Adding WOTECH participants.

Dear Eng Mahmoud,

Kindly be noted that GIS shall follow the designer requirements mentioned in FF design drawings issued by Onspec
and fulfil all standard requirements in NFPA 12 & NFPA 2001.

In Onspec drawings, the following is required:-

1- All carbon steel pipes shall be internally hot-dip galvanized.


2- All doors shall be automatically locked before gas suppression discharge.
3- All ventilation and louvers shall shut down automatically before system discharge.

The above points shall be shown in the shop drawings and performed by GIS/PTJ in terms of all necessary
mechanical and electrical related works.

Best regards.

From: Waleed Shafik


Sent: Monday, June 12, 2023 1:03 PM
To: Mahmoud Saad Mohamed <mahmsaad@petrojet.com.eg>
Cc: Amir Wadih Awadallah <awadih@petrojet.com.eg>; Ayman Yousif <ay-yousif@petrojet.com.eg>; Ahmed Samy
Korany <asamy@petrojet.com.eg>; Mohamed Hawwash <mhawash@petrojet.com.eg>; akamal@ethydco-eg.com;
Mohamed Dawood <mmbd1978@gmail.com>; 'Ahmed Sheshtawy' <Ashesht@outlook.com>; Osama Eltalkhawy
<osamaeltalkhawy@petrojet.com.eg>; Mohamed Fatouh <Mohamed-Fatouh@wotech-eg.com>; Mazen Emad
<mazen-emad@wotech-eg.com>
Subject: RE: MDF - SR 01B - Gas suppression shop drawing

Dear Eng Mahmoud,

1
Kindly be noted that GIS shall follow the designer requirements mentioned in FF design drawings issued by Onspec
and fulfil all standard requirements in NFPA 12 & NFPA 2001.

In Onspec drawings, the following is required:-

1- All carbon steel pipes shall be internally hot-dip galvanized.


2- All doors shall be automatically locked before gas suppression discharge.
3- All ventilation and louvers shall shut down automatically before system discharge.

The above points shall be shown in the shop drawings and performed by GIS/PTJ in terms of all necessary
mechanical and electrical related works.

Best regards.

From: Mahmoud Saad Mohamed <mahmsaad@petrojet.com.eg>


Sent: Monday, May 29, 2023 3:17 PM
To: Waleed Shafik <waleed-shafik@wotech-eg.com>; waleed.shafik1990@gmail.com
Cc: Amir Wadih Awadallah <awadih@petrojet.com.eg>; Ayman Yousif <ay-yousif@petrojet.com.eg>; Ahmed Samy
Korany <asamy@petrojet.com.eg>; Mohamed Hawwash <mhawash@petrojet.com.eg>; akamal@ethydco-eg.com;
Mohamed Dawood <mmbd1978@gmail.com>; 'Ahmed Sheshtawy' <Ashesht@outlook.com>; Osama Eltalkhawy
<osamaeltalkhawy@petrojet.com.eg>
Subject: FW: MDF - SR 01B - Gas suppression shop drawing

Dear Eng. Waleed,

Please we need your technical approval for attached CO2 gas suppression system shop drawing for SR-01B room, so
we can update all drawing for other rooms accordingly,

Your urgent reply is highly appreciated,

Best Regards,

Mahmoud Saad Mohamed,


Mechanical Design Engineer
PETROJET HEADQUARTER

 Plot 21~26 – Sector 1, City Center Fifth


Settlement, New Cairo
Cairo, Egypt
 Tel.: +20 2 2673 4000 Ext.: 5198
 Fax.: +20 2 26734001
 Email: mahmsaad@petrojet.com.eg
2
 Website: www.petrojet.com.eg

 Consider the environment.


Please don't print this e-mail unless you really need to.

From: Mahmoud Saad Mohamed


Sent: Wednesday, May 24, 2023 1:44 PM
To: Ahmed Samy Korany <asamy@petrojet.com.eg>; 'Ahmed Sheshtawy' <Ashesht@outlook.com>
Cc: Amir Wadih Awadallah <awadih@petrojet.com.eg>; Ayman Yousif <ay-yousif@petrojet.com.eg>; Karim Mostafa
Yousry <karim.yousry@petrojet.com.eg>; Mohamed Hawwash <mhawash@petrojet.com.eg>; Mostafa Elrais
<mostafaelrais@petrojet.com.eg>; Ahmed Ragab Nassar (Eng) <aragab@petrojet.com.eg>; 'Mohamed Dawood'
<mmbd1978@gmail.com>; Osama Eltalkhawy <osamaeltalkhawy@petrojet.com.eg>;
ahmedtahoon012@yahoo.com; Samir Refaat M <samirr11@petrojet.com.eg>; Tamer Fathalla
<tamerfathalla@gmail.com>; Elsayed Abouzeid <sayedabouzeid@petrojet.com.eg>; Menna Mahmoud Abaza
<menna.abaza@petrojet.com.eg>
Subject: FW: MDF - SR 01B - Gas suppression shop drawing

Dear All,

Kindly find attached updated CO2 gas suppression system shop drawing for SR 01B, which is approved from
firefighting discipline but fire alarm discipline has a comment “Fire Fighting Control Panel Model FR-320-R” shall be
completed with outdoor weatherproof protection cover”.

