You are on page 1of 10

P1: JsY

ASCE003-13.tex ASCE003/SIE-v1.cls October 10, 2005 18:0

Chapter 13
SEISMIC DESIGN REQUIREMENTS FOR NONSTRUCTURAL COMPONENTS

13.1 GENERAL 13.1.5 Applicability of Nonstructural Component Require-


ments. Where the weight of a nonstructural component is greater
13.1.1 Scope. This chapter establishes minimum design criteria
than or equal to 25 percent of the effective seismic weight, W ,
for nonstructural components that are permanently attached to
defined in Section 12.7.2, the component shall be classified as a
structures and for their supports and attachments.
nonbuilding structure and shall be designed in accordance with
13.1.2 Seismic Design Category. For the purposes of this chap- Section 15.3.2.
ter, nonstructural components shall be assigned to the same seis- Nonbuilding structures (including storage racks and tanks) that
mic design category as the structure that they occupy or to which are supported by other structures shall be designed in accordance
they are attached. with Chapter 15. Where Section 15.3 requires that seismic forces
be determined in accordance with Chapter 13 and values for R p
13.1.3 Component Importance Factor. All components shall are not provided in Table 13.5-1 or 13.6-1, R p shall be taken as
be assigned a component importance factor as indicated in this equal to the value of R listed in Section 15. The value of a p shall
section. The component importance factor, I p , shall be taken as be determined in accordance with footnote a of Table 13.5-1 or
1.5 if any of the following conditions apply: 13.6-1.
1. The component is required to function for life-safety pur-
poses after an earthquake, including fire protection sprinkler 13.1.6 Reference Documents. Where a reference document
systems. provides a basis for the earthquake-resistant design of a particular
type of system or component, that document is permitted to be
2. The component contains hazardous materials. used, subject to the approval of the authority having jurisdiction
3. The component is in or attached to an Occupancy Category and the following conditions:
IV structure and it is needed for continued operation of the
facility or its failure could impair the continued operation a. The design earthquake forces shall not be less than those de-
of the facility. termined in accordance with Section 13.3.1.
b. Each component’s seismic interactions with all other con-
All other components shall be assigned a component importance nected components and with the supporting structure shall be
factor, I p , equal to 1.0. accounted for in the design. The component shall accommo-
date drifts, deflections, and relative displacements determined
13.1.4 Exemptions. The following nonstructural components
in accordance with the applicable seismic requirements of this
are exempt from the requirements of this section:
standard.
1. Architectural components in Seismic Design Category B
other than parapets supported by bearing walls or shear walls 13.1.7 Reference Documents Using Allowable Stress Design.
provided that the component importance factor, I p , is equal Where a reference document provides a basis for the earthquake-
to 1.0. resistant design of a particular type of system or component, and
the same reference document defines acceptance criteria in terms
2. Mechanical and electrical components in Seismic Design of allowable stresses rather than strengths, that reference docu-
Category B. ment is permitted to be used. The allowable stress load combina-
3. Mechanical and electrical components in Seismic Design tion shall consider dead, live, operating, and earthquake loads in
Category C provided that the component importance factor, addition to those in the reference document. The earthquake loads
I p , is equal to 1.0. determined in accordance with Section 13.3.1 shall be multiplied
by a factor of 0.7. The allowable stress design load combina-
4. Mechanical and electrical components in Seismic Design tions of Section 2.4 need not be used. The component or system
Categories D, E, and F where the component importance shall also accommodate the relative displacements specified in
factor, I p , is equal to 1.0 and either: Section 13.3.2.
a. Flexible connections between the components and asso-
ciated ductwork, piping, and conduit are provided.
b. Components are mounted at 4 ft (1.22 m) or less above 13.2 GENERAL DESIGN REQUIREMENTS
a floor level and weigh 400 lb (1780 N) or less.
13.2.1 Applicable Requirements for Architectural, Mechani-
5. Mechanical and electrical components in Seismic Design cal, and Electrical Components, Supports, and Attachments.
Categories D, E, and F where the component importance Architectural, mechanical, and electrical components, supports,
factor, I p , is equal to 1.0 and and attachments shall comply with the sections referenced in
a. Flexible connections between the components and asso- Table 13.2-1. These requirements shall be satisfied by one of the
ciated ductwork, piping, and conduit are provided. following methods:
b. The components weigh 20 lb (89 N) or less or, for dis- 1. Project-specific design and documentation prepared and
tribution systems, weighing 5 lb/ft (73 N/m) or less. submitted by a registered design professional.

Minimum Design Loads for Buildings and Other Structures 143


P1: JsY
ASCE003-13.tex ASCE003/SIE-v1.cls October 10, 2005 18:0

TABLE 13.2-1 APPLICABLE REQUIREMENTS FOR ARCHITECTURAL, MECHANICAL, AND ELECTRICAL COMPONENTS:
SUPPORTS AND ATTACHMENTS
Nonstructural Element General Design Force and Displacement Attachment Requirements Architectural Component Mechanical and Electrical
(i.e., Component, Support, Requirements Section 13.2 Requirements Section 13.3 Section 13.4 Requirements Section 13.5 Component Requirements
Attachment) Section 13.6

Architectural Components X X X X
and Supports and
Attachments for
Architectural Components
Mechanical and Electrical X X X X
Components with I p > 1
Supports and Attachments X X X X
for Mechanical and
Electrical Components

