Professional Documents
Culture Documents
BY DZEVAD MUFTIC,
SANJAY NARAIN AND
RUKESH RAMNARAIN
@Eskom
GROUND WIRE OPTIMISATION
SYNOPSIS
This chapter explains the functions of the ground wire, positioning of the ground wire/s
on structures based on the electrogeometric model, selection of the ground wire,
materials that are commonly used and the latest technology using optical fibres within
ground wires.
Two examples are provided in this chapter, one is on effective shielding and the other
on selection of the ground wires for a typical 400 kV line. For clarification purposes, the
name ground wire will refer to earth wire, sky wire, static wire or shield wire.
16.1 INTRODUCTION
Initially the role of the ground wires was for protection against direct strikes of lightning
to the phase conductors. Being grounded , that is, connected to the earth at the supporting
structures and substations, it also became a substantial part of the earthing system and
thus important in providing a return path for short-circuit currents.
The position of the ground wires relative to the phase conductors also affects line
unbalance and is the reason for the use of segmented ground wires by some utilities.
(Eskom does not use segmented ground wires) . Induction in the ground wires is a source
of energy loss, but also suggests a role as a possible auxiliary power supply. The auxiliary
power supply can be obtained by having the ground wire as an active part (source), or a
passive part (as a support for a distribution line) . These aspects are, however, not dealt
with in this chapter.
The fact that the ground wire takes part of the return short-circuit current is used
for another role, that is, reduction of interference, for example, induction in adjacent
installations such as telecommunication lines and pipelines (see Chapter 14) .
Finally, ground wires are used more and more for telecommunications, either as Optical
Fibre Ground Wire (OPGW), or as a support messenger cable for insulated optical fibre
cable (ADLash or similar types).
For structure heights less than 100 m, most lightning flashes to the line are negative
downward flashes. That is, the cloud is negatively charged, with the leader progressing
downwards to the structure. The traditional role of ground wires was the protection
of the phase conductors from direct lightning strikes. The ground wire is intended to
intercept the lightning strike before it reaches the phase conductor, and conduct it to
ground thereby preventing flashovers on the phase conductors. For this role, the correct
placement of the ground wires is important to ensure proper shielding of the phase
conductors. The placement of ground wires will be covered in the electrogeometric
model section. In the case of ineffective shielding, the strike may terminate on the phase
CHAPTER 16
GROUND WIRE OPTIMISATION
When a direct strike occurs to the ground wire, a voltage develops on the ground wire
which depends on:
If the earthing impedance and lightning current magnitudes are high, this may lead to high
voltages on the ground wire, and backflashover from the tower to the phase conductors
may occur.
As an additional but critical role, the ground wire also reduces the amplitude of induced
surges on the phase conductors due to lightning strikes in the vicinity of the line [1,2].
s =Alb ( 16.1)
where:
S = 10.1° = ~-S
65
and r8 (16.2)
Sis the strike distance to the ground wire or phase conductor and\' is the strike distance
to earth. ~. which varies between 0.6 and 0.9, accounts for the horizontal ground plane
having a different attractive effect from a conductor suspended above the plane. IEEE has
suggested a dependency of~ on the tower height, 'h ', as per equation (16.3).
The concept of the electrogeometric model is illustrated in Figure 16.1, which shows
one side of a line profile.
CH PTER 16
GROUND WIRE OPTIMISATION
u
Ground
wire
Phase
conductor
In Figure 16.1, arcs RS, ST and line TU represent the limits of the strike distances to the
ground wire, phase conductor and earth respectively. Flash A terminating on arc RS, will
jump only to the ground wire because it is within the strike distance of the ground wire.
Flash C will jump to earth anywhere on line TU. Flash B intersects arc ST. Since this is
within the strike distance of the phase conductor, the flash will terminate on the phase
conductor. This model assumes only vertical flashes , and hence 'x' is the uncovered width
due to arc ST. Other models consider the angular nature of flashes, which causes 'x' to
change. Further, the width should also be adjusted for undulating terrain, nearby trees
or tall objects, and locations along the span (due to sag) .
