Professional Documents
Culture Documents
The most important factors governing the bending of bus conductors are:
(I) the ductility of the conductor, (2) the size and shape of the conductor,
(3) the method of bending, and (4) the bending equipment used
Flexible Conductors
o Most flexible conductors used in substation construction consist of all copper, all
aluminum, or aluminum with steel reinforcing (ACSR).
o The conductor type selected for a particular application is usually based on the
span length, tension and tolerable sag, and cost.
o For long spans, large supporting structures will be required. The size and cost of
these structures may depend on the conductor type and should be considered
during the selection process.
o Flexible conductors are available in many sizes. Size selection is based on
ampacity, strength, weight, and diameter.
o Conductor diameter becomes increasingly important at higher voltages where
corona can be a problem.
Select conductor type
There are many types of conductors that may be used. Factors considered include
the following:
o a) Ampacity
o b) Corona
o c) Mechanical strength and deflection
o d) Seismic withstand
o e) Cost
Conductor Ampacity
o Equipment that depends on air for its cooling medium will have a higher
temperature rise when operated at higher altitudes than when operating at
lower altitudes.
o For altitudes in excess of 3,300 feet, the correction factors listed in Table 1 should
be applied.
Altitude Correction Factors Current
Additional considerations must be made to finalize the design. These include the
following items:
o a) Clearances
o b) Transitions between different bus type and/or heights
o c) Bus to equipment connections
o d) Grade changes. A large station may have a grade change. To minimize bus
bends, the footing height may be varied to maintain a constant bus elevation.
Footing elevation changes can compensate for a certain amount of elevation
change, and beyond this, bus transitions will be required.
o e) Access to the equipment and bus during construction and maintenance.
Rigid Bus Design
o Select the material and size of the bus conductors based on continuous current
requirements
o In higher voltage systems with longer bus spans, the structural capabilities of the
conductors may be the factor that determines the conductor material and size
o Using Tables 2 and 3, determine the bus conductor centerline-to-centerline
spacing
Table 2 Substation Clearances
Table 3
Rigid Bus Design (Short circuit force on conductor)
Calculate the maximum short circuit forces the bus has to withstand
o The preceding equation applies maximum wind and maximum ice at the
same time
o NESC and ANSI/IEEE Std. 605 apply these forces individually, which
reduces FT
o Engineering judgment based on site conditions and design loads should
determine the maximum loading conditions of the bus
Maximum bus span or support spacing
o Four equal spans of 37.5 feet were assumed. From Table 5, KSE =
0.88 for three or more equal spans
o The assumed spacing of 11.43 meters (37.5 ft) is structurally permissible for
the conductors
Step 6. Calculate the maximum vertical conductor deflection
o Four equal spans of 37.5 feet were assumed. From Table 5, KDE =
11.9 for three or more equal spans
o Since the calculated value with 30 feet support spacing is less than the
maximum permissible deflection, this support spacing is adequate.
Step 6. Calculate the maximum vertical conductor
deflection
Step 6. Calculate the maximum vertical conductor deflection
o Since the calculated deflection is greater than the maximum permissible
deflection, the design has to be modified. The span length will be reduced to five
equal spans of 9.14 meters (30 feet) each.
o The maximum vertical deflection is then recalculated:
o Since the calculated value with 9.14 m (30 ft) support spacing is less than the
maximum permissible deflection, this support spacing is adequate.
Step 7.
Determine the minimum required support insulator cantilever strength
o From Table 4-5, select Technical Reference Number 291 for 5338 newton
(1200 pounds) cantilever strength post type insulators.
Step 8. Provide for conductor expansion
o Assuming a total conductor temperature variation of 50C, the total
conductor expansion is:
Step 8. Provide for conductor expansion
o Since the spans are fairly long, damaging vibrations may occur.
Consequently, a means for controlling the vibrations should be provided.
o Prefabricated dampers can be attached to the buses or scrap cables can
be installed in the buses. If cables are used, the cable weight has to be
added to the conductor weight for the bus calculations
o Assuming that the bus conductor is available in12.19-meter (40-foot) lengths, the
couplers should be positioned at points 2, 4, 6, and 8
o The conductor lengths are cut as required to position the couplers at these
approximate locations
Legend:
SF = Slip-fit bus support
F = Fixed bus support
EX = Expansion terminal
Aeolian Vibration:.
