BOILER SAFETY

BOILER STACKS AND CHIMNEYS


Recovering Boiler Systems After a Flood
HISTORY
CAUSES OF BOILER ACCIDENTS
BOILER WATER TREATMENT
WHY BOILER INSPECTIONS?
PROGRAM RESPONSIBILITIES
State Deputy Inspectors

Any boiler using a combustible fuel source requires a stack or chimney. The stack or chimney aids combustion
in natural draft boilers by helping to ensure a steady supply of combustion air which mixes with the fuel. The
primary purpose of a stack or chimney, though, is to exhaust the products of combustion at some elevation
above the boiler which aids the environmental conditions in the immediate area around the boiler. The height
of the stack or chimney is determined by several factors including:

• height of the nearest building or roof line

• prevailing wind direction

• height of surrounding manmade structures or natural landforms

• location of air intake vents


SAFETY
• type of boiler draft (natural or fan assisted)
Causes of Boiler Accidents
• type of fuel Be prepared

• local and/or national requirements

Stacks and chimneys should be designed by a competent engineer who will address all of the necessary
RECOVERY
factors for the speci�c application, including any jurisdictional (local, state or provincial, and national)
requirements.
Recovering Boiler Systems After
A Flood
Stacks and chimneys should be inspected periodically by a reputable and competent person familiar with stack Crucial Steps

and chimney design and construction. Jurisdictional requirements may specify who is allowed to make these
inspections. Stacks and chimneys deteriorate with age and are very susceptible to seismic or wind damage due
to their height.

During a stack or chimney inspection, the following items, as a minimum, should be observed:

• the stack/chimney base or foundation


For more information about
• external supports or guy wires, if used
obtaining a TDLR license or
• connection to the breeching or boiler renewing a TDLR license that
expired while serving on active
• condition of bricks and mortar joints in masonry stacks/chimneys duty, please go to the Military
Outreach page.
• condition of metal and joints in metallic stacks/chimneys

• condition of cap, cone, or spark arrestor, if used, at the top of the stack/chimney

• the height and diameter of the stack/chimney based upon the original design
For more information about the Boiler Safety
• vertical orientation (is it plumb?) program, contact customer service.

• condition of brick or metallic liner in masonry stacks/chimneys Texas Department of Licensing and
Regulation
• condition of interior metal and joints in a double-wall metallic stack/chimney Boiler Program
P.O. Box 12157
• the internal passageway (no obstructions or blockage)
Austin, Texas 78711

The above list is not intended to be exhaustive, but is provided as a basic guide. (800) 722-7843 (In Texas Only)
(512) 539-5716

1 of 5 9/3/2023, 1:38 AM
Boiler Information https://www.tdlr.texas.gov/boilers/blrinfo.htm

If repairs to a stack or chimney are required, the owner should be directed to contact the authority having (512) 539-5687 (fax)
jurisdiction over the stack/chimney to determine if a permit or other documentation is necessary. This
jurisdictional authority may be local (city), state or provincial, or national. Two examples of this are:

• the stack of a small gas-�red boiler may be within the jurisdiction of the city building or mechanical
inspection department, or

• the stack of a large sawdust-�red industrial boiler may be within the jurisdiction of the state or provincial
environmental protection department.

Floods, whether caused by nature or by structural or mechanical failures, can produce deaths, injuries, and
severe property damage. The following information is provided to assist in the recovery of boiler systems
a�ected by �ooding to help mitigate further risks to public safety and property damage.

• Safety of the personnel performing inspections and repairs is the highest priority. Because �ood waters
contain many hazardous chemicals and bacteria, personnel safety procedures should be developed and
enforced.

• All utilities in the boiler room should be turned o� until inspection and necessary repairs of the individual
systems allow reactivation.

• A careful visual inspection of the entire boiler system should be made, both internally and externally, with
notations of obvious problems and any special equipment or personnel needed to facilitate repairs.

• Keep in mind that some equipment may only be repaired by the original manufacturer or its licensed agents
in order to maintain warranties and/or certi�cation.

• The boiler setting or foundation should be examined closely to determine if it has been weakened or
undermined. Any movement of the boiler or building will have an adverse e�ect on piping and other
equipment connected to both the boiler and building structure.

• Waterlogged insulation will hasten external corrosion of boilers and pipes. If removal is deemed necessary,
remember that asbestos is still present in many boiler rooms and requires handling by specially licensed
personnel. If the insulation is left in place and the boiler is �red before thoroughly drying, steam can be
generated within the insulation layers, creating the potential for explosive damage to the external lagging.

