You are on page 1of 1

N2XSY 8,7/15 kV; DNC-ET-031b Contact

Local Sales
ventas.peru@nexans.com

ELECTRICAL DATA
Max. DC A.C. Conductor Phase reactance Perm. current rating Nominal
Cross Resistance of
Resist. Cond. resist. at 90 °C - flat 60 Hz - flat buried 20°C - flat capacitanc
section the screen
20°C formation formation formation e
[mm²] [Ohm/km]
[Ohm/km] [Ohm/km] [Ohm/km] [A] [pF/m]
25 0.727 1.5 0.9271 0.2413 139 164.0
35 0.524 1.5 0.6683 0.2327 165 180.0
50 0.387 1.5 0.4937 0.2249 194 197.0
70 0.268 1.5 0.3421 0.2158 235 222.0
120 0.153 1.5 0.1958 0.2022 311 273.0
240 0.0754 1.5 0.0976 0.1898 436 353.0

PRODUCT LIST
Nexans Ref. Country Name Conductor cross- Conductor Diameter over
Ref. section diameter insulation
[mm²] [mm] [mm]
N2XSY 8,7/15 kV 70
P00001396-3 - 70 9.5 19.8
mm2
N2XSY 8,7/15 kV 240
P00001391-3 - 240 18.0 28.3
mm2
N2XSY 8,7/15 kV 120
P00001390-3 - 120 12.8 23.1
mm2
N2XSY 8,7/15 kV 25
P00001392-5 - 25 5.8 16.1
mm2
N2XSY 8,7/15 kV 35
P00001394-4 - 35 6.8 17.1
mm2
N2XSY 8,7/15 kV 50
P00001395-3 - 50 7.9 18.2
mm2
= Make to order, = In stock,

Lead free Rated Voltage Uo/U Cable flexibility U.V resistance Flame retardant Oil resistance Maximum operating
Yes (Um) Class 2 IEC 60228 UL 2556 - Sunlight IEC 60332-1-2; FT1 ICEA S-93-639 temperature
8.7/15 kV Resistance 90 °C

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 6/9/23 www.nexans.pe Page 4 / 5