You are on page 1of 117

V-520 10/20

V-520 MAX 10/20


TK 54343-1-MM (Rev 0, 12/09)

Copyright© 2009 Thermo King Corp., Minneapolis, MN, USA.


Printed in USA.
The maintenance information in this manual covers unit models:
V-520-10 900829
V-520-20 900830
V-520 MAX-10 900831
V-520 MAX-20 900833
V-520 SPECTRUM-10 900834
V-520 SPECTRUM-20 900835
For further information, refer to:
V-520 Series Operating Manual TK 54342
V-520 Series Parts manual TK 53990
Diagnosing Thermo King Refrigeration Systems TK 5984
Evacuation Station Operation and Field Application TK 40612
Tool Catalog TK 5955
The information in this manual is provided to assist owners, operators and service people in the
proper upkeep and maintenance of Thermo King units. The above manuals may be purchased from
your local Thermo King dealer.

This manual is published for informational purposes only and the information so provided should
not be considered as all-inclusive or covering all contingencies. If further information is required,
Thermo King Corporation should be consulted.

Sale of product shown in this manual is subject to Thermo King’s terms and conditions
including, but not limited to, the Thermo King Limited Express Warranty. Such terms and
conditions are available upon request. Thermo King’s warranty will not apply to any
equipment which has been “so repaired or altered outside the manufacturer’s plants as,
in the manufacturer’s judgment, to effect its stability.”

No warranties, express or implied, including warranties of fitness for a particular


purpose or merchantability, or warranties arising from course of dealing or usage of
trade, are made regarding the information, recommendations, and descriptions
contained herein. Manufacturer is not responsible and will not be held liable in contract
or in tort (including negligence) for any special, indirect or consequential damages,
including injury or damage caused to vehicles, contents or persons, by reason of the
installation of any Thermo King product or its mechanical failure.
Recover Refrigerant
At Thermo King, we recognize the need to preserve the environment
and limit the potential harm to the ozone layer that can result from
allowing refrigerant to escape into the atmosphere.

We strictly adhere to a policy that promotes the recovery and limits


the loss of refrigerant into the atmosphere.

In addition, service personnel must be aware of Federal regulations


concerning the use of refrigerants and the certification of technicians.
For additional information on regulations and technician certification
programs, contact your local Thermo King dealer.

R-134a/R-404A
WARNING: Use only Polyol Ester-based refrigeration compressor oil in
R-134a/R-404A units. See Thermo King Parts Manual for part number.
Do not mix Polyol Ester and standard synthetic compressor oils. Keep Polyol
Ester compressor oil in tightly sealed containers. If Polyol Ester oil becomes
contaminated with moisture or standard oils, dispose of properly–DO NOT USE.
When servicing Thermo King R-134a or R-404A units, use only those service
tools certified for and dedicated to R134a/R-404A refrigerant and Polyol Ester
compressor oils. Residual non-HFC refrigerants or oils will contaminate R-134a
and R-404A systems.
Table of Contents

Table of Contents
Table of Contents ................................................1 Alarms ................................................................. 29
About This Manual ..............................................3 Manual Start: ................................................ 29
Safety Precautions ..............................................5 Auto Start: .................................................... 29
General Practices .................................................5 Buzzers ........................................................ 30
Auto Start/Stop ......................................................5 Alarm Code Descriptions .................................... 30
Refrigerant ............................................................5 Clearing Alarm Codes ......................................... 31
First Aid ..........................................................5 Viewing Information Screens .............................. 31
Refrigeration Oil ....................................................6 Main Menu .................................................... 31
First Aid ..........................................................6 Hourmeter Menu .......................................... 31
Electrical Hazards .................................................6 Post-Start Inspection .......................................... 31
Microprocessor Service ..................................6 Loading Procedure ............................................. 31
Welding of Units or Truck Bodies ...................7 Procedure after loading ...................................... 31
High Voltage ...................................................7 Maintenance Inspection Schedule .................. 33
Low Voltage ....................................................8 Electrical ............................................................. 33
Specifications ......................................................9 Refrigeration/Heating .......................................... 33
Electrical System ..................................................9 Structural ............................................................ 33
Refrigerant System .............................................10 Electrical Maintenance ..................................... 35
Compressors .......................................................10 Maintenance Inspection Schedule ...................... 35
AC Semi-Hermetic Compressor ..........................11 Defrost System ................................................... 35
Solder Applications .............................................11 Liquid Injection System (R-404A Units Only) ...... 36
General Description ..........................................13 Testing Liquid Injection Solenoid Valve
Introduction .........................................................13 and Metering Orifice ..................................... 36
Standard Features ..............................................13 Electric Standby Circuits ..................................... 36
Optional Features ...............................................13 Refrigeration Maintenance ............................... 37
Condenser ..........................................................13 Maintenance Inspection Schedule ...................... 37
Evaporator ..........................................................13 Recharging the Refrigeration System .......... 37
Compressor ........................................................13 Checking the Refrigerant Charge ................. 38
Control Circuits ...................................................14 Checking Compressor Oil Charge ...................... 39
Electronic Control System ...................................14 High Pressure Cutout Switch (HPCO) ................ 39
Oil Separator .......................................................15 Low Pressure Cutout Switch (LPCO) ................. 40
Refrigerant ..........................................................15 Cleanup Procedure for Small Truck Units .......... 40
Liquid Injection System .......................................15 Compressor/Clutch Maintenance .................... 43
Evaporator Drain Tube Heaters ..........................15 Handling instructions .......................................... 43
Electric Standby Operation .................................15 Refrigerant Handling-Safety ......................... 43
Protection Features .............................................16 Refrigerant Recovery ................................... 43
Control Box .........................................................16 Compressor Handling ................................... 44
P.C. Board ....................................................16 Compressor Removal ................................... 44
Connectors ...................................................16 Installation Guidelines for Compressors ....... 45
Electronic Control Module (ECM) .................16 Installation Precautions ................................ 45
Unit Operation .....................................................20 Checking the Compressor Oil for
Operation ............................................................20 Contamination .............................................. 46
Cool Mode Operation ...................................20 System Compressor And Oil ........................ 46
Serial Number Locations .....................................21 Checking the Oil Level ................................. 47
Unit Components ................................................22 Oil Contamination ......................................... 48
Operating Instructions .....................................27 Magnetic Clutch Run In. ............................... 49
Starting the Unit ..................................................27 Leak Test Procedure .................................... 49
Engine Operation ..........................................27 Clutch Test ................................................... 50
Electric Standby Operation ...........................27 Compressor Clutch Removal ....................... 50
Standard Display ..........................................27 Inspection ..................................................... 52
Single-temperature Units ..............................28 Clutch Installation ......................................... 52
Multi-temperature Units ................................28 Shaft Seal Cover And Shaft Seal:
Entering the Setpoint Temperature .....................28 Removal And Installation .............................. 54
In Single-temperature Units: .........................28 Cover Installation (When Equipped) ............. 56
In Multi-temperature Units ............................28 Front And Rear Cylinder Heads ................... 57
Initiating the Manual Defrost Cycle ...............29 Inspection ..................................................... 58

1
Table of Contents

Reassembly ................................................. 59
Belt Tensions ...................................................... 62
Engine Driven Compressor Belt and Pulleys 62
Structural Maintenance .................................... 63
Maintenance Inspection Schedule ...................... 63
Evaporator Coil ................................................... 63
Condenser Coil ................................................... 63
Unit Mounting Bolts ............................................ 63
Over-the-Road Mechanical Diagnosis ............ 65
Electric Standby Mechanical Diagnosis ......... 67
Electric Standby Service Checks ........................ 69
Refrigeration Diagnosis Chart ......................... 73
Wiring, Refrigeration and Schematic
Diagrams Index ................................................. 75

2
About This Manual

Purpose
The purpose of this manual is to provide general maintenance information necessary to maintain the
climate control unit at peak operating standards. This includes system and bill of material numbers, safety
information, general unit information, maintenance procedures and related information (such as wiring
and schematic diagrams), and some diagnostic and troubleshooting information.
This manual may cover more than one unit. Therefore, it may contain information not applicable to your
unit.

Contents
This manual is organized into the following chapters:

Chapter Purpose
Safety Precautions Provides detailed safety information. You should be familiar with the
safety precautions before working on any unit.
Model Systems (Systems This table lists the bills of material and kit options that apply to the
Designations) Table Thermo King units covered in this manual. Use this information to:
1. Determine if you have the right manual for your unit: the bill of material
(B/M) number on your unit serial plate should match one of the bill of
material numbers listed in this section. If you cannot find your unit in the
table, call TK Service for more information.)
2. Communicate with TK Service Department: If you need to call TK
Service, you must know your model number so that the service
representative can help you.
Specifications Lists unit specifications.
Unit Description Gives an overview description of the unit including standard and optional
features, general information, and unit photographs or illustrations.
Operating Instructions Provides unit operating instructions.
Maintenance Inspection Schedule Table of routine maintenance procedures.
Maintenance Chapters Provides detailed maintenance procedures required for your unit.
(Electrical, Refrigeration, Compressor, Clutch, Structural)
Diagnosis Chapters Provides troubleshooting information for diagnosing problems.
Diagrams Includes diagrams such as refrigeration, schematic, and wiring diagrams
applicable to units covered in this manual.

Before you Call Thermo King Service!


Who to call: Your Thermo King Service Representative.
Before you call Thermo King Service, have the following information on hand:
• Bill of Material (usually located on the unit serial plate)
• Model Number - found on side of the unit

Blank Pages
This manual may contain blank pages at the end of chapters. This is normal. There is no information
missing from the manual.

3
About This Manual

Roadside/Curbside Terminology
Roadside/Curbside terminology: These terms can be confusing because of differences between North
America and Europe. Please note:

Curbside: The side to the driver’s right when the driver is in his seat and facing forward.
Roadside: The side to the driver’s left when the driver is in his seat and facing forward.

4
Safety Precautions

General Practices Auto Start/Stop


1. Always wear goggles or safety glasses.
Refrigerant liquid, refrigeration oil, and CAUTION: The unit may start
battery acid can permanently damage the eyes. automatically and at any time when the
unit On/Off switch is in the On position.
2. Never close the compressor discharge service Units with CYCLE-SENTRYTM start
valve with the unit operating. automatically in both CYCLE-SENTRY
3. Never operate the unit with the compressor mode and Continuous mode. Be sure to
discharge valve closed. turn the On/Off switch Off before opening
doors or inspecting or working on any part
4. Keep your hands, clothing and tools clear of of the unit.
the fans and belts when the unit is running.
This should also be considered when opening
and closing the compressor service valves.
Refrigerant
When removing refrigerant from a unit, a
5. Make sure gauge manifold hoses are in good
recovery process that prevents or minimizes
condition. Never let them come in contact
refrigerant loss to the atmosphere is required by
with a belt, fan motor pulley, or any hot
law.
surface.
When a refrigerant is exposed to the atmosphere
6. Never apply heat to a sealed refrigeration
in the liquid state, it evaporates rapidly, freezing
system or container.
anything it contacts. If refrigerant contacts the
7. Fluorocarbon refrigerants in the presence of skin, severe frostbite can result.
an open flame produce toxic gases that are
severe respiratory irritants capable of causing First Aid
death.
In the event of frostbite, the objectives of First
8. Make sure all mounting bolts are properly Aid are to protect the frozen area from further
torqued and are of correct length for their injury, to warm the affected area rapidly and to
particular application. maintain respiration.
9. Use extreme caution when drilling holes in the • Eyes: For contact with liquid, immediately
unit. The holes may weaken structural flush eyes with large amounts of water and get
components, and holes drilled into electrical prompt medical attention.
wiring can cause fire or explosion. Holes
• Skin: Flush area with large amounts of
drilled into the refrigeration system will
lukewarm water. Do not apply heat. Remove
release refrigerant.
contaminated clothing and shoes. Wrap burns
10. Use caution when working around exposed with dry, sterile, bulky dressing to protect
coil fins. The fins can cause painful from infection/injury. Get medical attention.
lacerations. Wash contaminated clothing before reuse.
11. Use caution when working with a refrigerant • Inhalation: Move victim to fresh air and use
or refrigeration system in any closed or cardiopulmonary resuscitation (CPR) or
confined area with a limited air supply (for mouth-to-mouth ventilation if necessary. Stay
example, a truck body or garage). Refrigerant with victim until arrival of emergency medical
tends to displace air and can cause oxygen personnel.
depletion resulting in suffocation and possible
death.
12. When using ladder or scaffolding, use caution
and follow manufacturer recommendations.

5
Safety Precautions

Refrigeration Oil The following procedures must be rigidly adhered


to when servicing units to avoid microprocessor
Observe the following precautions when working damage or destruction.
with or around synthetic or polyol ester refrigerant
oil: 1. Disconnect all power to the unit.
• Do not allow refrigerant oil to contact your 2. Avoid wearing clothing that generates static
eyes. electricity (wool, nylon, polyester, etc.).
• Do not allow prolonged or repeated contact 3. Do wear a static discharge wrist strap (see
with skin or clothing. Tool Catalog) with the lead end connected to
the microprocessor’s ground terminal. These
• To prevent irritation, you should wash straps are available at most electronic
thoroughly immediately after handling equipment distributors. Do not wear these
refrigerant oil. Rubber gloves are straps with power applied to the unit.
recommended when handling polyol ester oil.
4. Avoid contacting the electronic components
First Aid on the circuit boards of the unit being
serviced.
• Eyes: Immediately flush eyes with large
amounts of water for at least 15 minutes while 5. Leave the circuit boards in their static proof
holding the eyelids open. Get prompt medical packing materials until ready for installation.
attention. 6. If a defective controller is to be returned for
• Skin: Remove contaminated clothing. Wash repair, it should be returned in the same static
thoroughly with soap and water. Get medical protective packing materials from which the
attention if irritation persists. replacement component was removed.
• Inhalation: Move victim to fresh air and 7. After servicing the controller or any other
restore breathing if necessary. Stay with circuits, the wiring should be checked for
victim until arrival of emergency personnel. possible errors before restoring power.
• Ingestion: Do not induce vomiting. Contact a 8. Never use testers consisting of a battery and a
local poison control center or physician light bulb to test circuits on any
immediately. microprocessor based equipment.
9. Before connecting or disconnecting the
Electrical Hazards battery, the Microprocessor Power On/Off
switch must be turned to the Off position. It is
Microprocessor Service located on the roadside of the unit, lower left
Precautions must be taken to prevent electrostatic corner.
discharge when servicing the microprocessor
controller and related components. Potential
differences considerably lower than those which
produce a small spark from a finger to a door
knob can severely damage or destroy solid-state
integrated circuit components.

