You are on page 1of 22

(Reaffirmed 2010)

IS 3844 : 1989
( Reaffirmed 2000 )

Indian Standard
CODE OF PRACTICE FOR
INSTALLATION AND MAINTENANCE
OF INTERNAL FIRE HYDRANTS AND HOSE
~

REELS ON PREMISES
( First Revision) .j

qf~~'{ it lfRRT ~ft;t ~T~Je: m'{ ~)\if ~t~ ~ m=~ m'{


"(~QfTq 'tt "{1fa {{~m

( ~m ,!'fU~)

© DIS 1990
BUREAU OF INDIAN STANDARDS
MANAK BHAVAN. 9 BAHADUR SHAH ZAFAR MAR.G
NEW DELHI 110002

May 1990 Prke Gr., 8


Fire Fighting Sectional Committee, DDC 22

FOREWORD
This Indian Standard ( First Revision) was adopted by the Bureau of Indian Standards on 20 February
1989, after the draft finalized by the Fire Fighting Sectional Committee had been approved by the Civil
Engineering Division Council.
The Dlain intentions of provision of first-aid and in-built fire fighting arrangements are to extinguish
fire at its inception or to control its spread, to assist the fire services in dealing with the fire and in
reducing the losses suffered as a result of fire. Such arrangements are therefore, supplementary to struc-
t

tural fire safety provisions Jaid down in relevant Indian Standards. The first-aid fire fighting arrange-
ments cover provision of portable fire extinguishers and first-aid hose reel instaUation with internal fire
hydrants. The selection, installation and maintenance of fire extinguishers are covered in IS 2190 : 1979
'Code of practice for selection, installation and maintenance of portable first· aid fire extinguishers
( second reVision Y, This standard covers requirements in respect of installation and maintenance of
internal fire hydrants and hose reel systems with or without sprinkler installation for different types
of buildings. Internal fire hydrants are intended for use by fire brigade or other trained personnel and
provide means of delivering considerable quantities of water to extinguish or to prevent the spread of
fire. Hose reels deJivering smaller quantities of water can be operated even by untrained persons and
can be more rapidly brought into action in the early stages of fire. This system is more effective when
the premises is provided with an early warning device of any outbreak of fire.
This standard covering wet- and dry..riser system was first published in 1966. The revision cover
generally only wet-riser system and the provisions given are in line with the ones followed in advanced
countries. The revision also covers the details of water tanks, fire pumps and other components as welJ
as maintenance of system.
For the purpose of deciding whether a particular requirement of this standard is complied with, the
final value, observed or calculated, expressing the result of a test or analysis. shaH be rounded off in
accordance with IS 2 : 1960 'Rules for rounding off numerical values ( revised y. The number of
significant pJaces retained in the rounded off value should be the same as that of the specified value in
this standard.
IS 3844 : 1989

Indian Standard
CODE OF PRACTICE' FOR
INSTALLATION AND MAINTENANCE
OF INTERNAL FIRE HYDRANTS AND HOSE
REELS ON PREMISES
( First Revision)
1 SCOPE 3.5 Jockey Pump
1.1 This standard lays down the requirements of A pump of small capacity which is set to come
installation and· maintenance of internal fire into operation, automatically with drop in static
hydrants and hose reels on the premises. pressure in the system and to automatically st-.JP
when the pre-set pressure is reached again.
NOTE - The requirements in regard to the in~t~l1a· 3.6 Terrace Pump
HOD and maintenance of external fire hydrants ar.
covered in separate Indian Standard. An electrically driven pump, located on the
terrace connected to a terrace tank with gate valve
1 REFERENCES on suction side and to the internal hydrant system
2.1 The Indian Standards listed in Annex A are with non·retum valve on delivery side.
necessary adjuncts to this standard. 3.7 Fire Pam,
3 TERMINOLOGY An electric/diesel pump installed at static water
tank to charge the wet-riser systems.
3.0 For the purpose or this standard. the fonowing
definitions shall apply. 3.8 Stand-by Pump
3.1 Static Water Tank A pump ot same capacity as fire pump, driven by
a diesel engine or connected to any other alternate·
Underground or surface water tank, constructed source of electric supply.
to store water for fire fighting.purpose.
3.9 Pump Panel
3.2 Terrace TaDk
" Panel comprising starting, stopping and indicating
A concrete/masonry/plastic steel tank constructed devices of fire pumps.
or erected on terrace or buHrung for fire fighting
purpose. 3.10 Dry-Riser
An arrangement of fire fighting within the building
3.3 PrIming Tank by means of vertical rising mairu not less than
A small tank erected in/over the pump house 100 mm internal dia with landing valves on each
ab~ve the fire .fighting pumps to keep tbe pump
floor/landing which is normally dry but is capable
casmg and suction of the fire pump permanently of being charged with water usuaUy by pumping
flooded., from fire service appliances. ,
3..11 Don-Comer
3.4 Foot Vahe
~ arrangement for fire fighting within the build-
A valve fixed in the suction strainer of the tire Ing by means of down-comer mains of not less
pump which opens only inwards to allow in-rush than 100 mm internal dia, connected to terrace
of water into the pump suction and fire pump tank through terrace pumpt gate valve and non-
when the fire pump is actuated automaticaUyJ return valve and landing valves on each floor/land-
manualJy. ing. It is also fitted with inlet connections at ground

