You are on page 1of 7

PROJE

CT
BUILDING MANAGEMENT SYSTEM

1 of 7
PROJE
CT
BUILDING MANAGEMENT SYSTEM

TECHNICAL DETAILS OF FIELD DEVICES PART TOTAL NO.


S.NO. EQUIPMENT FUNCTION & DESCRIPTION QTY AI AO DI DO SW CABLE TYPE Functional Test Remarks
FIELD DEVICES / INTERFACES NO. OF RUNS
1 DDC-B3-01 - (STORE-1)
FIRE PUMP ROOM MAKE-UP FANS (FPMF-1) 1
Fan Start/stop Command 1 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 1 ok
Fan Air Flow Status 1 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 1 ok
Fan HOA, Auto Status 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1 ok
Fan Trip Alarm 1 Volt free contact from Control Panel to DDC
FIRE PUMP ROOM EXTRACT FANS (FPEF-1) 1
Damper Open/Close Status 1 On/Off Damper Actuator - (By Others) 2 Core, 22 AWG Unshielded 1 ok
Fan Start/stop Command 1 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 1 ok
Fan Air Flow Status 1 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 1 ok
Fan HOA, Auto Status 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1 ok
Fan Trip Alarm 1 Volt free contact from Control Panel to DDC
CAR PARK MAKE-UP FANS (BMF-3) 3
Damper Open/Close Status 3 On/Off Damper Actuator - (By Others) 2 Core, 22 AWG Unshielded 3 OK
Fan Start/stop Command 3 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 3 OK
Fan Air Flow Status 3 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 3 OK
Fan HOA, Auto Status 3 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 3 OK
Fan Trip Alarm 3 Volt free contact from Control Panel to DDC
Fan VFD Speed Control 3 Analog Output by DDC to the VFD
4 Core, 18 AWG Shielded 3 OK
Fan VFD Speed Feedback 3 Analog Input to DDC by VFD
Fire Man Switch Status 3 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 3 OK
CAR PARK EXTRACT FANS (BEF-3) 3
Damper Open/Close Status 3 On/Off Damper Actuator - (By Others) 2 Core, 22 AWG Unshielded 3 ok
Fan Start/stop Command 3 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 3 OK
Fan Air Flow Status 3 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 3 OK
Fan HOA, Auto Status 3 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 3 OK
Fan Trip Alarm 3 Volt free contact from Control Panel to DDC
Fan VFD Speed Control 3 Analog Output by DDC to the VFD
4 Core, 18 AWG Shielded 3 OK
Fan VFD Speed Feedback 3 Analog Input to DDC by VFD
CO SENSOR 4
CO Status 4 CO sensor AX-GS-CM-VL-65 3 Core, 18 AWG Shielded 4 ok
FIRE PUMP SET(1D+1E+1J) 1 Set
Pump Run Status 3 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 3 not terminated
Pump Trip/Fault Alarm 3 Volt free contact from Control Panel to DDC
WATER TRANSFER PUMPS (1D+1S) 1 Set
Pump HOA, Auto Switch Position 2 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 2 ok
Pump Run Status 2 Volt free contact from Control Panel to DDC
Pump Trip Alarm 2 Volt free contact from Control Panel to DDC 4 Core, 22 AWG Unshielded 1 ok
SUMP/DRAIN PUMPS (2D+1S) 1 Set
Pump HOA, Auto Switch Position 3 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 3 ok
Pump Run Status 3 Volt free contact from Control Panel to DDC
Pump Trip Alarm 3 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 3 ok
Sump Pit High Level Alarm 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1 ok
Sump Pit Low Level Alarm 1 Volt free contact from Control Panel to DDC
WATER TANKS 3 Nos
Tank Level 3 0-10 VDC From Pressure Transmitter to DDC AX-LSPTD-V-500M 3 Core, 18 AWG Shielded 3 Tank Plumbing work incomplete
High/low level alarm x Via Software
CHLORINATION UNIT CIRCULATION PUMP SET 1 Set
Pump HOA, Auto Switch Position 2 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 2 ok
Pump Run Status 2 Volt free contact from Control Panel to DDC
Pump Trip Alarm 2 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 2 ok
IRRIGATION PUMPS 1
Pump HOA, Auto Switch Position 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1 ok
Pump Run Status 1 Volt free contact from Control Panel to DDC
Pump Trip Alarm 1 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 1 ok
GARBAGE SYSTEM 1
System On/off Status 1 Volt free contact from Panel to DDC
4 Core, 22 AWG Unshielded 1 panel not installed
System Trip Alarm 1 Volt free contact from Panel to DDC
1 TOTAL IO POINTS 13 6 68 8 67
2 DDC-B1-01 - (AHU ROOM)
AIR HANDLING UNIT - (AHU-01) 1
Pre Filter Status 1 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 1 ok
Bag Filter Status 1 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 1 ok
On Coil Temperature 1 Duct Temperature Sensor EGT447F102 2 Core, 18 AWG shielded 1 ok
Cooling Coil Control Valve Control & Feedback 1 1 Cooling Valves With Modulating Actuators 4 Core, 18 AWG Shielded 1 ok
EGT446F102+
Supply Chilled Water Temperatures 1 Immersion Temperature Sensor 2 Core, 18 AWG shielded 1 ok
0391022100
EGT446F102+
Return Chilled Water Temperatures 1 Immersion Temperature Sensor 2 Core, 18 AWG shielded 1 ok
0391022100
Off Coil Temperature & Humidity 2 Duct Temperature & Humidity Sensor EGH111F031 4 Core, 18 AWG Shielded 1 ok
Supply Fan Start/stop Command 1 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 1 ok