• Refractory and �re brick should be allowed to completely dry and checked for deterioration or loosening.

• Feedwater and condensate return systems should be thoroughly cleaned of any mud, silt, or debris. After the
boiler is put back in operation, the water quality should be checked often for contamination of any kind.

• Pressure relief devices should be checked for corrosion or any damage that would cause binding and failure
to operate. Only quali�ed personnel should perform disassembly or repair of a pressure relief device. Some
jurisdictions require this work to be performed by a company holding the National Board "VR" symbol stamp.
The outlet and discharge line of the pressure-relieving device should be inspected for blockage.

• All drains and blow-o� lines should be inspected to ensure there is no blockage by debris.

• Electric/electronic controls should be evaluated for replacement or repair as needed. Flame safeguard
controls, ignition transformers, and safety shuto� valves on the fuel system that have the potential for causing
furnace explosions should be replaced. Other fuel system components should be drained and cleaned or
replaced as necessary. All work performed on the fuel system and safety devices must comply with
jurisdictional requirements.

• All electric motors and wiring should be inspected closely to determine if repair or replacement is necessary.
All electrical work must comply with jurisdictional requirements.

• Check to make sure air inlets are clear and chimneys or stacks are open.

These items are not intended to be all-inclusive, as boiler systems and equipment vary in design and
operation. However, this list could be used as an outline in developing individual inspection and repair
guidelines to �t many systems a�ected by �ooding.

The Texas Boiler Law, Chapter 755 of the Health and Safety Code, was enacted on June 3, 1937, after a fatal
boiler accident.

For many years the program was a part of the agency then known as The Bureau of Labor Statistics. Later, the
agency name was changed to the Texas Department of Labor and Standards. In 1989, the name was changed
to and is currently named The Texas Department of Licensing and Regulation, where the Boiler Program
continues to function and work with an ever changing commercial and industrial environment.

Boiler systems are designed for safety and e�ciency. The boiler operator is the key to safe boiler operations.

2 of 5 9/3/2023, 1:38 AM
Boiler Information https://www.tdlr.texas.gov/boilers/blrinfo.htm

Having knowledge about boiler systems and maintenance can ensure years of safe, reliable service.

History has shown that without proper operation and maintenance, boiler conditions and safety deteriorate
causing potential hazards due to neglect and misunderstanding. Routine maintenance is well within the ability
of most boiler operators. Boiler tune up and repairs, however, are best left to trained professionals.
Understanding when to turn to quali�ed professionals for assistance is one of the operator’s responsibilities
and can save time and money. Some of the areas where trained professionals are needed are:

• Leaking safety and or safety relief valves

• Feed water to boiler

• Steam leaks (steam systems)

• High stack temperatures (excess of 350 F)

• Insu�cient heat for building

• Condensate dripping down stack or out the front of the boiler

• Constantly resetting of controllers and safety devices

Boiler accidents can occur when the boiler is allowed to operate without adequate water in the boiler. Proper
functioning low water cuto�s are essential to prevent these types of accidents. Boiler damage can run from
severe buckling and deforming of the boiler to complete meltdown or potential boiler explosions.

Another type of boiler accident and the most lethal is excessive pressure. These accidents occur when the
boiler can no longer contain the excessive pressure allowed to build in the boiler. Excessive pressure
accidents, even in small boilers, have been known to completely destroy a building.

Fuel related accidents usually occur when there is a failure to purge combustible gases from the �rebox before
ignition is attempted. Leaking fuel valves can also be the cause of these accidents. If the operator notices any
gas odor, the boiler should be shut down and the fuel supplier noti�ed immediately.

Boiler system (steam/water) loses water through steam and water leaks. Additional water called “make-up
water” is added to the boiler to replace these losses. The amount of make-up water and the level of naturally
occurring impurities in water will determine the type of water treatment required. Boiler heating systems that
have very few leaks will require a simple water treatment program. Your boiler water treatment professional
can assist you in developing an e�ective water treatment program.

All water contains dissolved minerals and these minerals, if allowed to reach high enough levels in the boiler
water, will come out of solutions and form as a hard shell on the hot surfaces of the boiler. This hard shell is
called “scale” and is often found on the outside of the �re tubes or the inside of water tubes. Scale insulates
the heating surfaces reducing the ability of the �re tubes to transfer heat from the hot combustion to the
boiler water. High stack temperatures or ruptured tubes are common problems related to scale build up.
Boiler water also contains dissolved gases such as oxygen or carbon dioxide. These gases, in the presence of
water and metal, can cause corrosion. Corrosion eats away the metal a�ecting the durability of the boiler.

