, refer to each model’s installation manual.
● Install the required protection net only if all installation requirements can be met.
P5416995-rev.1, 2017
This protection net is to protect the outdoor unit heat exchanger from external damages such as being hit
by a ball. Install it following the instructions below.
IMPORTANT NOTICE:
● Read and understand this manual before using this protection net.
● Perform the test run after installation to check for abnormalities.
● Forward this information to the building owner and request that they maintain all the equipment manuals.
● Signal words are used to identify levels of hazard seriousness.
Definitions for identifying hazard levels are provided below with their respective signal words.
1. Applicable Unit
NOTICE:
The applicable outdoor unit may be different depending on the product series. Be sure to confirm with the
product catalog before installation.
2. Installation Work
(1) Be sure to securely tighten the protection net with the supplied screws (accessories).
If the screws are not securely tightened, it may cause vibration or abnormal sound.
If they are over-tightened, the screw threads may be stripped. When tightening the screws, make sure
to follow the tightening torque below.
● Tightening Torque: 2.0+0.5 N●m
(2) Secure enough service space with consideration for attaching/detaching the protection net.
● Service Space with Protection Net: Service Space for Outdoor Unit + Min. 150mm
(3) Do not step on the protection net or the outdoor unit to prevent falls and injury.
(4) Fallen leaves or other debris may be caught by the protection net and cause airflow restrictions. Be
sure to check for accumulation and clean the protection net periodically.
(5) The protection net may accumulate ice or snow during cold weather.
NOTICE:
Do not use the snow protection hood for the side inlet if the protection net is installed.
3. Before Installation
Check that all the following accessories are packed with the unit before installation.
Unit: mm
Qty.
No. Accessory Remarks
PN-TP20R
1183
Protection Net
1 (for Side 1
Installation)
614
( ) indicate
2
M5 x 12L 9
Screw the number of
(with Washer) (2)
spare part
for drilling,
3
Self-Tapping M4 x 13L 2 ( ) indicate
Screw (without Washer) (1) the number of
spare part
4. Installation Procedures
Before installation, confirm the outdoor unit model. If the protection net is available for your model, follow
the installation procedures.
(1) Open holes at the location shown below using the self-tapping screw 3 . Remove three screws fixing
the side cover to the outdoor unit.
Unit: mm
Open a hole
( RAS-14
RAS-14 - 24FSXNS, RAS-8 - 18FSXNP and JTOR140 - 240VPE(U,F,R)BS1)
- 24FSNS, RAS-8 - 18FSNP and JTOH140 - 240VPE(U,F,R)BS1
191 191
< Front Side > < Rear Side > < Rear Side > < Front Side >
Open a hole
Remove the screws (x3) Remove the screws (x3)
fixing the side cover. fixing the side cover.
1311
1311
Side Cover
Side Cover
(2) Insert the screws 2 to the opened holes in step (1) but do not tighten. Loosen but do not remove one
screw attached at the top of the outdoor unit right side. Hook the protection net (for side installation) 1
over the top. Securely tighten the six screws 2 . Finally, tighten the top two screws completely.
NOTE:
Same procedure is applied when the protection net is used for left side installation.
<Applicable Model>
Heat Pump: RAS-14 - 24FSNS, RAS-8 - 18FSNP and JTOH140 - 240VPE(U,F,R)BS1
Heat Recovery: RAS-14 - 24FSXNS, RAS-8 - 18FSXNP and JTOR140 - 240VPE(U,F,R)BS1
Attached
Screw
Outdoor Unit
2 2
1
5. Installation Appearance
The following examples illustrate a small cabinet.
Unit: mm
Securing
Screw
(Accessory)
Protection Net
Protection Net [for Left Side
[for Side Installation]
Installation] (Other Protection
1675
Net Option)
Protection Net
[for Rear Side
Installation]
Outdoor Unit (Other Protection
100 100 Net Option) 100 765
< Right Side > < Rear Side > < Left Side >
Available Combinations
Model
RAS-8 - 12FSNS RAS-14 - 18FSNS RAS-20 - 24FSNS
Applicable Heat
RAS-5, 6FSNP RAS-8 - 14FSNP RAS-16, 18FSNP
Outdoor Unit Pump
JTOH080 - 120VPE(U,F,R)BS1 JTOH140 - 180VPE(U,F,R)BS1 JTOH200- 240VPE(U,F,R)BS1
(Representative
Model) RAS-8 - 12FSXNS RAS-14 - 18FSXNS RAS-20 - 24FSXNS
Heat
RAS-5, 6FSXNP RAS-8 - 14FSXNP RAS-16, 18FSXNP
Recovery
JTOR080 - 120VPE(U,F,R)BS1 JTOR140 - 180VPE(U,F,R)BS1 JTOR200 - 240VPE(U,F,R)BS1
Protection Net for
PN-TP20BA PN-TP20BB PN-TP20BC
Rear Side
Protection Net for
PN-TP20L PN-TP20R
Left Side
Protection Net for
PN-TP20R
Right Side
NOTICE:
● This manual applies only to the combination indicated with .
For other protection net options, refer to each model’s installation manual.
● Install the required protection net only if all installation requirements can be met.
P5416994-rev.1, 2017
Installation
Manual
for
Cooling / Heating
Change-Over Box
CH-Box
Models:
CH-AP160SSX
CH-AP280SSX
JCH-AP160SSX
JCH-AP280SSX
IMPORTANT:
4: Available
4
4
Current CH Unit Current VRF (Heat Recovery)
×: Not Available
×
4
4
New CH-Box New VRF (Heat Recovery)
4
4
● Current and new CH-Boxes can not be used in the same system together.
● Production of current CH unit shall be discontinued. However, it will be supplied for servicing and
maintenance until further notice. Contact us if there are order request for the current CH unit.
P5417023-rev.1 i
IMPORTANT NOTICE
● The applicable outdoor unit may be different depending on the product series.
Improper combination causes the unit to malfunction and an alarm will be triggered. Be sure to confirm
with the product catalogue before installation.
● The manufacturer of the product pursues a policy of continuous improvement in the design and
performance of products to meet regulatory requirements and industry standards. Therefore, the
manufacturer reserves the right to revise specifications without notice.
● The manufacturer of the product cannot anticipate every possible circumstance that might involve a
potential hazard.
● This heat pump air conditioner is designed for standard air conditioning applications only. Do not use this
heat pump air conditioner for other purposes, such as drying clothes, refrigerating foods, or for any other
cooling or heating process.
● Do not install the unit outdoors. Do not install the unit in the following places. It may cause a fire,
deformation, corrosion or failure.
* Places where there are high levels of oil mist (including machinery oil).
* Places where there are high alkalinity levels (i.e., chlorine or bromine such as over hot tubs, etc.).
* Places where flammable gases or liquids may be used or generated.
* Places with a high concentration of salts, salty mists or sprays (such as over salt-water aquariums).
* Places with an atmosphere of high nuisance dust. Places with organic solvent atmospheres, such as
painting and cleaning locations.
● Do not install a unit in the place where condensate water can leak onto the unit or electrical device failures
may occur.
● Pay attention to the following points when the unit is installed in a hospital or other facility where
electromagnetic waves generate from medical equipment.
* Do not install the unit in places where electromagnetic waves radiate to the electrical box, wired controller
cable or wired controller.
* Install the unit at least 3m (10 ft) away from electromagnetic waves or interferences such as a radio.
● The installer and system specialist shall secure against leakage according to local regulations or
standards. This system has both high and low pressure refrigerant and, as such, comprises a pressurized
system. Never loosen threaded joints while the system is under pressure and never open pressurized
system parts.
● No part of this manual may be reproduced without written permission.
● It is assumed that this heat pump air conditioner will be operated and serviced by English speaking people.
If this is not the case, the distributor or dealer can provide or add safety, caution and operating signs in the
native language.
● If you have any questions, contact your distributor.
● This manual describes the features of this heat pump air conditioner as well as for other models.
This manual should be considered as a permanent part of the air conditioning equipment and should remain
with the air conditioning equipment.
ii P5417023-rev.1
The standard installation and general use of this unit is explained in this manual.
Although common processes and procedures for installing units are presented in this manual, its use for
installation of units otherwise indicated in this manual is not recommended. Please contact your local agent,
as the occasion arises.
Our liability shall not cover defects arising from the alteration performed by a customer without our consent in
a written form.
SAFETY SUMMARY
Signal Words
● Signal words are used to identify levels of hazard seriousness.
Definitions for identifying hazard levels are provided below with their respective signal words.
CAUTION : CAUTION used with the safety alert symbol, indicates a hazardous situation which,
if not avoided, could result in minor or moderate injury.
P5417023-rev.1 iii
SAFETY SUMMARY
DANGER
● Do not perform installation work, refrigerant piping work, condensate pump, or condensate piping and
electrical wiring connection without referring to the installation manual. If the instructions are not followed,
it may result in a water leakage, electric shock or a fire.
● Use the specified non-flammable refrigerant (R410A) for the outdoor unit in the refrigerant cycle.
Charge only R410A into the unit. Do not charge other materials into the unit such as hydrocarbon
refrigerants (propane), oxygen, flammable gases (acetylene) or poisonous gases when installing,
maintaining and moving the unit. These flammables are extremely dangerous and may cause an
explosion, a fire, or injury. As originally manufactured, this unit contains refrigerant installed by the
manufacturer of the product. The manufacturer of the product uses only refrigerants that have been
approved for use in the unit’s intended country or market. Distributors similarly are only authorized
to provide refrigerants that have been approved for use in the countries or markets they serve. The
refrigerant used in this unit is identified on the unit’s faceplate and/or in the associated manuals. Any
additions of refrigerant into this unit must comply with the country’s requirements with regard to refrigerant
use and should be obtained from distributors. Use of unapproved refrigerant substitutes will void the
warranties and can cause injury or death.
● Do not pour water into the indoor or outdoor unit. These units are equipped with electrical parts.
Exposure to water may cause a serious electrical shock.