1
IS 3844 : 1989

level and air release valve at roof level for being 3.20 Fire Service Connections
capable of charged with water by pumping from
fire service appliances. This is a 4.. way collecting breeching with blank caps
(without non-return valve) fixed to a IS0-mm
3.11 Wet-Riser-cum-Down-Comer dia pipe which is connected to the fire tank for
An arrangement for fire fighting within the build- filling from external source.
ing by means of vertical rising mains of not less
than 100 mm internal dia with landing valves on 4 INTERNAL HYDRANT INSTAllATION
each floor/landing connected to terrace tank for
fire fighting purpose, through a terrace pump, gate 4.0 An internal hydrant, installation comprise the
valve and non-return valve near the tank and to following elements: .
a fire pump, gate and non-return valves, over the
static tank. a) Static or terrace tank for storing water for
fire fighting purpose;
3.13 Wet-Riser
b) Rise mains, down-comer mains or external
An arrangement for fire fighting within the build- mains to feed water from the source to the
ing by means of vertical rising mains of not less required point under pressure;
than 100 mm internal dia with landing valves
on each floor/landing for fire fighting purposes c) Fire fighting pump/pumps with all fitments
and permanently charged with water from a and components and pump control panel,.
pressurized supply. housed in a pump house; and '
3.14 Landing Valve d) AU necessary componentsIike internal
An assembly comprising va]ve(s) and out1et(s) hydrants (landing valves) and external
connection from a riser system,_ hydrants, hose reels, hoses and branch
pipes, suitably housed.
3.15 Hose Reel
4.1 Underground Static Water/Terrace Tanks
Fire fighting equipment, consisting of a length of
tubing fitted with a shut-off nozzle and connected 4.1.1 Underground Static Water Tanks
to· a reel, with a permanent connection to a
pressurized water supply. The capacity should be as given in Table 1. The
3.16 Air Release Valve tank should not be more than 3·5 m deep having
a slope ( 1 : 100) and 1 m deep sump of 1 x 2 m
A device by which the trapped air inside a riser at the lowest end. The side with sump should
main is ex.,pelled by water as the system is being preferably be at the front and should have an
charged. easily removable manhole cover through which
fire engine suction hose can be lowered into the
3.17 Air Vessel sump for direct pumping. Static water tank
should be designed and constructed in conjunction.
A cylindrical vessel installed in the wet-riser with domestic tank wherever feasible.
system at the bottom and top levels to counteract
the water hammer effects. U,nderground tanks should be provided with
compartments with external interconnection at
3.18 Pressure Switch
bottom levels having gate valves at both the ends
A switch connected on delivery line of fire pump, for periodical maintenance/cleaning purpose.'
or in the body of hydro-pneumatic tank at pre-set
pressure level So designed to automatically start' At least two manholes each of adequate size with
the fire pump or jockey pump, as the case may be, cover conforming to IS 1726 (Part 1) : 1974;
when the pressure in the system falls below the should be provided on the tanks (outside the.
pre-set level. pump house ) so as to facilitate fire appliances' to'
draw water from tank when necessary. .:
3.19 Fire Service Inlet
Access road to the tank where located outside the
A 2- or' 3-way col1ecting head (see 5.1.1 and building should be at least 6 m in width and the'
5.2.3 ) with non-return valves fitted to the down- same should be designed suitably to bear a load',
comer/wet-riser main, so that in case of need, fire of fire appliances weighing up to 18 tonnes. The
service can directly p~essurize the system with accesS road should be kept free from encroachment
their pump. and obstructions at all times. .
\
\
2
IS 3844 : 1989

4.1.2 Terrace Tanks separate panel, also located in the same pump
room or adjoining separate room. The paneJ
These should be mounted on suitable girders and should have· its separate battery, with battery
plates for equal distribution of load and should charging device,: and auto-manual changeover
be structuraUy stable and the capacity should arrangement. It should incorporate an interlock-
be as given in TabJe 1. . ing device with the main pump panel so that
both .the ,electric pump and the diesel pump do
4.2 rlre Pumps and Pump House not operate simultaneously.
4.2.1 The pump house should be located prefera- Air vessel of adequate capacity should be installed
bly outside the building with a minimum clear- in the pump house, with pressure switches incor-
ance of 6 m from adjoining buildings. The pump porated on the delivery line. There should be
house should have adequate natural ventilation two pressure switches - one with upper and lowel"
with windows, fitted with expanded metal for limit, for Jockey pump, and another only for
protection. If the pump house, houses a dieseJ Jower pressure limit for the main pump. Stopping
pump, the exhaust pipe of the diesel engine should of main pump shouJd be only by manual pusb
be extended to outside the pump house and button which should be prominently indicated on
exhaust discharged at an appropriate height in the the pump panel.
open air. The fioor of the pump house should
be sloped to the farthest end to drain away any Similar lower pressure limit switch should also
water leaking from glands, valves, etc. The pump be incorporated in the diesel pump to make the
house should have normal lighting, and also start automaticaUy at pre-set drop in pressure.
emergency lighting facility, either.from a second
source or from the generator. If the pump house 4~.2.1 Terrace Pump
is located inside the buHding, either on floor one
or in the basement, it should be separated from The· starting of terrace·· pump should' be automatic
the rest portion with a wall having 2 hour fire with pressure switch incorporated in down-comer
rating and fire check door at its entranec: having side so that with opening of· any hydrant valve.
1 hour fire rating. For pump house in basement. or bose ·reelon any ,ioor, it will start
forced mechanical ventilation . should be provided. automatically with fall in line pressure. In addi-
Pump house in floor oneshouJd be located on tion, there should be a manual push button
periphery of, building with access directly· from starter in the starter control panel to be located
outside/open area. . on ground floor ( floor one) of building. Stopping
of pump should be by a push button located in
4.2.2 Arrangement of Pumps the same starter control. Both the push buttons
shou](\ be prominently indicated, and should be in
The pump house should be of adequate dimension different colour for easy identification.
to house aU the pumps with suction, delivery
pipes, fittings and starter control panel, air vessel. 4.2.3 Suction and Delivery Pipe Sizes
etc, with adequate circulation area. A minimum
clearance of 1 m 'at front and back and 0·75 m The suction and delivery pipes should be of
on sides ·and between pumps should be provided adequate size to meet the functional requirements
for all ·major pumps exceedin,,2.280 l/min capa- of the pump, and should not be Jess than
city. For smaller pumps, including jockey pumps, following:
the clearance required, .should be 0·75 m at· front
and· back and O·60·m at sides ·and between:pumps. Suction .Delivery
- The head room clearance for all pump .houses a) 4S0.l/min terrace pump SO mm SOmm
should be minimum 2'75 In. SOmm
b) 900J/min u " 75 mm
The pump control panel,which should also be c) 1 400 1/min ,. " 100 mm l00mm
housed in the pump room should of adequate d) 2 280 J/min fire pump 150 mm lSOmm
dimension to incorporate : TPN switch and HRC
e) 2 850 t/min 200 mm 150mm
switch both of adequate capacity, selector switch II "

a~eter, voltmeter and phase indicating lights, f) 4 540 l/min " " 250 mm 200mm
sangle phase preventer, start and stop push
buttons, aut<rmanuaJ switch, auxiliary contactors Where a manifold is used to make a common
Cor inter-locking/sequence of operations and all suction header, the size of manifold should be at
necessary gauges, fittings required .to complete the least equal to the cross section of the main pumps
system (the busbar should of copper of appro- ( not counting stand·by pump ) suction inlets.
priate thickness ).
4.2.4 Priming of pumps in aU cases should 1
Where diesel pump is provided, it should have a preferably be by positive suction. This can be