Aeolian Vibration:
o Since the spans are fairly long, damaging vibrations may occur
o Consequently, a means for controlling the vibrations should be
provided.
o Prefabricated dampers can be attached to the buses or scrap cables
can be installed in the buses.
o If cables are used, the cable weight has to be added to the
conductor weight for the bus calculations.
CASE STUDY (Rigid bus design)
IEEE Method-II
Procedure for bus bar design IEEE Method
o Determine bus conductor size required for both maximum normal load and
short circuit current (Clause 8 and Annex C)
o Determine maximum corona on the bus and equipment (Clause 9 and Annex
D)
o Determine maximum forces on the structures (Clause 11)
o Determine maximum span length of the bus based on vertical deflection limit
and fiber stress (12.1 and12.2)
o Determine maximum required insulator rating (12.3 and 12.4)
o Determine thermal expansion requirements (11.4)
o Determine bus vibration and damping requirements (12.5, 12.6, and 12.7)
Rigid Bus Design Example
Table H.1—Design parameters
Parameters Values
o Maximum load 180 MVA, 1506 A
o Maximum fault current 20 kA
o Maximum operating voltage 69 kV
o Fault clearing time 0.25 s (15 cycles)
o Phase spacing 2.44 m (8 ft)
o Operating bus temperature 90 °C (194 ° °F)
o Maximum allowable temperature 250 °C (482 ° °F)
o Minimum/maximum ambient temperature 0 °C/ 40 °C (32 °F/ 104 °F)
o Maximum wind speed 144 km/h (90 mph)
o High wind speed with ice 64 km/h (40 mph)
o Maximum anticipated icing condition 6.35 mm (0.25 in)
o Latitude/longtitude 30°N, 112°W
o Elevation 366 m (1200 ft)
o Seismic activity Insignificant
o Atmospheric condition Clear
Step1.
Select the material and size of the bus conductors
o Conductors will be 6106-T6 (55% IACS) aluminum tube for rigid bus work and
1350-H19 (61% IACS) all aluminum conductor (AAC) for equipment connections
o The size for each will be selected for both normal and short-circuit conditions
o The full load current is 1506 A. A 20% allowance will be made for future growth
and overloading. The design load current then becomes 1807 A
Minimum size for load current (Refer to 8.1 and Annex C.)
o The conductors will be sized for a load current of 1807 A. The maximum
continuous conductor temperature will be 90 °C as recommended in 8.2.1. (IEEE
Std C37.30-1997). The designer needs to verify that the maximum temperature is
appropriate for the equipment being used in the substation.
o Ampacity tables may be used to select the conductor size. However, tables may
not be available to match the design parameters.
o Initial sizes will be selected from tables, and then values for the design
parameters will be calculated
Select the material and size of the bus conductors
Rigid bus
o From Table B.4, with sun, 0.5 emissivity, and a temperature rise of 50 °C, a 64
mm (2.5 in) SPS schedule 40 aluminum tube provides an ampacity of 1876 A.
o This conductor may be selected as a trial size, and the ampacity will be
confirmed for the design parameters using Equation (C.1)
o For two flexible conductors, the allowable short circuit current will be twice
the value above = 182 kA.
o Based on the above calculations, both the rigid bus and flexible conductors
are adequately rated for the short circuit current of 20 kA.
STEP-2. Determine maximum corona on the bus and
equipment (Clause 9 and Annex D)
For rigid conductor
o Corona cannot be eliminated, but it can be controlled to acceptable levels.
o The goal is that the corona is below the allowable voltage gradient. Refer to Clause 9 and Annex D.
o First we need to evaluate the corona onset gradient given by Equation (D.1):
where
o Ec is the corona onset gradient, kV/cm
o E0 is an empirical constant
o C is an empirical constant
o m is the conductor irregularity factor
o Da is the relative air density
o rc is the conductor outside radius, cm
o Peek found E0 = 30 kV/cm (peak value) or 21.1 kV/cm (rms value) and C = 0.301 cm–1.