2. Submittal of the manufacturer’s certification that the com- 13.2.6 Experience Data Alternative for Seismic Capacity
ponent is seismically qualified by Determination. As an alternative to the analytical requirements
a. Analysis. of Sections 13.2 through 13.6, use of experience data shall be
deemed as an acceptable method to determine the seismic capac-
b. Testing in accordance with the alternative set forth in
ity of components and their supports and attachments. Seismic
Section 13.2.5.
qualification by experience data based upon nationally recognized
c. Experience data in accordance with the alternative set procedures acceptable to the authority having jurisdiction shall
forth in Section 13.2.6. be deemed to satisfy the design and evaluation requirements pro-
vided that the substantiated seismic capacities equal or exceed the
13.2.2 Special Certification Requirements for Designated
seismic demands determined in accordance with Sections 13.3.1
Seismic Systems. Certifications shall be provided for designated
and 13.3.2.
seismic systems assigned to Seismic Design Categories C through
F as follows: 13.2.7 Construction Documents. Where design of nonstruc-
tural components or their supports and attachments is required
a. Active mechanical and electrical equipment that must remain by Table 13.2-1, such design shall be shown in construction
operable following the design earthquake shall be certified by documents prepared by a registered design professional for use
the supplier as operable based on approved shake table testing by the owner, building officials, contractors, and inspectors. Such
in accordance with Section 13.2.5 or experience data in ac- documents shall include a quality assurance plan if required by
cordance with Section 13.2.6. Evidence demonstrating com- Appendix 11A.
pliance of this requirement shall be submitted to the authority
having jurisdiction after review and approval by the registered
design professional. 13.3 SEISMIC DEMANDS ON NONSTRUCTURAL
b. Components with hazardous contents shall be certified by COMPONENTS
the supplier as maintaining containment following the design 13.3.1 Seismic Design Force. The horizontal seismic design
earthquake by (1) analysis, (2) approved shake table testing force (F p ) shall be applied at the component’s center of grav-
in accordance with Section 13.2.5, or (3) experience data in ity and distributed relative to the component’s mass distribution
accordance with Section 13.2.6. Evidence demonstrating com- and shall be determined in accordance with Eq. 13.3-1:
pliance of this requirement shall be submitted to the authority  
having jurisdiction after review and approval by the registered 0.4a p S DS W p z
design professional. Fp =   1+2 (13.3-1)
Rp h
13.2.3 Consequential Damage. The functional and physical in- Ip
terrelationship of components, their supports, and their effect on F p is not required to be taken as greater than
each other shall be considered so that the failure of an essential or
nonessential architectural, mechanical, or electrical component F p = 1.6S DS I p W p (13.3-2)
shall not cause the failure of an essential architectural, mechani-
cal, or electrical component. and F p shall not be taken as less than

13.2.4 Flexibility. The design and evaluation of components, F p = 0.3S DS I p W p (13.3-3)


their supports, and their attachments shall consider their flexi- where
bility as well as their strength.
F p = seismic design force
13.2.5 Testing Alternative for Seismic Capacity Determina- S DS = spectral acceleration, short period, as determined from
tion. As an alternative to the analytical requirements of Sec- Section 11.4.4
tions 13.2 through 13.6, testing shall be deemed as an acceptable a p = component amplification factor that varies from 1.00
method to determine the seismic capacity of components and to 2.50 (select appropriate value from Table 13.5-1 or
their supports and attachments. Seismic qualification by testing 13.6-1)
based upon a nationally recognized testing standard procedure, I p = component importance factor that varies from 1.00 to 1.50
such as ICC-ES AC 156, acceptable to the authority having ju- (see Section 13.1.3)
risdiction shall be deemed to satisfy the design and evaluation W p = component operating weight
requirements provided that the substantiated seismic capacities R p = component response modification factor that varies from
equal or exceed the seismic demands determined in accordance 1.00 to 12 (select appropriate value from Table 13.5-1 or
with Sections 13.3.1 and 13.3.2. 13.6-1)

144 ASCE 7-05


P1: JsY
ASCE003-13.tex ASCE003/SIE-v1.cls October 10, 2005 18:0

z = height in structure of point of attachment of component where


with respect to the base. For items at or below the base, z D p = relative seismic displacement that the component must be
shall be taken as 0. The value of z/ h need not exceed 1.0 designed to accommodate
h = average roof height of structure with respect to the base δx A = deflection at building Level x of Structure A, determined
The force (F p ) shall be applied independently in at least two or- by an elastic analysis as defined in Section 12.8.6
thogonal horizontal directions in combination with service loads δ y A = deflection at building Level y of Structure A, determined
associated with the component, as appropriate. For vertically by an elastic analysis as defined in Section 12.8.6
cantilevered systems, however, the force F p shall be assumed to δ y B = deflection at building Level y of Structure B, determined
act in any horizontal direction. In addition, the component shall by an elastic analysis as defined in Section 12.8.6
be designed for a concurrent vertical force ±0.2S DS W p . The re- h x = height of Level x to which upper connection point is
dundancy factor, ρ, is permitted to be taken equal to 1 and the attached
overstrength factor, 0 , does not apply. h y = height of Level y to which lower connection point is
EXCEPTION: The concurrent vertical seismic force need not be con- attached
sidered for lay-in access floor panels and lay-in ceiling panels. a A = allowable story drift for Structure A as defined in
Where nonseismic loads on nonstructural components exceed F p , Table 12.12-1
such loads shall govern the strength design, but the detailing re- a B = allowable story drift for Structure B as defined in
quirements and limitations prescribed in this chapter shall apply. Table 12.12-1
h sx = story height used in the definition of the allowable drift
In lieu of the forces determined in accordance with Eq. 13.3-1, a in Table12.12-1. Note that a /h sx = the drift index.
accelerations at any level are permitted to be determined by the
modal analysis procedures of Section 12.9 with R = 1.0. Seismic The effects of seismic relative displacements shall be consid-
forces shall be in accordance with Eq. 13.3-4: ered in combination with displacements caused by other loads as
appropriate.
ai a p W p
Fp =   Ax (13.3-4)
Rp 13.4 NONSTRUCTURAL COMPONENT
Ip ANCHORAGE
Components and their supports shall be attached (or anchored) to
Where ai is the acceleration at level i obtained from the modal the structure in accordance with the requirements of this section
analysis and where A x is the torsional amplification factor and the attachment shall satisfy the requirements for the parent
determined by Eq.12.8-14. Upper and lower limits of F p deter- material as set forth elsewhere in this standard.
mined by Eqs. 13.3-2 and 13.3-3 shall apply.
Component attachments shall be bolted, welded, or otherwise
13.3.2 Seismic Relative Displacements. The effects of seismic positively fastened without consideration of frictional resistance
relative displacements shall be considered in combination with produced by the effects of gravity. A continuous load path of suf-
displacements caused by other loads as appropriate. Seismic rel- ficient strength and stiffness between the component and the sup-
ative displacements (D p ) shall be determined in accordance with porting structure shall be provided. Local elements of the structure
the equations set forth in Sections 13.3.2.1 and 13.3.2.2. including connections shall be designed and constructed for the
component forces where they control the design of the elements
13.3.2.1 Displacements within Structures. For two connection or their connections. The component forces shall be those de-
points on the same Structure A or the same structural system, one termined in Section 13.3.1, except that modifications to F p and
at a height h x and the other at a height h y , D p shall be determined R p due to anchorage conditions need not be considered. The de-
as sign documents shall include sufficient information relating to
the attachments to verify compliance with the requirements of
D p = δx A − δ y A (13.3-5) this section.

