SAFETY INFORMATION
PLEASE READ THIS MANUAL
™
BEFORE INSTALLING AND
USING APPLIANCE
WARNING!
IF THE INFORMATION IN THIS Builder Rear Vent
MANUAL IS NOT FOLLOWED
EXACTLY, A FIRE OR EXPLO- Direct Vent
SION MAY RESULT CAUSING
PROPERTY DAMAGE, PER- Models: 33LDVR, 36LDVR,
SONAL INJURY OR LOSS OF
LIFE. 39LDVR, 43LDVR
FOR YOUR SAFETY
Installation and service must
be performed by a qualified
installer, service agency or
the gas supplier.
� � � � � ��
� � �� � � � � �
Table of Contents
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS
BEFORE USING APPLIANCE.
Thank you and congratulations on your purchase of a CFM Specialty Home Products fireplace.
IMPORTANT: Read all instructions and warnings carefully before starting installation.
Failure to follow these instructions fully may result in a possible fire hazard and will void the warranty.
Installation & Operating Instructions
Important Curing/Burning Instructions ................................................................................. 3
Locating Your Fireplace ....................................................................................................... 3
Fireplace Dimensions .......................................................................................................... 4
Clearance to Combustibles ................................................................................................. 5
Mantels ............................................................................................................................... 5
Hearth ............................................................................................................................... 5
Framing and Finishing ......................................................................................................... 6
Final Finishing ..................................................................................................................... 6
Gas Specifications............................................................................................................... 6
Gas Inlet and Manifold Pressures ....................................................................................... 6
High Elevations ................................................................................................................... 6
Gas Line Installation ............................................................................................................ 7
Remote ON/OFF Switch...................................................................................................... 7
Alternate Switch Location .................................................................................................... 7
EB-1 Electrical Box.............................................................................................................. 8
Electronic Gas Control Valve ............................................................................................... 8
General Venting Information
General Venting................................................................................................................... 9
General Venting Information-Termination Location ........................................................... 10
General Information Assembling Vent Pipes ..................................................................... 11
How to Use the Vent Graph............................................................................................... 12
Rear Wall Venting Applications & Installation .................................................................... 12
Vertical Sidewall Applications & Installation ...................................................................... 14
Below Grade Installation ................................................................................................... 17
Vertical Through-the-Roof Applications & Installation ....................................................... 18
Venting Components ......................................................................................................... 21
Operating Instructions
Glass Information .............................................................................................................. 22
Louvre Removal ................................................................................................................ 22
Window Frame Assembly Removal................................................................................... 22
Glass Cleaning .................................................................................................................. 22
Installation of Logs, Lava Rock & Ember Material............................................................. 23
Flame & Temperature Adjustment ..................................................................................... 25
Flame Characteristics........................................................................................................ 25
Lighting and Operating Instructions................................................................................... 26
Troubleshooting ................................................................................................................. 28
Fuel Conversion Instructions ............................................................................................. 30
Maintenance
Cleaning the Standing Pilot Control System ..................................................................... 31
Replacement Parts ..................................................................................................................... 32
Optional Accessories
Fan Kits ............................................................................................................................. 35
Ceramic Refractory Lining ................................................................................................. 36
Remote Controls ............................................................................................................... 36
Trim Kits ............................................................................................................................ 37
Screen Door Kits ............................................................................................................... 37
Filigree Louvre Kits............................................................................................................ 37
Warranty ....................................................................................................................................... 39
Energuide ..................................................................................................................................... 40
2 10007317
LDVR Series Direct Vent Gas Fireplace
10007317 3
LDVR Series Direct Vent Gas Fireplace
Fireplace Dimensions
Rough E
Opening
Depth
S
R
F
Low �
Voltage �
Access Electrical
Q Access
B D I
C Low
Gas Line Voltage
Access Electrical H
Access
M
M
O A J
N
P Gas Line K
Access L
G
4 10007317
LDVR Series Direct Vent Gas Fireplace
Clearance to Combustibles
Top of Unit to Ceiling ............................. 36” (914mm)
Appliance
Top ....................................................... 0” (0 mm)
Bottom .................................................. 0” (0 mm)
Side ...................................................... 0” (0 mm)
Back ..................................................... 0” (0 mm) J
I
Venting Black H
G
Concentric sections of DV Vent Surround F
Face
Top, bottom & sides ........................... 1” (25 mm) Mantel
Rear Vent Applications: CFM164a Leg
Top ..................................................... 2” (50 mm) K
L
Sides and Bottom ............................... 1” (25 mm) Side of M
Combustion Chamber N
Mantels CFM164a
Mantel Leg Chart
O
06/22/01 sta
The height that a combustible mantel is fitted above the
fireplace is dependent on the depth of the mantel. This
also applies to the distance between the mantel leg (if
fitted) and the fireplace.
For the correct mounting height and widths refer to
Figs. 3a and 3b, and the following Mantel Charts.
The fitting of a bay window trim kit does not effect
the distances and reference points referred to in the
diagram and chart.
CFM170
Noncombustible mantels and legs may be installed at
any height and width around the appliance.
Mantel Mantel Leg FromSide
When using paint or lacquer to finish the mantel, such Ref. Leg Depth Ref. of Comb. Opening
paint or lacquer must be heat resistant to prevent F CFM170
10” (254mm) K 11¹⁄₂” (292 mm)
discoloration. G
DV Builder Front
8” (203mm)
View L 9¹⁄₂” (241 mm)
V H 6” (152mm) M 7¹⁄₂” (191 mm)
W I 4” (101mm) N 5¹⁄₂” (140 mm)
X J 2” (50mm) O 3¹⁄₂” (89 mm)
Y
Z
Fig. 3b Combustible mantel leg minimum installation.