STEP-2. Determine maximum corona on the bus
and equipment (Clause 9 and Annex D)
For rigid conductor
o Using the variables of table H.15 given below
Table H.15—Variables for corona onset gradient Ec
calculation
Variable Description Value
m Air density factor, use worst case of 0.6–0.85 range 0.85
suggested in D.1.1
Eo Empirical constant per D.1.1 21.1 kV/cm
Da Relative air density per Equation (D.2), Equation (D.3) and 0.917
calculated below
C Empirical constant 0.301 cm-1
rc Conductor outside radius (equivalent radius for a bundle 3.65 cm for rigid bus
of n sub conductors) 3.81 cm for flexible
conductor
as calculated below
T Ambient air temperature 40 °C
To Air temperature used in determining constants Eo and C 25 °C
and factor m
A Altitude 0.366 km
For flexible conductor
Determine maximum corona on the bus and
equipment (Clause 9 and Annex D)
o For flexible conductor, we first need to calculate the equivalent single-
conductor radius of bundle sub conductors, using Equation (D.11) with n =
2 (2 flexible conductors):
Rigid bus conductor voltage gradient
The maximum voltage gradient is evaluated using Equation (D.6), Equation (D.7),
and Equation (D.8) using the data given in Table H.16.
Table H.16—Variables for voltage gradient calculations for rigid bus
Variable Description Value
he Conductor height above ground cm [in] 366 cm
o For satisfactory operation, Em < Ec. The 64 mm (2.5 in) SPS, schedule 40
aluminum tube meets this criteria and is acceptable.
Flexible bus conductor voltage gradient
The maximum voltage gradient is evaluated using Equation (D.12) and Equation
(D.13), and the data given in Table H.17.
o Average voltage Ea gradient per Equation (D.12):
For satisfactory operation, Em < Ec. The 954 kcmil AAC meets this criteria and is
acceptable.
Flexible bus conductor voltage gradient
o n is the number of sub conductors in bundle
o g is equal to 1 for bundle of 1, 2, or 3 sub conductors and is equal to 1.12 for bundle
of 4 sub conductors
o d is the conductor diameter, cm [in]
o s is the distance between conductors, cm [in]
o r is the conductor radius, cm [in] and is given by d/2
o re is the equivalent single-conductor radius of bundle sub conductors, cm [in], is
given by:
Table H.17—Variables for voltage gradient calculations
for flexible conductor bundle
Variable Description Value
Total force
o The total force is given by the vector sum of the vertical and horizontal forces,
as per Equation (78).
o We will consider here that short circuit is concurrent with wind and will
evaluate the cases without and with ice.
o The total force for extreme wind with no ice, short circuit, and conductor
weight is given by:
Total force
o The total force for high wind with ice, short circuit, and conductor weight
is given by:
o The higher loading occurs for extreme wind with no ice, FT1.
Step-4 Allowable span
Allowable span based on deflection limit
o The deflection of a span with pinned-pinned end conditions will be calculated without
any damping material.
o The recommended allowable deflection of 1:150 (0.67 %) will be used. i.e. the ratio
of conductor deflection to span length or the conductor diameter (0.5 to 1times the
diameter)
o The ice weight is usually not considered for vertical deflection. However, if the vertical
deflection during icing conditions is important, then ice weight should be considered
o The all allowable span is given by Equation (72), using the data in Table H.23:
o The total gravitational force on a conductor is the sum of the weights of the
conductor(FC), damping material(FD), and ice(FI, equation[6]) if the latter is of concern
in the allowable deflection
FG = Fc + FD + FI
Table H.23—Variables for allowable span calculations
based on deflection limit
Variable Description Value
η Allowable deflection as a fraction of span length 0.0067 (1/150)
(recommended allowable deflection of 1:150 (0.67 %))
E E Modulus of elasticity for aluminum 68.9 × 109 N/m2
J J Bending moment of inertia, per Equation (73), see 6.40 × 10-7 m4
calculation below
FG FG Gravitational force 29.4N/m
Do conductor outside diameter, m [in] as provided in table 0.073m
Di conductor inside diameter, m [in] as provided in table 0.0626m
Allowable span based on fiber stress
o Fiber stress will be based on a single span with pinned-pinned end conditions
that provide a worst-case result
o The yield stress of 6061-T6 aluminium is 240 MPa (35 ksi) according to AWS
D1.2-2003 (see Clause 2)
o Welded couplers and connectors will be used. Welding reduces the allowable
stress to approximately 50% according to the Aluminum Design manual (see
Clause 2)
o The allowable yield stress is therefore 120 MPa
o Using Equation (79) and the data in Table H.24, the allowable span is given by:
Table H.24—Variables for allowable span calculations based
on fiber stress
Variable Description Value
o The upper frequency with the upper wind speed is given by:
o The lower frequency with the lower wind speed is given by:
Step-5 Vibration
Table H.26—Variables for wind-induced vibration calculations
Variable values
C 0.19 for a cylinder per Equation (100) description
V wind speed in m/s: Upper: 72 km/h = 20.00 m/s;
Lower: 8 km/h = 2.22 m/s
Do 0.073 m
o A conductor will vibrate if its natural frequency is in the vicinity of either
the wind frequency or that of the alternating current (2f).