3
IS 3844 : 1989

achieved by having the pump bouse at lower level should be at least equal in length to the common
than the water tank, so as to have a permanently b~ plate of pump, motor and flexible coupling
flooded suction. However~ where this is not between pump and motor.
practicable, priming with the help of a priming
tank with a foot valve and strainer arrangement For diesel engines and pumps the foundation
may be used. The capacity of priming tank should be equivalent to railing length of engine
should be 8 times the total volume of the suction and pump with flexible couplings.
pipe, from pump up to the foot valve.
All fire pumps should be, horizontal split-casting
centrifugal type with C. I. casing, bronze impeUar.
4.2.5 For wet-riser-cum-down-comer system, two and stainless steel shaft mounted on heavy
pumps of different capacity - one for the wet.. duty bearings. All metal parts coming in constant
riser (for static tank) and the other for down- contact with water should be suitabJy treated
comer system ( for terrace tank) should be install- with anti-corrosive treatment, unless these are of
ed. The pumps should be fed from normal source non-ferrous metal.
of power supply and also by an alternative source
in case of failure of normal source of supply. 5 RISERS
4.2.6 For a wet-riser system two automatic 5.0 Internal hydrants form part of any of the
pumps should be instaHed to feed the wet-rising following systems: '
main, one of which should act as stand-by, each
pump should have different source of power and a) Dry-riser system,
so arranged that when acting as duty pump, it b) Wet..riser system,
will operate automatically when one or more
hydrant/hose reel is opened thus causing a drop c) Wet..riser-cum-down-comer syslem, and
in pressure.· The stand-by pump should be d) Down-comer system.
arranged to operate automatically in case of
failure of the duty pump. There should be an S.1 Dry-Riser System ( Cor Cold Regio.. )
interlocking arrangement between two main
pumps so that only one should come into opera- 5.1.1 Dry-riser main system could be installed in
tion at a time. buildings under Group A ( i, ii, iii, and iv) (see
IS 1641.: 1988) where the height of building is
4.2.7 An arrangement for supply of alternative above 15 m but not exceeding 24 m up to terrace
source of power automatically should be provided level and where the water supply for fire fighting
to drive pumps, etc, in case of failure of normal is immediately available either through the
power supply. The alternative source should be underground water storage tank/tanks or through
one of the following: water mains/town's main in lieu of provision given
in Table 1. The rising main should have two-way
a) Supply from a diesel generating set ot fire service inlet without non.. return valve at
adequate capacity to meet full requirement ground, level, in front of each such block. It
of fire pump(s) including initial current should also be' prov.jded with an air-releasing
for direct on line/star-delta starting device valve at the top level and drain valve at the bottom.
over and above the other requirements The inlet should be about 1 m from the ground
like automatic fire detection and alarm level, and easily accessible and unobstructed at
system, fire lift, staircase and corridor all times. Single headed landing valves conforming
.lighting circuits, fire pumps, pressurization to IS 5290 : 1983 should be provided at aU floor
system and mechanical exhaust systems etc, landing/staircase enclosures or other suitable
with automatic cbangeover. Fire pump easily accessible point.
may be connected to diesel engine having
same power as, that of electric fire pump 5.1.2 Dry-riser system does not include hose reel.
wjth automatic changeover in case of hose cabinets, fire hose and branch pipes.
power supply failure with interlocking
arrangement. 5.2 Wet-Riser System
b) A power supply from separate' sub-station
for operating emergency services ~entioned 5.2.1 Wet-riser system should be provided in the
in 4.2.7(a). ' types ofbuldings as indicated in Table 1 accord-
ing to the provision mentioned. The system
4.2.8 Pump Mounting ,should consist of a pipe or number of pipes
depending on the area cmd height of the buildings
The pumps should be mounted firmly on concrete permanently charged with water under pressure
foundation of minimum 75 rom thickness with with landing valves, hose reel, hose, branch pipe.
vibration absorbing . layer. The foundation etc, at every fioor level. A provision of pressure

4
,
differential switch to start the pump automatically, type of buildings indicated in Table 1 according
so that water under pressure is available' for. to provisions mentioned. . .
operational hydrant, hose ·reels, etc, as soon. ~s the
water is drawn from hydrant landing valves' 5.4.2 Single headed landing valve, connected to a
causing drop in pressure. The system also. incor- 100 mm diameter pipe taken from the.
terrace
porates a stand-by pump tocODle into operation pump delivery should ~ provided at each floor/
automatically when the'normal power suppJy landing, A hose reel conforming to IS 884 : 1985
source fails. . and directly tapped from the down. . comer pipe
should also be provided on each floor flanding.
5.2.% The distribution of wet-riSer installation in
the building should be so situated as not to be 5.5 Fire Service Inlet
farther than ·30 m €rom any point in the area
·covered by the hydrant and at·a height of 0·75 m S.5.1 The following facilities/arrangements should
to 1 m from .the floor. The: rising mains should' be applicable to wet.. riser systems:
not be' more thaD 5()m apart in horizontal.
a) A fire service inlet at ground level fitted
5.2.3 Fire service inlet with gate and non-return . with a non-return valve should also. be pro-
valve to charge the 'riser in the. event of failure vided to the rising main of each zone for
of the static pump directly from the mobile pump charging it by fire' service pUmp8. 'in case of
.of the fire services .should. be· provided on the failure of fire pump. If two rising mains',
wet-riser system. The. fire service inlet for 100 mm' are within a distance of 30 m ho~nt~dly·;
internal. diameter risiBg main should have colIect- a single fire service inlet will be sufficient. I
ing head with 2 numbers of 63 mm inlets and b) The fire service Inlet should be ·loCated~·;and.,'
for 150 mm rising main, collecting head with
4 numbers of 63 nun inlets should be provided. arranged on street side of the buH4ing'
preferably near main entrance. prominently .
5.3 Wet-Riser-cum-Down-COlileI' marked and without any obstruction so'
that fire service «an connect. hose lines'
5.3.1 A wet·riser·~dow~comer system should' without difficulty.' .
be provided in the type of .buildings indicated in
Table 1 according to the provision mentioned. . c) The inlet should be located inside a box .
However, instead, wet-riser system can be provided made of 1·6 mm mild steel 'plate with ..
with suitable modifications in their requirements openable 4 mm thick glass frontage with
as given in 4.2.6. locking arrangements. The words 'Fire'
Service Inlet' should be written in letters '
5.3.2 The position arid spacing of wet-riserwcum- at least 75.mm in height and 12 mm
in.
width in fluorescent fire red colour (see ~
down-comers should be similar to. wet-riser system
( See 5.2 ). IS 5 : 1978). '

5.4 DOWD-Come~ S)'ste~ 5.6 Internal diameter of rising mains/down-comer·.


mains for various types of building~ should be as
5.4.1 Down"'Comcr system should be provided in given in Table 2.

s
Table 1 Typical Fire Fiptilll JnstaUatlous{ReqaJremeau
( Clauses 4.1.1. 4.1.2. 5.1.1, 5.2.1, 5.3.1. 5.4.1 and 7.2 )

Type of Requirements
SI
No.
Type of the Bulldt..g!
OCCqpancy 1l1stalllatioQ ,--- ..
Water Supply Pump Capacity
,..--------"- , r----------------~.~-------------------~
Underground! Terrace Tank Near the UndergroUlld At the Terrace Leve'
Static Tank Static Tank
(Fire Pump)

(I) (2) (3) (4) (') (6)