6
Safety Precautions

Welding of Units or Truck Bodies Precautions


When electric welding is to be performed on any 1. Be certain the Unit On/Off switch is turned
portion of the temperature control unit, truck or Off before connecting or disconnecting the
truck chassis when the temperature control unit is standby power plug. Never attempt to stop the
attached, it is necessary to ensure that welding unit by disconnecting the power plug.
currents are not allowed to flow through the
2. Be certain the unit power plug is clean and dry
electronic circuits of the unit.
before connecting it to a power source.
These procedures must be rigidly adhered to when
3. When working on high voltage circuits on the
servicing units to avoid damage or destruction of
temperature control unit, do not make any
the controller.
rapid moves. If a tool drops, do not grab for it.
1. Disconnect all power to the unit. People do not contact high voltage wires on
purpose. It occurs from an unplanned
2. Disconnect all wire harnesses from the
movement.
controller.
4. Use tools with insulated handles that are in
3. Switch all of the electrical circuit breakers in
good condition. Never hold metal tools in
the control box to the Off position.
your hand if exposed, energized conductors
4. Weld unit or container per normal welding are within reach.
procedures. Keep ground return electrode as
5. Treat all wires and connections as high
close to the area to be welded as practical.
voltage until a meter and wiring diagram show
This will reduce the likelihood of stray
otherwise.
welding currents passing through any
electrical or electronic circuits. 6. Never work alone on high voltage circuits on
the temperature control unit. Another person
5. When the welding operation is completed, the
should always be present to shut off the
unit power cables, wiring and circuit breakers
temperature control unit and to provide aid in
must be restored to their normal condition.
the event of an accident.
High Voltage 7. Have electrically insulated gloves, cable
cutters and safety glasses available in the
When servicing or repairing a temperature control
immediate vicinity in the event of an accident.
unit, the possibility of serious or even fatal injury
from electrical shock exists. Extreme care must be
First Aid
used when working with a refrigeration unit that
is connected to a source of operating power, even Immediate action must be initiated after a person
if the unit is not operating. Lethal voltage has received an electrical shock. Obtain
potentials can exist at the unit power cord, inside immediate medical assistance if available.
the control box, at the motors and within the
The source of shock must be immediately
wiring harnesses.
removed by either shutting down the power or
removing the victim from the source. If it is not
possible to shut off the power, the wire should be
cut with either an insulated instrument (e.g., a
wooden handled axe or cable cutters with heavy
insulated handles) or by a rescuer wearing
electrically insulated gloves and safety glasses.
Whichever method is used do not look at the wire
while it is being cut. The ensuing flash can cause
burns and blindness.

7
Safety Precautions

If the victim must be removed from a live circuit,


pull the victim off with a non-conductive material.
Use the victim’s coat, a rope, wood, or loop your
belt around the victim’s leg or arm and pull the
victim off. Do not touch the victim. You can
receive a shock from current flowing through the
victim’s body. After separating the victim from
the power source, check immediately for the
presence of a pulse and respiration. If a pulse is
not present, start CPR (Cardiopulmonary
Resuscitation) and call for emergency medical
assistance. If a pulse is present, respiration may be
restored by using mouth-to-mouth resuscitation,
but call for emergency medical assistance.

Low Voltage
Control circuits used in the temperature control
unit are low voltage (12 and 24 Vdc). This voltage
potential is not considered dangerous, but the
large amount of current available (over 30 amps)
can cause severe burns if shorted or ground.
Do not wear jewelry, watch or rings when
working on the unit. If these items contact an
electrical circuit, severe burns may result.

8
Specifications

Electrical System
Fuses 12 Volt 24 Volt
Fuse 1: Power Supply Circuit 5 amps 5 amps
Fuse 2: Condenser Fan Motor (CFM1) 15 amps 10 amps
Fuse 3: Evaporator Fan Motor (EF1) 15 amps 10 amps
Fuse 4: Evaporator Fan Motor (EF2) 15 amps 10 amps
Fuse 5: Compressor Clutch 1 (CCL1), Liquid Injection Switch (LIS), 20 amps 10 amps
Liquid Injection Valve(LIV), Host Defrost Hot Solenoid Valve (PS1),
Compressor otor Contactor (CMC), Heat Pilot Solenoid (PS5),
Compressor Clutch 2 (CCL2)
Fuse 6: Condenser Fan 1, 2 (CF1, CF2) Heater 1, Heater 2 (HT1, 10 amps 7.5 amps
HT2)
Fuse 7: Condenser Fan Motor (CFM2) 15 amps 10 amps
Fuse 8: Remote Liquid Solenoid Valve (PS2), Host Liquid Solenoid 20 amps 10 amps
Valve (PS3), Remote Defrost Hot Gas Solenoid Valve (PS4)
Fuse 9: Evaporator Fan Motor (EF3) 15 amps 10 amps
Fuse 10: Evaporator Fan Motor (EF4) 15 amps 10 amps
Fuse 11: Heaters 10 amps 7.5 amps
Fuse 20: Transformer 4 amps 4 amps
Fuse 21: Battery Relay 15 amps 15 amps
Condenser Fan Motors
Voltage Full Load rpm Full Load Current
13 Vdc 3000 9.2 Amps
Evaporator Fan Motors
Voltage Full Load rpm Full Load Current
13 Vdc 2700 6.2 Amps
Coils for Hot Gas Solenoids, Condenser Solenoids, and Liquid Line Solenoids
Voltage Current Resistance
12 Vdc 2.3 amps 5.2 ohms

9
Specifications

Refrigerant System
R-134A REFRIGERATION SYSTEM (V-520)
Refrigerant Charge V-520 7.93 lbs (3.6 kg) R-134a
Defrost Termination Switch: Opens 48.0 ± 5.4 F (8.9 ± 3.0 C)
Closes 36.0 ± 5.4 F (2.2 ± 3.0 C)
High Pressure Transducer: Opens 300 ± 10 psi (2068 ± 69 kPa)
Closes 200 ± 20 psi (1378 ± 69 kPa)
Low Pressure Cutout: Opens 5 to 11 in. Hg vacuum (-17 to -34 kPa)
Closes 4 to 7 psi (28 to 48 kPa)
Condenser Fan Speed Control (CFSC) Pressure Cutout Switch:Opens 200 ± 7 psi (1379 ± 48 kPa)
Closes 160 ± 7 psi (1103 ± 48 kPa)
R-404A REFRIGERATION SYSTEM (V-520 Max)
Refrigerant Charge V-520 Max 8.15 lbs (3.7 kg) R-404A
Defrost Termination Switch: Opens 48.0 ± 5.4 F (8.9 ± 3.0 C)
Closes 36.0 ± 5.4 F (2.2 ± 3.0 C)
Liquid Injection Switch: Opens 200 ± 5 F (93 ± 3 C)
Closes 230 ± 5 F (110 ± 3 C)
High Pressure Transducer: Opens 450 ± 10 psi (3100 ± 69 kPa)
Closes 375 ± 10 psi (2585 ± 69 kPa)
Low Pressure Cutout: Opens 5 to 11 in. Hg vacuum(-17 to -34 kPa)
Closes 4 to 7 psi (28 to 48 kPa)

Compressors
Main Compressor TM-16XD, Engine Driven, Swash Plate,
6 Cylinder
Electrical Compressor D211Y, Reciprocating, 3 Cylinder,
System Oil Capacity Main: 5.1 oz (150 cc)
Standby Operation: 40.1 oz (1200 cc)
Compressor Oil Type Polyol Ester P/N 203-515
Defrost Method: Hot gas
Defrost Timer: Initiation Interval Adjustable, 1 hour to 10 hours
Termination Interval Termination is not timed.
Defrost is terminated by Klixon switch.
CAUTION: Failure to use correct Thermo King recommended oil will invalidate your warranty.

Belt Tension (Using Tool P/N 204-427)


Field Reset
Engine Driven Compressor Belt Check vehicle manufacturer specifications

10
Specifications

AC Semi-Hermetic Compressor
Full Load Locked Rotor
Voltage/Phase/Frequency Horsepower Kilowatts RPM
(Amps) Amps
230V/3PH/60Hz 2 1.5 1730 14.1 86.9
230V/1PH/60Hz 2 1.5 1730 16.0 83.2
230V/400V/3PH/60Hz 2 1.5 1730 14.1 51.7
400V/3PH/50Hz/60Hz 2 1.5 1450 11.8 43.1

Electric Standby Power Requirements


Supply Circuit Breaker 20 amp
Extension Cord Size 25 ft - 10 gauge, up to 75 ft - 8 gauge

Electric Heaters
Voltage Power Rating Watts Current Resistance
208/230 2000 14.7 Amps 16.2 ohms at 230 V

Solder Applications
Refrigeration Component
For general refrigeration tubing connections: Joint Clearances: 0.003 to 0.005 in. (0.076 to 0.127 mm)
copper to copper or copper to brass
Use: Solder Type 15% Silver TK No. 203-364 Use: Flux
Type TK No. 203-365
For refrigeration tubing connections of dissimilar Joint Clearances: 0.003 to 0.005 in. (0.076 to 0.127 mm)
metals: copper to stainless steel or brass to Use: Solder Type 35% Silver TK No. 203-366 Use: Flux
stainless steel Type TK No. 203-365

Hot Water Component


For hot water tubing connections: copper to Joint Clearances: 0.003 to 0.005 in. (0.076 to 0.127 mm)
copper or copper to brass
Use: Solder Type 95% Tin and 5% antimony
TK No. 204-167 Use: Flux Type TK No. 204-417
For hot water tubing connections of dissimilar Joint Clearances: 0.003 to 0.005 in. (0.076 to 0.127 mm)
metals: copper to stainless steel or brass to
Use: Solder Type 35% Silver TK No. 203-366 Use: Flux
stainless steel
Type TK No. 203-365

NOTE: Some units may be equipped with an compressor pressure regulating valve (CPR). To reduce the
chance of overheating the CPR valve, 95-5 solder or equivalent may be used.
Use 95-5 TK No. 204-167
Use Flux TK No. 204-417

11
Specifications

12
General Description

Introduction Standard Features


The Thermo King V-520 10/20 and V-520 MAX • In-cab Controls with digital LCD thermometer
truck refrigeration systems are two piece units.
• Hot Gas Defrost (Standard)
They are designed for medium-sized trucks and
vans carrying fresh produce and frozen and deep • Manual Defrost Switch (Standard)
frozen goods.
• Oil Separator (Standard)
The system condenser is mounted on the front of
• Liquid Injection
the truck box or container. The system evaporator
is mounted on the cargo compartment ceiling. The • Main Compressor TM 16 XD
main compressor is powered by the vehicle engine
via a belt. The unit is connected to the compressor Optional Features
by refrigeration hoses. In electric standby
operation models, the second compressor is • Electric Compressor, Model 20
driven by an elecric motor. • Evaporator Drain Heaters, Max Units
Control circuits operate on 12 and 24 VDC • Electric/Hot Water Heat, Model 20
supplied by the truck batteries for over-the-road
operation. The refrigeration system is protected • Hot Water Heat, Model 10
by a high pressure cutout and a low pressure
cutout. Condenser
The operating mode is selected automatically: The condenser has a unique design that allows it
When the unit is connected to an electric power to be mounted horizontally on the roof, or on the
source, engine-driven operation is automatically front of the truck box.
blocked. If the vehicle engine is started up while
the power cable is still connected to the electric Evaporator
power source, the unit will continue to operate in
electric standby mode. It is not possible to start An evaporator is mounted on the ceiling inside the
the engine-driven compressor until the power truck box.
cable is disconnected from the unit.
There are two basic models: Compressor
• Model 10: Cool and defrost on truck engine Refrigeration hoses or lines are used to connect
driven compressor operation. the condenser, the evaporator, the main
compressor and any other refrigeration
• Model 20: Cool and defrost on both truck components.
engine driven compressor operation and
electric standby compressor operation. Model 20 units have another compressor and an
electric motor mounted in the condenser section
for electric standby operation. The electric
standby compressor is connected in parallel with
the engine-driven compressor. The standby
compressor is driven by a belt from the electric
motor.
Both compressors use the same refrigeration
system circuit. Check valves isolate one
AMA1003 compressor from the other during operation.
Compressor operation is controlled by the
thermostat, which energizes the compressor clutch
Figure 1: V-520 Condenser Unit during engine operation or starts the electric

13
General Description

motor and energizes the compressor clutch on • Low Battery Voltage Alarm
electric standby operation. The refrigeration
• Buzzer
system is protected by a high pressure cutout
switch and a low pressure cutout switch. • Unit Control without In-cab Control Box
When plugged into standby power, engine • Manual or Automatic Defrost
operation is automatically locked out. If the truck
• Maintenance Warning
engine is turned on while the power cord is still
plugged into a power receptacle, the unit will • Return Air Temperature Sensor
remain working in electric mode; the engine
• Setpoint Temperature Reading
driven compressor cannot be started until the
power cord is unplugged from the unit as the • Electric Power Warning
selection of engine operation or standby operation Auto Start: Should the unit stop due to a failure in
is automatic. the power supply, whether during on-the-road or
electric standby operation, it will start up again as
Control Circuits soon as the power supply is re-established.
The control circuits operate on 12V supplied by Soft Start:All operation modes remain inactive
the truck batteries for engine operation. On for 15 seconds after an Auto Start.
standby operation, the power is rectified from an Active Display: The In-cab Control Box display is
AC transformer. always active and backlit except when the unit is
disconnected (no power) or when the unit is
Electronic Control System connected but has been manually switched off
from the In-cab Control Box (when there is no
The Electronic Control System is composed of an active alarm).
Electronic Control Module (located inside the
condenser unit) and the In-cab Control Box. This Lit Keypad: The In-cab Control Box keys are
In-cab Control Box allows the truck driver to always lit except when the unit is disconnected
operate the Thermo King refrigeration unit. (no power) or when the unit is connected but has
been manually switched off from the In-cab
Control Box (when there is no active alarm). The
On/Off key is always lit except when the unit is
disconnected (no power), and thus indicates the
presence of power in the unit.
Total Hourmeter: Total number of hours the unit is
ASA246
in operation.
Vehicle Compressor Hourmeter: Number of hours
Figure 2: In-cab Control Box
the unit has been operating on-the-road.
The Electronic Control System has the following Electric Standby Compressor Hourmeter:
characteristics:
Number of hours the unit has been operating in
• Auto Start electric standby.
• Soft Start Low Battery Voltage Alarm: Disconnects the unit
when the battery voltage falls below 10.5V in
• Active Display 12VDC systems or below 21V in 24VDC
• Lit Keypad systems.
• Total Hourmeter Buzzer: It is energised when the vehicle battery
and the electric power supply are connected at the
• Vehicle Compressor Hourmeter same time. It is also energised if the doors are
• Electric Standby Compressor Hourmeter opened while the refrigeration unit is running.