Note that hg and h<l> refer to the mean heights of th<:_ground wire and phase conductor
respectively. The mean height of a conductor ( h) is expressed by the following
equation:
(16.4)
where h.,, is the conductor attachment height at the tower and hmid is the conductor
midspan clearance to ground. Note that hatt - hmid is the conductor sag.
To determine the uncovered width for a particular stroke current, calculate S and rg as
per equations (16.2) and (16.3). Then, if ~S > h~:
j CHAPTER 16
GROUND WIRE OPTIMISATION
where
. _, 1--'flS -h <i
0 =Sin - - - ( 16.6)
S
_, F
O)= cos - ( 16. 7)
2S
( 16.8)
X$ - Xg is the horizontal distance between the phase and ground wire conductors.
Since the strike distance is logarithmically proportional to the lightning current magnitude,
the strike distance increases as the magnitude of the current increases. It is understandable
why low stroke currents can give rise to shielding failures. This is because the strike
distances become smaller, with the probability of an uncovered width being greater. As
the strike distance gets bigger, a point will be reached where arc ST becomes zero as
depicted in Figure 16.2.
hg
CHAPTER 16
GROUND WIRE OPTIMISATION
At this value of strike distance, there is effective shielding against any direct strikes to the
phase conductor. The angle a at this point is the effective shielding angle. The magnitude
of current for which this occurs will be denoted Imax·
To attain effective shielding, the co-ordinates of the phase conductor will be fixed and
the ground wire will be moved horizontally until the unprotected width is reduced to
zero as in Figure 16.2. If the X co-ordinate of the phase conductor (X~) is taken as zero,
then the X co-ordinate of the ground wire (Xg) with respect to it is:
( 16.10)
(16.11)
s ~ h, [ + ✓~ + AC l (16.12)
where:
(16.13)
(16.14)
2
B = ~(m + 1) (16.15)
C = (m 2 + 1) (16.16)
( 16.17)
CHAPTER 16
GROUND WIRE OPTIMISATION
As previously explained, !max is the value of stroke current magnitude, above which no
strokes terminate on the phase conductor and effective shielding exists. Below Imax' an
uncovered width exists for which shielding failure is possible.
In terms of the statistical distribution of lightning current magnitudes, a line may encounter
currents as low as 2-3 kA. This low current will be referred to as !min' Shielding failure
can occur for currents between I min. and I max .
The shielding failure rate (SFR) describes the rate of failure of ground wires to protect
the phase conductors i.e., the rate at which the phase conductors are directly struck by
lightning. For a specific value of current, I (between !min and Imax), the number of strokes
to the phase conductors depend on the area formed by the uncovered width (X), the
length of line (L), and the ground flash density (N ). Since there will be two uncovered
widths, one on each side of the ground wire, the ~FR is given by:
( 16.19)
The probability of occurrence of this current is f(I)dI, so that the incremental failure
rate d(SFR) is:
!max
Not all shielding failures will result in flashovers. The insulator string has a withstand
voltage level that must be exceeded for a flashover to take place. The magnitude of
stroke current required to produce a flashover, referred to as the critical current (IJ
can be determined as follows:
( 16.22)
Where Zc is the surge impedance of the conductor and (Lr-) is the negative polarity,
standard lightning impulse flashover voltage calculated as:
Note that 605 (kV/m) is the lightning surge, negative polarity breakdown gradient [1].
CHAPTER 16
GROUND WIRE OPTIMISATION
Ultra low
probability Shielding failure + Shielding failure + No shielding
of stroke No flashovers Flash overs failure
current
-
~
0 ! min I
C !max
(2-3 kA)
I SFR
SFFOR
If Ic is within the range !min - !max' then shielding failures will result in flashovers of the
phase conductor especially for the current range Ic :S: I :S: ! max · This flashover rate due
to shielding failures (SFFOR) is known as the shielding failure flashover rate and can be
determined as:
!m ax
Clearly, if Ic is set to ! max' then SFFOR is zero and 'perfect shielding' can be achieved.