RESIDENTIAL BUILDINGS ( A )

a} Lodging or Rooming Houses


( A-I)
Dormitories ( A-3 )
i) Up to IS m in height Nil 200001 Nil Nil Nil

( NOTE - No provisions are necessary for lodging and rooming houses with less than 20 persons and dormitories housing less than 20 persons. )

ii) Above IS m in height but One down-comer SO 0001 10000 1 Nil 450 l/min givins a pre-
not exceeding 24 m per 1 000 ml floor (20000 1 if ssure not less than
area per floor basement ill 300 kPa (3 'kgf/em S )
sprinklered ) at the topmost hyd-
rant

iii) Above 24 m in height but Wet-riser-cum- too 000 J 10000 J 2280 t!min giving a pres- 450 t/min giving a pre-
not e1lceeding 45 m down-comer per (200001 in sure not less tban 300 kPa ssure not less than
1000 mi floor case basement (3 kgf/cm l ) at topmost 300 kPa (3 kgf/cm l )
area per floor is sprinkJered hydrant at the topmost hyd-
.fee 7.12) rant

iv) Above 4S m in height but One wet-riser per 150000 1 NiJ i) 2 28012 820 l/min giving a NJI
not exceeding 60 m 1 OOOm. floor area pressure not less than 300
per floor. Riser kPa (3 kgf/em a) at the top-
shall be fully most hydrant. The pump
charged with ade- provided wiD be of multi-
quate pressure stale, multi-outlet (pre-
at the topmost ferably) type with suction
hydrant and shall aDd delivery sizes not less
be automatic in than 15 em dia with low
operation level riser upto 10 storeys
and higb level riser
delivery for upper floors
ii) Entire buiJdina ii) A stand-bY pump of equal
to be sprinldered capacity driven by diesel
Rl!aiql? PF j:o~nected to
alternate source of power
supply from diesel gene-
ra!qr "~
i) 9~c ~ct~ti,~r ~ I)q ~ i) ~.mp a~ i$3 14eltl l (a) ~iI
'p'er'} OOOm'floor (Iv )( I) above
area, riser shall
be ruUy charsed ii) Same as in Item I (a)
( iv ) ( ii ) above
;:1~suJ:4~~~r~~
topmost hyd-
raDt and shall
be automath: in
operation

Ii) Entire build in.


,~ lie sprinkler-
i:d
(N&TE - Buildiq witb hcjpt exc.edin. U m "ith shopping area exceeding 750 ml, the shopping area to be sprinklered. )

') Ga. or Two Family


Private Dwellings ( A-2 )
J\pp~~~qt ~ouses ( ,..-4 )
i) Up to IS m in h.i~t ~jl Nil Nil !\ljl Nil

(NOTE - Buildlnp of A-2 occupancy above IS m height not to be permitted. )

Ii) Above 1~ mb". n04 ,xceed- One down-comer 50000 1 200001 Nil 450 l/min with pressure
inl~m per I 800 tn' floor not less than 300 kPa
",. per floQf (3 kgf/c~~) at the
topmost hydrant

iii) Above ~ ~ ~ut not exceed- Op, wot-riscr-c/4M- 50000 I 20000 I 1 620 I/min with pressure not 450 Ifmin with pressure
illS 4~ III in h~ilh. (shoppln, 4owri-<:~er per less than 300 kPa (3 kgf/cm t ) not less than 300 kPa
ar~ n~t oit~~e"'II' ~~ ~~) 1 ~ 1Il~ Saor at the topmost h1drant (3 kgf/cm l ) at the
If'. RIC ~eor topmost hydrant

Iv) Above 24 m llut not exceed- One w,t-riser-c"m- 100000 1 200001 i) 2 280 I/min with pressure 900 I/min with pressure
ina 4S m in height (shopping dowD-comcr per not ICisli tl1an 300 kPa not less than 300 kPa
area above 250 m l but not IOOOml floor (3 klf/em-) lit the top- ( 3 kgf/cm l ) at the top-
exceedina7SO ml) area per floor mqllt bydi'\~t !11P$~ pyd~.. ~t

Ii) IUhe basement Cllr fa~~~


~~, :~ '!aO:e ~~e~rY:~
cw.doWu-comerpwnpto
feed sprinltJer" 'system
(ue7.11 )
Table I (Continued)

SI
No.
Type or tbe Bullding/
Occupancy
Type of
InstallatioD .
Reqmemeat.

.
Water Supply Pump <;apacity
Underground/ Terrace Tank Near the Underground At tbo Terrace Level
Static Tank Static Tank.
(Fire Pump)
(I) (2) (3) (4) (5) (6) (1)

v) Above 24 m but not exceed. One wet-riser per 100 000 I 20000 I i) Same as in item I (a) Nfl
ing 45 m in height shopping 1000 m- floor ( iv) ( i ) above
area exceed!na 750 mt but area ( shopping
below 1 000 ml area to be sprin. ii) Sarno as in item I (a)
kiered) ( iv) ( ii ) above
vi) Above 45 m in height but One wet-riser per 1500001 Nil i) Same' as in item I (a) Nil
not exceeding 60 m (with- 1000 ml Boor ( iv ) ( i ) above
out shopping/with shopping area per floor
, not, exceeding 250 mt ) ii) Same aI in item I (a )
( iv) ( ii ) above

vii) Above 45 m in height' but Same as in item I 1500001 Nil i) Same as in item I (a) Nil
not exceeding 60 m with ( a ) ( v ) above ( iv) ( i ) above
shopping area above 250 m'
but not exceeding 750 ml ii) Same as in item I (a)
( iv ) ( ii ) above

vi'li) Above 45 m in height but One wet-riser per ISO 000 1 250001 i) 2 820 l/min with rresaurc Nil
not exceeding 60 m with 1000 rnl floor not less than 300 kPa
shopping area exccedina area per Boor; (3 kgf/cm') at the top.
150ml (shopping area most hydrant
to be sprin.
klered) ii) Same as in item I (a)
( iv ) ( ii ) above
iii) If tbe basemont car park·
Ing area does not ellceed
730 m l , same wet-riser.
cumwdown·comer pump to
feed sprinkler system
(NOTE - Buildings above 60 m in belght not to be permitted.
c) Hotels ( A-5 )
i) Up to '15 m in height with One wet.riser-eum· 50 000] 200001 1 620 I/min with pressure 900 tlmin with pressure
total floor area exceedins down-comer per not less than 300 kPa ( 3 kgfl not less than 300 kPa
300 ml but not more than 1 000 ml of floor em' ) at the topmost hydrant ( 3 kgf/em- ) at tbe top
IOOOm l area per floor most hydrant

( NOTE -- Hotel. with total floor area not exceeding 300 mi. to be exempted (rom provisions of this requirement. )
ii) Up to JS m: in (height with One wet· riser for 100000 I 200001 2280 I/min (2820 tIm in it Nil
total floor area exceeding 750 ml of floor (if sprinklered sprinklered) with presllure
1000 ml area per floor. provided) not less than 300 kPa (3 kgfl
Wet-riser to be eml ) at tho topmost hydrant
fu lIy cba rged
with adequate
pres.sure and
automatic in
operation
iii) Above is m but not exceed- One wet-riser for ISO 000 1+50 000 1 200001 (if i) 2280 Ifmin (2 820 Ifmin Nil
iog 24 m .. 750 ml floor area for sprinkler for sprinklered) jf sprinklered) with pres-
per fioor s,"opping area sure not less tban 300 kPa
and If basement ( 3 kgf/em-) at the top-
used for car park most hydrant

ii) Same as jn Item I (a)