Hearth
A hearth is not mandatory but is recommended for
A B C D E
aesthetic purposes. We recommend a noncombustible
Fireplace hearth which projects out 12” (305mm) or more from
Top Louvre As- the front of the fireplace.
sembly
Cold climate installation recommendation:
Top of Combustion
Chamber When installing this unit against a
non-insulated exterior wall or chase,
CFM146
it is mandatory that the outer walls
Mantel Chart
CFM146
DV Mantel Chart
be insulated to conform to applicable
7/5/01 sta insulation codes.
Mantel Shelf Mantel from Top
Ref. or Breast Plate Ref. of Combustion Chamber This appliance may be installed in an aftermarket
Depth 36/39/43 LDVR 33LDVR permanently located, manufactured home or mobile
V 10” (254 mm) A 17” (432 mm) 16¹⁄₂” (419 mm) home, where not prohibited by local codes.
W 8” (203 mm) B 15” (381 mm) 14¹⁄₂” (368 mm) This appliance is only for use with the type of gas indicated
X 6” (152 mm) C 13” (330 mm) 12¹⁄₂” (318 mm) on the rating plate. This appliance is not convertible for
Y 4” (101 mm) D 11” (279 mm) 10¹⁄₂” (267 mm) use with other gases, unless a certified kit is used.
Z 2” (50 mm) E 9” (229 mm) 8¹⁄₂” (216 mm) The LDVR has been approved for mobile home
installations.
Fig. 3a Combustible mantel minimum installation.
10007317 5
LDVR Series Direct Vent Gas Fireplace
6 10007317
LDVR Series Direct Vent Gas Fireplace
FP1224
Ensure that the power to the supply line Electronic Gas Control
FP580 Valve
has been disconnected before commenc- INSTA VENT FREE
module.
The EB-1 Electrical junction box has been fitted stand-
ard on this model to allow for the easy connection of an Installation of the remote on/off starter switch or
optional fan kit. wall thermostat on electronic ignition units.
To connect the EB-1 box to the house electrical supply 1. Thread the wiring through the holes on the side
follow the steps below. panels of the appliance. Take care not to cut the wire
1. Unscrew the retaining screw from the EB-1 base or insulation on metal edges. Route the wire to a
plate and remove the EB-1 assembly from the conveniently located receptacle box.
appliance. (Fig. 8) 2. Attach the wire to the ON/OFF switch and install the
2. Remove the front cover of the EB-1 box. switch into the receptacle box.
3. Remove the plug socket assembly from the EB-1
box. 3. Connect the white wire from the wall switch or wall
4. Feed the supply line in through the EB-1 opening in thermostat to the white wire terminal from the elec-
the side of the appliance and then through the back tronic module. Connect the black wire from the wall
of the EB-1 assembly. (Fig. 8) switch or the red wire from the wall thermostat, to
5. Connect the black wire of the power supply line to the red wire terminal from the electronic module.
the brass screw (polarized) of the socket assembly.
6. Connect the white wire of the power line to the
chrome screw of the socket assembly.
7. Connect the ground wire of the supply line to the
green screw of the socket assembly.
8. Refit the socket assembly back into the electrical
box and replace the cover plate. Secure the cable
with the clamp on the outside of the EB-1 base
plate and refit the EB-1 assembly to the unit with the
screw removed in step 1.
8 10007317
LDVR Series Direct Vent Gas Fireplace
BLACK L1
WHITE L2
POWER CORD
GREEN
PURPLE
PILOT SENSING
CLEAR
PILOT IGNITER
YELLOW
M P
O O
VALVE
CIRCUIT BOARD
BLUE
ORANGE
RED ON/OFF SWITCH
WHITE OR
WALL THERMOSTAT
FP1571
General Venting
Your fireplace is approved to be vented either through
FP1571 There must not be any obstruction such as bushes,
the side wall, or vertically through the roof. garden sheds, fences, decks or utility buildings within
SIT822 24” (610mm) from the front of the termination hood.
• Only CFM Corporation venting components specifi-
Synetek wiring
cally approved and labelled for this fireplace may Do not locate termination hood where excessive snow
4/05be or ice build up may occur. Be sure to check vent termi-
used.
nation area after snow falls, and clear to prevent ac-
• Vent terminations shall not be recessed into a wall or cidental blockage of venting system. When using snow
siding. blowers, make sure snow is not directed towards vent
• Horizontal venting which incorporates the twist lock termination area.
pipe must be installed on a level plane without an Location of Vent Termination
inclining or declining slope. It is imperative the vent termination be located observ-
• Horizontal venting which incorporates the use of flex ing the minimum clearances as shown on the next
venting shall have an inclining slope from the unit of page.
1” (25 mm) per 24” (610 mm). *Check with local codes or in absence of same with
CSAB149.1 Installation Codes (1991) for Canada or fol-
low the current National Fuel Gas Code, ANSI Z223.1/
NFPA 54 for installations in the USA.