● Do not open the service cover or access panel for the indoor or outdoor units without turning OFF the main
power supply.
● Do not touch or adjust safety devices inside the indoor unit or outdoor units. If these devices are touched
or readjusted, it may cause a serious accident.
● Carefully check for escaping refrigerant gas. If there is significant leakage, it can cause difficulty in
breathing. Turn OFF the main switch, and contact your service contractor if refrigerant leakage occurs.
● Make sure that the refrigerant leakage test is performed.
Refrigerant (fluorocarbon) for this unit is incombustible, non-toxic and odorless.
However if the refrigerant is leaked and comes in contact with fire, toxic gas will generate.
Because fluorocarbon is heavier than air, the floor surface will be filled with it, which could cause
suffocation.
● The installer and system specialist shall secure against refrigerant leakage according to local regulations
or standards.
● Use a Earth Leakage Breaker (ELB).
In the event of fault, there is danger of an electric shock or a fire if it is not used.
iv P5417023-rev.1
SAFETY SUMMARY
WARNING
● Do not use any sprays such as insecticide, lacquer, hair spray or other flammable gases within
approximately 1.3m (4 ft) from the system.
● If the circuit breaker or fuse is often activated, stop the system and contact your service contractor.
● Check that the ground wiring is securely connected. If the unit is not correctly grounded, it may cause
electric shock. Do not connect the ground wiring to gas piping, condensate piping, lighting conductor or
ground wiring for telephones.
● Before performing any brazing work, check to ensure that there is no flammable material around.
When using refrigerant, be sure to wear leather gloves to prevent injury from cold.
● Insulate electrical wiring, condensate piping, and electrical components from threats posed by burrowing
animals and temperature extremes. Failure to do so can, over time, deteriorate system performance.
● Secure the cables. External forces on the terminals could lead to a fire.
● Tighten the flare nut with a torque wrench in the specified manner. Do not apply excessive force to the
flare nut when tightening. If you do, the flare nut can crack and refrigerant leakage may occur.
● When maintaining, relocating or disposing of the unit, dismantle the refrigerant piping after the compressor
stops.
● Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and
these instructions when wiring. Improper connections and inadequate grounding can cause serious injury
or death.
● Perform all electrical work in strict accordance with this installation and maintenance manual and all
relevant regulatory standards.
● Use specified cables between units.
● Be sure to install circuit breakers (ground fault interrupter, isolating switch, molded case circuit breaker
and so on), with the specified capacity. Ensure that the wiring terminals are tightened securely to
recommended torque specifications. If a circuit breaker or fuse is frequently activated, shut down the
system and contact your service contractor.
● Clamp electrical wires securely with a cable clamp after all wiring is connected to the terminal block.
In addition, run wires securely through the wiring access channel.
● When installing the power lines, do not apply tension to the cables. Secure the suspended cables at
regular intervals, but not too tightly.
● After stopping operation, be sure to wait at least five minutes before turning off the main power switch.
Otherwise, water leakage or electrical breakdown may result. Disconnect the power supply completely
before attempting any maintenance for electrical parts. Check to ensure that no residual voltage is present
after disconnecting the power supply.
● Insulate the refrigerant pipe connection to prevent condensation.
● Be sure to attach the cover so that it fits securely on the electrical box without any gaps. Secure the cover
with screws.
P5417023-rev.1 v
CAUTION
● Do not step on the unit.
● Do not put any foreign material on the unit or inside the unit.
● Provide a strong and correct foundation so that:
● The outdoor unit is not on an incline.
● Abnormal sound does not occur.
● The outdoor unit will not fall down due to a strong wind or earthquake.
NOTICE
● Be careful that moisture, dust, or variant refrigerant compounds not enter the refrigerant system during
installation work. Foreign matter could damage internal components or cause blockages.
● Do not install the indoor unit, outdoor unit, wired controller and cable within approximately 3m (10 ft) of
strong electromagnetic wave radiators such as medical equipment.
● After a long shutdown, apply power to the outdoor unit(s) at least 12 hours prior to operation of the system
for preheating of the compressor oil.
NOTE
● It is recommended that the room is ventilated every three to four hours.
● The heating capacity of the heat pump unit is decreased according to the outdoor air temperature.
Therefore, it is recommended that auxiliary heating equipment be used in the field when the unit is
installed in a low temperature region.
vi P5417023-rev.1
TABLE OF CONTENTS
2. Structure .........................................................................................................................................................1
2.1 Dimensions.............................................................................................................................................1
2.2 Refrigeration Cycle .................................................................................................................................2
2.3 Necessary Tools and Instrument List for Installation ..............................................................................3
P5417023-rev.1 vii
1. Safety Summary
● Do not perform installation work, refrigerant Do not install the CH-Box and cable within
piping work or electrical wiring connection approximately 3m (10 ft) from strong
without referring to our installation manual. electromagnetic wave radiators such as
● Check that the ground wire is securely medical equipment.
connected.
● Connect a fuse of specified capacity.
2. Structure
2.1 Dimensions
23(7/8) 330(13) Suspension Bracket
CH-AP160SSX (For Suspension Bolt) 2×(11(7/16)×34(1-5/16)) Unit: mm(inch)
JCH-AP160SSX Slotted Hole
(1-9/16)
40
Ground Terminal (M5)
Refrigerant Gas
376(14-13/16) (in Electrical Box) Pipe Connection
Electrical Box (ϕ15.88(5/8)
38(1-1/2) 301(11-7/8) 38(1-1/2)
Refrigerant Gas (Available Flare Nut)
(Low Pressure) for both sides)
214(8-7/16) Pipe Connection
(ϕ19.05(3/4) Flare Nut)
191(7-1/2)
89(3-1/2)
180(7-1/16)
Refrigerant Gas
(1-9/16)
(high/Low Pressure)
Pipe Connection
39
P5417023-rev.1 1
CH-AP280SSX
JCH-AP280SSX 23(7/8) 330(13)
(For Suspension Bolt)
Unit: mm(inch)
(1-9/16)
40
Suspension Bracket
2×(11(7/16)×34(1-5/16))
Slotted Hole
Ground Terminal (M5) Refrigerant Gas
376(14-13/16) (in Electrical Box) Pipe Connection
Refrigerant Gas Electrical Box (ϕ19.05(3/4)
(Low Pressure) 38(1-1/2) 301(11-7/8) 38(1-1/2)
Pipe Connection (Available Flare Nut)
8-7/16(214)
for both sides)
(ϕ19.05(3/4) Flare Nut)
Refrigerant Gas
(1-9/16)
89(3-1/2)
180(7-1/16)
191(7-1/2)
(high/Low Pressure)
Pipe Connection
39
25(1)
40 54 111(4-3/8)
20(13/16)
(1-9/16) (2-1/8)
151 63(2-1/2)
Indoor Unit Connecting Side
(5-15/16) 40(1-9/16) 221(8-11/16)
Power Supply
38(1-1/2) Wiring Connection
Outdoor Unit Connecting Side (ϕ20(13/16))
Control Wiring
Connection
(ϕ20(13/16))
Specifications
CH-AP280SSX
Model
JCH-AP280SSX
1/N~, 230V, 50Hz
1/N~, 220-240V, 50Hz
1/N~, 220V, 60Hz
Power Supply
1~, 208-230V, 60Hz*
1~ ,220V, 60Hz*
*For Mexico model only.
Power Consumption 5W
Refrigerant R410A
Net Weight 6kg
Number of Indoor Unit 6.1 to 10.0HP
Total Capacity (Max. 28kW)
Number of Connectable
1 to 8
Indoor Unit
Electronic Expansion
Strainer Valve [MVS1] Strainer
Low Pressure
Gas Pipe Connection S S Gas Pipe Connection
2 P5417023-rev.1
P5417023-rev.1 3
4. CH-Box Installation
NOTE
If any of these accessories are not packed with the
unit, please contact your distributor.
● Check to ensure that the ceiling slab is strong
enough.
● Do not install the CH-Box outdoors.
If installed outdoors, an electric hazard or
electric leakage may occur.
● Installation WARNING: Ensure that all safety
features, disconnects and interlocks are
in place and functioning properly prior to
putting the equipment into operation. Never
by-pass or jump-out any safety device or
switch.
Flaring Flaring
(2) ID f12.7 f15.88 2 ID f22.2 f19.05 2
Flare Nut
(1/2) Flare Nut (5/8) (7/8) (3/4)
Flaring
(4) - - ID f19.05 f15.88 1
Flare Nut
(3/4) (5/8)
ID f16
(5) 2 1
(5/8)
ID f20
(6) 1 - -
(13/16)
Insulation ID f22
(7) - - 2
Material (7/8)
ID f38
(8) 2 1
(1-1/2)
ID f43
(9) 1 2
(1-11/16)
(10) Clamp 6 6
4 P5417023-rev.1
(3-15/16)
Unit: mm (inch) CH-Box is activated, a change in the typical
refrigerant flow sounds may be heard or
100
perceived from the CH-Box. Take the following
action to minimize the sound.
Electrical Box
(A) Install the CH-Box inside the ceiling. As for
the ceiling material, select a material like a
plasterboard at least 9mm (1 inch), which
minimizes operation sound.
(B) Do not install the CH-Box in a place near
bedrooms or hospital rooms.
Service Access Door
● When the operation is changed to cooling/
heating mode, a change in the typical refrigerant
( 450 (17-11/16))
flow sounds may be heard or perceived from the
CH-Box.
2-Suspension Bolt Therefore, install the CH-Box in the ceiling of
M10 or W3/8 Upper Side the corridor so that the refrigerant flowing sound
(Field-Supplied) Min. 70 (2-3/4) may not be heard in the room.
● Do not install the CH-Box in a hot or humid
place, such as a kitchen, to prevent
condensation on the outer surface of the
CH-Box.
When installing the CH-Box in such places,
Min. A Min. A
apply additional insulation.
● Pay attention to the following points when the
Min. 2-3/4(70) CH-Box is installed in a hospital or other facility
Bottom Side where there are electronic waves from medical
equipment.