( iv ) ( iI) above

iv) Above 24 m but no(exceed- do 200 000 J +50 000 I do . i) Same as in Item I (c) Nil
ing4S m extra require- ( iii ) ( i ) above
ment for sprink-
Jer f(lr shopping ii) Same as in Item I (c)
area and If base- ( Hi ) ( ii ) abovo
ment used for
car park

v) Above 45 m do do do ·1) 2 820 Ilmln with pressure NH


Dot less than 300 kPa
( 3 kgf/em-) at the top-
most hydrant

ii) Pump of multi-stage type


or alternatively break pres-
sure wet-riser system by
interpolling suction tanks
and pumps at every 15
Ooor level

iii) Stand.by pump of equal


capacity on alternate
SOurce of supply

iv) All the floors to be sprin-


klered. with independent
pump
Table t (Continued)
SI
No.
Type or tbe Bailding!
OecapaDCf
Type of
laataUatioD .
Reqairements
water Supply Pump <;apacit)'
A

Undergroundl Terrace Tank Niar the Ilq4er,f!)uqd At the Terrace Level


Static Tank " ~tatrc'Tahk' "
(Fite Pump)
(1) (2) (3) (4) (5) (6) (7)

II EDUCATIONAL (B) AND INSTITUTIONAL (C) BUILDINGS

a) Buildings other than Hospitals


and Nursing Homes

i) Up to IS m in height Nil so 000 I Nil Nil Nil

( N01 E - Buildings not exceeding 3 storeys and area not exceeding 1 000 ml are exempted. )

ii) Above IS m in height but One wet·riser-cum- :>0 000 I 200001 1 610 1/~iD with prelKure Qot 450 l/min with pressure
npt QlCCf~ing 24 m beight down comer per leu tban 30Q kBa ( 3 kaf/cm-) not less tban 300 kPa
1 000 ml floor area at the topmost hydrant ( 3 kgf/cm ' ) at tbe top.
per floor/block most hydrant

iii) Above 24 m in beight but One wet· riser per 190000 1 200001 i) 2 280 Ifmin with pressure
not exceeding 3S m 1 OOOml floor arca ( ihprinklers Dot less thaD 300 kPa
per Hoor/bloclC are provided ( 3 ' kar/i:~' f 1:\' 'he top.
in basement) most hydra.nt
ii) Spt~q"ler, for ~,~efll"'nt
( ~ee' ~.U ) ' .. T

( NOTE - Buildings above 3' m in height not to be permitted. )

b) Hospitals and Nursing Homes

i) Up to IS m in height One down-comer S,O qqo ~ 200001 Nil 900 Ifmin with pressure
per 1 000 ml floor not less than 300 kPa
ar~ pc~t1oor ( 3 kgf/cmt) at the top-
most hydrant
( NOTE - Ground floor with beds Dot exceeding 100 and ground and two upper floors not exceeding 5() beds are exempted. )

ii) Above IS m in height but One wet~riier-cu",- 200 000 l+SO 000 1 200001 i) 2 280 I/min (2 820 Ifmin 900 lfmin with pres-
not exceeding 24 m down-C9Qler fQf if basement is if sprinklered) with pre- sure not less than 300
1 000.: rnl ftoql' sprinklered ssure not less tban 300 kPa kPa (3 kgf!cm~) at
area per fto~r (3 kgf/em') at tbe top- the topmost hydrant
mqst bydf~~t

2,', ~40 t/min jf ~sem'~t is


i'p{i~~lcre<\ { 3.f~, 74:i )
iii) Above 24 m in height but One wet·rjger 200 0001+50000 I 23 0001 2820 tIm in with pressure not Nil
not cltceedinl 3S m 1000 rna floor (if partially ( if partially less than 300 kPa ( 3 leaf/em' )
area per Boor sprinklered Iprinkiered at the topmost hydrant
sec 7.11) ;sel! 7.11)

( NOTE - Buildings above 35 m in height not to be permitted. )

III ASSEMBL Y BUILDINGS (D)

i) Up to 15 m in height One wet-riser-cum- SO 000 1 200(0) i) 2280 J!min ( 2 820 Ilmin if 900 Jfmin with pressure
down-comer per (2S0001 sprinklered ) with pressure not less than 300 kPa
500 m' 800r arca if partially not Jess than 300 kPa (3 (3 kif/em' ) at the
per floor sprinklered ks!,f/cm') at the topmost topmost hydrant
see 7.11) hydrant
ii) Stand·by pump as alternate
source of power supply
ii) Above 15 m in height but do 100 000 I do i) Same as in item III (i) do
not exceeding 24 m ( i ) above
ii) Same as in item III (i)
(ii ) abovo

iii) Above 24 m in height but One wet-riser per JSOOOO 1 NiJ j) Same as ill item III (i) Nil
not exceeding 35 m 500 ml floor area +50001 (i) above

- per floor. Riser


shall be fully
charged with ad..
equate preSlare
at the topmost
if .prinklered
(llet 7.1l) ii) Same as ill item
( ii) above
III (j)

hydrant and shall


be automatic in
operation
( NOTE - Buildings above 35 m in height'not to be permitted. )

IV BUSINESS (E) AND MERCANTILE (F) BUILDINGS

i) Up to 15 m in height One down-comer SO 000 I 200001 Nil 900 Ilmin with pressure
pcr SOU mB floor not less tban 300 kPa
area per floor (3 kgf/em l ) at the
topmost hydrant
( NOTE - Buildings with ground and up to two floors with total area not exceedlnl2 500 ml is e.llempte<i from above provision.)