10007317 9
LDVR Series Direct Vent Gas Fireplace
B C
V B
L V �����
B V
������
V �����
��� �������� G
���
�� ������
F V V
B
B V X M G
B J
I V K X V
A
A
V VENT TERMINATION X AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED
CFM145a
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner Outside Corner Recessed Location
D
B=
Combustible C C
A=
Combustible 6"(152mm) E
A
6"(152mm) Noncombustible
V V
Noncombustible 2"(50mm)
V 2"(50mm) B
Balcony - Balcony -
with no side wall with perpendicular side wall
USA Installations: Repeat process with 7” flex vent pipe. The same proce-
dure must be performed on the vent side.
The venting system must conform with local codes and/
or the current National Fuel Gas code ANSI Z223.1/
NFPA 54. Apply High Temperature
Sealant
Only venting components manufactured by CFM Corpo-
ration can be used in Direct Vent systems.
Flex Vent Pipes
Before joining the flex vent pipe to the unit, apply a
bead of high temperature sealant* (provided) to the 4”
pipe exiting the fireplace. Secure flex vent piep in place
with a hose clamp (provided).
Hose Clamp
*Be sure the flex pipe overlaps at least 1” (25mm) onto
FP1471
the collars of the fireplace and termination. If the ter-
mination has an internal bead, be sure to overlap and Fig. 11 Apply high temperature sealant to 4” and 7” pipes.
secure 1” (25mm) past the bead.
10007317 11
LDVR Series Direct Vent Gas Fireplace
end, then while bringing the pipe together, twist the pipe 19
18
until the flange on the female end contacts the external
17
flange on the male end. It is recommended that you
16
secure the joints with three (3) sheet metal screws, 15
however this is not mandatory with twist lock pipe. 14
To make it easier to assemble the joints we suggest 13
Fig. 12 Twist-lock pipe joints. Horizontal dimension from the outside face of the
wall to the center of the fireplace vent flange
How to Use the Vent Graph CFM102
Sidewall vent graph showing the relationship between vertical
DV Graphic
and horizontal dimensions for a Direct Vent flue system.
The vent chart should be read in conjunction with the
TWL100 9/28/00 sta
Twist Lock Pipe Fig. 13 Sidewall venting graph. (Dimensions in feet)
following vent installation instructions to determine the
3/12/99 djt
relationship of the vertical and horizontal dimensions of Rear Wall Venting Applications
the vent system.
1. Determine the height of the center of the horizontal When installed as a rear vent unit this appliance may
vent pipe exiting through the outer wall. Using this be vented directly to a termination located on the rear
dimension on the Sidewall Vent Graph (Fig. 13) wall behind the appliance.
locate the point intersecting with slanted graph line. • Only CFM Corporation venting components are
2. From the point of this intersection, draw a vertical approved to be used in these applications. (Refer to
line to the bottom of the graph. “Venting Components” listed for different installation
3. Select the indicated dimension, and position the requirements)
fireplace in accordance with same. • The maximum horizontal distance between the rear
Example A: of the appliance (or end of the transition elbow in a
If the vertical dimension from the floor of the corner application) and the outside face of the rear
fireplace is 11ʼ (3.4m) the horizontal run to the face wall is 20” (508mm). (Fig. 14)
of the outer wall must not exceed 14ʼ (4.3m).
• Only one 45° elbow is allowed in these installations.
Example B:
If the vertical dimension from the floor of the unit is • Minimum clearances between vent pipe and com-
7ʼ (2.14m), the horizontal run to the face of the outer bustible materials are as follows:
wall must not exceed 8¹⁄₂ʼ (2.6m). Top - 2” (50mm)
Sides - 1” (25mm)
Bottom - 1” (25mm)
12 10007317
LDVR Series Direct Vent Gas Fireplace
20"
(508mm) Framing
10³⁄₈” Detail
(264mm)
Top View
Straight Venting Fireplace Hearth
DVR584-600 Opening for Noncombustible Wall
20" 20"
Rear vent no elbows
(508mm) (508mm)
Max. Max. 7¹⁄₂”
2/99 djt (190mm)
VO584-100
45° 45° Fig. 15 Locate vent opening on wall.
VO584-100
Top View
REAR VENT-TOP VIEW
Rear Vent Corner Installation
#8 Screws
(2)
Vent Opening #8
Fig. 14 Rear vent applications, one 45° elbow. 2/99 djt Screws
(2)
FP836
Rear Wall Installation
Rear Vent-Top View Firestop
Twist Lock11/21/98
Pipe
Adjustable Zero Clearance Sleeve ZCS101
STEP 1
Fig. 16 AdjustableZCS101
zero clearance sleeve.
Locate vent opening on the wall. To locate hole center Zero Clearance Sleeve
consult with appropriate fireplace dimensions, Page 4. STEP 3 3/11/99 djt
Frame as shown below. Measure from the fireplace collar or elbow face to face
NOTE: When using flex vent, the opening will have to of outside wall (add 2” for vent pipe overlap). Mark
be measured according to the 1/2” (13 mm) rise in 12” pipes and cut to length. It is very important that the two
(305 mm) vertical run. pipes are flush with the outside wall once the fireplace
Combustible Walls (Fig. 15): Cut a 10³⁄₈”H x 9³⁄₈” W is in its final location. (Fig. 17)
(264 x 240mm) hole through the exterior wall and frame STEP 4
as shown. Slip 4” and 7” pipes onto respective flue collars. Make
Noncombustible Walls (Fig. 15): Hole opening must sure to fix to the fireplace collar the 4” pipe with three
be 7¹⁄₂” (190mm) in diameter. (3) screws before fixing the 7” pipe on the 7” collar.