14
General Description

Unit Control without In-cab Control Box: The unit Liquid Injection System
can also be operated by the Electronic Control
System without the In-cab Control Box, under V-520 MAX units use R-404A and have a liquid
conditions selected by the In-cab Control Box injection system to limit discharge temperature of
before it is disconnected. the engine driven compressor. If the discharge gas
leaving the compressor reaches a temperature of
Manual or Automatic defrost:It is possible to 230 ± 5 F (110 ± 3 C) the liquid injection switch
choose between manual or automatic defrost. closes, providing voltage to the liquid injection
Maintenance Warning: On-screen warning of the solenoid. The solenoid opens a valve, allowing
need to carry out maintenance on the unit. liquid refrigerant to flow from the liquid line near
Return Air Temperature Sensor: On-screen the drier inlet to the metering orifice attached to
reading of the temperature in the load the suction line fitting on the engine driven
compartment. In multi-temperature units, the compressor. As the refrigerant passes through the
temperature in both compartments can be read on metering orifice it expands and evaporates,
the same screen. cooling the suction gas entering the compressor.
This cooling effect is transferred to the discharge
Setpoint Temperature Reading: On-Screen gas leaving the compressor from the adjacent
Setpoint Temperature Reading. In cavity in the compressor head. When the
multi-temperature units, the setpoint temperature discharge gas is cooled to 200 ± 5 F (93 ± 3 C),
of both compartments can be read on the same the liquid injection switch opens, the liquid
screen. injection solenoid closes and refrigerant no longer
Electric Power Warning: On-screen warning that flows through the liquid injection system.
the unit is connected to an electric power supply.
Evaporator Drain Tube Heaters
Oil Separator Evaporator heaters are used in R-404A units to
An oil separator is a standard feature. The oil avoid drain tube blockage because of ice
separator separates compressor oil from accumulation inside the evaporator. Two
refrigerant vapor and returns the oil to the harnesses are located inside the drain tube. These
compressor through the suction line. The oil resistive wires melt the ice while the unit is in
separator helps provide positive oil return at high DEFROST mode.
compressor speeds and low operating
temperatures. This feature enhances compressor Electric Standby Operation
lubrication and extends compressor life.
During electric standby operation, the thermostat
controls the operation of the unit by energizing
Refrigerant and de-energizing the power relay, the electric
• V-520-10 and V-520-20 units use R-134a relays, and the heat contactor. The thermostat
refrigerant. places the unit in cool by energizing the power
• V-520 MAX-10 and V-520 MAX-20 units use relay and the electric relays.
R-404A refrigerant. The thermostat places the unit in null by
de-energizing all the relays and contactors. The
thermostat places the unit in heat by energizing
the heat contactor.
When the power relay and the electric relays are
energized, they close contacts that energize the
fan relay, the motor contactor, and the electric
standby compressor clutch.
When the heat contactor is energized, it energizes
the electric evaporator heaters and the fan relay.

15
General Description

Protection Features Electronic Control Module (ECM)


The ECM can be configured with only one printed circuit board
• High Pressure Transducer - The High Pressure (PCB1). This configuration (PCB1 only) is known as Platform1.
Cut Out Transducer is a pressure sensitive
device. It is located in the discharge line near
the oil separator on Model 10 units. It is
located in the discharge check valve on Model
20 units.
If the discharge pressure rises above the
transducer’s opening pressure, the transducer
opens the circuit to the PR Relay to stop the
unit.
For units with R-134a: the HPCO Transducer
opens at 300 PSIG and shuts down the unit. ECM Platform1
The HPCO closes when the pressure drops to 1 Connector 1 PCB1
200 PSIG. 2 Connector 2 PCB1
For units with R-404A: the HPCO Transducer The ECM can also be configured to contain a small printed circuit
opens at 450 PSIG and shuts down the unit. board (PCB2) mounted on top of PCB1. This configuration is
known as Platform2.
The HPCO Transducer closes when the
pressure drops to 375 PSIG.
• Low Pressure Cutout Switch - The Low
Pressure Cutout Switch is a pressure sensitive
switch located in the suction line. If the
pressure falls below 5 to 11 in. Hg vacuum
(-17 to -34 kPa), the switch opens the circuit
to the PR Relay to stop unit operation.

Control Box
ECM Platform2
P.C. Board
1 Connector 1 PCB1
All Printed Circuit Boards manufactured by 2 Connector 2 PCB1
Thermo King can be easily identified by the Part 3 Connector 1 PCB2
Number stamped on them. 4 Connector 2 PCB2

Connectors
All connector codes (C-1, C-2, etc.) are stamped
on the P.C. Board. Pins on the connectors are
numbered counter-clockwise.

16
General Description

Printed circuit board PCB1

Connectors RY3. When energized, connects AC motor to standby operation


(CMC).
CN1. Connector 1.
RY4. Controls hot gas solenoid valve (PS1).
CN2. Connector 2.
RY5. Controls condenser solenoid valve (PS5, heat option).
CN. PCB2 union connector.
RY6. When energized, starts condenser fan motor (CFM1).
CN6-1. Control module fan connector.
RY7. When energized, starts evaporator fan motor (EFM1).
Fuses
RY8. When energized, starts evaporator fan motor (EFM2).
F1: Fuse 1. Protects the printed circuit board (PCB1) from
RY9. Controls:
possible overloads.
Condenser fan motors (CFM1, CFM2).
F2: Fuse 2. Protects condenser fan motor (CFM1) from possible
overload.
Sensors
F3: Fuse 3. Protects evaporator fan motor (EFM1) from possible
PT2: Temperature Sensor. Protects control module from
overloads.
possible temperature overload.
F4: Fuse 4. Protects evaporator fan motor (EFM2) from possible
overloads.
F5: Fuse 5. Protects:
Engine compressor clutch coil (CCL1)
Standby compressor clutch coil (CCL2).
Liquid injection switch (LIS, MAX only).
Liquid injection valve coil (LIV, MAX only).
Hot gas solenoid valve coil (PS1).
AC power supply compressor motor contactor coil (CMC).
Hot gas solenoid valve coil (PS5, heat option).
F6: Fuse 6. Protects: Condenser fan motors (CF1, CF2).

Relays
RY1. When energised, starts the engine compressor clutch
(CCL1), liquid injection switch (LIS, MAX only), and liquid
injection valve (LIV, MAX only).
RY2. When energized, starts standby compressor clutch (CCL2).

17
General Description

Printed circuit board PCB2

Connectors STANDBY OPERATION FUSES


CN1. Connector 1. F20. Fuse 20: Located in the electrical panel. Protects the
CN2. Connector 2. transformer from possible overloads.

CN3. PCB1 Union connector. F21. Fuse 21: Located in the engine compartment. Protects the
vehicle battery from possible overloads.

Fuses
STANDBY OPERATION RELAYS
F7: Fuse 7. Protects condenser fan motor (CFM2) from possible
overloads. BATR. Battery Relay: When energized, unit is powered by
battery.
F8: Fuse 8. Protects:
STDR. Electrical power relay: When energized, unit is fed by
Remote evaporator liquid line solenoid valve coil (PS2). electrical system wires.
Main evaporator liquid line solenoid valve coil (PS3). C1R. Switching relay: When energized, disconnects BATR
Remote evaporator hot gas solenoid valve coil (PS4). battery relay coil feed. This prevents two power supply sources
(battery and alternating current) from being connected to the unit
The suction line solenoid valve coil (bypass)
at the same time.
(PS6 V-520 AC only).
OLR. AC motor overload relay: Switches off unit when
F9: Fuse 9. Protects evaporator fan motor (EFM3) from possible
current draw through AC motor is excessive.
overloads.
BATR, STDR, C1R and OLR relays are located in the electrical
F10: Fuse 10. Protects evaporator fan motor (EFM4) from
panel.
possible overloads.
SR. Start relay (single-phase units only): When energised,
F11: Fuse 11. Protects defrost heaters (HT1, HT2).
turns on the start capacitor to start the AC power supply motor.

Relays Contactors
RY10. When energized, starts condenser fan motor (CFM2).
CMC. Compressor motor contactor: When energized, turns
RY11. Controls remote evaporator liquid line solenoid valve on standby compressor’s AC motor.
(PS2).
RY12. Controls main evaporator liquid line solenoid valve (PS3). Clutches
RY13. Controls remote evaporator hot gas solenoid valve (PS4). Vehicle compressor clutch. Energized to activate the
RY14. Controls the suction line solenoid valve (bypass) engine-driven compressor when cooling, heating or defrost
(PS6 V-520 AC only). operation is required.

RY17. When energized, starts evaporator fan motor (EFM3).


RY19. Controls defrost cycle operation (H1, H2).

18
General Description

Standby compressor clutch. Energized to engage the standby


compressor when cooling, heating or defrost operation is required
and optional electric standby is energised.

19
General Description

Unit Operation The unit operates in Cool mode until the setpoint
temperature is reached. The unit then enters Null
Unit Operation Unit operation is fully automatic. mode. When the temperature rises to a
The compressor is turned on by the vehicle engine pre-determined number of degrees, the unit
at startup. Standard units operate in Cool mode or restarts in Cool mode.
Null mode, as required, to maintain the load
compartment temperature at the setpoint V-520 units only have a triple-cooling capacity
temperature. Defrost cycles occur manually or (TCC) feature that energizes condenser fans CF1
automatically, as required. and CF2 at low, medium, and high refrigerant
pressures. Controlled by the high pressure (HP)
If power is shut off, the unit comes back in Null transducer, the applicable relays (RY6, RY9,
mode when the unit is restarted. There is a RY10) remain closed or are opened, and operate
momentary delay at auto start-up for circuit the condenser fan speeds in the following manner:
protection. For units with Electric Standby, there
are protective delays for the compressor clutch • When HP pressure is less than 180 PSI (low
and electric compressor/electrical motor pressure), RY6, RY9, and RY10 open. CF1
contactor. and CF2 receive no voltage and are in Null
state.
Options
• When the HP pressure is between 180 PSI and
• The Heat option provides heating by hot gas. 300 PSI (medium pressure), RY9 closes. CF1
• The Electric Standby option provides a second and CF2 become connected in series, receive
compressor turned on by an electric motor for low voltage, and operate at low speed
standby applications. • When the HP pressure is greater than 300 PSI
• The TC options provide temperature control (high pressure), RY6 and RY10 close and RY9
for two-compartment systems. opens. CF1 and CF2 become connected in
parallel, receive high voltage, and operate at
high speed.
Operation
The vehicle engine must be running and the unit Cool Mode Operation - Electric Standby
must be turned on. On units with Electric Standby, Units
connect the external power cord and the unit
switches to Electric mode operation. Unit When cooling is required, the outputs of the
operation can be tailored, as required, using microprocessor energize the electric motor
programmable settings that are shown later is this contactor, standby compressor clutch, and
section. evaporator fans. (For units with Electric Standby,
compressor CLU2 and the Compressor Motor
Contactor are energized when the standby input is
Cool Mode Operation high).
Standard Units The condenser fan is also energized. The fan turns
When cooling is required (when there is a on when the condenser fan pressure switch closes,
requirement to lower the evaporator return air and turns off when the condenser fan pressure
temperature in the load compartment), the outputs switch opens.
of the microprocessor energize the compressor The unit operates in Cool mode until the setpoint
clutch and evaporator fans. The condenser fan is temperature is reached. The unit then enters Null
also energized and turns on when the condenser mode. When the temperature rises a
fan pressure switch closes, and turns off when the pre-determined number of degrees, the unit
condenser fan pressure switch opens. restarts in Cool mode.

20
General Description

Null Mode Operation - All Units The unit remains in Defrost mode until the
Defrost Termination Switch setpoint is reached
The unit operates in Null mode when the setpoint
(that is, when the evaporator coil temperature
temperature is reached and cooling (or heating) is
rises to 14°C (58°F), or until the Defrost
not required. All outputs are de-energized. If the
Termination Timer (DTT) count is completed). If
temperature rises a pre-determined number of
the evaporator coil temperature does not rise
degrees, the unit restarts in Cool mode. If the
above 14°C (58°F) within the defrost duration
temperature falls a pre-determined number of
time limit, the microprocessor terminates the
degrees, and a heat option is present, the unit
defrost operation.
restarts in Heat mode.
The startup of the evaporator fans is delayed for
In addition, the evaporator fans (parameter EFc)
several seconds after Defrost mode ends, to
operate during Null mode.
prevent water from the melting ice from being
sprayed on the load.
Heat Mode
If the Heat mode option is present, the unit enters Decrease in
Heat mode when the temperature falls a Temperature
COOL

pre-determined number of degrees below the X C/F above the setpoint

setpoint temperature. When heat is required, the


outputs of the microprocessor energize the NULL
Temperature Setpoint
evaporator fans. (For units with Electric Standby, MODE

compressor CLU2 and the Compressor Motor


X C/F below the setpoint
Contactor are energized when the standby input is Increase in
temperature
high) HEAT

The unit operates in Heat mode until the setpoint


temperature is reached. The unit then enters Null Figure 3: Thermostat Algorithm
mode.
• If the temperature falls a pre-determined Serial Number Locations
number of degrees, the unit restarts in Heat
mode. CONDENSER: Nameplate located on the back
inside wall of condenser frame.
• If the temperature rises a pre-determined
ENGINE DRIVEN COMPRESSOR: Nameplate
number of degrees, the unit restarts in Cool
located on compressor body. The engine driven
mode.
compressor is located in the truck engine
compartment.
Defrost Mode Operation - All Units
STANDBY COMPRESSOR: Nameplate located on
Defrost is initiated automatically by the compressor body. The Standby compressor is
programmable defrost timer, or manually by located inside the Condenser assembly.
means of the In-cab Control Box. If demand
defrost is enabled, a demand defrost cycle occurs,
based on the Defrost Initiation Timer (DIT) and
the Defrost Termination Switch (DK1 or DK2)
being closed. The evaporator coil temperature
must be below 2°C (35°F) to allow defrost.
When defrost is required, the microprocessor
output energizes the hot gas solenoid to supply hot
refrigerant to the evaporator coil. The Defrost
Initiation Timer (DIT) has counted-down its
required time-setting, and the Defrost Termination
Switch (DK1 or DK2) is closed.

