Professional Documents
Culture Documents
100
90
80 Synthetic Esters
70
60
50
40
Biodegradation (%)
30
20
Mineral Oil
10
Silicone Liquid
0
0 5 10 15 20 25 30
Time (Days)
90
80
70
60
50
40
Synthetic Ester
30
0
0 100 200 300 400 500 600 700 800 900 1000
Moisture Content (ppm)
10/26/2012 10
«0HVVDJH%R[( Arial, Font size 18 Bold)
Comparison of Transformers filled with K-class fluids v/s Dry
Type Transformers- Installation Analysis -2
10/26/2012 11
«0HVVDJH%R[( Arial, Font size 18 Bold)
Comparison of Transformers filled with K-class fluids v/s Dry
Type Transformers- Fire Safety -1
Effect of external fire : it will take much longer for a transformer filled
with K-class fluids to participate in the fire. The fluid is contained inside
the Transformer tank and will not be exposed to the flames unless the
tank bursts. The design of the tank is such that it can withstand internal
pressure.
Dry type transformers are more susceptible to external fire.
Internal fire: The flash point for K-class fluids is 275degC and the fire
point is 320 deg C. K-ĐůĂƐƐĨůƵŝĚƐŚĂǀĞďĞĞŶƉƌŽǀĞŶƚŽ͞ƐĞůĨĞdžƚŝŶŐƵŝƐŚ͘͟
This ensures that it does not contribute in any way to spreading of the
fire.
-Data indicates that there are no fires with K class fluids.
14
«0HVVDJH%R[( Arial, Font size 18 Bold)
WƌŽŽĨƐ͙͘͘>ŽƐƐ>ĞǀĞůĚĂƚĂ
10/26/2012 15
«0HVVDJH%R[( Arial, Font size 18 Bold)
Retrofilling Mineral Oil Filled Transformers with K Class Synthetic Esters
Draining of Mineral Oil ʹMineral Oil was pumped out of the transformer into a
container, the oil was completely drained and care was taken to remove as much
oil as possible. The core assembly was taken out and oil was allowed to drip. The
conservator tank and main tank were also cleaned properly. The core coil
assembly was rinsed with Synthetic ester and left for two hours to allow oil to be
released from the windings.
Rinsing-The core coil assembly was once again rinsed, the conservator
tank was flushed with the Synthetic Ester. The tank and radiator were
rinsed with warm oil thoroughly.
«0HVVDJH%R[( Arial, Font size 18 Bold)
Retrofilling Mineral Oil Filled Transformers with K Class Synthetic Esters
Preparing for refilling-All the gaskets, oil seals, bushings and silica gel
breather were replaced with new ones.
Filling with Synthetic Ester -The core assembly was placed inside the tank.
The transformer was filled with the Synthetic ester based oil through drain
valve in the bottom of the tank with a dedicated pump. The LV bushing
connections were done and the main tank covert was closed.
Max. Temperature rise above Ambient 9.5϶ΛϮϮйůŽĂĚŝŶŐ Max. Temperature rise above Ambient 4.4϶ΛϰйůŽĂĚŝŶŐ
Thermal profile on DT tank & Radiator observed ʹ Normal Thermal profile on DT tank & Radiator observed ʹ Normal