You are on page 1of 33

Electrical distribution system design calculation

DESIGN OF ELECTRICAL POWER DISTRIBUTION SYSTEM


REFURBISHMENT OF OLD PASSPORT OFFICE BUILDING, PUNCHI BORELLA

B1. Preliminary load estimation (for total building based on architectural drawings)
Power density (W/m2) Power requirement (W)
Sub Total
Floor Area (m )
2
Lighting Small power Lighting Small power (W)
Basement floor 1,300.00 6.00 0.00 7,800.00 0.00 7,800.00
Ground floor 1,300.00 12.90 18.00 16,770.00 23,400.00 40,170.00
First Floor 1,300.00 12.90 18.00 16,770.00 23,400.00 40,170.00
Second Floor 1,300.00 12.90 18.00 16,770.00 23,400.00 40,170.00
Third Floor 1,300.00 12.90 18.00 16,770.00 23,400.00 40,170.00
Fourth Floor 1,300.00 12.90 18.00 16,770.00 23,400.00 40,170.00
Fifth Floor 1,300.00 12.90 18.00 16,770.00 23,400.00 40,170.00
Machine Room
228.00 10.80 8.00 2,462.40 1,824.00 4,286.40
Floor
Total 9,328.00 110,882.40 142,224.00 253,106.40

A). Total power requirement for lighting = 110.88 kW


B). Total power requirement for small
= 142.22 kW
power
Sub total = 253.11 kW
Typically, in office buildings two third from the maximum demand will be utilized for fulfill the power
requirement of the air conditioning system(as per the instructions given by the supervisor and
previous project experience-rule of thumb). Therefore,

C).Estimated power requirement for AC


= 506.21 kW
system (A+B)×2
D). Other Special equipment = 100.00 kW

D).Total estimated power requirement


= 859.32 kW
for the building (A+B+C+D)

Considering the power factor(P.F.) as 0.8


and utilization factor(U.F.) as 0.8,
= (859.32/P.F.)×U.F.
maximum demand (kVA) for the complete
building
= 859.32 kVA

Estimated maximum demand(kVA) for the


complete building, considering 15% of = 859.32×1.15
unforseen loads and future expansions.
988.22 kVA

Considering the above calculation, 1000kVA, 3-phase electricity supply can be recommended for the
premises.

Prepared By : Eng. J.G.D. S. De Silva


Consultant Electrical Engineer
M-8383

1 of 33
Design report - Annexure B , Electrical distribution system design calculation

CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA


B2.Maximum demand calculation

Wattage or Single
Three
expected Diversity/ phase
Item Description Quantity phase
current per Utilization current
current (A)
unit (A)

LIGHTING
1 × 14, single fluorescent fitting with
Type - 01 diffuser and electronic ballast at 0.99 154 16.00 60.00% 6.49 -
p.f. (Ballast loss 2W)
1 × 28, single fluorescent fitting with
Type - 02 diffuser and electronic ballast at 0.97 41 32.70 60.00% 3.61 -
p.f. (Ballast loss 4.7W)
4 x 14W ceiling recessed mounted
lights with opal diffusers & electronic
Type - 03 ballast at 0.99 p.f. (Ballast Loss 432 61.00 80.00% 92.58 -
5W )
4 x 14W ceiling recessed mounted
lights with opal diffusers & electronic
Type - 04 ballast at 0.99 p.f. (Ballast Loss 173 61.00 80.00% 37.08 -
5W )

Ceiling recessed mounted down light


Type - 05 with 1x15W CFL and bottom glass at 160 15.00 60.00% 7.83 -
0.8p.f.
Sub total for lighting in single phase current (A) 147.59 -
Sub total for lighting in three phase current (A) 49.20
Fans
6 75W Ceiling fan at 0.8 p.f. 118 75.00 80.00% 38.48 -
7 51.9W wall fan at 0.8 p.f. 16 51.90 80.00% 3.61 -
Sub total for fans in single phase current (A) 42.09 -
Sub total for fans in three phase current (A) 14.03
Socket outlets
13A Socket outlets for fore exit signs
8 15 7.00 100.00% 0.57 -
(W)
9 13A Socket outlet (A) 755 1.00 40.00% 302.00 -
10 13A dedicated socket outlet (A) 77 7.00 30.00% 161.70 -
464.27 -
Sub total for socket outlets in three phase current (A) 154.76
Air Conditioning (AC) system
80kW three phase chillers at 0.8 p.f.
11 2 80,000.00 90.00% - 260.87
(02-duty)
8kW three phase chill water pumps
12 3 8,000.00 80.00% - 34.78
at 0.8 p.f. (03-duty)
13 10kW three phase AHU at 0.8 p.f. 2 10,000.00 90.00% - 32.61
14 8kW three phase AHU at 0.8 p.f. 2 1,500.00 90.00% - 4.89
15 2kW three phase AHU at 0.8 p.f. 1 1,500.00 90.00% - 2.45
16 1.5kW three phase AHU at 0.8 p.f. 18 1,500.00 90.00% - 44.02
100W Single phase fan coil unit at
17 34 100.00 90.00% 16.63 -
0.8p.f.
150W Single phase fan coil unit at
18 10 100.00 90.00% 4.89 -
0.8p.f.
250W Single phase fan coil unit at
19 2 100.00 90.00% 0.98 -
0.8p.f.

Professional review examination February/march 2020 B2+1


Design report - Annexure B , Electrical distribution system design calculation

22.50 379.62
Sub Total for AC System in three phase Line Currents (A) 387.12

Medical Gas System


15kW three phase (01-Duty) Medical
20 1 15000 80.00% - 21.65
air plant @ 0.8 p.f.
2.2kW three phase (01-Duty) Medical
21 1 2200 80.00% - 3.18
vacuum plant @ 0.8 p.f.
3kW three phase (01-Duty) AGSS
22 1 3000 80.00% - 4.33
pumps @ 0.8 p.f.
- 29.16
Sub Total for AC System in three phase Line Currents (A) 29.16

Other Special Loads


15kW three phase Bed Lift @ 0.8 p.f.
23 3 15000 100.00% - 81.19
9.3kW three phase Water pump (01-
24 Duty) @ 0.8 p.f. 1 9300 50.00% - 8.39
65kW three phase Xray Machine @
25 0.8 p.f. 1 65000 30.00% - 35.18
100kW three phase C.T. Machine @
26 0.8 p.f. 1 105000 30.00% - 56.83
500W single phase Operation theatre
27 lamp @ 0.8 p.f. 2 500 50.00% 2.72 -
2.72 181.60
Sub Total for Other Special Loads in three phase Line Currents (A) 182.51

Power requirement (in three phase line current)


A) For lighting = 49.20 A
B) For fans = 14.03 A
C) For socketoutlets = 154.76 A
D) For air conditioning system = 387.12 A
E) For medical gas system = 29.16 A
F) For other special loads = 182.51 A
For unforseen loads (5% of
G) = 31.71 A
A+B+C+D+E+F)
H) Total Load = 848.48 A

Total power requirement (three phase current) for the


= 848.48 A
complete building

Required kVA for the entire building = (3)0.5×400×848.48/1000 kVA


= 587.84 kVA

Professional review examination February/march 2020 B3+1


Design report - Annexure B , Electrical distribution system design calculation

B3. Selection of capacity of the transformer and generator

B3.1 Transformer capacity


Considering the calculation 630kVA transfomer was proposed to fulfill the maximum demand of the
building.
Impedance of 630kVA, 33kV/400V transformer is taken as 5.0% according to the Manufacturer's
catalogue (Reference page B46 of annexure B).

Fault level at transformer = 1


0.050
= 20

Fault current at transformer = 20×630×1000 A


400×1.732
= 18187 A
= 18.19 kA

B3.2 Generator capacity


X-ray machines, CT machines, Operating Theaters, Insentive care units, isolation rooms and wards
included to this building. Therefore this building can be consider as an essential load, and total laod shall
be backed up with standby generator supply. Therefore considering the maximum demand of this building,
generator capacity is selected to be 630kVA.

Approximate minimum load for generator

A) For lighting (30% of total demand) = 15 A


B) For fans (30% of total demand) = 4 A
C) For socket outlets (30% of demand) = 46 A
D) For other loads (50% of total demand) = 315 A
Total = 381 A

Approximate minimum kVA = (3)0.5×400×381/1000


= 264 kVA

1/3 rd of Minimum load of 630 kVA generetor = 210.00 kVA

Therefore the possibility to run the generator below 1/3 rd load is minimum.This will ensure the long life time
of engine of the generator.

