Fwd: STC PSS


musheer Khan <musheer.khaneee@gmail.com>
Tue 9/1/2020 11:31 AM
To:mtalha. sticco <mtalha.sticco@outlook.sa>;Shahid Hussain <hussainshahid9785@gmail.com>

3 attachments (6 MB)
image6d8e14.PNG; 20200831_155658.jpg; 20200831_155005.jpg;

---------- Forwarded message ---------


From: Antonino A. Loste <lostea@marafiq.com.sa>
Date: Tue, 1 Sep 2020, 8:32 am
Subject: RE: STC PSS
To: musheer Khan <musheer.khaneee@gmail.com>
Cc: najmul qamar <qamar.sticco@gmail.com>, kashif.samaconstruction@gmail.com
<kashif.samaconstruction@gmail.com>, Jerry A. Consorte <consorteja@marafiq.com.sa>, Usman
Gauhar <gauharu@marafiq.com.sa>, Mohammed Ebrahim Khan <khanme@marafiq.com.sa>

Classified as MARAFIQ Internal Use

Dear Qamar / Musheer,

This methodology (mounting the CT’s via screws and penetrating/damaging the bus bars insolation’s)
is not a good workmanship & practice. Kindly rectify this PSS (STC Tower area) immediately to avoid
any such electrical hazard in future. Once done, invite concerned PJ & T&D personnel for inspection.

Furthermore, apply the same rectifications to other PSS’s (on-going Constructions) in Saudi Aramco
Bachelor Housing, RC Health Services, Ansari Hospital, and Golden Kindergarten, etc. Thanks.

Regards,

From: musheer Khan <musheer.khaneee@gmail.com>


Sent: Monday, August 31, 2020 4:35 PM
To: Antonino A. Loste <lostea@marafiq.com.sa>
Cc: najmul qamar <qamar.sticco@gmail.com>; kashif.samaconstruction@gmail.com; Jerry A. Consorte
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 1/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

<consorteja@marafiq.com.sa>; Usman Gauhar <gauharu@marafiq.com.sa>


Subject: Re: STC PSS

EXTERNAL: This is an external email received from outside MARAFIQ. If the email contains any suspicious
content, please report it immediately using phishing reporter or email it to soc@marafiq.com.sa.

Hope everything is fine at your end.

I would like to inform that this the normal & general configuration from Al-Fanar side.

I have check today few Al-Fanar PSS and I found the same configuration in all.

Moreover the Insulation value from secondary to gorund found satisfactory.

Tomorrow Engr'Talha will take the PTWC for STC transformer and check again the insulation value from secondary
(Low voltage)to ground on 1KV for confirm the value again.

I had also shared the video also on your watsapps for your reference.

Regards

Musheer

On Mon, 31 Aug 2020, 3:15 pm Antonino A. Loste <lostea@marafiq.com.sa wrote:

Classified as MARAFIQ Internal Use

Dear Qamar,

Please find the attached pictures showing the LV CT’s mounted inside the PSS. Methodology
mounting it is not correct. Kindly rectify immediately.

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 2/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

Regards,

This email has been classified as MARAFIQ Internal Use by Antonino Loste on 31/08/2020
2:11 PM.

Antonino A. Loste

Project Engineer Electrical

Projects Implementation-Y Department

+966 14 396 6295 | lostea@marafiq.com.sa

cid:image8b8ab1.PNG@7b43a6d8.4496f www.marafiq.com.sa
bcd

Power and Water Utility Company for Jubail and Yanbu

cid:imagecf0f73.PNG@1918b6bc.4092e4
a8

cid:imageb284c6.PNG@8b882924.4f962
2a3

cid:imagef8e98e.PNG@342f5b1e.41bc22
c3

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 3/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

This email has been classified as MARAFIQ Internal Use by Antonino Loste on 01/09/2020
8:31 AM.

