You are on page 1of 10

Benha University

Benha Faculty of Engineering


Mechanical Engineering Department

Sheet (1)
11-9. A 10 in. (25 cm) round ceiling diffuser from Table 11-4 is to be used with 650 cfm (307 L/s). Compute the total
pressure, throw, and noise criteria for this application.
11-12. A linear floor diffuser is required for a space with an air supply rate of 600 cfm (283 L/s). The room has a 12
ft ceiling and a cooling load of 40 Btu/(hr-ft2) (126 W/m2). (a) Select a diffuser from Table 11-3 for this application.
(b) Determine the total pressure and NC for your selection.
11-13. Suppose a round ceiling diffuser is to be used in the situation described in Problem 11-12. The room has plan
dimensions of 26 × 28 ft (8 × 8.5 m). (a) Select a diffuser from Table 11-4 for this application. (b) Determine the total
pressure and NC for the diffuser.
11-14. Assume that two high sidewall diffusers are to be used for the room described in Problems 11-12 and 11-13,
and they are to be installed in the wall with the longest dimension. (a) Select suitable diffusers from Table 11-5. (b)
Determine the total pressure and NC for the diffusers.
11-15. Select a suitable return grille from Table 11-7 for the room described in Problem 11-12. Total pressure for the
grille should be less than 0.10 in. wg (25 Pa), and one dimension should be 12 in. (30 cm).
11-16. Select a perimeter-type diffuser system for the building shown in Fig. 11-13. It is a general office space.
11-17. Select a round ceiling diffuser system for the building in Problem 11-16.
11-18. Select a high sidewall diffuser system for the building in Problem 11-16.
11-19. Select return air grilles for the building in Problem 11-16. Assume that the return system must
be placed in the attic and each room must have a return.
11-20. Consider a room with a 20 ft exposed wall that has two windows. The other dimension is 42 ft (12.8 m). The
room is part of a variable air-volume system. (a) Layout and select T-bar diffusers from Table 11-6 if the room requires
a total air quantity of 800 cfm (380 L/s) and the maximum total pressure available is 0.10 in. wg (25 Pa). (b) Note the
total pressure, the throw to where the maximum velocity has decreased to 100 ft/min (0.5 m/s), and the NC for each
diffuser.
١1-21. Consider an 18 × 30 ft (5.5 × 9 m) room in the southwest corner of a zone. There are windows on both exterior
walls, and the peak air quantity for the room is 1000 cfm (470 L/s). (a) Layout and select T-bar diffusers from Table
11-6 using a maximum total pressure of 0.15 in. wg (38 Pa). (b) Note the total pressure, the throw to where the
maximum velocity has decreased to 100 ft/min (0.5 m/s), and the NC for each diffuser.

Dr. Radwan
Eng. Ramy Mohamed
Benha University
Benha Faculty of Engineering
Mechanical Engineering Department

Dr. Radwan
Eng. Ramy Mohamed
Benha University
Benha Faculty of Engineering
Mechanical Engineering Department

Dr. Radwan
Eng. Ramy Mohamed
Benha University
Benha Faculty of Engineering
Mechanical Engineering Department

Dr. Radwan
Eng. Ramy Mohamed
Benha University
Benha Faculty of Engineering
Mechanical Engineering Department

Dr. Radwan
Eng. Ramy Mohamed
Benha University
Benha Faculty of Engineering
Mechanical Engineering Department

Dr. Radwan
Eng. Ramy Mohamed
Benha University
Benha Faculty of Engineering
Mechanical Engineering Department

Dr. Radwan
Eng. Ramy Mohamed
Benha University
Benha Faculty of Engineering
Mechanical Engineering Department

Dr. Radwan
Eng. Ramy Mohamed
Benha University
Benha Faculty of Engineering
Mechanical Engineering Department

Dr. Radwan
Eng. Ramy Mohamed
Benha University
Benha Faculty of Engineering
Mechanical Engineering Department

Dr. Radwan
Eng. Ramy Mohamed

You might also like