Size (A) Do not install the CH-Box where the
A
Model electromagnetic wave is directly radiated to
CH-AP160SSX
300 (11-13/16)
the electrical box or communication cable.
JCH-AP160SSX
(B) Install the CH-Box and components as far
CH-AP280SSX
JCH-AP280SSX
400 (15-3/4) as practicable or at least 3m (10 ft) from the
electromagnetic wave radiator.
Figure 4.1 Service Space (C) Install a noise filter when the power supply
emits harmful noises.
● Ensure the installation place is convenient
for the refrigerant piping or electrical wiring
connection.
● Do not drill, or drive screws into the cabinet.
Use only mounting points provided.
P5417023-rev.1 5
40(1-9/16)
direction of the CH-Box. (For Suspension Bolt)
Pay careful attention to the space for the Suspension Bracket
piping, wiring and maintenance. 11(2-7/16) x 34(1-5/16)
Slotted Hole
(2) Mount suspension bolts.
(3) Mount the suspension bolts in the slotted
hole on the electrical box side as shown in
Figure 4.2. Electrical Box
(4) Contact a qualified contractor or carpenter
for the ceiling treatment.
Figure 4.2 Position of Suspension Bolts
Step 2
Mount suspension bolts, as shown in Figure 4.3.
Insert
100 to 150 kg
(220 to 331 lbs.)
Steal Concrete
Unit Body Use a hole saw Break a head portion Suspension Bolt
to make a hole. of anchor by using (M10 or W3/8)
a hammer.
(2) Resin Capsule Use a suspension bolt with 30 to 45o sloping edge.
Use the resin capsule within the warranty period.
Resin capsules deteriorate over time and should be used within
six mounths of the manufacturing date.
Stiffening Glass
Agent
Stone
Epoxy Resin
NOTE:
Use a suspension bolt (W3/8, Metric screw thread: M10).
Prepare washer and nut.
6 P5417023-rev.1
4.4 Installation
4.4.1 Changing the Location of the Electrical Box
Depending on the installation space, changing the location of the electrical box is available.
When changing the location of the electrical box, follow the procedures below:
(1) Remove the service cover for the electrical box.
(2) Remove the service cover for the electronic expansion valve.
(3) Remove the electrical box.
(4) Remove the wiring from the wire clip and edge saddle, and move the electrical box.
After moving the electrical box, put the wiring into the edge saddle and bound with the wire clip.
(Refer to “Enlarged View of A” below.)
(5) Mount the electrical box.
(6) Rotate the service cover for the electronic expansion valve 180 degrees and mount it.
(7) Mount the service cover for the electrical box.
(2) (6)
(6)
(7)
Electrical Box
(2) (6) (5)
(7)
(5)
(1) (3) A
Enlarged View of A
Edge Saddle Wire Clip *
Wire Clip
Edge Saddle
Electrical Box
MVS1 MVS1
MVD1 MVD1
Electrical Box
Edge Saddle
Edge Saddle
(Before Change) (After Change)
* Make sure that the wiring is bound with the wire clips
in order to prevent the electrical box from entering
water.
P5417023-rev.1 7
4.4.2 Marking of the Positions of the Suspension (2) Hanging the CH-Box
Bolts and Wiring Connections (a) Hang the CH-Box by putting hands on the
(1) Mark the positions of the suspension bolts, bottom of the cabinet.
refrigerant piping connections and wiring (b) Insert the suspension bolt into the groove
connection. part of the suspension bracket as shown
(2) Installation dimensions are shown in in Figure 4.5. Ensure that the washers
Figure 2.1. are correctly affixed to the suspension
bracket.
(c) After the hanging work, the piping and
4.4.3 Mounting and Hanging the CH-Box
wiring connection work is required inside
(1) Put nuts on each of the two suspension bolts the ceiling in the gap between the roof
before hanging the CH-Box, as shown in and ceiling so it is not visible. Therefore,
Figure 4.4. determine the drawing direction of the
T Mounting washers are required in order pipe after selecting the installation location
to affix the suspension bracket to the of the CH-Box. Before doing the hanging
suspension bolt. work, carry out the piping and wiring work
up to the connecting positions.
Field-Supplied Parts (d) Keep the CH-Box level to the ceiling
* Suspension Bolt: 2-M10 or W3/8 surface. If the CH-Box is not level, a
* Nut: 6-M10 or W3/8 malfunction may occur.
* Washer: 4-M10 or W3/8 (e) Tighten the nuts of the suspension
bolt with the suspension bracket after
adjustment is completed.
Adhesive must be applied to the nuts in
Suspension Bolt (M10 or W3/8)
order to prevent them from loosening.
(Field-Supplied)
Suspension Bracket
(Equipped with CH-Box)
Washer (Field-Supplied)
Double-Nut (Field-Supplied)
CH-Box
Suspension Bracket
Bottom Side
8 P5417023-rev.1
NOTE:
Do not use a joint other than those specified in
the table above.
P5417023-rev.1 9
10 P5417023-rev.1
191(7-1/2)
89
(7-1/16)
180
(3-1/2)
39
25(1)
82
54 Gas Pipe Connection (3-1/4) 111
(2-1/8) (φ15.88(5/8) Flare Nut) (4-3/8)
40
(1-9/16) 151 63(2-1/2) mm (inch) Indoor Unit Connecting Side
(5-15/16) Dimension
A B
Outdoor Unit Connecting Side Model
CH-AP160SSX
15.88(5/8) 89(3-1/2)
JCH-AP160SSX
CH-AP280SSX
19.05(3/4) 96(3-3/4)
JCH-AP280SSX
Upstream Downstream
Multi-Kit
Low Pressure
Gas Pipe
Gas Pipe
CH-Box
High/Low Pressure
Gas Pipe Indoor Indoor
Unit Unit
P5417023-rev.1 11
● Piping Connection
Perform the piping connection according to Table 5.1.
Unit: mm (inch)
Connected Indoor
CH-AP160SSX
Unit Capacity: Q
JCH-AP160SSX
(kW)
Unit: mm (inch)
Connected Indoor
CH-AP280SSX
Unit Capacity: Q
JCH-AP280SSX
(kW)
*1: Refer to the installation and maintenance manual for the outdoor unit for the following piping size.
• Upstream piping of CH-Box
• Downstream piping of CH-Box when the branch is located downstream of CH-Box.
*2: Refer to Section 5.1 for the flaring work.
NOTE:
The accessory numbers are listed in Table 4.1.
12 P5417023-rev.1
(9) Insulation
(ID 43(1-11/16)) (10) Clamp
(6) Insulation
(8) Insulation
(ID 20(13/16))
(ID 38(1-1/2))
CH-Box
CH-AP160SSX (Upper Surface)
JCH-AP160SSX
(5) Insulation
(ID 16(5/8))
(5) Insulation
(8) Insulation (10) Clamp
(ID 16(5/8))
(ID 38(1-1/2))
(9) Insulation
(ID 43(1-11/16)) (10) Clamp
(7) Insulation
(ID 22(7/8)) (9) Insulation
(ID 43(1-11/16))
CH-AP280SSX CH-Box
(Upper Surface)
JCH-AP280SSX
(5) Insulation
(ID 16(5/8))
(7) Insulation
(8) Insulation (10) Clamp
(ID 22(7/8))
(ID 38(1-1/2))
NOTES:
1. The accessory numbers are listed in Table 4.1.
2. When the humidity inside the ceiling is high, apply additional insulation to the flare nut connection.
Refer to Table 4.2 for more details.
P5417023-rev.1 13
6. Electrical Wiring
● LOCK ALL ELECTRICAL POWER SUPPLY SWITCHES IN THE OFF POSITION BEFORE INSTALLING
THE UNIT. FAILURE TO DISCONNECT POWER SUPPLY MAY RESULT IN ELECTRICAL SHOCK OR
EVEN DEATH.
● Turn off the main power switch to the CH-Box, the indoor unit and the outdoor unit before electrical
wiring work or a periodical check is performed.
● Insulate electrical wiring, condensate piping, and electrical components from threats posed by
burrowing animals and temperature extremes. Failure to do so can over time, deteriorate system
performance.
● Secure the cables. External forces on the terminals could lead to a fire.
● Tighten screws according to the following torque.
M4: 1.0 to 1.3 N●m (0.7 to 1.0 ft.lbs) (TB1, TB2)
● Wrap the field-supplied insulation around the wires, and plug the wiring connection hole with the
seal material to protect the product from any condensate water or insects.
● Tightly secure the wires with the cable clamp inside the CH-Box.
● Do not connect the ground wiring to the gas pipe, condensate pipe or lightening conductor.
Gas pipe: An explosion and ignition may occur when gas leaks.
Water pipe: There is no effect of ground wiring when a hard vinyl pipe is used.
Lightning conductor: The ground electric potential abnormally increases when a lightning
conductor is used.
14 P5417023-rev.1
NOTES:
1) Follow local codes and regulations when selecting field wires.
2) The wire sizes marked with *1 in the above table are selected at the maximum current of the unit according to the
European Standard, EN60 335-1. Use the wires which are not lighter than the ordinary tough rubber sheathed flexible
cord (code designation H05RN-F) or ordinary polychloroprene sheathed flexible cord (code designation H05RN-F).
3) The wire sizes marked with *2 in the above table are selected at the maximum current of the unit according to the
wire, MLFC (Flame Retardant Polyflex Wire) manufactured by Hitachi Cable Ltd., Japan.
4) Use a shielded cable for the transmitting circuit and connect it to ground.
5) In the case that power cables are connected in series, add each unit maximum current and select wires below.
Selection According to EN60 335-1 Selection According to MLFC (at Cable Temperature of 90oC)
Current i (A) Wire Size (mm2) Current i (A) Wire Size (mm2)
i< 6 0.75 i < 15 0.5 *3: In the case that
6 < i < 10 1 15 < i < 19 0.75 current exceeds 63A,
10 < i < 16 1.5 19 < i < 24 1.25 do not connect cables
16 < i < 25 2.5 24 < i < 34 2 in series.
