Direct Vent
Models: 33LDVT, 36LDVT
39LDVT, 43LDVT
INSTALLER/CONSUMER
SAFETY INFORMATION
PLEASE READ THIS MANUAL
BEFORE INSTALLING AND USING
APPLIANCE
WARNING!
IF THE INFORMATION IN THIS
MANUAL IS NOT FOLLOWED
EXACTLY, A FIRE OR EXPLOSION
MAY RESULT CAUSING
PROPERTY DAMAGE, PERSONAL
INJURY OR LOSS OF LIFE.
DO NOT STORE
OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND
LIQUIDS IN THE VICINITY OF THIS
OR ANY OTHER APPLIANCE.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
10007852 5/07 Rev. 9
Table of Contents
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING THIS APPLIANCE.
Thank you and congratulations on your purchase of a CFM Corporation fireplace.
IMPORTANT: Read all instructions and warnings carefully before starting installation.
Failure to follow these instructions may result in a possible fire hazard and will void the warranty.
2 10007852
�������
permanently located, manufactured home or mobile home,
� where not prohibited by local codes.
This appliance is only for use with the type of gas indicated
�������������� on the rating plate. This appliance is not convertible for
������������ use with other gases, unless a certified kit is used.
The LDVT has been approved for mobile home
������������������ installations.
�������������
�������������������� IMPORTANT:
��������������� PLEASE REVIEW THE FOLLOWING CAREFULLY
4. Under no circumstances should this fireplace be modified. Remove any plastic from from parts before turning the
Parts removed for servicing should be replaced prior to fireplace ON.
operating this fireplace again. It is normal for fireplaces fabricated of steel to give off
5. Installation and any repairs to this fireplace must be per- some expansion and/or contraction noises during the
formed by a qualified installer, service agency or gas sup- start up or cool down cycle. Similar noises are found
plier. A professional service person should be contacted to with your furnace heat exchanger or car engine.
inspect the fireplace annually. More frequent cleaning may It is not unusual for your gas fireplace to give off some
be required due to excess lint and dust from carpeting, bed-
odor the first time it is burned. This is due to the curing
ding material, etc.
6. Control compartments, burners and air passages in this fire-
of the paint and any undetected oil from the manufac-
place should be kept clean and free of dust and lint. Make turing process.
sure that the gas valve and pilot light are turned off before Please ensure that your room is well ventilated-open
you attempt to clean this fireplace. all windows.
7. The venting system (chimney) of this fireplace should be It is recommended that you burn your fireplace for at least
checked at least once a year and if needed your venting ten (10) hours the first time you use it. If the optional fan
system should be cleaned. kit has been installed, place the fan switch in the “OFF”
8. Keep the area around your fireplace clear of combustible position during this time.
materials, gasoline and other flammable vapour and liquids.
This fireplace should not be used as a dry-ing rack for cloth-
ing, nor should Christmas stockings or decorations be hung Proposition 65 Warning: Fuels used in gas, wood-
on or around the fireplace. burning or oil fired appliances, and the products of
9. Under no circumstances should any solid fuels (wood, coal, combustion of such fuels, contain chemicals known to
paper or cardboard etc.) be used in this fireplace.
the State of California to cause cancer, birth defects
10. The flow of combustion and ventilation air must not be ob-
structed in any way. and other reproductive harm.
11. When the fireplace is installed directly on carpeting, vinyl tile California Health & Safety Code Sec. 25249.6
or any combustible material other than wood, this fireplace
10007852 3
Fireplace Dimensions
Rough E
Opening
Depth
S
R I
Low
Voltage
Access Electrical
Q Access
G B C D
Gas Line Low
Voltage
Access Electrical
Access
M N
O J
A
P Gas Line K
Access L
Fig. 1 Fireplace specifications and framing dimensions.
4 10007852
Y
E A B
Y Z
X
C
D
Y A B C D E
X B
Fireplace
F
Top Louvre
Assembly
6 10007852
High Elevations The fireplace valve must not be subjected to any test
pressures exceeding 1/2 psi. Isolate or disconnect this
Input ratings are shown in BTU per hour and are or any other gas appliance control from the gas line
certified without deration for elevations up to when pressure testing.
4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA, Remote ON/OFF Switch
installations must be in accordance with the cur- Installation:
rent ANSI Z223.1/NFPA 54 and/or local codes hav-
ing jurisdiction. 1. Thread the wiring through holes on the end panels
of appliance. Take care not to cut wire or insulation
In Canada, please consult provincial and/or local on metal edges. Route the wire to a conveniently
authorities having jurisdiction for installations at located receptacle box.
elevations above 4,500 feet (1,370m).