21
General Description

Unit Components

10 11 12

9 1

2
8

7 6 5 AMA511

1. Filter-Drier 5. Oil Separator 9. Transformer Cover


2. Liquid Sight Glass 6. Electric Standby Compressor 10. Condenser Fans
3. Liquid Injection Valve 7. Condenser Coil 11. AC Compressor Electric Box
4. Liquid Tank 8. Rectifier Heat Sink 12. Defrost Valve
Figure 4: Unit Components (Model 20)

22
General Description

1
2

AMA1005
AMA1004

1. Electronic Control Module 3. Capacitor Box


(single temp shown)
2. Motor Contactor
Figure 5: Condenser Electric and Capacitor Boxes (Model 20)

23
General Description

4
1

2
AMA513 AMA51

1. Evaporator Fans 3. Temperature Sensor


2. Expansion Valve 4. Defrost Switch
Figure 6: Evaporator

24
General Description

AMA525

4 1

1. Hot Water Heat Defrost Coil 3. High Temperature Limit Switch


2. Electric Heat Element 4. Air Temperature Sensor
Figure 7: Evaporator with Hot Water and Electric Heat Options

25
General Description

26
Operating Instructions
In truck-driven units, temperature control is based Starting the Unit
on two values: The setting (Setpoint) of the
electronic thermostat and the evaporator return Engine Operation
temperature. The difference between these two
temperatures will determine the mode of 1. Start the truck engine.
operation: cool, heat, or null. 2. Press the On/Off switch located in the In-cab
Cool: When the temperature in the load Control Box. The In-cab Control Box display
compartment is higher than the setpoint, the unit will be activated.
runs in cool mode to reduce the evaporator return 3. Check the setpoint, and adjust if necessary.
temperature.
Heat: When the temperature in the load Electric Standby Operation
compartment is lower than the setpoint, the unit
1. Connect the external power supply to the
changes to heat mode to raise the evaporator
electric power receptacle. Ensure that the
return temperature.
power supply is of the correct voltage and
Null: Once the Setpoint Temperature has been phase for the unit.
reached, and while the temperature remains
between X F/C above or below the setpoint, there 2. Press the On/Off switch located in the In-cab
is no demand for transfer of heat or cold, and the Control Box. The In-cab Control Box display
unit runs in null mode. will be activated. The electric symbol will
appear on the screen.
Defrost: After a scheduled period of time in cool
mode, between 1 and 8 hours, the unit runs in this 3. Check the setpoint, and adjust if necessary.
fourth mode of operation to eliminate ice that has NOTE: The operating mode, whether
accumulated in the evaporator coil. Defrost can be engine-driven or electric standby, is selected
initiated automatically or manually. automatically. When the unit is connected to an
electric power source, engine-driven operation is
automatically blocked. If the truck engine is
Decrease in started up while the power cable is still
Temperature
COOL
connected to the electric power source, the unit
X C/F above the setpoint will continue to operate in electric standby mode.

Temperature Setpoint NULL


MODE
Standard Display
This is the display that appears when the ON/OFF
X C/F below the setpoint key is pressed and the unit started. It normally
Increase in
HEAT
temperature displays the return air temperature (of both load
compartments in multi-temperature units) and the
current operating mode with the appropriate
symbol.
Factory setting for X is 5 F (3 C). During unit
installation, this value can be adjusted by between Should there be an alarm, the alarm symbol will
2 and 9 F (1 and 5 C) in increments of 1 F/C. also appear on screen.
Units with R-134a refrigerant:
Temperatures can be controlled from -8 F to +71 F
(-22 C to +22 C ).
Units with R-404A refrigerant:
Temperatures can be controlled from -26 F to +71
F (-32 C to +22 C).

27
Operating Instructions

Single-temperature Units 2. Press the UP or DOWN arrow keys to select


the desired Setpoint Temperature. Each time
either of these buttons is pressed and released,
the Setpoint Temperature will change 1
degree.
3. Press and release the SELECT key, and the
Standard Display will reappear on screen.
Figure 8: Single-temperature Units
IMPORTANT: If the SELECT key is not pressed
The example in the drawing shows: 10.8 C within 20 seconds to select the new Setpoint
temperature, cool mode and standby operation. Temperature, the unit will continue to run at the
original Setpoint Temperature.
Multi-temperature Units
In Multi-temperature Units

Figure 9: Multi-temperature Unit

The example in the drawing shows: -10 C Figure 11: Multi-temperature Units
temperature and cool mode in the main 1. Main Load Compartment: Press and release
compartment, and 2 C temperature and heat mode the SELECT key twice, and the current
in the remote compartment. Unit running in Setpoint Temperature in the main
on-the-road mode. compartment and the letters SP will appear on
screen.
Entering the Setpoint 2. Press the UP or DOWN arrow keys to select
Temperature the desired Setpoint Temperature. Each time
either of these buttons is pressed and released,
The Setpoint Temperature can be quickly and the Setpoint Temperature will change 1
easily changed. degree.

In Single-temperature Units: 3. Press and release the SELECT key to change


to the Remote Compartment Setpoint
Temperature Setting Screen.
IMPORTANT: If the SELECT key is not pressed
within 20 seconds to select the new Setpoint
Temperature, the unit will continue to run at the
original Setpoint Temperature.
Figure 10: Single-temperature Units 4. Remote Load Compartment: The present
Setpoint Temperature in the remote
1. Press and release the SELECT key twice, and
compartment and the letters SP2 will appear
the current Setpoint Temperature and the
on screen.
letters SP will appear on screen.

28
Operating Instructions

DEFROST symbol will appear when the


defrost cycle begins (the klixon must be
closed).

5. Press the UP or DOWN arrow keys to select


the desired Setpoint Temperature. Each time
either of these buttons is pressed and released,
the Setpoint Temperature will change 1 Figure 14: Defrost Symbol in Display
degree.
6. Press and release the SELECT key, and the Alarms
Standard Display will reappear on screen.
When the unit is not operating properly, the
IMPORTANT: If the SELECT key is not pressed microprocessor records the alarm code, alerts the
within 20 seconds to select the new Setpoint operator by displaying the ALARM symbol and,
Temperature, the unit will continue to run at the depending on the type of alarm, shuts the unit
original Setpoint Temperature. down.
There are three alarm categories:
Initiating the Manual Defrost Cycle
CAUTION: Before initiating a manual defrost, Manual Start:
ensure that the unit is not already in a defrost
cycle. When the unit is in a defrost cycle the The alarm stops the unit, and only the ALARM
defrost symbol appears on screen. symbol appears on screen.
1. Press and release the SELECT key once, and
the letters dEF will appear (flashing) on screen
along with the present defrost condition OFF.

Figure 15: Manual Start

Once the alarm condition has been rectified, the


ON/OFF key must be pressed to start up again.
Figure 12: Defrost Condition Off
Press and release the SELECT key to display the
2. To activate manual defrost, press the ENTER current alarm code on screen. If there is more than
key and then the UP or DOWN key and the one active alarm, all the alarm codes on the unit
defrost condition will change to ON. can be viewed in sequence by pressing and
releasing the SELECT key.

Auto Start:
The alarm stops the unit, the ALARM symbol
appears on screen and the unit starts up
automatically once the alarm condition has been
Figure 13: Defrost Condition On rectified.
3. Press the SELECT key twice to return to the
STANDARD DISPLAY (three times in
multi-temperature units), where the

29
Operating Instructions

Alarm Code Descriptions


Alarm Description
Manual Start
OL Electric Motor Overload.
Unit protection system during electric standby
Figure 16: Auto Start operation. If the problem persists when the
unit is restarted, contact your Service Dealer.
Should a P1E alarm occur - return air temperature
bAt Low Battery Voltage. Unit and battery
read error alarm code - appear, --- will appear on protection system.
screen together with the alarm symbol, instead of
the return air temperature reading. Auto Start
HP High Pressure Alarm. Indicates that the
refrigeration system will shut down in the
event of excessively high pressure in the
refrigerant circuit. If the problem persists
when the unit is restarted, contact your
Service Dealer.
LP Low Pressure Alarm. Indicates that the
Figure 17: P1E Alarm refrigeration system will shut down in the
event of excessively low pressure in the
In multi-temperature units, should a P2E - return refrigerant circuit. If the problem persists
air temperature read error in the remote when the unit is restarted, contact your
compartment alarm code - appear, --- will also Service Dealer.
appear on screen together with the alarm symbol, PSE High Pressure Sensor Failure.
instead of the remote compartment return air The high pressure sensor has become faulty
temperature reading. or disconnected. Contact your Service
Dealer.
tEP Thermal protection alarm. If the problem
persists when the unit is restarted, contact
your Service Dealer
dr1, dr2 Doors Open. This option must be activated.
tCO Control Module Overheating. If the problem
(Hot) persists when the unit is restarted, contact
Figure 18: P2E Alarm your Service Dealer.
SOF Software failure. Contact your Service
Press and release the SELECT key to display the Dealer.
current alarm code on screen. If there is more than
P1E Main or Single Cargo Box Return Air
one active alarm, all the alarm codes on the unit
Temperature Reading Error (open circuit or
can be viewed in sequence by pressing and short-circuit). Contact your Service Dealer.
releasing the SELECT key.
P2E Remote Cargo Box Return Air Temperature
Reading Error (open circuit or short-circuit).
Buzzers Contact your Service Dealer.
They are energized when the vehicle battery and C Communications Failure. Contact your
the electrical supply are connected simultaneously Service Dealer.
(the unit continues running in standby mode).
They are also energized if the doors open, if this
option is selected.

30
Operating Instructions

Clearing Alarm Codes Defrost: When the unit has finished pre-cooling
the truck interior - the evaporator temperature
The alarm condition in the unit must first be should have dropped below 2 C (35.6 F) - initiate
corrected. After clearing the alarm condition, a defrost cycle with the manual defrost switch.
press and release the SELECT key to remove The defrost cycle should stop automatically.
existing ALARM codes. The standard display will
appear once the ALARM codes have been
cleared. Loading Procedure
1. To minimize frost accumulation in the
Viewing Information Screens evaporator coil and a heat increase inside the
load compartment, ensure that the unit is OFF
Main Menu before opening the doors. (The unit may
continue to run when the truck is being loaded
From the Standard Display use the SELECT key in a warehouse with the doors closed.)
to display:
2. Carefully check and record the load
1. Alarms (if any active) temperature when loading the truck. Note
2. Manual Defrost whether any products are out of temperature
range.
3. Temperature Setpoint
3. Load the product in such a way that there is
Hourmeter Menu sufficient space for the air to circulate
throughout the load. DO NOT block the
From the Standard Display press the SELECT evaporator inlet or outlet.
key for 3 seconds to open the Hourmeter Menu,
then use the SELECT key to display: 4. Product should be pre-cooled before loading.
Thermo King units are designed to maintain
1. HC: Hours remaining to maintenance notice. the load at the temperature at which it is
2. tH: The total amount of time the unit has been loaded. Transport refrigeration units are not
switched on protecting the load. designed to reduce the load temperature.

3. CC: Engine-driven compressor operating


hours. Procedure after loading
1. Ensure that all doors are closed and locked.
4. EC: Electric standby compressor operating
hours. 2. Adjust the thermostat to the desired
temperature setpoint.
5. Return to Main Menu.
3. Start the unit.
Post-Start Inspection 4. Half an hour after loading the truck, defrost
Thermostat: Adjust the thermostat setting to the unit for a moment by pressing the Manual
above and below the compartment temperature to Defrost switch. If the coil temperature drops
check thermostat operation (see Operating to below 2 C (35.6 F), the unit will defrost.
Modes). The defrost cycle should stop automatically.
Pre-cooling: With the thermostat set at the desired
temperature, run the unit for half-an-hour to one
hour (or longer if possible) before loading the
truck. Pre-cooling eliminates residual heat and
acts as a good test of the refrigeration system.

31
Operating Instructions

32
Maintenance Inspection Schedule
NOTE: Thermo King reserves the right to deny NOTE: See the appropriate chapter in this
warranty coverage on claims due to lack of maintenance manual for instructions on how to
maintenance or neglect. Claims in question must correctly perform required maintenance.
be supported by maintenance records.

Electrical
Semi-
Weekly Monthly Annual Annually Check condition of or service the following:
• • Check defrost initiation and termination.
• • Check thermostat cycle sequence.
• • Check operation of protection shutdown circuits.
• Check thermostat and thermometer calibration in 0 C (32 F)
ice-water bath.
• Inspect wire harness for damaged wires or connections.
• • Check defrost initiation and termination.

Refrigeration/Heating
Semi-
Weekly Monthly Annual Annually Check condition of or service the following:
• • Check refrigerant level.
• Replace dehydrator.

Structural
Semi-
Weekly Monthly Annual Annually Check condition of or service the following:
• • • • Visually inspect unit and refrigerant hoses for fluid leaks.
• • • • Visually inspect unit for damaged, loose or broken parts.
• • • • Clean defrost drains.
• • • Inspect belts for condition and proper tension
• • • Clean entire unit including evaporator coil and condenser coil.
• • Check all unit mounting bolts, brackets, lines, hoses, etc.

33
Maintenance Inspection Schedule

34
Electrical Maintenance

Maintenance Inspection Schedule


Semi-
Procedures Weekly Monthly Annual Annually
Check defrost initiation and termination. • •
Check thermostat cycle sequence. • •
Check operation of protection shutdown circuits. • •
Check thermostat and thermometer calibration in 0 C •
(32 F) ice-water bath.
Inspect wire harness for damaged wires or •
connections.
Inspect/replace DC fan motor brushes. •

WARNING: Take precautions to ensure the unit will not


accidentally start while you are servicing the system.

Defrost System Defrost initation and termination settings are


accessed through the Guarded Access Menu.
Defrost is initiated automatically by the Refer to the Direct Smart Reefer Diagnostic
programmable defrost timer, or manually by Manual for instructions on the use of Guarded
means of the In-cab Control Box. If demand Access Menu features.
defrost is enabled, a demand defrost cycle occurs,
based on the Defrost Initiation Timer (DIT) and The Defrost Initiation Timer offers programmng
the Defrost Termination Switch (DK1 or DK2) choices of 30 to 480 minutes, increments of 30
being closed. The evaporator coil temperature minutes. The factory setting is 240 minutes. This
must be below 2°C (35°F) to allow defrost. parameter allows maintenance personnel to set the
Defrost Initiation Timer. When it times-out, it
When defrost is required, the microprocessor switches the unit from Cool mode to Defrost
output energizes the hot gas solenoid to supply hot mode. The timer counts all the time that the unit is
refrigerant to the evaporator coil. The Defrost in Cool mode. The count resets when Defrost
Initiation Timer (DIT) has counted-down its mode starts. If the timer is set at 0 (zero), this is a
required time-setting, and the Defrost Termination test position. Defrost mode starts in 15 seconds.
Switch (DK1 or DK2) is closed.
The Defrost Termination Timer offers
The unit remains in Defrost mode until the programming choices of 5 to 50 minutes, in
Defrost Termination Switch setpoint is reached increments of 5 minutes. The factory setting is 45
(that is, when the evaporator coil temperature minutes. This parameter allows maintenance
rises to 14°C (58°F), or until the Defrost personnel to set the Defrost Termination Timer,
Termination Timer (DTT) count is completed). If which begins counting from the initiation of a
the evaporator coil temperature does not rise Defrost mode. When the timer times-out, the unit
above 14°C (58°F) within the defrost duration is switched from Defrost mode to Null mode. The
time limit, the microprocessor terminates the timer resets at the end of a Defrost mode, or after
defrost operation. the Defrost Termination Timer has timed-out. If
The startup of the evaporator fans is delayed for the timer is set at 0 (zero), this is a test position.
several seconds after Defrost mode ends to Defrost mode stops in 15 seconds.
prevent water from the melting ice from being
sprayed on the load.
On multi temp units defrost is performed on all
evaporators at the same time.