STEP 2 Both pipes must be on a level plane. (Fig 18)
Measure wall thickness and cut zero clearance sleeve STEP 5
parts to proper length (MAXIMUM 12”/305mm). Assem- Guide the vent termination 4” collar into the 4” pipe then
ble sleeve and attach to firestop with #8 sheet metal the 7” collar into the 7” pipe. Do not force the venting
screws (supplied). (Fig. 16) into position. If the pipes do not line up with the termi-
nation collars, disassemble pipes and reattach to the
fireplace collar. (Fig. 18)
STEP 6
Secure fireplace to floor through floor holes and adjust-
able frame drywall strip (nailing flange) to frame. (Refer
to Framing & Finishing Section).
10007317 13
LDVR Series Direct Vent Gas Fireplace
Zero Termination
Clearance
Sleeve
Flex Section
Appliance Collars
Firestop
CFM133
CFM133
DVR Series Typical corner install
FP1473
Finished Wall 2/26/01 sta
Fig. 19 Grasp the vent pipe close to the collar and bend to
Vent Termi-
45° angle. Do not exceed 45°.
nation
Rise
FP1473
corner flex install
4/04 djt
FP1472
14 10007317
LDVR Series Direct Vent Gas Fireplace
Maximum
Vertical Dimension 20 ft. (6.1m)
A + B = 17 ft. (Max.)
7¹⁄₂ʼ Minimum When 48" 7 ft. 6 in.
Horizontal Run is 12" (1.2m) (2286 mm)
20ʼ (305mm)
15 ft.
(4572mm)
CFM147
Example:
Fig. 21 Maximum number of 90° elbows is three (3). Elbow 1 = 90˚
CFM141 4
• If a 90° elbow is used2/2/01
in thestahorizontal vent run Elbow 2 = 45˚
(level height maintained) the maximum horizontal Elbow 3 = 45˚
vent length is reduced by 36” (914 mm). (Fig. 22) Elbow 4 = 90˚
This does not apply if the 90° elbows are used to Total angular variation = 270˚
increase or redirect a vertical rise. (Fig. 23) 1 + 2 + 3 + 4 = 270o
Maximum
3' (914mm) 3
2
1
CFM132
10007317 15
LDVR Series Direct Vent Gas Fireplace
CFM135
9³⁄₈” Zero Clearance Sleeve
(240mm) 2/26/01 sta
Ensure Pipes are
Concentric
�
Framing Detail
Fireplace Hearth
Opening for Noncombustible Wall
7¹⁄₂” ��������
16 10007317
LDVR Series Direct Vent Gas Fireplace
X X X
Always install hori-
zontal venting on a
level plane.
CFM138
CFM136
Fig. 28 Measure horizontal length including 2” overlap. Fig. 30 Horizontal length requirement.
CFM136 CFM138
X length
High Rear Vent horizontal Below Grade
4", 7" collarInstallations
2/26/01
Temperature Sealant sta 2/26/01 sta
When it is not possible to meet the required vent ter-
minal clearances of 12” (305mm) above grade level a
snorkel vent kit #7TDVSNORK is required. It allows
installation depth of down to 7” (178 mm) below grade
level. The 7” is measured from the center of the hori-
zontal vent pipe as it penetrates through the wall.
If venting system is installed below
ground, we recommend a window well with
adequate and proper drainage.
Ensure sidewall venting clearances are observed.
The maximum horizontal run with 24”
vertical rise is 36” (914 mm) from the
back of the fireplace to the face of the
exterior wall. See vent graph (Page 12) for
CFM137 extended horizontal run if the vertical rise
exceeds 24” (610 mm).
Fig. 29 Apply high temperature sealant.
1. Establish vent hole through the wall. (Fig. 25)
STEP 6 CFM137
Rear Vent length 2. Remove soil to a depth of approximately 16”
Apply high temperature sealant
2/26/01 sta to
4” (102 mm) and 7” (406mm) below base of snorkel. Install window
(178 mm) collars or the termination one inch away from well (not supplied). Refill hole with 12” (305 mm) of
the end. Guide the vent terminationʼs 4” and 7” collars coarse gravel leaving a clearance of approximately
into their respective vent pipes. Double check that the 4” (102 mm) below snorkel. (Fig. 31)
vent pipes overlap the collars by 2” (50 mm). Secure the 3. Install vent system. See Page 13, Steps 2 through 5.
termination to the wall with screws provided and caulk
4. Ensure a watertight seal is made around the vent
around the wall plate to weatherproof. (Fig. 30) pipe coming through the wall.
STEP 7 5. Apply high temperature sealant caulking (supplied)
Support the horizontal pipes every 36” (914 mm) with around the 4” and 7” snorkel collars.
metal pipe straps. Make sure that the horizontal vent 6. Slide into the vent pipe and secure to the wall.
pipe is installed on a level horizontal plane. 7. Level the soil to maintain a 4” (102 mm) clearance
STEP 8 below snorkel. (Fig. 31)
Re-check the fireplace to make sure that it is levelled,
properly positioned, and nailed or screwed to the floor.
If applied, the fireplaces adjustable frame drywall strips
(nailing flanges) should be fastened. Refer to “Framing
& Finishing”.
10007317 17
LDVR Series Direct Vent Gas Fireplace
Gravel
Maximum
Drain 10ʼ
(3 m)
Minimum
8ʼ (2.4 m) /
Foundation Wall Maximum
40ʼ (12 m) Vertical
*A minimum of 24” (608mm) Rise
vertical pipe must be installed
when using 7TDVSNORK Kit.