2. Attach the wire to the ON/OFF switch and install the
switch into the receptacle box.
Gas Line Installation
3. Connect the other ends of the wire to the gas control
When purging gas line, the front window valve. (Fig. 6)
frame removed. Remote ON/OFF
Switch or Thermostat or
Remote Control
The gas pipeline can be brought in through the rear
of the fireplace as well as the bottom. Knockouts are
provided on the bottom behind the valve to allow for the
gas pipe installation and testing of any gas connection.
It is most convenient to bring the gas line in from the TP
rear right side of the valve as this allows fan installation TH
Gas
or removal without disconnecting the gas line. Control
TP Valve
The gas line connection can be made with properly
tinned 3/8” copper tubing, 3/8” rigid pipe or an approved
flex connector. Since some municipalities have ad- TH
ditional local codes, it is always best to con- sult your
FP1224
local authority and the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 in the USA or the CSA-B149.1 installa- Fig. 6 Remote switch wiring diagram.
tion codes.
Alternate Switch Location
FP1224
1/2” Gas Supply
The remote switch canRemote
be installed on the front/side of
switch
1/2” NPT X 1/2” Flare Shut-off Valve the access door. Simply mount the switch to the bracket
11/02
provided and screw the bracket to either side of the
3/8” Flex line
frame, lining up the screws with the pre-punched holes.
(from valve)
(Fig. 7)
FP297A
When using copper or flex connector use only approved Fig. 7 Alternate switch location.
fittings. Always provide a union when using black iron
Do not wire the remote ON/OFF wall switch
pipe so that the gas line can be easily disconnected for
for the gas fireplace to the 120 volt power
burner or fan servicing . See gas specifications for pres- supply.
sure details and ratings.
10007852 7
FP1024
alternate
Downloaded from www.Manualslib.com manuals search engine
LDVT Series Direct Vent Gas Fireplace
INSIDE
EB-1 Electrical Box Electrical Box
Retaining Screw
The fireplace, when installed, must be elec-
trically connected and grounded in accord- ������
������
8 10007852
BLACK L1
WHITE L2
POWER CORD
GREEN
PURPLE
PILOT SENSING
PILOT IGNITER
YELLOW
M P
O O
VALVE
CIRCUIT BOARD
BLUE
ORANGE
RED ON/OFF SWITCH
WHITE OR
WALL THERMOSTAT
FP1571
General Venting
FP1571
Your fireplace is approved to be vented either through There must not be any obstruction such as bushes,
the side wall, or vertically through the roof. SIT822 garden sheds, fences, decks or utility buildings within
24” (610 mm) from the front of the termination hood.
• Only CFM Corporation venting componentsSynetek
spe- wiring
cifically approved and labelled for this fireplace
4/05 Do not locate termination hood where excessive snow
may be used. or ice build up may occur. Be sure to check vent termi-
nation area after snow falls, and clear to prevent ac-
• Vent terminations shall not be recessed into a wall cidental blockage of venting system. When using snow
or siding. blowers, make sure snow is not directed towards vent
• Horizontal venting which incorporates the twist lock termination area.
pipe must be installed on a level plane without an Location of Vent Termination
inclining or declining slope.
It is imperative the vent termination be located observ-
• Horizontal venting which incorporates the use of flex ing the minimum clearances as shown on the next
venting shall have an inclining slope from the unit of page.
1” (25 mm) per 24” (610 mm).
*Check with local codes or in absence of same with
CSA-B149.1 Installation Codes (1991) for Canada
or follow the current National Fuel Gas Code, ANSI
Z223.1/NFPA 54 for installations in the USA.
10007852 9
V VENT TERMINATION X AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner Outside Corner Alcove Applications*
D
C C
F=
G= Combustible
Combustible 6" (152 mm) V
G
6" (152 mm) Noncombustible
V
2" (51 mm) E
Noncombustible O
V 2" (51 mm) F
Balcony - Balcony -
with no side wall with perpendicular side wall
E = Min. 6” (152 mm) for
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O = 8’ (2.4 m) Min.
M M No.
of Caps DMin. CMax.