ii) Above IS m in height but One wet-riser-cum- UOOOOJ+SOOOI200001 'i} 2 280 1/min with pressure do
not exceeding 24 m down-comer per for basement if (25000 I if par- not less tban 300 kPa
SOO mt floor area sprinklered (see tially .prink. (3 klf/emt) at the top.-
per floor. Riser 7.1.2) lered See 7.11) most hydrant
shall be fuJly
charged
( NOTE -In case of reliable town hydrants system the capacity of water tank c(luld be reduced to tW() tbirds. )
Tablet ( CcmcfutUd) PJ!
SI Type of tbe Bulldlngl Type or Req~ements ~
~o. OCCllp.lRCJ fnatlUlltJol t
water. Supply PlIfTlP ~apacity ...
Underll'ouild/
StalleTallk·
Terrace Tank N!.ar ~~:trc-4:~roupd
(Fire Pump)
AI the Terrace Level
I
(1) (%) (3) (4) (') (6) (7)
iii) Above 24 m in heisbt but Onewet~rlser per 1'0 000 1+ '0 000 I Nil i) Same as In item IV eli) Nil
not ellccedinl45 m $00 tnt 1I00r area if basement is (i) above
~er floor. Riser sprinldcred ( Jeq
shall be fully '7.il) ii) Stand.by pump as alter.
charged with nate source of power
adequate. pres- 511pply
sure at the 101'_
most hydrant
and shall bo
automatic in
operation
iv) Above ., m In height i) do. 200 000 1+ '0 000 I Nil i) 2 820 Ilmin with pressure Nil
if sprinklered not less than 300 kPa
iI) All ~he
. f100TS (ue 7.12) (3 kgf/em') at the topmost
and basemen t & hydrant
N if any to bo
"llnkl!;rcd iI) Pump of multl·stasc type
or alternatively break
preasure wet-riser system
by interposing suction
tanks and pumps at every
IS floor level
Stand·by pump of equal
capacity on alternate soureo
of supply .
V INDUSTRIAL BUILDINGS (G)
i) Up to IS m in height One wet-riser- .50000 I 200001 i) 2280 I/min with pressure 900 Ilmin with pressure
cum-down-comer DOt less than 300 kPa not less than 300 kPa
fot .500 ml 1100r (3 kgf/em') . at the top. (3 k,f/"ml) at the
area per /loor most hydrant topmbst hydrant
( NOTE - Buildings with ground floor only or with ground and floors with total floor area oat exceeding 1 000 ml to be exempted. )
ii) Above IS m III heiaht but Wet-riser 1500001 i) Same as in item V ( i) ( i ) Nil
D{)t exceeding 24 m above '
Ii) Stand-by pump of equal
capacity on alternate
source of power supply
( NOTE - Buildings above 24 m not
and other such structures. ) .
to be permitted with exception or siloS! and processiol installatioQs such as rractional distillation columns
VI STORAGE (H) AND HAZARDoUS (J) BUILDINGS
i) Single storey buildinas Ring main type 100000 1 Nil i) 2280 I/min (2850 J/min Nil
hydrant system ( for agregate if sprinklered) with pre-
with mains. fully area not exceed- ssure not less than 300
charged with ing 1 000 m') kPa (3 kgf/cm ) at the
adequate pressure ISO 000 litres topmost hydrant'
at the remoto ( for area exceed-
hydrant inll OOOm S ) Ii) Stand-bY pump of equal
capacity on alternate
source of power supply if
area exceeds 1 000 m'
Ii) Up to 1S m in height One wet-riser- i) Same as in item IV (i) 900 I/min with pres-
cum-down-comer (i) above sure not less than 300
for SOO ml Boor kPa (3 kgf/cm') at
area per lIoor ii) Same as in item IV ( i) the topmost hydrant
(ii) above

( NOTE - Hazardous buildings above 15 m not to be permitted. )


IS m
iii) Storage buJldingJ above One wet.riser· 150 000 I i) Same as in item IV (i)
in height but not exceedin, cum·down-comer , (i) abovo
24 m for SOO ml floor
area ii) Same as in itom IV ( j )
( ii ) above
~ ( NOTE - StoralO buildinl above 24 m Dot to be permitted. )
IS 38A4 : 198'
Table 2 Size of MaiDs
( Clause S.6 )

Size 01 the Mains Type of Building Height or Building


( 3ee IS 1641 : 1988 )
(1) (2) (3)
100 mm single outlet laodina valves I) Residential buildings (A)
i) Lodging housing
ii) Dormitory
Hi) Family private
dwellings Above 15 m and not exceedins 45 m
iv) Apartment houses
V) With shopping area not
exceeding 250 ml
vi) Hotel buildinls up to Above 15 m in height but not exceed-
3 star grade ing 24 m and area not exceeding
600 rnl per fioor
do II) Educational buildinas (B) Above 15 m but not exceeding 35 m
do III) Institutional buildings (C)
a) For hospitals and unita- Above 15 m but not exceeding 25 an
rium with beds not
exceeding 100
b) For custodial places and Above 15 m but not exceeding 35 m
mental institu ti 001
do IV) Assembly buildings (D) Above 15 m but not exceeding 24 m
and total fioor area not exceedina
500 rnl/floor
do V) Business buildings (E) Above IS m but not exceeding 24 m
do VI) Mercantile buildings (F) Above IS rn but not exceedina 24 m
do VII) Industrial buildings (0) Above IS m but not exceedins 24 m
ISO mm with twin outlet landinl VIII) AU buildings classified Above 4S m
valve. under ( i ) to ( iv )
do IX) All buildings classified Above 24m
under ( v: ) above with shop..
pina area' no~ exceeding lSO ~I
do X) A II buildings classift~ Abpve 24 m and area exceedina 600 m a
under I ( vi ) above
do XI) Hotel buildiDgs of Above 15 m
"
4 star and 5 star grade
do XII) AU buiJdiftgs classified Above 2S m/35 m as applicable
under II and III above
do XIII) AU buildings classified Above 24 m and area exceeding 500
under IV above ml/floor
do XIV) AU buildings classified Above 24 m
under V above
do XV) AU buildings classified Above 24 m but not exceeding3S m
under VI above
do XVI) All buildings classified Above 24 m but not exce~dinl35 m
under vn above
do XVII) 'AU storage buildings (H) Above 10 m but not exceeding 24 m

14
IS 3844 : 1989

,5.7 The rising mains/down-comer mains should 5.13 To avoid ,pilferage, components lik~ 'lan4ing
,l;>e of galvanized iron pipes conforming to medium valves, hose couplings, branch pipes, lugs, etc,
class, of IS 1239 ( Part 1 ) : 1979 and their fit- made of aluminium aHoy_ are recommended
tings shQuld be according to IS 1239 ( Part 2 ): depending on \VeatJ:ter conditions.
198~.
5~14 Unless impracticable by structural considera-
5.8 1he position of risers should be located within tions., the landing valves should always be housed
lobby approach staircase or within· the staircase in hose boxes. Such hose boxes should be made
enclosure wben there is no lobby. However, tbe of MS plates of 2 mm minimum thickness with
risers or the landing valves connected to the risers gJass front. The size of the box should be adequate
should not obstruct the means of escape, neither to accommodate, single/double headed landing
reduce the width of the passage of staircase in any valves with 2 or 4 lengths of fire hose each of 15 m
way. length. and one or two branch pipe,S. The hose
reel mayor may not be accommodated inside the
5.9 Landing valves should be installed on each hose box. If the hose box is- also to accommodate
floor level and on the roof" if accessible, in such the hose reel, it should be of adequate dimensions.
a way that control line of landing valve is 1 to For single headed landing valve, the front opening
1'2 m above the floor level. In the event of pump glass door may be of single leaf, but for double
pressure being excessive at the lower floor leVels landing vaJve, double leaf doors are recommended.
in taU buildings a reducer should be provided in The location of the riser main, along the landing
the landing valves to limit operating pressure to valves and hose reel, etc, should be such as to leave
S',S, kgJcm~ (0'5 N/mm 2 ). The boses, nozzles enough clearance on poth sides and also below
and branch pipes should be kept adjacent to the the landing valve, for smooth operations. ' The
landing valves in wall boxes or in recesses. landing valves should be so fitted to the riser
main, that when the fire hose is connected to it,
5 ..10 In buildings with basements, the internal and charged with water under pressure, it will not
hydrants as well as the hose reel installations fqrm ~ny .kinlc:~ C~nsideratio~ .: should ~lsp .bf;
should be extended to' cover the basement area given to aJJo~: adeq~t,e ,', spaces . aro~.nd the valve
also, over and above sprinkler system, as to permit maintenance and fe~ting.
necessary. ~ ,
5.14.1 For such buildings where narrow space does
not permit fixing of hose boxes, the fire hoses,
5.11 A minimum of two hydrants connected to
internal hydrant system should be provided within and hose reel could be fixed in suitable niches
through which the riser main has been taken up.
the courtyard of the buildings. These should
preferably be sited 'adjacent to the roads along the
In such cases only a glass facing fixed on a frame
of angle iron maybe used. However, these may
compound wan and facilities provided for fire
brigade appliances. be used on1y for residential apartments.
\