2 of 7
PROJE
CT
BUILDING MANAGEMENT SYSTEM

TECHNICAL DETAILS OF FIELD DEVICES PART TOTAL NO.


S.NO. EQUIPMENT FUNCTION & DESCRIPTION QTY AI AO DI DO SW CABLE TYPE Functional Test Remarks
FIELD DEVICES / INTERFACES NO. OF RUNS
Supply Fan Air Flow Status 1 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 1 ok
Supply Fan HOA, Auto Status 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1 ok
Supply Fan Trip Alarm 1 Volt free contact from Control Panel to DDC
Supply Air Temperature & Humidity 2 Duct Temperature & Humidity Sensor EGH111F031 4 Core, 18 AWG Shielded 1 ok
Space Temperature Sensor 1 Space Temperature Sensor EGT430F102 2 Core, 18 AWG shielded 1 not installed
Return Air Temperature 1 Duct Temperature Sensor EGT447F102 2 Core, 18 AWG shielded 1 ok
Supply Air Discharge Pressure 1 Air differential Pressure Sensor 984M.54370 3 Core, 18 AWG Shielded 1 ok
Fire Alarm Status 1 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 1 ok
CAR PARK EXTRACT FANS (BEF-1) 3
Damper Open/Close Status 3 On/Off Damper Actuator - (By Others) 2 Core, 22 AWG Unshielded 3 ok
Fan Start/stop Command 3 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 3 ok
Fan Air Flow Status 3 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 3 ok
Fan HOA, Auto Status 3 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 3 ok
Fan Trip Alarm 3 Volt free contact from Control Panel to DDC
Fan VFD Speed Control 3 Analog Output by DDC to the VFD
4 Core, 18 AWG Shielded 3 ok
Fan VFD Speed Feedback 3 Analog Input to DDC by VFD
CO SENSOR 4
CO Status 4 CO sensor AX-GS-CM-VL-65 3 Core, 18 AWG Shielded 4 ok
EXTRACT FAN - (GNEF-1) 1
Fan Start/stop Command 1 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 1 ok
Fan Air Flow Status 1 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 1 ok
Fan HOA, Auto Status 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1 ok
Fan Trip Alarm 1 Volt free contact from Control Panel to DDC
GENERATOR 1
Generator On/ off Status 1 Volt free contact from Panel to DDC
4 Core, 22 AWG Unshielded 1 ok
Generator Common Fault 1 Volt free contact from Panel to DDC
Battery Status 1 Volt free contact from Panel to DDC 2 Core, 22 AWG Unshielded 1 ok
Generator Fuel Tank Level 1 0-10V from Panel to DDC 2 Core, 18 AWG shielded 1 not terminated
From Basement-2
CAR PARK MAKE-UP FANS (BMF-2) 3
Damper Open/Close Status 3 On/Off Damper Actuator - (By Others) 2 Core, 22 AWG Unshielded 3 ok
Fan Start/stop Command 3 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 3 ok
Fan Air Flow Status 3 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 3 ok
Fan HOA, Auto Status 3 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 3 ok