Best Regards,

Mahmoud Saad Mohamed,


Mechanical Design Engineer
PETROJET HEADQUARTER

 Plot 21~26 – Sector 1, City Center Fifth


Settlement, New Cairo
Cairo, Egypt
 Tel.: +20 2 2673 4000 Ext.: 5198
 Fax.: +20 2 26734001
 Email: mahmsaad@petrojet.com.eg
 Website: www.petrojet.com.eg
 Consider the environment.
Please don't print this e-mail unless you really need to.

3
From: Menna Mahmoud Abaza
Sent: Wednesday, May 24, 2023 2:40 PM
To: Mahmoud Saad Mohamed <mahmsaad@petrojet.com.eg>
Cc: Amir Wadih Awadallah <awadih@petrojet.com.eg>; Ayman Yousif <ay-yousif@petrojet.com.eg>; Ahmed Samy
Korany <asamy@petrojet.com.eg>; 'Ahmed Sheshtawy' <Ashesht@outlook.com>; Karim Mostafa Yousry
<karim.yousry@petrojet.com.eg>; Mohamed Hawwash <mhawash@petrojet.com.eg>; Mostafa Elrais
<mostafaelrais@petrojet.com.eg>; Ahmed Ragab Nassar (Eng) <aragab@petrojet.com.eg>
Subject: RE: MDF - SR 01B - Gas suppression shop drawing

Dear Eng Mahmoud,

Still same comment, “Fire Fighting Control Panel Model FR-320-R” shall be completed with outdoor weatherproof
protection cover.

Thanks

From: Mahmoud Saad Mohamed


Sent: Wednesday, May 24, 2023 2:35 PM
To: Menna Mahmoud Abaza <menna.abaza@petrojet.com.eg>
Cc: Amir Wadih Awadallah <awadih@petrojet.com.eg>; Ayman Yousif <ay-yousif@petrojet.com.eg>; Ahmed Samy
Korany <asamy@petrojet.com.eg>; 'Ahmed Sheshtawy' <Ashesht@outlook.com>; Karim Mostafa Yousry
<karim.yousry@petrojet.com.eg>; Mohamed Hawwash <mhawash@petrojet.com.eg>; Mostafa Elrais
<mostafaelrais@petrojet.com.eg>; Ahmed Ragab Nassar (Eng) <aragab@petrojet.com.eg>
Subject: RE: MDF - SR 01B - Gas suppression shop drawing

Dear Eng. Menna,

Please check below reply from GIS and feedback urgently to send attached shop drawing officially to WOTECH,

Best Regards,

Mahmoud Saad Mohamed,


Mechanical Design Engineer
PETROJET HEADQUARTER

 Plot 21~26 – Sector 1, City Center Fifth


Settlement, New Cairo
Cairo, Egypt

4
 Tel.: +20 2 2673 4000 Ext.: 5198
 Fax.: +20 2 26734001
 Email: mahmsaad@petrojet.com.eg
 Website: www.petrojet.com.eg
 Consider the environment.
Please don't print this e-mail unless you really need to.

From: Mahmoud Saied [mailto:Mahmoud@gis-nas.com]


Sent: Wednesday, May 24, 2023 2:32 PM
To: Mahmoud Saad Mohamed <mahmsaad@petrojet.com.eg>
Cc: Amir Wadih Awadallah <awadih@petrojet.com.eg>; Ayman Yousif <ay-yousif@petrojet.com.eg>; Ahmed Samy
Korany <asamy@petrojet.com.eg>; 'Ahmed Sheshtawy' <Ashesht@outlook.com>; Karim Mostafa Yousry
<karim.yousry@petrojet.com.eg>; Mohamed Hawwash <mhawash@petrojet.com.eg>; Menna Mahmoud Abaza
<menna.abaza@petrojet.com.eg>; 'Ayman Shaheen' <ayman@gis-nas.com>; Karim Mostafa Yousry
<karim.yousry@petrojet.com.eg>; Mostafa Elrais <mostafaelrais@petrojet.com.eg>; Ahmed Ragab Nassar (Eng)
<aragab@petrojet.com.eg>
Subject: RE: MDF - SR 01B - Gas suppression shop drawing

[EXTERNAL EMAIL] DO NOT CLICK links or attachments unless you recognize the sender and know the content is
safe.

Dear Eng. Mahmoud,

1- Pipe sizes as there are differences between layout and isometric in hydraulic calculation,
2- Add quantity of cylinders,
3- Update table of revisions,
4- Add revision clouds,
As per as our phone call Kindly find attached Shop drawing for Sr01B after modify as per your comments.