S.15 Building fitted with wet-riserIwet-riser-cum":,


5.12 Fire hoses should be of sufficient length to,
carry water from the nearest source of water' down-comer'mains should have access roads to
within 6 m from the boundary line of the building
supply to the: most distant point in the area
covered by a hydrant, by the normal route of and the nearest wet-riser stack should -·notbe
travel. For each internal hydrant ( single headed). more than 15 m from the boundary line of ~be
there should be a total length of not less than_ building.
30 m of 63 mm conforming to Type A of 6 HOSE REELS
IS 636 : 1988 or provided in two lengths of not
more than 15 m each wire wound with coupling 6.1 In addition to wet-riser systems, first aid hose
together with branch pipe conforming to reels should be installed on all floors of buildings
IS 287l : 1983. Spare hose pipes, landing va,lves above 15 m in height. The hose reel should be
lugs, valves wheel, etc. Minimum of 10 percent of directly taken from the wet-riser pipe by means of
each item should always be kept in stock readily a 37 mmsocket and pipe to which the hose reel is
available. Such spare hoses also should be in length to be attached. When taken from the landing valve,
of not more than 15 m complete with coupling. it should be connected to one of the female coupl- ·
Hoses and accessories should be kept- in hose cabi- iogs of the double outlet landing valves of the wet..
net painted fire red ( see IS 5 : 1978 ) and construct- riser installation by means of an adapter. The hose
ed preferably of wood with glass front. Wan boxes reel should conform to Type A of IS 884 : 1985.
constructed of cast iron or sheet iron should be
painted at regular intervals to obviate rusting and 6.2 The hose reel should be sited at each floor
consequent damage to hose. A set of spare rubber level, staircase, fobby or mid-landing adjacent to,
washers packed in French chalk for ,the pu~pose exits in- corridors in such a way that the nozzle of.
of preservation should be kept readily avaiiable. ' the hose can be taken into every room and within
IS 3844 : 1989

6 m of any part of a room leeping in view tbe 7.4 Priming of the main pump and terrace pump
layout and obstructions. The doors provided in case of wet-riser..cum",down...comer, or both the-
for the hose reeJ recesses should be capable of pumps in case of wet-riser instaUation, should
opening to approximately 1800 • When installation be automatic. This can be achieved either by
is in open areas, the position should be above having Booded suction, or by a priming tank with
head height and the nozzle retainer and the inlet foot valve arrangement. However, a flooded
valve should be at about 900 mm above lIoor suction is preferable.
level.. 7.5 Arrangements for draining a wet-ri~er main
6.3 It is essential that the hose reels remain should be incorporated to enable any necessary
unobstructed and that they should be available repairs to be carried out.
for use at aJl times. 7.6 To allow any trapped air .in the rising main
to escape when water is pressurized into system~
6.4 In buildings that have large open tloor areas air release valve should be incorporated above
such as warehouses, the stacking arrangement the highest outJet of each main.
should provide for unobstructed access to the
hose reel. It may also be considered necessary to 7.7 To reduce the risk of hose bursting, arrange-
provide guard rails around the hose reeJ position ments should be made so that when the water is
to prevent stacking adjacent to it, care being taken shut off at the nozzle the static pressure in any
that the guard rails do not obstruct the operation line of hose connected to a landiQg valve does.
of the hOle. not exceed 700 kPa ( 1 kgf/cms ).

6.5 The length of hose reels should be such that no 7.8 To reduce excess pressure at ground floor OF
part of the Boor .so protected is more tha.n 6 III lower tIoors [in excess of 400 kPa ( 4 kgf/cml )
away from the nozzle when the hose reel is fuHy suitable arrangement (orifice flange or other
extended. measure) Jshould be incorporated in the landing
valves.
'-, The bose reels should preferably be installed 7.9 For external hydrants, piping (water main)
in recesses so that they do not form obstructions should be laid preferably underground, to avoid it
on ~ route of escape. getting damaged by moving vehicles, etc. To avoid
'.7 Hose reel brackets should be firmly futed to. rusting. underground pipes should be either of
the wall. cast iron conforming to IS 1536 : 1976 or MS/GI
[ conforming to IS 1239 ( Part 1 ) : 1979 ], in which
7 WATER SUPPLIES AND PUMPING case it should be properly treated with a coat of
ARRANGEMENTS primary paint with two coats of bitumen paint.
7.1 For wet-riser mains and hose reels it is The pipes should be properly supported ot)
essential that pressures and flows should at all pedestals -:- not more than 3 m apart. Under....
times be adequate to serve the designed number . ground pipes shouJd be laid 1 m below to avoid
of jets likely to be used. This ia irrespective of damage during road repair, etc, and at road
or
the source water supply. crossings where beavy vehicles are expected to
pass. it should pass through RCC pipe for addi-
7.2 For wet-riser-cum-down-comer system, two tional protection.
pumps of different capacities (see Table 1 ) one 7.10 AIr Vessel
for the wet-riser and the other for down-comer
system should be instaJled. Tbe pumps should To take care of sma111eakages in the system, an air
be fed from normal source of power supply and vessel of appropriate size should be installed and
also by an alternative source in case of failure of connected to the wet..riser main.
normal source.
7.11 Jockey Pump
7.3 For a wet-riser system, two automatic pumps
should be installed to independently feed the wet- For bigger buildings or major installations, whete'
riser main, one of which should act as stand.. by, chance of such leakage is very considerable. it is.
each pump being supplied by a different source of desirable to install a small pump (using a small
power. The pump shall be arranged so that when motor and 200/300 l/min pump) with pressure
acting as duty-pump, operate automatically when switches for automatic start and stop.
oae or more hydrant is opened thus causing a drop 7.11 Using Wet-Riser System Pump for Partial
in pressure. The stand-by pump should be arranged Spr.inJdel' System
to operate automatically in case of failure of the
duty pump. The system should have an interlock.. In main high rise buiJdings, the basement is used
ing arrangement so that only one of the pumps for car parking/housing transformers/or storages
operate at a time. and other floors may be used as shopping are~