Professional review examination February/march 2020 B4+1


Design report - Annexure B , Electrical distribution system design calculation

CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA


B4.Design current calculation sheet for Floor Distribution Boards (FDB) and Distribution Boards (DB)
GFDB 1FDB 2FDB 3FDB
Wattage(W) Diversity/
Item Description Current Current Current Current Current Current Current Current
/Ammpere(A) Utilization(1) Qntity Qntity Qntity Qntity
(A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ
Light fittings
1 × 14, single fluorescent fitting with diffuser and
1 16.0 80% 18 1.01 - 37 2.08 - 43 2.42 - 13 0.73 -
electronic ballast at 0.99 p.f. (Ballast loss 2W)
1 × 28, single fluorescent fitting with diffuser and
2 32.7 80% 6 0.70 - - - - - - - 16 1.88 -
electronic ballast at 0.97 p.f. (Ballast loss 4.7W)
4 x 14W ceiling recessed mounted lights with opal
3 diffusers & electronic ballast at 0.99 p.f. (Ballast Loss 5W 61.0 90% 78 18.81 - 76 18.32 - 92 22.18 - 94 22.66 -
)
4 x 14W ceiling recessed mounted lights with opal
4 diffusers & electronic ballast at 0.99 p.f. (Ballast Loss 5W 61.0 90% 45 10.85 - 42 10.13 - 23 5.55 - 39 9.40 -
)
Ceiling recessed mounted down light with 1x15W CFL
5 15.0 80% 36 2.35 - 30 1.96 - 26 1.70 - 41 2.67 -
and bottom glass at 0.8p.f.
Fans
6 75W Ceiling fan at 0.8 p.f. 75.0 100% 13 5.30 - 34 13.86 - 37 15.08 - 6 2.45 -
7 51.9W wall fan at 0.8 p.f. 51.9 90% 2 0.51 - 5 1.27 - 4 1.02 - 1 0.25 -
Small power -
8 13A Socket outlets for fore exit signs (W) 3.5 100% 4 0.08 - 4 0.08 - 4 0.08 - 6 0.11 -
9 13A Socket outlet (A) 1.0 50% 113 56.50 - 111 55.50 - 145 72.5 - 237 118.50 -
10 13A dedicated socket outlet (A) 7.0 30% 8 16.80 - 16 33.60 - 19 39.9 - 16 33.60 -
Air Conditioning
11 10kW three phase AHU at 0.8 p.f. 10000.0 90% - - - - - - - - - -
12 8kW three phase AHU at 0.8 p.f. 8000.0 90% - - - - - - - - - -
13 2kW three phase AHU at 0.8 p.f. 2000.0 90% - - - - - - - - - -
14 1.5kW three phase AHU at 0.8 p.f. 1500.0 90% 3 - 7.34 5 - 12.23 5 - 12.23 - - -
15 100W Single phase fan coil unit at 0.8p.f. 100.0 100% 25 13.59 - 5 2.72 - 2 1.09 - - - -
16 150W Single phase fan coil unit at 0.8p.f. 150.0 100% 4 3.26 - - - - 1 0.82 - - - -
17 250W Single phase fan coil unit at 0.8p.f. 250.0 100% 2 2.72 - - - - - - - - - -
Other Special Loads
18 500W single phase Operation theatre lamp @ 0.8 p.f. 500.0 100% - - - - - - - - 2 5.43 -
Sub Total 01 132.47 7.34 139.51 12.23 162.32 12.23 197.70 0.00

Three phase line current in each pase(2) 51.49 A 58.73 A 66.33 A 65.90
Add 10% for single phase load inbalance(2) 4.42 A 4.65 A 5.41 A 6.59
Sub Total 02 55.91 A 63.38 A 71.74 A 72.49
Add 10% for future exapansions(3) 5.59 A 6.34 A 7.17 A 7.25
Sub Total 03 61.50 A 69.72 A 78.92 A 79.74

Design current for FDBs 62.00 A , 3Φ 70.00 A , 3Φ 79.00 A , 3Φ 80.00


Selected breaker(5) 100A, 4P MCCB 100A, 4P MCCB 100A, 4P MCCB 100A, 4P MCCB

CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA


B4.Design current calculation sheet for Floor Distribution Boards (FDB) and Distribution Boards (DB)

Professional review examination February/march 2020 B5


Design report - Annexure B , Electrical distribution system design calculation

4FDB DBMR1 DBMR2 3FDBAC


Wattage(W) Diversity/
Item Description Current Current Current Current Current Current Current Current
/Ammpere(A) Utilization(1) Qntity Qntity Qntity Qntity
(A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ
Light fittings
1 × 14, single fluorescent fitting with diffuser and
1 16.0 80% 43 2.42 - - - - - - - - - -
electronic ballast at 0.99 p.f. (Ballast loss 2W)
1 × 28, single fluorescent fitting with diffuser and
2 32.7 80% - - - 11 1.29 - 8 0.94 - - - -
electronic ballast at 0.97 p.f. (Ballast loss 4.7W)
4 x 14W ceiling recessed mounted lights with opal
3 diffusers & electronic ballast at 0.99 p.f. (Ballast Loss 5W 61.0 90% 92 22.18 - - - - - - - - - -
)
4 x 14W ceiling recessed mounted lights with opal
4 diffusers & electronic ballast at 0.99 p.f. (Ballast Loss 5W 61.0 90% 24 5.79 - - - - - - - - - -
)
Ceiling recessed mounted down light with 1x15W CFL
5 15.0 80% 24 1.57 - 2 0.11 - 1 0.05 - - - -
and bottom glass at 0.8p.f.
Fans
6 75W Ceiling fan at 0.8 p.f. 75.0 100% 28 11.41 - - - - - - - - - -
7 51.9W wall fan at 0.8 p.f. 51.9 90% 4 1.02 - - - - - - - - - -
Small power -
8 13A Socket outlets for fore exit signs (W) 3.5 100% 4 0.08 - 1 0.02 - 1 0.02 - - - -
9 13A Socket outlet (A) 1.0 50% 134 67.00 - 11 5.50 - 4 2 - - - -
10 13A dedicated socket outlet (A) 7.0 30% 18 37.80 - - - - - - - - - -
Air Conditioning
11 10kW three phase AHU at 0.8 p.f. 10000.0 90% - - - - - - - 2 - 32.61
12 8kW three phase AHU at 0.8 p.f. 8000.0 90% - - - - - - - 2 - 26.09
13 2kW three phase AHU at 0.8 p.f. 2000.0 90% - - - - - - - 1 - 3.26
14 1.5kW three phase AHU at 0.8 p.f. 1500.0 90% 5 - 12.23 - - - - - - - - -
15 100W Single phase fan coil unit at 0.8p.f. 100.0 100% 2 1.09 - - - - - - - - - -
16 150W Single phase fan coil unit at 0.8p.f. 150.0 100% 5 4.08 - - - - - - - - - -
17 250W Single phase fan coil unit at 0.8p.f. 250.0 100% - - - - - - - - - - - -
Lifts
18 15kW, three phase bed lifts @ 0.8p.f. 15000.0 100% - - - 1 - 27.17 1 - 27.17 - - -
Sub Total 01 154.42 12.23 6.92 27.17 3.01 27.17 0.00 61.96

Three phase line current in each pase(2) 63.70 A 29.48 A 28.18 A 61.96
Add 10% for single phase load inbalance(2) 5.15 A 0.23 A 0.10 A 0.00
Sub Total 02 68.85 A 29.71 A 28.28 A 61.96
Add 10% for future exapansions(3) 6.88 A 2.97 A 2.83 A 6.20
Sub Total 03 75.73 A 32.68 A 31.11 A 68.15

Design current for FDBs 76.00 A , 3Φ 33.00 A , 3Φ 32.00 A , 3Φ 69.00


Selected breaker(5) 100A, 4P MCCB 40A, 4P MCCB 40A, 4P MCCB 100A, 4P MCCB

Professional review examination February/march 2020 B6


Design report - Annexure B , Electrical distribution system design calculation

A
A
A
A
A

A , 3Φ

Professional review examination February/march 2020 B7


Design report - Annexure B , Electrical distribution system design calculation

A
A
A
A
A

A , 3Φ

Professional review examination February/march 2020 B8


Design report - Annexure B , Electrical distribution system design calculation

CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA


B4.Design current calculation sheet for Floor Distribution Boards (FDB) and Distribution Boards (DB)
DBCHILLER DBMG DBWP DBX DBCT
Wattage(W) / Diversity/
Item Description Current Current Current Current Current Current Current Current Current Current
Ammpere(A) Utilization(1) Qntity Qntity Qntity Qntity Qntity
(A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ
Medical Gas System
15kW three phase (01-Duty)
15000.0 100% - - - 1 - 27.17 - - - - - - - - -
Medical air plant @ 0.8 p.f.
2.2kW three phase (01-Duty)
Medical vacuum plant @ 0.8 2200.0 100% - - - 1 - 3.99 - - - - - - - - -
p.f.
3kW three phase (01-Duty)
3000.0 100% - - - 1 - 5.43 - - - - - - - - -
AGSS pumps @ 0.8 p.f.

Air Conditioning system


80kW three phase chillers at
80000.0 100% 2 - 289.86 - - - - - - - - - - - -
0.8 p.f. (02-duty)
8kW three phase chill water
8000.0 100% 3 - 43.48 - - - - - - - - - - - -
pumps at 0.8 p.f. (03-duty)
- - -
Other Special Loads - - -
9.3kW three phase Water
9300.0 100% - - - - - - 1 - 16.85 - - - - - -
pump (01- Duty) @ 0.8 p.f.
40kW three phase Xray
40000.0 100% - - - - - - - - - 1 - 72.46 - -
Machine @ 0.8 p.f.
70kW three phase C.T.
70000.0 100% - - - - - - - - - - - - 1 - 126.81
Machine @ 0.8 p.f.
Sub Total 01 0.00 333.33 0.00 36.59 0.00 16.85 0.00 72.46 0.00 126.81

Three phase line current in each pase(2) 333.33 A 36.59 A 16.85 A 72.46 A 126.81 A
Add 10% for single phase load inbalance(2) 0.00 A 0.00 A 0.00 A 0.00 A 0.00 A
Sub Total 02 333.33 A 36.59 A 16.85 A 72.46 A 126.81 A
Add 10% for future exapansions(3) 33.33 A 3.66 A 1.68 A 7.25 A 12.68 A
Sub Total 03 366.67 A 40.25 A 18.53 A 79.71 A 139.49 A

Design current for FDBs 367.00 A , 3Φ 41.00 A , 3Φ 19.00 A , 3Φ 80.00 A , 3Φ 140.00 A,3Φ
Selected breaker(5) 400A, 4P MCCB 63A, 4P MCCB 40A, 4P MCCB 100A, 4P MCCB 160A, 4P MCCB

Note: 1) Diversity/utilization is not applied in calculation of lighting, fan and other fixed loads. It was considered only for general socket outlets.
2) Three phase line current in each panel is taken by dividing single phase currents by 3 assuming three phase balanced load. But practically single phase currents can not be converted to balanced three
phase system. For this reason additional 10% is added for single phase currents.
3) 20% additional margin was added for the future expansions for all consumer units except the CUs for fixed loads and CU-LM & CU-WT (only 10% was added for those CUs).
4) For the socket out lets, following currents were taken. * 13A =1A, 13A dedicated Socket= 7A.
5) Rating of MCCBs/MCBs were selected based on design current & unexpected imbalance of single phase loads etc.
6) All Consumer Units are designed with spare breakers for future expansions.