35
Electrical Maintenance

Liquid Injection System If the contactor is pulled down and the overload
(R-404A Units Only) relay is closed, but the standby motor fails to start,
the trouble is probably in the standby motor.
This liquid injection switch is a temperature
sensitive switch located on the discharge fitting of If the contactor is not pulling down proceed as
the truck engine compressor. When the discharge follows:
temperature rises above 230 ± 5 F (110 ± 3 C), the 1. Check the AC line voltage and the transformer
switch closes to open the liquid injection solenoid fuse. If the AC line voltage is acceptable and
valve. When the discharge temperature falls the transformer fuse is intact, go to step 2.
below 200 ± 5 F (93 ± 3 C), the switch opens to
close the liquid injection solenoid valve. 2. Measure the transformer output voltage (AC)
at the terminal board. Measure the voltage
Testing Liquid Injection Solenoid between wires X1 and X4. The voltage
Valve and Metering Orifice reading should be approximately 12/24V
(depending on the unit voltage). If not, the
1. Disconnect the LIS wire from the liquid transformer is defective. If the transformer
injection solenoid valve. output voltage is acceptable, go to step 3.
2. Install the gauge manifold set on the 3. Check the rectifier output voltage (DC) on the
engine-driven compressor. 2R wire (Pin 3 C-2). If this voltage is less than
3. Set thermostat on the lowest setting. approximately 12/24V, the rectifier bridge is
defective. If the rectifier output voltage is
4. Start and run the unit on the engine-driven acceptable, go to step 4.
compressor until the suction pressure
stabilizes. 4. Check the voltage on 2R1 wire (Pin 4 C-4). If
voltage is not present, check Fuse 4. If Fuse 4
5. Place a jumper between CH and LIS terminal is intact, go to step 5.
on the liquid injection solenoid valve. This
simulates that the discharge temperature is 5. Check the voltage on Pin 2 C-9. If voltage is
higher than 230 F (110C). not present, check for open circuits on wires
2R1 and R. If voltage is present on Pin 2 C-9,
6. With the jumper wire in place the suction check the in-cab control box.
pressure should rise.
7. Remove the jumper. The suction pressure
should return to the stabilized pressure in
step 4.
8. If the suction pressure does not change, check
the CLU wire for voltage, the liquid injection
solenoid valve, or the metering orifice.
9. Shut off the unit and the truck, remove the
gauge manifold set, and replace the LIS wire.

Electric Standby Circuits


If the unit does not run in the electric standby
mode use the following procedure.
Make sure the unit is connected to the proper
power source.
Check the power cable receptacle for power. If
power is there, check for power at the unit
terminal plug.

36
Refrigeration Maintenance

Maintenance Inspection Schedule


Semi-
Procedures Weekly Monthly Annual Annually
Check refrigerant level. • •
Replace dehydrator. •

NOTE: The following procedures involve NOTE: If the system will not come down to
servicing the refrigeration system. Some of these 500 microns, there is probably a leak in the
service procedures are regulated by Federal, and system or in the evacuation and charging
in some cases, by State and Local laws. equipment hoses. Find and repair the leak.
All regulated refrigeration service procedures 1
must be performed by an EPA certified
technician, using approved equipment and 2
complying with all Federal, State and Local
laws.

Recharging the Refrigeration


System
The liquid line sight glass helps the operator to
determine the amount of charge under established 3
4
operating conditions. These units can be damaged
by an overcharge of refrigerant. The amount of
refrigerant the system can hold depends on circuit
volume which is affected by hose length.
ARA053

The most satisfactory method of charging the


1. Gauge Manifold Set
engine driven compressor circuit and the electric
standby driven compressor circuit is as follows: 2. Engine Driven Compressor
3. Evacuation Station
1. Connect a gauge manifold set to the suction
and discharge service ports on the engine 4. Refrigerant Drum
driven compressor. Figure 19: Charging Refrigeration System
2. Connect the center hose of the gauge manifold
6. After the additional hour of evacuation, close
to the manifold of an evacuation station. The
the valve at the evacuation pump, stop the
use of Thermo King Evacuation Station
vacuum pump, and observe the reading on the
P/N 204-725 is recommended.
vacuum gauge for 5 minutes. The pressure
3. Connect the hose from a drum of refrigerant to should not exceed 2000 microns.
the manifold of the evacuation station. Make
NOTE: If the pressure exceeds 2000 microns
sure the valve on the refrigerant drum is
within 5 minutes, look for a leak in the
closed.
system or in the evacuation and charging
4. Open the valves on the gauge manifold and equipment hoses. Find and repair the
the valves on the evacuation station. leak.Then repeat steps 5 and 6.
5. Start the vacuum pump and evacuate the 7. Open the vacuum valve at the vacuum pump,
system to 500 microns. After the system start the vacuum pump, and evacuate the
reaches 500 microns, evacuate the system for system to 500 microns.
an additional hour.

37
Refrigeration Maintenance

8. When the system reaches 500 microns, close b. Connect the electric power receptacle to
the vacuum valve at the evacuation station an appropriate electric power supply. Start
manifold. The system is now ready to charge. and run the unit in cool on electric
operation for a minimum of 15 minutes.
9. Close the low side valve on the gauge
manifold, leave the high side valve on the c. Turn the unit Off and disconnect the
gauge manifold open, and open the valve on electric power supply. Start the truck and
the refrigerant drum to deliver liquid. run the unit in cool on engine operation for
a minimum of 15 minutes.
10. Allow 2.60 lb (1.20 kg) of R-134a or 2.75 lb
(1.25 kg) of R- 404A refrigerant to enter the 20. Check the liquid line sight glass for bubbles.
system. Then close the valve on the refrigerant Repeat steps 13 through 20 if bubbles are
drum and the high side valve on the gauge visible.
manifold.
21. Stop the unit, shut off the truck engine and
11. Start the unit on engine operation and run the remove the gauge manifold set.
truck engine at approximately 1000 rpm.
22. The above conditions MUST be established
12. Set the thermostat at 32 F (0 C), and run the each time the refrigerant level is checked, or if
unit in cool until the box temperature refrigerant needs to be added for any reason.
approaches 32 F (0 C).
NOTE: To prevent oil migration from one
13. Make sure that the unit is running in cool, the compressor to another, and for proper oil
compressor is running at approximately 1000 return when a compressor is operating,
rpm, the suction pressure is 2 to 8 psig (14 to operate a compressor for a minimum of 15
55 kPa), and the head pressure is at least minutes. Do not operate a compressor for
180 psig (1241 kPa) for R-134a systems or shorter intervals.
275 psig (1896 kPa) for R-404A systems. If
necessary, raise the head pressure by covering Checking the Refrigerant Charge
the condenser grille.
If the unit has an insufficient charge of refrigerant,
14. With these conditions established, open the the evaporator will be “starved” and the box
valve on the refrigerant drum to deliver liquid. temperature will rise even though the unit is
operating. Also, an insufficient charge does not
15. Observe the suction pressure and slowly open
circulate enough oil to properly lubricate the
the low side gauge manifold valve to allow
compressor. The charge can be determined by
liquid refrigerant to flow into the compressor
inspection of the refrigerant through the sight
suction service valve.
glass with the following conditions established:
16. Control the liquid flow so the suction pressure
increases approximately 20 psig (138 kPa). Testing the Refrigerant Charge with an
Empty Box
17. Observe the liquid line sight glass. Close the
valve on the refrigerant drum when the 1. Place a test box over the evaporator.
bubbles disappear from the sight glass or
2. Install gauge manifold set.
when the system capacity has been reached
(see unit specifications). 3. Run the unit in cool on engine driven
compressor operation until the thermometer
18. Close the low side valve on the gauge
reads 32 F (0 C).
manifold and operate the unit for 15 minutes.
4. Establish head pressure of 180 psi (1241 kPa)
19. Model 20 only.
for R-134a systems or 275 psi (1896 kPa) for
a. Turn the unit Off and shut off the truck R-404A systems. It may be necessary to
engine. partially cover the condenser grille on the
front of the unit to create the desired head
pressure.

38
Refrigeration Maintenance

5. Look at the liquid line sight glass. Under these NOTE: A suction line oil separator can be
conditions there should be no bubbles in the improvised by installing a suction filter
flow of refrigerant through the liquid line sight upside down in the suction line near the
glass. Bubbles in the refrigerant indicate the compressor. Cap off both access ports, and
unit is low on refrigerant. Refer to “Charging use the lower one to drain off the
the Refrigeration System” for information accumulated oil.
about adding refrigerant.
2. Place a normal amount of oil in the cleanup
compressor before operating.
Testing the Refrigerant Charge with a
Loaded Box 3. Charge with 6.0 to 7.0 lb (2.7 to 3.2 kg) of
refrigerant.
1. Install a gauge manifold.
4. Operate at a low speed (600 to 800 rpm) for 2
2. Run the unit in cool on engine driven
hours, or until the compressor oil level reaches
compressor operation.
a minimum allowable level, whichever occurs
3. Cover the condenser to drive any excess first. Drain the collected oil from the oil
refrigerant from the condenser into the separator as it fills, taking care to not allow
receiver tank. any collected oil to recirculate.
4. As the head pressure rises, check the liquid 5. Prepare the original compressor that was
line sight glass. There should be no bubbles in removed from the unit (or a replacement) by
the flow of refrigerant through the liquid line draining out any existing oil and replacing the
sight glass. Bubbles in the refrigerant indicate oil with the amount of oil shown in the
the unit is low on refrigerant. Refer to Specifications chapter.
“Charging the Refrigeration System” for
6. Install the original compressor (or its
information about adding refrigerant.
replacement), and proceed with the manual
NOTE: If no bubbles are present, there is evacuation and refrigerant charging
sufficient refrigerant in the unit for that load procedure.
at that particular box temperature. This test
does not determine if the unit contains a full High Pressure Cutout Switch
charge of refrigerant.
(HPCO)
Checking Compressor Oil The high pressure cutout switch is located on a
discharge line inside the condenser unit. If the
Charge discharge pressure rises above 300 psig
The compressors are furnished with the amount of (2068 kPa) on R-134a units or 450 psig (3102
oil shown in the Specifications chapter. The oil kPa) on R-404A units, the switch opens the 7A
level in the compressor will change after the circuit de-energizing the power relay.
compressor is initially run, making any level
To test the switch, rework a gauge manifold per
measurements inaccurate.
Figure 20.
To ensure an adequate oil supply, the following
procedure must be followed whenever the
refrigerant charge is lost or removed from a unit:
1. Install a compressor on the system having a
residual oil supply and self-lubricating system
such as a TK 214 model. Connect an oil
separator on the discharge or suction line to
collect and drain out circulated oil.

39
Refrigeration Maintenance

Low Pressure Cutout Switch


(LPCO)
The low pressure cutout switch is located on the
suction line in the evaporator. If the suction
pressure drops below 5 to 11 in. Hg of vacuum
(-17 to -37 kPa), it opens the circuit to the power
relay to stop the unit. To check the low pressure
cutout:
1. Install a gauge manifold at the compressor.
2. Close the receiver tank outlet valve and run
the unit in cool.
3. When the suction pressure drops below 5 to
11 in. Hg of vacuum (-17 to -37 kPa), the
LPCO should open and the unit should stop.

Cleanup Procedure for Small


Truck Units

1. Relief Valve (66-7392)


2. O-Ring (33-1015)
3. Adapter Tee Weather Head (No. 552X3)
Figure 20: High Pressure Cutout Manifold

7. Connect the gauge manifold to the compressor


discharge service port.
NOTE: Service manifold hoses must have
Schrader valve (tube valve) depressors.
8. Set the thermostat well below the box
temperature so that the unit will be in cool.
9. Raise the discharge pressure of the
compressor by blocking the condenser coil air
flow. When the discharge pressure reaches
300 psig (2068 kPa) on R-134a units, or
450 psig (3102 kPa) on R-404A units, the 1. Remove Internal Parts From Expansion Valve
High Pressure Cutout will stop the 2. Disconnect and Cap (If So Equipped)
compressor.
3. Replace Drier With Tube
NOTE: The discharge pressure should never 4. Discharge Line
be allowed to exceed a pressure of 450 psig
(3102 kPa). 5. Flushing Compressor
6. Suction Line
10. Failure of the high pressure cutout system to
stop compressor operation should be 7. Suction Oil
investigated first by checking the control 8. Recovered Oil
circuit operation and second by high pressure
Figure 21: Connecting Flushing Compressor to
cutout switch replacement. Unit

40
Refrigeration Maintenance

NOTE: If a Van Steenburgh reclaimer is 14. Install HFC refrigerant and flush the system.
available, do not use this procedure. Follow (Energize the defrost solenoid during 30% to
procedure described in Service Bulletin T&T 40% of the clean-up. Solid contaminants will
134. collect in the suction line filter. Oil from the
system and from the flushing compressor will
Tools Required drain out of the suction line filter. (Add
compressor oil as required.) Refrigerant oil in
• Motor-driven TK 214 “Flushing Compressor”
the flushing compressor will absorb acids
• Suction Line Filter (P/N 204-498 with Filter from the system.
P/N 66-2988)
15. Test the recovered compressor oil for acid
• Pipes (In Place of Oil Separator, Check Valve, contamination.
Oil Separator and Standby Compressor)
16. Continue flushing until the compressor oil is
clean.
Clean-up Procedure
1. Make sure all hose routing is correct. Putting the Unit Back Into Operation
2. Make sure that the oil trap is correctly 1. Replace the check valve (or check valve
installed. seats).
3. Recover the contaminated refrigerant from the 2. Install a new oil separator.
system.
3. Install a new liquid injection orifice.
4. Remove the lines from the compressors
4. Install a new drier.
(engine driven and standby).
5. Install a new expansion valve.
5. Flush each compressor using the flushing
compressor and an HFC refrigerant. (Always 6. Install the compressors and lines.
recover the refrigerant before disconnecting
7. Use dry nitrogen to pressurize the system to
the flushing compressor.)
150 psi (1034 kPa).
6. Remove the check valve (or check valve seats)
8. Use a bubble solution to check for leaks.
from system to ensure flow in all directions.
9. Install correct amount of oil.
7. Remove the oil separator and install a
connecting pipe. 10. If no leaks are found, evacuate the system. A
leak-free and dry system will maintain a 1000
8. Remove the internal parts from the expansion
micron vacuum for five minutes or longer.
valve.
11. Charge the system with proper amount of the
9. Open the suction pressure regulator (CPR)
correct refrigerant.
valve to its highest setting.
12. Operate the unit and check for proper
10. Install a temporary suction line filter (P/N
operation. (Adjust the suction pressure
204-498 and P/N 66-2988) in the suction line.
regulator.)
11. Install a connecting pipe in place of the
13. After two weeks of operation, change the
standby compressor.
drier.
12. Connect the flushing system to the engine
driven discharge and suction lines (see
illustration).
13. Evacuate the system and check for leaks.
Continue to evacuate to remove moisture and
air.

