Kindly be noted that GIS shall follow the designer requirements mentioned in FF design drawings issued by Onspec
and fulfil all standard requirements in NFPA 12 & NFPA 2001.
The above points shall be shown in the shop drawings and performed by GIS/PTJ in terms of all necessary
mechanical and electrical related works.
Best regards.
1
Kindly be noted that GIS shall follow the designer requirements mentioned in FF design drawings issued by Onspec
and fulfil all standard requirements in NFPA 12 & NFPA 2001.
The above points shall be shown in the shop drawings and performed by GIS/PTJ in terms of all necessary
mechanical and electrical related works.
Best regards.
Please we need your technical approval for attached CO2 gas suppression system shop drawing for SR-01B room, so
we can update all drawing for other rooms accordingly,
Best Regards,
Dear All,
Kindly find attached updated CO2 gas suppression system shop drawing for SR 01B, which is approved from
firefighting discipline but fire alarm discipline has a comment “Fire Fighting Control Panel Model FR-320-R” shall be
completed with outdoor weatherproof protection cover”.
Best Regards,
3
From: Menna Mahmoud Abaza
Sent: Wednesday, May 24, 2023 2:40 PM
To: Mahmoud Saad Mohamed <mahmsaad@petrojet.com.eg>
Cc: Amir Wadih Awadallah <awadih@petrojet.com.eg>; Ayman Yousif <ay-yousif@petrojet.com.eg>; Ahmed Samy
Korany <asamy@petrojet.com.eg>; 'Ahmed Sheshtawy' <Ashesht@outlook.com>; Karim Mostafa Yousry
<karim.yousry@petrojet.com.eg>; Mohamed Hawwash <mhawash@petrojet.com.eg>; Mostafa Elrais
<mostafaelrais@petrojet.com.eg>; Ahmed Ragab Nassar (Eng) <aragab@petrojet.com.eg>
Subject: RE: MDF - SR 01B - Gas suppression shop drawing
Still same comment, “Fire Fighting Control Panel Model FR-320-R” shall be completed with outdoor weatherproof
protection cover.
Thanks
Please check below reply from GIS and feedback urgently to send attached shop drawing officially to WOTECH,
Best Regards,
4
Tel.: +20 2 2673 4000 Ext.: 5198
Fax.: +20 2 26734001
Email: mahmsaad@petrojet.com.eg
Website: www.petrojet.com.eg
Consider the environment.
Please don't print this e-mail unless you really need to.
[EXTERNAL EMAIL] DO NOT CLICK links or attachments unless you recognize the sender and know the content is
safe.
1- Pipe sizes as there are differences between layout and isometric in hydraulic calculation,
2- Add quantity of cylinders,
3- Update table of revisions,
4- Add revision clouds,
As per as our phone call Kindly find attached Shop drawing for Sr01B after modify as per your comments.
Best regards.
5
From: Mahmoud Saied [mailto:Mahmoud@gis-nas.com]
Sent: Wednesday, May 24, 2023 12:42 PM
To: 'Mahmoud Saad Mohamed' <mahmsaad@petrojet.com.eg>
Cc: 'Amir Wadih Awadallah' <awadih@petrojet.com.eg>; 'Ayman Yousif' <ay-yousif@petrojet.com.eg>; 'Ahmed
Samy Korany' <asamy@petrojet.com.eg>; 'Ahmed Sheshtawy' <Ashesht@outlook.com>; 'Karim Mostafa Yousry'
<karim.yousry@petrojet.com.eg>; 'Mohamed Hawwash' <mhawash@petrojet.com.eg>; 'Menna Mahmoud Abaza'
<menna.abaza@petrojet.com.eg>; 'Ayman Shaheen' <ayman@gis-nas.com>; 'Karim Mostafa Yousry'
<karim.yousry@petrojet.com.eg>; 'Mostafa Elrais' <mostafaelrais@petrojet.com.eg>; 'Ahmed Ragab Nassar (Eng)'
<aragab@petrojet.com.eg>
Subject: RE: MDF - SR 01B - Gas suppression shop drawing
Best regards.
1- Pipe sizes as there are differences between layout and isometric in hydraulic calculation,
2- Add quantity of cylinders,
3- Update table of revisions,
4- Add revision clouds,
5- Check attached fire alarm department comment (mail),
6
Best Regards,
Please check attached more detailed shop drawing for SR 01B, please feedback urgently,
Best Regards,
7
Tel.: +20 2 2673 4000 Ext.: 5198
Fax.: +20 2 26734001
Email: mahmsaad@petrojet.com.eg
Website: www.petrojet.com.eg
Consider the environment.
Please don't print this e-mail unless you really need to.