You are on page 1of 1

COLD WATER SUPPLY LINE

Building 1 (42 units)


WFSU / WSFU per
Public QTY
Unit type of
Water Closet Flush
42 5 210
Tank
Lavatory 84 2 168
Kitchen Sink 42 4 168
Shower 42 4 168
Bidet 42 4 168
TOTAL WFSU 882
195 GPM/ 12.30 lps

TDH 45 psi 70 ft

TDH x Q
Pump Power =
(3960) x Eff.

70 x 195 gpm
Pump Power =
(3960) x 0.7
Pump Power = 5 hp (Booster Pump)

COLD WATER SUPPLY LINE


Building 2 (38 units)
WFSU / WSFU per
Public QTY
Unit type of
Water Closet Flush
38 5 190
Tank
Lavatory 76 2 152
Kitchen Sink 38 4 152
Shower 38 4 152
Bidet 38 4 152
TOTAL WFSU 798
182 GPM/ 11.5 lps

TDH 45 psi 103.95 ft

TDH x Q
Pump Power =
(3960) x Eff.

103.95 x 182 gpm


Pump Power =
(3960) x 0.7
Pump Power = 5 hp (Transfer Pump)

Time to fill the


30 minutes
Overhead Tank
Capacity
Description QTY Head (ft) Motor RPM Controller and Inclusion V Phase Hertz Remarks
(GPM)
End Suction Centrifugal
Booster Pump 4 195 103.95 5 hp 3450 Pressure Switch 220 3 60 Pump,Electric Motor, Goulds,
Grundfos or Equivalent

End Suction Centrifugal


Pressure Tank, Pressure
Transfer 2 195 60 5 hp 3450 220 3 60 Pump,Electric Motor, Goulds,
Switch, Liquid Level Control
Grundfos or Equivalent