41
Refrigeration Maintenance

42
Compressor/Clutch Maintenance

Handling instructions Refrigerant Recovery


Some air conditioner system refrigerant
Refrigerant Handling-Safety compounds are chlorofluorocarbons, and
DANGER: Explosion Hazard! Never therefore may be damaging to the earth’s ozone
throw or strike service cans and never layer. Consequently, the release of refrigerant into
handle the packing carton roughly. Do not the atmosphere must be avoided. Whenever
use service cans which are damaged or refrigerant is to be released from the air
dented. Store service cans out of reach of conditioner system, a refrigerant recovery unit
children. must be used to recover the refrigerant. This
refrigerant can then be recycled and reused, which
DANGER: Explosion Hazard! Never is both environmentally safe and economical.
directly heat service cans or put them in NOTE: Consult your recovery unit’s operators
hot water heated above 104F (40C) since manual for proper hookup and operating
the can may explode and cause personal procedures.
injury. When it is necessary to heat service
cans for charging in cold weather, use
warm water at a temperature below 104F
(40C).

DANGER: Explosion Hazard! Never put


service cans on the engine or the radiator
when charging Excessive Heat increases
pressure to a dangerous level which may
cause can or bottle to explode.

DANGER: Explosion Hazard! Never store


service cans in direct sunlight, near flame
or where the temperature exceeds 104F
(40C). Always store service cans in a cool
dry place.

CAUTION: Do not put the charge valve in


the warm water.

Figure 22: Recovery Unit

43
Compressor/Clutch Maintenance

Compressor Handling Compressor Removal

CAUTION: Do not strike or turn the When the compressor is operational.


compressor upside down. If the 1. Perform “OIL RETURN OPERATION” (For
compressor is knocked over or turned more information see“Checking the Oil
upside down, rotate the compressor 5 to 6 Level” on page 47).
times by hand to circulate the oil which
has settled in the cylinder. Sudden rotation 2. Perform the Refrigerant Recovery (For more
with oil in the cylinder can cause valve information, see “Refrigerant Recovery” on
damage and adversely affect durability. page 43).
3. Drain the oil from the compressor and cap or
plug all open connections immediately.
4. Check the quantity and the degree of
contamination. (For more information, see
“Oil Contamination” on page 48).

When the compressor is inoperable


1. Perform the Refrigerant Recovery” (For more
information, see “Refrigerant Recovery” on
page 43.)
2. Remove the compressor.
3. Drain the oil from the compressor and cap or
plug all open connections immediately.
1. Rotate Compressor’s Magnetic Clutch 5 to
6 Times 4. Check the quantity and the degree of
contamination. (For more information, See
Figure 23: Rotate Clutch
“Oil Contamination” on page 48).
Compressor Storage
Both new and rebuilt compressors should be
stored with the correct oil charge. They should be
stored within the orientation range shown on the
next page. If the compressor is allowed to sit
outside that orientation for more than a minute,
the compressor must be turned over by hand
(slowly) to clear oil from the cylinders.
NOTE: All compressors in storage must have a
holding charge of refrigerant or nitrogen to a
pressure of between 7 to 21 psig (48 to 145 kPa,
0.5 to 1.5 bar, 0.5Kg/cm2 to 1.5 Kg/cm2). This will
protect internal parts from moisture and Figure 24: Draining the oil
corrosion.

44
Compressor/Clutch Maintenance

Installation Guidelines for


Compressors
Installation Position
The compressor should be installed on the vehicle
within the range shown at right. If installed
outside this range, the compressor will be
adversely affected. This compressor is equipped
with a pressure feed lubrication system which
cannot function properly if the compressor is
installed outside this range. As a precaution, it is
recommended that once the compressor is
mounted in its proper and final position, it is
turned over by hand at least 10 revolutions before
hooking the drive belt up to the pulley. If this is
not done before the compressor is put in service, Figure 26: Loosen Cap
damage to the compressor valving can result from
oil slugging. This is not covered under
warranty! CAUTION: Take care not to let oil escape.

2. Slowly rotate the compressor’s magnetic


clutch several times by hand to distribute the
oil which has settled in the cylinders.

Figure 25: Compressor Installation Range

Installation Precautions
The new compressor is filled with the specified
quantity of compressor oil and nitrogen gas (N2).
When mounting the compressor on the vehicle,
take the following steps:
1. Loosen the discharge side connector’s cap and
gently release N2 from compressor. Figure 27: Rotate Clutch

3. When replacing the compressor on a system,


the compressor should be installed after
adjusting the amount of oil, (see “Checking
the Oil Level” on page 47.) When installing
the compressor on a new system, be sure to
follow factory specifications.

45
Compressor/Clutch Maintenance

Mounting Compressors
CAUTION: DO NOT leave the oil
Clearance between the compressor mounting
container open to the air any longer than
supports and its bracket must be less than 0.004
necessary for proper servicing of the
inches (0.10 mm). Use shims as necessary to
system. Refrigeration oils are
adjust this clearance. This will reduce the stresses
hydroscoptic, which means they attract
on the compressor which can cause components to
moisture from the air.
fail. Be sure to maintain proper pulley alignment
for the drive belt.
CAUTION: DO NOT open refrigeration
system unnecessarily. This increases the
chance of contamination.

CAUTION: Always discard used


containers. These containers are
hazardous.

CAUTION: Never store PAG oil in plastic


containers. PAG oil will absorb moisture
through the plastic container

1. Bracket
Checking the Compressor Oil for
Contamination
2. Shim
It is only necessary to check or replace the
3. Compressor
compressor oil:
Figure 28: Shim Installation
• When the compressor, evaporator coil,
It is important that the compressor be mounted condenser coil, or receiver tank (if used) is
properly when installed. The picture on the replaced.
previous page shows the maximum range of • When the refrigerant system has leaked
motion for the compressor. Be sure to verify this refrigerant.
positioning at both extremes of the belt
adjustment. • When the refrigerant system has an oil-related
problem.
CAUTION: Keep all containers tightly
closed until ready to use. Both System Compressor And Oil
Polyalkylene Glycol (PAG) and Polyol
Ester (POE) oil will pull moisture right Compressor Installation
out of the air. Moisture which gets into the
oil causes a chemical reaction which The compressor is mounted on the bus engine
creates ACID. Evacuation of the system using a special mounting bracket. The side to side
WILL NOT remove this moisture from the mounting angle of the compressor must remain ±
oil. This process is not reversible and will 45° from the horizontal. The forward to backward
happen in a short period of time. angle must be within ± 10° of horizontal. (See
45.) Access to the air conditioning system service
ports may vary, but usually access to the system
can be made from under the engine compartment
hood from the front of the bus.
Special care must be used when routing the
suction and discharge hoses through the engine
compartment. These hoses must be kept away

46
Compressor/Clutch Maintenance

from sharp objects and hot areas of the engine.


These things can cause damage to the hoses and CAUTION: Keep all oil containers tightly
leaks of the refrigerant. The hot areas can also rob sealed from the air. Oil tends to absorb
you of cooling by adding heat into the refrigerant moisture from the air and can become
inside the hoses. This added heat must then be contaminated if left open. If contaminated
rejected by the condensing coil. Since each coil oil is put into a system, it may damage the
has a limited ability to reject heat, that kind of components of the system.
extra heat simply means less cooling inside the
bus where it is needed. Major Loss of Refrigerant
Each compressor kit comes with a standard charge In case of a major loss of refrigerant, it must be
oil inside. This quantity of oil is enough to supply assumed that some system oil is lost also. The oil
the compressor lubrication when it is installed into level should be verified by the “Checking the Oil
an already “oil wet” system. New systems require Level” method. See below.
an extra quantity of oil be added to “wet” all the
interior surfaces of the system. Checking the Oil Level

CAUTION: Be sure to verify the oil that is Oil Return Procedure (System
used in the compressor kit matches the oil Operational)
used in your system. Failure to use the There is a close affinity between oil and
correct oil will contaminate and damage refrigerant. During normal operation, part of the
your system. oil circulates with the refrigerant in the system.
During normal operation there is always a Before checking the level of oil can be done, or
quantity of oil that travels around inside the replacing any system components need to place
system. This oil lubricates all the components, the system in a condition that will return as much
returns to the compressor for a while, and again oil as possible to the compressor sump. As the oil
travels around the system. returns, it will reach a maximum level inside the
compressor—this is the point we need to verify.
Adding Extra Oil to the System To get the oil to return to the compressor it is
necessary to run the A/C system at an elevated
The initial oil charge into a new system is based load condition for 20 minutes. Place the engine in
on the size of the system and the amount of oil, idle or high idle (if equipped). Compressor speed
which remains in the compressor during should be between 800 and 1500 rpm. Open the
operation. vehicles doors and windows to rise the interior air
NOTE: Check the system decals and operation (unit’s return air temperature between 75 to 80
manual for the proper oil. degrees (25 to 27 C). The condenser’s inlet air
(ambient air temperature) should be above 85
CAUTION: Check the system decals and degrees F (29 C) or partially block the condenser
operation manual for the proper oil. The air flow to raise the compressor discharge
mixing of incompatible oils will cause pressure above 170 psig (1172 kPa, 12 bar, 12
system damage. Compressor Oil 1L PAG kg/cm2). This condition will return most oil to the
recommended for R-134a Systems. compressor.

CAUTION: Be sure to verify the oil that is


used in your compressor kit matches the
oil that is used your system. Failure to use
the correct oil will contaminate and
damage your system.

47
Compressor/Clutch Maintenance

removed from the compressor. Measure the oil in


a measuring cylinder. Also, inspect the oil for
signs of contamination.
NOTE: Some compressors may also have an oil
drain plug. Be sure to replace and tighten drain
plug to specifications.
Check the oil quantity and the degree of
contamination. After removing its oil drain plug,
install the compressor and tighten bolts to the
specified torque (10 to 12 ft-lbs, 14 to 16 N•m).
1. Oil Return Operation
2. Refrigerant Recovery
Oil Contamination
3. Compressor Removal Unlike engine oil, no cleaning agent is added to
the compressor oil. Even if the compressor is run
4. Oil Inspection
for a long period (approximately 1 season), the oil
Figure 29: Oil Return Procedure never becomes turbid as long as there is nothing
wrong with the compressor or its method of use.
Inspect the extracted oil for any of the following:
CAUTION: Some systems without service
valves will require the removal of 1. Dirt in the oil.
refrigerant from the system before 2. Color changed to red.
removing the compressor from the system.
3. Presence of foreign substances, metal
When the compressor is inoperable: shavings, etc. in the oil.

1. Recover the refrigerant from the system using NOTE: Always replace oil with new fresh oil
a refrigerant recovery unit. taken from a sealed metal container only.

2. Remove the compressor. NOTE: Always replace the system’s filter-drier


anytime the system has been opened for service.
Drain the Oil
CAUTION: Check the system decals and
operation manual for the proper oil. The
mixing of incompatible oils will cause
system damage. Compressor Oil 1L PAG
recommended for R-134a Systems.

When a System Becomes Contaminated


A severely contaminated system may be indicated
by black oil in the compressor. If severe
contamination occurs, it will be necessary to flush
the complete system. If flushing is required, use
industry approved materials.
Figure 30: Draining the Oil In all cases when this occurs, the extent of
contamination must be determined. Do this by
Drain the oil from the compressor drain plug and
removing the filter-drier and determine if the
all other ports. Extract the remaining oil through
darker-colored oil is present at that point of the
the discharge side connector by rotating the drive
system. If so, flushing the system is
plate several times by hand. Repeat until all oil is
recommended.

48
Compressor/Clutch Maintenance

If the oil appears clean at the filter-drier, install a Magnetic Clutch Run In.
new filter-drier and replace the compressor with
1. Install the clutch on the compressor. (For more
clean new oil.
information, see “Inspection Components” on
page 52.)
2. Install the compressor on the engine, charge,
and operate the compressor by running the
system.
3. Maintain the compressor speed at idle.
Operate the A/C Switch through the ON/OFF
cycle at least 10 times (“ON” for 10 seconds
“OFF” for 10 seconds”).

Leak Test Procedure


Compressor Removed
Figure 31: Typical Compressor Oil Fill Procedure When a compressor is repaired it should be
Compressor oil is to be placed in the compressor checked prior to installation.
through the suction port. 1. Install the discharge and suction caps on the
connector.
Oil Check Interval
Unlike engine oil, it is not necessary to frequently
check or change the compressor oil. However it is
necessary to check and replenish or replace the
compressor oil in the following cases:
• At the start of the season or
• Every 3,200 miles (5000 km) or every 5
months for commercial vehicles and vehicles
that are in constant use.
• Whenever the compressor, evaporator,
condenser or receiver-drier is replaced.
• Whenever the refrigerant has leaked from the
system. (i.e. High Pressure Relief Valve
discharges)
Figure 32: Compressor Caps
• When gas or refrigerant leaks from the
2. Fill the compressor with refrigerant gas (same
compressor.
type that is used in the system) through the
• Whenever any oil-related problems occur in connector’s suction port raising the pressure to
the cooling cycle. at least 70 psig (0.5 Mpa).
3. Check the compressor for leaks using a
reliable leak detector.
NOTE: Be sure that the leak tester being used is
capable of detecting fluorine based refrigerants.

49
Compressor/Clutch Maintenance

Removal
CAUTION: Never leave the compressor
1. Remove the center armature bolt.
upside down for longer than 30 seconds.
This is because the oil inside the
compressor will enter the cylinders,
causing liquid compression which will
damage the compressor’s suction and
discharge valves.

Clutch Test
1. If the field coil lead wire is broken, replace the
field coil.
2. Check the amperage and voltage. The
amperage range should be 3.6 to 4.2 at 12
volts or 1.8 to 2.1 at 24 volts. Note the
following symptoms and conditions: 1. Holder
a. A very high amperage reading—a short Figure 33: Remove Center Bolt
within the field coil.
2. Remove the armature plate using the armature
b. No amperage reading—an open circuit in
plate puller. Then remove the shims from
the winding.
either the armature shaft or the armature plate.
c. An intermittent or poor system ground
results in lower voltage at the clutch.
Check for tight fit on the coil retaining
snap ring or for good ground at the coil
retaining screws.

Compressor Clutch Removal


NOTE: Make sure the proper tools are available
before performing maintenance procedures.
Refer to the tool listing at the end of this chapter
for tools required. Contact your local
International Components Engineering Dealer
for further information. Figure 34: Remove Drive Plate

3. Remove the snap ring using external snap ring


pliers. Remove the cover (if equipped).

50
Compressor/Clutch Maintenance

5. Remove the coil’s lead wire from the holder


on the top of the compressor.
6. Remove the three screws that attach the coil to
the compressor and remove the coil.
NOTE: DO NOT hold the coil by the lead wire.