Professional review examination February/march 2020 B7


Design report - Annexure B , Electrical distribution system design calculation

A,3Φ

Professional review examination February/march 2020 B8


CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA
B4.Design current calculation sheet for Distribution Boards (FDB) and Consumer units (DB) of ground floor
Wattage GDB1 GDB2 CUXR CUCT
Diversity/
(W)
Item Description Utilization Current Current Current Current Current Current Current Current (A) -
/Ammpe (1) Qntity Qntity Qntity Qntity
re(A) (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ 3Φ
Light fittings
1 × 14, single fluorescent fitting with diffuser and
16.0 80% 10 0.56 - 8 0.45 - - - - - - -
electronic ballast at 0.99 p.f. (Ballast loss 2W)
1 × 28, single fluorescent fitting with diffuser and
32.7 80% - - - 6 0.70 - - - - - - -
electronic ballast at 0.97 p.f. (Ballast loss 4.7W)
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 90% 28 6.75 - 28 6.75 - 6 1.45 - 16 3.86 -
Loss 5W )
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 90% 23 5.55 - 22 5.30 - - - - - -
Loss 5W )
Ceiling recessed mounted down light with 1x15W
15.0 80% 20 1.30 - 14 0.91 - 1 0.07 - 1 0.07 -
CFL and bottom glass at 0.8p.f.
Fans
75W Ceiling fan at 0.8 p.f. 75.0 100% 10 4.08 - 3 1.22 - - - - - -
51.9W wall fan at 0.8 p.f. 51.9 90% - - - 2 0.51 - - - - - -
Small power -
13A Socket outlets for fore exit signs (W) 3.5 100% 2 0.04 - 2 0.04 - - - - - - -
13A Socket outlet (A) 1.0 50% 33 16.50 - 48 24.00 - 8 4 - 24 12.00 -
13A dedicated socket outlet (A) 7.0 30% 3 6.30 - 4 8.40 - - - 1 2.10 -
Other Special Loads -
500W single phase Operation theatre lamp @ 0.8
500.0 100% - - - - - - - - - - -
p.f.
Sub Total 01 41.08 0.00 48.29 0.00 5.51 0.00 18.02 0.00

Three phase/ single phase line current in each


13.69 A 16.10 A 5.51 A 18.02 A
pase(2)
Add 10% for single phase load inbalance(2) 1.37 A 1.61 A 0.18 A 0.60 A
Sub Total 02 15.06 A 17.71 A 5.70 A 18.62 A
Add 10% for future exapansions(3) 1.51 A 1.77 A 0.57 A 1.86 A
Sub Total 03 16.57 A 19.48 A 6.27 A 20.49 A

Design current for FDBs 17.00 A , 3Φ 20.00 A , 3Φ 7.00 A , 1Φ 21.00 A , 1Φ


Selected breaker(5) 32A, 4P MCB 32A, 4P MCB 32A, 2P MCB 32A, 2P MCB

CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA


B4.Design current calculation sheet for Distribution Boards (FDB) and Consumer units (DB) of first floor
Wattage 1DB1 1DB2 1CU1
Diversity/
(W)
Item Description Utilization
(1)
Diversity/
(W)
Item Description Utilization Current Current Current Current Current Current
/Ammpe (1) Qntity Qntity Qntity
re(A) (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ
Light fittings
1 × 14, single fluorescent fitting with diffuser and
16.0 80% 12 0.67 - 24 1.35 - 1 0.07 -
electronic ballast at 0.99 p.f. (Ballast loss 2W)
1 × 28, single fluorescent fitting with diffuser and
32.7 80% - - - - - - - - -
electronic ballast at 0.97 p.f. (Ballast loss 4.7W)
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 90% 30 7.23 - 41 9.89 - 5 1.21 -
Loss 5W )
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 90% 25 6.03 - 17 4.10 - - -
Loss 5W )
Ceiling recessed mounted down light with 1x15W
15.0 80% 12 0.78 - 15 0.98 - - - -
CFL and bottom glass at 0.8p.f.
Fans
75W Ceiling fan at 0.8 p.f. 75.0 100% 16 6.52 - 18 7.34 - - -
51.9W wall fan at 0.8 p.f. 51.9 90% - - - 5 1.27 - - -
Small power -
13A Socket outlets for fore exit signs (W) 3.5 100% 2 0.04 - 2 0.04 - - - -
13A Socket outlet (A) 1.0 50% 35 17.50 - 63 31.50 - 13 6.5 -
13A dedicated socket outlet (A) 7.0 30% 6 12.60 - 8 16.80 - 2 4.20 -
Other Special Loads
500W single phase Operation theatre lamp @ 0.8
500.0 100% - - - - - - - -
p.f.
Sub Total 01 51.38 0.00 73.26 0.00 11.98 0.00

Three phase/ single phase line current in each


17.13 A 24.42 A 11.98 A
pase(2)
Add 10% for single phase load inbalance(2) 1.71 A 2.44 A 0.40 A
Sub Total 02 18.84 A 26.86 A 12.37 A
Add 10% for future exapansions(3) 1.88 A 2.69 A 1.24 A
Sub Total 03 20.72 A 29.55 A 13.61 A

Design current for FDBs 21.00 A , 3Φ 30.00 A , 3Φ 14.00 A , 1Φ


Selected breaker(5) 32A, 4P MCB 40A, 4P MCB 32A, 2P MCB

CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA


B4.Design current calculation sheet for Distribution Boards (FDB) and Consumer units (DB) of second floor
Wattage 2DB1 2DB2 2CU1
Diversity/
(W)
Item Description Utilization Current Current Current Current Current Current
/Ammpe (1) Qntity Qntity Qntity
re(A) (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ
Light fittings
1 × 14, single fluorescent fitting with diffuser and
16.0 80% 19 1.07 - 23 1.29 - 1 0.07 -
electronic ballast at 0.99 p.f. (Ballast loss 2W)
1 × 28, single fluorescent fitting with diffuser and
32.7 80% - - - - - - - - -
electronic ballast at 0.97 p.f. (Ballast loss 4.7W)
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 90% 47 11.33 - 37 8.92 - 5 1.21 -
Loss 5W )
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 90% 10 2.41 - 13 3.13 - - -
Loss 5W )
Ceiling recessed mounted down light with 1x15W
15.0 80% 11 0.72 - 15 0.98 - - - -
CFL and bottom glass at 0.8p.f.
Fans
75W Ceiling fan at 0.8 p.f. 75.0 100% 19 7.74 - 18 7.34 - - -
51.9W wall fan at 0.8 p.f. 51.9 90% 1 0.25 - 4 1.02 - - -
Small power -
13A Socket outlets for fore exit signs (W) 3.5 100% 2 0.04 - 2 0.04 - - - -
13A Socket outlet (A) 1.0 50% 70 35.00 - 62 31.00 - 13 6.5 -
13A dedicated socket outlet (A) 7.0 30% 10 21.00 - 7 14.70 - 2 4.20 -
Other Special Loads
500W single phase Operation theatre lamp @ 0.8
500.0 100% - - - - - - - -
p.f.
Sub Total 01 79.57 0.00 68.42 0.00 11.98 0.00

Three phase/ single phase line current in each


26.52 A 22.81 A 11.98 A
pase(2)
Add 10% for single phase load inbalance(2) 2.65 A 2.28 A 0.40 A
Sub Total 02 29.17 A 25.09 A 12.37 A
Add 10% for future exapansions(3) 2.92 A 2.51 A 1.24 A
Sub Total 03 32.09 A 27.59 A 13.61 A

Design current for FDBs 33.00 A , 3Φ 28.00 A , 3Φ 14.00 A , 1Φ


Selected breaker(5) 40A, 4P MCB 40A, 4P MCB 32A, 2P MCB

CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA


B4.Design current calculation sheet for Distribution Boards (FDB) and Consumer units (DB) of Third floor
Wattage 3CU1 3DB1 3DB2 3DB3
Diversity/
(W)
Item Description Utilization Current Current Current Current Current Current Current Current (A) -
/Ammpe (1) Qntity Qntity Qntity Qntity
re(A) (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ 3Φ
Light fittings
1 × 14, single fluorescent fitting with diffuser and
16.0 100% 4 0.28 - 5 0.35 - - - - - - -
electronic ballast at 0.99 p.f. (Ballast loss 2W)
1 × 28, single fluorescent fitting with diffuser and
32.7 100% 6 0.88 - 6 - - - - - - - -
electronic ballast at 0.97 p.f. (Ballast loss 4.7W)
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 100% 4 1.07 - 36 9.64 - 9 2.41 - 9 2.41 -
Loss 5W )
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 100% 4 1.07 - 17 4.55 - 4 1.07 - 2 0.54 -
Loss 5W )
Ceiling recessed mounted down light with 1x15W
15.0 100% 22 1.79 - 8 0.65 - - - - - - -
CFL and bottom glass at 0.8p.f.
Fans
75W Ceiling fan at 0.8 p.f. 75.0 100% 5 2.04 - 1 0.41 - - - - - - -
51.9W wall fan at 0.8 p.f. 51.9 90% - - - - - - - - - - - -
Small power -
13A Socket outlets for fore exit signs (W) 3.5 100% 1 0.02 - 1 0.02 - - - - - - -
13A Socket outlet (A) 1.0 60% 12 7.20 - 39 23.40 - 32 19.2 - 32 19.2 -
13A dedicated socket outlet (A) 7.0 40% - - - 1 2.80 - 2 5.60 - 2 5.6 -
Other Special Loads
500W single phase Operation theatre lamp @ 0.8
500.0 100% - - - - - 1 2.72 - 1 2.72 -
p.f.
Sub Total 01 14.35 0.00 41.83 0.00 31.00 0.00 30.46 0.00

Three phase/ single phase line current in each


14.35 A 13.94 A 31.00 A 30.46 A
pase(2)
Add 10% for single phase load inbalance(2) 0.48 A 1.39 A 1.03 A 1.02 A
Sub Total 02 14.83 A 15.34 A 32.03 A 31.48 A
Add 10% for future exapansions(3) 1.48 A 1.53 A 3.20 A 3.15 A
Sub Total 03 16.32 A 16.87 A 35.24 A 34.63 A