Fan Trip Alarm 3 Volt free contact from Control Panel to DDC
Fan VFD Speed Control 3 Analog Output by DDC to the VFD
4 Core, 18 AWG Shielded 3 ok
Fan VFD Speed Feedback 3 Analog Input to DDC by VFD
Fire Man Switch Status 3 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 3 ok
CAR PARK EXTRACT FANS (BEF-2) 3
Damper Open/Close Status 3 On/Off Damper Actuator - (By Others) 2 Core, 22 AWG Unshielded 3 ok
Fan Start/stop Command 3 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 3 ok
Fan Air Flow Status 3 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 3 ok
Fan HOA, Auto Status 3 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 3 ok
Fan Trip Alarm 3 Volt free contact from Control Panel to DDC
Fan VFD Speed Control 3 Analog Output by DDC to the VFD
4 Core, 18 AWG Shielded 3 ok
Fan VFD Speed Feedback 3 Analog Input to DDC by VFD
CO SENSOR 4
CO Status 4 CO sensor AX-GS-CM-VL-65 3 Core, 18 AWG Shielded 4 ok
2 TOTAL IO POINTS 29 10 51 11 77
3 DDC-GF-01 - (FIRE COMMAND ROOM)
AUTOMTIC GREASE TRAP 3 Panel not installed
Healthy Status 3 Volt free contact from Panel to DDC
4 Core, 22 AWG Unshielded 3 Continuity OK 1/3 panels terminated
Fault Alarm 3 Volt free contact from Panel to DDC
FIRE ALARM PANELS 1
Panel On/off Status 1 Volt free contact from Panel to DDC 2 Core, 22 AWG Unshielded 1 Continuity ok Termination not done
Panel Healthy Status 1 Volt free contact from Panel to DDC
4 Core, 22 AWG Unshielded 1 Continuity ok Termination not done
Panel Fault Alarm 1 Volt free contact from Panel to DDC
LPG LEAK DETECTION PANEL 1
Panel Healthy Status 1 Volt free contact from Panel to DDC 2 Core, 22 AWG Unshielded 1 Continuity ok Panel not installed
LV PANEL - (MDB-1, MDB-2 & MDB-E) 3 Access not available for testing
Incoming Breaker On/off Status 4 Volt free contact from Panel to DDC 2 Core, 22 AWG Unshielded 4
Outgoing Breakersr On/off Status 25 Volt free contact from Panel to DDC 2 Core, 22 AWG Unshielded 25
CAPACITOR BANK 2
On/Off Status 2 Volt free contact from Panel to DDC 2 Core, 22 AWG Unshielded 2 Access not available for testing
AUTO TRANSFER SWITCH 1 ATS not available in site
ATS Common Fault 1 Volt free contact from Panel to DDC 2 Core, 22 AWG Unshielded 1
ATS Change Over Fault 1 Volt free contact from Panel to DDC
4 Core, 22 AWG Unshielded 1
ATS Transfer Override 1 Volt free contact from Panel to DDC
MAIN UPS 1
UPS On/off Status 1 Volt free contact from Panel to DDC
4 Core, 22 AWG Unshielded 1 Continuity ok termination not done
UPS Fault Status 1 Volt free contact from Panel to DDC

3 of 7
PROJE
CT
BUILDING MANAGEMENT SYSTEM

TECHNICAL DETAILS OF FIELD DEVICES PART TOTAL NO.