Pipe Straps Every
3ʼ (914 mm)
BG400
18 10007317
LDVR Series Direct Vent Gas Fireplace
Attic Insulation
Shield
Max.
8ʼ
(2.4m)
Joist
45° Typical
Ceiling
40ʼ
(12m) Support
Max.
8ʼ Application
(2.4m)
11"
Upper Floor
Joist
Typical Roof
Support Ap-
Firestop Spacer
plication
TWL101a
Twist Lock Pipe
2/8/99 djt
10007317 19
LDVR Series Direct Vent Gas Fireplace
Vent
Roof Termination
Joists
FP1185
FP1022
Fig. 37 Typical straight-up installation.
FP1022
Typical Straight Up Installation
1/26/00 djt
20 10007317
LDVR Series Direct Vent Gas Fireplace
Venting Components
Operating Instructions
Glass Information
22 10007317
LDVR Series Direct Vent Gas Fireplace
10007317 23
LDVR Series Direct Vent Gas Fireplace
Rear
(B135) 43LDVR
1. Place rear log (BD15) on rear bracket (ensure log is
centered and seated properly to the log support).
2. Place front left log (BD16). Use logʼs bottom notch to
locate it onto the front support and just rest on top of
the burner housing tile.
3. Place front right log (BD17). Use logʼs bottom notch
to locate it onto the front support and just rest on top
of the burner housing.
4. Place ember material on top of burner.
Front Left
(B136) 5. Scatter the ember material over the tiles on the front
Front Center area of the burner housing. (Fig. 44) Do not pack
(B138) Front Right the ember material. Separate it when unpacked and
LG383 (B137)
keep it in a fluffy and loose condition for a more
Fig. 42 Correct log placement for 36LDVR. realistic ember effect.
6. Place front center log (B138) on top of the two small
39LDVR shelves at the front log support, and between the left
and right logs.
1. Place rear lob (BC14) on rear bracket (ensure log is
LG383
centered and seated properly to the log support). 7. Place top center log (BD18) on top of the rear log
36LDVR
2. Place front left log (BC15). logshole to
Use logʼs bottom
using the hole locator under the log and on top of
front right log.
locate it onto the front support and just rest on top of
the rear log.
1/05 8. Scatter lava rock material round the firebox base.
3. Place front right log (BC16). Use logʼs bottom hole Do not place any of the lava rock material
to locate it onto the front support and the top hole to on the burner housing assembly.
the knob on the rear log.
4. Place front center log (B138) on top of the two small
Top Center
shelves at the front log support, and between the left Rear (BBD18)
and right logs. (BD15)
Front Right
5. Place ember material on top of burner. Scatter the (BD17)
ember material over the tiles on the front area of Front
the burner housing. (Fig. 50) Separate it when un- Left
packed and keep it in a fluffy and loose condition for (BD16)
a more realistic ember effect.
Do not place any of the lava rock material
on the burner housing assembly.
Lava
Front Left Rock
(BC15) Front Right Lava Rock Ember Material
(BC16)
Rear Front Center
(BC14) (B138) LG434
Front Center
(B138) LG414
24 10007317
�����
�
LDVR Series Direct Vent Gas Fireplace
Flame Characteristics
FP390
It is important to periodically performKNOB
FLAME ADJUSTMENT a visual check Glowing Embers LG385
11/21/96
of the pilot and burner flames. Compare them to the Fig. 49 Correct burner flame appearance for 36LDVR.
illustrations. (Figs. 47-51)
If the flame patterns appear abnormal contact a
qualified service provider for service and adjustment.
�����
����������������
SIT EN/EP
����
FP1541
10007317 25
�����
������ ���������������
�����
LDVR Series Direct Vent Gas Fireplace
Lighting Instructions
1. STOP! Read the safety information above. 10. Push the control knob all the way in and hold.
2. Turn off all electrical power to the fireplace. Immediately light the pilot by repeatedly depress-
3. For MN/MP/TN/TP appliances ONLY, go on to ing the piezo spark ignitor until a flame appears.
Step 4. For RN/RP appliances turn the ON/OFF Continue to hold the control knob in for about one
switch to “OFF” position or set thermostat to (1) minute after the pilot is lit. Release knob and it
lowest level. will pop back up. Pilot should remain lit. If it goes
4. Open control access panel. out, repeat steps 5 through 8.
5. Push in gas control knob slightly and turn clock-
wise to “OFF”. 3/8" - 1/2"
���
PILOT
�
��
��
1 2
Pilot
��
OFF
��
OFF
O FF
3 4 5
26 10007317
LDVR Series Direct Vent Gas Fireplace
A. This fireplace is equipped with an ignition device Follow the gas suppliers instructions.
which automatically lights the pilot. DO NOT try to • If you cannot contact your gas supplier call
light the pilot by hand. the Fire Department
B. BEFORE OPERATING, smell all around the C. Use only your hand to push in or turn the gas control
appliance area for gas. Be sure to smell next to knob. Never use tools. If the knob will not push in
the floor because some gas is heavier than the air or turn by hand do not try to repair it, call a qualified
and will settle on the floor. service technician. Force or attempting repair may
What to do if you smell gas result in a fire or explosion.
• Do not try to light any appliance D. Do not use this appliance if any part has been under
• Do not operate any electrical switch. water. Immediately call a qualified service technician
to inspect the appliance and replace any part of the
• Do not use any phone in your building. control system and any gas control that has been
• Immediately call your gas supplier from a under water.
neighborʼs phone.