25 < i < 32 4 34 < i < 47 3.5
32 < i < 40 6 47 < i < 63 5.5
40 < i < 63 10 63 < i < 78 8
63 < i *3 78 < i < 113 14
113 < i < 148 22
148 < i < 179 30
P5417023-rev.1 15
Terminal Block
for Communication
CN1 CN2
Terminal Block
for Power Supply
PCB1 TB1
TB2 PCN1
Ground Wiring
Cable Clamp
NOTE:
The accessory numbers are listed in Table 4.1.
16 P5417023-rev.1
The following figure shows an example of electrical wiring around the CH-Boxes.
Outdoor Unit
Power Supply Outdoor Unit
1~/N~ 230V/50Hz Connect the operating line for
1~/N~ 220-240V/50Hz the outdoor unit to the terminal
1~/N~ 220V/60Hz “1” and “2” of TB2 on the CH-Box.
For Mexico 1~, 208-230V, 60Hz TB2
model only. 1~, 220V, 60Hz 1 2 3 4
Connect the operating line for
CH-Box CH-Box
the indoor unit (exclusive use of
ELB TB1 TB2 TB1 TB2 cooling operation) to the terminal
1 Earth Leakage 3 3 “1” and “2” of TB2 on the CH-Box.
L1 N 1 2 3 4 L1 N 1 2 3 4
Breaker
S
2 Main Switch
Wired
4 Pull Box Controller
5
Operating Line TB2 TB2 TB2 TB2
(Non-pole, DC5V)
2 1 BA 2 1BA 2 1BA 2 1 BA
Indoor Unit Wired Indoor Unit Wired Indoor Unit Indoor Unit
Controller Controller (Exclusive Use of
Cooling Operation)
In case that the multiple indoor units
are connected to the same CH-Box,
the operation mode (cooling/heating)
for the indoor units will be the same.
NOTES:
1. Do not apply excessive voltage to the communication cable DC5V (non-polarity) between the outdoor
unit and the CH-Box, between the CH-Box and the indoor unit or between CH-Boxes.
2. Use 2-Conductor shielded communication cable for the communication cable. (Do not use 3-Conductor
cable or over.)
3. Connect the communication cable for the outdoor unit to terminals “1” and “2” on TB2 in the CH-Box.
4. Connect the communication cable for the indoor unit exclusively for cooling operation to the terminal “1”
and “2” on TB2 in the CH-Box.
5. For a CH-Box in the same refrigerant cycle, an electrical power supply can be supplied by one main
switch.
6. Do not connect the power supply line (220-240V/220V/230V) to the terminal block for transmission line.
7. Connect the ground wiring for the outdoor/indoor units and CH-Box. When ground resistance is less
than 100 ohms, ground wiring work should be performed by the qualified electrician.
8. Do not run the communication cables along with power supply wiring in the CH-Box.
Separate communication cables from the power supply wirings.
P5417023-rev.1 17
7. Test Run
NOTICE
Refrigerant piping and connecting wires should be connected to the same refrigerant cycle system.
If they are connected to the dissimilar refrigerant cycle systems, a malfunction may occur.
250
(Countermeasures
Not Needed)
150
50
Perform a test run according to the “Installation and Maintenance Manual” of the outdoor unit.
● Do not operate the system until all the check points are cleared.
(A) Check to ensure that the electrical resistance is more than 1 megohm by measuring the
resistance between ground and the terminal block in the electrical box. If not, do not operate
the system until the electrical leakage is found and repaired.
(B) Check to ensure that the stop valves of the outdoor unit are fully opened, and then start the
system.
(C) Apply power to the outdoor unit(s) at least 12 hours prior to operation of the system for
preheating of the compressor oil.
● Pay attention to the following items while the system is running.
(A) Do not touch any of the parts by hand at the discharge gas side, since the compressor
chamber and the pipes at the discharge side are heated higher than 90°C (194°F).
18 P5417023-rev.1
P5417023-rev.1 19
Installation
Manual
for
Cooling / Heating
Change-Over Box
CH-Box
Models:
CH-AP04MSSX
CH-AP08MSSX
CH-AP12MSSX
CH-AP16MSSX
JCH-AP04MSSX
JCH-AP08MSSX
JCH-AP12MSSX
JCH-AP16MSSX
IMPORTANT:
4: Available
4
4
Current CH Unit Current VRF (Heat Recovery)
×: Not Available
×
4
4
New CH-Box New VRF (Heat Recovery)
4
4
● Current and new CH-Boxes can not be used in the same system together.
● Production of current CH unit shall be discontinued. However, it will be supplied for servicing and
maintenance until further notice. Contact us if there are order request for the current CH unit.
P5417025-rev.1 i
IMPORTANT NOTICE
● The applicable outdoor unit may be different depending on the product series.
Improper combination causes the unit to malfunction and an alarm will be triggered. Be sure to confirm
with the product catalogue before installation.
● The manufacturer of the product pursues a policy of continuous improvement in the design and
performance of products to meet regulatory requirements and industry standards. Therefore, the
manufacturer reserves the right to revise specifications without notice.
● The manufacturer of the product cannot anticipate every possible circumstance that might involve a
potential hazard.
● This heat pump air conditioner is designed for standard air conditioning applications only. Do not use this
heat pump air conditioner for other purposes, such as drying clothes, refrigerating foods, or for any other
cooling or heating process.
● Do not install the unit outdoors. Do not install the unit in the following places. It may cause a fire,
deformation, corrosion or failure.
* Places where there are high levels of oil mist (including machinery oil).
* Places where there are high alkalinity levels (i.e., chlorine or bromine such as over hot tubs, etc.).
* Places where flammable gases or liquids may be used or generated.
* Places with a high concentration of salts, salty mists or sprays (such as over salt-water aquariums).
* Places with an atmosphere of high nuisance dust. Places with organic solvent atmospheres, such as
painting and cleaning locations.
● Do not install a unit in the place where condensate water can leak onto the unit or electrical device failures
may occur.
● Pay attention to the following points when the unit is installed in a hospital or other facility where
electromagnetic waves generate from medical equipment.
* Do not install the unit in places where electromagnetic waves radiate to the electrical box, wired controller
cable or wired controller.
* Install the unit at least 3m (10 ft) away from electromagnetic waves or interferences such as a radio.
● The installer and system specialist shall secure against leakage according to local regulations or
standards. This system has both high and low pressure refrigerant and, as such, comprises a pressurized
system. Never loosen threaded joints while the system is under pressure and never open pressurized
system parts.
● No part of this manual may be reproduced without written permission.
● It is assumed that this heat pump air conditioner will be operated and serviced by English speaking people.
If this is not the case, the distributor or dealer can provide or add safety, caution and operating signs in the
native language.
● If you have any questions, contact your distributor.
● This manual describes the features of this heat pump air conditioner as well as for other models.
This manual should be considered as a permanent part of the air conditioning equipment and should remain
with the air conditioning equipment.
ii P5417025-rev.1
The standard installation and general use of this unit is explained in this manual.
Although common processes and procedures for installing units are presented in this manual, its use for
installation of units otherwise indicated in this manual is not recommended. Please contact your local agent,
as the occasion arises.
Our liability shall not cover defects arising from the alteration performed by a customer without our consent in
a written form.
SAFETY SUMMARY
Signal Words
● Signal words are used to identify levels of hazard seriousness.
Definitions for identifying hazard levels are provided below with their respective signal words.
CAUTION : CAUTION used with the safety alert symbol, indicates a hazardous situation which,
if not avoided, could result in minor or moderate injury.
P5417025-rev.1 iii
SAFETY SUMMARY
DANGER
● Do not perform installation work, refrigerant piping work, condensate pump, or condensate piping and
electrical wiring connection without referring to the installation manual. If the instructions are not followed,
it may result in a water leakage, electric shock or a fire.
● Use the specified non-flammable refrigerant (R410A) for the outdoor unit in the refrigerant cycle.
Charge only R410A into the unit. Do not charge other materials into the unit such as hydrocarbon
refrigerants (propane), oxygen, flammable gases (acetylene) or poisonous gases when installing,
maintaining and moving the unit. These flammables are extremely dangerous and may cause an
explosion, a fire, or injury. As originally manufactured, this unit contains refrigerant installed by the
manufacturer of the product. The manufacturer of the product uses only refrigerants that have been
approved for use in the unit’s intended country or market. Distributors similarly are only authorized
to provide refrigerants that have been approved for use in the countries or markets they serve. The
refrigerant used in this unit is identified on the unit’s faceplate and/or in the associated manuals. Any
additions of refrigerant into this unit must comply with the country’s requirements with regard to refrigerant
use and should be obtained from distributors. Use of unapproved refrigerant substitutes will void the
warranties and can cause injury or death.
● Do not pour water into the indoor or outdoor unit. These units are equipped with electrical parts.
Exposure to water may cause a serious electrical shock.
● Do not open the service cover or access panel for the indoor or outdoor units without turning OFF the main
power supply.
● Do not touch or adjust safety devices inside the indoor unit or outdoor units. If these devices are touched
or readjusted, it may cause a serious accident.
● Carefully check for escaping refrigerant gas. If there is significant leakage, it can cause difficulty in
breathing. Turn OFF the main switch, and contact your service contractor if refrigerant leakage occurs.
● Make sure that the refrigerant leakage test is performed.
Refrigerant (fluorocarbon) for this unit is incombustible, non-toxic and odorless.
However if the refrigerant is leaked and comes in contact with fire, toxic gas will generate.
Because fluorocarbon is heavier than air, the floor surface will be filled with it, which could cause
suffocation.
● The installer and system specialist shall secure against refrigerant leakage according to local regulations
or standards.
● Use a Earth Leakage Breaker (ELB).