S.NO. EQUIPMENT FUNCTION & DESCRIPTION QTY AI AO DI DO SW CABLE TYPE Functional Test Remarks
FIELD DEVICES / INTERFACES NO. OF RUNS
UPS Low Battery Status 1 Volt free contact from Panel to DDC 2 Core, 22 AWG Unshielded 1 Continuity ok termination not done
SELF MONITORING PANEL FOR EM LIGHT (CMP) 1
Panel Healthy Status 1 Volt free contact from Panel to DDC 2 Core, 22 AWG Unshielded 1 continuity ok Termination not done
3 TOTAL IO POINTS 0 0 48 0 42
4 DDC-GF-02 - (FIRE COMMAND ROOM)
EXTRACT FAN - (FCEF-1) 1
Fan Start/stop Command 1 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 1 ok
Fan Air Flow Status 1 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 1 ok
Fan HOA, Auto Status 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1 ok
Fan Trip Alarm 1 Volt free contact from Control Panel to DDC
FIRE COMMAND ROOM MAKEUP FAN - (FCMF-1) 1
Fan Start/stop Command 1 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 1 ok
Fan Air Flow Status 1 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 1 ok
Fan HOA, Auto Status 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1 ok
Fan Trip Alarm 1 Volt free contact from Control Panel to DDC
GATE BARRIERS 4 Cable not pulled
Gate Barrier On/off Status 4 Volt free contact from Panel to DDC
4 Core, 22 AWG Unshielded 4
Gate Barrier Healthy Status 4 Volt free contact from Panel to DDC
SECURITY CCTV SYSTEM 1
Panel Healthy Status 1 Volt free contact from Panel to DDC
4 Core, 22 AWG Unshielded 1 Continuity ok Termination not done
Panel Common Fault Alarm 1 Volt free contact from Panel to DDC
SECURITY ACCESS CONTROL SYSTEM 1
Panel Healthy Status 1 Volt free contact from Panel to DDC 2 Core, 22 AWG Unshielded 1 Continuity ok Termination not done
PUBLIC ADDRESS SYSTEM 1 Cable not pulled
Panel Healthy Status 1 Volt free contact from Panel to DDC 2 Core, 22 AWG Unshielded 1
CO2 SENSOR (ATRIUM) 1
CO2 Reading 1 CO2 Sensor EGQ220F031 3 Core, 18 AWG Shielded 1 ok
4 TOTAL IO POINTS 1 0 18 2 14
5 DDC-GF-03 - (ETS PUMP ROOM)
SECONDARY CHILLED WATER PUMPS (SP-1, 2, 3 & 4) 4
Pump VFD Enable/Disable Command 4 Volt Free Contact by DDC to the Panel 2 Core, 22 AWG Unshielded 4 ok
Pump Run Status 4 Volt free Contact to DDC from Liquid DP Switch DSD137F002 2 Core, 22 AWG Unshielded 4 ok
Pump H/O/A Switch Position 4 Volt Free Contact to DDC From the Panel
4 Core, 22 AWG Unshielded 4 ok
Pump VFD Trip Alarm 4 Volt Free Contact to DDC From the Panel
Pump VFD Speed Control 4 Analog Output by DDC to the VFD
4 Core, 18 AWG Shielded 4 ok
Pump VFD Speed Feedback 4 Analog Input to DDC by VFD
EGT447F102+