Design current for FDBs 17.00 A , 1Φ 17.00 A , 3Φ 36.00 A , 1Φ 35.00 A , 1Φ


Selected breaker(5) 40A, 2P MCB 32A, 4P MCB 40A, 2P MCB 40A, 2P MCB

CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA


B4.Design current calculation sheet for Distribution Boards (FDB) and Consumer units (DB) of Third floor
Wattage 3DB4 3DB5 3DB6 3CU2
Diversity/
(W)
Item Description Utilization Current Current Current Current Current Current Current Current (A) -
/Ammpe (1) Qntity Qntity Qntity Qntity
re(A) (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ 3Φ
Light fittings
1 × 14, single fluorescent fitting with diffuser and
16.0 100% - - - - - - 1 0.08 - 3 0.21 -
electronic ballast at 0.99 p.f. (Ballast loss 2W)
1 × 28, single fluorescent fitting with diffuser and
32.7 100% - - - - - - - - - 4 0.59 -
electronic ballast at 0.97 p.f. (Ballast loss 4.7W)
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 100% - - - 16 4.29 - 16 4.29 - 4 1.07 -
Loss 5W )
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 100% - - - - - - - - - 12 3.21 -
Loss 5W )
Ceiling recessed mounted down light with 1x15W
15.0 100% - - - - - - - - - 11 0.90 -
CFL and bottom glass at 0.8p.f.
Fans
75W Ceiling fan at 0.8 p.f. 75.0 100% - - - - - - - - - - - -
51.9W wall fan at 0.8 p.f. 51.9 90% - - - - - - - - - 1 0.25 -
Small power -
13A Socket outlets for fore exit signs (W) 3.5 100% - - - - - - - - - 1 0.02 -
13A Socket outlet (A) 1.0 60% 20 12.00 - 36 21.60 - 60 36 - 6 3.6 -
13A dedicated socket outlet (A) 7.0 40% 3 8.40 - 6 16.80 - 1 2.80 - 1 2.8 -
Other Special Loads
500W single phase Operation theatre lamp @ 0.8
500.0 100% - - - - - - - - - - -
p.f.
Sub Total 01 20.40 0.00 42.69 0.00 43.16 0.00 12.65 0.00

Three phase/ single phase line current in each


20.40 A 42.69 A 14.39 A 12.65 A
pase(2)
Add 10% for single phase load inbalance(2) 0.68 A 1.42 A 1.44 A 0.42 A
Sub Total 02 21.08 A 44.11 A 15.83 A 13.07 A
Add 10% for future exapansions(3) 2.11 A 4.41 A 1.58 A 1.31 A
Sub Total 03 23.19 A 48.52 A 17.41 A 14.38 A

Design current for FDBs 24.00 A , 1Φ 49.00 A , 1Φ 18.00 A , 3Φ 15.00 A , 1Φ


Selected breaker(5) 40A, 2P MCB 63A, 2P MCB 40A, 4P MCB 40A, 2P MCB

CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA


B4.Design current calculation sheet for Distribution Boards (FDB) and Consumer units (DB) of Fourth floor
Wattage 4DB1 4DB2 4CU1
Diversity/
(W)
Item Description Utilization Current Current Current Current Current Current
/Ammpe (1) Qntity Qntity Qntity
re(A) (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ
Light fittings
1 × 14, single fluorescent fitting with diffuser and
16.0 80% 17 0.96 - 25 1.41 - 1 0.07 -
electronic ballast at 0.99 p.f. (Ballast loss 2W)
1 × 28, single fluorescent fitting with diffuser and
32.7 80% - - - - - - - - -
electronic ballast at 0.97 p.f. (Ballast loss 4.7W)
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 90% 47 11.33 - 40 9.64 - 5 1.21 -
Loss 5W )
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 90% 10 2.41 - 14 3.38 - - -
Loss 5W )
Ceiling recessed mounted down light with 1x15W
15.0 80% 11 0.72 - 13 0.85 - - - -
CFL and bottom glass at 0.8p.f.
Fans
75W Ceiling fan at 0.8 p.f. 75.0 100% 15 6.11 - 13 5.30 - - -
51.9W wall fan at 0.8 p.f. 51.9 90% 1 0.25 - 3 0.76 - - -
Small power -
13A Socket outlets for fore exit signs (W) 3.5 100% 2 0.04 - 2 0.04 - - - -
13A Socket outlet (A) 1.0 50% 63 31.50 - 58 29.00 - 13 6.5 -
13A dedicated socket outlet (A) 7.0 30% 9 18.90 - 7 14.70 - 2 4.20 -
Other Special Loads
500W single phase Operation theatre lamp @ 0.8
500.0 100% - - - - - - - -
p.f.
Sub Total 01 72.22 0.00 65.07 0.00 11.98 0.00

Three phase/ single phase line current in each


24.07 A 21.69 A 11.98 A
pase(2)
Add 10% for single phase load inbalance(2) 2.41 A 2.17 A 0.40 A
Sub Total 02 26.48 A 23.86 A 12.37 A
Add 10% for future exapansions(3) 2.65 A 2.39 A 1.24 A
Sub Total 03 29.13 A 26.25 A 13.61 A

Design current for FDBs 30.00 A , 3Φ 27.00 A , 3Φ 14.00 A , 1Φ


Selected breaker(5) 40A, 4P MCB 40A, 4P MCB 32A, 2P MCB

CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA


B4.Design current calculation sheet for Distribution Boards (FDB) and Consumer units (DB) of Machine room floor
Wattage CUMR1 CUMR2
Diversity/
(W)
Item Description Utilization Current Current Current Current
/Ammpe (1) Qntity Qntity
re(A) (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ
Light fittings
1 × 14, single fluorescent fitting with diffuser and
16.0 80% - - - - - -
electronic ballast at 0.99 p.f. (Ballast loss 2W)
1 × 28, single fluorescent fitting with diffuser and
32.7 80% 11 1.26 - 8 0.92 -
electronic ballast at 0.97 p.f. (Ballast loss 4.7W)
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 90% - - - - - -
Loss 5W )
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast 61.0 90% - - - - - -
Loss 5W )
Ceiling recessed mounted down light with 1x15W
15.0 80% 2 0.13 - 1 0.07 -
CFL and bottom glass at 0.8p.f.
Fans
75W Ceiling fan at 0.8 p.f. 75.0 100% - - - - - -
51.9W wall fan at 0.8 p.f. 51.9 90% - - - - - -
Small power -
13A Socket outlets for fore exit signs (W) 3.5 100% 1 0.02 - 1 0.02 -
13A Socket outlet (A) 1.0 50% 11 5.50 - 4 2.00 -
13A dedicated socket outlet (A) 7.0 30% - - - - - -
500W single phase Operation theatre lamp @ 0.8
500.0 100% - - - - -
p.f.
Sub Total 01 6.91 0.00 3.00 0.00

Three phase/ single phase line current in each


6.91 A 3.00 A
pase(2)
Add 10% for single phase load inbalance(2) 0.23 A 0.10 A
Sub Total 02 7.14 A 3.10 A
Add 10% for future exapansions(3) 0.71 A 0.31 A
Sub Total 03 7.86 A 3.41 A

Design current for FDBs 8.00 A , 1Φ 4.00 A , 1Φ


Selected breaker(5) 32A, 2P MCB 32A, 2P MCB

CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA


B4.Design current calculation sheet for Distribution Boards (FDB) and Consumer units (DB) of Mechanical works
Wattage GDBAC 1DBAC 2DBAC 4DBAC
Diversity/
(W)
Item Description Utilization Current Current Current Current Current Current Current Current (A) -
/Ammpe (1) Qntity Qntity Qntity Qntity
re(A) (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ 3Φ
Small power -
13A Socket outlets for fore exit signs (W) 3.5 100% - - - - - - - - - 1 0.02 -
Air Conditioning
10kW three phase AHU at 0.8 p.f. 10000.0 100% - - - - - - - - - -
8kW three phase AHU at 0.8 p.f. 8000.0 100% - - - - - - - - - -
2kW three phase AHU at 0.8 p.f. 2000.0 100% - - - - - - - - - -
1.5kW three phase AHU at 0.8 p.f. 1500.0 100% 3 - 8.15 5 - 13.59 5 - 13.59 5 - 13.59
100W Single phase fan coil unit at 0.8p.f. 100.0 100% 25 13.59 - 5 2.72 - 2 1.09 - 2 1.09 -
150W Single phase fan coil unit at 0.8p.f. 150.0 100% 4 3.26 - - - - 1 0.82 - 5 4.08 -
250W Single phase fan coil unit at 0.8p.f. 250.0 100% 2 2.72 - - - - - - - - - -
Other Special Loads
500W single phase Operation theatre lamp @ 0.8
500.0 100% - - - - - - - - - - -
p.f.
Sub Total 01 19.57 8.15 2.72 13.59 1.90 13.59 5.18 13.59
Three phase/ single phase line current in each
14.67 A 14.49 A 14.22 A 15.31 A
pase(2)
Add 10% for single phase load inbalance(2) 0.65 A 0.09 A 0.06 A 0.17 A
Sub Total 02 15.33 A 14.58 A 14.28 A 15.49 A
Add 10% for future exapansions(3) 1.53 A 1.46 A 1.43 A 1.55 A
Sub Total 03 16.86 A 16.04 A 15.71 A 17.04 A

Design current for FDBs 17.00 A , 3Φ 17.00 A , 3Φ 16.00 A , 3Φ 18.00 A , 3Φ


Selected breaker(5) 32A, 4P MCB 32A, 4P MCB 32A, 4P MCB 32A, 4P MCB
A B C D E F G H I J K L M N O P Q R S T U V W X
1 CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUW
2 B4.Cable selection and protective fault currents - Calculation sheet 01 of 04
3