Antonino A. Loste
Project Engineer Electrical
Projects Implementation-Y Department

+966 14 396 6295 | lostea@marafiq.com.sa


www.marafiq.com.sa
Power and Water Utility Company for Jubail and Yanbu

From: Mohammed Ebrahim Khan


Sent: Monday, August 31, 2020 10:49 AM
To: Antonino A. Loste <lostea@marafiq.com.sa>; Hussain Abdullah Abdulrahman Qashqari
<qashqarihaa@marafiq.com.sa>
Cc: Najmul Qamar <najmulqamar@gmail.com>; musheer Khan <musheer.khaneee@gmail.com>;
kashif.samaconstruction@gmail.com; Zulfiqar Ahmad (zulfiqara576@gmail.com)
<zulfiqara576@gmail.com>; mtalha. sticco <mtalha.sticco@outlook.sa>; Yasser Mohammed Al-
Harbi <harbiym@marafiq.com.sa>; Jerry A. Consorte <consorteja@marafiq.com.sa>; Abdullah
Moayedh Hasan Al-Muhaya <muhayaamh@marafiq.com.sa>; Saad Nuwayfi Al-Sulami
<sulamisn@marafiq.com.sa>; Usman Gauhar <gauharu@marafiq.com.sa>; Mohammed Abdullah
Mohammed Al-Najdi <Najdiam@marafiq.com.sa>; Abdullah Moayedh Hasan Al-Muhaya
<muhayaamh@marafiq.com.sa>
Subject: RE: STC Tower Energization Clearance

Classified as MARAFIQ Internal Use

Dear all,

With reference to the attached , Please instruct the contractor to carry out the rectification work in a
Professional manner , in order to avoid any safety Related Incidents. Please arrange to expedite the
rectification work at the earliest.

Regards,

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 4/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

This email has been classified as MARAFIQ Internal Use by Mohammed Khan on 31/08/2020 10:48
AM.

Mohammed Ebrahim Khan

Supervisor, Distribution Operation

Power Distribution

Tel 6636

From: Mohammed Ebrahim Khan


Sent: Sunday, August 30, 2020 7:00 AM
To: Antonino A. Loste <lostea@marafiq.com.sa>; Mohammed Abdullah Mohammed Al-Najdi
<Najdiam@marafiq.com.sa>; Hussain Abdullah Abdulrahman Qashqari
<qashqarihaa@marafiq.com.sa>
Cc: Najmul Qamar <najmulqamar@gmail.com>; musheer Khan <musheer.khaneee@gmail.com>;
kashif.samaconstruction@gmail.com; Zulfiqar Ahmad (zulfiqara576@gmail.com)
<zulfiqara576@gmail.com>; mtalha. sticco <mtalha.sticco@outlook.sa>; Yasser Mohammed Al-
Harbi <harbiym@marafiq.com.sa>; Jerry A. Consorte <consorteja@marafiq.com.sa>; Abdullah
Moayedh Hasan Al-Muhaya <muhayaamh@marafiq.com.sa>; Saad Nuwayfi Al-Sulami
<sulamisn@marafiq.com.sa>
Subject: RE: STC Tower Energization Clearance

Classified as MARAFIQ Internal Use

Dear,

Please advise the APR to Co Ordinate with our API ( Najdi) & Project Team ( Huassain Qasqari) for
Permit and access. We r ready to issue the requested Permit.

Regards,

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 5/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

This email has been classified as MARAFIQ Internal Use by Mohammed Khan on 30/08/2020 6:59
AM.

From: Antonino A. Loste <lostea@marafiq.com.sa>


Sent: Thursday, August 27, 2020 2:20 PM
To: Saad Nuwayfi Al-Sulami <sulamisn@marafiq.com.sa>; Mohammed Ebrahim Khan
<khanme@marafiq.com.sa>
Cc: Najmul Qamar <najmulqamar@gmail.com>; musheer Khan <musheer.khaneee@gmail.com>;
kashif.samaconstruction@gmail.com; Zulfiqar Ahmad (zulfiqara576@gmail.com)
<zulfiqara576@gmail.com>; mtalha. sticco <mtalha.sticco@outlook.sa>; Yasser Mohammed Al-
Harbi <harbiym@marafiq.com.sa>; Jerry A. Consorte <consorteja@marafiq.com.sa>; Abdullah
Moayedh Hasan Al-Muhaya <muhayaamh@marafiq.com.sa>
Subject: RE: STC Tower Energization Clearance

Classified as MARAFIQ Internal Use

Gentlemen,

Please find attached PTW for your Signature & approval. We & our Contractor are ready to repair
the Misaligned MV Switches of the PSS of STC Tower project. Appreciate for your support. Thank
you very much.