V V
1 3’ (914 mm) 2 x DActual
P 2 6’ (1.8 m) 1 x DActual
Combustible & 3 9’ (2.7 m) 2/3 x DActual
M= Noncombustible 4 12’ (3.7 m) 1/2 x DActual
Combustible &
Noncombustible M = 24" (610 mm)
DMin. = # of Termination caps x 3
12" (305 mm) P = 20” (508 mm)
CMax. = (2 / # termination caps) x DActual 584-15
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
Fig. 10a Termination clearances.
the collars of the fireplace and termination. If the ter- Fig. 11 Apply high temperature sealant to 4” and 7” pipes.
mination has an internal bead, be sure to overlap and
secure 1” (25 mm) past the bead.
10007852 11
Fig. 12 Twist-lock pipe joints. Horizontal dimension from the outside face of the wall to
the center of the fireplace vent flange
How to Use the Vent Graph CFM102
Sidewall vent graph showing the relationship between vertical
DV Graphic
and horizontal dimensions for a Direct Vent flue system.
The vent chart should be read in conjunction with the
TWL100 9/28/00 sta
following vent installation instructions
Twist Lock Pipe to determine the Fig. 13 Sidewall venting graph. (Dimensions in feet)
3/12/99and
relationship of the vertical djt horizontal dimensions of
Vertical Sidewall Applications
the vent system.
1. Determine the height of the center of the horizontal Since it is very important that the vent-
vent pipe exiting through the outer wall. Using this ing system maintain its balance between
dimension on the Sidewall Vent Graph. (Fig. 13) the combustion air intake and the flue
locate the point intersecting with the slanted graph gas exhaust, certain limitations as to vent
line. configurations apply and must be strictly
2. From the point of this intersection, draw a vertical adhered to.
line to the bottom of the graph. The vent graph showing the relationship between verti-
3. Select the indicated dimension, and position the cal and horizontal side wall venting will help to deter-
fireplace in accordance with same. mine the various dimensions allowable.
12 10007852
20' (6m)
A
B
Pipe
7.5' (2.3m)
Straps Every
3’ (914mm)
Pipe Straps 7.5' 1 x 90° elbow in horizontal plane = 3’ (914mm)
Every 3’ (914mm) (2.3m)
3'
(914mm)
1 + 2 + 3 + 4 = 270°
3
2
1
FP1237
FP1239
Fig. 15 Maximum horizontal vent run.
Fig. 17 Maximum number of elbow degrees.
FP1237
horizontal plane
12/02
10007852 13
Framing
9³⁄₈” Detail
(240mm)
FP1240
FP1241
14 10007852
STEP 5
Measure the horizontal length requirement including
a 2” (51 mm) overlap, ie from the elbow to the outside
wall face plus 2” (51 mm) (or the distance required if
installing a second 90° elbow). (Fig. 21)
Always install horizontal venting on a level
plane.
STEP 6
Use appropriate length of pipe sections - telescopic or
fixed - and install the horizontal vent sections. The sec-
tions which go through the wall are packaged with the
starter kit, and can be cut to suit if necessary. (Fig. 22)
Sealing vent pipe and firestop gaps with
FP1243
high temperature sealant will restrict cold
air being drawn in around fireplace. Fig. 23 Apply high temperature sealant to collars or termina-
tions.
Support horizontal pipes every 3’ (914 mm) with metal
pipe straps. Make sure the horizontal vent pipe is in-
stalled on a level horizontal plane.
6���"
(172mm)
FP1474
10007852 15
FP1474
spacer springs
4/04 djt
Downloaded from www.Manualslib.com manuals search engine
LDVT Series Direct Vent Gas Fireplace
Zero Clearance
Sleeve Screws
(if required) 7TDVSNORK
(Snorkel)
Firestop
4” (102mm)
7” Pipe Clearance
6���" (165mm) Min.
Window
24” (610mm) Well
Minimum*
FP1475
Gravel
Fig. 25 Bend flex vent at 90° so horizontal portion is 6¹⁄₂”
(165 mm) off top of unit. Drain
16 10007852
1 + 2 + 3 + 4 = 270°
Min. Height
7���' (2.3m)
1 2
FP1244
FP1245
Fig. 28 Support straps for horizontal runs.
Fig. 29 Typical offset application.
• Up to two 45° elbows may be used within the
horizontal run. For each 45° elbow used on the
FP1245
horizontal level the maximum horizontal length must
through the roof
be reduced by 18” (457 mm). 90 & 45 degree
FP1244 12/02
through the roof
max/min dims
12/02
10007852 17
#7DVAIS into position and secure. (Fig. 30) Fig. 31 Roof and ceiling supports.
Attic Insulation
Shield
CFM110
Typical ceiling/roof support
#8 Sheet Metal Screws
Joist 10/90 (3 per joint)
Sealant
Storm Collar
Firestop Spacer
18 10007852
10007852 19
Venting Components
Operating Instructions
Glass Information 6. Tilt the glass frame out slightly at the bottom, lift the
frame up and away from the fireplace.
