To,
The Sr. Manager (ID)
HLL Infra Tech Services Ltd. (HITES)
B-1-14-A, Sector- 62,
NOIDA-201307
e-mail: sujeetkumar@hllhites.com
Name of work: Engineering, Procurement, and Construction (EPC) of PGIMER Satellite Centre at Una,
Himachal Pradesh, 300 Bedded Hospital with allied services and facilities.
Dear Sir,
We hereby submit the profile of M/s Sika along with the technical data sheet with test reports of Crystalline
waterproofing concrete additive/admix Sika Control WT-200 P – SIKA for concrete to make it leak-proof.
As the approved make in agreement, only Penetron is able to submit test reports of 16 bar pressure test. The
other approved makes are submitting their test reports for 5 bar pressure.
According to our agreement in Volume 5, Clause 13.3.1-A, we are required to subject DIN 1048 to hydrostatic
pressure ranging from 72.5 psi (5 bars) to 150 psi (10 bars) for a period of 72 to 96 hours. The reduction of
water penetration should be between 50% to 90%. The aforementioned requirements comply with the
technical specifications. Please refer to the attached copy of the agreement for your information and
necessary action.
You are requested to kindly accord your decision to allow us to move ahead accordingly.
Thanking you,
Yours faithfully,
Authorized Signatory