o It is recommended that an allowance for variations be allowed. This is
accomplished by ensuring the ratio of the natural frequency to the
inducing frequency is not in the range 0.5 to , as given by Equation (101):
o It is observed for the pinned-pinned conditions that the ratios are outside
the range to avoid, so wind-induced vibration is unlikely to occur
Fixed-fixed condition
o It is observed for the fixed-fixed conditions that the ratio using the lower
frequency of wind excitation is within the range to avoid, so wind-
induced vibration is likely to occur
Step-5 Vibration
Induced vibration from alternating current
o Vibration due to alternating current excitation will occur when fb > f per Equation
(102). Using the maximum possible value of fb for fixed-fixed conditions, and the
power frequency of 50 Hz, we have: 6.30<50
o So the bus should not be affected by vibrations from alternating current
excitation
Vibration attenuation requirements
o Based on this analysis, vibration dampers will be required due to wind-induced
vibration
o The use of either a damping cable or dampers is recommended
o Therefore, the calculations for allowable span may have to be reviewed if a
damping cable is used since this adds mass and therefore increases the weight by
unit length in the vertical direction
Step-6 Thermal expansion
o The expansion of this section of bus will be calculated for an installation temperature of 0 °C
and the operating temperature of 90 °C, using the data in Table H.27.
o A length of 16.6 m will be used, which is the largest length for this example (two continuous
spans of 8.3 m). Using Equation (65):
Table H.27—Variables for thermal expansion calculations
Variable values
α 23.1 × 10-6 1/°C for aluminum per Table 17
Ti 0 °C, minimum normal temperature
Tf 90 °C, maximum normal temperature
Li 16.6 m, length of bus
o A 16.6 m section of bus will therefore have 34.5 mm of expansion over the minimum-to-
maximum temperature range
o Supports need to be selected to accommodate this movement, or a thermal expansion fitting
at one support is recommended
Step-7 Insulator selection
o A sample calculation will be done for a two-supports bus span. The designers will be
required to carry out the same calculations for all spans and to select insulators for the
entire substation based on the maximum force from them.
Trial insulator selection
o Refer to insulator tables from a manufacturer. Most insulators are assigned a Technical
Reference number, which all manufacturers can supply.
o The standard strength 350 kV BIL insulator is a TR-216 insulator with a rated cantilever
strength of 6.67 kN (1500 lbf).
Span force calculations
o Calculations will be done considering two continuous spans of 8.3 m with support
boundary conditions P-C-P as per Table 18
o The sample bus uses vertically mounted insulators to support horizontal rigid bus. The
total cantilever force on the mid insulator is calculated using Equation (89)
o In this example, only forces in the x direction (see Figure 31) will create cantilever forces
because provision is made for bus expansion so that no force will be generated due to
thermal effects
Span force calculations
o The formula to calculate the cantilever force, using extreme wind with no ice gives
o The wind force on the insulator is calculated per Equation (8) and constants determined
earlier in H.6.3:
o Incorporating Equation (83), Equation (84), and Equation (87), and the data in Table
H.28, gives:
Table H.28—Variables for cantilever force calculations
variables parameters Value
FW1 Wind force on insulator calculated per calculation above 187.9 N/m
V Extreme wind velocity, from Figure 14 1440 m/s (144 km/h)
Di Effective insulator diameter 0.28 m
FW2 Wind force on the conductor per H.6.3 (Fw) 49.0 N/m
FSC Short-circuit force on the conductor per H.6.4 195.2 N/m
LE Effective length of conductor span for two 8.3 m continuous 10.4 m
spans with P-C-P conditions as per Table 18 (5 L/4)
HT Total height of the insulator column 0.762 m
Hf Height from the insulator top to the bus center line, 0.08 m
refer to bus support manufacturer for value
kW Load factor for wind forces 2.5
kSC Load factor for short-circuit current (the requirements of 12.3.4 1.0
have been met).
Step-7 Insulator selection