Only glass approved by CFM Corporation
7. To replace the glass frame reverse the procedure.
should be used on this fireplace.
� ������� Window
�������������� Frame As-
sembly
������������
Window
������������������ Frame
Pull
Assembly
������������� Push Clamp
Clamp Hook
�������������������� Handle
��������������� FP1228
10007852 21
Top Center
Rear Left (A44)
(A41) Rear Right
(A42)
Front Left
LG382
(A43)
Fig. 37 Correct log placement for 33LDVT.
22 10007852
36LDVT
1. Place rear log (B158) on rear brack- Rear
et (ensure log is seated properly to (B158)
the bracket and located to the two
pins), so it will not move from side to
side and is firmly positioned on the
bracket.
2. Place front left log (B160). Use the
log’s bottom hole to locate it onto
the front support and just rest on top
of the rear log.
3. Place front right log (B159). Use the
log’s bottom hole to locate it onto
the front support and the top hole to
the knob onto the rear log.
4. Place front center log (B161) on top
of the two small shelves at the front
log support and between the left
and right logs.
Front Left Front Right
5. Place ember material on top of (B160) Front Center (B159)
burner. Scatter the ember material (B161) LG481
over the tiles on the front area of Fig. 38 Correct log placement for 36LDVT.
the burner housing. (Fig. 45) Do not
pack the ember material. Separate it when unpacked Do not place any of the lava rock material
and keep it in a fluffy and loose condition for a more on the burner housing assembly.
realistic ember effect.
6. Scatter the lava rock material around the firebox
base. �����
39LDVT ����������
1. Place rear lob (BC14) on rear bracket
����
(ensure log is centered and seated Front Left
(BC15) Front Right
properly to the log support). (BC16)
2. Place front left log (BC15). Use log’s Rear
bottom hole to locate it onto the front (BC14)
support and just rest on top of the
rear log.
3. Place front right log (BC16). Use log’s
bottom hole to locate it onto the front
support and the top hole to the knob
on the rear log.
4. Place front center log (B138) on top
of the two small shelves at the front
log support, and between the left and
right logs.
5. Place ember material on top of
burner. Scatter the ember material
Front Center
over the tiles on the front area of the (B138) LG414
burner housing. (Fig. 46) Separate it
when unpacked and keep it in a fluffy Fig. 39 Correct log placement for 39LDVT.
and loose condition for a more realis-
tic ember effect. Do not place any of the lava rock material
on the burner housing assembly.
10007852 ����� 23
����������
Downloaded from www.Manualslib.com manuals search engine ����
LDVT Series Direct Vent Gas Fireplace
43LDVT
1. Place rear log (BD15) on rear bracket
(ensure log is centered and seated Top Center
(BBD18)
properly to the log support). Rear
(BD15)
2. Place front left log (BD16). Use log’s
Front Right
bottom notch to locate it onto the front (BD17)
support and just rest on top of the
Front
burner housing assembly. Left
3. Place front right log (BD17). Use log’s (BD16)
bottom notch to locate it onto the front
support and just rest on top of the
burner housing assembly.
4. Place ember material on top of burner.
5. Scatter the ember material over the
tiles on the front area of the burner
housing. (Fig. 40) Do not pack the
ember material. Separate it when
unpacked and keep it in a fluffy and Lava
Rock
loose condition for a more realistic
Lava Rock
ember effect. Ember Material
6. Place front center log (B138) on top of
Front Center
the two small shelves at the front log (B138) LG434
support, and between the left and right
logs. Fig. 40 Correct log placement for 43LDVT.
7. Place top center log (BD18) on top of �����
Do not place any of the lava rock material
the rear log using the hole locator under the log and
on top of front right log. ����������
on the burner housing assembly.
8. Scatter lava rock material round the firebox base. �����
Flame Characteristics
Flame & Temperature Adjustment It is important to periodically perform a visual check of
the pilot and burner flames. Compare them to Figures
RN/RP & EN/EP Models 43 and 44.