Lighting Instructions
1. STOP! Read the safety information above before 5. Turn the remote switch, if used, OFF. Turn the
continuing. wireless remote, if used, OFF.
2. Turn off all electrical power to the appliance. 6. Wait five (5) minutes to clear out any gas. Then
3. This appliance is equipped with an ignition device smell for gas, including near the floor. If you smell
which automatically lights the pilot. DO NOT try to gas STOP. Follow instructions B in the safety
light the pilot by hand. warnings above. If you do not smell gas go onto the
4. Access the gas control by lowering the lower next step.
access door (louvre assembly). 7. Close the access door.
8. Turn ON all electrical power to the appliance.
9. Turn remote switch or wireless remote to “ON”.
10. If the appliance will not operate, follow the
LO instructions TURNING OFF THE GAS TO THE
APPLIANCE and call your service technician or
HI gas supplier.
10007317 27
FP297A
INSTA VENT FREE
UVHB26 GAS SUPPLY
7/1/98
LDVR Series Direct Vent Gas Fireplace
START CHECK
▼
• Shutoff Valve Open
YES
▼
Pilot Lights With Piezo NO
Ignitor 1/8" Gap To Pilot Hood Needed.
• All Wiring Connections
• Replace Piezo Ignitor
• Replace Thermopile
• Thermocouple Needs A Min. Of
14mv
• Defective Valve. Turn To Pilot,
Meter Should Read Greater
YES Than 100mv. If Not, Replace.
• Valve Is Turned On
▼
• Wall Switch Is Not Turned On.
Pilot Lights Main Burner NO Watch For Grounded Wires!
▼
▼
SYSTEM OK
28 10007317
LDVR Series Direct Vent Gas Fireplace
0 Sec Purge
LED: 5 Flashes?
Reverse power cord polarity
YES
Pilot, Valve OFF, Spark OFF
Spark Off. Main Valve ON. NO
Have three ignition trials been completed?
Pilot Flame Continuously
Monitored
LED: 3 Flashes?
Lockout: Flame Loss
Reset by interrupting ON/OFF switch or
Pilot Flame Sense OK? NO
power for 10 sec
YES
NO
Have three pilot flame losses been
Pilot and Main Valve OFF? YES
detected?
YES
10007317 29
LDVR Series Direct Vent Gas Fireplace
FP
IL
O OT
FP
IL
O OT
Maintenance
Burner and Burner Compartment
To obtain proper operation, it is imperative that the pilot
It is important to keep the burner and the burner and burnerʼs flame characteristics are steady, not lifting
compartment clean. At least once per year the logs and or floating.
lava rock/ember material should be removed and the
Typically, the top 3/8” to 1/2” of the thermopile should
burner compartment vacuumed and wiped out. Remove
be engulfed in the pilot flame. (Refer to Page 25, Figure
and refit the logs as per the instructions in this manual.
47)
Always handle the logs with care as they To adjust pilot burner: (by qualified service technician)
are fragile and may also be hot if the
fireplace has been in use. 1. Remove pilot adjustment cap
2. Adjust pilot screw to provide properly sized flame.
FK24/FK12 Fan Assembly
3. Replace pilot adjustment cap.
The fan unit requires periodic cleaning. At least once
The primary air shutter is set at factory and should
per month in the operating season open the lower
only be adjusted, if necessary, by a qualified service
louvre panels and wipe or vacuum the area around the
technician.
fan to remove any build up of dust or lint.
Brass Trim
Clean the brass trim pieces using a soft cloth lightly
dampened with lemon oil. Do not use water or
household cleaners on any brass components.
10007317 31
LDVR Series Direct Vent Gas Fireplace
1h 1i 2 12 14 11
3 9
6a,b 7a,b 16
18a,b 19a,b 15
13
17
LO 8
HI
20
21
23
26
30
27 29
31
22 24 36
25
28
33
34
32
35
37
39 40
41
42
43
CFM Specialty Home Products reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products
at any time, without notice.