In the event of fault, there is danger of an electric shock or a fire if it is not used.
iv P5417025-rev.1
SAFETY SUMMARY
WARNING
● Do not use any sprays such as insecticide, lacquer, hair spray or other flammable gases within
approximately 1.3m (4 ft) from the system.
● If the circuit breaker or fuse is often activated, stop the system and contact your service contractor.
● Check that the ground wiring is securely connected. If the unit is not correctly grounded, it may cause
electric shock. Do not connect the ground wiring to gas piping, condensate piping, lighting conductor or
ground wiring for telephones.
● Before performing any brazing work, check to ensure that there is no flammable material around.
When using refrigerant, be sure to wear leather gloves to prevent injury from cold.
● Insulate electrical wiring, condensate piping, and electrical components from threats posed by burrowing
animals and temperature extremes. Failure to do so can, over time, deteriorate system performance.
● Secure the cables. External forces on the terminals could lead to a fire.
● Tighten the flare nut with a torque wrench in the specified manner. Do not apply excessive force to the
flare nut when tightening. If you do, the flare nut can crack and refrigerant leakage may occur.
● When maintaining, relocating or disposing of the unit, dismantle the refrigerant piping after the compressor
stops.
● Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and
these instructions when wiring. Improper connections and inadequate grounding can cause serious injury
or death.
● Perform all electrical work in strict accordance with this installation and maintenance manual and all
relevant regulatory standards.
● Use specified cables between units.
● Be sure to install circuit breakers (ground fault interrupter, isolating switch, molded case circuit breaker
and so on), with the specified capacity. Ensure that the wiring terminals are tightened securely to
recommended torque specifications. If a circuit breaker or fuse is frequently activated, shut down the
system and contact your service contractor.
● Clamp electrical wires securely with a cable clamp after all wiring is connected to the terminal block.
In addition, run wires securely through the wiring access channel.
● When installing the power lines, do not apply tension to the cables. Secure the suspended cables at
regular intervals, but not too tightly.
● After stopping operation, be sure to wait at least five minutes before turning off the main power switch.
Otherwise, water leakage or electrical breakdown may result. Disconnect the power supply completely
before attempting any maintenance for electrical parts. Check to ensure that no residual voltage is present
after disconnecting the power supply.
● Insulate the refrigerant pipe connection to prevent condensation.
● Be sure to attach the cover so that it fits securely on the electrical box without any gaps. Secure the cover
with screws.
P5417025-rev.1 v
CAUTION
● Do not step on the unit.
● Do not put any foreign material on the unit or inside the unit.
● Provide a strong and correct foundation so that:
● The outdoor unit is not on an incline.
● Abnormal sound does not occur.
● The outdoor unit will not fall down due to a strong wind or earthquake.
NOTICE
● Be careful that moisture, dust, or variant refrigerant compounds not enter the refrigerant system during
installation work. Foreign matter could damage internal components or cause blockages.
● Do not install the indoor unit, outdoor unit, wired controller and cable within approximately 3m (10 ft) of
strong electromagnetic wave radiators such as medical equipment.
● After a long shutdown, apply power to the outdoor unit(s) at least 12 hours prior to operation of the system
for preheating of the compressor oil.
NOTE
● It is recommended that the room is ventilated every three to four hours.
● The heating capacity of the heat pump unit is decreased according to the outdoor air temperature.
Therefore, it is recommended that auxiliary heating equipment be used in the field when the unit is
installed in a low temperature region.
vi P5417025-rev.1
TABLE OF CONTENTS
2. Structure .........................................................................................................................................................1
2.1 Dimensions.............................................................................................................................................1
2.2 Refrigeration Cycle .................................................................................................................................4
2.3 Necessary Tools and Instrument List for Installation ..............................................................................5
P5417025-rev.1 vii
1. Safety Summary
● Do not perform installation work, refrigerant Do not install the CH-Box and cable within
piping work or electrical wiring connection approximately 3m (10 ft) from strong
without referring to our installation manual. electromagnetic wave radiators such as
● Check that the ground wire is securely medical equipment.
connected.
● Connect a fuse of specified capacity.
2. Structure
2.1 Dimensions
CH-AP04MSSX Unit: mm
JCH-AP04MSSX Specifications
CH-AP04MSSX
Model
JCH-AP04MSSX
1/N~, 220-240V, 50Hz
View from P P 1/N~, 220V, 60Hz
1/N~, 230V, 50Hz
Power Supply
67 60 x 3 = 180 Refrigerant Liquid Pipe 1~, 208-230V, 60Hz*
Connections 20 340 1~, 220V, 60Hz*
60
A D C B (4 x ɸ9.52 Flare Nuts) (For Suspension Bolt) *For Mexico model only.
60
50
Power Supply Wiring 35 176
42
(I.D. ɸ25.6)
Outdoor Unit Connecting Side
P5417025-rev.1 1
Unit: mm
CH-AP08MSSX
JCH-AP08MSSX Specifications
CH-AP08MSSX
Model
JCH-AP08MSSX
1/N~, 220-240V, 50Hz
1/N~, 220V, 60Hz
View from P P 1/N~, 230V, 50Hz
Refrigerant Liquid Pipe Power Supply
67 60 x 7 = 420 1~, 208-230V, 60Hz*
Connections 1~, 220V, 60Hz*
60 (8 x ɸ9.52 Flare Nuts) 20 580
(For Suspension Bolt)
*For Mexico model only.
198 Input (W) 22.4
A D C B E H G F
60
156
Refrigerant Gas
Pipe Connection 110 Refrigerant R410A
30
(8 x ɸ15.88 Net Weight (kg) 25
Flare Nuts)
256
Connectable Indoor Unit 6.0HP or less
Total Capacity per Branch (Max. 16.0kW)
Suspension Bracket Number of Connectable
4 - (12 x 32) Slotted Hole 1 to 6
551 Indoor Unit per Branch
199 352 780
Refrigerant Gas Refrigerant Liquid
86 67 38 543 38 (High/Low Pressure) Pipe Connection
Pipe Connection (I.D. ɸ12.9)
Electrical Box (I.D. ɸ22.36)
260
156
(in Electrical Box)
60
50
42
Power Supply Wiring 35 176 240 Control Wiring Connection
Connection (ɸ26) 180
(2 x ɸ26)
Refrigerant Gas 244
(Low Pressure)
Pipe Connection
34
(I.D. ɸ28.75)
Outdoor Unit Connecting Side
CH-AP12MSSX
JCH-AP12MSSX Specifications
CH-AP12MSSX
Model
JCH-AP12MSSX
View from P 1/N~, 220-240V, 50Hz
1/N~, 220V, 60Hz
Refrigerant Liquid Pipe Connections
(12 x ɸ9.52 Flare Nuts) P Power Supply
1/N~, 230V, 50Hz
1~, 208-230V, 60Hz*
67 60 x 11 = 660 1~, 220V, 60Hz*
60 20 820 *For Mexico model only.
A D C B E H G F I J K L (For Suspension Bolt) Input (W) 33.6
60
156
198
Refrigerant R410A
110
30
50
42
Power Supply Wiring 35 176 240 240 Control Wiring Connection 180
Connection (ɸ26) (3 x ɸ26) Refrigerant Gas
(Low Pressure) 244
Pipe Connection
34
(I.D. ɸ28.75)
Outdoor Unit Connecting Side
2 P5417025-rev.1
Unit: mm
CH-AP16MSSX
JCH-AP16MSSX Specifications
CH-AP16MSSX
Model
JCH-AP16MSSX
View from P 1/N~, 220-240V, 50Hz
Refrigerant Liquid Pipe Connections 1/N~, 220V, 60Hz
(16 x ɸ9.52 Flare Nuts) 1/N~, 230V, 50Hz
Power Supply
67 900 1~, 208-230V, 60Hz*
60 P 1~, 220V, 60Hz*
*For Mexico model only.