For units equipped with ‘HI/LO’ valves the flame If the flame patterns appear abnormal contact a
adjustment is accomplished by rotating the ‘HI/LO’ qualified service provider for service and adjustment.
adjustments knob located near the center of the gas
control valve. (Fig. 41-42)
to decrease to increase
flame height flame height
SIT EN/EP
Turn
counterclockwise HV102 Turn clockwise
HI
flame height
Fig. 42 Flame adjustment knob for SIT valve. FP1541
24 FP390 10007852
FLAME ADJUSTMENT KNOB
11/21/96
33LDVT
LG384
Glowing Embers
36LDVT
LG482
LG384
Glowing Embers
33LDV log flames
1/05
39LDVT
�����
LG415
����������������
����
Glowing Embers
�����
����������������
43LDVT
����
LG435
Glowing Embers
10007852 25
Lighting Instructions
1. STOP! Read the safety information above. 10. Push the control knob all the way in and hold.
2. Turn off all electrical power to the fireplace. Immediately light the pilot by repeatedly depress-
3. For MN/MP/TN/TP appliances ONLY, go on to ing the piezo spark ignitor until a flame appears.
Step 4. For RN/RP appliances turn the ON/OFF Continue to hold the control knob in for about one
switch to “OFF” position or set thermostat to (1) minute after the pilot is lit. Release knob and it
lowest level. will pop back up. Pilot should remain lit. If it goes
4. Open control access panel. out, repeat steps 5 through 8.
5. Push in gas control knob slightly and turn clock-
wise to “OFF”. 3/8" - 1/2"
���
PILOT
�
��
��
1 2
Pilot
��
OFF
��
OFF
O FF
3 4 5
26 10007852
A. This fireplace is equipped with an ignition device Follow the gas suppliers instructions.
which automatically lights the pilot. DO NOT try to • If you cannot contact your gas supplier call
light the pilot by hand. the Fire Department
B. BEFORE OPERATING, smell all around the C. Use only your hand to push in or turn the gas
appliance area for gas. Be sure to smell next to control knob. Never use tools. If the knob will not
the floor because some gas is heavier than the air push in or turn by hand do not try to repair it, call
and will settle on the floor. a qualified service technician. Force or attempting
What to do if you smell gas repair may result in a fire or explosion.
• Do not try to light any appliance D. Do not use this appliance if any part has been
• Do not operate any electrical switch. under water. Immediately call a qualified service
technician to inspect the appliance and replace
• Do not use any phone in your building. any part of the control system and any gas control
• Immediately call your gas supplier from a that has been under water.
neighbor’s phone.
Lighting Instructions
1. STOP! Read the safety information above before 5. Turn the remote switch, if used, OFF. Turn the
continuing. wireless remote, if used, OFF.
2. Turn off all electrical power to the appliance. 6. Wait five (5) minutes to clear out any gas. Then
3. This appliance is equipped with an ignition device smell for gas, including near the floor. If you smell
which automatically lights the pilot. DO NOT try to gas STOP. Follow instructions B in the safety
light the pilot by hand. warnings above. If you do not smell gas go onto the
4. Access the gas control by lowering the lower next step.
access door (louvre assembly). 7. Close the access door.
8. Turn ON all electrical power to the appliance.
9. Turn remote switch or wireless remote to “ON”.
10. If the appliance will not operate, follow the
LO instructions TURNING OFF THE GAS TO THE
APPLIANCE and call your service technician or
HI gas supplier.
10007852 27
FP297A
INSTA VENT FREE
UVHB26 GAS SUPPLY
Downloaded from www.Manualslib.com manuals search engine 7/1/98
LDVT Series Direct Vent Gas Fireplace
START CHECK
YES
• Valve Is Turned On
• Wall Switch Is Not Turned On.
Pilot Lights Main Burner NO Watch For Grounded Wires!
• Thermopile Needs A Min. 325mv.
• Plugged Burner Orifice
YES
SYSTEM OK
28 10007852
0 Sec Purge
LED: 5 Flashes?
Reverse power cord polarity
YES
Pilot, Valve OFF, Spark OFF
Spark Off. Main Valve ON. NO
Have three ignition trials been completed?
Pilot Flame Continuously
Monitored
LED: 3 Flashes?
Lockout: Flame Loss
Reset by interrupting ON/OFF switch or
Pilot Flame Sense OK? NO
power for 10 sec
YES
NO
Have three pilot flame losses been
Pilot and Main Valve OFF? YES
detected?
YES
10007852 29
FP
IL
O OT
FP
IL
O OT
FC107
Fig. 46 Nova SITSIT820
820 gas valve. FC108
valve conversion
b. Ensure the10/03
rubber gasket
SIT(D) is properly posi-
Log Locator tioned and install the new regulator
Hi/Lo pressure regula-
Pin
tor to the valve using the newconversion
screws (E) supplied
10/03
with the kit. Tighten screws securely. (Reference
Propane Gas torque - 25 in.LB)
�
c. Install the enclosed identification label (F) to the
valve body where it can be easily seen.