7317
33/36/39/43LDVR LDVR parts
1/05
32 10007317
LDVR Series Direct Vent Gas Fireplace
LDVR (continued)
Ref. Description 33LDVR 36LDVR 39LDVR 43LDVR
1. Log Set (complete) 10007567 10007318 10008214 10008314
1a. Log Front Left A43 B136 BC15 BD16
1b. Log Front Right -- B137 BC16 BD17
1c. Log Front Center -- B138 B138 B138
1d. Log Rear -- B135 BC14 BD15
1e. Log Rear Left A41 -- -- --
1f. Log Rear Right A42 -- -- --
1g. Log Top Center A44 -- -- BD18
1h. Lava Rock Package 10001454 10001454 10001454 10001454
1i. Ember (Package) 51915 51915 51915 51915
2a. Burner Housing Assy - Natural 10007558 10007127 10008218 10008464
2b. Burner Housing Assy - LP 10007558 10008042 10008586 10008587
3. Ceramic Tile (Single) 57803 57803 57803 57803
4a. Orifice Burner - Natural Refer to Rating Plate for Orifice Size
4b. Orifice Burner - Propane Refer to Rating Plate for Orifice Size
5a. Orifice Pilot - Natural 10002268 10002268 10002268 10002268
5b. Orifice Pilot - Propane 10002269 10002269 10002269 10002269
6a. Pilot Assy SIT - RN 10002264 10002264 10002264 10002264
6b. PIlot Assy SIT - RP 10002265 10002265 10002265 10002265
7a. PIlot Assy SIT - EN 10002387 10002387 10002387 10002387
7b. Pilot Assy SIT - EP 10002388 10002388 10002388 10002388
8. Pilot Tubing w/Fittings SIT 10001296 10001296 10001296 10001296
9. Pilot Hood 10002385 10002385 10002385 10002385
10. Manifold Tubing w/Fittings 57318 57318 57318 57318
11. Thermocouple - RN/RP 53373 53373 53373 53373
12. Thermopile - RN/RP 51827 51827 51827 51827
13. Electrode Ignitor w/Cable - RN/RP 10001297 10001297 10001297 10001297
14. Electrode Ignitor - EN/EP 52465 52465 52465 52465
15. Cable Ignitor - EN/EP 10000696 10000696 10000696 10000696
16. Sensing Electrode - EN/EP 57885 57885 57885 57885
17. Ignitor Piezo SIT820 Valve 52464 52464 52464 52464
18a. Valve SIT 820 - RN 52677 52677 52677 52677
18b. Valve SIT 820 - RP 52678 52678 52678 52678
19a. Valve SIT 822 - EN 57884 57884 57884 57884
19b. Valve SIT 822 - EP 57883 57883 57883 57883
20. Flexible Gas Line w/ON/OFF Shut-Off Valve 20002500 20002500 20002500 20002500
21. Fan Assy w/Bracket (FK24 Option) ZA1100 ZA1100 ZA1100 ZA1100
22. Fan Assy (FK12 Option) ZA1110 ZA1110 ZA1110 ZA1110
23. Electrical Cord (6ft) 51865 51865 51865 51865
24. Fan Temperature Sensor (FK24) 51704 51704 51704 51704
25. Speed Control (FK24) 51738 51738 51738 51738
26. Speed Control Knob (FK24) 51882 51882 51882 51882
27. Glass w/Gasket 10007391 10007094 10008212 10008310
28. Gasket Glass 57317 57317 57317 37317
29. Frame Window 10007399 10007093 10007972 10008309
30. Clamp Frame Window 54174 54174 54174 54174
31. Top Louvre Assy 10007400 10007090 10007984 10008311
32. Bottom Louvre Assy 10007397 10007092 10007986 10008307
33a. Support Rear Log 10007561 10007162 10008211 10008480
33b. Support Rear Log - LP 10007561 10008045 10008211 10008480
34. Support Front Log 10007562 10007112 10008416 10008469
35. ON/OFF Switch 51842 51842 51842 51842
36. Ceramic Refractory Lining Kit (Optional) GADT3I0 GADT3J0 GADT3K0 GADT3N0
10007317 33
LDVR Series Direct Vent Gas Fireplace
LDVR (continued)
Ref. Description 33LDVR 36LDVR 39LDVR 43LDVR
37. Relief Plate Assy (Burner Base) 10004192 10004192 10004192 10004192
38. Remote Switch Kit (Not shown) 53875 53875 53875 53875
39. Ignition Control from Synetek (EN) 10007939 10007939 10007939 10007939
40. Wire Harness (EN) Synetek (low voltage) 10008139 10008139 10008139 10008139
41. Wire Harness (EN) Synetek (high voltage) 10008140 10008140 10008140 10008140
42. Clevis Pin 10008615 10008615 10008615 10008615
43. Clip Pin Hitch 10008616 10008616 10008616 10008616
34 10007317
LDVR Series Direct Vent Gas Fireplace
10007317 35
LDVR Series Direct Vent Gas Fireplace
Wiring Instructions
The fireplace, when installed, must be
electrically connected and grounded in
accordance with local codes or, in the
absence of local codes, with the current Side
Panel Back Panel Side
CSA C22.1 Canadian Electric Code. Panel
Log Support
For USA installations follow the local codes Burner Tray
and the national electrical code ANSI/NFPA
No. 70.
Should this fan require servicing or repair
the power supply must be disconnected. FP1231
For rewiring of any replacement parts refer
Fig. 56 Ceramic panel installation.
to Figure 55.
Any electrical rewiring of this fan must be Rear Refrac-
done by a licensed electrician. tory Panel
36 10007317
LDVR Series Direct Vent Gas Fireplace
10007317 37
LDVR Series Direct Vent Gas Fireplace
38 10007317
LIMITED LIFETIME WARRANTY
LDVR Series Direct Vent Gas Fireplace
PRODUCT COVERED BY THIS WARRANTY
All Vermont Castings gas stoves, gas inserts, and gas fireplaces, and all Majestic or Northern Flame brand gas fireplaces
equipped with an Insta-Flame Ceramic Burner, or standard steel tube burner.
BASIC WARRANTY • Any part and/or component replaced under the provisions of this
CFM Specialty Home Products (hereinafter referred to collectively as warranty is covered for six months or the remainder of the original
the Company) warrants that your new Vermont Castings or Majestic warranty, whichever is longest.
Gas Fireplace/Stove is free from manufacturing and material defects • This warranty is limited to the repair of or replacement of part(s) found
for a period of one year from the date of purchase, subject to the to be defective in material or workmanship, provided that such part(s)
following conditions and limitations. have been subjected to normal conditions of use and service, after
said defect is confirmed by the Companyʼs inspection.