4 Cable characteristics Correction factor(3)


Ref. Max.
(It)
Nominal method Nominal Type of Number Voltage Accept/
Length Design Voltage drop Current Voltage
5 Cable from Un (min) Cable to CCT Φ of current Pro. Cross current of drop up to Not
(m) current (mv/A/m) rating (A) drop (V)(5)
(V)(1) installatio (In) (A) device section rating Type circuits Cg Ca Ci Cc the cable Accept(6)
(Ib)(2) (4)
n (mm2) (Iz ) end(6)
6 r x z

Incomer 240 XLPE


7 Transformer 400.00 3 F 10.00 848.48 1000 MCCB 1268 0.170 0.165 0.240 2 0.88 1 1 1 1115.84 1.02 0.25% Accept
Panel (1C×8) (TC 900)

Incomer 240 XLPE


8 Generator 400.00 3 F 15.00 848.48 1000 MCCB 1268 0.170 0.165 0.240 2 0.88 1 1 1 1115.84 1.53 0.38% Accept
Panel (1C×8) (TC 900)

Incomer 240 XLPE


9 398.98 MDB 3 F 20.00 848.48 1000 MCCB 1268 0.170 0.165 0.240 2 0.82 1 1 1 1039.76 2.04 0.76% Accept
Panel (1C×8) (TC 900)

10

XLPE
11 MDB 396.95 GFDB 3 F 45.00 62.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 1 0.72 1 1 1 113.76 3.21 1.57% Accept
(TC 900)

XLPE
12 MDB 396.95 1FDB 3 E 35.00 70.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 1 0.72 1 1 1 113.76 2.82 1.47% Accept
(TC 900)

XLPE
13 MDB 396.95 2FDB 3 E 40.00 79.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 1 0.72 1 1 1 113.76 3.63 1.67% Accept
(TC 900)

XLPE
14 MDB 396.95 3FDB 3 E 50.00 80.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 1 0.72 1 1 1 113.76 4.60 1.91% Accept
(TC 900)

XLPE
15 MDB 396.95 3DBAC 3 E 30.00 69.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 1 0.72 1 1 1 113.76 2.38 1.36% Accept
(TC 900)

XLPE
16 MDB 396.95 4FDB 3 E 30.00 76.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 1 0.72 1 1 1 113.76 2.62 1.42% Accept
(TC 900)

17
18
19 Notes : 1) Nominal Voltage (Un) - Voltage at relevant panel 6) Conditions for "ACCEPT"
20 2) Design current is taken with the future expansion loads in all panels. a) In>Ib & It>In
21 3) The reference for the correction factors is IEE BS 7671 18 th edition b) Criteria for Voltage drop, Vd as follows,
22 4) Equation for the derated current carrying capacity, I t = Iz×Cg×Ca×Ci×Cc From Transformer to Incomer panel - 0.4% & from Incomer panel to MDB - 0.6%
Where Cg - grouping factor, Ca - correction for ambient temperature, Ci - correction for thermal From MDB to FDBs - 2.0% (total Voltage drop at FDB < 3.0%) From MDB to DBs of other
23
insulation, Cc - factor for type of the protective device or installation condition loads - 3.6%to(total
From FDBs DBsdrop at DB <+ 4.6%)
for lighting small power - 1.0% (total Voltage drop - 4.0%) , From FDB
24 5) Equation for Voltage drop = L×Ib×z/1000
to mechanical loads - 1.0% (total voltage drop < 4.0%)
25 From DBs to lighting points - 1.0% (total voltage drop < 5%)
26 From DBs to loads other than lighting/mechanical loads - 1.0% (total Voltage drop <5%)
Maximum Voltage drop for lighting circuit is lees than 5%, this is acceptable since this
27
building has dedicated transformer.
28
29
30
A B C D E F G H I J K L M N O P Q R S T U V W X
31
32
33 CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUW
34 B4.Cable selection and protective fault currents - Calculation sheet 02 of 04
35

36 Cable characteristics Correction factor(3)


Ref. Max.
(It)
Nominal method Nominal Type of Number Voltage Accept/
Length Design Voltage drop Current Voltage
37 Cable from Un (min) Cable to CCT Φ of current Pro. Cross current of drop up to Not
(m) current (mv/A/m) rating (A) drop (V)(5)
(V)(1) installatio (In) (A) device section rating Type circuits Cg Ca Ci Cc the cable Accept(6)
(Ib)(2) (4)
n (mm2) (Iz ) end(6)
38 r x z

PVC (TC
39 MDB 396.95 DBMR1 3 E 30.00 33.00 40 MCCB 10 (4C×1) 60 - - 3.800 1 0.72 1 1 1 43.2 3.76 1.70% Accept
700

PVC (TC
40 MDB 396.95 DBMR2 3 E 90.00 32.00 40 MCCB 10 (4C×1) 60 - - 3.800 1 0.72 1 1 1 43.2 10.94 3.50% Accept
700

XLPE
41 MDB 396.95 DBCHILLER 3 F 90.00 367.00 400 MCCB 95 (1C×8) 684 0.430 0.170 0.460 2 0.72 1 1 1 492.48 7.60 2.66% Accept
(TC 900)

XLPE
42 MDB 396.95 DBMG 3 F 30.00 41.00 63 MCCB 16 (4C×1) 80 - - 2.400 1 0.82 1 1 1 65.6 2.95 1.50% Accept
(TC 900)

PVC (TC
43 MDB 396.95 DBWP 3 F 15.00 19.00 40 MCCB 10 (4C×1) 60 - - 3.800 1 0.72 1 1 1 43.2 1.08 1.03% Accept
700

XLPE
44 MDB 396.95 DBX 3 E 40.00 80.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 1 0.72 1 1 1 113.76 3.68 1.68% Accept
(TC 900)

XLPE
45 MDB 396.95 DBCT 3 E 20.00 140.00 160 MCCB 70 (4C×1) 246 0.590 0.130 0.600 1 0.72 1 1 1 177.12 1.68 1.18% Accept
(TC 900)

46
47
48 Notes : 1) Nominal Voltage (Un) - Voltage at relevant panel 6) Conditions for "ACCEPT"
49 2) Design current is taken with the future expansion loads in all panels. a) In>Ib & It>In
50 3) The reference for the correction factors is IEE BS 7671 18 th edition b) Criteria for Voltage drop, Vd as follows,
51 4) Equation for the derated current carrying capacity, I t = Iz×Cg×Ca×Ci×Cc From Transformer to Incomer panel - 0.4% & from Incomer panel to MDB - 0.6%
Where Cg - grouping factor, Ca - correction for ambient temperature, Ci - correction for thermal From MDB to FDBs - 2.0% (total Voltage drop at FDB < 3.0%) From MDB to DBs of other
52
insulation, Cc - factor for type of the protective device or installation condition loads FDBs
From - 3.6%to(total
DBsdrop at DB <+ 4.6%)
for lighting small power - 1.0% (total Voltage drop - 4.0%) , From FDB
53 5) Equation for Voltage drop = L×Ib×z/1000
to mechanical loads - 1.0% (total voltage drop < 4.0%)
54 From DBs to lighting points - 1.0% (total voltage drop < 5%)
55 From DBs to loads other than lighting/mechanical loads - 1.0% (total Voltage drop <5%)
Maximum Voltage drop for lighting circuit is lees than 5%, this is acceptable since this
56
building has dedicated transformer.
57
58
59
60
61
62
63
64
65
66
A B C D E F G H I J K L M N O P Q R S T U V W X
67
68
69
70
71 CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUW
72 B4.Cable selection and protective fault currents - Calculation sheet 03 of 04
73

74 Cable characteristics Correction factor(3)


Ref. Max.
(It)
Nominal method Nominal Type of Number Voltage Accept/
Length Design Voltage drop Current Voltage
75 Cable from Un (min) Cable to CCT Φ of current Pro. Cross current of drop up to Not
(m) current (mv/A/m) rating (A) drop (V)(5)
(V)(1) installatio (In) (A) device section rating Type circuits Cg Ca Ci Cc the cable Accept(6)
(Ib)(2) (4)
n (mm2) (Iz ) end(6)
76 r x z

6 PVC (TC
77 GFDB 393.74 GDB1 3 E 20.00 17.00 32 MCB 43 - - 6.400 1 0.75 1 1 1 32.25 2.18 2.11% Accept
(4C×1) 700
6 PVC (TC
78 GFDB 393.74 GDB2 3 E 18.00 20.00 32 MCB 43 - - 6.400 1 0.75 1 1 1 32.25 2.30 2.14% Accept
(4C×1) 700
6 PVC (TC
79 GFDB 393.74 CUXR 1 E 20.00 7.00 32 MCB 51 - - 7.300 1 0.75 1 1 1 38.25 1.02 1.61% Accept
(2C×1) 700
6 PVC (TC
80 GFDB 393.74 CUCT 1 E 25.00 21.00 32 MCB 51 - - 7.300 1 0.75 1 1 1 38.25 3.83 2.12% Accept
(2C×1) 700
6 PVC (TC
81 GFDB 393.74 GDBAC 3 E 5.00 17.00 32 MCB 43 - - 6.400 1 0.75 1 1 1 32.25 0.54 1.70% Accept
(4C×1) 700
82
6 PVC (TC
83 1FDB 394.13 1DB1 3 E 21.00 21.00 32 MCB 43 - - 6.400 1 0.77 1 1 1 33.11 2.82 2.17% Accept
(4C×1) 700
10 PVC (TC
84 1FDB 394.13 1DB2 3 E 18.00 30.00 40 MCB 75 - - 3.800 1 0.77 1 1 1 57.75 2.05 1.98% Accept
(4C×1) 700
6 PVC (TC
85 1FDB 394.13 1CU1 1 E 15.00 14.00 32 MCB 51 - - 7.300 1 0.77 1 1 1 39.27 1.53 1.73% Accept
(2C×1) 700
6 PVC (TC
86 1FDB 394.13 1DBAC 3 E 21.00 17.00 32 MCB 43 - - 6.400 1 0.77 1 1 1 33.11 2.28 2.04% Accept
(4C×1) 700
87
88 Notes : 1) Nominal Voltage (Un) - Voltage at relevant panel 6) Conditions for "ACCEPT"
89 2) Design current is taken with the future expansion loads in all panels. a) In>Ib & It>In
90 3) The reference for the correction factors is IEE BS 7671 18 th edition b) Criteria for Voltage drop, Vd as follows,
91 4) Equation for the derated current carrying capacity, I t = Iz×Cg×Ca×Ci×Cc From Transformer to Incomer panel - 0.4% & from Incomer panel to MDB - 0.6%
Where Cg - grouping factor, Ca - correction for ambient temperature, Ci - correction for thermal From MDB to FDBs - 2.0% (total Voltage drop at FDB < 3.0%) From MDB to DBs of other
92
insulation, Cc - factor for type of the protective device or installation condition loads FDBs
From - 3.6%to(total
DBsdrop at DB <+ 4.6%)
for lighting small power - 1.0% (total Voltage drop - 4.0%) , From FDB
93 5) Equation for Voltage drop = L×Ib×z/1000
to mechanical loads - 1.0% (total voltage drop < 4.0%)
94 From DBs to lighting points - 1.0% (total voltage drop < 5%)
95 From DBs to loads other than lighting/mechanical loads - 1.0% (total Voltage drop <5%)
Maximum Voltage drop for lighting circuit is lees than 5%, this is acceptable since this
96
building has dedicated transformer.
97
98
99
100
101
102
103
104
105
106
A B C D E F G H I J K L M N O P Q R S T U V W X
107
108
109
110
111
112
113
114 CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUW
115 B4.Cable selection and protective fault currents - Calculation sheet 04 of 04
116