CHW Common Supply Headder Temperature 1 Immersion Temperature Sensor 2 Core, 18 AWG shielded 1 ok 2 nos. provided for before and after bypass
0391022200
EGT447F102+
CHW Common Return Headder Temperature 1 Immersion Temperature Sensor 2 Core, 18 AWG shielded 1 ok 2 nos. provided for before and after bypass
0391022200
Flow Meter 1 Flow Meter 3 Core, 18 AWG Shielded 1 Pulled to basement DDC
CHW Index Differential pressure 1 Liquid Differential Pressure Sensor DSDU103F021 3 Core, 18 AWG Shielded 1 ok
Motorised Valves With Modulating Actuators - (By
Minimum Flow Bypass Modulating Valve 1 1 4 Core, 18 AWG Shielded 1 required to configure the valve for Voltage
Others)
PRESSURIZATION UNIT 1
Common Fault Alarm 1 Volt Free Contact to DDC From the Panel
4 Core, 22 AWG Unshielded 1 ok point changed to trip status
Run Status 1 Volt Free Contact to DDC From the Panel
Supply Pressure 1 Liquid Pressure Sensor DSU216F002 3 Core, 18 AWG Shielded 1 ok
CHEMICAL DOSING PUMPS 1
Common Fault Alarm 1 Volt Free Contact to DDC From the Panel
4 Core, 22 AWG Unshielded 1 ok
Run Status 1 Volt Free Contact to DDC From the Panel
5 TOTAL IO POINTS 10 5 16 4 24
6 DDC-P3-01 - (AHU ROOM)
AIR HANDLING UNIT 1
Pre Filter Status 1 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 1 ok
Bag Filter Status 1 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 1 ok
On Coil Temperature 1 Duct Temperature Sensor EGT447F102 2 Core, 18 AWG shielded 1 signal not received
Cooling Coil Control Valve Control & Feedback 1 1 Cooling Valves With Modulating Actuators 4 Core, 18 AWG Shielded 1 ok
EGT446F102+
Supply Chilled Water Temperatures 1 Immersion Temperature Sensor 2 Core, 18 AWG shielded 1 ok
0391022100
EGT446F102+
Return Chilled Water Temperatures 1 Immersion Temperature Sensor 2 Core, 18 AWG shielded 1 signal not received
0391022100
Off Coil Temperature & Humidity 2 Duct Temperature & Humidity Sensor EGH111F031 4 Core, 18 AWG Shielded 1 signal not received
Supply Fan Start/stop Command 1 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 1 ok
Supply Fan Air Flow Status 1 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 1 ok
Supply Fan HOA, Auto Status 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1 ok
Supply Fan Trip Alarm 1 Volt free contact from Control Panel to DDC
Supply Air Temperature & Humidity 2 Duct Temperature & Humidity Sensor EGH111F031 4 Core, 18 AWG Shielded 1 ok
Space Temperature Sensor 1 Space Temperature Sensor EGT430F102 2 Core, 18 AWG shielded 1 ok
Return Air Temperature 1 Duct Temperature Sensor EGT447F102 2 Core, 18 AWG shielded 1 ok
Supply Air Discharge Pressure 1 Air differential Pressure Sensor 984M.54370 3 Core, 18 AWG Shielded 1 ok