Regards,

This email has been classified as MARAFIQ Internal Use by Antonino Loste on 27/08/2020
2:19 PM.

Antonino A. Loste

Project Engineer Electrical

Projects Implementation-Y

Tel 6295
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 6/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

From: mtalha. sticco <mtalha.sticco@outlook.sa>


Sent: Thursday, August 27, 2020 2:08 PM
To: Jerry A. Consorte <consorteja@marafiq.com.sa>; Antonino A. Loste <lostea@marafiq.com.sa>;
Yasser Mohammed Al-Harbi <harbiym@marafiq.com.sa>
Cc: Najmul Qamar <najmulqamar@gmail.com>; musheer Khan <musheer.khaneee@gmail.com>;
kashif.samaconstruction@gmail.com; Zulfiqar Ahmad (zulfiqara576@gmail.com)
<zulfiqara576@gmail.com>
Subject: Re: STC Tower Energization Clearance

EXTERNAL: This is an external email received from outside MARAFIQ. If the email contains any suspicious
content, please report it immediately using phishing reporter or email it to soc@marafiq.com.sa.

Dear Sir,

Greeting's

You are requested to arrange PTWC, to get access in 18TXF-015A Medium Voltage Door to
check and rectify the operating Switch comment.

Thanks & Regards

M.Talha Burny
Electrical Engineer
Saudi Al-Terais Trading Industrial Contracting Co. Ltd. (STICCO)
( : + 966500545640

: E Mail : mtalha.alig@gmail.com
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 7/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

City: Yanbu (KSA)

From: najmul qamar <qamar.sticco@gmail.com>


Sent: Thursday, August 27, 2020 1:55 PM
To: mtalha. sticco <mtalha.sticco@outlook.sa>
Subject: Fwd: FW: Re: STC Tower Energization Clearance

FYA

Najmul Qamar
Project Manager, SAMA / STICCO Construction Limited

+966 143 213268, Ext.: 118 | +966 556698345 |


[mailto:qamar.sticco@gmail.com+&+najmul@samaa-
group.com]qamar.sticco@gmail.com & najmul@samaa-group.com

---------- Forwarded message ---------


From: Jerry A. Consorte <consorteja@marafiq.com.sa>
Date: Thu, Aug 27, 2020 at 1:54 PM
Subject: FW: Re: STC Tower Energization Clearance
To: najmul qamar <qamar.sticco@gmail.com>
Cc: Antonino A. Loste <lostea@marafiq.com.sa>, musheer Khan <musheer.khaneee@gmail.com>,
Kashif Khan <kashif.samaconstruction@gmail.com>, Zulfiqar Ahmad (zulfiqara576@gmail.com)
<zulfiqara576@gmail.com>

Classified as MARAFIQ Internal Use

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 8/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

TOP URGENT!

Dear Qamar,

Feeder 2KA07 / 2KB07 is in radial mode. Please expedite to rectify IAI #1 for misaligned switch.

Plan to energize the cable in loop thru mode today.