Alternatively, D p is permitted to be determined using modal pro- 13.4.1 Design Forces. The force in the attachment shall be de-
cedures described in Section 12.9, using the difference in story termined based on the prescribed forces and displacements for the
deflections calculated for each mode and then combined using component determined specified in Sections 13.3.1 and 13.3.2.
appropriate modal combination procedures. D p is not required to
13.4.2 Anchors in Concrete or Masonry. Anchors embedded
be taken as greater than
in concrete or masonry shall be proportioned to carry the least of
(h x − h y ) a A the following:
Dp = (13.3-6) a. 1.3 times the force in the component and its supports due to
h sx
the prescribed forces.
13.3.2.2 Displacements between Structures. For two connec- b. The maximum force that can be transferred to the anchor by
tion points on separate Structures A and B or separate structural the component and its supports.
systems, one at a height h x and the other at a height h y , D p shall The value of R p used in Section 13.3.1 to determine the forces in
be determined as the connected part shall not exceed 1.5 unless
 
D p = |δx A | + δ y B 
a. The component anchorage is designed to be governed by the
(13.3-7)
strength of a ductile steel element.
D p is not required to be taken as greater than b. The design of post-installed anchors in concrete used for the
component anchorage is prequalified for seismic applications
h x a A h y a B in accordance with ACI 355.2.
Dp = + (13.3-8)
h sx h sx c. The anchor is designed in accordance with Section 14.2.2.14.

Minimum Design Loads for Buildings and Other Structures 145


P1: JsY
ASCE003-13.tex ASCE003/SIE-v1.cls October 10, 2005 18:0

13.4.3 Installation Conditions. Determination of forces in 1. The design load for such items shall be equal to 1.4 times the oper-
attachments shall take into account the expected conditions of ating weight acting down with a simultaneous horizontal load equal
installation including eccentricities and prying effects. to 1.4 times the operating weight. The horizontal load shall be ap-
plied in the direction that results in the most critical loading for
13.4.4 Multiple Attachments. Determination of force distribu- design.
tion of multiple attachments at one location shall take into account 2. Seismic interaction effects shall be considered in accordance with
the stiffness and ductility of the component, component supports, Section 13.2.3.
attachments, and structure and the ability to redistribute loads to 3. The connection to the structure shall allow a 360◦ range of motion
other attachments in the group. Designs of anchorage in concrete in the horizontal plane.
in accordance with Appendix D of ACI 318 shall be considered
to satisfy this requirement. 13.5.2 Forces and Displacements. All architectural compo-
nents, and their supports and attachments, shall be designed for
13.4.5 Power Actuated Fasteners. Power actuated fasteners the seismic forces defined in Section 13.3.1.
shall not be used for tension load applications in Seismic Design Architectural components that could pose a life-safety haz-
Categories D, E, and F unless approved for such loading. ard shall be designed to accommodate the seismic relative dis-
13.4.6 Friction Clips. Friction clips shall not be used for anchor- placement requirements of Section 13.3.2. Architectural compo-
age attachment. nents shall be designed considering vertical deflection due to joint
rotation of cantilever structural members.
13.5 ARCHITECTURAL COMPONENTS 13.5.3 Exterior Nonstructural Wall Elements and Connec-
13.5.1 General. Architectural components, and their supports tions. Exterior nonstructural wall panels or elements that are at-
and attachments, shall satisfy the requirements of this section. tached to or enclose the structure shall be designed to accommo-
Appropriate coefficients shall be selected from Table 13.5-1. date the seismic relative displacements defined in Section 13.3.2
EXCEPTIONS: Components supported by chains or otherwise sus- and movements due to temperature changes. Such elements shall
pended from the structure are not required to satisfy the seismic force be supported by means of positive and direct structural supports
and relative displacement requirements provided they meet all of the fol- or by mechanical connections and fasteners in accordance with
lowing criteria: the following requirements:

TABLE 13.5-1 COEFFICIENTS FOR ARCHITECTURAL COMPONENT


Architectural Component or Element ap a Rp b

Interior Nonstructural Walls and Partitionsb


Plain (unreinforced) masonry walls 1.0 1.5
All other walls and partitions 1.0 2.5
Cantilever Elements (Unbraced or braced to structural frame below its center of mass)
Parapets and cantilever interior nonstructural walls 2.5 2.5
Chimneys and stacks where laterally braced or supported by the structural frame 2.5 2.5
Cantilever Elements (Braced to structural frame above its center of mass)
Parapets 1.0 2.5
Chimneys and Stacks 1.0 2.5
Exterior Nonstructural Wallsb 1.0b 2.5
Exterior Nonstructural Wall Elements and Connectionsb
Wall Element 1.0 2.5
Body of wall panel connections 1.0 2.5
Fasteners of the connecting system 1.25 1.0
Veneer
Limited deformability elements and attachments 1.0 2.5
Low deformability elements and attachments 1.0 1.5
Penthouses (except where framed by an extension of the building frame) 2.5 3.5
Ceilings
All 1.0 2.5
Cabinets
Storage cabinets and laboratory equipment 1.0 2.5
Access Floors
Special access floors (designed in accordance with Section 13.5.7.2) 1.0 2.5
All other 1.0 1.5
Appendages and Ornamentations 2.5 2.5
Signs and Billboards 2.5 2.5
Other Rigid Components
High deformability elements and attachments 1.0 3.5
Limited deformability elements and attachments 1.0 2.5
Low deformability materials and attachments 1.0 1.5
Other Flexible Components
High deformability elements and attachments 2.5 3.5
Limited deformability elements and attachments 2.5 2.5
Low deformability materials and attachments 2.5 1.5
a A lower value for a shall not be used unless justified by detailed dynamic analysis. The value for a shall not be
p p
less than 1.00. The value of a p = 1 is for rigid components and rigidly attached components. The value of ap = 2.5 is
for flexible components and flexibly attached components. See Section 11.2 for definitions of rigid and flexible.
b Where flexible diaphragms provide lateral support for concrete or masonry walls and partitions, the design forces for
anchorage to the diaphragm shall be as specified in Section 12.11.2.