Numerical integration is required to solve for SFFOR. J.G. Anderson suggested a simplified
approach [2]. He noticed that the average value of the uncovered width , X, over the
interval from Ic to !max is half the value at I = Ic. Letting X at Ic be Xe, then:
X !m ax
SFFOR = 2N L-c J f(I)dI
g 2
le
= NgLXc[F(Imax ) - F(Ic)]
where:
Approximate equations for Q(I), based on the Cigre cumulative distribution are [4]:
CHAPTER 16
GROUND WIRE OPTIMISATION
z2
--
3 to 20 Q = 1-0.31 e 1.6
20 to 60 Q = 0.50 - 0.35Z
z2
- -1.7
60 to 200 Q = 0.278 e
where:
z = ln(I/M 1 ) (16.27)
~I
Mr and ~r are the median and log standard deviation for the Cigre distribution given in
Table 16.2:
3 to 20 61.1 1.33
> 20 33.3 0.605
Determine the SFFOR for a 400 kV line whose dimensions are shown in Figure 16.4.
Also, calculate the perfect shielding angle.
Assume:
CHAPTER 16
GROUND WIRE OPTIMISATION
8.0 m
5.Sm -i
w
N
C>
3
N
--.J
C>
3
16.3.3.1 Solution:
1. Using '<1> ' and 'g' to denote phase conductor and ground wire respectively, the average
conductor heights are (from Figure 16.4):
- 2
h~ = 27 - (18) = 15m
3
- 2
h =32 - -(15)=22m
g 3
CHA Tr.: 16
GROUND WIRE OPTIMISATION
3. From Equations (16.12) to (16.17), the maximum strike distance for effective shielding
is calculated as follows:
8 55
m= - · = 0.36
22-15
C = 0.36 2 + 1 = 1.13
B = 0.77x1.13 = 0.87
ho= 15 + 22 = 18.5
2
I = [42.89]o.6s = 9 .40 kA
max 10
I = 2x605x2.5 = 8 .4 0 kA
C 360
6. Note that, since Ic < Imax' shielding failure flashovers will occur.
CHAPTER 16
GROUND WIRE OPTIMISATION
Since rg > h<l>' the uncovered width (X) can be calculated according to equations (16.5)
to (16.8):
a =tan -18-5
- - -.5= 19650
.
22-15
8 55
F= - · = 7.43 m
sin 19.65
7 3
CD= cos- 1 .4 = 84.65°
2 X 39.89
At I,,
<-1;◄: >2
2
Z c = ln( 9 .40 / 61 · 1) = -1.492 , Oc = 1- O.31e = 0.9228
1.33
At !max'
(- 1.408)2
(9 0 / 61 1)
Z max = In .4 . = -1.408 , Q max = 1-0.31e-- 1·6- = 0.9102
1.33
SFFOR = 5x 1OO x O.55 x O.OO1 x (O.9228 - 0.9102) = 0.004/ 100 km/ years, which is
negligible.
8. To find the perfect shielding angle, let !max = I,. Note that 'S' at l e = 39.89 m. From
Equations (16.10) and (16.11):
Reducing the shielding angle improves shielding. The shielding angle can even go negative,
i.e., the ground wires are positioned outside the phase conductors. Negative shielding
angle improves shielding further. Thus , designs such as the cross-rope towers (Figures
20.6 and 20.7) give superior shield ing and lightning protection.
CHAPTER 16
GROUND WIRE OPTIMISATION
Shielding of the central phase is not governed by the shielding angle, although a shielding
angle of 60° was used in the past. Shielding of the central phase is governed by the geometry
(position of the central phase and the ground wires) and the minimum striking distance
derived from this geometry. The shielding of the central phase is very effective, resulting
in a small probability of faults due to shielding failure.
Sometimes, an additional ground wire can be positioned below the phase conductors,
especially with the vertical configuration of phases. It is known as an under-built ground
wire. This improves the coupling of the lower phases co the ground wires, thereby
reducing the development of overvoltages on the lower phases. This greatly helps to
reduce the backflashover rate.
Ground wires play the role of preventing direct lightning strikes to the phase conductors.