A D C B E H G F I J K O N M L P
Input (W) 44.8
60
156
20 1060
(For Suspension Bolt)
Refrigerant R410A
198
Refrigerant Gas Pipe Connection 110 Net Weight (kg) 47
30
(16 x ɸ15.88 Flare Nuts) Connectable Indoor Unit
30.0HP or less
Indoor Unit Connecting Side Total Capacity
156
(in Electrical Box)
60
35 176 240 240 240 50
42
Power Supply Wiring Control Wiring Connection
180
Connection (ɸ26) (4 x ɸ26) Refrigerant Gas
(Low Pressure) 244
Pipe Connection
(I.D. ɸ32)
34
P5417025-rev.1 3
CH-AP04MSSX CH-AP08MSSX
JCH-AP04MSSX JCH-AP08MSSX
G (High/Low Pressure) G (High/Low Pressure)
G (Low Pressure) G (Low Pressure)
L L
To Outdoor Unit Side To Outdoor Unit Side
2 2
1
S S S S
1 1
1
<MVD4>
<MVD3>
<MVD2>
<MVD1>
<MVD4>
<MVD3>
<MVD2>
<MVD1>
<MVD4>
<MVD3>
<MVD2>
<MVD1>
<MVS4>
<MVS3>
<MVS2>
<MVS1>
<MVS4>
<MVS3>
<MVS2>
<MVS1>
<MVS4>
<MVS3>
<MVS2>
<MVS1>
S S S S S S S S S S S S
2 2
L L L L L L L L L L L L
G G G G G G G G G G G G
Unit D Unit C Unit B Unit A Unit H Unit G Unit F Unit E Unit D Unit C Unit B Unit A
CH-AP12MSSX
JCH-AP12MSSX
G (High/Low Pressure)
G (Low Pressure)
L
S S
1
<MVD4>
<MVD3>
<MVD2>
<MVD1>
<MVD4>
<MVD3>
<MVD2>
<MVD1>
<MVD4>
<MVD3>
<MVD2>
<MVD1>
<MVS4>
<MVS3>
<MVS2>
<MVS1>
<MVS4>
<MVS3>
<MVS2>
<MVS1>
<MVS4>
<MVS3>
<MVS2>
<MVS1>
S S S S S S S S S S S S
2
L L L L L L L L L L L L
G G G G G G G G G G G G
Unit L Unit K Unit J Unit I Unit H Unit G Unit F Unit E Unit D Unit C Unit B Unit A
4 P5417025-rev.1
CH-AP16MSSX
JCH-AP16MSSX
G (High/Low Pressure)
2 G (Low Pressure) 1
L Outdoor Unit Side
S S
<MVD4>
<MVD3>
<MVD2>
<MVD1>
<MVD4>
<MVD3>
<MVD2>
<MVD1>
<MVD4>
<MVD3>
<MVD2>
<MVD1>
<MVD4>
<MVD3>
<MVD2>
<MVD1>
<MVS4>
<MVS3>
<MVS2>
<MVS1>
<MVS4>
<MVS3>
<MVS2>
<MVS1>
<MVS4>
<MVS3>
<MVS2>
<MVS1>
<MVS4>
<MVS3>
<MVS2>
<MVS1>
S S S S S S S S S S S S S S S S
2
L L L L L L L L L L L L L L L L
G G G G G G G G G G G G G G G G
Unit P Unit O Unit N Unit M Unit L Unit K Unit J Unit I Unit H Unit G Unit F Unit E Unit D Unit C Unit B Unit A
P5417025-rev.1 5
Maximum Total Capacity of 16.0HP or less 30.0HP or less 30.0HP or less 30.0HP or less
All Connected Indoor Units (Max. 44.8kW) (Max. 85.0kW) (Max. 85.0kW) (Max. 85.0kW)
Single Unit
Per Branch Maximum Total Capacity of
6.0HP or less 6.0HP or less 6.0HP or less 6.0HP or less
Connected Indoor Units Per
(Max. 16.0kW) (Max. 16.0kW) (Max. 16.0kW) (Max. 16.0kW)
Branch
Maximum Number of
Connected Indoor Units Per 6 6 6 6
Branch
Multiple Units
Maximum Total Capacity of 16.0HP or less 30.0HP or less 30.0HP or less 30.0HP or less
Per Branch
All Connected Indoor Units (Max. 44.8kW) (Max. 85.0kW) (Max. 85.0kW) (Max. 85.0kW)
(*1)
Maximum Total Capacity of
6.0HP or less 6.0HP or less 6.0HP or less 6.0HP or less
Connected Indoor Units Per
(Max. 16.0kW) (Max. 16.0kW) (Max. 16.0kW) (Max. 16.0kW)
Branch
(*1) When multiple indoor units are connected to the same branch of CH-Box, they are controlled with the
same operation mode.
NOTES:
1. Exceeding the total capacity may cause insufficient performance and abnormal sound. Be sure to
connect the CH-Box within the allowable total capacity.
2. In case of 8HP or 10HP type indoor unit connection:
Only single unit per branch is allowed to be connected.
Up to two 8HP or 10HP type indoor units can be connected to the CH-Box within the “Maximum Total
Capacity of All Connected Indoor Units” shown in above table.
Make sure to increase the pipe connection size by using the appropriate accessory pipe.
6 P5417025-rev.1
4. CH-Box Installation
NOTE
If any of these accessories are not packed with the
● Check to ensure that the ceiling slab is strong unit, please contact your distributor.
enough.
● Do not install the CH-Box outdoors.
If installed outdoors, an electric hazard or
electric leakage may occur.
● Installation WARNING: Ensure that all safety
features, disconnects and interlocks are
in place and functioning properly prior to
putting the equipment into operation. Never
by-pass or jump-out any safety device or
switch.
(1) 4 8 12 16
Flaring
f15.88 (5/8)
ID f6.35 (1/4)
(2) 4 8 12 16
Flaring
Accessory f9.52 (3/8)
Pipe ID f19.05 (3/4)
(3) 2 2 2 2
Flaring
Flare Nut Flare Nut Flare Nut Flare Nut
f15.88 (5/8)
ID f22.2 (7/8)
(4) 1 2 2 2
Flaring
Flare Nut Flare Nut Flare Nut Flare Nut
f15.88 (5/8)
ID f26
(5) 4 8 12 16
(1)
Insulation
Material
ID f35
(6) 4 8 12 16
(1-3/8)
(7) Clamp 17 34 51 68
P5417025-rev.1 7
100
100
8 P5417025-rev.1
A
110 Model
30
(4-5/16) CH-AP04MSSX
340 (13-3/8)
JCH-AP04MSSX
256 (10-1/16)
For Suspension
CH-AP08MSSX
580 (22-13/16)
JCH-AP08MSSX
CH-AP12MSSX
820 (32-5/16)
Bolt
JCH-AP12MSSX
Suspension Bracket CH-AP16MSSX
1060 (41-3/4)
12 (4-1/2) x 32 (1-1/4) JCH-AP16MSSX
4x
Slotted Hole
Figure 4.2 Position of Suspension Bolts
Step 2
Mount suspension bolts, as shown in Figure 4.3.
For Steel Beam For Wooden Beam
Wooden Bar
(60 to 90mm
Antiskid Clamp Suspension Bolt (2-3/8 to 3-9/16 inch) Square)
C-shaped (Bend it) Nut Square
Clamp Wooden Washer
Beam
Nut
Suspension I Beam Nut
Square
Bolt Support Angle Washer
Suspension Bolt Suspension Bolt
Suspension Bolt (M10 or W3/8) (M10 or W3/8)
(M10 or W3/8)
Insert
100 to 150 kg
(220 to 331 lbs.)
Steal Concrete
Unit Body Use a hole saw Break a head portion Suspension Bolt
to make a hole. of anchor by using (M10 or W3/8)
a hammer.
(2) Resin Capsule Use a suspension bolt with 30 to 45o sloping edge.
Use the resin capsule within the warranty period.
Resin capsules deteriorate over time and should be used within
six mounths of the manufacturing date.
Stiffening Glass
Agent
Stone
Epoxy Resin
NOTE:
Use a suspension bolt (W3/8, Metric screw thread: M10).
Prepare washer and nut.
4.4 Installation
4.4.1 Marking of the Positions of the Suspension (2) Hanging the CH-Box
Bolts and Wiring Connections (a) Hang the CH-Box by putting hands on the
(1) Mark the positions of the suspension bolts, bottom of the cabinet.
refrigerant piping connections and wiring (b) Insert the suspension bolt into the groove
connection. part of the suspension bracket as shown
(2) Installation dimensions are shown in in Figure 4.5. Ensure that the washers
Figure 2.1 and 2.2. are correctly affixed to the suspension
bracket.
(c) After the hanging work, the piping and
4.4.2 Mounting and Hanging the CH-Box wiring connection work is required inside
(1) Place nuts and washers onto the suspension the ceiling in the gap between the roof
bolts before installing the CH-Box. and ceiling so it is not visible. Therefore,
determine the drawing direction of the
NOTE: pipe after selecting the installation location
Make sure to use washers for installing the of the CH-Box. Before doing the hanging
suspension bolts to the suspension brackets. work, carry out the piping and wiring work
Install the washer with the insulation side up to the connecting positions.
facing down for suspended installation (d) Keep the CH-Box level to the ceiling
applications. This way, the washers surface. If the CH-Box is not level, a
themselves remain in position on the malfunction may occur.
suspension bolts during the installation (e) Tighten the nuts of the suspension
phase. bolt with the suspension bracket after
adjustment is completed.
Field-Supplied Parts Adhesive must be applied to the nuts in
* Suspension Bolt: 4-M10 or W3/8 order to prevent them from loosening.
* Nut: 12-M10 or W3/8
* Washer: 4-M10 or W3/8
* Washer with Insulation: 4-M10 or W3/8 Suspension Bolt
Suspension Bolt
(Field-Supplied) Suspension Bracket
Nut (Field-Supplied) (Four Places)
Suspension Bracket
(Attached Indoor Unit)
1-15/16 inch)
30 to 50mm
Washer (Field-Supplied)
(1-3/16 to
Double-Nut
(Field-Supplied)
Figure 4.5 Hanging Method
10 P5417025-rev.1
NOTE:
Do not use a joint other than those specified in
the table above.
P5417025-rev.1 11
12 P5417025-rev.1
* a Unit: mm (inch)
260
(10-1/4)
198
Refrigerant Liquid Pipe
(7-13/16)
(7-13/16)
(1-15/16)
Connection for Outdoor Unit
199
110
(3-3/8)
50
I.D. φD
86
(4-5/16)
(7-1/16)
551 (21-11/16)
180
352 (13-7/8)
(9-5/8)
244
Refrigerant Gas (Low Pressure)
Pipe Connection for Outdoor Unit
Refrigerant Gas (High/Low Pressure) 42
(2-5/8)
60
I.D. φB
(2-3/8)
A
156
(6-1/8)
Unit: mm (inch)
Dimension
A B C D
Model
CH-AP04MSSX
303 (11-15/16) 22.2 (7/8) 25.4 (1) 12.7 (1/2)
JCH-AP04MSSX
CH-AP08MSSX
543 (21-3/8) 22.2 (7/8) 28.58 (1/1/8) 12.7 (1/2)
JCH-AP08MSSX
CH-AP12MSSX
783 (30-13/16) 25.4 (1) 28.58 (1/1/8) 15.88 (5/8)
JCH-AP12MSSX
CH-AP16MSSX
1023 (40-9/32) 28.58 (1-1/8) 31.75 (1-1/4) 19.05 (3/4)
JCH-AP16MSSX
CH-AP04MSSX CH-AP12MSSX
JCH-AP04MSSX JCH-AP12MSSX
Refrigerant Gas Pipe Connection Refrigerant Gas Pipe Connection
for Indoor Unit for Indoor Unit
(2-3/8)
156 (2-3/8)
(4 x φ15.8 (5/8) Flare Nut)
60
60
(6-1/8)
(6-1/8)
156
ࠉ
ࠉ Refrigerant Liquid Pipe
Refrigerant Liquid Pipe D C B A Connection for Indoor Unit L K J I H G F E D C B A
CH-AP08MSSX CH-AP16MSSX
JCH-AP08MSSX JCH-AP16MSSX
Refrigerant Gas Pipe Connection Refrigerant Gas Pipe Connection
for Indoor Unit for Indoor Unit
(2-3/8)
60
(6-1/8)
(6-1/8)
156
P5417025-rev.1 13
14 P5417025-rev.1
Details of changes to the piping size for connection to the CH-Box are shown below.