Regards,

This email has been classified as MARAFIQ Internal Use by Jerry Consorte on 27/08/2020 1:53 PM.

cid:image001.png@01D67C7D.23E059 Jerry A. Consorte


30

Engineer, Electrical

Projects Implementation - Yanbu Department

+966 14 324 6562 | consorteja@marafiq.com.sa

www.marafiq.com.sa

Power and Water Utility Company for Jubail and Yanbu

cid:image002.png@01D67C7D.23E059
30

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 9/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

cid:image003.png@01D67C7D.23E059
30

cid:image004.png@01D67C7D.23E059
30

From: Abdullah Moayedh Hasan Al-Muhaya


Sent: Thursday, August 27, 2020 1:41 PM
To: Antonino A. Loste <lostea@marafiq.com.sa>
Cc: Yasser Mohammed Al-Harbi <harbiym@marafiq.com.sa>; Saad Nuwayfi Al-Sulami
<sulamisn@marafiq.com.sa>; Fahad Saleem Saadi <saadfs@marafiq.com.sa>; Hani Abdullah
Baabdullah <baabdullahha@marafiq.com.sa>; Antonino A. Loste <lostea@marafiq.com.sa>; Jerry A.
Consorte <consorteja@marafiq.com.sa>; Mohammed Ebrahim Khan <khanme@marafiq.com.sa>
Subject: RE: Re: STC Tower Energization Clearance

Dear Antonino,

Contractor spoke with me and he confirm that he need 10 minutes to raise the shutter up. However,
please coordinate with the concerned to complete this task today ASAP.

Abdullah Moayedh Hasan Al-Muhaya

Supervisor, Power Connection

Power Distribution

Tel 6602

From: Abdullah Moayedh Hasan Al-Muhaya


Sent: Thursday, August 27, 2020 1:31 PM
To: Mohammed Ebrahim Khan <khanme@marafiq.com.sa>; Antonino A. Loste
<lostea@marafiq.com.sa>
Cc: Yasser Mohammed Al-Harbi <harbiym@marafiq.com.sa>; Saad Nuwayfi Al-Sulami
<sulamisn@marafiq.com.sa>; Fahad Saleem Saadi <saadfs@marafiq.com.sa>; Hani Abdullah
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 10/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

Baabdullah <baabdullahha@marafiq.com.sa>; Antonino A. Loste <lostea@marafiq.com.sa>; Jerry A.


Consorte <consorteja@marafiq.com.sa>
Subject: RE: Re: STC Tower Energization Clearance

Dear Antonino,

Please prepare the energization clearance for cable only as per operation request.

From: Mohammed Ebrahim Khan


Sent: Thursday, August 27, 2020 1:22 PM
To: Antonino A. Loste <lostea@marafiq.com.sa>; Abdullah Moayedh Hasan Al-Muhaya
<muhayaamh@marafiq.com.sa>; Jerry A. Consorte <consorteja@marafiq.com.sa>; Hussain
Abdullah Abdulrahman Qashqari <qashqarihaa@marafiq.com.sa>; Turki Abdulhafiz Al-Marwani
<marwanita@marafiq.com.sa>
Cc: Yasser Mohammed Al-Harbi <harbiym@marafiq.com.sa>; Saad Nuwayfi Al-Sulami
<sulamisn@marafiq.com.sa>; Fahad Saleem Saadi <saadfs@marafiq.com.sa>; Bandar Lafi Al-Harbi
<harbibl@marafiq.com.sa>; Faisal Mokhaydheer Bakheet Hojaily <hojailyfmb@marafiq.com.sa>;
Hani Abdullah Baabdullah <baabdullahha@marafiq.com.sa>
Subject: RE: Re: STC Tower Energization Clearance

Classified as MARAFIQ Internal Use

Dear all,

Please be informed that Distribution Feeder 2KA07 / 2KB07 is a Single Loop Distribution Feeder
and is currently on radial Mode, Due to Cut over work. If any Power interruption occurs in the
Subject Feeder, Power to Majority of the connected customers will be lost due to radial mode.

Please arrange to expedite to energization clearance of the newly Installed Package Substation
with Comments in Loop Thru Mode , in order for us to Operate in Loop Mode during Emergencies.

Note : No Deficiency was signed by all involved parties prior to the Spiking of the Loop Feeder.

Regards,

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 11/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

This email has been classified as MARAFIQ Internal Use by Mohammed Khan on 27/08/2020 1:21
PM.