117 Cable characteristics Correction factor(3)


Ref. Max.
(It)
Nominal method Nominal Type of Number Voltage Accept/
Length Design Voltage drop Current Voltage
118 Cable from Un (min) Cable to CCT Φ of current Pro. Cross current of drop up to Not
(m) current (mv/A/m) rating (A) drop (V)(5)
(V)(1) installatio (In) (A) device section rating Type circuits Cg Ca Ci Cc the cable Accept(6)
(Ib)(2) (4)
n (mm2) (Iz ) end(6)
119 r x z

10 PVC (TC
120 2FDB 393.31 2DB1 3 E 25.00 33.00 40 MCB 75 - - 3.800 1 0.75 1 1 1 56.25 3.14 2.46% Accept
(4C×1) 700
10 PVC (TC
121 2FDB 393.31 2DB2 3 E 15.00 28.00 40 MCB 75 - - 3.800 1 0.75 1 1 1 56.25 1.60 2.07% Accept
(4C×1) 700
6 PVC (TC
122 2FDB 393.31 2CU1 1 E 15.00 14.00 32 MCB 51 - - 7.300 1 0.75 1 1 1 38.25 1.53 1.94% Accept
(2C×1) 700
6 PVC (TC
123 2FDB 393.31 2DBAC 3 E 25.00 16.00 32 MCB 43 - - 6.400 1 0.75 1 1 1 32.25 2.56 2.04% Accept
(4C×1) 700
124
6 PVC (TC
125 3FDB 392.35 3DB1 3 E 21.00 17.00 32 MCB 43 - - 6.400 1 1 1 1 1 43 2.28 2.48% Accept
(4C×1) 700
10 PVC (TC
126 3FDB 392.35 3DB2 1 E 18.00 36.00 40 MCB 70 - - 4.400 1 0.73 1 1 1 51.1 2.85 2.75% Accept
(2C×1) 700
10 PVC (TC
127 3FDB 392.35 3DB3 1 E 15.00 35.00 40 MCB 70 - - 4.400 1 0.73 1 1 1 51.1 2.31 2.52% Accept
(2C×1) 700
10 PVC (TC
128 3FDB 392.35 3DB4 1 E 15.00 24.00 40 MCB 70 - - 4.400 1 0.73 1 1 1 51.1 1.58 2.20% Accept
(2C×1) 700
16 PVC (TC
129 3FDB 392.35 3DB5 1 E 15.00 49.00 63 MCB 94 - - 2.800 1 0.73 1 1 1 68.62 2.06 2.41% Accept
(2C×1) 700
10 PVC (TC
130 3FDB 392.35 3DB6 3 E 15.00 18.00 40 MCB 75 - - 3.800 1 0.73 1 1 1 54.75 1.03 2.06% Accept
(4C×1) 700
10 PVC (TC
131 3FDB 392.35 3CU1 1 E 25.00 17.00 40 MCB 70 - - 4.400 1 0.73 1 1 1 51.1 1.87 2.33% Accept
(2C×1) 700
10 PVC (TC
132 3FDB 392.35 3CU2 1 E 21.00 15.00 40 MCB 70 - - 4.400 1 0.73 1 1 1 51.1 1.39 2.12% Accept
(2C×1) 700
133
134 Notes : 1) Nominal Voltage (Un) - Voltage at relevant panel 6) Conditions for "ACCEPT"
135 2) Design current is taken with the future expansion loads in all panels. a) In>Ib & It>In
136 3) The reference for the correction factors is IEE BS 7671 18 th edition b) Criteria for Voltage drop, Vd as follows,
137 4) Equation for the derated current carrying capacity, I t = Iz×Cg×Ca×Ci×Cc From Transformer to Incomer panel - 0.4% & from Incomer panel to MDB - 0.6%
Where Cg - grouping factor, Ca - correction for ambient temperature, Ci - correction for thermal From MDB to FDBs - 2.0% (total Voltage drop at FDB < 3.0%) From MDB to DBs of other
138
insulation, Cc - factor for type of the protective device or installation condition loads FDBs
From - 3.6%to(total
DBsdrop at DB <+ 4.6%)
for lighting small power - 1.0% (total Voltage drop - 4.0%) , From FDB
139 5) Equation for Voltage drop = L×Ib×z/1000
to mechanical loads - 1.0% (total voltage drop < 4.0%)
140 From DBs to lighting points - 1.0% (total voltage drop < 5%)
141 From DBs to loads other than lighting/mechanical loads - 1.0% (total Voltage drop <5%)
Maximum Voltage drop for lighting circuit is lees than 5%, this is acceptable since this
142
building has dedicated transformer.
A B C D E F G H I J K L M N O P Q R S T U V W X
143
144
145
146
147
148
149
150
151
152
153 CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUW
154 B4.Cable selection and protective fault currents - Calculation sheet 04 of 04
155

156 Cable characteristics Correction factor(3)


Ref. Max.
(It)
Nominal method Nominal Type of Number Voltage Accept/
Length Design Voltage drop Current Voltage
157 Cable from Un (min) Cable to CCT Φ of current Pro. Cross current of drop up to Not
(m) current (mv/A/m) rating (A) drop (V)(5)
(V)(1) installatio (In) (A) device section rating Type circuits Cg Ca Ci Cc the cable Accept(6)
(Ib)(2) (4)
n (mm2) (Iz ) end(6)
158 r x z

10 PVC (TC
159 4FDB 393.31 4DB1 3 E 25.00 30.00 40 MCB 75 - - 3.800 1 0.77 1 1 1 57.75 2.85 2.38% Accept
(4C×1) 700
10 PVC (TC
160 4FDB 393.31 4DB2 3 E 15.00 27.00 40 MCB 75 - - 3.800 1 0.77 1 1 1 57.75 1.54 2.06% Accept
(4C×1) 700
6 PVC (TC
161 4FDB 393.31 4CU1 1 E 15.00 14.00 32 MCB 51 - - 7.300 1 0.77 1 1 1 39.27 1.53 1.94% Accept
(2C×1) 700
162
6 PVC (TC
163 DBMR1 392.35 CUMR1 1 E 21.00 8.00 32 MCB 51 - - 6.400 1 1 1 1 1 51 1.08 1.98% Accept
(2C×1) 700
10 PVC (TC
164 DBMR2 392.35 CUMR2 1 E 18.00 4.00 40 MCB 70 - - 4.400 1 0.73 1 1 1 51.1 0.32 1.65% Accept
(2C×1) 700
165
Light point 1.5 PVC (TC
166 3CU1 224.65 1 E 25.00 3.00 6 MCB 14.5 - - 29.0 1 0.7 1 1 1 10.15 2.18 3.27% Accept
at 4th floor (C×2) 700
13A socket
2.5 PVC (TC
167 3CU1 224.65 outlet at 4th 1 E 25.00 7.00 16 MCB 20 - - 18.0 1 0.8 1 1 1 16 3.15 3.70% Accept
(C×2) 700
floor
168
169 Notes : 1) Nominal Voltage (Un) - Voltage at relevant panel 6) Conditions for "ACCEPT"
170 2) Design current is taken with the future expansion loads in all panels. a) In>Ib & It>In
171 3) The reference for the correction factors is IEE BS 7671 18 th edition b) Criteria for Voltage drop, Vd as follows,
172 4) Equation for the derated current carrying capacity, I t = Iz×Cg×Ca×Ci×Cc From Transformer to Incomer panel - 0.4% & from Incomer panel to MDB - 0.6%
Where Cg - grouping factor, Ca - correction for ambient temperature, Ci - correction for thermal From MDB to FDBs - 2.0% (total Voltage drop at FDB < 3.0%) From MDB to DBs of other
173
insulation, Cc - factor for type of the protective device or installation condition loads - 3.6%to(total
From FDBs DBsdrop at DB <+ 4.6%)
for lighting small power - 1.0% (total Voltage drop - 4.0%) , From FDB
174 5) Equation for Voltage drop = L×Ib×z/1000
to mechanical loads - 1.0% (total voltage drop < 4.0%)
175 From DBs to lighting points - 1.0% (total voltage drop < 5%)
176 From DBs to loads other than lighting/mechanical loads - 1.0% (total Voltage drop <5%)
Maximum Voltage drop for lighting circuit is lees than 5%, this is acceptable since this
177
building has dedicated transformer.
A B C D E F G H I J K L M N O P Q R S
1 CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA
2 B4.Calculation of prospective fault currents and cable size verification using adiabatic equation - Calculation sheet 01 of 04
3 origin
4 Cable characteristics om t/f to the equivation
Nominal Type of Number Impeadance /
Cable Length Design Cross current Voltage drop point (t/f (disconnection
5 Cable to CCT Φ current Pro. of of the line kA K factor
from (m) current section rating (mv/A/m) Type impedance time of
6 (In) (A) device r x z circuits (Zline) (IBASE =
(Ib)(2) (mm2) (Iz ) 0.05PU) protection
909.35)
240
7 Transformer Incomer Panel 3 10.00 848.48 1000 MCCB 1268 0.170 0.165 0.240 XLPE (TC 900) 2 0.003 0.053 17.16 143 12.00
(1C×8)
240
8 Generator Incomer Panel 3 15.00 848.48 1000 MCCB 1268 0.170 0.165 0.240 XLPE (TC 900) 2 0.004 0.054 16.84 143 11.78
(1C×8)
Incomer 240
9 MDB 3 20.00 848.48 1000 MCCB 1268 0.170 0.165 0.240 XLPE (TC 900) 2 0.005 0.058 15.68 143 10.96
Panel (1C×8)
10