CH-AP04MSSX
JCH-AP04MSSX Unit: mm (inch)
Piping Connection Required
Field-Supplied Remarks
Size for CH-Box Pipe Size
f19.05 OD25.4 ID19.05 Apply Field-Supplied Reducer
→
(3/4) (1) (3/4) (2 Size Down)
ɸ22.2 OD25.4 ID22.2
→ Apply Field-Supplied Reducer
Low Pressure ɸ25.4 (7/8) (1) (7/8)
Gas Pipe (A) (1) ɸ25.4
- -
(1)
ɸ28.58 OD25.4 ID28.58
→ Apply Field-Supplied Reducer
(1-1/8) (1) (1-1/8)
ɸ12.7 OD22.2 ID12.7 Apply Field-Supplied Reducer
→
(1/2) (7/8) (1/2) (3 Size Down)
f15.88 OD22.2 ID15.88 Apply Field-Supplied Reducer
High/Low →
ɸ22.2 (5/8) (7/8) (5/8) (2 Size Down)
Pressure
(7/8) f19.05 OD22.2 ID19.05
Gas Pipe (B) → Apply Field-Supplied Reducer
(3/4) (7/8) (3/4)
ɸ22.2
- -
(7/8)
f9.52 OD12.7 ID9.52
→ Apply Field-Supplied Reducer
ɸ12.7 (3/8) (1/2) (3/8)
Liquid Pipe (C)
(1/2) ɸ12.7
- -
(1/2)
CH-AP08MSSX
JCH-AP08MSSX Unit: mm (inch)
Piping Connection Required
Field-Supplied Remarks
Size for CH-Box Pipe Size
f19.05 OD28.58 ID19.05 Apply Field-Supplied Reducer
→
(3/4) (1-1/8) (3/4) (3 Size Down)
ɸ22.2 OD28.58 ID22.2 Apply Field-Supplied Reducer
→
(7/8) (1-1/8) (7/8) (2 Size Down)
Low Pressure ɸ28.58 ɸ25.4 OD28.58 ID25.4
→ Apply Field-Supplied Reducer
Gas Pipe (A) (1-1/8) (1) (1-1/8) (1)
ɸ28.58
- -
(1-1/8)
f34.93 OD28.58 ID34.93
→ Apply Field-Supplied Reducer
(1-3/8) (1-1/8) (1-3/8)
f15.88 OD22.2 ID15.88 Apply Field-Supplied Reducer
→
(5/8) (7/8) (5/8) (2 Size Down)
f19.05 OD22.2 ID19.05
→ Apply Field-Supplied Reducer
(3/4) (7/8) (3/4)
High/Low
ɸ22.2 ɸ22.2
Pressure - -
(7/8) (7/8)
Gas Pipe (B)
ɸ25.4 OD22.2 ID25.4
→ Apply Field-Supplied Reducer
(1) (7/8) (1)
ɸ28.58 OD22.2 ID28.58 Apply Field-Supplied Reducer
→
(1-1/8) (7/8) (1-1/8) (2 Size Up)
f9.52 OD12.7 ID9.52
→ Apply Field-Supplied Reducer
(3/8) (1/2) (3/8)
ɸ12.7
- -
ɸ12.7 (1/2)
Liquid Pipe (C)
(1/2) f15.88 OD12.7 ID15.88
→ Apply Field-Supplied Reducer
(5/8) (1/2) (5/8)
f19.05 OD12.7 ID19.05 Apply Field-Supplied Reducer
→
(3/4) (1/2) (3/4) (2 Size Up)
P5417025-rev.1 15
CH-AP12MSSX
JCH-AP12MSSX Unit: mm (inch)
Piping Connection Required
Field-Supplied Remarks
Size for CH-Box Pipe Size
ɸ22.2 OD28.58 ID22.2 Apply Field-Supplied Reducer
→
(7/8) (1-1/8) (7/8) (2 Size Down)
ɸ25.4 OD28.58 ID25.4
→ Apply Field-Supplied Reducer
Low Pressure ɸ28.58 (1) (1-1/8) (1)
Gas Pipe (A) (1-1/8) ɸ28.58
- -
(1-1/8)
f34.93 OD28.58 ID34.93
→ Apply Field-Supplied Reducer
(1-3/8) (1-1/8) (1-3/8)
f19.05 OD25.4 ID19.05 Apply Field-Supplied Reducer
→
(3/4) (1) (3/4) (2 Size Down)
ɸ22.2 OD25.4 ID22.2
High/Low → Apply Field-Supplied Reducer
ɸ25.4 (7/8) (1) (7/8)
Pressure
(1) ɸ25.4
Gas Pipe (B) - -
(1)
ɸ28.58 OD25.4 ID28.58
→ Apply Field-Supplied Reducer
(1-1/8) (1) (1-1/8)
f9.52 OD15.88 ID9.52 Apply Field-Supplied Reducer
→
(3/8) (5/8) (3/8) (2 Size Down)
ɸ12.7 OD15.88 ID12.7
→ Apply Field-Supplied Reducer
ɸ15.88 (1/2) (5/8) (1/2)
Liquid Pipe (C)
(5/8) f15.88
- -
(5/8)
f19.05 OD15.88 ID19.05
→ Apply Field-Supplied Reducer
(3/4) (5/8) (3/4)
CH-AP16MSSX
JCH-AP16MSSX Unit: mm (inch)
Piping Connection Required
Field-Supplied Remarks
Size for CH-Box Pipe Size
ɸ22.2 OD31.75 ID22.2 Apply Field-Supplied Reducer
→
(7/8) (1-1/4) (7/8) (3 Size Down)
ɸ25.4 OD31.75 ID25.4 Apply Field-Supplied Reducer
→
Low Pressure ɸ31.75 (1) (1-1/4) (1) (2 Size Down)
Gas Pipe (A) (1-1/4) ɸ28.58 OD31.75 ID28.58
→ Apply Field-Supplied Reducer
(1-1/8) (1-1/4) (1-1/8)
f31.75
- -
(1-1/4)
f19.05 OD28.58 ID19.05 Apply Field-Supplied Reducer
→
(3/4) (1-1/8) (3/4) (3 Size Down)
ɸ22.2 OD28.58 ID22.2 Apply Field-Supplied Reducer
High/Low →
ɸ28.58 (7/8) (1-1/8) (7/8) (2 Size Down)
Pressure
(1-1/8) ɸ25.4 OD28.58 ID25.4
Gas Pipe (B) → Apply Field-Supplied Reducer
(1) (1-1/8) (1)
ɸ28.58
- -
(1-1/8)
f9.52 OD19.05 ID9.52 Apply Field-Supplied Reducer
→
(3/8) (3/4) (3/8) (3 Size Down)
ɸ12.7 OD19.05 ID12.7 Apply Field-Supplied Reducer
→
ɸ19.05 (1/2) (3/4) (1/2) (2 Size Down)
Liquid Pipe (C)
(3/4) f15.88 OD19.05 ID15.88
→ Apply Field-Supplied Reducer
(5/8) (3/4) (5/8)
f19.05
- -
(3/4)
16 P5417025-rev.1
NOTES:
1. When connecting the Gas Pipe (D) and Liquid Pipe (E), reuse the flare nut attached to the
CH-Box.
2. When the connected indoor unit capacity is 6.3kW or less and the piping length exceeds 15m (49ft.),
use 9.52mm (3/8 inch) for the liquid pipe.
NOTICE
In case the piping connection is not used for the indoor unit side piping connection, it must be
sealed using the closed flare nut originally attached. These flare nuts have been tightened by
torque specifications shown below before shipping. Ensure that they are sealed completely.
P5417025-rev.1 17
NOTICE
1. In case of 8 and 10HP type indoor unit connection:
Up to two 8 and 10HP type indoor units can be connected to the CH-Box within the “Maximum
Total Capacity of All Connected Indoor Units”. Make sure to increase the pipe connection size by
using the appropriate accessory pipe.
2. In case of 8 and 10HP type indoor unit connection:
Only single unit per branch is allowed to be connected.
3. In case the number of indoor unit connection is less and the piping connections are left over:
● Unused piping connections must be sealed using the
closed flare nut originally attached.
It is unnecessary to attach closed-end piping.
Refrigerant leakage is caused by loosened flare nuts. CH-Box
Ensure that they are sealed completely.
Use specified tightening torque according to the table
“Tightening Torque for Flare Nut before shipping”
above.
● Any piping connections can be left over. Example;
4. In case there is plan for additional indoor units in the Use three In case one of the
connection ports. piping connection is
future: unused, ensure the
● Do not plan the piping size for additional indoor closed flare nut originally
attached is secured.
units. Ensure to select the piping again in the future. (For gas and liquid sides)
● Additional indoor units can be connected only after Above figure illustrate the example of CH-AP04MSSX.
the refrigerant is recovered.
(a) After the air-tight leakage test, perform insulation work as shown below.
18 P5417025-rev.1
(b) Insulate gas and liquid pipe separately using the accessory insulation material.
In the event that temperature and humidity levels inside the ceiling exceed 30°C (86oF)/RH, relative
humidity 80%, apply additional insulation materials (approximately 10mm (3/8 inch) thickness) to the
surface of the accessory insulation material to avoid condensation.
(c) Perform cold insulation work by insulating and taping the flare connection and reducer connection.
Also insulate all the refrigerant pipes.
Check that there are no gaps between Check there are no gaps between insulation materials.
the CH-Box and the insulation. If the gaps are occurs, seal the gap with vinyl tape.