When strikes terminate on the ground wire or tower top, the lightning current must
effectively be conducted to ground via the tower footing resistance. A high tower footing
resistance impedes the flow of this current, resulting in a build-up of the tower-top voltages
and subsequent backflashover from the structure to the phase conductors. On some
lines, a low footing resistance may not be achievable. Also, some lines are unshielded at
distribution and sub-transmission voltages, with a significant number of strikes terminating
on the phase conductor and tower tops. With double-circuit towers, backflashovers
frequently affect both circuits, resulting in a double-circuit outage. For these situations,
power line surge arresters can be used to reduce lightning outages. Many line surge
arresters are in service today, and substantial experience has been accumulated.
There are many software packages available on the market to perform surge arrester
placement and the calculation of shielding effectiveness of ground wires. Eskom currently
uses Sigma SLP [SJ and T-Flash [6] in this regard.
The material for ground wire is dictated by its purpose on the specific line. If only lightning
protection is required, then it is not necessary to have much conductive material. Although
currents can be high, they last for a very short time. This is why steel wire is often used
as ground wire. Reduction of the current through the ground, or corrosion protection,
can require the use of ACSR. or similar stranding for ground wire [7].
The size of ground wire is dictated mostly by short-circuit current capabilities (thermal
capabilities in short-circuit conditions) [8,9]. A lightning strike directly to the ground wire
will develop the highest temperature at the point of strike. This led to the conclusion that
the minimum cross sectional area of any conductor in a lightning protection installation
has to be about 35 mm 2 (I2t considerations). The minimum diameter of individual strands
of a stranded conductor should be at least 2.5 mm.
CHAPTER 16
GROUND WIRE OPTIMISATION
- Steel wire 7/3.51 mm for lower voltages and lower short-circuit currents.
- Steel wire 19/2.70 mm for higher voltages and higher short-circuit currents.
The maximum current-carrying capacity of the ground wire can be calculated ( 16.28)
as [10]:
I= KA (16.28)
K
where K is given by:
( 16.29)
where:
For 19/2.7 steel ground wire, use of equation (16.28) yields the following results:
ec (·q 400*
0b (oC) 40
C Q/kg ·q 480
p (kg/m 3) 7850
CHAPTER 1
GROUNDWIRE OPTIMISATION
9.1 0.8
8.1 1.0
For a single-phase-to-ground fault, selection of the fault duration for design purposes
must be based on the present protection scheme. Eskom's past practice was to use one
second, which included backup protection fault clearing times. Advances in protection
technology have resulted in shorter fault clearance times in the range 0.5 to 0.8 s (275
kV and above) .
Advances in computing time and software applications have resulted in complex modelling
being possible. One such software application that is used widely is CDEGS (Current
Distribution Electromagnetic Interference Grounding and Soil Structure Analysis)[11]. A
typical ground wire selection example will be illustrated using an actual case. The overhead
power line that will be considered is a typical 400 kV line on the Eskom network. As
mentioned earlier, the main function of any ground wire is the control of fault conditions,
which presumes a short-circuit at any point of the line or substation busbar. Hence the
ground wire or optical ground wire must be chosen so that when it carries fault current
it retains its mechanical and electrical properties without degradation.
16.4.3.1 Analysis
CDEGS models the line as a full three-phase line with real spans (impedances and mutual
impedances along the line) as shown in Figure 16.5.
Source A Source B
Far ground
CHAPTER 16
GROUND WIRE OPTIMISATION
To model this line correctly, the fault levels at each busbar (say Substation A and
Substation B) must be determined. Use is made of a power system simulation package-
PSS/E: acronym for Power System Simulation for Engineers, from PT! in the USA, to
calculate the fault levels.
The overhead power line parameters are calculated using CDEGS, based on the tower,
conductor and ground wire/s. The tower to be used for this simulation will be the cross-
rope suspension tower with 3 X Tern ACSR and two 1912.7mm ground wires. Due to
the magnitude of the fault level (33 kA), 7/3.51 ground wire could not be considered.
29 m
t _ •j
l ....
1
l._,___..o
·1 \ \
I \
8.2 m
\
29 m
I
I
I \ 18.Bm 20.25 m
I •
\
\
I \
I
\
I
/
I / I 1 / I l I I / I
I' I I
CHAPTER 16
GROUND WIRE OPTIMISATION
Figure 16.7: Fault current distribution along the line with the
application of a single-phase-to-ground fault.