11 MDB GFDB 3 50.00 62.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 XLPE (TC 900) 1 0.131 0.189 4.81 143 3.36

12 MDB 1FDB 3 35.00 70.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 XLPE (TC 900) 1 0.092 0.150 6.06 143 4.24

13 MDB 2FDB 3 40.00 79.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 XLPE (TC 900) 1 0.105 0.163 5.58 143 3.90

14 MDB 3FDB 3 50.00 80.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 XLPE (TC 900) 1 0.131 0.189 4.81 143 3.36

15 MDB 3DBAC 3 30.00 69.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 XLPE (TC 900) 1 0.078 0.136 6.69 143 4.68

16 MDB 4FDB 3 30.00 76.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 XLPE (TC 900) 1 0.078 0.136 6.69 143 4.68

17 MDB DBMR1 3 30.00 33.00 40 MCCB 10 (4C×1) 60 - - 3.800 PVC (TC 700) 1 0.259 0.317 2.87 115 2.49

18 MDB DBMR2 3 90.00 32.00 40 MCCB 10 (4C×1) 60 - - 3.800 PVC (TC 700) 1 0.777 0.835 1.09 115 0.95

19 MDB DBCHILLER 3 90.00 367.00 400 MCCB 95 (1C×8) 684 0.430 0.170 0.460 XLPE (TC 900) 2 0.047 0.105 8.66 143 6.06

20 MDB DBMG 3 30.00 41.00 63 MCCB 16 (4C×1) 80 - - 2.400 PVC (TC 700) 1 0.164 0.222 4.10 115 3.56

21 MDB DBWP 3 15.00 19.00 40 MCCB 10 (4C×1) 60 - - 3.800 PVC (TC 700) 1 0.130 0.188 4.84 115 4.21

22 MDB DBX 3 40.00 80.00 100 MCCB 35 (4C×1) 158 1.150 0.135 1.150 XLPE (TC 900) 1 0.105 0.163 5.58 143 3.90

23 MDB DBCT 3 20.00 140.00 160 MCCB 70 (4C×1) 246 0.590 0.130 0.600 XLPE (TC 900) 1 0.027 0.085 10.70 143 7.48

24
25
26
27
28
29
30
31
32
33
34
35
36
37
A B C D E F G H I J K L M N O P Q R S
38
39
40
41
42 CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA
43 B4.Calculation of protective fault currents and cable size verification using adiabatic equation - Calculation sheet 01 of 04
44
Total
45 Cable characteristics IPSSC at the
impedancefr
origin
om t/f to the
Nominal Type of Number Impeadance /
Cable Length Design Voltage drop point (t/f Minimum cable
46 Cable to CCT Φ current Pro. of of the line kA K factor
from (m) current Cross current (mv/A/m) impedance size /
(In) (A) device section rating Type circuits (Zline) (IBASE =
(Ib)(2) 0.05PU)
(mm2) (Iz ) 909.35)
47 r x z / PU (Z) (8)
(7)

6
48 GFDB GDB1 3 20.00 17.00 32 MCB 43 - - 6.400 PVC (TC 700) 1 0.291 0.480 1.89 115 1.65
(4C×1)
6
49 GFDB GDB2 3 18.00 20.00 32 MCB 43 - - 6.400 PVC (TC 700) 1 0.262 0.451 2.02 115 1.75
(4C×1)
6
50 GFDB CUXR 1 20.00 7.00 32 MCB 51 - - 7.300 PVC (TC 700) 1 0.575 0.764 1.19 115 1.03
(2C×1)
6
51 GFDB CUCT 1 25.00 21.00 32 MCB 51 - - 7.300 PVC (TC 700) 1 0.719 0.908 1.00 115 0.87
(2C×1)
6
52 GFDB GDBAC 3 5.00 17.00 32 MCB 43 - - 6.400 PVC (TC 700) 1 0.073 0.262 3.47 115 3.02
(4C×1)
53
6
54 1FDB 1DB1 3 21.00 21.00 32 MCB 43 - - 6.400 PVC (TC 700) 1 0.306 0.456 1.90 115 1.65
(4C×1)
10
55 1FDB 1DB2 3 18.00 30.00 40 MCB 75 - - 3.800 PVC (TC 700) 1 0.155 0.305 2.84 115 2.47
(4C×1)
6
56 1FDB 1CU1 1 15.00 14.00 32 MCB 51 - - 7.300 PVC (TC 700) 1 0.431 0.581 1.49 115 1.30
(2C×1)
6
57 1FDB 1DBAC 3 21.00 17.00 32 MCB 43 - - 6.400 PVC (TC 700) 1 0.306 0.456 1.90 115 1.65
(4C×1)
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
A B C D E F G H I J K L M N O P Q R S
79
80
81
82
83
84
85
86
87
88
89
90
91 CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA
92 B4.Calculation of protective fault currents and cable size verification using adiabatic equation - Calculation sheet 01 of 04
93 origin
94 Cable characteristics om t/f to the
Nominal Type of Number Impeadance /
Cable Length Design Cross current Voltage drop point (t/f Minimum cable
95 Cable to CCT Φ current Pro. of of the line kA K factor
from (m) current section rating (mv/A/m) Type impedance size /
96 (In) (A) device r x z circuits (Zline) (IBASE =
(Ib)(2)
(mm )2
(Iz ) 0.05PU)
10 909.35)
97 2FDB 2DB1 3 25.00 33.00 40 MCB 75 - - 3.800 PVC (TC 700) 1 0.216 0.379 2.40 115 2.09
(4C×1)
10
98 2FDB 2DB2 3 15.00 28.00 40 MCB 75 - - 3.800 PVC (TC 700) 1 0.130 0.293 3.10 115 2.70
(4C×1)
6
99 2FDB 2CU1 1 15.00 14.00 32 MCB 51 - - 7.300 PVC (TC 700) 1 0.431 0.594 1.53 115 1.33
(2C×1)
6
100 2FDB 2DBAC 3 25.00 16.00 32 MCB 43 - - 6.400 PVC (TC 700) 1 0.364 0.527 1.73 115 1.50
(4C×1)
101
6
102 3FDB 3DB1 3 21.00 17.00 32 MCB 43 - - 6.400 PVC (TC 700) 1 0.306 0.495 1.84 115 1.60
(4C×1)
10
103 3FDB 3DB2 1 18.00 36.00 40 MCB 70 - - 4.400 PVC (TC 700) 1 0.312 0.501 1.82 115 1.58
(2C×1)
10
104 3FDB 3DB3 1 15.00 35.00 40 MCB 70 - - 4.400 PVC (TC 700) 1 0.260 0.449 2.03 115 1.76
(2C×1)
10
105 3FDB 3DB4 1 15.00 24.00 40 MCB 70 - - 4.400 PVC (TC 700) 1 0.260 0.449 2.03 115 1.76
(2C×1)
16
106 3FDB 3DB5 1 15.00 49.00 63 MCB 94 - - 2.800 PVC (TC 700) 1 0.165 0.354 2.57 115 2.23
(2C×1)
10
107 3FDB 3DB6 3 15.00 18.00 40 MCB 75 - - 3.800 PVC (TC 700) 1 0.130 0.319 2.85 115 2.48
(4C×1)
10
108 3FDB 3CU1 1 25.00 17.00 40 MCB 70 - - 4.400 PVC (TC 700) 1 0.433 0.622 1.46 115 1.27
(2C×1)
10
109 3FDB 3CU2 1 21.00 15.00 40 MCB 70 - - 4.400 PVC (TC 700) 1 0.364 0.553 1.64 115 1.43
(2C×1)
110
111
112
113
114
115
116
117
118
119
120
121
A B C D E F G H I J K L M N O P Q R S
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137 CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA
138 B4.Calculation of protective fault currents and cable size verification using adiabatic equation - Calculation sheet 01 of 04
139 origin
140 Cable characteristics om t/f to the
Nominal Type of Number Impeadance /
Cable Length Design Cross current Voltage drop point (t/f Minimum cable
141 Cable to CCT Φ current Pro. of of the line kA K factor
from (m) current section rating (mv/A/m) Type impedance size /
142 (In) (A) device r x z circuits (Zline) (IBASE =
(Ib)(2) (mm2) (Iz ) 0.05PU)
10 909.35)
143 4FDB 4DB1 3 25.00 30.00 40 MCB 75 - - 3.800 PVC (TC 700) 1 0.216 0.352 2.58 115 2.25
(4C×1)
10
144 4FDB 4DB2 3 15.00 27.00 40 MCB 75 - - 3.800 PVC (TC 700) 1 0.130 0.266 3.42 115 2.97
(4C×1)
6
145 4FDB 4CU1 1 15.00 14.00 32 MCB 51 - - 7.300 PVC (TC 700) 1 0.431 0.567 1.60 115 1.39
(2C×1)
146
6
147 DBMR1 CUMR1 1 21.00 8.00 32 MCB 51 - - 6.400 PVC (TC 700) 1 0.529 0.846 1.07 115 0.93
(2C×1)
10
148 DBMR2 CUMR2 1 18.00 4.00 40 MCB 70 - - 4.400 PVC (TC 700) 1 0.312 0.629 1.45 115 1.26
(2C×1)
149
Light point at 4th 1.5
150 4DB2 1 25.00 3.00 6 MCB 14.5 - - 29.0 PVC (TC 700) 1 2.855 3.477 0.26 115 0.23
floor (C×2)
13A socket outlet 2.5
151 4DB2 1 25.00 7.00 16 MCB 20 - - 18.0 PVC (TC 700) 1 1.772 2.394 0.38 115 0.33
at 4th floor (C×2)
F VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA
B5.Selection of protective conductors using Adiabatic equation, Calculation sheets 01 of 03