CH-Box Side
CH-Box Side
Insulation Insulation Material Insulation
(Field-Supplied) (Attached to the CH-Box) (Field-Supplied)
Clamp
Securely fasten cable clamps (Accessory (7))
and the vinyl tape (Field-Supplied). Securely fasten.
Insulation Work for Gas (High/Low Pressure and Low Pressure)
Pipe of Outdoor Unit Side Insulation Work for Gas Pipe of Indoor Unit Side
Check that there are no gaps between Check that there are no gaps between
the CH-Box and the insulation. the CH-Box and the insulation.
CH-Box Side
Insulation Insulation
(Field-Supplied) (Field-Supplied)
Securely fasten cable clamps Clamp
and the vinyl tape (Field-Supplied). (Accessory (7)) Securely fasten.
Insulation Work for Liquid Pipe of Outdoor Unit Side Insulation Work for Liquid Pipe of Indoor Unit Side
Clamp
(Accessory (7)) Securely fasten.
P5417025-rev.1 19
6. Electrical Wiring
● LOCK ALL ELECTRICAL POWER SUPPLY SWITCHES IN THE OFF POSITION BEFORE INSTALLING
THE UNIT. FAILURE TO DISCONNECT POWER SUPPLY MAY RESULT IN ELECTRICAL SHOCK OR
EVEN DEATH.
● Turn off the main power switch to the CH-Box, the indoor unit and the outdoor unit before electrical
wiring work or a periodical check is performed.
● Insulate electrical wiring, condensate piping, and electrical components from threats posed by
burrowing animals and temperature extremes. Failure to do so can over time, deteriorate system
performance.
● Secure the cables. External forces on the terminals could lead to a fire.
● Be sure to attach the cover so that it fits securely on the electrical box without any gaps.
Secure the cover with screws.
● Tighten screws according to the following torque.
M4: 1.0 to 1.3 N.m (0.7 to 1.0 ft.lbs) (TB1, TB2, TB3, TB4)
● Wrap the field-supplied insulation around the wires, and plug the wiring connection hole with the
seal material to protect the product from any condensate water or insects.
● Tightly secure the wires with the cable clamp inside the CH-Box.
● Do not connect the ground wiring to the gas pipe, condensate pipe or lightening conductor.
Gas pipe: An explosion and ignition may occur when gas leaks.
Water pipe: There is no effect of ground wiring when a hard vinyl pipe is used.
Lightning conductor: The ground electric potential abnormally increases when a lightning
conductor is used.
20 P5417025-rev.1
NOTES:
1) Follow local codes and regulations when selecting field wires.
2) The wire sizes marked with *1 in the above table are selected at the maximum current of the unit according to the
European Standard, EN60 335-1. Use the wires which are not lighter than the ordinary tough rubber sheathed flexible
cord (code designation H05RN-F) or ordinary polychloroprene sheathed flexible cord (code designation H05RN-F).
3) The wire sizes marked with *2 in the above table are selected at the maximum current of the unit according to the
wire, MLFC (Flame Retardant Polyflex Wire) manufactured by Hitachi Cable Ltd., Japan.
4) Use a shielded cable for the transmitting circuit and connect it to ground.
5) In the case that power cables are connected in series, add each unit maximum current and select wires below.
Selection According to EN60 335-1 Selection According to MLFC (at Cable Temperature of 90oC)
Current i (A) Wire Size (mm2) Current i (A) Wire Size (mm2)
i< 6 0.75 i < 15 0.5 *3: In the case that
6 < i < 10 1 15 < i < 19 0.75 current exceeds 63A,
10 < i < 16 1.5 19 < i < 24 1.25 do not connect cables
16 < i < 25 2.5 24 < i < 34 2 in series.
25 < i < 32 4 34 < i < 47 3.5
32 < i < 40 6 47 < i < 63 5.5
40 < i < 63 10 63 < i < 78 8
63 < i *3 78 < i < 113 14
113 < i < 148 22
148 < i < 179 30
P5417025-rev.1 21
The following figure shows an example of electrical wiring around the CH-Boxes.
Outdoor Unit
TB2
H-LINK O.U.-O.U.
1 2 3 4 Connect
communication cable
from outdoor unit
to the outdoor
terminal block (TB2)
in CH-Box.
NOTES:
1. Do not apply excessive voltage to the communication cable DC5V (non-polarity) between the outdoor
unit and the CH-Box, between the CH-Box and the indoor unit or between CH-Boxes.
2. Use 2-Conductor shielded communication cable for the communication cable. (Do not use 3-Conductor
cable or over.)
3. Connect the communication cable for the outdoor unit to terminals “1” and “2” on TB2 in the CH-Box.
4. Connect the communication cable for the indoor unit exclusively for cooling operation to the terminal “1”
and “2” on TB2 in the CH-Box.
5. For a CH-Box in the same refrigerant cycle, an electrical power supply can be supplied by one main
switch.
6. Do not connect the power supply line (220-240V/220V/230V) to the terminal block for transmission line.
7. Connect the ground wiring for the outdoor/indoor units and CH-Box. When ground resistance is less
than 100 ohms, ground wiring work should be performed by the qualified electrician.
8. Do not run the communication cables along with power supply wirings in the CH-Box.
Separate communication cables from the power supply wirings.
22 P5417025-rev.1
Terminal Block
PCN1 PCN2 PCN1 PCN2 PCN1 PCN2
CN1
CN1
LED11 LED11 LED11
LED2
LED2
LED2
LED12 LED12 LED12
LED1
LED1
LED1
LED13 LED13 LED13
CN2
CN2
CN2
LED14 LED14 LED14
LED15 LED4 LED5 LED6 LED7 LED15 LED4 LED5 LED6 LED7 LED15 LED4 LED5 LED6 LED7
CN3
CN3
CN3
TP DSW1 DSW2 DSW3 TP DSW1 DSW2 DSW3 TP DSW1 DSW2 DSW3
ON ON ON ON ON ON ON ON ON
LED16 1 2 3 4 5 6 1 2 3 4 1 2
LED16 1 2 3 4 5 6 1 2 3 4 1 2
LED16 1 2 3 4 5 6 1 2 3 4 1 2
TB2
CN11 CN11 CN11
LED17 LED17 LED17
LED3
LED3
LED3
Wire Clip
CN4
CN4
CN4
DSW5
DSW6
DSW7
DSW8
DSW5
DSW6
DSW7
DSW8
DSW5
DSW6
DSW7
DSW8
ON ON ON ON ON ON ON ON ON ON ON ON
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
(Use to
CN12 CN12 CN12
CN5
CN5
CN5
ON ON ON
DSW4
DSW4
DSW4
1 2 1 2 1 2
route wiring)
CN6
CN6
CN6
TB3 TB4 TB3 TB4 TB3 TB4
CN9 CN10 CN9 CN10 CN9 CN10
1 2 3 4 1 2 3 4 1 2 3 4
A B C D E F G H I J K L
NOTE:
The accessory numbers are listed in Table 4.1.
Figure 6.1 Electrical Wiring Connection
P5417025-rev.1 23
Connection Ports
for Indoor Unit
A B C D M N O P
Table 6.2 Cross reference table of DIP switch settings and connection ports for indoor unit.
CH-AP16MSSX
Models CH-AP12MSSX JCH-AP16MSSX
PCB1 PCB4
CH-AP04MSSX CH-AP08MSSX JCH-AP12MSSX
DSW1 DSW1
JCH-AP04MSSX JCH-AP08MSSX
DSW2 DSW2
DSW3 DSW3
Connection ports for indoor unit A B C D E F G H I J K L M N O P
DSW5 DSW6 DSW5 DSW6 PCB No. PCB1 PCB2 PCB3 PCB4
DSW4 DSW7 DSW4 DSW7 DSW2 Pin No. 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
DSW8 DSW8 DSW5~8 DSW DSW DSW DSW DSW DSW DSW DSW DSW DSW DSW DSW DSW DSW DSW DSW
5 6 7 8 5 6 7 8 5 6 7 8 5 6 7 8
DSW4~8 Fuse Recover
In the case of applying high voltage to terminals of TB2, TB3 or TB4, the 0.5A
DSW1 DSW2 Connection Port Setting DSW3 fuse on the PCB is open. In such a case, first reconnect the wiring correctly
This setting is required. to the terminal block, and then set the No.1 pin to ON.
No setting is required. When the connection port is not used, turn ON No setting is required. DSW4 (for TB2) DSW5~8 (for TB3 and TB4)
the applicable pin shown in the table 6.2.
Factory Setting Fuse Recover Factory Setting Fuse Recover
ON ON (Example) ON
When connection port "D" is ON ON ON ON
123456 1234 not used, turn ON 12 12 12 12 12
DSW2-No.4 pin on PCB1.
NOTE
The “n” mark indicates the position of DIP switches. Figures show setting before shipment.
NOTICE
All indoor and outdoor units must be shut down prior to attempting to make DIP Switch adjustments,
otherwise, the settings will not take effect.
24 P5417025-rev.1
7. Test Run
NOTICE
Refrigerant piping and connecting wires should be connected to the same refrigerant cycle system.
If they are connected to the dissimilar refrigerant cycle systems, a malfunction may occur.
250
(Countermeasures
Not Needed)
150
50
Perform a test run according to the “Installation and Maintenance Manual” of the outdoor unit.
● Do not operate the system until all the check points are cleared.
(A) Check to ensure that the electrical resistance is more than 1 megohm by measuring the
resistance between ground and the terminal block in the electrical box. If not, do not operate
the system until the electrical leakage is found and repaired.
(B) Check to ensure that the stop valves of the outdoor unit are fully opened, and then start the
system.
(C) Apply power to the outdoor unit(s) at least 12 hours prior to operation of the system for
preheating of the compressor oil.
● Pay attention to the following items while the system is running.
(A) Do not touch any of the parts by hand at the discharge gas side, since the compressor
chamber and the pipes at the discharge side are heated higher than 90°C (194°F).
P5417025-rev.1 25
26 P5417025-rev.1