146 ASCE 7-05


P1: JsY
ASCE003-13.tex ASCE003/SIE-v1.cls October 10, 2005 18:0

a. Connections and panel joints shall allow for the story drift The tributary areas of the horizontal restraints shall be approx-
caused by relative seismic displacements (D p ) determined in imately equal.
Section 13.3.2, or 0.5 in. (13 mm), whichever is greatest. EXCEPTION: Rigid braces are permitted to be used instead of di-
b. Connections to permit movement in the plane of the panel for agonal splay wires. Braces and attachments to the structural system
story drift shall be sliding connections using slotted or oversize above shall be adequate to limit relative lateral deflections at point of
attachment of ceiling grid to less than 0.25 in. (6 mm) for the loads
holes, connections that permit movement by bending of steel,
prescribed in Section 13.3.1.
or other connections that provide equivalent sliding or ductile
capacity. d. For ceiling areas exceeding 2,500 ft2 (232 m2 ), a seismic sepa-
ration joint or full height partition that breaks the ceiling up into
c. The connecting member itself shall have sufficient ductility
areas not exceeding 2,500 ft2 shall be provided unless struc-
and rotation capacity to preclude fracture of the concrete or
tural analyses are performed of the ceiling bracing system for
brittle failures at or near welds.
the prescribed seismic forces that demonstrate ceiling system
d. All fasteners in the connecting system such as bolts, inserts, penetrations and closure angles provide sufficient clearance
welds, and dowels and the body of the connectors shall be to accommodate the anticipated lateral displacement. Each
designed for the force (F p ) determined by Section 13.3.1 with area shall be provided with closure angles in accordance with
values of R p and a p taken from Table 13.5-1 applied at the item 2 and horizontal restraints or bracing in accordance with
center of mass of the panel. item 3.
e. Where anchorage is achieved using flat straps embedded in e. Except where rigid braces are used to limit lateral deflec-
concrete or masonry, such straps shall be attached to or hooked tions, sprinkler heads and other penetrations shall have a 2 in.
around reinforcing steel or otherwise terminated so as to effec- (50 mm) oversize ring, sleeve, or adapter through the ceiling
tively transfer forces to the reinforcing steel or to assure that tile to allow for free movement of at least 1 in. (25 mm) in
pullout of anchorage is not the initial failure mechanism. all horizontal directions. Alternatively, a swing joint that can
13.5.4 Glass. Glass in glazed curtain walls and storefronts shall accommodate 1 in. (25 mm) of ceiling movement in all hori-
be designed and installed in accordance with Section 13.5.9. zontal directions is permitted to be provided at the top of the
sprinkler head extension.
13.5.5 Out-of-Plane Bending. Transverse or out-of-plane bend- f. Changes in ceiling plan elevation shall be provided with posi-
ing or deformation of a component or system that is subjected tive bracing.
to forces as determined in Section 13.5.2 shall not exceed the
deflection capability of the component or system. g. Cable trays and electrical conduits shall be supported indepen-
dently of the ceiling.
13.5.6 Suspended Ceilings. h. Suspended ceilings shall be subject to the special inspection
13.5.6.1 Seismic Forces. The weight of the ceiling, W p , shall requirements of Section 11A.1.3.9 of this standard.
include the ceiling grid and panels; light fixtures if attached to, 13.5.6.3 Integral Construction. As an alternate to providing
clipped to, or laterally supported by the ceiling grid; and other large clearances around sprinkler system penetrations through
components that are laterally supported by the ceiling. W p shall ceiling systems, the sprinkler system and ceiling grid are per-
be taken as not less than 4 psf (19 N/m2 ). mitted to be designed and tied together as an integral unit. Such
The seismic force, F p , shall be transmitted through the ceiling a design shall consider the mass and flexibility of all elements
attachments to the building structural elements or the ceiling- involved, including the ceiling system, sprinkler system, light
structure boundary. fixtures, and mechanical (HVAC) appurtenances. Such design
shall be performed by a registered design professional.
13.5.6.2 Industry Standard Construction. Unless designed in
accordance with Section 13.5.6.3, suspended ceilings shall be 13.5.7 Access Floors.
designed and constructed in accordance with this section. 13.5.7.1 General. The weight of the access floor, W p , shall in-
13.5.6.2.1 Seismic Design Category C. Suspended ceilings clude the weight of the floor system, 100 percent of the weight of
in structures assigned to Seismic Design Category C shall be all equipment fastened to the floor, and 25 percent of the weight
designed and installed in accordance with ASTM C635, ASTM of all equipment supported by, but not fastened to the floor. The
C636, and the CISCA for Seismic Zones 0-2, except that seismic seismic force, F p , shall be transmitted from the top surface of the
forces shall be determined in accordance with Sections 13.3.1 and access floor to the supporting structure.
13.5.6.1. Overturning effects of equipment fastened to the access floor
13.5.6.2.2 Seismic Design Categories D through F. Sus- panels also shall be considered. The ability of “slip on” heads for
pended ceilings in Seismic Design Categories D, E, and F shall be pedestals shall be evaluated for suitability to transfer overturning
designed and installed in accordance with ASTM C635, ASTM effects of equipment.
C636, and the CISCA for Seismic Zones 3-4 as modified by the Where checking individual pedestals for overturning effects,
following: the maximum concurrent axial load shall not exceed the portion
of W p assigned to the pedestal under consideration.
a. A heavy duty T-bar grid system shall be used.
b. The width of the perimeter supporting closure angle shall be 13.5.7.2 Special Access Floors. Access floors shall be consid-
not less than 2.0 in. (50 mm). In each orthogonal horizontal ered to be “special access floors” if they are designed to comply
direction, one end of the ceiling grid shall be attached to the with the following considerations:
closure angle. The other end in each horizontal direction shall 1. Connections transmitting seismic loads consist of me-
have a 0.75 in. (19 mm) clearance from the wall and shall rest chanical fasteners, anchors satisfying the requirements of
upon and be free to slide on a closure angle. Appendix D of ACI 318, welding, or bearing. Design load
c. For ceiling areas exceeding 1,000 ft2 (92.9 m2 ), horizontal re- capacities comply with recognized design codes and/or
straint of the ceiling to the structural system shall be provided. certified test results.

