Professional Documents
Culture Documents
Seimens make
Generator Protection
Neumerical relay
7UM622--
Information List
No. Information Type of In- Comments
formation
1722 >BLOCK I> SP >BLOCK I>
1811 I> Fault L1 OUT O/C fault detection stage I> phase L1
1812 I> Fault L2 OUT O/C fault detection stage I> phase L2
1813 I> Fault L3 OUT O/C fault detection stage I> phase L3
1815 I> TRIP OUT O/C I> TRIP
1950 >Useal-inBLK SP >O/C prot. : BLOCK undervoltage seal-in
1965 I> OFF OUT O/C prot. stage I> is switched OFF
1966 I> BLOCKED OUT O/C prot. stage I> is BLOCKED
1967 I> ACTIVE OUT O/C prot. stage I> is ACTIVE
1970 U< seal in OUT O/C prot. undervoltage seal-in
2.0 Definite-Time Overcurrent Protection (I>>, ANSI 50, 51, 67) with
Direction Detection
The time-overcurrent protection is used as backup protection for the short-circuit protection of the
protected object. It also provides backup protection for downstream network components if faults
there are not discon- nected in time thus endangering the protected object.
Information List
No. Information Type of In- Comments
formation
1720 >BLOCK dir. SP >BLOCK direction I>> stage
1721 >BLOCK I>> SP >BLOCK I>>
1801 I>> Fault L1 OUT O/C fault detection stage I>> phase L1
1802 I>> Fault L2 OUT O/C fault detection stage I>> phase L2
1803 I>> Fault L3 OUT O/C fault detection stage I>> phase L3
1806 I>> forward OUT O/C I>> direction forward
1807 I>> backward OUT O/C I>> direction backward
1808 I>> picked up OUT O/C prot. I>> picked up
1809 I>> TRIP OUT O/C I>> TRIP
1955 I>> OFF OUT O/C prot. stage I>> is switched OFF
1956 I>> BLOCKED OUT O/C prot. stage I>> is BLOCKED
1957 I>> ACTIVE OUT O/C prot. stage I>> is ACTIVE
3.0 Thermal Overload Protection (ANSI 49)
The thermal overload protection prevents thermal overloading of the stator windings of the machine
being pro- tected.
The unbalanced load protection detects asymmetrical loads of three-phase induction machines. Unbalanced loads create
a counter-rotating field which acts on the rotor at double frequency. Eddy currents are induced on the rotor surface,
leading to local overheating at the transition between the slot wedges and the winding bundles. Another effect of
unbalanced loads is overheating of the damper winding. In addition, this protection function may be used to detect
interruptions, faults, and polarity problems with current transformers. It is also useful for detecting 1-pole and 2-pole
faults with magnitudes lower than the load currents.
Information List:
Short circuit between the phases of the stator windings causes normally very large fault currents. The short
Circuit gives risk of damages on insulation, windings and stator iron core. The large short circuit currents
Cause large forces, which can cause damage even to other components in the power plant, such as turbine
and generator turbine shaft.
To limit the damage due to stator winding short circuits, the fault clearance must be as fast as possible (instantaneous). If
the generator block is connected to the power system close to other generating blocks, the fast fault clearance is essential
to maintain the transient stability of the non-faulted generators.
Normally, the short circuit fault current is very large, that is, significantly larger than the generator rated current. There is
a risk that a short circuit can occur between phases close to the neutral point of the generator, thus causing a relatively
small fault current. The fault current can also be limited due to low excitation of the generator. Therefore, it is desired that
the detection of generator phase-to-phase short circuits shall be relatively sensitive, detecting small fault currents.
To combine fast fault clearance, as well as sensitivity and selectivity, the generator differential protection is normally the
best choice for phase-to-phase generator short circuits.
