You are on page 1of 34

10th IndiaDoble Power Forum, 2012

Health monitoring / life enhancement of


power transformer - the role of
transformer accessories

Ramakrishnan Nagarajan

10th IndiaDoble Power Forum, 1


2012, Vadodara, Gujarat, INDIA
POWER TRANSFORMER
VITAL FEW ACCESSORIES
• Vital few accessories
– Bushings
– OLTC – The main topic of this paper
– Transformer oil
• Thermal degradation
• Root cause for many other parts failure
>>Cellulose failure determines life of transformer
• Oxygen concentration in transformer oil

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 2


OLTC TECHNOLOGY
• Recent design improvements aimed at
reliability enhancement
– Vacuum proof sealing of upper part
– Transit damage – a very rare case
– OLTC hanging from top cover of transformer
– Cantilever effect amplifies the vibration
– Poor road conditions and handling facilities
– Suggested use of temporary support
– Fiberglass terminal strips

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 3


HELIUM LEAK DETECTOR

Photo

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 4


OLTC SINGLE POLE
TOP COVER

UPPER PART LINE TERMINAL

SELECTOR
TERMINAL STRIP

TAP TERMINAL
TRANSITION
RESISTANCE
DIVERTER
SWITCH NEUTRAL TERMINAL

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 5


PERFORMANCE
REQUIREMENTS
• No discontinuity during switching
• Various interlocks
• Contact resistance measurements
• Mechanical endurance tests
• Tightness tests
• Electrical routine tests
• Others
• Intank OLTC application demands highest
reliability standard
– A single loose joint is disastrous
– So computerised test system installed
10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 6
COMPUTERISED TEST
SYSTEM
• All routine tests included
• No human error
• Computerised T.C. Photo
• Easy traceability
• For all OLTC models
• Editable for new models
• Single deviation stops test

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 7


ON-LINE FILTER
• CONTROL PANEL FILTER CABIN
Auto/
PLC manual
switch

Pump
Panel on/ off
lock switch

On/off Change
switch filter
with olr alarm

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 8


VACUUM OLTC
• Validation for application inside transformer
environment for anticipated long life of diverter
switch:
– Non operation for long periods to very frequent
operations and seasonal load variations
– Harmonics
– Errors in commissioning
• Fool proof system to prevent operation in the
event of vacuum failure causing explosion

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 9


CASE STUDY 1: EARLY
FAILURES
• Drive mechanism
– coupled and decoupled at
• OLTC manufacturer’s end
• Transformer manufacturer’s end
• Utility during commissioning
• Errors do occur due to unavoidable
triplication of coupling process needing
trained and skilled manpower

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 10


CASE STUDY 1:
COMMON ERRORS
• Leakage from OLTC top cover
– Top cover bolts found loose
• Drive mechanism coupling loose
• Interconnection of electrical wires between
DM box and RTCC wrong
• Wrong phase sequence
• Wiring loose
• DM box door kept open & rusty parts
10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 11
CASE STUDY 1 :
PREVENTIVE ACTIONS
• Top cover bolts kept loose
• Prominent caution label
• Drive mechanism
• Selector - Improved packaging

Photo

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 12


MAINTENANCE
SERVICE QUALITY
• Objectives
– Immediately restore power
– Prevent outage
– Predict probable failures through health
monitoring
• Requires special health monitoring device
• Needs data interpretation
– Restore the transformer to its original condition and
enhance the life
• See case study 5

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 13


OLTC – PREVENTIVE
MAINTENANCE
• Mostly time bound
• Planning has to be site specific
– Consider age of transformer
– Number of trained staff available
– Transformer loading pattern
– Number of OLTC operations / day
– OLTC type and model
– Historical data

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 14


OLTC HEALTH
CLASSIFY SYMPTOMS
• Considering parts affected
– Mechanical
– Electrical
– Dielectric
• Considering failure mode
– Errors - immediately after commissioning
– Ageing - after long periods of service
• Takes long time for symptom to appear
• So prevent failure through health monitoring
– Cause of failure not originated from OLTC

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 15


CASE STUDY 2: OLTC
HEALTH MONITORING
• Transformer winding resistance
– Measured at site using special equipment at
low DC current
– Linear tap winding

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 16


TRANSFORMER
WINDING RESISTANCE
• Reversing tap winding

• Dr.Paul G Slade seminars at New Delhi


& at Holme USA
10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 17
DGA DATA
INTERPRETATION
• DGA – most popular method for transformer
health monitoring
• More than 400 laboratories
– across the world
Photo
• Data interpretation
– Use multiple techniques
– IEC 60599 & Dovel’s triangle
– Validate conclusion with infrared thermography
– Training to utilities
– Case study 3: Carbon deposition all around selector
contacts. Customer believes OLTC has some defect

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 18


CASE STUDY 3:
OLTC & DGA
• OLTC is healthy:
– when contact force measured at site
is acceptable
– electrical joints are tight Photo
– C2H2 concentration is within limit
– OLTC operations normal
• DGA interpretation oil overheating
• Carbon due to decomposition of oil under
thermal fault conditions
– resultant carbon radicals get preferentially deposited
on HV contacts
10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 19
Other diagnostic tools
• Infrared thermography
– Need thermal imaging camera
– Infrared thermometer
– Can locate a fault
– Easy to operate
– Can locate hot spot
– Validating DGA conclusion
• Motor current monitoring
– Equipment with higher sampling rate
– Refer next section

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 20


VIBRO-ACCOUSTIC
• Most suitable for OLTC
– Stable OLTC gives stable vibro-accoustic
pattern
– Non-intrusive technique
• both on line and off line
– Combines with motor current trace
• Strongest as it can detect almost all failure modes
• Acts as stethoscope
• Specialized software to develop envelope from raw
data and superimpose envelopes for comparison

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 21


VIBRO-ACCOUSTICS

RAW DATA

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 22


VIBRO-ACCOUSTICS
• Envelope

Demo

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 23


VIBRO-ACCOUSTICS
• Comparison of waves by superposition

Demo

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 24


CASE STUDY 4 -
VIBRO-ACOUSTIC
• Demo

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 25


TRANSFORMER
DEHYDRATOR
• Removes moisture from oil and paper
• Patented technologies
– Hydraulic piston
– Bubble bed
• No adverse impact on oil quality
– No heating involved

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 26


Case study 5
HEALTH ENHANCEMENT
• TRANSFORMER DATA

TABLE

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 27


DEHYDRATION
• Chart

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 28


LABORATORY
REPORT

Table

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 29


PERFORMANCE
REPORT

Table

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 30


ANALYSIS

Chart

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 31


DEGASING TREND

Chart

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 32


25/08/2012
DGA REPORT

Table

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 33


THANK YOU
????????

10th IndiaDoble Power Forum, 2012, Vadodara, Gujarat, INDIA 34

You might also like