4 of 7
PROJE
CT
BUILDING MANAGEMENT SYSTEM

TECHNICAL DETAILS OF FIELD DEVICES PART TOTAL NO.


S.NO. EQUIPMENT FUNCTION & DESCRIPTION QTY AI AO DI DO SW CABLE TYPE Functional Test Remarks
FIELD DEVICES / INTERFACES NO. OF RUNS
Fire Alarm Status 1 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 1 ok
From Podium-1 ok
DX UNITS 2 not terminated
Run Status 2 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 2
Trip Alarm 2 Volt free contact from Control Panel to DDC
From Podium-2
DX UNITS 1 not terminated
Run Status 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1
Trip Alarm 1 Volt free contact from Control Panel to DDC
From Concourse Level
CO2 SENSOR (Restaurant) 1 not installed
CO2 Reading 1 CO2 Sensor EGQ220F031 3 Core, 18 AWG Shielded 1
6 TOTAL IO POINTS 12 1 12 1 19
7 DDC-LRF-01
GARBAGE EXTRACT FAN - (GEF-1) 1
Fan Start/stop Command 1 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 1 ok
Fan Air Flow Status 1 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 1 ok
Fan HOA, Auto Status 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1 ok
Fan Trip Alarm 1 Volt free contact from Control Panel to DDC
From Upper Roof
CORRIDOR SMOKE MAKE-UP FANS - (MAF-1) 1
Damper Open/ Close Status 1 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 1 ok
Fan Air Flow Status 1 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 1 ok
Fan HOA, Auto Status 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1 ok
Fan Trip Alarm 1 Volt free contact from Control Panel to DDC
Fire Alarm Status 1 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 1 ok
CORRIDOR SMOKE EXTRACT FANS - (SEF-1, 2) 2
Damper Open/ Close Status 2 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 2 ok
Fan Air Flow Status 2 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 2 ok
Fan HOA, Auto Status 2 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 2 ok
Fan Trip Alarm 2 Volt free contact from Control Panel to DDC
Fire Alarm Status 2 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 2 ok
STAIRCASE PRESSURIZATION FANS - (SP-1, 2) 2
Damper Open/ Close Status 2 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 2 ok
Pressure Relif Damper Open/ Close Status 2 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 2 ok
Fan Air Flow Status 2 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 2 ok
Fan HOA, Auto Status 2 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 2 ok
Fan Trip Alarm 2 Volt free contact from Control Panel to DDC
Fire Alarm Status 2 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 2 ok
Pressure Sensor Reading 2 0-10V Signal from DPT Tto VFD 984M.52370 3 Core, 18 AWG Shielded 2 not terminated
LIFT PRESSURIZATION FANS - (LPF-1, 1A & LPF-2) 3
Damper Open/ Close Status 3 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 3 ok
Pressure Relif Damper Open/ Close Status 3 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 3 ok
Fan Air Flow Status 3 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 3 not terminated
Fan HOA, Auto Status 3 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 3 ok
Fan Trip Alarm 3 Volt free contact from Control Panel to DDC
Fire Alarm Status 3 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 3 ok
Pressure Sensor Reading 3 0-10V Signal from DPT Tto VFD 984M.52370 3 Core, 18 AWG Shielded 3 not terminated
7 TOTAL IO POINTS 5 0 48 1 45
8 DDC-LRF-02
FRESH AIR HANDLING UNIT - (FAHU-1) 1 online values to be tested after Termination complete
Outdoor Air Temperature X Outside Temperature & Humidity Sensor power provided
Fresh Air Damper Open/Close Command 1 On/Off Damper Actuator - (By Others)
4 Core, 22 AWG Unshielded 1
Fresh Air Damper Open/Close Status 1 On/Off Damper Actuator - (By Others)
Extract Air Damper Open/Close Command 1 On/Off Damper Actuator - (By Others)
4 Core, 22 AWG Unshielded 1
Extract Air Damper Open/Close Status 1 On/Off Damper Actuator - (By Others)
Pre Filter Status 1 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 1
Bag Filter Status 1 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 1
On Recovery Wheel Temperature & Humidity 2 Duct Temperature & Humidity Sensor EGH111F031 4 Core, 18 AWG Shielded 1
Off Recovery Wheel Temperature & Humidity 2 Duct Temperature & Humidity Sensor EGH111F031 4 Core, 18 AWG Shielded 1
Cooling Coil Control Valve Control & Feedback 1 1 Cooling Valves With Modulating Actuators 4 Core, 18 AWG Shielded 1
EGT446F102+
Supply Chilled Water Temperatures 1 Immersion Temperature Sensor 2 Core, 18 AWG shielded 1
0391022100
EGT446F102+
Return Chilled Water Temperatures 1 Immersion Temperature Sensor 2 Core, 18 AWG shielded 1
0391022100
On Coil Temperature & Humidity 2 Duct Temperature & Humidity Sensor EGH111F031 4 Core, 18 AWG Shielded 1
Supply Fan Start/stop Command 1 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 1
Supply Fan Air Flow Status 1 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 1
Supply Fan HOA, Auto Status 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1
Supply Fan Trip Alarm 1 Volt free contact from Control Panel to DDC
Supply Air Flow Monitoring 1 Air Flow Measuring Device - (By Others) 4 Core, 18 AWG Shielded 1