Logic Diagram of the Tripping Logic in Differential Protection
Information List
No. Information Type of In- formation Comments
5603 >Diff BLOCK SP >BLOCK differential protection
5615 Diff OFF OUT Differential protection is switched OFF
5616 Diff BLOCKED OUT Differential protection is BLOCKED
5617 Diff ACTIVE OUT Differential protection is ACTIVE
5620 Diff Adap.fact. OUT Diff: adverse Adaption factor CT
5631 Diff picked up OUT Differential protection picked up
5644 Diff 2.Harm L1 OUT Diff: Blocked by 2.Harmon. L1
5645 Diff 2.Harm L2 OUT Diff: Blocked by 2.Harmon. L2
5646 Diff 2.Harm L3 OUT Diff: Blocked by 2.Harmon. L3
5647 Diff n.Harm L1 OUT Diff: Blocked by n.Harmon. L1
5648 Diff n.Harm L2 OUT Diff: Blocked by n.Harmon. L2
5649 Diff n.Harm L3 OUT Diff: Blocked by n.Harmon. L3
5651 Diff Bl. exF.L1 OUT Diff. prot.: Blocked by ext. fault L1
5652 Diff Bl. exF.L2 OUT Diff. prot.: Blocked by ext. fault L2
5653 Diff Bl. exF.L3 OUT Diff. prot.: Blocked by ext. fault.L3
5657 DiffCrosBlk2HM OUT Diff: Crossblock by 2.Harmonic
5658 DiffCrosBlknHM OUT Diff: Crossblock by n.Harmonic
5660 DiffCrosBlk exF OUT Diff: Crossblock by ext. fault
5662 Block Iflt.L1 OUT Diff. prot.: Blocked by CT fault L1
5663 Block Iflt.L2 OUT Diff. prot.: Blocked by CT fault L2
5664 Block Iflt.L3 OUT Diff. prot.: Blocked by CT fault L3
5666 Diff in.char.L1 OUT Diff: Increase of char. phase L1
5667 Diff in.char.L2 OUT Diff: Increase of char. phase L2
5668 Diff in.char.L3 OUT Diff: Increase of char. phase L3
5671 Diff TRIP OUT Differential protection TRIP
5672 Diff TRIP L1 OUT Differential protection: TRIP L1
5673 Diff TRIP L2 OUT Differential protection: TRIP L2
5674 Diff TRIP L3 OUT Differential protection: TRIP L3
5681 Diff> L1 OUT Diff. prot.: IDIFF> L1 (without Tdelay)
5682 Diff> L2 OUT Diff. prot.: IDIFF> L2 (without Tdelay)
5683 Diff> L3 OUT Diff. prot.: IDIFF> L3 (without Tdelay)
5684 Diff>> L1 OUT Diff. prot: IDIFF>> L1 (without Tdelay)
5685 Diff>> L2 OUT Diff. prot: IDIFF>> L2 (without Tdelay)
5686 Diff>> L3 OUT Diff. prot: IDIFF>> L3 (without Tdelay)
5691 Diff> TRIP OUT Differential prot.: TRIP by IDIFF>
5692 Diff>> TRIP OUT Differential prot.: TRIP by IDIFF>>
5701 Diff L1: VI Diff. current in phase L1 at trip
5702 Diff L2: VI Diff. current in phase L2 at trip
5703 Diff L3: VI Diff. current in phase L3 at trip
5704 Res L1: VI Restr. current in phase L1 at trip
5705 Res L2: VI Restr. current in phase L2 at trip
5706 Res L3: VI Restr. current in phase L3 at trip
5713 Diff CT-S1: VI Diff. prot: Adaptation factor CT side 1
5714 Diff CT-S2: VI Diff. prot: Adaptation factor CT side 2
5742 Diff DC L1 OUT Diff: DC L1
5743 Diff DC L2 OUT Diff: DC L2
5744 Diff DC L3 OUT Diff: DC L3
5745 Diff DC InCha OUT Diff: Increase of char. phase (DC)
Information List
14
8.0 Forward Active Power Supervision (ANSI 32F)
The machine protection includes an active power supervision which monitors whether the active
power falls below one settable value as well as whether a separate second settable value is exceeded.
Each of these functions can initiate different control functions.
When, for example, with generators operating in parallel, the active power output of one machine
becomes so small that other generators could take over this power, then it is often appropriate to
shut down the lightly loaded machine. The criterion in this case is that the "forwards" power
supplied into the network falls below a certain value.
Information List
Machine impedance protection is used as a selective time graded protection to provide the shortest
possible tripping times for short-circuits in the synchronous machine, on the terminal leads as well
as in the unit trans- former. It thus also provides backup protection functions to the main protection
of a power plant or protection equipment connected in series like generator, transformer differential
and system protection devices.
General
Dynamic occurrences such as sudden load changes, short circuits, automatic reclosure or switching
operations within the power system may cause power swings. Therefore impedance protection is
complemented by a power swing blocking function to avoid spurious tripping.
Power swings are three-phase symmetrical occurrences. The first prerequisite is therefore effective
symmetry of the three phase currents, which is verified by evaluation of the negative sequence
current. This means that asymmetrical (all single-phase and two-phase) short circuits cannot cause
the power swing blocking to pick up. Even if a power swing has been detected, the asymmetrical
short-circuits following it quickly deactivate the power swing blocking and make tripping by
impedance protection possible. Since a power swing happens much more slowly than a short-circuit,
the rate of change of the impedance is a reliable criterion for its identifi- cation. Because of its
symmetrical nature, the positive sequence impedance obtained from the positive se- quence
components of the currents and voltages is evaluated.