Honeywell Gas Control Valve (Fig. 47)
The Honeywell valve fitted to this unit is suitable for
use with LP or Natural Gas. It is converted to the
required gas application by the installation of a color
Log Locator
Pin coded “conversion screw”.
KT615
a) Using a suitable small screwdriver lift out the
central regulator cap from the “Hi - Lo” knob on
Fig. 45 Move log locator pins to new locations on rear log the valve.
support. b) Unscrew the exposed conversion screw.
7. Remove the main burner orifice and replace it with c) Insert the new color coded conversion screw.
the orifice supplied in the conversion kit. Do not over-tighten the screw, it must be finger
8. SIT top Convertible Pilot����� tight.
Gently lift off the pilot hood from the pilot. (Do not
���������������� d) Refit the regulator cap.
remove the spring clip holding the hood in place). e) Mount the conversion label supplied with con-
���� the exposed orifice.
Using a 5/32” Allen key, unscrew version screw to the valve in a visible position.
Insert the new orifice supplied in the kit, do not over 11. Reassemble the fireplace in the reverse order, ex-
tighten the orifice. Replace the pilot hood ensuring cept for the window frame assembly. Leave this off
the index tab aligns with the notch on the hood. until after the unit has been checked for leaks and
the gas supply has been bled.
30 10007852
12. After bleeding the gas line and checking for leaks
with a soap solution, replace the window frame Regulator Cap Conversion Screw
assembly. Fire up the unit, check for flame impinge-
ment on the logs, adjusting them if necessary. Check
manifold and supply pressures against appliance
specifications. LO
Pressure Regu-
lator Housing
HV120
Maintenance
Burner and Burner Compartment Most of theseHV120
components may require only an
It is important to keep the burner and the burner occasional checkup and cleaning
Honeywell valve and some may
compartment clean. At least once per year the logs and require adjustment. If repair is necessary, it should
conversion
lava rock/ember material should be removed and the be performed by a qualified technician.
9/24/02 djt
burner compartment vacuumed and wiped out. Remove 1. Turn off pilot light at gas valve.
and refit the logs as per the instructions in this manual. 2. Allow fireplace to cool if it has been operating.
Always handle the logs with care as they 3. Remove window frame assembly. (Refer to Window
are fragile and may also be hot if the Frame Assembly Removal section.)
fireplace has been in use. 4. Remove logs.
FK24/FK12 Fan Assembly 5. Vacuum burner compartment especially around
orifice primary air openings.
The fan unit requires periodic cleaning. At least once
6. Visually inspect pilot. Brush or blow away any dust
per month in the operating season open the lower
or lint accumulation.
louvre panels and wipe or vacuum the area around the
fan to remove any build up of dust or lint. 7. Reinstall logs.
8. Ignite pilot - Refer to Lighting Instructions.
Brass Trim
9. Reinstall window frame assembly.
Clean the brass trim pieces using a soft cloth lightly
To obtain proper operation, it is imperative that the pilot
dampened with lemon oil. Do not use water or
and burner’s flame characteristics are steady, not lifting
household cleaners on any brass components.
or floating.
Cleaning the Standing Typically, the top 3/8” to 1/2” of the thermopile should
Pilot Control System be engulfed in the pilot flame. (Refer to Page 24, Figure
43)
The burner and control system consist of:
To adjust pilot burner: (by qualified service technician)
• burner • gas orifice 1. Remove pilot adjustment cap
• pilot assembly • thermopile
2. Adjust pilot screw to provide properly sized flame.
• millivolt gas valve
3. Replace pilot adjustment cap.
The primary air shutter is set at factory and should
only be adjusted, if necessary, by a qualified service
technician.
10007852 31
1h 1i 2 3 12 14 11 9
7a,b 16
6a,b
18a,b
19a,b
15 13
17
LO
8
HI
21 20
23
26
31
29
22
24
33 25
32
30
40
39
35
34
42 41
43
44
37
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time,
with out notice.
