Chapter Two
Symmetrical Faults
2.1 Introduction
A fault in a cireuit is any failure which interferes with the normal
flow of current. In most faults, @ short cizcuit path forms between two or
more phases, or between one or more phases and the ground, Since the
impedance of a new path is usually low, an excessive current may flow
2.2 Causes of Faults
1. Tree branches near the transmission lines.
. Lightning,
3. Winds.
4. Birds shorting lines.
5. Vehicles colliding with towers.
6. Small animals entering switchgear.
2.3 Types of Faults
‘There are two main types of faults:
1. Symmetrical Faults (Three Phase Faults): These faults are rare, but
they are easier to analyze. When a symmetrical fault takes place, the
system remains balanced. This occurs when all three phases of a
transmission line are shorted together.
2, Unsymmetrical Faults: Such faults are more common, but they are
more difficult to analyze, When an unsymmetrical fault takes place, the
system is no longer balanced. The unsymmetrical faults contains all the
transmission lines faults except the three phase types. These faults are:a. Single Line to Ground (SLG): A short circuit path forms
between one phase and the ground.
b. Line to Line (LL): Two phases of a line may touch, or
flashover may occur between two phases.
¢. Double Line to Ground: Two lines touch each other and also
touch the ground.
2.4 Transient in RL Series Circuits
Consider an AC voltage is applied to a circuit containing constant
values of resistance and inductance as shown in Fig. 1 below:
e pdt 5
Vnax Sin(oot + a) = REALS (>
The solution of this equation is: @
— 6) et sina—
i=" [sin(wr+a—6)—e-*/"sin(a—8)] aco
iL
where |Z| = R? + (Lp and @ = tan~?
R
Fig. 2 shows the variation of current with time according to the above
equation
Fig 2: Current as a function of time in RL circuit for’ (a) a-8
: (b) a8 = -n/22.5 Short Circuit Current and Reactance of Synchronous
Machine
Fig. 3: Current as a function of time for a synchronous generator short-circuited while
running at no load,
From Fig. 3:
11) = 24 = HE — seoady seat ft
= = 52 = Steady state current
Vi Xe "
Ob _ Esl
| = =H = Transient current
| Va OX
Oc E,
uy = 26 el
El — sub — transient current
v2 Xe
where: Xj is the direct axis synchronous reactance, Xj is the direct
transient reactance, Xj is the direct subtransient reactance and E, is the
1m. voltage fiom one terminal of the generator to the neutral.Example 1: Two generators are connected in parallel to the low voltage
side of 3-ph A-Y transformer as shown in Fig. 4. Generator 1 is rated
50000 kVA , 13.8 kV. Generator 2 is rated 25000 kVA, 13.8 kV. Each
generator has a subtransient reactance of 25% on its own base. The
transformer is rated 75000 kVA, 13.8 4 / 69 ¥ kY, with a reactance of
10%. Before the fault occurs, the voltage on the HTS of the transformer is
66 KY. The transformer is unloaded and there is no circulating current
between the generators. Find the subtransient current in each generator
when a 3-ph short circuit occurs on the HTS of the transformer. (Select
69 kV, 75000 kVA as base in the HTS).
® r
@2) aY
Fig. 4: SLD for Example 1
‘Solution:
Generator 1:
X= 0.25% eae 0.375 pu
50000
Eq = G5 = 0.957 pu
Generator 2:
: 75000
Xag = 0.25 X Fe559 = 0.75 pu
Fyn = 8° = 0.957 pu
#69
Transformer:
X, =0.1 pu
The equivalent subtransient reactance is:j0.375 x j0.75
50.375 + j0.75
= j0.25 pu
The voltage on the A side of the transformer is:
Ve = (—J2.735)(J0.1) = 0.2735 pu
. 87 — 0.274 75000
Ba = pape = 1.823 pu = —f1.823 x = 720A
fat 90.375 dSee PAD V3x 138
. _ 0957 ~0.274 75000
Ij, = poe = —j0.912 pu = -j0.912 x = 2860 A
ca J0.75 eee est V3x 138
os