HOW: Perform a whole house and room-by-room load calculation (Manual J). Then apply
the following formula:
HOW: Determine the external static pressure of the blower using the manufacturer's specs.
Then, deduct the pressure drops created by any components added to the air distribution
system (a/c coils, filters, grills, registers, dampers, etc). This is the available static pressure
for the duct system. Next, determine the total effective length. The total effective length
equals the measured length from the farthest supply outlet through the equipment and to the
farthest return outlet plus the equivalent lengths of all turns and fittings. To get the friction
rate apply the following formula:
NOTE: Although it is not an engineering acceptable practice, for most typical duct
systems, a default friction rate of .05-.08 may be used in lieu of performing the above
calculation.
HOW: Using friction chart. For sizing the supply and return trunks select the duct size
at the intersecting lines of the friction rate and the equipment CFM. As the trunks are
reduced use the total CFM of the remaining downstream branches. To size the branch
ducts, select the duct size at the intersecting lines of the friction rate and the room CFM.
Using a duct calculator. For sizing either the trunks or branches simply align the friction
rate with the CFM and the duct size will be displayed
NOTE: Whether using a friction chart or duct calculator, always check the velocity on the
friction chart or duct calculator. Generally, the velocity should be no more than 700 FPM. If the
velocity is too high, select one pipe size larger until the velocity falls below 700 FPM.