5-Check attached fire alarm department comment (mail).


Waiting for the PO.

Best regards.

Mahmoud Saied Mahmoud


Assistance site manager
(002) 01062063363
Global Integrated Systems

5
From: Mahmoud Saied [mailto:Mahmoud@gis-nas.com]
Sent: Wednesday, May 24, 2023 12:42 PM
To: 'Mahmoud Saad Mohamed' <mahmsaad@petrojet.com.eg>
Cc: 'Amir Wadih Awadallah' <awadih@petrojet.com.eg>; 'Ayman Yousif' <ay-yousif@petrojet.com.eg>; 'Ahmed
Samy Korany' <asamy@petrojet.com.eg>; 'Ahmed Sheshtawy' <Ashesht@outlook.com>; 'Karim Mostafa Yousry'
<karim.yousry@petrojet.com.eg>; 'Mohamed Hawwash' <mhawash@petrojet.com.eg>; 'Menna Mahmoud Abaza'
<menna.abaza@petrojet.com.eg>; 'Ayman Shaheen' <ayman@gis-nas.com>; 'Karim Mostafa Yousry'
<karim.yousry@petrojet.com.eg>; 'Mostafa Elrais' <mostafaelrais@petrojet.com.eg>; 'Ahmed Ragab Nassar (Eng)'
<aragab@petrojet.com.eg>
Subject: RE: MDF - SR 01B - Gas suppression shop drawing

Dear Eng. Mahmoud,


Kindly find attached Shop drawing for Sr01B after modify as per your comments.

Best regards.

Mahmoud Saied Mahmoud


Assistance site manager
(002) 01062063363
Global Integrated Systems

From: Mahmoud Saad Mohamed [mailto:mahmsaad@petrojet.com.eg]


Sent: Wednesday, May 24, 2023 11:24 AM
To: Mahmoud Saied <Mahmoud@gis-nas.com>
Cc: Amir Wadih Awadallah <awadih@petrojet.com.eg>; Ayman Yousif <ay-yousif@petrojet.com.eg>; Ahmed Samy
Korany <asamy@petrojet.com.eg>; Ahmed Sheshtawy <Ashesht@outlook.com>; Karim Mostafa Yousry
<karim.yousry@petrojet.com.eg>; Mohamed Hawwash <mhawash@petrojet.com.eg>; Menna Mahmoud Abaza
<menna.abaza@petrojet.com.eg>; 'Ayman Shaheen' <ayman@gis-nas.com>; Karim Mostafa Yousry
<karim.yousry@petrojet.com.eg>; Mostafa Elrais <mostafaelrais@petrojet.com.eg>; Ahmed Ragab Nassar (Eng)
<aragab@petrojet.com.eg>
Subject: RE: MDF - SR 01B - Gas suppression shop drawing

Dear Eng. Mahmoud,

Please revise attached after implementing below comments:

1- Pipe sizes as there are differences between layout and isometric in hydraulic calculation,
2- Add quantity of cylinders,
3- Update table of revisions,
4- Add revision clouds,
5- Check attached fire alarm department comment (mail),

6
Best Regards,

Mahmoud Saad Mohamed,


Mechanical Design Engineer
PETROJET HEADQUARTER

 Plot 21~26 – Sector 1, City Center Fifth


Settlement, New Cairo
Cairo, Egypt
 Tel.: +20 2 2673 4000 Ext.: 5198
 Fax.: +20 2 26734001
 Email: mahmsaad@petrojet.com.eg
 Website: www.petrojet.com.eg
 Consider the environment.
Please don't print this e-mail unless you really need to.

From: Mahmoud Saad Mohamed


Sent: Wednesday, May 24, 2023 10:38 AM
To: Menna Mahmoud Abaza <menna.abaza@petrojet.com.eg>
Cc: Amir Wadih Awadallah <awadih@petrojet.com.eg>; Ayman Yousif <ay-yousif@petrojet.com.eg>; Ahmed Samy
Korany <asamy@petrojet.com.eg>; 'Ahmed Sheshtawy' <Ashesht@outlook.com>; Karim Mostafa Yousry
<karim.yousry@petrojet.com.eg>; Mohamed Hawwash <mhawash@petrojet.com.eg>
Subject: MDF - SR 01B - Gas suppression shop drawing

Dear Eng. Menna,

Please check attached more detailed shop drawing for SR 01B, please feedback urgently,

Best Regards,

Mahmoud Saad Mohamed,


Mechanical Design Engineer
PETROJET HEADQUARTER

 Plot 21~26 – Sector 1, City Center Fifth


Settlement, New Cairo
Cairo, Egypt

7
 Tel.: +20 2 2673 4000 Ext.: 5198
 Fax.: +20 2 26734001
 Email: mahmsaad@petrojet.com.eg
 Website: www.petrojet.com.eg
 Consider the environment.
Please don't print this e-mail unless you really need to.

You might also like