Mohammed Ebrahim Khan

Supervisor, Distribution Operation

Power Distribution

Tel 6636

From: Mohammed Ebrahim Khan


Sent: Thursday, August 27, 2020 10:05 AM
To: Antonino A. Loste <lostea@marafiq.com.sa>; Abdullah Moayedh Hasan Al-Muhaya
<muhayaamh@marafiq.com.sa>; Jerry A. Consorte <consorteja@marafiq.com.sa>; Hussain
Abdullah Abdulrahman Qashqari <qashqarihaa@marafiq.com.sa>; Turki Abdulhafiz Al-Marwani
<marwanita@marafiq.com.sa>
Cc: Yasser Mohammed Al-Harbi <harbiym@marafiq.com.sa>; Saad Nuwayfi Al-Sulami
<sulamisn@marafiq.com.sa>; Fahad Saleem Saadi <saadfs@marafiq.com.sa>; Bandar Lafi Al-Harbi
<harbibl@marafiq.com.sa>; Faisal Mokhaydheer Bakheet Hojaily <hojailyfmb@marafiq.com.sa>;
Hani Abdullah Baabdullah <baabdullahha@marafiq.com.sa>
Subject: RE: Re: STC Tower Energization Clearance

Classified as MARAFIQ Internal Use

Dear all,

Please find attached the Pictures taken site , showing the Misalignment of the Medium Voltage
Switches in the Newly Installed Package Substation. Please arrange to expedite the rectification
works at the earliest , in order for us to Energize the New Transformer safely.

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 12/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

Regards,

This email has been classified as MARAFIQ Internal Use by Mohammed Khan on 27/08/2020 10:04
AM.

From: Antonino A. Loste <lostea@marafiq.com.sa>


Sent: Wednesday, August 26, 2020 2:29 PM
To: Abdullah Moayedh Hasan Al-Muhaya <muhayaamh@marafiq.com.sa>; Bandar Lafi Al-Harbi
<harbibl@marafiq.com.sa>; Mohammed Ebrahim Khan <khanme@marafiq.com.sa>
Cc: Jerry A. Consorte <consorteja@marafiq.com.sa>; Yasser Mohammed Al-Harbi
<harbiym@marafiq.com.sa>
Subject: Re: STC Tower Energization Clearance

Classified as MARAFIQ Internal Use

Gentlemen,

Please find attached Cables & Equipment Testing and Energization Clearance for STC Tower for your
approval. Thank you very much.

Regards,

This email has been classified as MARAFIQ Internal Use by Antonino Loste on 26/08/2020 2:28 PM.

Antonino A. Loste

Project Engineer Electrical

Projects Implementation-Y
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 13/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook
j p

Tel 6295

DISCLAIMER: This email and any files transmitted with it are confidential and intended
solely for the use of the individual or entity to whom they are addressed. If you have
received this email in error, please notify the sender. Please note that any views or
opinions presented in this email are solely those of the author and do not necessarily
represent Power and Water Utility Company for Jubail and Yanbu (MARAFIQ). Finally,
the recipient should check this email and any attachments for the presence of viruses.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) accepts no liability
for any damage caused by any virus transmitted by this email.

DISCLAIMER: This email and any files transmitted with it are confidential and intended
solely for the use of the individual or entity to whom they are addressed. If you have
received this email in error, please notify the sender. Please note that any views or
opinions presented in this email are solely those of the author and do not necessarily
represent Power and Water Utility Company for Jubail and Yanbu (MARAFIQ). Finally,
the recipient should check this email and any attachments for the presence of viruses.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) accepts no liability
for any damage caused by any virus transmitted by this email.

DISCLAIMER: This email and any files transmitted with it are confidential and intended
solely for the use of the individual or entity to whom they are addressed. If you have
received this email in error, please notify the sender. Please note that any views or opinions
presented in this email are solely those of the author and do not necessarily represent
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ). Finally, the recipient
should check this email and any attachments for the presence of viruses. Power and Water
Utility Company for Jubail and Yanbu (MARAFIQ) accepts no liability for any damage caused
by any virus transmitted by this email.