Figure 2-64 Logic Diagram for the Power Swing Blocking of the Impedance
Protection Z(Tent) First value inside the power swing polygon (at the
moment of Tent) Z(Tent-t) Last value outside the power swing polygon
P/SPOL Power swing polygon
TPOL Trip polygon
Z/t Rate of change of the impedance phasor
Information List
Depending on power network conditions and feeding generators, dynamic occurrences such as load jumps, short-
circuits not disconnected quickly enough, auto-reclosure or switching actions, may cause system swings. Such power
swings endanger power network stability. Stability problems often result from active power swings which can lead to
pole-slipping and generator overloading.
The undervoltage protection function detects voltage dips on electrical machines and prevents inadmissible operating
states and a possible loss of stability. Two-pole short circuits or ground faults cause a dip in asymmetrical voltages.
Compared to three single-phase measuring systems, the detection of the positive phase sequence system is not influenced
by these procedures and is particularly advantageous for assessing stability problems.
Information List
Overvoltage protection serves to protect the electrical machine and connected electrical plant
components from the effects of inadmissible voltage increases. Overvoltages can be caused by
incorrect manual operation of the excitation system, faulty operation of the automatic voltage
regulator, (full) load shedding of a generator, separation of the generator from the system or during
island operation.
Information List
The frequency protection function detects abnormally high and low frequencies in the generator. If the frequen- cy lies
outside the permissible range, appropriate switching actions are initiated, e.g. separating the generator from the
system.
A decrease in system frequency occurs when the system experiences an increase in real power demand, or when a
malfunction occurs with a generator governor or automatic generation control (AGC) system. The fre- quency protection
function is also used for generators which (for a certain time) operator to an island network. This is due to the fact that
the reverse power protection cannot operate in case of drive power failure. The gen- erator can be disconnected from the
power system by means of the frequency decrease protection.
An increase in system frequency occurs e.g. when large loads (island network) are removed from the system, or on
frequency control malfunction. This entails risk of self-excitation for generators feeding long lines under no-load
conditions.
Due to the use of filter functions, the frequency evaluation is free from harmonic influences and very accurate.
Information List
Overexcitation protection is used to detect inadmissibly high induction in generators and transformers, espe- cially in
power station unit transformers. The protection must intervene when the limit value for the protected object (e.g. unit
transformer) is exceeded. The transformer is endangered, for example, if the power station block is disconnected from the
system from full-load, and if the voltage regulator either does not operate or does not operate sufficiently fast to control
the associated voltage rise. Similarly a decrease in frequency (speed), e.g. in island systems, can lead to an inadmissible
increase in induction.
An increase in induction above the rated value quickly saturates the iron core and causes large eddy current losses.
Information List
The stator earth fault protection detects earth faults in the stator windings of three-phase machines. The machine can be
operated in busbar connection (directly connected to the network) or in unit connection (via unit transformer). The
criterion for the occurrence of an earth fault is mainly the emergence of a displacement voltage, or additionally with
busbar connection, of an earth current. This principle makes possible a protected zone of 90 % to 95 % of the stator
winding.
Information List
The 100 % stator earth fault protection detects earth faults in the stator windings of generators which are con- nected with
the network via a unit transformer. This protection function, which works with a 20 Hz injected volt- age, is independent of
the network frequency displacement voltage appearing in earth faults, and detects earth faults in all windings including the
machine starpoint. The measuring principle used is not influenced at all by the generator operating mode and allows
measurements even with the generator at standstill. The two mea- suring principles – measurement of the displacement
voltage and evaluation of the measured quantities at an injected 20 Hz voltage – allow to implement reliable protection
concepts that complement one another.
if an earth fault in the generator starpoint or close to the starpoint is not detected, the generator is operated as "earthed". A
subsequent fault (e.g. a second earth fault) causes a single-pole short-circuit that may have an extremely high fault current
because the generator zero impedance is very small.
The 100 % stator earth fault protection is for this reason a basic function for large generators.
Logic Diagram of the 100 % Stator Earth Fault Protection
Information List
Information List
The rotor earth fault protection detects high and low resistance earth faults in the excitation circuit of
synchro- nous generators. An earth fault in the excitation winding itself causes no direct damage. If
however a second earth fault occurs, this results in a winding short-circuit in the excitation circuit. The
resulting magnetic imbal- ances can cause extreme mechanical forces which may destroy the machine.
The following protection function differs from the function described in Section 2.34 in that it is far
more sensitive; it is used for large generators.
Information List
The inadvertent energization protection has the task to limit damage caused by the accidental energization of the
stationary or already started, but not yet synchronized generator by quickly actuating the generator circuit
breaker. A connection to a stationary machine is equivalent to connecting to a low-ohmic resistor. Due to the
nominal voltage impressed by the power system, the generator starts up with a high slip as an asynchronous
machine. Thereby inadmissibly high currents are induced in the rotor which could destroy it.