EXTENDED LIFETIME WARRANTY
• The company may, at its discretion, fully discharge all obligations
The heat exchanger, where applicable, and combustion chamber with respect to this warranty by refunding the wholesale price of the
of every Vermont Castings or Majestic gas product is warranted for defective part(s)
life against through wall perforation. All appliances equipped with an
• Any installation, labor, construction, transportation, or other related
Insta-Flame Ceramic Burner have limited lifetime coverage on the
costs/expenses arising from defective part(s), repair, replacement,
ceramic burner plaque. Warrantees are made to the original owner
or otherwise of same, will not be covered by this warranty, nor shall
subject to proof of purchase and the conditions and limitations listed
the Company assume responsibility for same. Further, the Company
on this Warranty Document
will not be responsible for any incidental, indirect, or consequential
COMPONENT WARRANTY damages except as provided by law.
CAST IRON: All external and internal cast iron parts are warranted for a • SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR
period of three years. LIMITATIONS OF INCIDENTAL AND CONSEQUENTIAL DAMAGES
Note: On porcelain enamel finished external parts and accessories The OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY
Company offers no Warranty on chipping of enamel surfaces. Inspect LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR
all product prior to accepting it for any damage to the enamel. CIRCUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC
RIGHTS AND YOU MAY HAVE OTHER RIGHTS WHICH VARY FROM
The salt air environment of coastal areas or a high humidity environment
STATE TO STATE.
can be corrosive to the porcelain enamel finish. These conditions can
cause rusting of the cast iron beneath the porcelain enamel finish, • All other warranties-expressed or implied- with respect to the product,
which will cause the finish to flake off. its components and accessories, or any obligations/liabilities on the
part of the Company are hereby expressly excluded.
Dye lot variations with replacement parts and/or accessories can occur
and are not covered by warranty. • The Company neither assumes, nor authorizes any third party to
assume on its behalf, any other liabilities with respect to the sale of
GLASS DOORS: Glass doors are covered for a period of one year.
this Vermont Castings or Majestic product
Glass doors are not warranted for breakage due to misuse or accident.
Glass doors are not covered for discoloration or burned in stains due to • The warranties as outlined within this document do not apply to chimney
environmental issues, or improper cleaning and maintenance. components or other non CFM Specialty Home Products accessories
used in conjunction with the installation of this product..
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be
• Damage to the unit while in transit is not covered by this warranty but
cleaned with Lemon oil only. Brass cleaners cannot be used. Mortar
is subject to claim against the common carrier. Contact the dealer
mix and masonry cleaners may corrode the brass finish. The Company
from whom you purchased your fireplace/stove (do not operate the
will not be responsible for, nor will it warrant any brass parts which are
appliance as this might negate the ability to process the claim with the
damaged by external chemicals or down draft conditions.
carrier).
GAS VALVES: Gas valves are covered for a period of one year • The Company will not be responsible for:
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and a) Down drafts or spillage caused by environmental conditions such
mechanical components of the burner assembly are covered for one year. as near-by trees, buildings, roof tops, hills, or mountains.
All steel tube burners are warranted for one year. b) Inadequate ventilation or negative air pressure caused by
ACCESSORIES: Unless otherwise noted all components and CFM mechanical systems such as furnaces, fans, clothes dryers, etc.
Specialty Home Products company supplied accessories are covered for • This warranty is void if:
a period of one year. a) The fireplace has been operated in atmospheres contaminated by
CONDITIONS AND LIMITATIONS chlorine, fluorine, or other damaging chemicals.
b) The fireplace has been subjected to prolonged periods of dampness
• This new Vermont Castings or Majestic product must be installed by
or condensation
a competent, authorized, service contractor. A licensed technician, as
c) Any damages to the fireplace, combustion chamber, heat exchanger
prescribed by the local jurisdiction must perform any installation/service
or other components due to water, or weather damage, which is the
work. It must be installed and operated at all times in accordance with
result of but not limited to, improper chimney/venting installation.
the Installation and Operating instructions furnished with the product.
d) Any alteration, willful abuse, accident, or misuse of the product
Any alteration, willful abuse, accident, or misuse of the product shall
nullify this warranty. has occurred.
• This warranty is non-transferable, and is made to the original owner, IF WARRANTY SERVICE IS NEEDED…
provided that the purchase was made through an authorized supplier
of the Company.
1) Contact your supplier. Make sure you have your warranty,
your sales receipt, and the model/serial number of your CFM
• The customer must pay for any Authorized Dealer in-home travel fees
or service charges for in-home repair work. It is the dealers option
Specialty Home Products product.
whether the repair work will be done in the customerʼs home or in the 2) DO NOT ATTEMPT TO DO ANY SERVICE WORK
dealerʼs shop. YOURSELF.
• If upon inspection, the damage is found to be the fault of the manufacturer,
repairs will be authorized at no charge to the customer parts and/or
labor.
10007317 39
Efficiency Ratings
Model EnerGuide Ratings Steady State (%) D.O.E.
Fireplace Efficiency (%) Fan-OFF Fan-ON (AFUE%)
33LDVRRN 62.6 81 82 59
33LDVRRP 62.6 82 83 59
33LDVREN 72.7 81 82 59
33LDVREP 72.7 82 83 59
36LDVRRN 57.5 81 82 58
36LDVRRP 57.5 82 83 58
36LDVREN 63.6 81 82 58
36LDVREP 63.6 82 83 58
39LDVRRN 50.2 76 79 63
39LDVRRP 50.2 79 80 63
39LDVREN 54.2 78 79 63
39LDVREP 54.2 79 80 63
43LDVRRN 54.3 77 78 63
43LDVRRP 54.3 78 79 63
43LDVREN 58.3 77 78 63
43LDVREP 58.3 78 79 63