16
:. IS 3844 : 1989

departmental stores, etc, the total area used for that they are in satisfactory condition, so that all
such purpose being small, in such cases, the same equipment is ready for immediate use. Also
wet-riser pump may be used for feeding the fonowing checks should be done:
sprinkler system provided that:
a) Check on the cleanJiness of storage tanks,
a) the total area of the basement to be pro- and
tected is less than 500 m2 •
h} Thorough check of the jockey pumps and
b) the total area utilized as shops depart.. their associated mechanical and electrical
mental stores is less than I 000 m:.l. equipment.
c) the pump bas a capacity of at least 2 850 9.4 Where any outlet on the rising mains is found
l/min with suitable motor. to be defective and no replacement is immediately
d) a separate stand-by pump of equal capacity available, the whole valve assembly should be
is installed, either diesel driven, or by a removed from the main and be replaced with a
generator of appropriate capacity - as blanking off plate or plug, in order that the system
indicated in 4.2.7. remains operative.
8 INITIAL TESTING 9.5 Hose reels should be subjected to regular
inspection to ensure that the inlet valve, the auto"
8.1 The system should be tested before use by matic on/off valve, jf any, glands, tubing and shut
charging with water to a pressure of 700 kPa off nozzle are sound and free from leaKS, and also
( 7 kgf/cm2) measured at the inlet for a period to ensure that the outlet of the nozzle is not
of at least 30 minutes. During this period, an choaked.
inspection of the system should be done to check
tbat no leakage of water is taking place at any of 9.6 If jockey pumps have been installed, such
the joints or landing valves and the pressure in pumps and the associated mechanical and electri-
the system does not drop by more than 50 kPa cal equipments should also be checked.
( 0·5 kgf/cm2 ).
9.7 Once a year the hose reels should be com-
8.2 After the test in accordance with 8.1 is com.. pletely run out and subjected to operational
pleted, a flow teat should be carried out. water pressure to ensure that the hose is in good
condition and that the coupling joints are water-
9 MAINTENANCE tight. A flow test should be carried out to ensure
9.1 Periodic inspections of the viCinity of all that discharge of at least 0"5 lis (30 l/min ) is
hydrants should also be done to ensure that there achieved. If it is not possible to test every hose
are no obstructions impeding accessibility and that reel, at least the highest reel on each rising main
hydrant indicator plates are in position. should be tested.

9.2 Periodic inspection should be done to ensure 9.8 It is essential that all defects are rectified in
that aU isolating valves for systems are kept the shortest possible time, to ensure that the fixed
locked in an 'opent position. Also flow and fire-fighting equipment is restored to a satisfactory
pressure should be checked to ensure that sup- condition in as short a time as possible.
plies have not deteriorated, leakage does not exist
and that the entire system is in satisfactory 9.9 Where, due to unforeseen difficulties it is
condition. necessary to leave an installation not avaiJable
for use, the fire service should be informed
9.3 Inlets, landing valves, drain valves, door immediately in order that alternative arrange-
hinges and locking arrangements to the inlet and ments may be made to cover this deficiency should
landing valve boxes should be inspected every six the need arise. In addition, a suitable notice to
months. Special attention should be given to aU indicate that the installation is not available for
valves, spindles, glands and washers to ensure use should be placed in a prominent position.

17
IS 3844 : 1,.'
ANNEX A
( Clause 2.1 )
. LIST OF REFERRED INDIAN STANDARDS
, "

IS No.. Title IS No. Titl~


IS 5 : 1978 Colours for ready mixed IS 1536 : 1976 Centrifugally cast ( spun)
paints andenameIs ( third iconpces£ure pipes for
revision) waters, gas and sewage
( second revisioR )
IS 636 : 1988 Non~ percola ting flexibJe
fire fighting delivery hose IS 1641 : 1988 Code of practice for fire
( third revision ) safety of buildings ( gene-
ral ) : General principles
IS &84 : 1915 First-aid hose-reel for fire .aDd fire grading and
fighting(fint refisUm ) classification (first
revision)
IS 12)9 (Partt ); 1979 Mild steel tubes, tubulacs
and other WfOUgkt steel IS 1726 ( Part 1 ) : 1974 Cast Iron manhole covers
fittings : Part t Mud steeJ and frames: Part 1
tubes (!lJJUrtb revWon.) General requirements
.( second revision )
IS 1239 ( Part 2 ) : 1982 Mild steel tubes, tubulars
and other wtought steel IS 2871 : 1983 Branch pipe, universal,
fittings: Part 2 Mild steel for fire fightmg purposes
tubulars and other wrought (first re,ilkm )
steel pipe fittings (third IS S290 ': 1983 Landing valves (.co1Ul
revision) I'el'ision)

18
Staodard Mark
The use of the Standard Mark is governed by the provisions of the Bureau of Indian
Standards Act, 1986 and the Rules and Regulations made thereunder. The Standard Mark on
products covered by an Indian Standard conveys the assurance that they have been produced
to comply with the requirements of that standard under a well defined system of inspection,
testing and quality control which is devised and supervised by BIS and operated by the
producer. Standard marked products are also continuously checked by BIS for conformity
to that standard as a further safeguard. Details of conditions 'Under which a licence for the
use of the Standard Mark may be granted to manufacturers or producers may be obtained
from the Burca u of Indian Standards.
Bureau of IadJu StaDdards
DIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods
and attending to connected matters in the country.

Copyright

DIS has the copyright of aU its publications. No part of these publications may be reproduced in
any form without the prior permission in writing of BIS. This does not preclude the free use, in the
course of implementing the standard, of necessary details, such as symboJs and sizes, type or grade
designations. Enquiries relating to copyright be addressed to the Director ( Publications ), BlS.

Revision of Indlau Standards

Indian Standards are reviewed periodicaUy and revised t when necessary and amendments, if any. are
issued from time to time. Users of Indian Standards should ascertain that they are in possession of
the latest amendments or edition Comments on this Indian Standard may be sent to BIS giving the
following reference:

Doc : No. DOC 22 ( 4454 )

Ame.ndmeatl Issued Since PabUcatioa

Amend No. Date of .bsue Text Affected

BUREAU OF INDIAN STANDARDS

Headquarters :
Manak Bhavan, 9 Bahadur Shah Zalar Marg, New Delhi 110002
Telephones: 331 01 31, 331 1375 . Telegrams ~ Manaksanstha
( Common to aU Offices )

Regional Offices : TeJephone

Central: Manak Bhavan, 9 Bahadur Shah Zafar Mara 5331 01 31


NEW DELHI 110002 l331 13 75
Eastern: 1/14 C. I. T . .scheme VII M, V. I. P. Road, Maniktola 318662
CALCUITA 700054
Northern: SeQ 445-446, Sector 35-C, CHANDIGARH 160036 2 1843
Southern: C. I. T. ~ampus, IV Cross Road, MADRAS 600113 41 29 16
Western : Manakalaya, E9 MIDC, Marol, Andheri ( East) 6 32 9295
BOMBAY 400093
Branchea : AHMADABAD. BANGALORE. BHOPAL.·BHUBANESHWARr-COIMBATORE.- .. ·
FARIDABAD. OHAZIABAD. GUWAHATI. HYDERABAD. JAlPUR. KANPUR.
PATNA. TRIVANDRUM.

Printed at Printwell Prlnten~ Deihl. India

You might also like