Kode Error
Kode Error
e
The Lock Drops off
02 in Operation The lock is missing in operation although the safety circuit is there.
(Emergency Stop)
Both Up and Down Limit switches activated at the same time while
The Up Limit Switch the car is NOT on the top floor at all during normal service.
03
Drops off
The Up Limit switch drops off during a travel upward.
Both Up and Down Limit switches activated at the same time while
The Down Limit the car is NOT on the lowest floor at all during normal service.
04
Switch Drops off
The Down Limit switch drops off during a travel downward.
The door fails to open fully in 15 seconds, during which the door-
opening signal has kept coming (exclusive of lack of door-lock
signals), the error is recorded if this is the case for three times
Failure in Opening continually.
05
the Door Lock
The landing door lock is bridged when the lift is in the door zone
with door-lock signals and door-open limit signal (for 1.5 s).
Interference in communication.
The resistor jumper is NOT yet connected on the terminals.
An inverter error appears at input Port X11 while the master control
09 Inverter Failure PCB is at work properly for 10 seconds, which will be recorded
error.
Positioning Errors of Check when power on or after the self-learning travel: the
10 Deceleration deceleration switch for single-floor up is positioned higher than 3/5
Switches 1 for of the rise of the top floor.
Check when power on or after the self-learning travel: the
deceleration switch for single-floor up is positioned lower than the
shortest decelerating distance.
Check when the lift is stopped: the deceleration switch for double-
floor up is positioned 150 mm lower than the one for double-floor
up positioned for self-learning.
Check when the lift is stopped: the deceleration switch for double-
floor up is positioned 200 mm higher than the one for double-floor
up positioned for self-learning and it fails to activate.
Only one-step deceleration switches are installed but set as two-
step deceleration switches (See F182).
Check when power on or after the self-learning travel: the
deceleration switch for double-floor down is positioned lower than
3/5 of the rise of the floor, in which it is located.
Check in lift operation: the deceleration switch for double-floor
down is positioned 150 mm higher than the one for double-floor up
positioned for self-learning.
Check in lift operation: the deceleration switch for double-floor
Positioning Errors of
down is positioned 250 mm lower than the one for double-floor
Deceleration
13 down positioned for self-learning.
Switches TWO for
Check when the lift is stopped: the deceleration switch for double-
Going-down
floor down is positioned 150 mm higher than the one for double-
floor down positioned for self-learning.
Check when the lift is stopped: the deceleration switch for double-
floor down is positioned 200 mm lower than the one for double-
floor down positioned for self-learning and it fails to activate.
Only one-step deceleration switches are installed but set as two-
step deceleration switches (See F182).
Check when power on or after the self-learning travel: the
deceleration switch for triple-floor up is positioned higher than 3/5
of the rise of the floor, in which it is located.
Check in lift operation: the deceleration switch for triple-floor up is
positioned 250 mm lower than the one for triple-floor up positioned
for self-learning.
Check in lift operation: the deceleration switch for triple-floor up is
Positioning Errors of positioned 300 mm higher than the one for triple-floor up
Deceleration positioned for self-learning.
14 Check when the lift is stopped: the deceleration switch for triple-
Switches THREE for
Going-up floor up is positioned 250 mm lower than the one for triple-floor up
positioned for self-learning.
Check when the lift is stopped: the deceleration switch for triple-
floor down is positioned 250 mm lower than the one for triple-floor
down positioned for self-learning and it fails to activate.
Protection against The leveling switch fails to function in travel (excluding inspection
20
Slippage service) beyond the delay set by F62.
If the value of feedback goes under the permitted speed for 0.5 s,
Error 24 is recorded.
If the reference speed is under 1.0 m/s, the permitted speed =
24 Under-speeding
Reference Speed - 0.25m/s.
If the reference speed is over 1.0 m/s, the permitted speed = 0.5 x
Reference Speed.
The up-leveling switch fails to work after the lift slows down ready
for stop.
Door-lock Contact The signal of door-opening position limit works and the door-lock
37
Stuck-up signal is detected.