Minimum Design Loads for Buildings and Other Structures 147


P1: JsY
ASCE003-13.tex ASCE003/SIE-v1.cls October 10, 2005 18:0

2. Seismic loads are not transmitted by friction, power actuated h p = the height of the rectangular glass panel
fasteners, adhesives, or by friction produced solely by the b p = the width of the rectangular glass panel
effects of gravity. c1 = the clearance (gap) between the vertical glass edges and the
frame
3. The design analysis of the bracing system includes the c2 = the clearance (gap) between the horizontal glass edges and
destabilizing effects of individual members buckling in the frame
compression. 2. Fully tempered monolithic glass in Occupancy Categories I, II, and III
located no more than 10 ft (3 m) above a walking surface need not
4. Bracing and pedestals are of structural or mechanical shapes comply with this requirement.
produced to ASTM specifications that specify minimum
mechanical properties. Electrical tubing shall not be used. 3. Annealed or heat-strengthened laminated glass in single thickness with
interlayer no less than 0.030 in. (0.76 mm) that is captured mechanically
5. Floor stringers that are designed to carry axial seismic in a wall system glazing pocket, and whose perimeter is secured to the
loads and that are mechanically fastened to the supporting frame by a wet glazed gunable curing elastomeric sealant perimeter
pedestals are used. bead of 0.5 in. (13 mm) minimum glass contact width, or other approved
anchorage system need not comply with this requirement.
13.5.8 Partitions.
13.5.9.2 Seismic Drift Limits for Glass Components. fallout ,
13.5.8.1 General. Partitions that are tied to the ceiling and all the drift causing glass fallout from the curtain wall, storefront, or
partitions greater than 6 ft (1.8 m) in height shall be laterally partition shall be determined in accordance with AAMA 501.6,
braced to the building structure. Such bracing shall be independent or by engineering analysis.
of any ceiling splay bracing. Bracing shall be spaced to limit
horizontal deflection at the partition head to be compatible with
ceiling deflection requirements as determined in Section 13.5.6 13.6 MECHANICAL AND ELECTRICAL
for suspended ceilings and elsewhere in this section for other COMPONENTS
systems. 13.6.1 General. Mechanical and electrical components and their
EXCEPTION: Partitions that meet all of the following conditions: supports shall satisfy the requirements of this section. The attach-
1. The partition height does not exceed 9 ft (2,740 mm). ment of mechanical and electrical components and their supports
2. The linear weight of the partition does not exceed the product of 10 lb to the structure shall meet the requirements of Section 13.4. Ap-
(0.479 kN) times the height (ft) of the partition. propriate coefficients shall be selected from Table 13.6-1.
3. The partition horizontal seismic load does not exceed 5 psf. EXCEPTIONS: Light fixtures, lighted signs, and ceiling fans not con-
nected to ducts or piping, which are supported by chains or otherwise
13.5.8.2 Glass. Glass in glazed partitions shall be designed and suspended from the structure, are not required to satisfy the seismic force
installed in accordance with Section 13.5.9. and relative displacement requirements provided they meet all of the
following criteria:
13.5.9 Glass in Glazed Curtain Walls, Glazed Storefronts, and 1. The design load for such items shall be equal to 1.4 times the operat-
Glazed Partitions. ing weight acting down with a simultaneous horizontal load equal to
1.4 times the operating weight. The horizontal load shall be applied in
13.5.9.1 General. Glass in glazed curtain walls, glazed store- the direction that results in the most critical loading for design.
fronts, and glazed partitions shall meet the relative displacement 2. Seismic interaction effects shall be considered in accordance with
requirement of Eq. 13.5-1: Section 13.2.3.
3. The connection to the structure shall allow a 360◦ range of motion in
fallout ≥ 1.25ID p (13.5-1) the horizontal plane.
or 0.5 in. (13 mm), whichever is greater where: Where design of mechanical and electrical components for seis-
mic effects is required, consideration shall be given to the dynamic
where effects of the components, their contents, and where appropriate,
fallout = the relative seismic displacement (drift) at which glass their supports. In such cases, the interaction between the compo-
fallout from the curtain wall, storefront wall, or partition nents and the supporting structures, including other mechanical
occurs (Section 13.5.9.2) and electrical components, shall also be considered.
D p = the relative seismic displacement that the component
must be designed to accommodate (Eq. 13.3-2). D p 13.6.2 Component Period. The fundamental period of the me-
shall be applied over the height of the glass component chanical and electrical component (and its attachment to the build-
under consideration ing), T p , shall be determined by the following equation provided
I = the occupancy importance factor (Table 11.5-1) that the component and attachment can be reasonably represented
analytically by a simple spring and mass single degree-of-freedom
EXCEPTIONS:
system:
1. Glass with sufficient clearances from its frame such that physical con-
tact between the glass and frame will not occur at the design drift, as 
demonstrated by Eq. 13.5-2, need not comply with this requirement: Wp
T p = 2π (13.6-1)
K pg
Dclear ≥ 1.25D p (13.5-2)

where where
Dclear = relative horizontal (drift) displacement, measured over the T p = component fundamental period
height of the glass panel under consideration, which causes W p = component operating weight
initial glass-to-frame contact. For rectangular glass panels g = gravitational acceleration
within a rectangular wall frame
K p = stiffness of resilient support system of the component and
 
h p c2 attachment, determined in terms of load per unit deflection
Dclear = 2c1 1 +
b p c1 at the center of gravity of the component