5 of 7
PROJE
CT
BUILDING MANAGEMENT SYSTEM

TECHNICAL DETAILS OF FIELD DEVICES PART TOTAL NO.


S.NO. EQUIPMENT FUNCTION & DESCRIPTION QTY AI AO DI DO SW CABLE TYPE Functional Test Remarks
FIELD DEVICES / INTERFACES NO. OF RUNS
Return Air Temperature 1 Duct Temperature Sensor EGT447F102 2 Core, 18 AWG shielded 1
Return Filter Status 1 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 1
Extract Fan Start/stop Command 1 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 1
Extract Fan Air Flow Status 1 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 1
Extract Fan HOA, Auto Status 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1
Extract Fan Trip Alarm 1 Volt free contact from Control Panel to DDC
Energy Recovery Wheel Start/stop Command 1 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 1
Energy Recovery Wheel HOA, Auto Status 1 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 1
Energy Recovery Wheel Motor Run Status 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1
Energy Recovery Wheel Trip Alarm 1 Volt free contact from Control Panel to DDC
Fire Alarm Status 1 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 1
MAKEUP AIR HANDLING UNIT - (MAHU-1, 2 & 3) 3 Equipment not installed
Fresh Air Damper Open/Close Command 3 On/Off Damper Actuator - (By Others)
4 Core, 22 AWG Unshielded 3
Fresh Air Damper Open/Close Status 3 On/Off Damper Actuator - (By Others)
Pre Filter Status 3 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 3
Bag Filter Status 3 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 3
On Coil Temperature 3 Duct Temperature Sensor EGT447F102 2 Core, 18 AWG shielded 3
Cooling Coil Control Valve Control & Feedback 3 3 Cooling Valves With Modulating Actuators 4 Core, 18 AWG Shielded 3
Supply Fan Start/stop Command 3 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 3
Supply Fan Air Flow Status 3 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 3
Supply Fan HOA, Auto Status 3 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 3
Supply Fan Trip Alarm 3 Volt free contact from Control Panel to DDC
Supply Fan Trip Alarm 6 Duct Temperature & Humidity Sensor EGH111F031 4 Core, 18 AWG Shielded 3
Supply Air Discharge Pressure 3 Air differential Pressure Sensor 984M.54370 3 Core, 18 AWG Shielded 3
Fire Alarm Status 3 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 3
ECOLOGY UNIT - (ECU-1, 2 & 3) 3 Equipment not installed
Exhaust Air Damper Open/Close Command 3 On/Off Damper Actuator - (By Others)
4 Core, 22 AWG Unshielded 3
Exhaust Air Damper Open/Close Status 3 On/Off Damper Actuator - (By Others)
Electrostatic Precipitator Washing Cycle On Status 3 On/Off Damper Actuator - (By Others)
4 Core, 22 AWG Unshielded 3
Electrostatic Precipitator Panel Healthy Status 3 On/Off Damper Actuator - (By Others)
Electrostatic Precipitator Dirty Status 3 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 3
Pre Filter Status 3 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 3
Bag Filter Status 3 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 3
Carbon Filter Status 3 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 3
Fan Start/stop Command 3 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 3
Fan Air Flow Status 3 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 3
Fan HOA, Auto Status 3 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 3
Fan VFD Trip Alarm 3 Volt free contact from Control Panel to DDC
Fan VFD Speed Control 3 Analog Output by DDC to the VFD
4 Core, 18 AWG Shielded 3
Fan VFD Speed Feedback 3 Analog Input to DDC by VFD
Earth Leakage Status 3 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 3
Local On/ Off Switch 3 Volt free contact from Control Panel to DDC
Fire Man Switch Status 3 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 3
LIFT PRESSURIZATION FANS - (LPF-3) 1
Damper Open/ Close Status 1 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 1
Pressure Relif Damper Open/ Close Status 1 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 1
Fan Air Flow Status 1 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 1
Fan HOA, Auto Status 1 Volt free contact from Control Panel to DDC status cable connected to power supply causing controller damage
4 Core, 22 AWG Unshielded 1
Fan Trip Alarm 1 Volt free contact from Control Panel to DDC
Fire Alarm Status 1 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 1
Pressure Sensor Reading 1 0-10V Signal from DPT Tto VFD 984M.52370 3 Core, 18 AWG Shielded 1
DOMESTIC HEAT EXCHANGER 1 sensors not installed
EGT446F102+
Secondary Side - Supply Water Temperature 1 Immersion Temperature Sensor 2 Core, 22 AWG Shielded 1
0391022100
EGT446F102+
Secondary Side - Return Water Temperature 1 Immersion Temperature Sensor 2 Core, 22 AWG Shielded 1
0391022100
Motorised Valves With Modulating Actuators - (By
Primary Side - Supply 2-Way Valve Control & Feedback 1 1 4 Core, 22 AWG Shielded 1
Others)
WATER BOOSTER PUMP VFD (1D+1S) - (BP-RF-01) 1 Set
Pump HOA, Auto Switch Position 2 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 2 ok
Pump Run Status 2 Volt free contact from Control Panel to DDC
Pump Trip Alarm 2 Volt free contact from Control Panel to DDC 4 Core, 22 AWG Unshielded 1 ok
Pump VDF Feedback 2 0-10V from Control Panel to DDC 4 Core, 18 AWG Shielded 1 ok
Pump VFD Fault Status 2 Volt free contact from Control Panel to DDC 4 Core, 22 AWG Unshielded 1 ok
Pump Start/Stop Command 2 Volt free contact from DDC to Control Panel 4 Core, 22 AWG Unshielded 1 only 1 cmd for both pumps
Supply Pressure 1 Liquid Pressure Sensor DSU216F002 3 Core, 18 AWG Shielded 1 not installed
CIRCULATION PUMP SET (1D+1S) - (CP-RF-01) 1
Pump Start/Stop Command 1 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 1 ok
Pump HOA, Auto Switch Position 1 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 1 ok
Pump Run Status 1 Volt free contact from Control Panel to DDC
Pump Trip Alarm 1 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 1 ok

6 of 7
PROJE
CT
BUILDING MANAGEMENT SYSTEM

TECHNICAL DETAILS OF FIELD DEVICES PART TOTAL NO.