1. Snap Ring
2. Cover (If Equipped)

Figure 35: Remove Snap Ring and Cover

4. Remove the pulley assembly using the pulley


remover and the spacer positioned on the Figure 37: Remove Coil
cylinder head hub.

CAUTION: To avoid damaging the pulley


groove, the puller claws should be hooked
into (Not Under) the pulley groove.

Figure 36: Remove Pulley

51
Compressor/Clutch Maintenance

Inspection
1. Armature Plate
If the contact surface is scorched, the armature
plate and pulley should be replaced.
2. Pulley Assembly
Inspect the appearance of the pulley assembly.
If the pulley’s contact surface is excessively
grooved due to slippage, both the coil, pulley
assembly and armature plate must be
replaced. There should also be no foreign
matter, such as oil or grit, lodged between the
clutch plate and pulley. Thoroughly clean
these contact surfaces and the drive plate with
Figure 39: Instant Coil
a suitable solvent before installation.
3. Coil 3. Install the pulley assembly using the Installer
and a hand press.
Inspect the coil for a loose connector or
cracked insulation. If the insulation is cracked,
replace the coil. Repair or replace the wire or
the connector if either is loose or damaged.

1. Drive Plate
2. Pulley Assemble
3. Coil Figure 40: Install Pulley

Figure 38: Inspection Components

Clutch Installation
NOTE: Before installation refer to the
“Inspection” procedures previously described.
1. Install the coil on the compressor (with the
lead wire on top) then tighten the mounting
screws to the specified torque.
NOTE: Specified torque: 2.9 to 4.3 ft-lbs (0.4
to 0.6 Kgm).
2. Install the lead wire in the wire holder on the
compressor.

52
Compressor/Clutch Maintenance

4. Install the cover and the snap ring using 6. Tighten the bolt to the specified torque using
external ring pliers. the Arbor puller to prevent drive-plate
rotation.
NOTE: Specified torque: 8.7 to 10.1 ft-lbs
(1.2 to 1.4 kgm).

After tightening the bolt, ensure that the pulley


rotates smoothly.

1. Snap Ring
2. Cover (If Equipped)
Figure 41: Install Cover and Snap Ring

NOTE: The snap ring should be installed 1. Shims


with the chamfered inner edge outward
Figure 43: Install Shims and Drive Plate
(facing away from seal).
7. Ensure that the clutch clearance is as
specified. If necessary, adjust the clearance
using shims.
NOTE: Specified clearance: 0.016 to 0.031
in. (0.4 to 0.8 mm).

1. Snap Ring
2. Cover (If Equipped)

Figure 42: Install Cover and Snap Ring


Figure 44: Check Clearance
5. Install the driver plate on the drive shaft,
together with the original shim(s). Press the
drive plate down by hand.
NOTE: : If replacement or additional shims
are required, a clutch hardware kit is
available.

53
Compressor/Clutch Maintenance

Electrical Connection 4. Use the seal remover (from the shaft seal kit)
to remove the shaft seal. Turn the seal remover
1. Connect the lead wire to the electrical circuit.
to engage the hook on the seal remover with
NOTE: The stationary field is grounded at the hook on the shaft seal, then slowly pull the
the factory; therefore, it is necessary only to shaft seal housing out of the cylinder head.
connect the hot (lead) wire.
2. Engage and disengage the clutch several times
to check the clutch engagement. The disc
should snap firmly against the pulley.

Shaft Seal Cover And Shaft Seal:


Removal And Installation
Removal
1. Remove the magnetic clutch assembly, as
outlined in “Clutch Removal” (see
“Compressor Clutch Removal” on page 50.)
2. Use the seal remover (from the shaft seal kit)
1. Shaft Seal
to remove the shaft seal cover. Turn the seal
remover to engage the hook on the seal Figure 46: Remove Shaft Seal
remover with the hook on the shaft seal cover,
then slowly pull the shaft seal cover out of the Inspection
cylinder head (some models).
The shaft seal should not be reused. Always use a
3. Remove the snap ring using internal snap ring new shaft seal when reassembling the compressor.
pliers. Be extremely careful that the lip of the new shaft
seal is not scratched or damaged in any way.
NOTE: The shaft seal cover SHOULD NOT
Make sure the shaft seal is free from lint and dirt
be reused. Always use a new shaft seal cover
that could damage the shaft seal surface.
when reassembling a compressor. (Some
Models)

Figure 47: Inspect Shaft Seal

1. Shaft Seal Cover (Some Models)

Figure 45: Remove Shaft Seal Cover

54
Compressor/Clutch Maintenance

Shaft Seal Installation 5. Use the seal installer (from the shaft seal kit)
to press the shaft seal into the cylinder head as
Before installing a shaft seal inspect it carefully
far as possible.
(see “Inspection,” previous paragraph).
6. Remove the seal guide from the spline shaft.
1. Clean the seal section of the front cylinder
head that holds shaft seal.
2. Apply clean compressor oil to the new shaft
seal and to the front cylinder head. If the slip
surfaces are dirty, clean them with thinners,
dry the clean surfaces, and apply clean
compressor oil — same type that is used in the
system.
3. Place the seal guide (from the shaft seal kit)
on the end of the spline shaft.

Figure 50: Press Seal Into Cylinder Head

7. Install the snap ring using internal snap ring


pliers. Press the snap ring using the installing
end of the remover until a “Click” is heard.

1. Seal Guide

Figure 48: Place Guide on Shaft

4. Place the shaft seal over the seal guide and


slide the seal into the front cylinder head.
1. Shaft Seal
2. Guide
3. Snap Ring

Figure 51: Install Snap Ring

NOTE: When installing the snap ring, the


chamfered edge of the snap ring must face
upward as shown in the figure below.

1. Seal Guide
2. Shaft Seal

Figure 49: Place Shaft Seal on Drive

55
Compressor/Clutch Maintenance

Cover Installation (When Equipped) 4. Remove the seal guide from the spline shaft.
1. Place the seal guide (from the shaft seal kit) NOTE: Position the shaft seal cover as shown in
on the end of the shaft. the illustration.
2. Place the shaft seal cover on the seal guide
and slide the shaft seal cover into the cylinder
head.

1. Top
Figure 52: Install Shaft Seal Cover 2. Shaft Seal Cover
(When equipped)
3. Bottom
3. Use the seal installer (from the shaft seal kit) Figure 53: Proper Shaft Seal Cover Position
to press the shaft seal cover into the cylinder.

56
Compressor/Clutch Maintenance

Front And Rear Cylinder Heads 6. Remove the O-ring from the front cylinder
head and the remove all the gasket material
Disassembly from the front cylinder head.
1. Remove the magnetic clutch assembly, as
outlined in “Clutch Removal TM 16-HD
Compressors”.
2. Remove the connector’s caps and the drain
plug and then drain the oil.
3. Remove the shaft seal cover and shaft seal, as
outlined in “Shaft Seal Cover and Shaft Seal
Removal”.
4. Remove the six body bolts securing the head
using a socket wrench.
1. O-ring
2. Gasket
3. Front Cylinder Head

Figure 56: Remove O-Ring

7. Remove the valve plate and suction valve


from the cylinder shaft assembly and remove
all the gasket material from the valve plate.

Figure 54: Remove Bolts

5. To remove the front cylinder head alternately


tap the two projections on the circumference
of the front cylinder head with a screwdriver
and a plastic mallet.

1. Valve Plate
2. Suction Valve

Figure 57: Remove Valve Plate

Figure 55: Remove Front Cylinder Head

57
Compressor/Clutch Maintenance

8. To remove the rear cylinder head alternately 10. Remove the valve plate and suction valve
tap the projections on the circumference of the from the cylinder shaft assembly and remove
rear head with a screwdriver and a plastic all the gasket material from the valve plate.
mallet.

1. Valve Plate
Figure 58: Remove Cylinder Head
2. Suction Valve
9. Remove the O-ring from the rear cylinder Figure 60: Remove Valve Plate
head, and remove all the gasket material from
the rear cylinder head. Inspection
Check the front and rear valve plates for
scratched, bent or damaged parts. Inspect both
cylinder heads and both valve plate assemblies
for nicks and/or burrs on the sealing surfaces.
Clean or replace them if damaged. Ensure that
all passages in the valve plate are
unobstructed. If either the cylinder head or
valve plate is cracked, it must be replaced.

1. O-ring
2. Gasket

Figure 59: Remove O-Ring 1. Front Cylinder


2. Valve Plate

Figure 61: Check Valve Plates

58
Compressor/Clutch Maintenance

Reassembly
Rear Cylinder Head
1. Place the cylinder shaft assembly on the bench
with the rear side up.

1. Escape Groove
2. Suction Valve
3. Piston
Figure 62: Alignment

Figure 64: Rear Side

2. Install the rear suction valve so that it aligns


with the alignment pin.

CAUTION: Ensure that the valve is


aligned with the valve escape groove of
each cylinder.

1. Rear Cylinder Head


2. O-ring
3. Gasket
4. Valve Plate
5. Suction Valve

Figure 63: Cylinder Shaft Assembly

1. Escape Groove
2. Suction Valve
3. Piston

Figure 65: Alignment

3. Install the rear valve plate on the rear suction


valve.

59
Compressor/Clutch Maintenance

CAUTION: Be careful not to mistake the


front valve plate for the rear valve plate.

4. Coat the new gasket with clean compressor oil


and install it on the rear valve plate. Use the
same type of oil that is used in the system.
5. Thinly coat the new O-ring with clean
compressor oil (same type of oil that is used in
the system) and install it on the rear cylinder
head.
6. Install the rear cylinder head. If the rear
cylinder head is difficult to install, tap the
cylinder head lightly with a mallet. 1. Escape Groove
2. Suction Valve
3. Piston

Figure 67: Alignment

CAUTION: Ensure that the valve is


aligned with the valve escape groove of
each cylinder.
3. Install the front valve plate on the front
suction valve.

CAUTION: Be careful not to mistake the


rear valve plate for the front valve plate.
1. Rear Cylinder Head
2. O-ring
Coat the new gasket with clean compressor oil
3. Gasket
(same type of oil that is used in the system) and
4. Valve Plate install it on the front valve plate.
5. Suction Valve
Thinly coat the new O-ring with clean compressor
Figure 66: Rear Cylinder Assembly oil (same type of oil that is used in the system)
and install it on the front cylinder head.
Front Cylinder Head
Install the front cylinder head. If the front cylinder
1. Place the cylinder shaft assembly on the bench head is difficult to install, tap the cylinder head
with the front side up. lightly with a plastic mallet.
2. Install the front suction valve so that it aligns
with alignment pin.

60
Compressor/Clutch Maintenance

8. Install the magnetic clutch as outlined in


“Inspection Components” on page 52.
Carry out the leak test as outlined in “Leak
Test” 49.
9. Air Gap—An incorrect air gap could cause
erratic engagement or disengagement and/or
clutch rattle. Check the air gap with a feeler
gauge (0.016 to 0.031 in. [0.4 to 0.8 mm]).
Adjust based on “Inspection Components” on
page 52.

1. Front Cylinder Head


2. Valve Plate
3. Suction Valve
4. Gasket
5. O-ring
Figure 68: Front Cylinder Assembly

4. Install new gaskets on the body bolts. Insert


the six body bolts from the front cylinder head
side and tighten them to the specified torque. Figure 69: Tightening Sequence
Each bolt should be gradually tightened in
three or more stages to ensure the specified NOTE: Specified torque:14.5 to 17.3 ft-lbs
torque. The bolts should be tightened in the (20 to 24 N•m).
order shown in the tightening sequence
drawing on the next page.
Specified torque:14.5 to 17.3 ft-lbs
(20 to 24 N•m).
5. Turn the drive shaft 2 to 3 times by hand to
ensure that the shaft rotates smoothly.
6. Install the oil drain plug with a new O-ring,
thinly coated with clean compressor oil, and
tighten it to the specified torque.
Specified torque: 9.4 to 10.8 ft-lbs
(13 to 15 N•m).
1. Drain Plug
7. Fill the compressor with the specified amount
of clean compressor oil through the Figure 70: Drain Plug
suction-side connector.

CAUTION: Be sure to verify the oil you


are using matches what is used in the
system. The use of the incorrect oil will
damage the system.

61
Compressor/Clutch Maintenance

Belt Tensions
Engine Driven Compressor Belt and
Pulleys
Correct pulley alignment and proper belt tension
are very important factors in compressor
installation. The compressor clutch must be
perfectly aligned with the engine pulley and any
auxiliary idler or belt adjustment pulley
components. When installing the clutch, be sure
the shaft drive key is in place and the shaft bolt is
properly tightened. Check the pulley alignment by
holding a 24 to 35 in. (60 to 90 cm) long rod, 0.5
in.(13 mm) in diameter firmly into the V-groove
of the clutch pulley and make sure the rod aligns
squarely with the engine drive pulley groove.
Double check by making sure the belt goes from
pulley to pulley in perfect alignment with no
indication of a sideward bend.
Adjust the belt tension to vehicle manufacturer
specifications. Check the belt tension again after
36 to 48 hours of initial operation of the unit
because the belt may stretch slightly during the
first hours of use. Remember, good alignment and
proper belt tension ensure long belt life.

62
Structural Maintenance

Maintenance Inspection Schedule


Semi-
Procedures Weekly Monthly Annual Annually
Visually inspect unit and refrigerant hoses for fluid • • • •
leaks.
Visually inspect unit for damaged, loose or broken • • • •
parts.
Clean defrost drains. • • • •
Inspect belts for condition and proper tension (belt • • •
tension tool P/N 204-427).
Clean entire unit including evaporator coil and • • •
condenser coil.
Check all unit mounting bolts, brackets, lines, hoses, • •
etc.

WARNING: Take precautions to ensure Unit Mounting Bolts


the unit will not accidentally start while Periodically check and torque the unit mounting
you are servicing the system. bolts.

Evaporator Coil
Clean the coils during scheduled maintenance
inspections. Remove any debris (e.g., leaves or
plastic wrap) that reduces the air flow. Clean dirty
coils with compressed air or a pressure washer. Be
careful not to bend the fins when cleaning a coil.
If possible, blow the air or water through the coil
in the direction opposite the normal air flow.
AMA523
Repair bent fins and any other noticeable damage.
Figure 71: Evaporator
CAUTION: The air pressure should not
be high enough to damage coil fins.

Condenser Coil
Clean the coils during scheduled maintenance
inspections. Remove any debris (e.g., leaves or
plastic wrap) that reduces the air flow. Clean dirty
coils with compressed air or a pressure washer. Be
careful not to bend the fins when cleaning a coil.
AMA1003
If possible, blow the air or water through the coil
in the direction opposite the normal air flow. Figure 72: Condenser
Repair bent fins and any other noticeable damage.