148 ASCE 7-05


P1: JsY
ASCE003-13.tex ASCE003/SIE-v1.cls October 10, 2005 18:0

TABLE 13.6-1 SEISMIC COEFFICIENTS FOR MECHANICAL AND ELECTRICAL COMPONENTS


MECHANICAL AND ELECTRICAL COMPONENTS ap a Rp b

Air-side HVAC, fans, air handlers, air conditioning units, cabinet heaters, air distribution boxes, and other mechanical components 2.5 6.0
constructed of sheet metal framing.
Wet-side HVAC, boilers, furnaces, atmospheric tanks and bins, chillers, water heaters, heat exchangers, evaporators, air separators, 1.0 2.5
manufacturing or process equipment, and other mechanical components constructed of high-deformability materials.
Engines, turbines, pumps, compressors, and pressure vessels not supported on skirts and not within the scope of Chapter 15. 1.0 2.5
Skirt-supported pressure vessels not within the scope of Chapter 15. 2.5 2.5
Elevator and escalator components. 1.0 2.5
Generators, batteries, inverters, motors, transformers, and other electrical components constructed of high deformability materials. 1.0 2.5
Motor control centers, panel boards, switch gear, instrumentation cabinets, and other components constructed of sheet metal framing. 2.5 6.0
Communication equipment, computers, instrumentation, and controls. 1.0 2.5
Roof-mounted chimneys, stacks, cooling and electrical towers laterally braced below their center of mass. 2.5 3.0
Roof-mounted chimneys, stacks, cooling and electrical towers laterally braced above their center of mass. 1.0 2.5
Lighting fixtures. 1.0 1.5
Other mechanical or electrical components. 1.0 1.5
VIBRATION ISOLATED COMPONENTS AND SYSTEMSb
Components and systems isolated using neoprene elements and neoprene isolated floors with built-in or separate elastomeric snubbing 2.5 2.5
devices or resilient perimeter stops.
Spring isolated components and systems and vibration isolated floors closely restrained using built-in or separate elastomeric snubbing 2.5 2.0
devices or resilient perimeter stops.
Internally isolated components and systems. 2.5 2.0
Suspended vibration isolated equipment including in-line duct devices and suspended internally isolated components. 2.5 2.5
DISTRIBUTION SYSTEMS
Piping in accordance with ASME B31, including in-line components with joints made by welding or brazing. 2.5 12.0
Piping in accordance with ASME B31, including in-line components, constructed of high or limited deformability materials, with joints 2.5 6.0
made by threading, bonding, compression couplings, or grooved couplings.
Piping and tubing not in accordance with ASME B31, including in-line components, constructed of high-deformability materials, with 2.5 9.0
joints made by welding or brazing.
Piping and tubing not in accordance with ASME B31, including in-line components, constructed of high- or limited-deformability 2.5 4.5
materials, with joints made by threading, bonding, compression couplings, or grooved couplings.
Piping and tubing constructed of low-deformability materials, such as cast iron, glass, and nonductile plastics. 2.5 3.0
Ductwork, including in-line components, constructed of high-deformability materials, with joints made by welding or brazing. 2.5 9.0
Ductwork, including in-line components, constructed of high- or limited-deformability materials with joints made by means other than 2.5 6.0
welding or brazing.
Ductwork, including in-line components, constructed of low-deformability materials, such as cast iron, glass, and nonductile plastics. 2.5 3.0
Electrical conduit, bus ducts, rigidly mounted cable trays, and plumbing. 1.0 2.5
Manufacturing or process conveyors (nonpersonnel). 2.5 3.0
Suspended cable trays. 2.5 6.0
a A lower value for a is permitted where justified by detailed dynamic analyses. The value for a shall not be less than 1.0. The value of a equal to 1.0 is for
p p p
rigid components and rigidly attached components. The value of a p equal to 2.5 is for flexible components and flexibly attached components.
b Components mounted on vibration isolators shall have a bumper restraint or snubber in each horizontal direction. The design force shall be taken as 2F if the
p
nominal clearance (air gap) between the equipment support frame and restraint is greater than 0.25 in. If the nominal clearance specified on the construction
documents is not greater than 0.25 in., the design force is permitted to be taken as F p .

Alternatively, the fundamental period of the component in s (T p ) 3. Where piping or HVAC ductwork components are attached
is permitted to be determined from experimental test data or by a to structures that could displace relative to one another and
properly substantiated analysis. for isolated structures where such components cross the
13.6.3 Mechanical Components. HVAC ductwork shall meet isolation interface, the components shall be designed to
the requirements of Section 13.6.7. Piping systems shall meet the accommodate the seismic relative displacements defined in
requirements of Section 13.6.8. Boilers and vessels shall meet the Section 13.3.2.
requirements of Section 13.6.9. Elevators shall meet the require- 13.6.4 Electrical Components. Electrical components with I p
ments of Section 13.6.10. All other mechanical components shall greater than 1.0 shall be designed for the seismic forces and rela-
meet the requirements of Section 13.6.11. Mechanical compo- tive displacements defined in Sections 13.3.1 and 13.3.2 and shall
nents with I p greater than 1.0 shall be designed for the seismic satisfy the following additional requirements:
forces and relative displacements defined in Sections 13.3.1 and 1. Provision shall be made to eliminate seismic impact between
13.3.2 and shall satisfy the following additional requirements: components.
1. Provision shall be made to eliminate seismic impact for 2. Loads imposed on the components by attached utility or
components vulnerable to impact, for components con- service lines that are attached to separate structures shall be
structed of nonductile materials, and in cases where material evaluated.
ductility will be reduced due to service conditions (e.g., low 3. Batteries on racks shall have wrap-around restraints to en-
temperature applications). sure that the batteries will not fall from the rack. Spacers
2. The possibility of loads imposed on components by attached shall be used between restraints and cells to prevent damage
utility or service lines, due to differential movement of sup- to cases. Racks shall be evaluated for sufficient lateral load
port points on separate structures, shall be evaluated. capacity.