Min. cable
Cable size/
characteristics adiabatic
Ipscc at equation
Earth Selected
the K (disconnecti
Cable from Cable to cable size cable size
origin factor(2) on time of
(mm2)(1) (mm2)(3)
/kA the
Area protective
Type
(mm2) device =
0.01s) mm2

Incomer 240 XLPE (TC


Transformer 240.00 17.16 143 12.00 50.00
Panel (1C×8) 900)
Incomer 240 XLPE (TC
Generator 240.00 16.84 143 11.78 50.00
Panel (1C×8) 900)
Incomer 240 XLPE (TC
MDB 240.00 15.68 143 10.96 50.00
Panel (1C×8) 900)

XLPE (TC
MDB GFDB 35 (4C×1) 16.00 4.81 143 3.36 10.00
900)
XLPE (TC
MDB 1FDB 35 (4C×1) 16.00 6.06 143 4.24 10.00
900)
XLPE (TC
MDB 2FDB 35 (4C×1) 16.00 5.58 143 3.90 10.00
900)
XLPE (TC
MDB 3FDB 35 (4C×1) 16.00 4.81 143 3.36 10.00
900)
XLPE (TC
MDB 3DBAC 35 (4C×1) 16.00 6.69 143 4.68 10.00
900)
XLPE (TC
MDB 4FDB 35 (4C×1) 16.00 6.69 143 4.68 10.00
900)
PVC (TC
MDB DBMR1 10 (4C×1) 10.00 2.87 115 2.49 10.00
700)
PVC (TC
MDB DBMR2 10 (4C×1) 10.00 1.09 115 0.95 10.00
700)
XLPE (TC
MDB DBCHILLER 95 (1C×8) 95.00 8.66 143 6.06 35.00
900)
PVC (TC
MDB DBMG 16 (4C×1) 16.00 4.10 115 3.56 16.00
700)
PVC (TC
MDB DBWP 10 (4C×1) 10.00 4.84 115 4.21 10.00
700)
XLPE (TC
MDB DBX 35 (4C×1) 16.00 5.58 143 3.90 16.00
900)
XLPE (TC
MDB DBCT 70 (4C×1) 35.00 10.70 143 7.48 16.00
900)
CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA
B5.Selection of protective conductors using Adiabatic equation, Calculation sheets 02 of 03

Min. cable
Cable size/
characteristics adiabatic
Ipscc at equation
Earth Selected
the K (disconnecti
Cable from Cable to cable size cable size
origin factor ) on time of
(2
(mm2)(1) (mm2)(3)
/kA the
Area protective
Type device =
(mm2)
0.01s) mm2

6 PVC (TC
GFDB GDB1 6.00 1.89 115 1.65 6.00
(4C×1) 700)
6 PVC (TC
GFDB GDB2 6.00 2.02 115 1.75 6.00
(4C×1) 700)
6 PVC (TC
GFDB CUXR 6.00 1.19 115 1.03 6.00
(2C×1) 700)
6 PVC (TC
GFDB CUCT 6.00 1.00 115 0.87 6.00
(2C×1) 700)
6 PVC (TC
GFDB GDBAC 6.00 3.47 115 3.02 6.00
(4C×1) 700)

6 PVC (TC
1FDB 1DB1 6.00 1.90 115 1.65 6.00
(4C×1) 700)
10 PVC (TC
1FDB 1DB2 10.00 2.84 115 2.47 10.00
(4C×1) 700)
6 PVC (TC
1FDB 1CU1 6.00 1.49 115 1.30 6.00
(2C×1) 700)
6 PVC (TC
1FDB 1DBAC 6.00 1.90 115 1.65 6.00
(4C×1) 700)

10 PVC (TC
2FDB 2DB1 10.00 2.40 115 2.09 10.00
(4C×1) 700)
10 PVC (TC
2FDB 2DB2 10.00 3.10 115 2.70 10.00
(4C×1) 700)
6 PVC (TC
2FDB 2CU1 6.00 1.53 115 1.33 6.00
(2C×1) 700)
6 PVC (TC
2FDB 2DBAC 6.00 1.73 115 1.50 6.00
(4C×1) 700)
CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA
B5.Selection of protective conductors using Adiabatic equation, Calculation sheets 03 of 03

Min. cable
Cable size/
characteristics adiabatic
Ipscc at equation
Earth Selected
the K (disconnecti
Cable from Cable to cable size cable size
origin factor ) on time of
(2
(mm2)(1) (mm2)(3)
/kA the
Area protective
Type device =
(mm2)
0.01s) mm2

6 PVC (TC
3FDB 3DB1 6.00 1.84 115 1.60 6.00
(4C×1) 700)
10 PVC (TC
3FDB 3DB2 10.00 1.82 115 1.58 10.00
(2C×1) 700)
10 PVC (TC
3FDB 3DB3 10.00 2.03 115 1.76 10.00
(2C×1) 700)
10 PVC (TC
3FDB 3DB4 10.00 2.03 115 1.76 10.00
(2C×1) 700)
16 PVC (TC
3FDB 3DB5 16.00 2.57 115 2.23 16.00
(2C×1) 700)
10 PVC (TC
3FDB 3DB6 10.00 2.85 115 2.48 10.00
(4C×1) 700)
10 PVC (TC
3FDB 3CU1 10.00 1.46 115 1.27 10.00
(2C×1) 700)
10 PVC (TC
3FDB 3CU2 10.00 1.64 115 1.43 10.00
(2C×1) 700)

10 PVC (TC
4FDB 4DB1 10.00 2.58 115 2.25 6.00
(4C×1) 700)
10 PVC (TC
4FDB 4DB2 10.00 3.42 115 2.97 10.00
(4C×1) 700)
6 PVC (TC
4FDB 4CU1 6.00 1.60 115 1.39 10.00
(2C×1) 700)

6 PVC (TC
DBMR1 CUMR1 6.00 1.07 115 0.93 6.00
(2C×1) 700)
10 PVC (TC
DBMR2 CUMR2 10.00 1.45 115 1.26 6.00
(2C×1) 700)

Light point 1.5 PVC (TC


4DB2 2.50 0.26 115 0.23 2.50
at 4th floor (1C×2) 700)
13A socket
2.5 PVC (TC
4DB2 outlet at 4th 2.50 0.38 115 0.33 2.50
(1C×2) 700)
floor
CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA
B5.Selection of breaking capapcities for the MCCBs and MCBs. Calculation sheets 01 of 02

Type of Main IPSSC at the


Selected
Protection Device (Ib) Design (In) Nominal origin
Location Breaking
of the Distribution Current (A) Current (A) /kA
Capacity/kA
Board

Incomer Panel MCCB 848.48 1000 17.157 25


MDB MCCB 848.48 1000 15.678 25

GFDB MCCB 62.00 100 4.81 25


1FDB MCCB 70.00 100 6.06 25
2FDB MCCB 79.00 100 5.58 25
3FDB MCCB 80.00 100 4.81 25
3DBAC MCCB 69.00 100 6.69 25
4FDB MCCB 76.00 100 6.69 25
DBMR1 MCCB 33.00 40 2.87 25
DBMR2 MCCB 32.00 40 1.09 25
DBCHILLER MCCB 367.00 400 8.66 25
DBMG MCCB 41.00 63 4.10 25
DBWP MCCB 19.00 40 4.84 25
DBX MCCB 80.00 100 5.58 25
DBCT MCCB 140.00 160 10.70 25

GDB1 MCB 17.00 32.00 1.89 10


GDB2 MCB 20.00 32.00 2.02 10
CUXR MCB 7.00 32.00 1.19 10
CUCT MCB 21.00 32.00 1.00 10
GDBAC MCB 17.00 32.00 3.47 10

1DB1 MCB 21.00 32.00 1.90 10


1DB2 MCB 30.00 40.00 2.84 10
1CU1 MCB 14.00 32.00 1.49 10
1DBAC MCB 17.00 32.00 1.90 10

2DB1 MCB 33.00 40 2.40 10


2DB2 MCB 28.00 40 3.10 10
2CU1 MCB 14.00 32 1.53 10
2DBAC MCB 16.00 32 1.73 10
CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA
B5.Selection of breaking capapcities for the MCCBs and MCBs. Calculation sheets 02 of 02

Type of Main IPSSC at the


Selected
Protection Device (Ib) Design (In) Nominal origin
Location Breaking
of the Distribution Current (A) Current (A) /kA
Capacity/kA
Board

3DB1 MCB 17.00 32 1.837 10


3DB2 MCB 36.00 40 1.815 10
3DB3 MCB 35.00 40 2.025 10
3DB4 MCB 24.00 40 2.025 10
3DB5 MCB 49.00 63 2.569 10
3DB6 MCB 18.00 40 2.851 10
3CU1 MCB 17.00 40 1.462 10
3CU2 MCB 15.00 40 1.644 10

4DB1 MCB 30.00 40 2.58 10


4DB2 MCB 27.00 40 3.42 10
4CU1 MCB 14.00 32 1.60 10

CUMR1 MCB 8.00 32 1.07 10


CUMR2 MCB 4.00 40 1.45 10

Light point at 4th


MCB 3.00 6 0.26 10
floor
13A socket outlet
MCB 7.00 16 0.38 10
at 4th floor

You might also like