S.NO. EQUIPMENT FUNCTION & DESCRIPTION QTY AI AO DI DO SW CABLE TYPE Functional Test Remarks
FIELD DEVICES / INTERFACES NO. OF RUNS
GRP WATER TANKS WITH PARTITION 1 No
Tank Level 2 0-10 VDC From Pressure Transmitter to DDC AX-LSPTD-V-500M 3 Core, 18 AWG Shielded 2 sensor not installed
High/low level alarm x Via Software
LIFT CONTROL PANEL 9
Lift Healthy Status 9 Volt free contact from Panel to DDC
4 Core, 22 AWG Unshielded 9 termination pending from lift supplier
Lift Common Fault Alarm 9 Volt free contact from Panel to DDC
Lift Cabin Call Alarm Status 9 Volt free contact from Panel to DDC 2 Core, 22 AWG Unshielded 9
termination pending from lift supplier
From Concourse Level
CO2 SENSOR (Restaurant) 1
CO2 Reading 1 CO2 Sensor EGQ220F031 3 Core, 18 AWG Shielded 1 not installed
8 TOTAL IO POINTS 39 8 119 20 132
9 ZA-L01-OS-04

AIR HANDLING UNIT - (L1-BR-01, L1-BR-02, L1-BR-03, L1-BR-04 & L1-BR-05) 5


Pre Filter Status 5 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 5
Bag Filter Status 5 Air differential pressure switch 930.83/6555 2 Core, 22 AWG Unshielded 5
On Coil Temperature 5 Duct Temperature Sensor EGT447F102 2 Core, 18 AWG shielded 5
Cooling Coil Control Valve Control & Feedback 5 5 Cooling Valves With Modulating Actuators 4 Core, 18 AWG Shielded 5
EGT446F102+
Supply Chilled Water Temperatures 5 Immersion Temperature Sensor 2 Core, 18 AWG shielded 5
0391022100
EGT446F102+
Return Chilled Water Temperatures 5 Immersion Temperature Sensor 2 Core, 18 AWG shielded 5
0391022100
Off Coil Temperature & Humidity 10 Duct Temperature & Humidity Sensor EGH111F031 4 Core, 18 AWG Shielded 5
work not started
Supply Fan Start/stop Command 5 Volt free contact from DDC to Control Panel 2 Core, 22 AWG Unshielded 5
Supply Fan Air Flow Status 5 Air differential pressure switch 930.80/6555 2 Core, 22 AWG Unshielded 5
Supply Fan HOA, Auto Status 5 Volt free contact from Control Panel to DDC
4 Core, 22 AWG Unshielded 5
Supply Fan Trip Alarm 5 Volt free contact from Control Panel to DDC
Supply Air Temperature & Humidity 10 Duct Temperature & Humidity Sensor EGH111F031 4 Core, 18 AWG Shielded 5
Space Temperature Sensor 5 Space Temperature Sensor EGT430F102 2 Core, 18 AWG shielded 5
Return Air Temperature 5 Duct Temperature Sensor EGT447F102 2 Core, 18 AWG shielded 5
Supply Air Discharge Pressure 5 Air differential Pressure Sensor 984M.54370 3 Core, 18 AWG Shielded 5
Fire Alarm Status 5 Volt free contact from Control Panel to DDC 2 Core, 22 AWG Unshielded 5
9 TOTAL IO POINTS 55 5 30 5 75
FAN COIL UNIT - COMMUNICATING TYPE 150
Space/ Return Temperature 150 Room Thermostat STR-T15-MLNE-FV
Temperature Setpoint X Included via Software
Fan Speed Control 150 0‐10V to FCU from FCU Controller
Cooling Coil Valve Control 150 0‐10V to Actuator from FCU Controller
THIRD PARTY SOFTWARE INTEGRATION INTEGRATION PROTOCOL
HEX (COLD SIDE) PRIMARY SIDE INTEGRATION WITH ETS/PLC-B1 1 No BACnet/IP
FIRE ALARM SYSTEM 1 No BACnet/IP
MSFD MONITORING/MOTORIZED DAMPERS / FIRE DAMPERS VIA FIRE
103 Nos BACnet/IP Via FACP
ALARM
CLOSE CONTROL UNITS 3 Nos BACnet/IP
GENERATOR 1 No Modbus
LIGHTING CONTROL SYSTEM/EMERGENCY LIGHTING CONTROL SYSTEM 1 No BACnet/IP
CENTRAL BATTERY SYSTEM 1 No BACnet/IP
24/7 CIVIL DEFENSE PANEL 1 No BACnet/IP
ACB 8 Nos BACnet/IP
LEAK DETECTION SYSTEM 3 Nos BACnet/IP
DX FCU 2 Nos BACnet/IP
VFD 29 Nos Modbus
UPS 1 No BACnet/IP

7 of 7