33/36/39/43LDVT 7852
LDVT parts
1/05
33LDVT units: GFTN2I0, GFTL2I0, GFTE2I0 �����
36LDVT units: GFTN2J1, GFTL2J1, GFTE2J1
39LDVT units: GFTN2K0, GFTE2K0
43LDVT units: GFTN2N0, GFTE2N0
32 10007852
33/36/39/43LDVT (continued)
Ref. Description 33LDVT 36LDVT 39LDVT 43LDVT
1. Log Set (complete) 10007567 10010113 10008214 10008314
1a. Front Left Log A43 B160 BC15 BD16
1b. Front Right Log -- B159 BC16 BD17
1c. Front Center Log -- B161 B138 B138
1d. Rear Log -- B158 BC14 BD15
1e. Rear Left Log A41 -- -- --
1f. Rear Right Log A42 -- -- --
1g. Top Center Log A44 -- -- BD18
1i. Lava Rock Package 10001454 10001454 10001454 10001454
1k. Ember (Package) 51915 51915 51915 51915
2a. Burner Housing Assy - Natural 10007558 10007127 10008218 10008464
2b. Burner Housing Assy - Propane 10007558 10008042 10008586 10008587
3. Ceramic Tile (Single) 57803 57803 57803 57803
4a. Orifice Burner - Natural Refer to Rating Plate for Orifice Size
4b. Orifice Burner - Propane Refer to Rating Plate for Orifice Size
5a. Orifice Pilot - Natural 10002268 10002268 10002268 10002268
5b. Orifice Pilot - Propane 10002269 10002269 10002269 10002269
6a. Pilot Assy SIT - RN 10002264 10002264 10002264 10002264
6b. Pilot Assy SIT - RP 10002265 10002265 10002265 10002265
7a. Pilot Assy SIT - EN 10002387 10002387 10002387 10002387
7b. Pilot Assy SIT - EP 10002388 10002388 10002388 10002388
8. Pilot Tubing w/Fittings SIT 10001296 10001296 10001296 10001296
9. Pilot Hood 10002385 10002385 10002385 10002385
10. Manifold Tubing w/Fittings 57318 57318 57318 57318
11. Thermocouple - RN/RP 53373 53373 53373 53373
12. Thermopile - RN/RP 51827 51827 51827 51827
13. Electrode Ignitor w/Cable -RN/RP 10001297 10001297 10001297 10001297
14. Electrode Ignitor - EN/EP 52465 52465 52465 52465
15. Cable Ignitor - EN/EP 10000696 10000696 10000696 10000696
16. Sensing Electrode - EN/EP 57885 57885 57885 57885
17. Ignitor Piezo, SIT 820 Valve 52464 52464 52464 52464
18a. Valve SIT 820 - RN 52677 52677 52677 52677
18b. Valve SIT 820 - RP 52678 52678 52678 52678
19a. Valve SIT 822 - EN 57884 57884 57884 57884
19b. Valve SIT 822 - EP 57883 57883 57883 57883
20. Flexible Gas Line w/ON/OFF Shut-off Valve 20002500 20002500 20002500 20002500
21. Fan Assy (w/Brkt) (FK24 Option) ZA1100 ZA1100 ZA1100 ZA1100
22. Fan Assy (FK12 Option) ZA1110 ZA1110 ZA1110 ZA1110
23. Electrical Cord (6 ft.) 51865 51865 51865 51865
24. Fan Temperature Sensor (FK24) 51704 51704 51704 51704
25. Speed Control (FK24) 51738 51738 51738 51738
26. Speed Control Knob (FK24) 51882 51882 51882 51882
29. Frame Window w/glass 10009693 10009694 10009695 10008535
30. Clamp Frame Window 54174 54174 54174 54174
31. Top Louvre Assy 10007400 10007090 10007984 10008311
32. Bottom Louvre Assy 10007397 10007092 10007986 10008307
10007852 33
33/36/39/43LDVT (continued)
Ref. Description 33LDVT 36LDVT 39LDVT 43LDVT
33a. Support Rear Log - Natural 10007561 10007162 10008211 10008480
33b. Support Rear Log - LP 10007561 10008045 10008211 10008490
34. Support Front Log 10007562 10007112 10008416 10008469
35. ON/OFF Switch 51842 51842 51842 51842
37. Relief Plate Assy (Burner Base) 10004192 10004192 10004192 10004192
38. Remote Switch Kit (Not Shown) 53875 53875 53875 53875
39. Ignition Control from Synetek (EN) 10007939 10007939 10007939 10007939
40. Wire Harness (EN) Synetek (low voltage) 10008139 10008139 10008139 10008139
41. Wire Harness (EN) Synetek (high voltage) 10008140 10008140 10008140 10008140
42. Restrictor Plate -- 10008048 10008048 10008048
43. Clevis Pin 10008615 10008615 10008615 10008615
44. Clip Pin Hitch 10008616 10008616 10008616 10008616
34 10007852
Optional Accessories
Fan Kits Thermal Sen-
sor Fan
FK24 Fan Assembly
This auxiliary fan system increases the efficiency of the
circulation of the heating air.