Much like your automobile, furnace, or air conditioner, a boiler requires an ongoing, routine maintenance and
inspection program. Well trained maintenance personnel, boiler operators and boiler inspectors are important
components to the safe operation of a boiler.

Routine boiler inspections are required by the Texas Boiler Law and Rules. The State and Authorized
Inspection Agencies provide trained personnel throughout the state to perform the required inspections to be
in compliance with the Texas Boiler Law and Rules.

A boiler should be examined internally and externally to determine the operating condition of the boiler and
to ascertain the true condition of the boiler.

Boiler inspectors examine the structural integrity of the boiler along with the associated safety devices
attached to the boiler. These devices must remain in good operating condition for the continued safe
operation of the boiler.

The loss of water (low water), furnace explosion, over pressure and excessive temperature are the principal
causes for boiler accidents and are primarily the direct result of the missing or inoperative controls and safety
devices, lack of maintenance, untrained operators, and complacency. These are some reasons why boiler
inspections are so important and what could result if boilers are left uninspected.

The Texas Boiler Law requires that all boilers operating in the State of Texas be registered with the
department and, depending on the use, be inspected annually, biennially, or triennially. Additionally,

3 of 5 9/3/2023, 1:38 AM
Boiler Information https://www.tdlr.texas.gov/boilers/blrinfo.htm

department representatives review quality control systems for issuance of Certi�cates of Authorization to
boiler and pressure vessel manufacturers, repair organizations, and state owner/user organizations.

Throughout the State of Texas there are approximately 55,000 registered boilers. Our records indicate that
approximately 60 percent of these registered boilers are under inspection agreements and are inspected by
Authorized Inspectors employed by an Authorized Inspection Agency; and the remaining 40 percent of boilers
are inspected by State Deputy Inspectors.

The following are the �ve (5) regional areas of responsibility for State Deputy Inspectors, and three (3) of the
major regions (91, 93 & 94) are further subdivided between State Deputy Inspectors by zip codes and/or
counties. To �nd out which State Deputy Inspector conducts inspections in your area please contact the
Department for further assistance at (800) 722-7843 or (512) 539-5716 or by email.

• Forrest Andrews (Southwest)


(214) 335-5855
Forrest.Andrews@tdlr.texas.gov

• Vacant (Southeast)
(214) 868-5883

• Jim Jake Templin (Northeast)


(972) 623-7154
Jim.Templin@tdlr.texas.gov

• Dennis Summers
(214) 870-6651
Dennis.Summers@tdlr.texas.gov

• Timothy Adams (East Texas)


(903) 376-4975
Timothy.Adams@tdlr.texas.gov

• Chrys Gri�ng (Lubbock)


(806) 239-3601
Chrys.Gri�ng@tdlr.texas.gov

• Lee Garde
(726) 223-1474
Lee.Garde@tdlr.texas.gov

• Tim Larrew (Austin)


(512) 636-4923
Timothy.Larrew@tdlr.texas.gov

• Terry Hewitt
(361) 800-5643
Terry.Hewitt@tdlr.texas.gov

• Felix Okedara (Northwest)


(832) 367-7755
Felix.Okedara@tdlr.texas.gov

• John Leos (Southwest)


(832) 453-3115
John.Leos@tdlr.texas.gov

• Sal Guzman (Southeast)


(832) 470-4428
Sal.Guzman@tdlr.texas.gov

• BJ Lang (Northeast)
(832) 840-1328

4 of 5 9/3/2023, 1:38 AM
Boiler Information https://www.tdlr.texas.gov/boilers/blrinfo.htm

BJ.Lang@tdlr.texas.gov

• Jay Kim
(915) 861-6519
Jay.Kim@tdlr.texas.gov

For more information about boilers contact:

Texas Department of Licensing and Regulation


Boiler Program
P.O. Box 12157
Austin, Texas 78711

(800) 722-7843 (In Texas Only)


(512) 539-5716
(512) 539-5687 (fax)

Contact customer service

Privacy and Security Policy Compact with Texans Texas Homeland Security
Accessibility Report Suspected Fraud, Waste, or Abuse Texas Transparency
Open Records Policy Texas.gov Texas Veterans Portal
Link Policy Statewide Search Contact TDLR

5 of 5 9/3/2023, 1:38 AM

You might also like