The first step in this simulation is to verify the model based on the fault levels from PSS/E.
The line length assumed was 265 km, with 350 m spans, 50 m slack spans and a nominal
tower footing resistance of 40 ohms per tower.
16.4.3.2 Results
The results obtained are typical of the fault current distribution along the line, with the
highest fault current being at busbar A followed by a general decrease as the fault moves
away from A, reaching a minimum and increasing near busbar B. These results indicate
that the critical spans occur near the substations at the terminal towers and for this line
the Substation A end is the critical end in terms of ground wire rating.
8.1 1.0
For this line the fault duration for design purposes was selected as 1 second, which
included backup protection clearing time.
To determine the maximum fault current through the ground wires a fault was simulated
near the Substation A end in the first few spans with the following results:
CHAPTER 16
GROUND WIRE OPTIMISATION
Tower 3 13.52
Tower 4 12.84
From the results in Table 16.8 it can be seen that the fault current in the ground wires
exceeds the rated value given in Table 16.7.
To overcome th is limitation, there are a few options which are available to the designer,
these include:
• The use of larger overhead ground wires, which will result in higher short-circuit
ratings. The tower strength has to be checked for this option.
• The diversion of part of the fault current along a third ground wire.
• As above but using a buried counterpoise conductor instead of the third ground wire
to carry part of the fault current.
• Intensive earthing on towers close to substations. This is not a solution in itself but
must be used in combination with the above methods.
The buried counterpoise was selected as the most effective method for this line.
The counterpoise (19/2.7) was modelled from Substation A to the firrh tower. A phase-to-
ground fault was inserted adjacent co the counterpoise and the fault current distribution
in the ground wires was calculated. This process was implemented by gradually increasing
the length of the counterpoise until the fault levels in the ground wires were within the
ratings as shown in Table 16.9.
!CHAPTER 16
GROUND WIRE OPTIMISATION
The conclusion from this is that 19/2.7 or equivalent counterpoise must be used from
Substation A to tower 25 in order to reduce the fault current in the ground wires to
levels which can be withstood.
Losses in the ground wire are the result of induced current. The induced current has a
component which flows following the direction of the current in the phase conductors and
another component in which current is circulated in the loop of the two ground wires.
These currents can be calculated from the general equations of line impedance:
( 16.30)
Solving gives the current Ig (or Ig,• Ig2) for the two ground wires. The losses can now
be calculated:
where:
OPGW is a composite cable in which optical fibres are incorporated into a metallic
ground wire at the manufacturing stage. The cable is designed to fulfill the dual function
of a ground wire, i.e., it provides an electrical path for lightning and fault currents, and
the optical fibres continue to operate to provide consistent and reliable transmission
(telecommunications) characteristics. More on OPGW is given in Chapter 27.
The ground wire is a vital component of the overhead line transmission system in areas
of high lightning activity. Not only must it protect phase conductors from direct lightning
strikes and provide a return path for fault current, but the increasing use of optical fibres
in the ground wire gives it a dual role in telecommunications as well.
Care must be taken when selecting OPGW, especially near power stations or substations
where there is a likelihood of high fault currents.
HAP 6
GROUND WIRE OPTIMISATION
16.8 REFERENCES
[1] Hileman AR., Insulation co-ordination for power systems, 1st ed., New York,
Marcel Dekker, Inc., 1999.
[2] Anderson J.G., Lightning performance of transmission lines, In: Laforest J.J. (ed) ,
Transmission Line Reference Book (345 kV and above), 2nd ed. revised, EPRI, Palo
Alto, Project UHV, 1987.
[4] Cigre, Guide to procedures for estimating the lightning performance of transmission
lines, WG 33-01 , October 1991.
[7] Dzubur I. and Timic Z., Steel OHGWs are unreliable in aggressive environments,
Transmission and Distribution International, September 1991, pp 18-20.
[9] Duncan J.W. and Johnson J., Guideline for the selection of overhead ground wire
for transmission lines based on a fault current criteria, Florida Power and Light
Company, Juno Beach, Florida, March 1990.
(10] IEC 60 865-1, Short circuit currents - calculation of effects: Part 1: Definitions and
calculation methods, October 1993.
CHAPTER 16