You are on page 1of 2
SAFARI FACILITIES MANAGEMENT Ba ae SAFARI (flaws nagemene gait Date | 18/10/2022 ae KFCA_SAFARI_SA_TR #032 Discipline: Civil Telecom Electrical Mechanical 'Safety/General Formation Of Moisture Inside the Main Distribution Panel 1711012022 10:50 AM ‘SA-06 Civil Defense Building > TWAS NOTED OURING OUR WEEKLY PREVENTIVE MAINTENANCE THAT THERE WAS & FORMATION OF MOISTURE INSIDE THE MAIN m5 DOOR BECAUSE OF THE HOT WEATER CONDITIONS. > _ DUE TO THE EXCESSIVE WATER INSIDE PANEL CAN RESULT INTO THE DAMAGE OF PANEL BODY IT IS OBSERVED THAT IN THE SA-06 CORRIDER OUTER SIDE OF THE PANEL VIHERE THE TENPERATURE IS COLD DUE TO AC AND INNER SIDE IS HOT. DUE TO THIS THERE IS A FORMATION OF MOISTURE INSIDE THE PANEL. TIS RECOMMENDED TO PROVIDE THE PROPER CIRCULATION OF THE AIR INSIDE THE PANEL SO AS TO AVOID ANY HEAT EXCHANGE AND THE FORMATION OF THE MOISTUREINSIDE THE PANEL. MOHAMMAD AARIZ CHRISTIAN BAIN ATEYAH AL, Name Name fr Name THAGAFT Tile ELECTRICAL | Title PRovect | Tite SR. PROJECT ENGINEER MANAGER MANAGER Signature Md. POF | Signature 10, Signature Date: page Date: 18/ipfab22 Date: 10/2022 __ Page 1 SS Rixe eeatsem sey Rose MSnogemene ait ‘ATTACHMENT SAFARI FACILITIES MANAGEMENT Page 2 sas