Minimum Design Loads for Buildings and Other Structures 149


P1: JsY
ASCE003-13.tex ASCE003/SIE-v1.cls October 10, 2005 18:0

4. Internal coils of dry type transformers shall be positively the base is not reinforced with stiffeners or is not capable of
attached to their supporting substructure within the trans- transferring the required loads.
former enclosure.
3. Where weak-axis bending of cold-formed steel supports is
5. Electrical control panels, computer equipment, and other relied on for the seismic load path, such supports shall be
items with slide-out components shall have a latching mech- specifically evaluated.
anism to hold the components in place.
4. Components mounted on vibration isolators shall have a
6. Electrical cabinet design shall comply with the applica- bumper restraint or snubber in each horizontal direction,
ble National Electrical Manufacturers Association (NEMA) and vertical restraints shall be provided where required to
standards. Cutouts in the lower shear panel that have not resist overturning. Isolator housings and restraints shall be
been made by the manufacturer and reduce significantly the constructed of ductile materials. (See additional design force
strength of the cabinet shall be specifically evaluated. requirements in footnote b to Table 13.6-1.) A viscoelastic
pad or similar material of appropriate thickness shall be used
7. The attachments for additional external items weighing
between the bumper and components to limit the impact
more than 100 lb (445 N) shall be specifically evaluated
load.
if not provided by the manufacturer.
5. Expansion anchors shall not be used for non-vibration iso-
8. Where conduit, cable trays, or similar electrical distribution
lated mechanical equipment rated over 10 hp (7.45 kW).
components are attached to structures that could displace
relative to one another and for isolated structures where EXCEPTION: Undercut expansion anchors are permitted.
such components cross the isolation interface, the compo- 6. The supports for electrical distribution components shall be
nents shall be designed to accommodate the seismic relative designed for the seismic forces and relative displacements
displacements defined in Section 13.3.2. defined in Sections 13.3.1 and 13.3.2 if any of the following
13.6.5 Component Supports. Mechanical and electrical com- conditions apply:
ponent supports (including those with I p = 1.0) and the means a. I p is equal to 1.5 and conduit diameter is greater than
by which they are attached to the component shall be designed 2.5 in. (64 mm) trade size.
for the forces and displacements determined in Sections 13.3.1 b. Trapeze assemblies supporting conduit, and bus ducts or
and 13.3.2. Such supports include structural members, braces, cable trays where I p is equal to 1.5 and the total weight of
frames, skirts, legs, saddles, pedestals, cables, guys, stays, snub- the bus duct, cable tray, or conduit supported by trapeze
bers, and tethers, as well as elements forged or cast as a part of assemblies exceeds 10 lb/ft (146 N/m).
the mechanical or electrical component. c. Supports are cantilevered up from the floor.
13.6.5.1 Design Basis. If standard supports, for example, ASME d. Supports include bracing to limit deflection.
B31, NFPA 13, or MSS SP-58, or proprietary supports are used, e. Supports are constructed as rigid welded frames.
they shall be designed by either load rating (i.e., testing) or for the
f. Attachments into concrete utilize nonexpanding insets,
calculated seismic forces. In addition, the stiffness of the support,
power actuated fasteners, or cast iron embedments.
where appropriate, shall be designed such that the seismic load
path for the component performs its intended function. g. Attachments utilize spot welds, plug welds, or minimum
size welds as defined by AISC.
13.6.5.2 Design for Relative Displacement. Component sup-
ports shall be designed to accommodate the seismic relative dis- 7. For piping, boilers, and pressure vessels, attachments to con-
placements between points of support determined in accordance crete shall be suitable for cyclic loads.
with Section 13.3.2. 8. For mechanical equipment, drilled and grouted-in-place an-
13.6.5.3 Support Attachment to Component. The means by chors for tensile load applications shall use either expansive
which supports are attached to the component, except where in- cement or expansive epoxy grout.
tegral (i.e., cast or forged), shall be designed to accommodate
both the forces and displacements determined in accordance with 13.6.6 Utility and Service Lines. At the interface of adjacent
Sections 13.3.1 and 13.3.2. If the value of I p = 1.5 for the com- structures or portions of the same structure that may move
ponent, the local region of the support attachment point to the independently, utility lines shall be provided with adequate
component shall be evaluated for the effect of the load transfer on flexibility to accommodate the anticipated differential movement
the component wall. between the portions that move independently. Differential dis-
13.6.5.4 Material Detailing Requirements. The materials placement calculations shall be determined in accordance with
comprising supports and the means of attachment to the compo- Section 13.3.2.
nent shall be constructed of materials suitable for the application, The possible interruption of utility service shall be considered
including the effects of service conditions, for example, low tem- in relation to designated seismic systems in Occupancy Cate-
perature applications. Materials shall be in conformance with a gory IV as defined in Table 1-1. Specific attention shall be given
nationally recognized standard. to the vulnerability of underground utilities and utility interfaces
between the structure and the ground where Site Class E or F soil
13.6.5.5 Additional Requirements. The following additional
is present, and where the seismic coefficient S DS at the under-
requirements shall apply to mechanical and electrical component
ground utility or at the base of the structure is equal to or greater
supports:
than 0.33.
1. Seismic supports shall be constructed so that support en-
gagement is maintained.
13.6.7 HVAC Ductwork. Seismic supports are not required for
2. Oversized plate washers or other reinforcement shall be pro- HVAC ductwork with I p = 1.0 if either of the following conditions
vided at bolted connections through a sheet metal base if is met for the full length of each duct run:

150 ASCE 7-05


P1: JsY
ASCE003-13.tex ASCE003/SIE-v1.cls October 10, 2005 18:0

a. HVAC ducts are suspended from hangers 12 in. (305 mm) or 1. The hangers and sway bracing of the fire protection sprinkler
less in length. The hangers shall be detailed to avoid significant systems shall be deemed to meet the requirements of this
bending of the hangers and their attachments. section if both of the following requirements are satisfied:
b. HVAC ducts have a cross-sectional area of less than 6 ft2 a. The hangers and sway bracing are designed and con-
(0.557 m2 ). structed in accordance with NFPA 13.
HVAC duct systems fabricated and installed in accordance with b. The force and displacement requirements of Sections
standards approved by the authority having jurisdiction shall 13.3.1 and 13.3.2 are satisfied.
be deemed to meet the lateral bracing requirements of this 2. The fire protection sprinkler system piping itself shall meet
section. the force and displacement requirements of Section 13.3.1
Components that are installed in-line with the duct system and and 13.3.2.
have an operating weight greater than 75 lb. (334 N), such as fans, 3. The design strength of the fire protection sprinkler system
heat exchangers, and humidifiers, shall be supported and laterally piping for seismic loads in combination with other service
braced independent of the duct system and such braces shall meet loads and appropriate environmental effects shall be based
the force requirements of Section 13.3.1. Appurtenances such as on the following material properties:
dampers, louvers, and diffusers shall be positively attached with
a. For piping and components constructed with ductile ma-
mechanical fasteners. Unbraced piping attached to in-line equip-
terials (e.g., steel, aluminum, or copper), 90 percent of
ment shall be provided with adequate flexibility to accommodate
the minimum specified yield strength.
differential displacements.
b. For threaded connections in components constructed
13.6.8 Piping Systems. Piping systems shall satisfy the require- with ductile materials, 70 percent of the minimum spec-
ments of this section except that elevator system piping shall sat- ified yield strength.
isfy the requirements of Section 13.6.10. c. For piping and components constructed with nonductile
materials (e.g., plastic, cast iron, or ceramics), 10 percent
Except for piping designed and constructed in accordance with
of the material minimum specified tensile strength.
NFPA 13, seismic supports shall not be required for other piping
systems where one of the following conditions is met: 13.6.8.4 Other Piping Systems. Piping not designed and con-
1. Piping is supported by rod hangers; hangers in the pipe structed in accordance with ASME B31 or NFPA 13 shall comply
run are 12 in. (305 mm) or less in length from the top of with the requirements of Section 13.6.11.
the pipe to the supporting structure; hangers are detailed
to avoid bending of the hangers and their attachments; and 13.6.9 Boilers and Pressure Vessels. Boilers or pressure ves-
provisions are made for piping to accommodate expected sels designed in accordance with ASME BPVC shall be deemed
deflections. to meet the force, displacement, and other requirements of this
section. In lieu of the specific force and displacement require-
2. High-deformability piping is used; provisions are made to ments provided in the ASME BPVC, the force and displace-
avoid impact with larger piping or mechanical components ment requirements of Sections 13.3.1 and 13.3.2 shall be used.
or to protect the piping in the event of such impact; and the Other boilers and pressure vessels designated as having an
following size requirements are satisfied: I p = 1.5, but not constructed in accordance with the require-
a. For Seismic Design Categories D, E, or F where I p is ments of ASME BPVC shall comply with the requirements of
greater than 1.0, the nominal pipe size shall be 1 in. (25 Section 13.6.11.
mm) or less.
13.6.10 Elevator and Escalator Design Requirements. Eleva-
b. For Seismic Design Category C, where I p is greater than tors and escalators designed in accordance with the seismic re-
1.0, the nominal pipe size shall be 2 in. (51 mm) or less. quirements of ASME A17.1 shall be deemed to meet the seismic
c. For Seismic Design Categories D, E, or F where I p is force requirements of this section, except as modified in the fol-
equal to 1.0, the nominal pipe size shall be 3 in. (76 mm) lowing text.
or less.
13.6.10.1 Escalators, Elevators, and Hoistway Structural Sys-
13.6.8.1 ASME Pressure Piping Systems. Pressure piping sys- tem. Escalators, elevators, and hoistway structural systems shall
tems, including their supports, designed and constructed in ac- be designed to meet the force and displacement requirements of
cordance with ASME B31 shall be deemed to meet the force, Sections 13.3.1 and 13.3.2.
displacement, and other requirements of this section. In lieu of
specific force and displacement requirements provided in ASME 13.6.10.2 Elevator Equipment and Controller Supports and
B31, the force and displacement requirements of Sections 13.3.1 Attachments. Elevator equipment and controller supports and
and 13.3.2 shall be used. attachments shall be designed to meet the force and displacement
requirements of Sections 13.3.2 and 13.3.2.
13.6.8.2 Fire Protection Sprinkler Systems in Seismic Design
Category C. In structures assigned to Seismic Design Category 13.6.10.3 Seismic Switches. Elevators operating with a speed of
C, fire protection sprinkler systems designed and constructed in 150 ft/min (46 m/min) or greater shall be provided with seismic
accordance with NFPA 13 shall be deemed to meet the other switches. Seismic switches shall provide an electrical signal in-
requirements of this section. dicating that structural motions are of such a magnitude that the
operation of elevators may be impaired. The seismic switch shall
13.6.8.3 Fire Protection Sprinkler Systems in Seismic Design be located at or above the highest floor serviced by the elevators.
Categories D through F. In structures assigned to Seismic De- The seismic switch shall have two horizontal perpendicular axes
sign Categories D, E, or F, the following requirements shall be of sensitivity. Its trigger level shall be set to 30 percent of the
satisfied: acceleration of gravity. Upon activation of the seismic switch,

Minimum Design Loads for Buildings and Other Structures 151


P1: JsY
ASCE003-13.tex ASCE003/SIE-v1.cls October 10, 2005 18:0

elevator operations shall conform to requirements of ASME 2. Where mechanical components contain a sufficient quan-
A17.1, except as noted in the following text. tity of hazardous material to pose a danger if released, and
for boilers and pressure vessels not designed in accordance
In facilities where the loss of the use of an elevator is a life-
with ASME BPVC, the design strength for seismic loads in
safety issue, the elevator shall only be used after the seismic switch
combination with other service loads and appropriate envi-
has triggered provided that:
ronmental effects shall be based on the following material
1. The elevator shall operate no faster than the service speed. properties.
2. Before the elevator is occupied, it is operated from top to a. For mechanical components constructed with ductile
bottom and back to top to verify that it is operable. materials (e.g., steel, aluminum, or copper), 90 percent
of the minimum specified yield strength.
13.6.10.4 Retainer Plates. Retainer plates are required at the top
and bottom of the car and counterweight. b. For threaded connections in components constructed
with ductile materials, 70 percent of the minimum spec-
13.6.11 Other Mechanical and Electrical Components. ified yield strength.
Mechanical and electrical components, including distribution sys- c. For mechanical components constructed with nonductile
tems, not designed and constructed in accordance with the refer- materials (e.g., plastic, cast iron, or ceramics), 10 percent
ence documents in Chapter 23 shall meet the following: of the material minimum specified tensile strength.
1. Components, their supports and attachments shall comply d. For threaded connections in piping constructed with non-
with the requirements of Sections 13.4, 13.6.3, 13.6.4, and ductile materials, 8 percent of the material minimum
13.6.5. specified tensile strength.

152 ASCE 7-05

You might also like