63
Structural Maintenance

64
Over-the-Road Mechanical Diagnosis
If desired box temperature cannot be obtained 9. AIR IN SYSTEM. Air is not condensable. Its
during engine driven compressor operation, any presence in the system increases head
of the following may be indicated: pressure. When the compressor is stopped, air
will gather at the high point of the high side.
1. EXCESSIVE HEAT LOAD. An excessive
Reclaim the refrigerant, evacuate the system
heat load on the system will be caused by too
to 500 microns and recharge with the proper
many, or excessively long, stops with the
amount of refrigerant.
doors open. Excessive heat loads will also be
caused by loose doors, loose body panels, 10. TEMPERATURE OF THE LIQUID LINE.
warm loads and poor insulation. During normal operation, the liquid line will
be slightly warmer than surrounding air. An
2. DIRT ON COILS. Dirt on the condenser or
extremely hot line indicates either shortage of
evaporator coil acts as an insulator reducing
refrigerant or lack of a liquid seal at the
the capacity of the unit.
receiver outlet. A cold line indicates a
3. INCORRECT BELT TENSION. If the drive restriction, and some flashing takes place in
belt is not correctly tensioned, the compressor the liquid line sight glass.
will not be driven at proper speed, and unit
11. DIRTY OR WET FILTER DRIER. If the
efficiency will be reduced. By contrast, too
outlet line of the filter drier is colder than the
much tension will place an additional load on
inlet line, the filter is either saturated with
the bearings causing rapid wear.
moisture or is dirty and must be replaced.
4. SHORTAGE OF REFRIGERANT. Shortage
12. DIRT IN THE EXPANSION VALVE
of refrigerant reduces capacity of the unit.
SCREEN. Reclaim the refrigerant charge,
Find and remedy the cause of the shortage and
remove the screen and clean. Moisture is in
recharge the system. DO NOT operate the unit
the system will collect at the expansion valve
if there is an indication of low charge.
and freeze. This is indicated by abnormally
5. FAULTY EXPANSION VALVE low suction pressure. Replace the drier, dry
ADJUSTMENT. High superheat settings will the system and recharge.
starve the evaporator causing low suction
13. ICE ON THE EVAPORATOR COIL. Note
pressure. Low superheat settings will flood the
operation under DEFROST CYCLE.
coil causing high suction pressure. The
superheat setting should be adjusted ONLY by 14. AIR FLOW. Do not load product directly in
a trained refrigeration serviceman. front of the air return or discharge. Insure that
the fan is correctly positioned in the orifice to
6. EXCESSIVE OIL. Too much compressor oil
achieve maximum air flow.
in the system may result in lower than normal
suction pressure as well as lowered capacity. 15. COMPRESSOR LIFE. The following will
shorten the life of the compressor:
7. MOISTURE IN THE SYSTEM. Symptom:
Expansion valve freeze-up—will not • Operating a contaminated system
refrigerate. Usually this can be checked by
• No oil trap
warming the expansion valve with either the
hand or hot towels to see if the valve opens. • Clogged oil separator (JetLube™)
Evacuate the system in the same manner used
• Clogged liquid injection orifice
during installation. Install a new drier.
(JetCool™)
8. EXPANSION VALVE LOSES ITS CHARGE.
• Defective liquid injection switch
If the expansion valve loses its charge, the
(JetCool™)
valve will close causing the system to go into
vacuum. Replace the valve. • Insufficient oil charge
• Wrong or mixed oil

65
Over-the-Road Mechanical Diagnosis

• Lack of compressor lubrication on


installation and startup
• Excessive compressor speed (maximum
speed 3,000 rpm)

66
Electric Standby Mechanical Diagnosis
Condition Possible Cause Remedy

Compressor does not run Improperly wired Check wiring against diagram

Low line voltage Check line voltage, determine


location of voltage drop

Relay contacts not closing Check by operating manually.


Replace relay if defective

Fuses blown Replace fuses

Open circuit in motor winding Check stator leads

High pressure cutout open Eliminate cause of excessive


pressure

Thermostat faulty Repair or replace

Compressor faulty Replace compressor

Shortage of refrigerant Recharge

Low pressure cutout open Recharge leak test

Overload relay open Locate overload, reset

Unit short cycles Shortage of refrigerant Repair leak and recharge


(low pressure cutout)

Restricted expansion valve Clean expansion valve

Refrigerant overcharge Remove excess charge


(high pressure cutout)

Cycling on high pressure cutout Check air flow and fan

Dirty condenser coil Clean coil

Defrost timer set too low for Adjust timer to higher interval.
application.

67
Electric Standby Mechanical Diagnosis

Condition Possible Cause Remedy

Unit operates long or Shortage of refrigerant Repair leak and recharge


continuously
Discharge valve leaking Replace leak

Thermostat faulty Repair or replace

Dirty condenser Clean condenser

Air in system Evacuate and recharge system

Compressor inefficient Replace compressor

Plugged expansion valve Clean expansion valve

Iced or plugged coil Defrost or clean coil

Defective truck body insulation Correct or replace

Too many door openings Keep doors closed, install plastic


curtains

Load too warm Precool hot product

Excessive superheat at expansion Adjust superheat


valve

Door seals worn Repair/replace

Box temperature too high Refrigerant shortage Repair leak and recharge

Thermostat setpoint too high Reset thermostat

Expansion valve or strainer plugged Clean or replace

Restricted lines Clean restriction. Tubing pinched


shut

Hot load Precool hot product

Expansion valve superheat too high Adjust superheat


or too low

Head pressure too high Refrigerant overcharge Remove excess

Air in system Evacuate and recharge system

Dirty condenser Clean

Restricted condenser Clean condenser

Condenser fan not running Check fan motor

Condenser fan rotation Check fan motor polarity

68
Electric Standby Mechanical Diagnosis

Condition Possible Cause Remedy

Head pressure too low Refrigerant shortage Repair leak and recharge

Compressor suction or discharge Replace valve


valve inefficient

Noisy unit Insufficient compressor oil Add oil to proper level

Mounting bolts loose Tighten

Refrigerant flooding back Adjust oil level or refrigerant charge.


Check expansion valve for proper
superheat

Compressor loses oil Shortage of refrigerant Repair leak and recharge

Plugged expansion valve or strainer Clean expansion valve

Wrong oil viscosity Use proper oil

Short cycling Refer to unit “short cycling”

Superheat too high Adjust expansion valve

Frosted or sweating suction line Expansion valve set too low, Adjust expansion valve
admitting excess refrigerant

Hot liquid line Shortage of refrigerant Repair leak and recharge

Condenser fan not running Check fan motor

Dirty condenser coil Clean condenser

Frosted liquid line Restricted dehydrator or strainer Replace restricted part

Condenser coil is cool when unit Refrigerant undercharge Repair leak and recharge
is in cool operation
Compressor inefficient Replace compressor

Unit in vacuum. Frost expansion Ice plugging expansion valve orifice Apply hot wet cloth to expansion
valve only valve. Moisture indicated by
increase in suction pressure.
Replace drier

Plugged expansion valve strainer Clean strainer

Sensor bulb lost charge Replace expansion valve

Electric Standby Service Checks


1.Compressor does not run. a.Check for power at source.
b.Check for power at plug.
c.Check for power at compressor contactor.
d.Check for power at overload terminals (contactor
closed).
e.Check for power at motor terminals.
2.Power at compressor terminals but motor does not a.Replace compressor.
run.

69
Electric Standby Mechanical Diagnosis

Electric Standby Service Checks


3.Compressor hums but does not run. a.Check for locked rotor.
b.Check for worn bearings. Replace if necessary.
c.Check for locked compressor and repair.
d.Check power source for single phasing (on three
phase units).
e.Check capacitors (on single phase units).
f.Check start relay.
4.Check transformer. a.Check for power output.
5.Check rectifier. a.Check for rectifier output.

70
71
72
Refrigeration Diagnosis Chart

Unit cools in defrost cycle

Suction line frosting back


Unit operating in vacuum
High suction pressure
Low suction pressure

Unit not refrigerating


No suction pressure

SYMPTOM
High head pressure
Low head pressure

Sight glass / empty

Unit not defrosting


Noisy compressor
No head pressure
Unit Not Heating
Rapid cycling

POSSIBLE CAUSES
• • Overcharge of refrigerant
• • • • • • • Shortage of refrigerant
• • • • • • • • No refrigerant
• Air through condenser too hot (ambient)
• Air flow through condenser restricted (dirty)
• • Air through condenser too cold (ambient)
• • • Air in refrigerant system
• Condenser fan blades bent or broken
• Air short cycling around evaporator coil
• • • • Air through evaporator restricted
• • • • • • Evaporator needs defrosting
• • Broken engine driven compressor belt
• Compressor discharge valves leaking
• • • Too much compressor oil in system
• Loose engine driven compressor pulley
• Compressor bearing loose or burned out
• • • • Broken valve plate in compressor
• • • • Expansion valve power element lost its charge
• • • Expansion valve feeler bulb improperly mounted
• • • Expansion valve feeler bulb making poor contact
• • • • Expansion valve open too much
• • Expansion valve closed too much
• • • Expansion valve needle eroded or leaking
• • • • Expansion valve partially closed by ice, dirt or wax
• Hot gas solenoid stuck open
• Water valves not open
• Water pump not working.
• Truck engine not running
• • • • Liquid refrigerant entering compressor
• • • Restricted line on the low side
• • Restricted line on the high side
• • • Restricted dehydrator
• • Reverse fan rotation
• • • • Faulty pilot solenoid
• • Loose or broken electrical connections
• • • • Gauge out of calibration
• Condenser fan motor not operating
• • • • • • Evaporator fan motor not operating

73
Refrigeration Diagnosis Chart

74
Wiring, Refrigeration and Schematic
Diagrams Index

Dwg No. Drawing Title Page


1E49393 V-520-10, V-520 MAX-10 Wiring Diagram 77

1E49392 V-520-10, V-520 MAX-10 Schematic Diagram 78

1E49437 V-520-20 1PH, V-520 MAX-20 1PH Wiring Diagram 80

1E49436 V-520-20 1PH, V-520 MAX-20 1PH Schematic Diagram 83

1E49439 V-520-20 3PH, V-520-20 3PH Wiring Diagram 86

1E49438 V-520-20 3PH, V-520-20 3PH Schematic Diagram 89

1E53768 V-520-20 3PH, V-520 MAX-20 3PH, 50/60 Hz Wiring Diagram 92

1E49424 V-520-MAX-10 SPECTRUM Wiring Diagram 94

1E49423 V-520-MAX-10 SPECTRUM Schematic Diagram 95

1E49441 V-520-MAX-20 SPECTRUM 1PH Wiring Diagram 97

1E49440 V-520-MAX-20 SPECTRUM 1PH Schematic Diagram 100

1E49443 V-520-MAX-20 SPECTRUM 3PH Wiring Diagram 103

1E49442 V-520-MAX-20 SPECTRUM 3PH Schematic Diagram 106

1E53769 V-520-MAX-20 SPECTRUM 3PH, 50/60 Hz Wiring Diagram 109

1E51277 V-520-10 Refrigeration DiagramV-520-10 Refrigeration Diagram 110

1E49821 V-520-20 Refrigeration DiagramVV-520 MAX-10 Refrigeration Diagram 111

1E51294 V-520-10 SPECTRUM Refrigeration DiagramVV-520-20 Refrigeration Diagram 112

1E49667 V-520-20 SPECTRUM Refrigeration DiagramVV-520 MAX-20 Refrigeration Diagram 113

75
Wiring, Refrigeration and Schematic Diagrams Index

76
V-520-10, V-520 MAX-10 Wiring Diagram

77
V-520-10, V-520 MAX-10 Schematic Diagram, page 1 of 2

78
V-520-10, V-520 MAX-10 Schematic Diagram, page 2 of 2

79
V-520-20 1PH, V-520 MAX-20 1PH Wiring Diagram, page 1 of 3

80
V-520-20 1PH, V-520 MAX-20 1PH Wiring Diagram, page 2 of 3

81
V-520-20 1PH, V-520 MAX-20 1PH Wiring Diagram, page 3 of 3

82
V-520-20 1PH, V-520 MAX-20 1PH Schematic Diagram, page 1 of 3

83
V-520-20 1PH, V-520 MAX-20 1PH Schematic Diagram, page 2 of 3

84
V-520-20 1PH, V-520 MAX-20 1PH Schematic Diagram, page 3 of 3

85
V-520-20 3PH, V-520-20 3PH Wiring Diagram, page 1 of 3

86
V-520-20 3PH, V-520-20 3PH Wiring Diagram, page 2 of 3

87
V-520-20 3PH, V-520-20 3PH Wiring Diagram, page 3 of 3

88
V-520-20 3PH, V-520-20 3PH Schematic Diagram, page 1 of 3

89
V-520-20 3PH, V-520-20 3PH Schematic Diagram, page 2 of 3

90
V-520-20 3PH, V-520-20 3PH Schematic Diagram, page 3 of 3

91
V-520-20 3PH, V-520 MAX-20 3PH, 50/60 Hz Wiring Diagram, page 1 of 2

92
V-520-20 3PH, V-520 MAX-20 3PH, 50/60 Hz Wiring Diagram, page 2 of 2

93
V-520-MAX-10 SPECTRUM Wiring Diagram, page 1 of 1

94
V-520-MAX-10 SPECTRUM Schematic Diagram page 1 of 2

95
V-520-MAX-10 SPECTRUM Schematic Diagram page 2 of 2

96
V-520-MAX-20 SPECTRUM 1PH Wiring Diagram, page 1 of 3

97
V-520-MAX-20 SPECTRUM 1PH Wiring Diagram, page 2 of 3

98
V-520-MAX-20 SPECTRUM 1PH Wiring Diagram, page 3 of 3

99
V-520-MAX-20 SPECTRUM 1PH Schematic Diagram, page 1 of 3

100
V-520-MAX-20 SPECTRUM 1PH Schematic Diagram, page 2 of 3

101
V-520-MAX-20 SPECTRUM 1PH Schematic Diagram, page 3 of 3

102
V-520-MAX-20 SPECTRUM 3PH Wiring Diagram, page 1 of 3

103
V-520-MAX-20 SPECTRUM 3PH Wiring Diagram, page 2 of 3

104
V-520-MAX-20 SPECTRUM 3PH Wiring Diagram, page 3 of 3

105
V-520-MAX-20 SPECTRUM 3PH Schematic Diagram, page 1 of 3

106
V-520-MAX-20 SPECTRUM 3PH Schematic Diagram, page 2 of 3

107
V-520-MAX-20 SPECTRUM 3PH Schematic Diagram, page 3 of 3

108
V-520-MAX-20 SPECTRUM 3PH, 50/60 Hz Wiring Diagram, page 1 of 2

109
V-520-10 Refrigeration Diagram, page 1 of 1

110
V-520-20 Refrigeration Diagram, page 1 of 1

111
V-520-10 SPECTRUM Refrigeration Diagram, page 1 of 1

112
V-520-20 SPECTRUM Refrigeration Diagram, page 1 of 1

113

You might also like