The FK24 fan kit allows variable speed control of the
circulation fan and also incorporates a heat sensor in
the circuit.
Specifications
115 Volt / 60Hz / 56 Watts Fan Speed Gas EB-1
Lines Receptacle
Maintenance FP1230 Switch Box
The fan itself does not require regular maintenance,
Fig. 48 FK24 fan placement.
however periodic cleaning of the fan and the
surrounding area is required. FK12
Check the area under the control door (lower louvre This auxiliary fan system increases the efficiency of the
assembly) and in front of the fan and wipe or vacuum this FP1230
circulation of the heating air.
area at least once a month during the operating season. The FK12 Fan Assembly is FK24
a fixed speed fan system
Installation fan install
and does not allow for variable speed control. It does
The fan assembly and other components are supplied not use the speed control 11/02
unit or the heat sensor used
fully wired eliminating the need for a licensed electrician in the FK24 Kit.
to carry out the installation. Specifications
If hard wiring the fan using Method B (following), we 115 Volts / 60 Hz / 56 Watts.
strongly recommend the use of a licensed electrician. Maintenance
1. Open the lower louvre assembly. Maneuver the fan The fan itself does not require regular maintenance,
& bracket assembly around the gas valve and lines however periodic cleaning of the fan and the
to locate the unit onto the screw studs on the back of surrounding area is required.
the fireplace.
2. Install the thermal sensor under the bottom of the of Check the area under the control door (lower louvre
the firebox, locating it over the two 10 mm studs and assembly) and in front of the fan and wipe or vacuum this
secure it with nuts. area at least once a month during the operating season.
3. Locate the fan speed control unit. This can be fitted Installation
behind the lower louvre assembly as in Figure 48 The fan assembly is supplied fully wired eliminating the
or located remotely in a conveniently located wall need for a licensed electrician to carry out the installation.
mounted electrical box. Remote location of the 1. Open the lower Louvre assembly. Maneuver the
speed control will require suitable extension of the fan & bracket assembly around the gas valve and
component wiring. lines to locate the unit against the back wall of the
4. The power supply may be connected in two ways: appliance, resting on the base.
Method A 2. With the protective cover removed from the self-
Route the 6’ lead fitted to the unit to a conveniently adhesive ‘Velcro’ strips apply mild pressure to the
located wall socket. fan & bracket unit to secure the strips to the metal
Method B (Using EB-1 Receptacle Box) panels. No further securing is required.
The EB-1 receptacle box (Pt. # ZA1200) may be 3. Power to the fan can be supplied by plugging the
hard wired into the house supply. The fan lead is supplied lead into a conveniently located wall socket
then plugged into the EB-1 box. For instruction on or by using a hard-wired EB-1 connector box.
wiring the EB-1 Electrical Junction Box see the
earlier chapter in the Installation section of this
manual.
10007852 35
Firebox Back
Fan
FP1231 Panel
Temperature Sensor Rear Panel Sup-
port Brackets Ceramic panels
Speed Control 11/02
Black
White
Ground Rear Log
Support
FP1025
FP1232
Fig. 49 FK24 fan wiring. FP394 Fig. 51 Rear refractory panel installation.
WIRING DIAGRAM
Ceramic Refractory
11/20/96
Panels
Remote Controls
Ceramic refractory panels are available for the LDV
series appliances Optional remote control FP1232
units are available to control
Kit Model and Finish different functions of the appliances
rear ceramic panel
Unit Sandstone Red Black Grey Model Function/s Controlled
33LDVT GAHC3I0 GAFC3I0 GABC3I0 GAGC3I0
11/02
RCI ON/OFF
36LDVT GAHC3J0 GAFC3J0 GABC3J0 GAGC3J0 RC2 ON/OFF and Temperature.
39LDVT 39LDVCR
IMTFK Wall mounted thermostat control
43LDVT 43LDVCR
Take care when handling the refractory
panels as they are fragile until held in place
and supported.
Installation, refer to Figures 50 & 51
1. Remove the front window frame assembly.
2. Remove the logs.
3. Place the rear refractory panel in place. Locate the
lower edge of the panel in the ledge formed by the
top of the rear log support bracket.
4. Slide the side refractory panels into place to hold
the rear panel secure. Repeat the procedure on the
other side.
5. Replace the logs and window frame assembly.
36 10007852
10007852 37
38 10007852
10007852 39
CFM Corporation
410 Admiral Blvd. • Mississauga, Ontario, Canada L5T 2N6
800-668-5323 • www.cfmcorp.com