REINFORCEMENT STEEL DESIGN
FOR PANEL – RSW WALL
Considering the connector position for various heights, span has been considered as per design.
Considering the connector position for various heights, span has been considered as per design.
Design Factored width of Reinforcement
Sr. Depth of Effective
No.
Height (in Moment at
Panel Depth
the panel provided
meter) end considered (sq.mm/m)
457 (8 dia. 110
1 12.000 21.833 180 120 67.233 500 35 1000 441.46 c/c)
From above table, it has been clearly derived that for the height above 8 meter, panel reinforcement required is 8 mm dia @110 mm c/cin main direction and 8
mm dia @ 150 c/c in other direction and for height upto 8m, panel reinforcement required is 8 mm dia @ 150 mm in both direction.
600 mm
800 mm
mm
200 BM Diagram
Note:For panels with three connector, there is an additional reinforcement, in between this
two connectors and the required strength of geogrid is lesser than the maximum (250 Kn/m)
considered here for calculations. Hence the case of 600mm cantilever span and cantilever
moment is the worst case in all the types of panels.
Sample calculation:
Maximum Bending Moment is 21.833 KN-m/m
BM = 0.138 x σck x b x d2
21.833 1 10
. =
1000 0.138 35
Hence Ok.
Panel Steel required,
Hence OK.
Considering higher factor of safety for the stresses, finally, reinforcements for panels are provided as 8mm
diameter @ 120mm c/c in main direction and 8mm diameter @ 150mm c/c in other direction. Please find
below the reinforcement layout for panel:
Maximum tension in each grid 300mm wide = 43.350/ 1.5 = 28.90kN (For 250 kN/m Tensile strength Geogrid
of 300mm width); where in 1.5 is to consider actual load on connector.
Hence, OK.
Hence, OK.
C) Development Length for connector:
∅
=
Where,
bd= Design bond stress = 1.7(M35) (as per Table 26.2.1.1 of IS: 456)
Therefore, bd= 1.7 N/mm2
Therefore = = 143.736N/mm2
.
.
= = 388.202 mm
.
Provided full length of zig zag connection, hence the total resistance length is much more than above.
Note:If we considered for single leg, then the length of each leg is to be increased by 100mm. In that case total
length of connector rod is increased to 200mm, for maximum strength of grid, otherwise above dimension is
OK.
CHECK FOR PANEL REINFORCEMENT AT THE TIME OF LIFTING
Considering the lifting hook position, span has been considered as below:
BM = 0.138 x σck x b x d2
Hence Ok.
500 At
0.54 x 106 0.87 500 At (120 )
11000
At < 10 mm2
Provided 8 T @ 150 mm c/c – both ways = 350mm2/m, which is greater than required.
Hence OK.
=======